1Life support policy ....................................................................................................................................................... 4
5Putting the PDx-113-57/60-SE into operation ....................................................................................................... 8
5.1Starting up ............................................................................................................................................................. 9
5.2Writing a simple TMCLTM program ................................................................................................................ 10
5.3Operating the module in direct mode ........................................................................................................ 11
6TMCLTM and TMCL-IDE ................................................................................................................................................ 12
6.1Binary command format .................................................................................................................................. 12
6.2Reply format ........................................................................................................................................................ 13
6.4.3I/O port commands..................................................................................................................................... 15
6.6.1Format of the command line ................................................................................................................... 18
6.6.2Format of a reply ......................................................................................................................................... 18
6.6.3Commands that can be used in ASCII mode ..................................................................................... 18
6.6.4Configuring the ASCII interface .............................................................................................................. 18
6.7.31Customer specific TMCLTM command extension (UF0…UF7/user function) ................................... 74
6.7.32Request target position reached event ................................................................................................. 75
6.7.33BIN (return to binary mode) .................................................................................................................... 76
6.7.34TMCLTM Control Functions .......................................................................................................................... 77
9Hints and tips .............................................................................................................................................................. 87
9.5Using the RS485 interface ............................................................................................................................... 89
9.5.1Using RS485 with converter ..................................................................................................................... 89
9.5.2Using RS485 with USB-2-X interface converter ................................................................................... 89
10Revision history .......................................................................................................................................................... 90
TRINAMIC Motion Control GmbH & Co. KG does not
authorize or warrant any of its products for use in life
support systems, without the specific written consent of
TRINAMIC Motion Control GmbH & Co. KG.
Life support systems are equipment intended to support or
sustain life, and whose failure to perform, when properly
used in accordance with instructions provided, can be
reasonably expected to result in personal injury or death.
Information given in this data sheet is believed to be
accurate and reliable. However neither responsibility is
assumed for the consequences of its use nor for any
infringement of patents or other rights of third parties,
which may result from its use.
Specifications are subject to change without notice.
The PDx-113-57/60-SE is a full mechatronic device consisting of a NEMA 23 (flange size 57mm) or NEMA 24
(flange size 60mm) stepper motor, controller/driver electronics and integrated encoder. The electronics itself
is also available without the motor as TMCM-113-57/60-SE module.
Applications
Compact single-axis stepper motor solutions
Encoder feedback for high reliability operation (-SE option)
Electrical data
Supply voltage: +24V DC nominal (+7V .. +28.5V DC)
Motor current: up-to 2.8A RMS (programmable)
Integrated motor (for PDx-113-57/60-SE only)
Two phase bipolar stepper motor with 2.8A RMS nom. coil current
Holding torque with 57mm motor: 0.55Nm, 1.01Nm, 1.26Nm or 1.89Nm
Holding torque with 60mm motor: 1.1Nm, 1.65Nm, 2.1Nm or 3.1Nm
Integrated encoder (for –SE option only)
Integrated sensOstep™ magnetic encoder (max. 256 increments per rotation) for step-loss detection
under all operating conditions
Integrated motion controller
Motion profile calculation in real-time (TMC428 motion controller)
On the fly alteration of motor parameters (e.g. position, velocity, acceleration)
Integrated bipolar stepper motor driver
Up-to 16 microsteps per full step
High-efficient operation, low power dissipation (TMC249 stepper driver with external MOSFETs)
Dynamic current control
Integrated protection
Integrated stallGuard™ for motor stall detection (e.g. elimination of end switches)
Integrated chopSync™ for high velocity operation
Interfaces
2 inputs for reference switches, 2 general purpose inputs and 2 general purpose outputs
either RS-232 or RS-485 serial communication interfaces
Software
Available with TMCL (both interface options)
stand-alone operation or remote controlled operation
program memory (non volatile) for up-to 2048 TMCL commands
PC-based application development software TMCL-IDE available for free
Single axis bipolar stepper motor controller /
driver electronics with integrated encoder
electronics
board size: 60mm x 60mm
Interface option
Communication interface
232
RS232 interface
485
RS485 interface
3 Order codes
The PDx-113-57/60-SE is currently available with two different stepper motor series (NEMA23 / 57mm flange
size or) with four stepper motors of different length and holding torque each and two interface options:
With NEMA 23 / 57mm flange size motor:
Table 3.1: Order codes (PDx-113-57-SE)
With NEMA 24 / 60mm flange size motor:
Table 3.2: Order codes (PDx-113-60-SE)
The electronic module TMCM-113-57/60-SE itself is also available with two serial interface options:
Table 3.3: Order codes (TMCM-113-57/60-SE)
Serial interface options:
Table 3.4: Options
For cost critical applications and applications with reduced requirements with regard to position feedback
both versions - with and without motor - are also available without sensOstep™ encoder as PDx-113-57/60
and TMCM-113-57/60 on request.
As with most TRINAMIC modules the software running on the microprocessor of the PDx-113-57/60-SE
consists of two parts, a boot loader and the firmware itself. Whereas the boot loader is installed during
production and testing at TRINAMIC and remains – normally – untouched throughout the whole lifetime, the
firmware can be updated by the user. New versions can be downloaded free of charge from the TRINAMIC
website (http://www.trinamic.com).
The firmware shipped with this PANdriveTM is related to the standard TMCLTM firmware shipped with most of
TRINAMIC modules with regard to protocol and commands. Corresponding, the module of the PANdriveTM is
based on the TMC428 motion controller for stepper motors and the TMC249 high power driver and supports
the standard TMCLTM with a special range of values. All commands and parameters available with this unit
are explained on the following pages.
Left reference switch input
Right reference switch input
Supply and signal ground
Power supply output
General purpose output 0
General purpose output 1
General purpose input 0
General purpose input 1
1
2
3
4
5
6
7
8
GND
RS232_RxD or RS485A / RS485+
GND
Supply and signal ground
Supply and system ground
1
2
3
4
VDD
GND
Power supply input
Supply and system ground
2
1
RS232_TxD or RS485B / RS485-
BB+
AA+
Motor coil B
Motor coil B
Motor coil A
Motor coil A
4
3
2
1
5 Putting the PDx-113-57/60-SE into operation
Here you can find basic information for putting your PANdrive into operation. The text contains a simple
example for a TMCLTM program and a short description of operating the module in direct mode.
The things you need:
PDx-113-57/60-SE
Interface (RS232 or RS485) suitable to your PDx-113-57/60-SE version with cables
Power supply for 24V
TMCL-IDE program and PC
Precautions:
Do not connect or disconnect the motor while powered!
Do not mix up connections or short-circuit pins.
Avoid bounding IO wires with motor power wires as this may cause noise picked up from the
motor supply.
Do not exceed the maximum power supply of 28.5V.
Start with power supply OFF!
Here we show you, how to connect the RS232 interface. Use the RS485 interface similarly please.
1. Connect the interface:
Please keep in mind that the RS232 transmit signal wire of the master has to be connected to the
RS232 receive signal wire of the board and vice versa.
2. Connect power supply:
3. Turn power ON. The green LED of the module glows and gives notice that the module is powered
with its supply voltage. If this does not occur, switch power OFF and check your connections as
well as the power supply.
4. Start the TMCL-IDE software development environment (available on the TechLibCD and
www.trinamic.com).
Installing the TMCL-IDE:
Make sure the COM port you intend to use is not blocked by another program.
Open TMCL-IDE by clicking TMCL.exe.
Choose Setup and Options and thereafter the Connection tab.
The PDx-113-57/60-SE supports TMCLTM direct mode (binary commands or ASCII interface) and stand-alone
TMCLTM program execution. You can store up to 2048 TMCLTM instructions on it.
In direct mode the TMCLTM communication over RS485 or RS232 follows a strict master/slave relationship.
That is, a host computer (e.g. PC/PLC) acting as the interface bus master will send a command to the PDx113-57/60-SE. The TMCLTM interpreter on the module will then interpret this command, do the initialization of
the motion controller, read inputs and write outputs or whatever is necessary according to the specified
command. As soon as this step has been done, the module will send a reply back over RS485/RS232 to the
bus master. The master should not transfer the next command till then. Normally, the module will just
switch to transmission and occupy the bus for a reply, otherwise it will stay in receive mode. It will not
send any data over the interface without receiving a command first. This way, any collision on the bus will
be avoided when there are more than two nodes connected to a single bus.
The Trinamic Motion Control Language (TMCLTM) provides a set of structured motion control commands.
Every motion control command can be given by a host computer or can be stored in an EEPROM on the
TMCMTM module to form programs that run stand-alone on the module. For this purpose there are not only
motion control commands but also commands to control the program structure (like conditional jumps,
compare and calculating).
Every command has a binary representation and a mnemonic. The binary format is used to send commands
from the host to a module in direct mode, whereas the mnemonic format is used for easy usage of the
commands when developing stand-alone TMCLTM applications using the TMCL-IDE (Integrated Development
Environment).
There is also a set of configuration variables for the axis and for global parameters which allow individual
configuration of nearly every function of a module. This manual gives a detailed description of all TMCLTM
commands and their usage.
TM
and TMCL-IDE
6.1 Binary command format
Every command has a mnemonic and a binary representation. When commands are sent from a host to a
module, the binary format has to be used. Every command consists of a one-byte command field, a one-byte
type field, a one-byte motor/bank field and a four-byte value field. So the binary representation of a
command always has seven bytes. When a command is to be sent via RS232 or RS485 interface, it has to be
enclosed by an address byte at the beginning and a checksum byte at the end. In this case it consists of
nine bytes.
The binary command format for RS232 and RS485 is as follows:
The checksum is calculated by adding up all the other bytes using an 8-bit addition.
As mentioned above, the checksum is calculated by adding up all bytes (including the module address byte)
using an 8-bit addition. Here are two examples to show how to do this:
in C:
unsigned char i, Checksum;
unsigned char Command[9];
//Set the “Command” array to the desired command
Checksum = Command[0];
for(i=1; i<8; i++)
Checksum+=Command[i];
Command[8]=Checksum; //insert checksum as last byte of the command
//Now, send it to the module
in Delphi:
var
i, Checksum: byte;
Command: array[0..8] of byte;
//Set the “Command” array to the desired command
//Calculate the Checksum:
Checksum:=Command[0];
for i:=1 to 7 do Checksum:=Checksum+Command[i];
Command[8]:=Checksum;
//Now, send the “Command” array (9 bytes) to the module
6.2 Reply format
Every time a command has been sent to a module, the module sends a reply.
The reply format for RS485 and RS232 is as follows:
The checksum is also calculated by adding up all the other bytes using an 8-bit addition.
Do not send the next command before you have received the reply!
The status code can have one of the following values:
6.3 Stand-alone applications
The module is equipped with an EEPROM for storing TMCLTM applications. You can use the TMCL-IDE for
developing stand-alone TMCLTM applications. You can load your program down into the EEPROM and then it
will run on the module. The TMCL-IDE contains an editor and a TMCLTM assembler where the commands can
be entered using their mnemonic format. They will be assembled automatically into their binary
representations. Afterwards this code can be downloaded into the module to be executed there.
