DHCP/Manual configuration support
10/100 Mbps auto-sensing
Real-time clock backup maintains the time of day and date even if the PDU is unpowered
Tiered access privileges allow an administrator and a guest to login via web browser
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP
protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications (set of
2 9mm buttons pre-installed, 2 9mm and 4 6mm spare buttons included)
Nut-and-bolt mounting support for other racks
TAA Compliant Version Available - Order Tripp Lite PDU3VSR10L23TAA
Specifications
OVERVIEW
PDU Type Switched
OUTPUT
Output Capacity Details 8.6kVA total; 13.9A per bank (balanced)
Frequency compatibility 60 Hz
Output nominal voltage 208V single phase
Overload protection 3 20A double-pole circuit breakers (1 per output phase)
Outlet quantity / type 24 total - 21 C13 (7 per phase), 3 C19 (1 per phase)
Outlet Type IEC-C13, IEC-C19
Customized load
management receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage 208
Maximum Input Amps (A) 24
PDU Plug Type NEMA L21-30P
Input cord length (ft.) 10
Input cord length (m) 3.05
Phase 3-Phase
LEDS ALARMS & SWITCHES
Switches Pushbutton scroll switch enables local power consumption display of each phase or outlet separately, display
rotate and display IP address functions
Front panel LEDs 2 digit current meter display reports output amps per phase and IP address self identification
PHYSICAL
Shipping Dimensions
(HWD/in)
75.4 x 6.6 x 9.3
Shipping Dimensions
(HWD/cm)
191.5 x 16.8 x 23.6
Shipping weight (lbs) 20.45