11.5kW 3-Phase Basic PDU - 45 208-240V Outlets (36 C13, 9 C19), IEC 309 16/20A Red 360-415V Input, 6 ft. Cord, 70 in. 0U, TAA
MODEL NUMBER: PDU3XV6G20
Delivers 208V-240V single-phase AC power to multiple loads from a utility outlet, generator or UPS system in a data center or network closet.
Features
3-Phase 360-415V input / 208V-240V output PDU Distributes Network-Grade Power to Multiple Loads
This basic PDU is an ideal no-frills unit for networking, telecom, security, audio/video and sound reinforcement applications. Recommended for small to mid-sized data centers, computer rooms and network closets, the PDU3XV6G20 features 36 C13 and six C19 (208-240V) outlets in three single-phase output load banks for connecting equipment. A six-foot (1.8-meter) cord with IEC 309 16/20A Red 360415V (3P+N+E) 3-phase input plug connects to your facility’s AC power source, generator or protected UPS system to distribute power to connected loads.
Easy to Install Vertically in an EIA-Standard 19 in. Rack
The 70-inch 0U PDU’s all-metal housing mounts vertically using the pre-installed toolless mounting buttons or the included brackets. Spare buttons are also included. Use the included
PDUMVROTATEBRKT kit to install the PDU with outlets facing the rear for better airflow or equipment access. Cable retention brackets keep power cords organized and your rack free of clutter. The PDU’s switchless design helps prevent an accidental shutdown, which could lead to costly downtime.
TAA-Compliant for GSA Schedule Purchases
The PDU3XV6G20 is compliant with the Federal Trade Agreements Act (TAA), which makes it eligible for
GSA (General Services Administration) Schedule and other federal procurement contracts.
Highlights
●Ideal no-frills PDU for telecom, security, audio/video and other network applications
●36 C13 and 6 C19 single-phase outlets distribute AC power to connected equipment
●Switchless design helps prevent accidental shutdowns that can lead to costly downtime
●6 ft. power cord with IEC 309 16/20A Red 3-phase input connects to AC source
●Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
Applications
Deliver network-grade power to high-density equipment in networking, telecom, security, audio/video and sound reinforcement applications
Package Includes
●PDU3XV6G20 11.5kW 208V240V 3-Phase Basic PDU
●Cable retention brackets with installation hardware
●Rack-mounting hardware
●Owner’s manual
Specifications
OVERVIEW
UPC Code |
037332255679 |
|
|
PDU Type |
Basic |
|
|
INPUT |
|
PDU Input Voltage |
360-415V |
|
|
1 / 3
Recommended Electrical Service |
Three-phase 16A 360-415V service |
|
|
Maximum Input Amps |
16 |
|
|
PDU Plug Type |
IEC-309 16/20A RED (3P+N+E) |
|
|
Input Phase |
3-Phase |
|
|
Input Cord Length (ft.) |
6 |
|
|
Input Cord Length (m) |
1.83 |
|
|
OUTPUT |
|
Output Capacity Details |
11.5kW (415/240V), 11.1kW (400/230V), 10.5kW (380/220V), 10kW (360/208V) total capacity; 16A max per output |
|
phase (L1-L2, L2-L3, L3-L1); 16A max per C19 outlet; 12A max (10A CE) per C13 outlet |
|
|
Frequency Compatibility |
50 / 60 Hz |
|
|
Output Receptacles |
(36) C13; (9) C19 |
|
|
Output Nominal Voltage |
208-240V |
|
|
Overload Protection |
n/a |
|
|
PHYSICAL |
|
Form Factors Supported |
Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button- |
|
mount compatible racks |
|
|
Material of Construction |
Metal |
|
|
PDU Form Factor |
Vertical (0U) |
|
|
Shipping Dimensions (hwd / in.) |
6.00 x 6.50 x 76.00 |
|
|
Shipping Weight (kg) |
6.62 |
|
|
Unit Dimensions (hwd / cm) |
177.8 x 5.6 x 4.9 |
|
|
Unit Dimensions (hwd / in.) |
70 x 2.2 x 1.93 |
|
|
Unit Weight (kg) |
4.08 |
|
|
Unit Weight (lbs.) |
9.00 |
|
|
ENVIRONMENTAL |
|
Operating Temperature Range |
0C ~ 40C (32F ~ 104F) |
|
|
Storage Temperature Range |
-30°C to +50°C (-22°F to +122°F) |
|
|
Relative Humidity |
5 to 95% non-condensing |
|
|
Operating Elevation (ft.) |
0-10,000 |
|
|
Operating Elevation (m) |
0-3000 |
|
|
STANDARDS & COMPLIANCE |
|
Certifications |
Tested to UL60950-1, CAN/CSA, CE, Class A, RoHS, TAA Compliant |
|
|
Certification Details |
Series Number (s) AGPD8420; Safety Standards (Canada) CAN/CSA-C22.2 No. 60950-1:2007 (2nd Ed) +A1:2011 |
|
+A2:2014; Safety Standards (U.S.)UL60950-1:2007 (2nd Ed)+A1 R10.14; FCC/ICES Compliant Class A; Safety |
|
Standards (International) IEC60950-1:2005 (2nd Ed)+A1:2009+A2:2013 |
|
|