Tripp Lite 200803016 95-2924 User Manual

TECHNICAL APPLICATION BULLETIN # 95-2924
Tripp Lite Network-Grade Power Distribution Units (PDUs)
Tripp Lite Network-Grade PDUs are highly reliable multiple-outlet strips that distribute power from a UPS system, generator or utility wall outlet to multiple devices. Tripp Lite offers three separate types of rackmount PDUs (see selector guide, below) with features and benefits to match every application—networking, server, telecom and more.
See inside for an additional selector guide, application diagrams and complete specifications
1111 W. 35th Street, Chicago, IL 60609 • (773) 869-1234 • www.tripplite.com




Feature Focus (See page 8)
• PDUs with Redundant Input Cords and Automatic Transfer Switch (ATS)
• PDUs with Dual Input Cords and Dual Independent Power Circuits
PDU Selector Guide
(Features/Benefits)
Choose a PDU by identifying the ideal features and benefits for your application.
Tripp Lite PDUs
Basic PDUs Metered PDUs Switched PDUs
Feature Benefit
See page 4 See page 5 See pages 6-7
Multiple Outlets Increase the number of devices that
can be powered by a UPS system, generator or utility source.
High-Current Plug and Increase connection flexibility by Low-Current Outlets* converting a single high-amperage outlet
into multiple low-amperage outlets.
Long Input Power Cord Increases installation flexibility by allowing
devices to be located far from an input power source.
Digital Load Meter Avoid overloads and safely add loads
as total equipment power consumption is displayed.
Remote Control of Reduces frequency of costly service calls Individual Outlets by rebooting locked devices. Extends (via SNMP, Web or runtime of critical devices by turning off Telnet) nonessential loads during blackouts.
Remote monitoring and Prevents over loads that cause condition reporting equipment downtime.
* Select models.
2
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
PDU Selector Guide
(Input/Output)
Choose by matching power source input to PDU output.
Using a Tripp Lite UPS System as Power Source Input
The most common application for a PDU is to distribute UPS System power to connected computer equipment. The table below shows common outlet types and a partial list of Tripp Lite UPS Systems that include each outlet type.
OUTLET SMARTPRO SMARTONLINE TYPE UPS SYSTEMS UPS SYSTEMS
5-15R All 500-3000VA (120V) All 750-3000VA (120V) 5-15/20R All 2200-5000VA (120V) All 2200VA-16kVA (120V) L5-20R Select 2200-2600VA (120V) All 2200VA (120V) L5-30R All 3000VA (120V) All 3000VA (120V) L6-20R Select 5000VA All 5000VA and Select 6-16kVA L6-30R All 5000VA All 5000VA and Select 6-16kVA C13 All International Versions All International Versions C19 All 2200-5000VA International Versions All 2200-3000VA International Versions
* 5-20R wall outlets and 5-15/20R PDU outlets accept 5-15P or 5-20Pplugs. ** Model includes ATS. †User provides input cable for this application.
PDU Part Number Decoder
PDU = Power Distribution Unit M = Metered H = Horizontal V = Vertical AT = ATS with Redundant Input Cords NET = Network Card for Remote
Monitoring and Control
HV = High Voltage (200-250V)
Tripp Lite Power Cords and Adapters
Model Description
P002-002 C14 to 5-15R Power Cable (2 ft.) P004-006 C13 to C14 Power Cable (6 ft.) P005-010 Heavy-Duty C13 to C14 Power Cable (10 ft.) P006-006 C13 to 5-15P Power Cable (6 ft.) P007-010 Heavy-Duty C13 to 5-15P Power Cable (10 ft.) P010-012 C13 to 5-15P Power Cable (12 ft.) P022-001 5-15R to 5-15P Power Cable (1 ft.) P032-007 C13 to C20 Power Cable (7 ft.) P034-010 Heavy-Duty C19 to 5-15P Power Cable (10 ft.) P040-010 C19 to L6-20P Power Cable (10 ft.) P044-06I L5-20R to 5-20P Adapter (6 in.) P045-010 Heavy-Duty C19 to L5-20P Power Cable (10 ft.) P047-010 Heavy-Duty C14 to C19 Power Cable (10 ft.) P049-010 Heavy-Duty C19 to 5-20P Power Cable (10 ft.) UNIPLUGINT C13 to Wonpro Universal Outlet Adapter (Wonpro outlet is compatible with
more than 20 North American and international plug types.)
