Tripp Lite PDUBHV10 User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model Number: PDUBHV10
Highlights
Single phase 10A 200-240V Hot-swap PDU
Enables live replacement of a standard UPS with zero downtime
2U horizontal rackmount installation
Compatible with any 200-240V UPS with a C14 input
Manual transfer switch controls PDU input power source
Pair of C14 compatible inputs connect to separate Utility and UPS inputs
8 Built-in C13 outlets
Description
Tripp Lite’s Hot-swap PDU systems enable live-replacement of standard UPS systems for maintenance with no interruption of connected server or networking loads. Dual input power cables support PDU connection to separate Utility and UPS power sources. Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS. Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS. Set the switch to Utility to momentarily power connected equipment from the Utility line cord and bypass the UPS while the UPS system is removed and replaced with a fresh one. Once the new UPS is up and running with all data and electrical connections restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS power to connected equipment.
Applications
Hot-swap PDUs are ideal to install along with standard UPS systems to ensure that connected networking equipment will see no power interruption
as the UPS is serviced, replaced or upgraded
Package Includes
Hot-swap PDU System
2U mounting brackets
Set of 2 C13-C14 interconnect cables
User manual with warranty information
Features
Tripp Lite Hot-swap PDU systems support live-replacement of standard UPS systems for maintenance with no interruption of connected
server or networking loads
PDUBHV10 is universally compatible with any Tripp Lite or other brand of 200-240V UPS rated up to 1500VA with a C14 input cable option
2U horizontal rackmount form factor compatible with 2 or 4 post racks
Supports space saving rear-post mounting in the same rack space as many Tripp Lite Rackmount UPS systems (select installations, see
manual)
Pair of detachable PDU input cables connect to separate Utility and UPS power sources (2 C13-C14 interconnect cables included - user
supplied alternate cabling supported)
8 C13 outlets support critical networking loads in both Utility and UPS operating modes
One additional C13 pass-through outlet supports UPS input power cord
Dual input power cables support PDU connection to separate Utility and UPS power sources
Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS
Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS
Set the switch to Utility to bypass the UPS and provide connected equipment with unfiltered power directly from the Utility line cord while the
UPS system is removed and replaced with a fresh one
Once the new UPS is up and running with all connections restored, set the switch back to the UPS setting to once again provide
fully-conditioned UPS power to connected equipment
Specifications
OVERVIEW
PDU Type Hot-Swap
OUTPUT
Output Watt Capacity (watts)
2300
Output Capacity Details 2.1kW (208V input), 2.2kW (220V input), 2.3kW (230V input), 2.4kW (240V input), 2.0kW (200V input); 10A
maximum
Frequency compatibility 50 / 60 Hz
Output nominal voltage 200-240V nominal, single phase
Outlet quantity / type 8 C13 outlets support critical connected loads; 1 designated pass-through C13 outlet supports C14 input plug
from UPS
Outlet Type IEC-C13
INPUT
PDU Input Voltage 200; 208; 220; 230; 240
Maximum Input Amps (A)
10
Input connection type UTILITY & UPS inputs are available from separately labelled C14 inlets, compatible with included C13-C14
interconnect cables or with compatible user-supplied cabling
PDU Plug Type IEC-320 C14
Input cord length (ft.) 6
Input cord length (m) 1.83
Phase Single-Phase
LEDS ALARMS & SWITCHES
Switches Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6
milliseconds
Front panel LEDs Lighted indicators confirm UPS and Utility switch position and operating mode
PHYSICAL
Shipping Dimensions (HWD/in)
9.84 x 22.75 x 9.44
Shipping Dimensions (HWD/cm)
25 x 57.8 x 24
Shipping weight (lbs) 11
Shipping weight (kg) 5
Unit Dimensions (HWD/in)
3.42 x 17.32 x 3.03
Loading...