6.4 TMCL
In this section a short overview of the TMCLTM commands is given.
TM
command overview
6.4.1 Motion commands
These commands control the motion of the motor. They are the most important commands and can be used
in direct mode or in stand-alone mode.
Calculate using the accumulator and a
constant value
CALCX
33
Calculate using the accumulator and the
X register
AAP
34
Copy accumulator to an axis parameter
AGP
35
Copy accumulator to a global parameter
6.4.2 Parameter commands
These commands are used to set, read and store axis parameters or global parameters. Axis parameters can
be set independently for the axis, whereas global parameters control the behavior of the module itself.
These commands can also be used in direct mode and in stand-alone mode.
6.4.3 I/O port commands
These commands control the external I/O ports and can be used in direct mode and in stand-alone mode.
6.4.4 Control commands
These commands are used to control the program flow (loops, conditions, jumps etc.). It does not make
sense to use them in direct mode. They are intended for stand-alone mode only.
6.4.5 Calculation commands
These commands are intended to be used for calculations within TMCLTM applications. Although they could
also be used in direct mode it does not make much sense to do so.
Set axis parameter (motion control
specific settings)
GAP
6
<parameter>, <motor number>
Get axis parameter (read out motion
control specific settings)
STAP
7
<parameter>, <motor number>
Store axis parameter permanently (non
volatile)
RSAP
8
<parameter>, <motor number>
Restore axis parameter
SGP
9
<parameter>, <bank number>, value
Set global parameter (module specific
settings e.g. communication settings or
TMCL™ user variables)
GGP
10
<parameter>, <bank number>
Get global parameter (read out module
specific settings e.g. communication
settings or TMCL™ user variables)
STGP
11
<parameter>, <bank number>
Store global parameter (TMCL™ user
variables only)
RSGP
12
<parameter>, <bank number>
Restore global parameter (TMCL™ user
variable only)
RFS
13
START|STOP|STATUS, <motor number>
Reference search
SIO
14
<port number>, <bank number>, <value>
Set digital output to specified value
GIO
15
<port number>, <bank number>
Get value of analogue/digital input
CALC
19
<operation>, <value>
Process accumulator & value
COMP
20
<value>
Compare accumulator <-> value
JC
21
<condition>, <jump address>
Jump conditional
JA
22
<jump address>
Jump absolute
CSUB
23
<subroutine address>
Call subroutine
RSUB
24 Return from subroutine
WAIT
27
<condition>, <motor number>, <ticks>
Wait with further program execution
STOP
28 Stop program execution
SCO
30
<coordinate number>, <motor number>,
<position>
Set coordinate
GCO
31
<coordinate number>, <motor number>
Get coordinate
CCO
32
<coordinate number>, <motor number>
Capture coordinate
CALCX
33
<operation>
Process accumulator & X-register
AAP
34
<parameter>, <motor number>
Accumulator to axis parameter
AGP
35
<parameter>, <bank number>
Accumulator to global parameter
For calculating purposes there is an accumulator (or accu or A register) and an X register. When executed in
a TMCLTM program (in stand-alone mode), all TMCLTM commands that read a value store the result in the
accumulator. The X register can be used as an additional memory when doing calculations. It can be loaded
from the accumulator.
When a command that reads a value is executed in direct mode the accumulator will not be affected. This
means that while a TMCLTM program is running on the module (stand-alone mode), a host can still send
commands like GAP, GGP or GIO to the module (e.g. to query the actual position of the motor) without
affecting the flow of the TMCLTM program running on the module.
6.5 TMCL
The following TMCLTM commands are currently supported:
TMCLTM also offers an ASCII interface that can be used to communicate with the module and to send some
commands as text strings.
The ASCII command line interface is entered by sending the binary command 139 (enter ASCII
mode).
Afterwards the commands are entered like in the TMCL-IDE. Please note that only those commands,
which can be used in direct mode, also can be entered in ASCII mode.
For leaving the ASCII mode and re-enter the binary mode enter the command BIN.
6.6.1 Format of the command line
As the first character, the address character has to be sent. The address character is A when the module
address is 1, B for modules with address 2 and so on. After the address character there may be spaces (but
this is not necessary). Then, send the command with its parameters. At the end of a command line a <CR>
character has to be sent.
Here are some examples for valid command lines:
AMVP ABS, 1, 50000
A MVP ABS, 1, 50000
AROL 2, 500
A MST 1
ABIN
These command lines would address the module with address 1. To address e.g. module 3, use address
character C instead of A. The last command line shown above will make the module return to binary mode.
6.6.2 Format of a reply
After executing the command the module sends back a reply in ASCII format. This reply consists of:
the address character of the host (host address that can be set in the module)
the address character of the module
the status code as a decimal number
the return value of the command as a decimal number
a <CR> character
So, after sending AGAP 0, 1 the reply would be BA 100 –5000 if the actual position of axis 1 is –5000, the
host address is set to 2 and the module address is 1. The value 100 is the status code 100 that means
command successfully executed.
6.6.3 Commands that can be used in ASCII mode
The following commands can be used in ASCII mode: ROL, ROR, MST, MVP, SAP, GAP, STAP, RSAP, SGP, GGP,
STGP, RSGP, RFS, SIO, GIO, SAC, SCO, GCO, CCO, UF0, UF1, UF2, UF3, UF4, UF5, UF6, and UF7.
There are also special commands that are only available in ASCII mode:
BIN: This command quits ASCII mode and returns to binary TMCL
RUN: This command can be used to start a TMCL
STOP: Stops a running TMCL
TM
application.
TM
program in memory.
TM
mode.
6.6.4 Configuring the ASCII interface
The module can be configured so that it starts up either in binary mode or in ASCII mode. Global
parameter 67 is used for this purpose (please see also chapter 8.1). Bit 0 determines the startup mode: If
this bit is set, the module starts up in ASCII mode, else it will start up in binary mode (default). Bit 4 and
Bit 5 determine how the characters that are entered are echoed back. Normally, both bits are set to zero. In
this case every character that is entered is echoed back when the module is addressed. A Character can also
be erased using the backspace character (press the backspace key in a terminal program). When bit 4 is set
and bit 5 is clear the characters that are entered are not echoed back immediately but the entire line will be
echoed back after the <CR> character has been sent. When bit 5 is set and bit 4 is clear there will be no
echo, only the reply will be sent. This may be useful in RS485 systems.
With this command the motor will be instructed to rotate with a specified velocity (opposite direction
compared to ROR, decreasing the position counter).
Internal function: First, velocity mode is selected. Then, the velocity value is transferred to axis parameter
#0 (target velocity).
The module is based on the TMC428 motor controller and the TMC249 power driver. This makes possible
choosing a velocity between 0 and 2047.
Related commands: ROR, MST, SAP, GAP
Mnemonic: ROL 0, <velocity>
Binary representation:
*motor number is always O as only one motor is involved
With this command the motor will be instructed to stop with deceleration ramp (soft stop). For information
about hard stops refer to chapter 9 (hints and tips) please.
Internal function: The axis parameter target velocity is set to zero.
Related commands: ROL, ROR, SAP, GAP
Mnemonic: MST 0
Binary representation:
*motor number is always O as only one motor is involved
With this command the motor will be instructed to move to a specified relative or absolute position or a
pre-programmed coordinate. It will use the acceleration/deceleration ramp and the positioning speed
programmed into the unit. This command is non-blocking – that is, a reply will be sent immediately after
command interpretation and initialization of the motion controller. Further commands may follow without
waiting for the motor reaching its end position. The maximum velocity and acceleration are defined by axis
parameters #4 and #5.
Three operation types are available:
Moving to an absolute position in the range from - 8388608 to +8388607 (-2
Starting a relative movement by means of an offset to the actual position. In this case, the new
resulting position value must not exceed the above mentioned limits, too.
Moving the motor to a (previously stored) coordinate (refer to SCO for details).
Please note, that the distance between the actual position and the new one should not be more than
8388607 microsteps. Otherwise the motor will run in the wrong direction for taking a shorter way. If
the value is exactly 8388608 the motor maybe stops.
Internal function: A new position value is transferred to the axis parameter #2 target position.
The desired position in position mode (see ramp
mode, no. 138).
2
23
1
actual position
The current position of the motor. Should only be overwritten for reference point setting.
223
2
target (next) speed
The desired speed in velocity mode (see ramp
mode, no. 138). In position mode, this parameter is
set by hardware: to the maximum speed during
acceleration, and to zero during deceleration and
rest.
2047
3
actual speed
The current rotation speed.
2047
4
maximum positioning
speed
Should not exceed the physically highest possible
value. Adjust the pulse divisor (no. 154), if the
speed value is very low (<50) or above the upper
limit. See TMC 428 datasheet (p.24) for calculation of
physical units.
0...2047
5
maximum acceleration
The limit for acceleration (and deceleration).
Changing this parameter requires re-calculation of
the acceleration factor (no. 146) and the acceleration
divisor (no.137), which is done automatically. See
TMC 428 datasheet (p.24) for calculation of physical
units.
0... 2047
6
absolute max. current
The most important motor setting, since too high
values might cause motor damage! The maximum
value is 255 (which mean 100% of the maximum
current of the module).
0..255
6.7.5 SAP (set axis parameter)
With this command most of the motion control parameters of the module can be specified. The settings will
be stored in SRAM and therefore are volatile. That is, information will be lost after power off. Please use command STAP (store axis parameter) in order to store any setting permanently.
Internal function: The parameter format is converted ignoring leading zeros (or ones for negative values).
The parameter is transferred to the correct position in the appropriate device.
Related commands: GAP, STAP, RSAP , AAP
Mnemonic: SAP <parameter number>, 0, <value>
Binary representation:
*motor number is always O as only one motor is involved
Reply in direct mode:
List of parameters, which can be used for SAP:
Please note, that for the binary representation <parameter number> has to be filled with the number
and the <value> has to be filled with a value from range.
The current limit two seconds after the motor has
stopped.
0..255
12
right limit switch disable
if set, deactivates the stop function of the right
switch
0/1
13
left limit switch disable
Deactivates the stop function of the left switch resp.
reference switch if set.
0/1
130
minimum speed
Should always be set 1 to ensure exact reaching of
the target position. Normally no need to change.
0... 2047
136
acceleration threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and 145.
Normally not needed.
0... 2047
137
acceleration divisor
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for details.
Normally no need to change.
0…13
138
ramp mode
Automatically set when using ROR, ROL, MST and
MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position
differ. Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously
and the speed will be changed with constant
(maximum) acceleration, if the parameter "target
speed" is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
0/1/2
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation speed
in the same relation:
*) The full-step setting and the half-step setting are
not optimized for use without an adapted
microstepping table. These settings just step
through the microstep table in steps of 64
respectively 32. To get real full stepping use axis
parameter 211 or load an adapted microstepping
table.
**) If the module is specified for 16 microsteps only,
switching to 32 or 64 microsteps brings an
enhancement in resolution and smoothness. The
position counter will use the full resolution, but,
however, the motor will resolve a maximum of 24
different microsteps only for the 32 or 64 microstep
units.
