This manual contains important instructions and warnings that should be
followed during the installation, operation and storage of all Tripp Lite UPS
Systems.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, dust or
direct sunlight.
• For best performance, keep the indoor temperature between 32° F and
104° F (between 0° C and 40° C).
• Leave adequate space around all sides of the UPS for proper ventilation.
UPS Connection Warnings
• Connect your UPS to a three-wire, grounded AC power outlet. Do not
remove or modify the ground pin of the UPS's plug.
• Do not use two-prong adapters with the UPS's plug. Do not plug your UPS
into itself; this will damage the UPS and void your warranty.
• If you are connecting your UPS to a motor-powered AC generator,
the generator must provide clean, filtered computer-grade output.
• Use only the power supply cord provided with this unit. The power cord for
the UPS is wired in accordance with National Electrical Code (NEC) specifications. Be sure that your wall outlet is also wired to these specifications.
Equipment Connection Warnings
• Do not use Tripp Lite UPS Systems for life support applications in which
a malfunction or failure of a Tripp Lite UPS System could cause failure or
significantly alter the performance of a life-support device.
Battery Warnings
• Your UPS does not require routine maintenance. Do not open your UPS
for any reason. There are no user-serviceable parts inside.
• Battery replacement must be performed by qualified service personnel.
Because the batteries present a risk of electrical shock and burn from high
short-circuit current, qualified service personnel should observe proper
precautions: Unplug and turn off the UPS before performing battery
replacement. Use tools with insulated handles and replace the existing
batteries with the same number and type of new batteries (Sealed LeadAcid). Do not open the batteries. Do not short or bridge the battery terminals with any object.
• The UPS batteries are recyclable. Refer to local codes for disposal requirements or call 1-800-SAV-LEAD (1-800-728-5323) for complete recycling
information. Do not dispose of the batteries in a fire.
• Do not attempt to add external batteries.
2
Installation
Mounting
Note: When removing the mounting bracket screws to change the mounting profile of your UPS, do not remove the
screws which secure the UPS cabinet. Two of these screws are located at each end of the UPS, between the four holes
used for the mounting brackets.
Rackmount
Your UPS’s mounting brackets are pre-set at a standard depth for 19-in. rack
installation.* Additional bracket holes allow you to mount the UPS at additional
depths. To adjust the depth: Remove mounting bracket screws; adjust brackets
to the desired depth; replace screws.
Desktop/Under-Monitor
Remove mounting brackets (if desired). Place on your desktop or under your computer monitor. CAUTION: Do not place more than 50 lb. (22.7 kg) on your UPS.
Vertical Tower
Remove mounting bracket screws. Position brackets as shown in Figure 1 to serve
as stabilizers for the UPS in a vertical position. Install 2 mounting screws in each
bracket. Make sure the control and LED panel is UP when you are finished.
Wallmount
Remove mounting bracket screws. Position brackets as shown in Figure 2 to
mount the UPS perpendicular to a wall along a straight, vertical line. Adjust
bracket to desired distance from wall. Install 4 mounting screws in each bracket.
Mount UPS to the wall.* Make sure the control and LED panel is UP when you
are finished. Additional bracket holes allow you to mount up to two UPSs sideby-side on the same set of brackets (Figure 3).**
* Using screws and appropriate hardware (user supplied) to mount to rack, wall or other surface.
** CAUTION: each UPS weighs 15-1/2 lbs. (7 kg). Ensure adequate wall fasteners are used.
Figure 1 – Vertical Tower
Figure 2 – Wallmounting
One UPS
Figure 3 – Wallmounting
Two UPSs
3
Connection
Plug one end of the
1
detachable line cord
into your UPS's AC
Inlet Receptacle and
the other end into an
electrical outlet.
Plug your computer,
2
monitor and other
critical devices into your
UPS's Battery-Supported
Receptacles.*
Plug a printer or other
peripheral equipment
into your UPS's SurgeOnly Receptacle.
–Optional–
Using Tripp Lite cable, connect
the serial port of your computer
to the serial port of your UPS.**
Load software and run
installation program appropriate
to your operating system.
Turn your UPS ON
3
by pressing the Main
Power Switch, holding
it for 3 seconds and
releasing it.***
* Your UPS is designed to support only computer equipment. You will overload your UPS if you connect household
appliances, laser printers or surge suppressors to the UPS's Battery-Supported Outlets. ** DB9 port connection is
optional. Your UPS will function properly without this connection. *** The UPS will execute a 10-second self-test.
The "Normal" LED will illuminate and the UPS will emit one beep to indicate normal operation.
4
Basic Operation
Front
13
11
10
Back
6
9
12
8
8
234 5
1
11
7
Switch
1. Main Power Switch
This switch activates three separate UPS functions:
UPS Power
Press the switch, hold it for 3 seconds and release it to turn the UPS
ON or OFF.*
Alarm Silence
Press the switch and immediately release it to silence the UPS Alarm.
UPS Cold Start
Press the switch, hold it for 5 seconds and release it to turn your UPS
ON and to use it as a stand-alone power source (operating from the
battery without AC input).**
* The UPS will execute a 10-second self-test when you turn it on. The “Normal" LED will illuminate, and
the UPS will beep once to indicate the UPS is turned ON. If the UPS alarm sounds and the "Replace Battery" LED
illuminates, turn your UPS OFF, let your UPS charge its batteries for 12 hours and turn UPS back ON to repeat the
automatic self-test. If alarm still sounds, contact Tripp Lite for service. CAUTION: Do not unplug your UPS to test its
batteries. This will remove safe electrical grounding and may introduce a damaging surge into your network
connections.
