Tripp Lite PDUMH15NET, PDUMH20NET, PDUMH15HVNET, PDUMH20HVNET Owner's Manual

1
Owner’s Manual
PDUMH15NET/PDUMH20NET
Switched Rack PDU
• 120V, 60Hz AC Input and Output
PDUMH15HVNET/PDUMH20HVNET
Switched Rack PDU
• 208/230V, 50/60Hz AC Input and Output
Русский 25
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2016 Tripp Lite. All rights reserved.
16-11-165-93368A.indb 1 1/3/2017 5:01:26 PM
A
B
A
1-1
C
D
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation, and storage of this product. Failure to heed these instructions and warnings may affect the product warranty.
Important Safety Instructions
• The PDU provides convenient multiple outlets, but it DOES NOT provide surge or line noise protection for connected equipment.
• The PDU is designed for indoor use only in a controlled environment away from excess moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that eliminate the connection to ground.
• The power requirement for each piece of equipment connected to the PDU must not exceed the individual outlet’s load rating.
• The total power requirement for equipment connected to the PDU must not exceed the maximum load rating for the PDU.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable parts inside.
• Do not attempt to modify the PDU, including the input plugs and power cables.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Never attempt to install electrical equipment during a thunderstorm.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Installation
Mounting the PDU
The PDU supports five primary mounting configurations: 1U Rack, 0U Rack (Vertical), Wall, Under­Counter and Reduced-Depth.
Note: Regardless of configuration, the user must determine the fitness of hardware and procedures before mounting. The PDU and included hardware are designed for common rack and rack enclosure types and may not be appropriate for all applications. Exact mounting configurations may vary. Screws for attaching the mounting brackets and cord retention shelf to the PDU are included. Use only the screws supplied by the manufacturer, or their exact equivalent (#6-32, 3/16" flat head).
1-1 1U Rack Mounting: Use 3 screws A to
attach each of the 2 longer mounting brackets B to the PDU as shown. You can mount the PDU in a recessed position by attaching the mounting brackets so they extend beyond the front panel of the PDU. (If you plan to use the cord retention shelf, attach the mounting brackets in a recessed position.) Mount the PDU in the rack by inserting 4 user-supplied screws C through the mounting brackets D and into the mounting holes of the rack rails.
16-11-165-93368A.indb 2 1/3/2017 5:01:27 PM
1-2
A
B
C
D
1-3
A
B
C
D
A
B
1-4
C
D
1-6
A
B
1-5
C
D
A
B
3
1-2 0U Rack Mounting: Use 3 screws A to
attach each of the 2 shorter mounting brackets
B
to the PDU as shown. Mount the PDU vertically by inserting 2 or more user-supplied screws C through the mounting brackets D and into mounting points in the rack or rack enclosure.
1-3 Wall Mounting: Use 3 screws A to attach
each of the 2 shorter mounting brackets B to the PDU as shown. Mount the PDU to the wall by inserting 2 or more user-supplied screws C through the mounting brackets D and into secure mounting points.
1-4 Under-Counter Mounting: Use 3 screws
A
to attach each of the 2 shorter mounting brackets B to the PDU as shown. Mount the PDU under the counter by inserting 2 or more user-supplied screws C through the mounting brackets D and into secure mounting points.
1-5 Reduced-Depth Mounting: Use 3 screws
A
to attach each of the 2 shorter mounting brackets B to the PDU as shown. Mount the PDU to a stable surface with the outlets facing upward by inserting 2 or more user-supplied screws C through the mounting brackets D and into secure mounting points.
1-6 Cord Retention Shelf Attachment
(Optional): Use 2 screws A to attach the cord retention shelf B to the front panel of the PDU.
Installation continued
16-11-165-93368A.indb 3 1/3/2017 5:01:30 PM
2-1
88
PDUMH15HVNET
PDUMH15NET/PDUMH20NET
A
B
C
88
2-2
PDUMH20HVNET
B
B
A
A
C
C
A
2-3
4
Connecting the PDU
2-1 NEMA Adapter Connection (Optional -
PDUMH20HVNET Only): The PDUMH20HVNET includes a plug adapter that adds a NEMA L6-20P plug to the input power cord. Use this adapter only if you will be connecting the PDUMH20HVNET to a NEMA L6-20R outlet. Insert the IEC 60320 C19 connector A of the adapter into the IEC 60320 C20 connector B of the input power cord. Secure the connection with the retention bracket
C
by using the included bolts to fasten the two halves of the bracket around the connection as shown. Caution: To avoid the risk of electric
shock, ensure that the Neutral (L2) conductor has been identified before connecting the PDU.