0…6
141
ref. switch tolerance
For three-switch mode: a position range, where an
additional switch (connected to the REFL input)
won't cause motor stop.
For referencing purposes, the exact position at
hitting of the reference switch can be captured in
this parameter. A dummy value has to be written
first to prepare caption.
223
143
max. current at rest
In contrast to the standby current, this current limit
becomes immediately active when the motor speed
reaches zero. The value represents a fraction of the
absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 –12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
0…7
144
max. current at low accel.
An optional current reduction factor, see parameters
136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
145
max. current at high
accel.
An optional current reduction factor, see parameters
136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
146
acceleration factor
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for details.
Normally no need to change.
0…128
149
soft stop flag
If cleared, the motor will stop immediately
(disregarding motor limits), when the reference or
limit switch is hit.
0/1
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in
steps of one).
0…13
154
pulse divisor
The exponent of the scaling factor for the pulse
(step) generator – should be de/incremented
carefully (in steps of one).
0…13
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left
switch is searched.
3 – Three-switch-mode: the right switch is searched
first, and then the reference switch will be
searched.
1/2/3
194
referencing search speed
For the reference search this value specifies the
search speed as a fraction of the maximum velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
0…8
195
referencing switch speed
Similar to parameter no. 194, the speed for the
switching point calibration can be selected.
If the actual velocity is above this threshold, mixed
decay will be used. This can also be set to –1 which
turns on mixed decay permanently also in the rising
part of the microstep wave. This can be used to fix
microstep errors.
0..2048
or -1
204
freewheeling
Time after which the power to the motor will be
cut when its velocity has reached zero
0..65535
0 = never
205
Stall Detection Threshold
Stall detection threshold. Only usable on modules
equipped with TMC246 or TMC249 motor drivers. Set
it to 0 for no stall detection or to a value between
1 (low threshold) and 7 (high threshold). The motor
will be stopped if the load value exceeds the stall
detection threshold. Switch off mixed decay to get
usable results.
0..7
209
Encoder Position
Position of motor axis within one rotation
0..255
210
encoder prescaler
Prescaler for the encoder (since firmware version
3.38). For more information refer to 9.2 please.
211
Fullstep Threshold
When exceeding this speed the driver will switch to
real full step mode. To disable this feature set this
parameter to zero or to a value greater than 2047.
Setting a full step threshold allows higher motor
torque of the motor at higher velocity. When
experimenting with this in a given application, try
to reduce the motor current in order to be able to
reach a higher motor velocity!
0..2048
214
power down delay
Standstill period before the current is changed
down to standby current. The standard value is
200msec.
from
10msec
on
Please use theTMCL-IDE axis parameter calculation tool for getting best values.
Example:
Set the absolute maximum current of motor to 200mA
The desired position in position mode (see ramp mode,
no. 138).
2
23
1
actual position
The current position of the motor. Should only be overwritten for reference point setting.
223
2
target (next) speed
The desired speed in velocity mode (see ramp mode, no.
138). In position mode, this parameter is set by
hardware: to the maximum speed during acceleration,
and to zero during deceleration and rest.
2047
3
actual speed
The current rotation speed.
2047
4
maximum positioning
speed
Should not exceed the physically highest possible value.
Adjust the pulse divisor (no. 154), if the speed value is
very low (<50) or above the upper limit. See TMC 428
datasheet (p.24) for calculation of physical units.
0...2047
5
maximum acceleration
The limit for acceleration (and deceleration). Changing
this parameter requires re-calculation of the acceleration
factor (no. 146) and the acceleration divisor (no.137),
which is done automatically. See TMC 428 datasheet
(p.24) for calculation of physical units.
0... 2047
6
absolute max. current
The most important motor setting, since too high values
might cause motor damage! The maximum value is 255
(which mean 100% of the maximum current of the
module).
0..255
7
standby current
The current limit two seconds after the motor has
stopped.
0..255
8
target pos. reached
Indicates that the actual position equals the target
position.
0/1
6.7.6 GAP (get axis parameter)
Most parameters of the PDX-113-57/60-SE can be adjusted individually for the axis. With this parameter they
can be read out. In stand-alone mode the requested value is also transferred to the accumulator register for
further processing purposes (such as conditioned jumps). In direct mode the value read is only put out in
the value field of the reply (without affecting the accumulator).
Internal function: The parameter is read out of the correct position in the appropriate device. The parameter
format is converted adding leading zeros (or ones for negative values).
Related commands: SAP, STAP, AAP, RSAP
Mnemonic: GAP <parameter number>, 0
Binary representation:
*motor number is always O as only one motor is involved
Reply in direct mode:
List of parameters, which can be used for GAP:
Please note, that for the binary representation <parameter number> has to be filled with the number
and the <value> has to be filled with a value from range.
The logical state of the reference (left) switch.
See the TMC 428 data sheet for the different switch
modes. Default is two switch modes: the left switch as
the reference switch, the right switch as a limit (stop)
switch.
0/1
10
right limit switch status
The logical state of the (right) limit switch.
0/1
11
left limit switch status
The logical state of the left limit switch (in three switch
mode)
0/1
12
right limit switch disable
if set, deactivates the stop function of the right switch
0/1
13
left limit switch disable
Deactivates the stop function of the left switch resp.
reference switch if set.
0/1
130
minimum speed
Should always be set 1 to ensure exact reaching of the
target position. Do not change!
0... 2047
135
actual acceleration
The current acceleration (read only).
0... 2047
136
acceleration threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and 145.
Normally not needed.
0... 2047
137
acceleration divisor
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
0…13
138
ramp mode
Automatically set when using ROR, ROL, MST and MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position differ.
Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously and
the speed will be changed with constant (maximum)
acceleration, if the parameter "target speed" is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
0/1/2
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation speed in
the same relation:
*) The full-step setting and the half-step setting are not
optimized for use without an adapted microstepping
table. These settings just step through the microstep
table in steps of 64 respectively 32. To get real full
stepping use axis parameter 211 or load an adapted
microstepping table.
**) If the module is specified for 16 microsteps only,
switching to 32 or 64 microsteps brings an enhancement
in resolution and smoothness. The position counter will
use the full resolution, but, however, the motor will
resolve a maximum of 24 different microsteps only for
the 32 or 64 microstep units.
For three-switch mode: a position range, where an
additional switch (connected to the REFL input) won't
cause motor stop.
0...4095
142
snapshot position
For referencing purposes, the exact position at hitting of
the reference switch can be captured in this parameter. A
dummy value has to be written first to prepare caption.
223
143
max. current at rest
In contrast to the standby current, this current limit
becomes immediately active when the motor speed
reaches zero. The value represents a fraction of the
absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 – 12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
0…7
144
max. current at low accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
145
max. current at high
accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
146
acceleration factor
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
0…128
149
soft stop flag
If cleared, the motor will stop immediately (disregarding
motor limits), when the reference or limit switch is hit.
0/1
151
position latch flag
Indicates that a position snapshot has been completed
(see parameter 142).
0/1
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in steps
of one).
0…13
154
pulse divisor
The exponent of the scaling factor for the pulse (step)
generator – should be de/incremented carefully (in steps
of one).
0…13
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left switch
is searched.
3 – Three-switch-mode: the right switch is searched first,
and then the reference switch will be searched.
1/2/3
194
referencing search speed
For the reference search this value specifies the search
speed as a fraction of the maximum velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
0…8
195
referencing switch speed
Similar to parameter no. 194, the speed for the switching
point calibration can be selected.
If the actual velocity is above this threshold, mixed decay
will be used. This can also be set to –1 which turns on
mixed decay permanently also in the rising part of the
microstep wave. This can be used to fix microstep errors.
0..2048
or -1
204
freewheeling
Time after which the power to the motor will be cut
when its velocity has reached zero
0..65535
0 = never
205
Stall Detection Threshold
Stall detection threshold. Only usable on modules
equipped with TMC246 or TMC249 motor drivers. Set it to
0 for no stall detection or to a value between 1 (low
threshold) and 7 (high threshold). The motor will be
stopped if the load value exceeds the stall detection
threshold. Switch off mixed decay to get usable results.
0..7
206
Actual Load Value
Readout of the actual load value used for stall detection.
0..7
208
driver error flags
TMC249 error flags.
209
Encoder Position
Position of motor axis within one rotation
0..255
210
encoder prescaler
Prescaler for the encoder (since firmware version 3.38).
For more information refer to 9.2 please.
211
Fullstep Threshold
When exceeding this speed the driver will switch to real
full step mode. To disable this feature set this parameter
to zero or to a value greater than 2047.
Setting a full step threshold allows higher motor torque
of the motor at higher velocity. When experimenting
with this in a given application, try to reduce the motor
current in order to be able to reach a higher motor
velocity!
0..2048
214
power down delay
Standstill period before the current is changed down to
standby current. The standard value is 200msec.
Should not exceed the physically highest possible
value. Adjust the pulse divisor (no. 154), if the
speed value is very low (<50) or above the upper
limit. See TMC 428 datasheet (p.24) for calculation
of physical units.
5
maximum acceleration
The limit for acceleration (and deceleration).
Changing this parameter requires re-calculation of
the acceleration factor (no. 146) and the
acceleration divisor (no.137), which is done
automatically. See TMC 428 datasheet (p.24) for
calculation of physical units.
6
absolute max. current
The most important motor setting, since too high
values might cause motor damage! The maximum
value is 255 (which mean 100% of the maximum
current of the module).
7
standby current
The current limit two seconds after the motor has
stopped.
12
right limit switch
disable
if set, deactivates the stop function of the right
switch
13
left limit switch
disable
Deactivates the stop function of the left switch
resp. reference switch if set.
130
minimum speed
Should always be set 1 to ensure exact reaching
of the target position. Normally no need to change!
136
acceleration threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and
145. Normally not needed.
6.7.7 STAP (store axis parameter)
An axis parameter previously set with a Set Axis Parameter command (SAP) will be stored permanent. Most
parameters are automatically restored after power up.
Internal function: An axis parameter value stored in SRAM will be transferred to EEPROM and loaded from
EEPORM after next power up.
Related commands: SAP, RSAP, GAP, AAP
Mnemonic: STAP <parameter number>, 0
Binary representation:
*1motor number is always O as only one motor is involved
*2the value operand of this function has no effect. Instead, the currently used value (e.g. selected by SAP) is saved.
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for
details. Normally no need to change.
138
ramp mode
Automatically set when using ROR, ROL, MST and
MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position
differ. Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously
and the speed will be changed with constant
(maximum) acceleration, if the parameter "target
speed" is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation
speed in the same relation:
*) The full-step setting and the half-step setting
are not optimized for use without an adapted
microstepping table. These settings just step
through the microstep table in steps of 64
respectively 32. To get real full stepping use axis
parameter 211 or load an adapted microstepping
table.
**) If the module is specified for 16 microsteps
only, switching to 32 or 64 microsteps brings an
enhancement in resolution and smoothness. The
position counter will use the full resolution, but,
however, the motor will resolve a maximum of 24
different microsteps only for the 32 or 64
microstep units.