** The "Backup" LED will illuminate since your UPS will operate from battery power.
5
Indicator Lights
The SmartPro 450 RT utilizes dual function Indicator Lights that alert you to
different information depending on whether they illuminate constantly or are
flashing. All Indicator Light Descriptions refer to when the UPS is connected to
the wall outlet and turned ON.
2. "AC Normal/AVR" LED
This green light will illuminate constantly to indicate the utility-supplied AC
line voltage at your wall outlet is normal. It will flash to indicate your UPS is
automatically correcting high or low AC line voltage (AVR=Automatic Voltage
Regulation). The longer the UPS is correcting voltage, the longer the LED will
flash. This is a normal, automatic operation of your UPS, and no action is required
on your part.
3. "Backup/Low Batt" LED
This yellow light will illuminate constantly to indicate your UPS is providing
your equipment with battery power. (The UPS's Alarm will sound once every
15 seconds.) The light will flash when the UPS's battery is low and the UPS
is initiating an automatic system shutdown. (The UPS's Alarm will sound once
every second for approximately 2 minutes, depending on load, prior to shutdown).
4. "Fault/Overload" LED
This red light will illuminate constantly to indicate a short circuit in the UPS
or other fault. The light will illuminate and the UPS's Alarm will sound constantly
for 30 seconds before the UPS automatically shuts down. The light
will flash (and the UPS's Alarm will sound once each second) when the UPS's
capacity has been exceeded while it is operating from battery power. Immediately
remove overload from battery-supported outlets.
5. "Replace Batt" LED
This red light will illuminate constantly if your UPS fails the automatic self-test
(after you turn your UPS ON) and the UPS battery is less than fully charged.
Turn the UPS OFF and let it charge for 12 hours and turn it back ON to perform
a second automatic self-test. If the light continues to stay on, contact Tripp Lite
for service.
6. "Fault" LED
This red light shines constantly when your UPS detects a wiring fault in your
wall outlet (reversed phases, missing ground, etc.) Have an electrician fix the
fault immediately. Your UPS will identify the presence of most (
ing faults.
6
but not all) wir-
Other UPS Features
7. AC Receptacles (Battery Backup Supported)
These receptacles provide your connected equipment with AC line power during
normal operation and battery power during blackouts and brownouts. They also
protect your equipment against damaging surges and line noise. Connect computer, monitor and other essential equipment to these receptacles.
8. AC Receptacle (Surge-Only)
This receptacle provides equipment that does not require battery backup (such
as printers) with complete surge and line noise protection. Do not connect
computers or other essential equipment to this receptacle.
9. “SMART” RS-232 Port
The RS-232 port connects your UPS to any PC or workstation. Use with Tripp Lite
software and cabling to monitor and manage network power and automatically
save open files and shut down equipment during a blackout. This port uses
RS-232 communications to transmit UPS and power conditions.
10. Accessory Slot
Contact Tripp Lite Customer Support for more information and a list of available
SNMP, network management and connectivity products.
11. Mounting Brackets
The mounting brackets are already set for mounting in standard 19 in. racks.
See Installation section for using the mounting brackets to suit under-monitor,
tower and wallmount applications.
12. AC Inlet Receptacle
Connect one end of the detachable line cord into this receptacle and the other end
into your wall outlet.
13. Battery Replacement Door
Under normal conditions, the original battery in your UPS will last several years.
Battery replacement should be performed only by qualified service personnel.
Refer to “Battery Warnings” in the Safety section. When replacing batteries,
qualified service personnel should follow this procedure: 1) turn UPS OFF; 2)
remove the snap-on battery replacement door, on left front of unit; 3) pull
batteries partially out of case; 4) make a detailed sketch of the batteries and the
polarity, color and connection of all cables; 5) disconnect battery terminals; 6)
dispose of used batteries; 7) reconnect replacement batteries exactly as original
batteries were; 8) push batteries back into case and replace cover.*
* You may not receive full runtime until your replacement batteries have fully charged.
7
Storage & Service
Storage
First turn your UPS OFF and disconnect its power cord from the wall outlet.
Then disconnect all equipment to avoid battery drain. If you plan on storing
your UPS for an extended period of time, fully recharge the UPS batteries once
every three months by plugging the UPS into a live AC outlet, turning the Power
Switch ON and letting the UPS charge for 4-6 hours. If you leave your UPS
batteries discharged for an extended period of time, they will suffer permanent
loss of capacity.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the
ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter
describing the symptoms of the problem. If the UPS is within the 2 year warranty
period, enclose a copy of your sales receipt.
Specifications
ModelSMART 450 RT
Output Capacity (VA/Watts):450/270
Battery Runtime (Half Load/Full Load) Min.:12/3
Battery Recharge Rate:2-4 hrs.
Approvals:UL 1778, cUL, FCC Class B
Input Voltage (120V); Input Frequency (50/60 Hz Auto-Selecting); On-Line Input Voltage Range (86 - 147 volts); Voltage-Regulated
Output Voltage Range (120V +/- 10%); On Battery Output Voltage Range (120V +/- 5%); Output Waveform Line Mode (filtered
sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards);
AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).
FCC Radio/TV Interference Notice
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference using one or more of the following measures: reorient
or relocate the receiving antenna; increase the separation between the equipment and receiver; connect the equipment into an outlet
on a circuit different from that which the receiver is connected; consult the dealer or an experienced radio/television technician for help.
The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly
approved by the party responsible for compliance could void the user's authority to operate the equipment.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.