TW/.., XW/R/IQ data sheet
TA200780
XW/R/IQ Configuration
Tool Manual TE200793
(c) c1: Select Configuration/Output Mode 0 - All transmitters [Binary]
(configuration software communications window will show communications from sensors)
communications window
configuration software
c2: Select appropriate sensor identification no. from window
e.g. Thermistor Temperature TX.: 16946 Temperature: 26.8
ADC: 367 f/w V4 $---- etc.
sensor’s identification number
Note: if no reception from sensor, see step 6 below.
c3: Type sensor ident ification number into Transmitter Address
slot, and type its Analogue Node Number, and O/S
(outstation) Address into adjacent slots in table
sensor table
(d) Configure Table and PIN (if required) (repeat steps c2, c3 for all sensors)
metItluafeDfiegnahCotegnahCetoN
rebmunNIP4321
rettimsnarT
woRrettimsnarT
0rettimsnartwenputesot
sserddA
eugolanA
000rettimsnartwenputesot
.oNedoN
S/O
0rettimsnartwenputesot
sserddA
evah)s(rellortnoC
putes)s(sdrowssap
'4321'ottnereffid
eS
anA
ocnidesuNIP
)s(rellortn
59=>levelytiroirpfo
noitacifitnedirosn
rosnesmorfrebmun
)stigid
eulav
8(lebalnoitacifitnedi
nirebmunedoneugol
rosneserotsotrellortnoc
nosserddarellortnoC
ebnac(krowtenlacol
htonarorellortnoclacol
re
)krowtennorellortnoc
Notes:
1If the values from the XW are to be sent to more than one controller, check if passwords (PINs)
set up in any of them. One PIN must be the same in all controllers and of priority level >=95.
2If sensor value is to be sent to another controller (other than the local controller) the local
supervisor port address must be greater than zero.
PIN
1
1
2
(e) Configure Table into XW
e1 Change Configuration/Output Mode to ‘5 Programmed Transmitter Trend Protocol (ASCII)’
e2 Select Configuration/Programme Channels 1-16
e3 Select Configuration (Read Channels 1-16) and check table is correct
Note that to program channels 17-32 select:
Read Channels 17-32 step b3
Program Channels 17/32 step e2
Read Channels 17-32 step e3
CAUTION
Ensure that the menu item Configuration/Output Mode is set back to ‘5 Programmed Transmitters Trend Protocol (ASCII)’ or the receiver will not operate.
2Move sensor or receiver slightly in case of a standing wave null position
Configure IQ controller strategy
7
For IQ3 the sensor’s target analogue node must be created
using SET. An example strategy including decoding of
alarm bits is given in the TW/.., XW/R/IQ data sheet
Connect receiver to controller
8
Note XW/R/IQ current consumption <= 50 mA
either for IQ3 or current IQ2xx (excluding IQ251)
current IQ2xx (not IQ251)
or IQ3
TW/.., XW/R/IQ
Data Sheet
TA200780
RJ11
or IQ251 and older IQ2xx’s without 24 V on local supervisor port
cable: RD/SDU-ADAPTOR IQ2xx
Test System
9
e.g. TB/TI/..
XW/R/IQ
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.