143
max. current at rest
In contrast to the standby current, this current
limit becomes immediately active when the motor
speed reaches zero. The value represents a fraction
of the absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 – 12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
144
max. current at low
accel.
An optional current reduction factor, see
parameters 136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
145
max. current at high
accel.
An optional current reduction factor, see
parameters 136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for
details. Normally no need to change.
149
soft stop flag
If cleared, the motor will stop immediately
(disregarding motor limits), when the reference or
limit switch is hit.
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in
steps of one).
154
pulse divisor
The exponent of the scaling factor for the pulse
(step) generator – should be de/incremented
carefully (in steps of one).
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left
switch is searched.
3 – Three-switch-mode: the right switch is
searched first, and then the reference switch will
be searched.
194
referencing search
speed
For the reference search this value specifies the
search speed as a fraction of the maximum
velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
195
referencing switch
speed
Similar to parameter no. 194, the speed for the
switching point calibration can be selected.
203
mixed decay threshold
If the actual velocity is above this threshold,
mixed decay will be used. This can also be set to
–1 which turns on mixed decay permanently also
in the rising part of the microstep wave. This can
be used to fix microstep errors.
204
freewheeling
Time after which the power to the motor will be
cut when its velocity has reached zero
205
Stall Detection
Threshold
Stall detection threshold. Only usable on modules
equipped with TMC246 or TMC249 motor drivers.
Set it to 0 for no stall detection or to a value
between 1 (low threshold) and 7 (high threshold).
The motor will be stopped if the load value
exceeds the stall detection threshold. Switch off
mixed decay to get usable results.
210
encoder prescaler
Prescaler for the encoder (since firmware version
3.38). For more information refer to 9.2 please.
211
Fullstep Threshold
When exceeding this speed the driver will switch
to real full step mode. To disable this feature set
this parameter to zero or to a value greater than
2047.
Setting a full step threshold allows higher motor
torque of the motor at higher velocity. When
experimenting with this in a given application, try
to reduce the motor current in order to be able to
reach a higher motor velocity!
Should not exceed the physically highest possible value.
Adjust the pulse divisor (no. 154), if the speed value is
very low (<50) or above the upper limit. See TMC 428
datasheet (p.24) for calculation of physical units.
5
maximum acceleration
The limit for acceleration (and deceleration). Changing
this parameter requires re-calculation of the acceleration
factor (no. 146) and the acceleration divisor (no.137),
which is done automatically. See TMC 428 datasheet
(p.24) for calculation of physical units.
6
absolute max. current
The most important motor setting, since too high values
might cause motor damage! The maximum value is 255
(which mean 100% of the maximum current of the
module).
7
standby current
The current limit two seconds after the motor has
stopped.
12
right limit switch disable
if set, deactivates the stop function of the right switch
13
left limit switch disable
Deactivates the stop function of the left switch resp.
reference switch if set.
130
minimum speed
Should always be set 1 to ensure exact reaching of the
target position. Do not change!
136
acceleration threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and 145.
Normally not needed.
137
acceleration divisor
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
6.7.8 RSAP (restore axis parameter)
For all configuration-related axis parameters non-volatile memory locations are provided. By default, most
parameters are automatically restored after power up. A single parameter that has been changed before can
be reset by this instruction also.
Internal function: The specified parameter is copied from the configuration EEPROM memory to its RAM
location.
Relate commands: SAP, STAP, GAP, and AAP
Mnemonic: RSAP <parameter number>, 0
Binary representation:
*motor number is always O as only one motor is involved
Automatically set when using ROR, ROL, MST and MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position differ.
Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously and
the speed will be changed with constant (maximum)
acceleration, if the parameter "target speed" is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation speed in
the same relation:
*) The full-step setting and the half-step setting are not
optimized for use without an adapted microstepping
table. These settings just step through the microstep
table in steps of 64 respectively 32. To get real full
stepping use axis parameter 211 or load an adapted
microstepping table.
**) If the module is specified for 16 microsteps only,
switching to 32 or 64 microsteps brings an enhancement
in resolution and smoothness. The position counter will
use the full resolution, but, however, the motor will
resolve a maximum of 24 different microsteps only for
the 32 or 64 microstep units.
143
max. current at rest
In contrast to the standby current, this current limit
becomes immediately active when the motor speed
reaches zero. The value represents a fraction of the
absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 – 12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
144
max. current at low accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
145
max. current at high
accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
146
acceleration factor
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
149
soft stop flag
If cleared, the motor will stop immediately (disregarding
motor limits), when the reference or limit switch is hit.
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in steps
of one).
The exponent of the scaling factor for the pulse (step)
generator – should be de/incremented carefully (in steps
of one).
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left switch
is searched.
3 – Three-switch-mode: the right switch is searched first,
and then the reference switch will be searched.
194
referencing search speed
For the reference search this value specifies the search
speed as a fraction of the maximum velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
195
referencing switch speed
Similar to parameter no. 194, the speed for the switching
point calibration can be selected.
203
mixed decay threshold
If the actual velocity is above this threshold, mixed decay
will be used. This can also be set to –1 which turns on
mixed decay permanently also in the rising part of the
microstep wave. This can be used to fix microstep errors.
204
freewheeling
Time after which the power to the motor will be cut
when its velocity has reached zero
205
Stall Detection Threshold
Stall detection threshold. Only usable on modules
equipped with TMC246 or TMC249 motor drivers. Set it to
0 for no stall detection or to a value between 1 (low
threshold) and 7 (high threshold). The motor will be
stopped if the load value exceeds the stall detection
threshold. Switch off mixed decay to get usable results.
210
encoder prescaler
Prescaler for the encoder (since firmware version 3.38).
For more information refer to 9.2 please.
211
Fullstep Threshold
When exceeding this speed the driver will switch to real
full step mode. To disable this feature set this parameter
to zero or to a value greater than 2047.
Setting a full step threshold allows higher motor torque
of the motor at higher velocity. When experimenting
with this in a given application, try to reduce the motor
current in order to be able to reach a higher motor
velocity!
214
power down delay
Standstill period before the current is changed down to
standby current. The standard value is 200msec.
Setting this parameter to a different value as $E4 will
cause re-initialization of the axis and global
parameters (to factory defaults) after the next power
up. This is useful in case of miss-configuration.
0…255
65
RS232/RS485 baud rate
0
9600 baud (default)
1
14400 baud
2 19200 baud
3
28800 baud
4
38400 baud
5 57600 baud
6
76800 baud
Not supported by Windows!
7
(115200 baud)
0…7
66
Serial address
The module (target) address for RS-232/RS-485.
0…255
67
ASCII mode
Configure the TMCLTM ASCII interface:
Bit 0: 0 – start up in binary (normal) mode
1 – start up in ASCII mode
Bits 4 and 5:
00 – Echo back each character
01 – Echo back complete command
10 – Do not send echo, only send command reply
73
Configuration EEPROM
lock flag
Write: 1234 to lock the EEPROM, 4321 to unlock it.
Read: 1=EEPROM locked, 0=EEPROM unlocked.
0/1
6.7.9 SGP (set global parameter)
With this command most of the module specific parameters not directly related to motion control can be
specified and the TMCLTM user variables can be changed. Global parameters are related to the host interface,
peripherals or application specific variables. The different groups of these parameters are organized in
"banks" to allow a larger total number for future products. Currently, only bank 0 and 1 are used for global
parameters, and bank 2 is used for user variables.
All module settings will automatically be stored non-volatile (internal EEPROM of the processor). The
TMCLTM user variables will not be stored in the EEPROM automatically, but this can be done by using
STGP commands.
Internal function: the parameter format is converted ignoring leading zeros (or ones for negative values).
The parameter is transferred to the correct position in the appropriate (on board) device.
Pause time before the reply via RS232 or RS485 is
sent. For RS232 set to 0.
For RS485 it is often necessary to set it to 15 (for
RS485 adapters controlled by the RTS pin).
For CAN interface this parameter has no effect!
0…255
76
Serial host address
Host address used in the reply telegrams sent back
via RS232 or RS485.
0..255
77
Auto start mode
0: Do not start TMCLTM application after power up
(default).
1: Start TMCLTM application automatically after power
up.
0/1
80
Shutdown pin
functionality
Select the functionality of the SHUTDOWN pin
0 – no function
1 – high active
2 – low active
0..2
81
TMCLTM code protection
Protect a TMCLTM program against disassembling or
overwriting.
0 – no protection
1 – protection against disassembling
2 – protection against overwriting
3 – protection against disassembling and overwriting
If you switch off the protection against
disassembling, the program will be erased first!
Changing this value from 1 or 3 to 0 or 2, the
TMCLTM program will be wiped off.
0,1,2,3
132
Tick timer
A 32 bit counter that gets incremented by one every
millisecond. It can also be reset to any start value.
Global parameters of bank 1, which can be used for SGP:
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Global parameters of bank 2, which can be used for SGP:
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
Setting this parameter to a different value as $E4 will
cause re-initialization of the axis and global parameters
(to factory defaults) after the next power up. This is
useful in case of miss-configuration.
0…255
65
RS232/RS485 baud rate
0
9600 baud (default)
1
14400 baud
2 19200 baud
3
28800 baud
4
38400 baud
5 57600 baud
6
76800 baud
Not supported by Windows!
7
(115200 baud)
0…11
66
Serial address
The module (target) address for RS-232/RS-485.
0…255
67
ASCII mode
Configure the TMCLTM ASCII interface:
Bit 0: 0 – start up in binary (normal) mode
1 – start up in ASCII mode
Bits 4 and 5:
00 – Echo back each character
01 – Echo back complete command
10 – Do not send echo, only send command reply
73
Configuration EEPROM
lock flag
Write: 1234 to lock the EEPROM, 4321 to unlock it.
Read: 1=EEPROM locked, 0=EEPROM unlocked.
0/1
75
Telegram pause time
Pause time before the reply via RS232 or RS485 is sent.
For RS232 set to 0.
For RS485 it is often necessary to set it to 15 (for RS485
adapters controlled by the RTS pin).
For CAN interface this parameter has no effect!
0…255
76
Serial host address
Host address used in the reply telegrams sent back via
RS232 or RS485.
0..255
6.7.10 GGP (get global parameter)
All global parameters can be read with this function. Global parameters are related to the host interface,
peripherals or application specific variables. The different groups of these parameters are organized in
"banks" to allow a larger total number for future products. Currently, only bank 0 and 1 are used for global
parameters, and bank 2 is used for user variables. Please refer to chapter 0 for a complete parameter list.
Internal function: The parameter is read out of the correct position in the appropriate device. The parameter
format is converted adding leading zeros (or ones for negative values).
Related commands: SGP, STGP, RSGP, AGP
Mnemonic: GGP <parameter number>, <bank number>
Binary representation:
Reply in direct mode:
Global parameters of bank 0, which can be used for GGP:
0: Do not start TMCLTM application after power up
(default).
1: Start TMCLTM application automatically after power up.