Step 1 Step 2
Choose Power Source Input Choose PDU Output
Receptacle Type Voltag e Current Basic PDUs Metered PDUs Switched PDUs
Model Outlet Outlet Model Outlet Outlet Model Outlet Outlet Number Qty. Type* Number Qty. Type* Number Qty. Type*
5-15R 100-125V 15A PDU1215 13 5-15R PDUMH15 13 5-15R PDUMH15ATNET** 8 5-15R
PDU1415 14 5-15R PDUMV15 16 5-15R PDUMV15NET 16 5-15/20R PDUNV 14 2 C19 / 12 C13 PDUMH15AT** 8 5-15R PDUV15 12 5-15R
5-20R* 100-125V 20A PDU1220 13 5-15/20R PDUMV20 20 5-15/20R PDUMH20ATNET** 16 5-15/20R
PDUNV 14 2 C19 / 12 C13 PDUMV40 32 5-15/20R PDUMV20NET 24 5-15/20R PDU40TDUAL 40 5-15/20R PDUMH20AT** 16 5-15/20R PDUV20 12 5-15/20R PDUMH20 13 5-15/20R
L5-20R 100-125V 20A PDU1220T 13 5-15/20R PDUMV20 20 5-15/20R PDUMH20ATNET** 16 5-15/20R
PDU1420T 14 5-15/20R PDUMV40 32 5-15/20R PDUMV20NET 24 5-15/20R PDU40TDUAL 40 5-15/20R PDUMH20AT** 16 5-15/20R PDUNV 14 2 C19 / 12 C13 PDUMH20 13 5-15/20R
L5-30R 100-125V 30A PDU2430 24 5-15R PDUMV30 28 5-15/20R PDUMV30NET 24 5-15/20R
PDUMH30NET 16 5-15/20R
L6-20R 200-250V 20A PDUNV 14 2 C19 / 12 C13 PDUMV20HV 38 6 C19 / 32 C13 PDUMV20HVNET 24 4 C19 / 20 C13
L6-30R 200-250V 30A PDU1230 18 2 C19 / 16 C13 PDUMV30HV 30 6 C19 / 24 C13 PDUMV30HVNET 24 4 C19 / 20 C13
PDUV30HV 38 6 C19 / 32 C13 PDUMH30HVNET 16 C13
C13 Varies Varies PDUNV 14 2 C19 / 12 C13 PDUMH15HVNET 8 C13
C19 Varies Varies PDUNV 14 2 C19 / 12 C13 PDUMH20HVNET 8 C13
PDUMV20HVNET 24 4 C19 / 20 C13
VARIES Varies Varies PDU12IEC 14
2 C19 / 12 C13 PDUMV20HV†38 6 C19 / 32 C13 PDUMV20HVNET†24 4 C19 / 20 C13
(User provides PDUMH15ATNET**
8 5-15R
C19 or C13, PDUMH20ATNET**
16 5-15/20R
depending on
model, to the input
plug of their choice.)
Network
Jack
Power Distribution Unit
(PDUMV20HVNET Shown)
Remote Computer
1
TCP/IP
3
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
PDU Application Diagrams
Tripp Lite PDUs can be used in a variety of applications. The most popular applications are shown below. Contact Tripp Lite's technical support department at (773) 869-1234 for additional assistance with a specific application.
Application #1: Adding More Outlets to a UPS System
Applicable Tripp Lite PDUs: All Models
Description: PDU plugs into UPS system outlet. PDU increases total number of outlets powered by the UPS system (from 6 to 18 in this example. Additional front panel outlet not shown.).
21
Application #2: Converting a Single High-Amperage Outlet into Multiple Low-Amperage Outlets
Applicable Tripp Lite PDUs: Models with High-Amperage Plugs
Description: PDU plugs into UPS system's high-amperage outlet (30-amp L5-30R outlet in this example). PDU increases total number of low-amperage outlets powered by the UPS system (from 8 to 32 in this example; additional 12 front panel outlets not shown).
2
1
Application #3: Remotely Controlling Individual Outlets (via SNMP,Web or Telnet)
Applicable Tripp Lite PDUs: All Switched Models
Description: PDU's Ethernet port connects to network wall jack.
Remote user controls power to PDU outlets for a variety of purposes. Benefits include rebooting locked devices to reduce the frequency of costly service calls and turning off nonessential loads during blackouts to extend battery backup runtime for critical devices.
2
1
SMART1000RM1U UPS System (Rear Panel Shown)
PDU1215 Power Distribution Unit (Rear Panel Shown)
1
2
SMART3000RM2U UPS System (Rear Panel Shown)
PDU2430 Power Distribution Unit (Rear Panel Shown)
2
1
2
2
2
SU5000RT4U UPS System (Rear Panel Shown)
Application #4: Distributing Facility UPS/Generator Power to Multiple Outlets
Applicable Tripp Lite PDUs: All Models
Description: PDU plugs into a wall outlet supported by facility UPS/generator power. PDU distributes power to equipment via 16 outlets. (All PDU models support facility UPS/generator applications, including all available PDU features.)