2-2 Input Power Cord Connection (Select
Models with Unattached Power Cords Only): Insert the IEC 60320 C19 (PDUMH20HVNET) or IEC 60320 C13 (PDUMH15HVNET) connector A of the input power cord into the IEC 60320 C20 (PDUMH20HVNET) or IEC 60320 C14 (PDUMH15HVNET) inlet B of the PDU. Connect the other end of the input power cord C to a compatible source of AC power, such as a UPS system, PDU or utility outlet. The PDU should be provided with over-current protection: PDUMH20HVNET should be provided with a maximum 20A branch-rated over-current protection device; PDUMH15HVNET should be provided with a maximum 15A branch-rated over-current protection device.
Note: The AC power source should not share a circuit with a heavy electrical load (such as an air conditioner or refrigerator).
2-3 Connect Input Power Cord
(PDUMH15NET and PDUMH20NET):
Connect the input plug A to a compatible source of AC power, such as a UPS system, PDU or utility outlet. The PDU should be provided with over-current protection: PDUMH15NET with a maximum 15A branch-rated protection device. PDUMH20NET with a maximum 20A branch­rated protection device.
Installation continued
16-11-165-93368A.indb 4 1/3/2017 5:01:31 PM
15
2-4
A
B
C
D
15
2-5
PDUMH20NET
PDUMH15NET
PDUMH15HVNET/PDUMH20HVNET
B
B
D
D
C
C
5
Installation continued
2-4 Equipment Power Cord Connection:
Insert the IEC 60320 C14 connectors A of the equipment power cords into the IEC 60320 C13 output receptacles B of the PDU (PDUMH15HVNET and PDUMH20HVNET). Insert power cords into the NEMA 5-15R output receptacles B (PDUMH15NET) or NEMA 5-15/20R output receptacles B (PDUMH20NET). The LED C near each output receptacle illuminates when the receptacle is ready to distribute live AC power. The digital load meter D will display the total connected equipment load in amps.
2-5 Cord Retention (Optional): If you
attached the cord retention shelf in step
1-6
, tie the input power cord and each equipment power cord to the retention shelf. Attach each cord to the retention shelf by looping the cord and securing it to an attachment point with one of the included cable ties. Make sure that each cord can be unplugged from the PDU without removing the cable tie.
Networking the PDU
For network configuration instructions, please refer to the WEBCARDLX owner’s manual (PN 93358E) included with this product.
16-11-165-93368A.indb 5 1/3/2017 5:01:34 PM
A
B
A
B
6
Features
AC Input Power Inlet (Model PDUMH15HVNET): The IEC 60320 C14 inlet connects to the detachable AC Input Power Cord.
AC Input Power Inlet (Model PDUMH20HVNET): The IEC 60320 C20 inlet connects to the detachable AC Input Power Cord.
AC Input Power Cord (Model PDUMH15HVNET): The detachable cord has an IEC 60320 C13 connector A and an IEC 60320 C14 connector B.
AC Input Power Cord (Model PDUMH20HVNET): The detachable cord has an IEC 60320 C19 connector A and an IEC 60320 C20 connector B.
AC Input Power Cord (Model PDUMH15NET): The cord is permanently attached to the PDU and has a NEMA 5-15P plug.
AC Input Power Cord (Model PDUMH20NET): The cord is permanently attached to the PDU and has a NEMA L5-20P plug.
AC Input Adapter (Model PDUMH20HVNET): The adapter converts the AC input power cord to a NEMA L6-20P plug. The included retention bracket (not shown) secures the connection.
AC Input Adapter (Model PDUMH20NET): The adapter converts NEMA L5-20P input plugs to NEMA 5-20P input plugs.
16-11-165-93368A.indb 6 1/3/2017 5:01:35 PM
RESET
STATUS
CONFIG
7
NEMA 5-15R Output Receptacles (PDUMH15NET): During normal operation, the output receptacles distribute AC power to connected equipment. When an outlet is live, the associated LED illuminates.
NEMA 5-15/20R Output Receptacles (PDUMH20NET): During normal operation, the output receptacles distribute AC power to connected equipment. When an outlet is live, the associated LED illuminates.
IEC 60320 C13 Output Receptacles (PDUMH15HVNET & PDUMH20HVNET): During normal operation, the output
receptacles distribute AC power to connected equipment. When an outlet is live, the associated LED illuminates.
Digital Load Meter (Ammeter): The total electrical current drawn by connected equipment is displayed on the meter in amperes.
Cord Retention Shelf: When it is attached to the PDU, the cord retention shelf provides secure attachment points for the input cord and connected equipment cords. Use the included cable ties to secure the cords to the shelf.
