TREND T-PS User Manual

Important: Retain these instructions
UNPACKING
INSTALLATION
Dimensions
85 mm (3.35”)
Installation Instructions
T/PS
PRT Temperature Sensor
T/PS Installation Instructions TG200760
85 mm (3.35”) 26 mm (1.02”)
Requirements
a
d
T/PS PRT Temperature Sensor Installation Instructions TG200760 Issue 1/B 25/04/07
e
> 50 cm (20”)
b
f
c
1.5 m (5 ft)
g
1
T/PS Installation Instructions INSTALLATION (continued)
Requirements (continued)
h
i
-10 °C
j
(14 °F) 0 °C
(32 °F)
0 %RH
H O
2
+50 °C (122 °F)
+40 °C measurement (104 °F)
90 %RH
l
k
Remove backplate
a
wall box
b
Do not use centre 2nd hole down as screw will foul the potentiometers
60 mm (2.36”)
Mount backplate
BESA box
35 mm (1.38”)
wall
35 mm (1.38”)
2
FR
ABS
Remove cutout(s)
as required
35 mm (1.38”)
Route cables
T/PS PRT Temperature Sensor Installation Instructions TG200760 Issue 1/B 25/04/07
35 mm (1.38”)
Installation Instructions T/PS INSTALLATION (continued)
Wire to controller
Terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
J1
OP
OP
J1
OP OP
polarity independent
J1
OP OP
polarity independent
Assemble unit
IQ1xx, 2xx
24 V IN
IQ3
0 (0 V ) N (in) + (+24 V)
‘click’
Analogue input channel linked for loop powered current (I)
I
Universal input channel linked for current (I)
I
T/PS PRT Temperature Sensor Installation Instructions TG200760 Issue 1/B 25/04/07
3
T/PS Installation Instructions INSTALLATION (continued)
Set up IQ Sensor type
It is recommended to use SET (software tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, select the appropriate SET Unique Reference from the following:
PRT I -10+40 (°C) PRT I +14+104 F (°F)
Alternatively enter scaling manually as defined in table below with mode set to 5 (characterise).
For all other IQ controllers see Sensor Scaling Reference Card TB100521A.
C°F°
10
Test system
Δ T
stinU
epyttupnI
Y
tnenopxE
E
reppU
U
rewoL
L
stnioP
P xxI)C°(xO)F°(xO
401-41
1
0204401
2
3
04401
01-41
2
)tnerruc(2
I Q
DISPOSAL
WEEE Directive :
At the end of their useful life the packaging and product should be disposed of by a
Do not dispose of with normal household waste. Do not burn.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
4
suitable recycling centre.
T/PS PRT Temperature Sensor Installation Instructions TG200760 Issue 1/B 25/04/07