0/1
80
Shutdown pin
functionality
Select the functionality of the SHUTDOWN pin
0 – no function
1 – high active
2 – low active
0..2
81
TMCLTM code protection
Protect a TMCLTM program against disassembling or
overwriting.
0 – no protection
1 – protection against disassembling
2 – protection against overwriting
3 – protection against disassembling and overwriting
If you switch off the protection against
disassembling, the program will be erased first!
Changing this value from 1 or 3 to 0 or 2, the TMCLTM
program will be wiped off.
0,1,2,3
128
TMCLTM application
status
0 –stop
1 – run
2 – step
3 – reset
0..3
129
Download mode
0 – normal mode
1 – download mode
0/1
130
TMCLTM program
counter
The index of the currently executed TMCLTM instruction.
132
Tick timer
A 32 bit counter that gets incremented by one every
millisecond. It can also be reset to any start value.
Global parameters of bank 1, which can be used for GGP:
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Global parameters of bank 2, which can be used for GGP:
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
This command is used to store TMCLTM user variables permanently in the EEPROM of the module. Some
global parameters are located in RAM memory, so without storing modifications are lost at power down.
This instruction enables enduring storing. Most parameters are automatically restored after power up (see
the list of global parameters in chapter 0).
Internal function: The specified parameter is copied from its RAM location to the configuration EEPROM.
Related commands: SGP, GGP, RSGP, AGP
Mnemonic: STGP <parameter number>, <bank number>
Binary representation:
Reply in direct mode:
Global parameters of bank 0, which can be used for STGP:
The global parameter bank 0 is not required for the STGP command, because these parameters are
automatically stored with the SGP command in EEPROM.
Global parameters of bank 1, which can be used for STGP:
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Global parameters of bank 2, which can be used for STGP:
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
With this command the contents of a TMCLTM user variable can be restored from the EEPROM. For all
configuration-related axis parameters, non-volatile memory locations are provided. By default, most
parameters are automatically restored after power up (see axis parameter list in chapter 0). A single
parameter that has been changed before can be reset by this instruction.
Internal function: The specified parameter is copied from the configuration EEPROM memory to its RAM
location.
Relate commands: SAP, STAP, GAP, and AAP
Mnemonic: RSAP <parameter number>, 0
Binary representation:
*motor number is always O as only one motor is involved
Reply structure in direct mode:
Global parameters of bank 0, which can be used for RSGP:
The global parameter bank 0 is not required for the RSGP command, because these parameters are
automatically stored with the SGP command in EEPROM.
Global parameters of bank 1, which can be used for RSGP:
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Global parameters of bank 2, which can be used for RSGP:
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
0 START – start ref. search
1 STOP – abort ref. search
2 STATUS – get status
0*
(don't care)
STATUS
VALUE
100 – OK
(don't care)
STATUS
VALUE
100 – OK
0 – no ref. search active
other values – ref.
search is active
Byte Index
0 1 2 3 4 5 6 7 8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$0d
$00
$00
$00
$00
$00
$00
$0f
6.7.13 RFS (reference search)
The PDx-113-57/60-SE has a built-in reference search algorithm which can be used. The reference search
algorithm provides switching point calibration and three switch modes. The status of the reference search
can also be queried to see if it has already finished. (In a TMCLTM program it is better to use the WAIT
command to wait for the end of a reference search.) Please see the appropriate parameters in the axis
parameter table to configure the reference search algorithm to meet your needs (chapter7). The reference
search can be started, stopped, and the actual status of the reference search can be checked.
Internal function: The reference search is implemented as a state machine, so interaction is possible during
execution.
Related commands: WAIT
Mnemonic: RFS <START|STOP|STATUS>, 0
Binary representation:
*motor number is always O as only one motor is involved
Reply in direct mode:
When using type 0 (START) or 1 (STOP):
When using type 2 (STATUS):
Example:
Start reference search of motor 0
Mnemonic: RFS START, 0
Binary:
With this PANdrive it is possible to use stall detection instead of a reference search. Please see section
8 for details.
Set OUT_1 to high (bank 2, output 1; general purpose output)
Mnemonic: SIO 1, 2, 1
Binary:
Available I/O ports of PDx-113-57/60-SE:
Addressing both output lines with one SIO command:
Set the type parameter to 255 and the bank parameter to 2.
The value parameter must then be set to a value between 0…255, where every bit represents one
output line.
Furthermore, the value can also be set to -1. In this special case, the contents of the lower 8 bits of
the accumulator are copied to the output pins.
Example:
Set both output pins high.
Mnemonic: SIO 255, 2, 3
The following program will show the states of the input lines on the output lines:
With this command the status of the two available general purpose inputs of the module can be read out.
The function reads a digital or analogue input port. Digital lines will read 0 and 1, while the ADC channels
deliver their 10 bit result in the range of 0…1023. In stand-alone mode the requested value is copied to the
"accumulator" (accu) for further processing purposes such as conditioned jumps. In direct mode the value is
only output in the “value” field of the reply, without affecting the accumulator. The actual status of a digital
output line can also be read.
Internal function: The specified line is read.
Related commands: SIO, WAIT
Mnemonic: GIO <port number>, <bank number>
Binary representation:
Reply in direct mode:
Example:
Get the analogue value of ADC channel 1
Mnemonic: GIO 1, 1
Binary:
Reply:
value: 506
6.7.15.1 I/O bank 0 – digital inputs:
The ADIN lines can be read as digital or analogue inputs at the same time. The analogue values can
be accessed in bank 1.
Reading all digital inputs with one GIO command:
Set the type parameter to 255 and the bank parameter to 0.
In this case the status of all digital input lines will be read to the lower eight bits of the
0 ADD – add to accu
1 SUB – subtract from accu
2 MUL – multiply accu by
3 DIV – divide accu by
4 MOD – modulo divide by
5 AND – logical and accu with
6 OR – logical or accu with
7 XOR – logical exor accu with
8 NOT – logical invert accu
9 LOAD – load operand to accu
(don't care)
<operand>
Byte Index
0 1 2 3 4 5 6 7 8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$13
$02
$00
$FF
$FF
$EC
$78
$78
6.7.16 CALC (calculate)
A value in the accumulator variable, previously read by a function such as GAP (get axis parameter), can be
modified with this instruction. Nine different arithmetic functions can be chosen and one constant operand
value must be specified. The result is written back to the accumulator, for further processing like
comparisons or data transfer.
Related commands: CALCX, COMP, JC, AAP, AGP, GAP, GGP, GIO
Mnemonic: CALC <op>, <value>
where <op> is ADD, SUB, MUL, DIV, MOD, AND, OR, XOR, NOT or LOAD
The specified number is compared to the value in the accumulator register. The result of the comparison can
for example be used by the conditional jump (JC) instruction. This command is intended for use in standalone operation only.
The host address and the reply are only used to take the instruction to the TMCL™ program memory
while the program loads down. It does not make sense to use this command in direct mode.
Internal function: The specified value is compared to the internal "accumulator", which holds the value of a
preceding "get" or calculate instruction (see GAP/GGP/GIO/CALC/CALCX). The internal arithmetic status flags
are set according to the comparison result.
Related commands: JC (jump conditional), GAP, GGP, GIO, CALC, CALCX
Mnemonic: COMP <value>
Binary representation:
Example:
Jump to the address given by the label when the position of motor is greater than or equal to 1000.
GAP 1, 2, 0 //get axis parameter, type: no. 1 (actual position), motor: 0, value: 0 (don't care)
COMP 1000 //compare actual value to 1000
JC GE, Label //jump, type: 5 greater/equal, the label must be defined somewhere else in the
0 ZE - zero
1 NZ - not zero
2 EQ - equal
3 NE - not equal
4 GT - greater
5 GE - greater/equal
6 LT - lower
7 LE - lower/equal
8 ETO - time out error
9 EAL – external alarm
12 ESD – shutdown error
(don't care)
<jump address>
Byte Index
0 1 2 3 4 5 6 7 8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$15
$05
$00
$00
$00
$00
$0a
$25
6.7.18 JC (jump conditional)
The JC instruction enables a conditional jump to a fixed address in the TMCLTM program memory, if the
specified condition is met. The conditions refer to the result of a preceding comparison. Please refer to
COMP instruction for examples. This function is for stand-alone operation only.
The host address and the reply are only used to take the instruction to the TMCL™ program memory
while the program loads down. It does not make sense to use this command in direct mode. See the
host-only control functions for details.
Internal function: the TMCLTM program counter is set to the passed value if the arithmetic status flags are in
the appropriate state(s).
Related commands: JA, COMP, WAIT, CLE
Mnemonic: JC <condition>, <label>
where <condition>=ZE|NZ|EQ|NE|GT|GE|LT|LE|ETO|EAL|EDV|EPO
Binary representation:
Example:
Jump to address given by the label when the position of motor is greater than or equal to 1000.
GAP 1, 0, 0 //get axis parameter, type: no. 1 (actual position), motor: 0, value: 0 (don't care)
COMP 1000 //compare actual value to 1000
JC GE, Label //jump, type: 5 greater/equal
...
...
Label: ROL 0, 1000
Binary format of “JC GE, Label” when Label is at address 10:
Jump to a fixed address in the TMCLTM program memory. This command is intended for stand-alone
operation only.
Note that the host address and the reply is only used to transfer this instruction to the TMCLTM program
memory. This command cannot be used in direct mode.
Internal function: the TMCLTM program counter is set to the passed value.
Related commands: JC, WAIT, CSUB
Mnemonic: JA <Label>
Binary representation:
Example:
An infinite loop in TMCLTM
Loop: MVP ABS, 0, 10000
WAIT POS, 0, 0
MVP ABS, 0, 0
WAIT POS, 0, 0
JA Loop //Jump to the label “Loop”
Binary format of “JA Loop” assuming that the label “Loop” is at address 20:
This function calls a subroutine in the TMCLTM program memory. It is intended for stand-alone operation
only.
Note that the host address and the reply is only used to transfer this instruction to the TMCLTM program
memory. This command cannot be used in direct mode.
Internal function: The actual TMCLTM program counter value is saved to an internal stack, afterwards
overwritten with the passed value. The number of entries in the internal stack is limited to 8. This also
limits nesting of subroutine calls to 8. The command will be ignored if there is no more stack space left.
Related commands: RSUB, JA
Mnemonic: CSUB <Label>
Binary representation:
Example:
Call a subroutine
Loop: MVP ABS, 0, 10000
CSUB SubW //Save program counter and jump to label “SubW”
MVP ABS, 0, 0
JA Loop
SubW: WAIT POS, 0, 0
WAIT TICKS, 0, 50
RSUB //Continue with the command following the CSUB command
Binary format of the “CSUB SubW” command assuming that the label “SubW” is at address 100:
Return from a subroutine to the command after the CSUB command. This command is intended for use in
stand-alone mode only.
Note that the host address and the reply is only used to transfer this instruction to the TMCLTM program
memory. This command cannot be used in direct mode.
Internal function: The TMCL program counter is set to the last value of the stack. The command will be
ignored if the stack is empty.
Related command: CSUB
Mnemonic: RSUB
Binary representation:
Example: Please see the CSUB example (section 6.7.20).
