120V 20A Single-Phase Hot-Swap PDU with
Manual Bypass - 6 NEMA 5-20R Outlets, 2 5-20P
Inputs, 1U Rack/Wall
MODEL NUMBER: PDUB201U
Bypass PDU maintains continuous power to connected equipment during scheduled UPS maintenance or
replacement.
Features
Bypass PDU Recommended for Maintaining Continuous Power During UPS Maintenance
Keeping mission-critical data center equipment operating at its optimal level often means scheduled
maintenance. But what if you are unable to afford the costly downtime involved in powering down for
regular upkeep? This 120V 20A single-phase hot-swap PDU works in conjunction with your UPS system
to keep everything running 24/7/365. It allows you to manually transfer connected equipment to utility
power via the PDU’s bypass switch, permitting maintenance or equipment replacement with no
interruption of performance.
Features Dual Inputs and a Manual Transfer Switch for Uninterrupted Operation
The PDUB201U includes separate UPS and utility input cables with NEMA 5-20P plugs. The manual
transfer switch allows PDU output power to flow from either input. Flip the switch to Bypass to replace the
UPS and flip back to Normal once the maintenance or UPS replacement is complete. Equipment
connected to the six NEMA 5-20R outlets will continue to operate without interruption.
Optional ECO Switching Feature Enables Cost-Cutting Power Savings
By enabling the ECO power saving feature, you can power off a single bank of five controlled 5-20R
outlets all at once when the device connected to the master 5-20R outlet is powered off or goes into a lowpower consumption mode.
Mounts into 1U of Rack Space or Wall
Use the included mounting hardware to install the PDUB201U’s all-metal housing into 1U of space in an
EIA-standard 19-inch rack. You may also use the mounting brackets to secure the PDU to a wall.
Highlights
●
Ideal for supporting critical IT
equipment that require 24/7/365
uptime
●
Transfers connected
components to utility power with
no downtime during UPS
maintenance
●
Dual UPS and utility input
cables with NEMA 5-20P plugs
deliver AC power
●
ECO mode saves power by
shutting down controlled outlet
bank in certain conditions
●
Mounts into 1U of rack space or
onto wall using included
mounting hardware
Applications
●
Set the bypass switch to UPS
during normal operation, so
connected equipment can
receive fulltime conditioned
power
●
Set the bypass switch to Utility
to bypass the UPS and provide
connected equipment with
unfiltered power during UPS
maintenance or replacement
●
Enable ECO Switching to save
power by shutting down one
load bank when the device
connected to the master outlet is
powered off or in lowconsumption mode
1 / 3
Package Includes
●
PDUB201U 120V 20A SinglePhase Hot-Swap PDU
Specifications
OVERVIEW
UPC Code 037332256201
PDU Type Hot-Swap
INPUT
PDU Input Voltage 100; 120; 127
Recommended Electrical Service 20A
Maximum Input Amps 12
PDU Plug Type (2) NEMA 5-20P
Input Cord Length Details Utility input cable (10 ft / 3m) / UPS input cable (4 ft / 1.2m)
Input Phase Single-Phase
●
Mounting hardware
●
Owner’s manual
OUTPUT
Output Capacity Details 2.03kW (127V), 1.92kW (120V), 1.6kW (100V) / 20A total capacity (Agency de-rated to 16A); 16A max per 5-15/20R
Frequency Compatibility 50 / 60 Hz
Output Receptacle Details Set of 6 output receptacles are arranged in two groups to support the optional ECO Power-Saving feature; One
Output Receptacles (6) 5-20R
Output Nominal Voltage 100; 120; 127
Overload Protection n/a
USER INTERFACE, ALERTS & CONTROLS
Front Panel LEDs Front panel LEDs report UTILITY Input Power ON (green), BYPASS-MODE Switch Setting (yellow), MASTER Outlet
Switches 2 position Manual Transfer switch offers Break-Before-Make transfer between UPS and Utility operating modes with
PHYSICAL
Form Factors Supported Includes installation accessories for wall mount and 1U horizontal rackmount installation in 2 or 4 post equipment
outlet
MASTER-outlet provides optional current-sense capability that when enabled, automatically powers off the bank of 5
CONTROLLABLE GROUP-outlets when the device connected to the MASTER-outlet is powered off or enters a low
power sleep mode consuming 20W or less (±5W)
Power ON (green), CONTROLLABLE GROUP Outlets Power ON (green)
less than 8 milliseconds (typical) transfer time; Additional switch offers ENABLE/DISABLE control of the ECO
Power-Saving feature
racks
Material of Construction Metal