Tripp Lite PDUB201U User Manual

Tripp Lite PDUB201U User Manual

120V 20A Single-Phase Hot-Swap PDU with Manual Bypass - 6 NEMA 5-20R Outlets, 2 5-20P Inputs, 1U Rack/Wall

MODEL NUMBER: PDUB201U

Bypass PDU maintains continuous power to connected equipment during scheduled UPS maintenance or replacement.

Features

Bypass PDU Recommended for Maintaining Continuous Power During UPS Maintenance

Keeping mission-critical data center equipment operating at its optimal level often means scheduled maintenance. But what if you are unable to afford the costly downtime involved in powering down for regular upkeep? This 120V 20A single-phase hot-swap PDU works in conjunction with your UPS system to keep everything running 24/7/365. It allows you to manually transfer connected equipment to utility power via the PDU’s bypass switch, permitting maintenance or equipment replacement with no interruption of performance.

Features Dual Inputs and a Manual Transfer Switch for Uninterrupted Operation

The PDUB201U includes separate UPS and utility input cables with NEMA 5-20P plugs. The manual transfer switch allows PDU output power to flow from either input. Flip the switch to Bypass to replace the UPS and flip back to Normal once the maintenance or UPS replacement is complete. Equipment connected to the six NEMA 5-20R outlets will continue to operate without interruption.

Optional ECO Switching Feature Enables Cost-Cutting Power Savings

By enabling the ECO power saving feature, you can power off a single bank of five controlled 5-20R outlets all at once when the device connected to the master 5-20R outlet is powered off or goes into a lowpower consumption mode.

Mounts into 1U of Rack Space or Wall

Use the included mounting hardware to install the PDUB201U’s all-metal housing into 1U of space in an EIA-standard 19-inch rack. You may also use the mounting brackets to secure the PDU to a wall.

Highlights

Ideal for supporting critical IT equipment that require 24/7/365 uptime

Transfers connected components to utility power with no downtime during UPS maintenance

Dual UPS and utility input cables with NEMA 5-20P plugs deliver AC power

ECO mode saves power by shutting down controlled outlet bank in certain conditions

Mounts into 1U of rack space or onto wall using included mounting hardware

Applications

Set the bypass switch to UPS during normal operation, so connected equipment can receive fulltime conditioned power

Set the bypass switch to Utility to bypass the UPS and provide connected equipment with unfiltered power during UPS maintenance or replacement

Enable ECO Switching to save power by shutting down one load bank when the device connected to the master outlet is powered off or in lowconsumption mode

Package Includes

PDUB201U 120V 20A Single-

Phase Hot-Swap PDU

1 / 3

Mounting hardware

Owner’s manual

Specifications

OVERVIEW

UPC Code

037332256201

 

 

PDU Type

Hot-Swap

 

 

INPUT

 

PDU Input Voltage

100; 120; 127

 

 

Recommended Electrical Service

20A

 

 

Maximum Input Amps

12

 

 

PDU Plug Type

(2) NEMA 5-20P

 

 

Input Cord Length Details

Utility input cable (10 ft / 3m) / UPS input cable (4 ft / 1.2m)

 

 

Input Phase

Single-Phase

 

 

OUTPUT

 

Output Capacity Details

2.03kW (127V), 1.92kW (120V), 1.6kW (100V) / 20A total capacity (Agency de-rated to 16A); 16A max per 5-15/20R

 

outlet

 

 

Frequency Compatibility

50 / 60 Hz

 

 

Output Receptacle Details

Set of 6 output receptacles are arranged in two groups to support the optional ECO Power-Saving feature; One

 

MASTER-outlet provides optional current-sense capability that when enabled, automatically powers off the bank of 5

 

CONTROLLABLE GROUP-outlets when the device connected to the MASTER-outlet is powered off or enters a low

 

power sleep mode consuming 20W or less (±5W)

 

 

Output Receptacles

(6) 5-20R

 

 

Output Nominal Voltage

100; 120; 127

 

 

Overload Protection

n/a

 

 

USER INTERFACE, ALERTS & CONTROLS

Front Panel LEDs

Front panel LEDs report UTILITY Input Power ON (green), BYPASS-MODE Switch Setting (yellow), MASTER Outlet

 

Power ON (green), CONTROLLABLE GROUP Outlets Power ON (green)

 

 

Switches

2 position Manual Transfer switch offers Break-Before-Make transfer between UPS and Utility operating modes with

 

less than 8 milliseconds (typical) transfer time; Additional switch offers ENABLE/DISABLE control of the ECO

 

Power-Saving feature

 

 

PHYSICAL

 

Form Factors Supported

Includes installation accessories for wall mount and 1U horizontal rackmount installation in 2 or 4 post equipment

 

racks

 

 

Material of Construction

Metal

 

 

2 / 3