This instruction interrupts the execution of the TMCLTM program until the specified condition is met. This
command is intended for stand-alone operation only.
Note that the host address and the reply is only used to transfer this instruction to the TMCLTM program
memory. This command is not to be used in direct mode.
There are five different wait conditions that can be used:
TICKS: Wait until the number of timer ticks specified by the <ticks> parameter has been reached.
POS: Wait until the target position of the motor specified by the <motor> parameter has been
reached. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
REFSW: Wait until the reference switch of the motor specified by the <motor> parameter has
been triggered. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
LIMSW: Wait until a limit switch of the motor specified by the <motor> parameter has been
triggered. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
RFS: Wait until the reference search of the motor specified by the <motor> field has been
reached. An optional timeout value (0 for no timeout) must be specified by the <ticks>
parameter.
The timeout flag (ETO) will be set after a timeout limit has been reached. You can then use a JC ETO
command to check for such errors or clear the error using the CLE command.
Internal function: The TMCLTM program counter is held until the specified condition is met.
Related commands: JC, CLE
Mnemonic: WAIT <condition>, 0, <ticks>
where <condition> is TICKS|POS|REFSW|LIMSW|RFS
Binary representation:
1
*
one tick is 10 milliseconds (in standard firmware)
*2 motor number is always O as only one motor is involved
Example:
wait for motor 0 to reach its target position, without timeout
Up to 20 position values (coordinates) can be stored for every axis for use with the MVP COORD command.
This command sets a coordinate to a specified value.
Please note that the coordinate number 0 is always stored in RAM only. All others are also stored in
the EEPROM.
Internal function: The passed value is stored in the internal position array.
Related commands: GCO, CCO, MVP
Mnemonic: SCO <coordinate number>, 0, <position>
Binary representation:
* motor number is always 0 as only one motor is involved
This command makes possible to read out a previously stored coordinate. In stand-alone mode the
requested value is copied to the accumulator register for further processing purposes such as conditioned
jumps. In direct mode, the value is only output in the value field of the reply, without affecting the
accumulator.
Please note that the coordinate number 0 is always stored in RAM only. All others are also stored in
the EEPROM.
Internal function: The desired value is read out of the internal coordinate array, copied to the accumulator
register and -in direct mode- returned in the value field of the reply.
Related commands: SCO, CCO, MVP
Mnemonic: GCO <coordinate number>, 0
Binary representation:
* motor number is always 0 as only one motor is involved
0 ADD – add X register to accu
1 SUB – subtract X register from accu
2 MUL – multiply accu by X register
3 DIV – divide accu by X-register
4 MOD – modulo divide accu by x-register
5 AND – logical and accu with X-register
6 OR – logical or accu with X-register
7 XOR – logical exor accu with X-register
8 NOT – logical invert X-register
9 LOAD – load accu to X-register
10 SWAP – swap accu with X-register
(don't care)
(don't care)
Byte Index
0 1 2 3 4 5 6 7 8
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Checksum
Value (hex)
$01
$21
$02
$00
$00
$00
$00
$00
$24
6.7.27 CALCX (calculate using the X register)
This instruction is very similar to CALC, but the second operand comes from the X register. The X register
can be loaded with the LOAD or the SWAP type of this instruction. The result is written back to the
accumulator for further processing like comparisons or data transfer.
Related commands: CALC, COMP, JC, AAP, AGP
Mnemonic: CALCX <operation>
with <operation>=ADD|SUB|MUL|DIV|MOD|AND|OR|XOR|NOT|LOAD|SWAP
The desired position in position mode (see ramp mode,
no. 138).
1
actual position
The current position of the motor. Should only be overwritten for reference point setting.
2
target (next) speed
The desired speed in velocity mode (see ramp mode, no.
138). In position mode, this parameter is set by
hardware: to the maximum speed during acceleration,
and to zero during deceleration and rest.
3
actual speed
The current rotation speed.
4
maximum positioning
speed
Should not exceed the physically highest possible value.
Adjust the pulse divisor (no. 154), if the speed value is
very low (<50) or above the upper limit. See TMC 428
datasheet (p.24) for calculation of physical units.
5
maximum acceleration
The limit for acceleration (and deceleration). Changing
this parameter requires re-calculation of the acceleration
factor (no. 146) and the acceleration divisor (no.137),
which is done automatically. See TMC 428 datasheet
(p.24) for calculation of physical units.
6
absolute max. current
The most important motor setting, since too high values
might cause motor damage! The maximum value is 255
(which mean 100% of the maximum current of the
module).
7
standby current
The current limit two seconds after the motor has
stopped.
12
right limit switch disable
if set, deactivates the stop function of the right switch
13
left limit switch disable
Deactivates the stop function of the left switch resp.
reference switch if set.
130
minimum speed
Should always be set 1 to ensure exact reaching of the
target position. Do not change!
136
acceleration threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and 145.
Normally not needed.
6.7.28 AAP (accumulator to axis parameter)
The content of the accumulator register is transferred to the specified axis parameter. For practical usage,
the accumulator has to be loaded e.g. by a preceding GAP instruction. The accumulator may have been
modified by the CALC or CALCX (calculate) instruction.
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
138
ramp mode
Automatically set when using ROR, ROL, MST and MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position differ.
Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously and
the speed will be changed with constant (maximum)
acceleration, if the parameter "target speed" is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation speed in
the same relation:
*) The full-step setting and the half-step setting are not
optimized for use without an adapted microstepping
table. These settings just step through the microstep
table in steps of 64 respectively 32. To get real full
stepping use axis parameter 211 or load an adapted
microstepping table.
**) If the module is specified for 16 microsteps only,
switching to 32 or 64 microsteps brings an enhancement
in resolution and smoothness. The position counter will
use the full resolution, but, however, the motor will
resolve a maximum of 24 different microsteps only for
the 32 or 64 microstep units.
141
ref. switch tolerance
For three-switch mode: a position range, where an
additional switch (connected to the REFL input) won't
cause motor stop.
142
snapshot position
For referencing purposes, the exact position at hitting of
the reference switch can be captured in this parameter. A
dummy value has to be written first to prepare caption.
143
max. current at rest
In contrast to the standby current, this current limit
becomes immediately active when the motor speed
reaches zero. The value represents a fraction of the
absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 – 12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
144
max. current at low accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
145
max. current at high
accel.
An optional current reduction factor, see parameters 136
and 143 for details. Normally not used, use parameters 6 and 7 instead!
A ramping parameter, can be adjusted in special cases,
automatically calculated by setting the maximum
acceleration (e.g. during normal initialization). See the
TMC428 data sheet for details. Normally no need to change.
147
ref. switch disable flag
If set, the reference switch (left switch) won't cause the
motor to stop. See parameters 12 and 13.
148
limit switch disable flag
If set, the limit switch (right switch) won't cause the
motor to stop. See parameters 12 and 13.
149
soft stop flag
If cleared, the motor will stop immediately (disregarding
motor limits), when the reference or limit switch is hit.
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in steps
of one).
154
pulse divisor
The exponent of the scaling factor for the pulse (step)
generator – should be de/incremented carefully (in steps
of one).
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left switch
is searched.
3 – Three-switch-mode: the right switch is searched first,
and then the reference switch will be searched.
194
referencing search speed
For the reference search this value specifies the search
speed as a fraction of the maximum velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
195
referencing switch speed
Similar to parameter no. 194, the speed for the switching
point calibration can be selected.
203
mixed decay threshold
If the actual velocity is above this threshold, mixed decay
will be used. This can also be set to –1 which turns on
mixed decay permanently also in the rising part of the
microstep wave. This can be used to fix microstep errors.
204
freewheeling
Time after which the power to the motor will be cut
when its velocity has reached zero
205
Stall Detection Threshold
Stall detection threshold. Only usable on modules
equipped with TMC246 or TMC249 motor drivers. Set it to
0 for no stall detection or to a value between 1 (low
threshold) and 7 (high threshold). The motor will be
stopped if the load value exceeds the stall detection
threshold. Switch off mixed decay to get usable results.
209
Encoder Position
Position of motor axis within one rotation
210
encoder prescaler
Prescaler for the encoder (since firmware version 3.38).
For more information refer to 9.2 please.
211
Fullstep Threshold
When exceeding this speed the driver will switch to real
full step mode. To disable this feature set this parameter
to zero or to a value greater than 2047.
Setting a full step threshold allows higher motor torque
of the motor at higher velocity. When experimenting
with this in a given application, try to reduce the motor
current in order to be able to reach a higher motor
velocity!
Setting this parameter to a different value as $E4 will
cause re-initialization of the axis and global parameters
(to factory defaults) after the next power up. This is
useful in case of miss-configuration.
65
RS232/RS485 baud rate
0
9600 baud (default)
1
14400 baud
2 19200 baud
3
28800 baud
4
38400 baud
5 57600 baud
6
76800 baud
Not supported by Windows!
7
(115200 baud)
66
Serial address
The module (target) address for RS-232/RS-485.
67
ASCII mode
Configure the TMCLTM ASCII interface:
Bit 0: 0 – start up in binary (normal) mode
1 – start up in ASCII mode
Bits 4 and 5:
00 – Echo back each character
01 – Echo back complete command
10 – Do not send echo, only send command reply
The CAN ID for replies from the board (default: 2)
71
CAN ID
The module (target) address for CAN (default: 1)
73
Configuration EEPROM
lock flag
Write: 1234 to lock the EEPROM, 4321 to unlock it.
Read: 1=EEPROM locked, 0=EEPROM unlocked.
6.7.29 AGP (accumulator to global parameter)
The content of the accumulator register is transferred to the specified global parameter. For practical usage,
the accumulator has to be loaded e.g. by a preceding GAP instruction. The accumulator may have been
modified by the CALC or CALCX (calculate) instruction. Note that the global parameters in bank 0 are EEPROM-only and thus should not be modified automatically by a stand-alone application. (See chapter
0 for a complete list of global parameters).
Related commands: AAP, SGP, GGP, SAP, GAP, GIO
Mnemonic: AGP <parameter number>, <bank number>
Binary representation:
Reply in direct mode:
Global parameters of bank 0, which can be used for AGP:
Pause time before the reply via RS232 or RS485 is sent.
For RS232 set to 0.
For RS485 it is often necessary to set it to 15 (for RS485
adapters controlled by the RTS pin).
For CAN interface this parameter has no effect!
76
Serial host address
Host address used in the reply telegrams sent back via
RS232 or RS485.
77
Auto start mode
0: Do not start TMCLTM application after power up
(default).
1: Start TMCLTM application automatically after power up.
80
Shutdown pin
functionality
Select the functionality of the SHUTDOWN pin
0 – no function
1 – high active
2 – low active
81
TMCLTM code protection
Protect a TMCLTM program against disassembling or
overwriting.
0 – no protection
1 – protection against disassembling
2 – protection against overwriting
3 – protection against disassembling and overwriting
If you switch off the protection against
disassembling, the program will be erased first!
Changing this value from 1 or 3 to 0 or 2, the TMCLTM
program will be wiped off.