Longer Mounting Brackets: Use these brackets to mount the PDU horizontally in a standard rack or rack enclosure. The mounting depth can be adjusted by attaching the brackets to different positions on the PDU.
Shorter Mounting Brackets: Use these brackets to mount the PDU in a 0U rack, wall or under-counter configuration.
Factory Port: The port is reserved for configuration by factory authorized personnel only. Do not connect anything to the port.
WEBCARDLX: Allows you to operate this PDU as a managed network device, accessible via SNMP network management platform, web browser, SSH or Telnet.
Features continued
16-11-165-93368A.indb 7 1/3/2017 5:01:36 PM
8
Warranty and Warranty Registration
LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 2 years from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609 USA. Seller will pay return shipping charges. Visit www.tripplite.com/support before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
FCC Notice, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use shielded cables and connectors with this equipment. Any changes or modifications to this equipment not expressly approved by Tripp Lite could void the user’s authority to operate this equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Technical Support
Website: www.tripplite.com/support
E-mail: techsupport@tripplite.com
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
16-11-165-93368A.indb 8 1/3/2017 5:01:37 PM
9
Manual del Propietario
PDUMH15NET / PDUMH20NET
PDU Controlable para Rack
• Entrada y Salida de CA 120V, 60Hz
PDUMH15HVNET / PDUMH20HVNET
PDU Controlable para Rack
• Entrada y Salida de CA 208V / 230V, 50/60Hz
Русский 25
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • www.tripplite.com/support
Copyright © 2016 Tripp Lite. Todos los derechos reservados.
16-11-165-93368A.indb 9 1/3/2017 5:01:37 PM
A
B
A
1-1
C
D
10
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante la instalación, operación y almacenamiento de este producto. La omisión en la observancia de estas instrucciones y advertencias puede afectar la garantía del producto.
Instrucciones de Seguridad Importantes
• El PDU proporciona múltiples tomacorrientes convenientes, pero NO proporciona protección contra sobretensiones o ruido en la línea para los equipos conectados.
• El PDU está diseñado solo para uso en interiores en un entorno controlado lejos de humedad excesiva, temperaturas extremas, contaminantes conductivos, polvo o luz del sol directa.
• No conecte el PDU a un toma corriente que no esté conectada a tierra o cables de extensión o adaptadores que eliminen la conexión a tierra.
• Los requerimientos de alimentación para cada dispositivo conectado al PDU no debe exceder la capacidad de carga de cada toma corriente individual.
• El requerimiento de energía total para el equipo conectado al PDU no debe exceder la capacidad de carga máxima del PDU.
• No perfore ni intente abrir ninguna parte del gabinete del PDU. No tiene partes a las que el usuario pueda dar servicio.
• No intente modificar el PDU, incluso las clavijas de entrada y los cables de alimentación.
• No intente usar el PDU si se daña cualquier parte.
• No intente instalar el PDU en una superficie inestable o no segura.
• Nunca intente instalar equipos eléctricos durante una tormenta eléctrica.
• No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda razonablemente hacer esperar que cause la falla del equipo de soporte de vida o afectar significativamente su seguridad o efectividad. No use este equipo en presencia de una mezcla inflamable de anestésicos con aire, oxígeno u óxido nitroso.
Instalación
Instalación del PDU
El PDU soporta cinco configuraciones primarias de instalación: Rack de 1U, Rack 0U (vertical), en la Pared, Bajo el Mostrador y Profundidad Reducida
Nota: Sin importar la configuración, antes de la instalación, el usuario debe determinar la adecuación de los accesorios y procedimientos. El PDU y los accesorios incluidos están diseñados para tipos comunes de racks y gabinetes y pueden no ser apropiados para todas las aplicaciones. Las configuraciones de instalación exactas pueden variar. Están incluidos los tornillos para fijar los soportes y la bandeja de retención de cable para instalación al PDU. Use solamente los tornillos suministrados por el fabricante o su equivalente exacto (#6-32, cabeza plana de 3/16”).
1-1 Instalación en Rack de 1U: Use 3 tornillos
A
para instalar cada uno de los 2 soportes grandes de instalación B al PDU como se muestra. Puede instalar el PDU en una posición empotrada adjuntando los soportes de instalación para que sobresalga de la parte frontal del PDU. (Si va a utilizar la repisa de retención de cable, conecte los soportes de instalación en una posición empotrada). Instale el PDU en el rack insertando 4 tornillos suministrados por el usuario C a través de los soportes de instalación
D
y en los orificios de instalación de los rieles del rack.