132
Tick timer
A 32 bit counter that gets incremented by one every
millisecond. It can also be reset to any start value.
Global parameters of bank 1, which can be used for AGP:
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Global parameters of bank 2, which can be used for AGP:
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
The user definable functions UF0 through UF7 are predefined, "empty" functions for user specific purposes.
Contact TRINAMIC for customer specific programming of these functions.
Internal function: Call user specific functions implemented in C by TRINAMIC.
This command is the only exception to the TMCLTM protocol, as it sends two replies: One immediately after
the command has been executed (like all other commands also), and one additional reply that will be sent
when the motor has reached its target position. This instruction can only be used in direct mode (in
stand-alone mode, it is covered by the WAIT command) and hence does not have a mnemonic.
Internal function: Send an additional reply when the motor has reached its target position
Mnemonic: ---
Binary representation:
* motor number
Reply in direct mode (right after execution of this command):
Additional reply in direct mode (after motors have reached their target positions):
a running TMCLTM standalone
application is stopped
(don't care)
(don't care)
(don't care)
129 – run application
TMCLTM execution is started (or
continued)
0 - run from
current address
1 - run from
specified address
(don't care)
(don't care)
starting address
130 – step application
only the next command of a
TMCLTM application is executed
(don't care)
(don't care)
(don't care)
131 – reset application
the program counter is set to
zero, and the standalone
application is stopped (when
running or stepped)
(don't care)
(don't care)
(don't care)
132 – start download
mode
target command execution is
stopped and all following
commands are transferred to
the TMCLTM memory
(don't care)
(don't care)
starting address of
the application
133 – quit download
mode
target command execution is
resumed
(don't care)
(don't care)
(don't care)
134 – read TMCLTM
memory
the specified program memory
location is read
(don't care)
(don't care)
<memory address>
135 – get application
status
one of these values is
returned:
0 – stop
1 – run
2 – step
3 – reset
(don't care)
(don't care)
(don't care)
136 – get firmware
version
return the module type and
firmware revision either as a
string or in binary format
0 – string
1 – binary
(don’t care)
(don’t care)
137 – restore factory
settings
reset all settings stored in the
EEPROM to their factory
defaults
This command does not send
back a reply.
(don’t care)
(don’t care)
must be 1234
138 – reserved
139 – enter ASCII
mode
Enter ASCII command line (see
chapter 6.6)
(don’t care)
(don’t care)
(don’t care)
6.7.34 TMCL
The following functions are for host control purposes only and are not allowed for stand-alone mode.
In most cases, there is no need for the customer to use one of those functions (except command 139).
They are mentioned here only for reasons of completeness. These commands have no mnemonics, as they
cannot be used in TMCLTM programs. The Functions are to be used only by the TMCL-IDE to communicate
with the module, for example to download a TMCLTM application into the module.
The only control commands that could be useful for a user host application are:
get firmware revision (command 136, please note the special reply format of this command,
run application (command 129)
All other functions can be achieved by using the appropriate functions of the TMCL-IDE.
The desired position in position mode (see ramp
mode, no. 138).
2
23
[µsteps]
RW
1
actual position
The current position of the motor. Should only be overwritten for reference point setting.
2
23
[µsteps]
RW
2
target (next) speed
The desired speed in velocity mode (see ramp
mode, no. 138). In position mode, this parameter is
set by hardware: to the maximum speed during
acceleration, and to zero during deceleration and
rest.
2047
16MHz
65536
2
PD
steps
sec
RW
3
actual speed
The current rotation speed.
2047
16MHz
65536
2
PD
steps
sec
RW
4
maximum positioning
speed
Should not exceed the physically highest possible
value. Adjust the pulse divisor (no. 154), if the
speed value is very low (<50) or above the upper
limit. See TMC 428 datasheet (p.24) for calculation
of physical units.
0...2047
16MHz
65536
2
PD
steps
sec
RWE
5
maximum
acceleration
The limit for acceleration (and deceleration).
Changing this parameter requires re-calculation of
the acceleration factor (no. 146) and the
acceleration divisor (no.137), which is done
automatically. See TMC 428 datasheet (p.24) for
calculation of physical units.
0... 2047
16MHz
65536
2
PD
steps
sec
RWE
6
absolute max. current
The most important motor setting, since too high
values might cause motor damage! The maximum
value is 255 (which mean 100% of the maximum
current of the module).
0..255
max. module current
255
RWE
7
standby current
The current limit two seconds after the motor has
stopped.
0..255
max. module current
255
RWE
8
target pos. reached
Indicates that the actual position equals the target
position.
0/1
R
9
ref. switch status
The logical state of the reference (left) switch.
See the TMC 428 data sheet for the different switch
modes. Default is two switch modes: the left
switch as the reference switch, the right switch as
a limit (stop) switch.
0/1
R
10
right limit switch
status
The logical state of the (right) limit switch.
0/1
R
11
left limit switch
status
The logical state of the left limit switch (in three
switch mode)
0/1 R 12
right limit switch
disable
if set, deactivates the stop function of the right
switch
0/1
RWE
13
left limit switch
disable
Deactivates the stop function of the left switch
resp. reference switch if set.
0/1
RWE
7 Axis parameters
The following section describes all axis parameters that can be used with the SAP, GAP, AAP, STAP and RSAP
commands.
Meaning of the letters in column Access:
R = readable (GAP)
W = writable (SAP)
E = automatically restored from EEPROM after reset or power-on
Should always be set 1 to ensure exact reaching of
the target position. Do not change!
0... 2047
max. module current
255
RWE
135
actual acceleration
The current acceleration (read only).
0... 2047*
R
136
acceleration
threshold
Specifies the threshold between low and high
acceleration values for the parameters 144 and 145.
Normally not needed.
0... 2047
RWE
137
acceleration divisor
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for
details. Normally no need to change.
0…13
RWE
138
ramp mode
Automatically set when using ROR, ROL, MST and
MVP.
0: position mode. Steps are generated, when the
parameters actual position and target position
differ. Trapezoidal speed ramps are provided.
2: velocity mode. The motor will run continuously
and the speed will be changed with constant
(maximum) acceleration, if the parameter target speed is changed.
For special purposes, the soft mode (value 1) with
exponential decrease of speed can be selected.
0/1/2
RWE
140
microstep resolution
0 – full step *)
1 – half step *)
2 – 4 microsteps
3 – 8 microsteps
4 – 16 microsteps
5 - 32 microsteps**)
6 – 64 microsteps**)
Modifying this parameter effects the rotation speed
in the same relation:
*) The full-step setting and the half-step setting are
not optimized for use without an adapted
microstepping table. These settings just step
through the microstep table in steps of 64
respectively 32. To get real full stepping use axis
parameter 211 or load an adapted microstepping
table.
**) If the module is specified for 16 microsteps
only, switching to 32 or 64 microsteps brings an
enhancement in resolution and smoothness. The
position counter will use the full resolution, but,
however, the motor will resolve a maximum of 24
different microsteps only for the 32 or 64 microstep
units.
0…6
RWE
141
ref. switch tolerance
For three-switch mode: a position range, where an
additional switch (connected to the REFL input)
won't cause motor stop.
0...4095
[µsteps]
RW
142
snapshot position
For referencing purposes, the exact position at
hitting of the reference switch can be captured in
this parameter. A dummy value has to be written
first to prepare caption.
In contrast to the standby current, this current limit
becomes immediately active when the motor speed
reaches zero. The value represents a fraction of the
absolute maximum current:
0 – no change of current at rest (default, 100%)
1…7 – 12.5% …87.5%
See the TMC428 datasheet for details. Normally not used, use parameters 6 and 7 instead!
0…7
RWE
144
max. current at low
accel.
An optional current reduction factor, see
parameters 136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
RWE
145
max. current at high
accel.
An optional current reduction factor, see
parameters 136 and 143 for details. Normally not used, use parameters 6 and 7 instead!
0…7
RWE
146
acceleration factor
A ramping parameter, can be adjusted in special
cases, automatically calculated by setting the
maximum acceleration (e.g. during normal
initialization). See the TMC428 data sheet for
details. Normally no need to change.
0…128
RWE
149
soft stop flag
If cleared, the motor will stop immediately
(disregarding motor limits), when the reference or
limit switch is hit.
0/1
RWE
151
position latch flag
Indicates that a position snapshot has been
completed (see parameter 142).
0/1
R
153
ramp divisor
The exponent of the scaling factor for the ramp
generator- should be de/incremented carefully (in
steps of one).
0…13
RWE
154
pulse divisor
The exponent of the scaling factor for the pulse
(step) generator – should be de/incremented
carefully (in steps of one).
0…13
RWE
193
referencing mode
1 – Only the left reference switch is searched.
2 – The right switch is searched, and then the left
switch is searched.
3 – Three-switch-mode: the right switch is searched
first, and then the reference switch will be
searched.
1/2/3
RWE
194
referencing search
speed
For the reference search this value specifies the
search speed as a fraction of the maximum
velocity:
0 – full speed
1 – half of the maximum speed
2 – a quarter of the maximum speed
3 – 1/8 of the maximum speed (etc.)
0…8 RWE
195
referencing switch
speed
Similar to parameter no. 194, the speed for the
switching point calibration can be selected.
0..8 RWE
203
mixed decay
threshold
If the actual velocity is above this threshold, mixed
decay will be used. This can also be set to –1
which turns on mixed decay permanently also in
the rising part of the microstep wave. This can be
used to fix microstep errors.
0..2048
or -1
16MHz
65536
2
PD
steps
sec
RWE
204
freewheeling
Time after which the power to the motor will be
cut when its velocity has reached zero
Stall detection threshold. Set it to 0 for no stall
detection or to a value between 1 (low threshold)
and 7 (high threshold). The motor will be stopped
if the load value exceeds the stall detection
threshold. Switch off mixed decay to get usable
results.
0..7
RWE
206
Actual Load Value
Readout of the actual load value used for stall
detection.
0..7
R
208
driver error flags
TMC249 error flags. Read only!
R
209
Encoder Position
Position of motor axis within one rotation
0..255
[encoder steps]
RW
210
encoder prescaler
Prescaler for the encoder (since firmware version
3.38). For more information refer to 9.2 please.
RWE
211
Fullstep Threshold
When exceeding this speed the driver will switch
to real full step mode. To disable this feature set
this parameter to zero or to a value greater than
2047.
Setting a full step threshold allows higher motor
torque of the motor at higher velocity. When
experimenting with this in a given application, try
to reduce the motor current in order to be able to
reach a higher motor velocity!
0..2048
16MHz
65536
2
PD
steps
sec
RWE
214
power down delay
Standstill period before the current is changed
down to standby current. The standard value is 200
(value equates 2000msec).
1… 65535
[10msec]
RWE
215
absolute encoder
value
Absolute value of the encoder.
0…255
[encoder steps]
R
* Unit of acceleration:
536870912 2
_ + _
16
2
microsteps
sec
2
Please use theTMCL-IDE axis parameter calculation tool for getting best values.
Setting this parameter to a different value as $E4 will
cause re-initialization of the axis and global parameters
(to factory defaults) after the next power up. This is
useful in case of miss-configuration.
0…255
RWE
65
RS232/RS485 baud rate
0
9600 baud (default)
1
14400 baud
2 19200 baud
3
28800 baud
4
38400 baud
5 57600 baud
6
76800 baud
Not supported by Windows!
7
(115200 baud)
0…7
RWE
66
Serial address
The module (target) address for RS-232/RS-485.
0…255
RWE
67
ASCII mode
Configure the TMCLTM ASCII interface:
Bit 0: 0 – start up in binary (normal) mode
1 – start up in ASCII mode
Bits 4 and 5:
00 – Echo back each character
01 – Echo back complete command
10 – Do not send echo, only send command reply
RWE
8 Global parameters
The global parameters apply for all types of TMCM modules.
They are grouped into 3 banks:
bank 0 (global configuration of the module)
bank 1 (normally not available; for customer specific extensions of the firmware)
bank 2 (user TMCL
Please use SGP and GGP commands to write and read global parameters.
8.1 Bank 0
Parameters with numbers from 64 on configure stuff like the serial address of the module RS232/RS485 baud
rate or the CAN bit rate. Change these parameters to meet your needs. The best and easiest way to do this
is to use the appropriate functions of the TMCL-IDE. The parameters with numbers between 64 and 128 are
stored in EEPROM only.
An SGP command on such a parameter will always store it permanently and no extra STGP command
is needed.
Take care when changing these parameters, and use the appropriate functions of the TMCL-IDE to do it
in an interactive way.
Note: The PDX-113-57/60-SE does not have the parameters 0…38. They are used for modules which address
more than one motor.
Meaning of the letters in column Access:
R = readable (GGP)
W = writeable (SGP)
E = automatically restored from EEPROM after reset or power-on.
The CAN ID for replies from the board (default: 2)
0..7ff
RWE
71
CAN ID
The module (target) address for CAN (default: 1)
0..7ff
RWE
73
Configuration EEPROM
lock flag
Write: 1234 to lock the EEPROM, 4321 to unlock it.
Read: 1=EEPROM locked, 0=EEPROM unlocked.
0/1
RWE
75
Telegram pause time
Pause time before the reply via RS232 or RS485 is sent.
For RS232 set to 0.
For RS485 it is often necessary to set it to 15 (for RS485
adapters controlled by the RTS pin).
For CAN interface this parameter has no effect!
0…255
RWE
76
Serial host address
Host address used in the reply telegrams sent back via
RS232 or RS485.
0..255
RWE
77
Auto start mode
0: Do not start TMCLTM application after power up
(default).
1: Start TMCLTM application automatically after power up.
0/1
RWE
80
Shutdown pin
functionality
Select the functionality of the SHUTDOWN pin
0 – no function
1 – high active
2 – low active
0..2
RWE
81
TMCL
TM
code protection
Protect a TMCLTM program against disassembling or
overwriting.
0 – no protection
1 – protection against disassembling
2 – protection against overwriting
3 – protection against disassembling and overwriting
If you switch off the protection against
disassembling, the program will be erased first!
Changing this value from 1 or 3 to 0 or 2, the TMCLTM
program will be wiped off.
0,1,2,3
RWE
128
TMCLTM application
status
0 –stop
1 – run
2 – step
3 – reset
0..3
R
129
Download mode
0 – normal mode
1 – download mode
0/1 R 130
TMCLTM program
counter
The index of the currently executed TMCLTM instruction.
R 132
Tick timer
A 32 bit counter that gets incremented by one every
millisecond. It can also be reset to any start value.
The global parameter bank 1 is normally not available. It may be used for customer specific extensions of
the firmware. Together with user definable commands (see section 7.3) these variables form the interface
between extensions of the firmware (written in C) and TMCLTM applications.
Bank 2 contains general purpose 32 bit variables for the use in TMCLTM applications. They are located in RAM
and can be stored to EEPROM. After booting, their values are automatically restored to the RAM.
Up to, 56 user variables are available.
Meaning of the letters in column Access:
R = readable (GGP)
W = writeable (SGP)
E = automatically restored from EEPROM after reset or power-on.
Figure 9.3: Limit switches with extra
reference switch
motor
ref sw itch
eccentric
REF_L_x
Figure 9.4: Circular
system
9 Hints and tips
This chapter gives some hints and tips on using the functionality of TMCLTM, for example how to use and
parameterize the built-in reference point search algorithm or the incremental encoder interface.
9.1 Reference search
The built-in reference search features switching point calibration. There is one reference switch per axis. The
internal operation is based on an individual state machine that can be started, stopped and monitored
(instruction RFS, no. 13). The settings of the automatic stop function corresponding to the switch (axis
parameters 12 and 13) do not have any influence on the reference search.
Figure 9.1: Definition of the switches
Selecting the referencing mode (axis parameter 193): in modes 1 and 2, the motor will start by moving
"left" (negative position counts). In mode 3 (three-switch mode), the right stop switch is searched first
to distinguish the left stop switch from the reference switch by the order of activation when moving left
(reference switch and left limit switch share the same electrical function).
Until the reference switch is found for the first time, the searching speed is identical to the maximum
After hitting the reference switch, the motor slowly moves right until the switch is released. Finally the
switch is re-entered in left direction, setting the reference point to the center of the two switching
points. This low calibrating speed is a quarter of the maximum positioning speed by default (axis
parameter 195).
In figure 8.2 the connection of the left and the right limit switch is shown. Figure 8.3 shows the
connection of three switches as left and right limit switch and a reference switch for the reference
point. The reference switch is connected in series with the left limit switch. The differentiation between
the left limit switch and the reference switch is made through software. Switches with open contacts
(normally closed) are used.
In circular systems there are no end points and thus only one reference switch is used for finding the
Suggestion for micro step solution
(setting of parameter 140)
6400
12.5 (default)
SAP 210, 0, 6400
6 (64 micro steps)
3200
6.25
SAP 210, 0, 3200
5 (32 micro steps)
1600
3.125
SAP 210, 0, 1600
4 (16 micro steps)
800
1.5625
SAP 210, 0, 800
3 (8 micro steps)
400
0.78125
SAP 210, 0, 400
2 (4 micro steps)
200
0.390625
SAP 210, 0, 200
1 (2 micro steps)
Adder for
<p>
SAP command for motor 0
SAP 210, M0, <p>
4
Clear encoder with next null channel event
Prescaler = _p_
512
9.2 Changing the prescaler value of an encoder
The PD-113-57/60-SE PANdrive™ is a full mechatronic solution including a NEMA 23 (flange size 57mm) or
NEMA 24 (flange size 60mm) stepper motor, a motion controller/driver and a sensOstepTM magnetic encoder
(max. 256 increments per rotation), e.g. for step-loss detection under all operating conditions.
For the operation with encoder please consider the following hints:
The encoder counter can be read by software and can be used to control the exact position of the
motor. This also makes closed loop operation possible.
To read out or to change the position value of the encoder, axis parameter #209 is used.
So, to read out the position of your encoder 0 use GAP 209, 0. The position values can also be
changed using command SAP 209, 0, <n>, with n = ± 0, 1, 2…
To change the encoder settings, axis parameter #210 is used. For changing the prescaler of the
encoder 0 use SAP 210, 0, <p>.
Automatic motor stop on deviation error is also usable. This can be set using axis parameter 212
(maximum deviation). This function is turned off when the maximum deviation is set to 0.
To select a prescaler, the following values can be used for <p>:
The table above just shows a subset of those prescalers that can be selected. Also other values between
those given in the table can be used. Only the values 1, 2, 4, and 16 must not be used for <p> (because they
are needed to select the special encoder function below or rather are reserved for intern usage).
Consider the following formula for your calculation:
Example: <p> = 6400
6400/512 = 12.5 (prescaler)
There is one special function that can also be configured using <p>. To select it just add the following value
to <p>:
Add up both <p> values from these tables to get the required value for the SAP 210 command. The
resulting prescaler is Value/512.
The module is equipped with TMC249 motor driver chips. These chips feature load measurement that can be
used for stall detection. The stallGuardTM function effects that the motor will be stopped when the load gets
too high. It is controlled by axis parameter #205. If this parameter is set to a value between 1 and 7 the
stall detection will be activated. Setting it to 0 means that stall detection is turned off. A greater value
means a higher threshold. This also depends on the motor and on the velocity. There is no stall detection
while the motor is being accelerated or decelerated.
Stall detection can also be used for finding the reference point. You can do this by using the following
TMCLTM code:
SAP 205, 0, 5 //Turn on Stall Detection (use other threshold if needed)
ROL 0, 500 //Let the motor run (or use ROR or other velocity)
Loop: GAP 3, 0
COMP 0
JC NE, Loop //Wait until the motor has stopped
SAP 1, 0, 0 //Set this position as the zero position
Do not use RFS in this case.
Mixed decay should be switched off when stallGuard™ operational in order to get usable results.
9.4 Fixing microstep errors
Due to the zero crossing problem of the TMC249 stepper motor drivers, microstep errors may occur with
some motors as the minimum motor current that can be reached is slightly higher than zero (depending on
the inductivity, resistance and supply voltage of the motor).
This can be solved by setting the mixed decay threshold parameter (axis parameter 203) to the value -1. This
switches on mixed decay permanently, in every part of the microstepping waveform. Now the minimum
reachable motor current is always near zero which gives better microstepping results.
A further optimization is possible by adapting the motor current shape and the zero offset of the wave. (For
further information about TMCL-IDE please refer to the TMCLTM reference and programming manual.)
Use SAP 203, <motor number>, -1 to turn on this feature.
9.5 Using the RS485 interface
9.5.1 Using RS485 with converter
With most RS485 converters that can be attached to the COM port of a PC the data direction is controlled by
the RTS pin of the COM port. Please note that this will only work with Windows 2000, Windows XP,
Windows NT4 or Vista, not with Windows 95, Windows 98 or Windows ME (due to a bug in these operating
systems). Another problem is that Windows 2000/XP/NT4 switches the direction back to receive too late. To
overcome this problem, set the telegram pause time (global parameter #75) of the module to 15 (or more if
needed) by issuing an SGP 75, 0, 15 command in direct mode. The parameter will automatically be stored in
the configuration EEPROM.
9.5.2 Using RS485 with USB-2-X interface converter
Another possibility offers the TRINAMIC USB-2-X device. It is an interface converter that is equipped with a
CAN interface, an IIC interface, a LIN interface, an SPI interface and an RS485 interface. It is connected to the
PC via an USB interface. The following data apply for RS485:
half duplex communication mode
industry standard 75179 transceiver
2400, 9600, and 19200 bps supported
Note: For RS232 set the telegram pause time to zero for maximum data throughput.
[QSH5718] 57mm stepper motor reference manual (see http://www.trinamic.com)
[QSH6018] 60mm stepper motor reference manual (see http://www.trinamic.com)
[USB-2-485] USB-2-485 interface converter reference manual (see http://www.trinamic.com)
[TMCL] TMCLTM reference and programming manual (see http://www.trinamic.com)