Important: Retain these instructions
UNPACKING
Installation
Installation Instructions
T/PO
T/PO Installation
Instructions TG200241A
Dimensions
1
57 mm (2.24”)
97 mm (3.82”)
2
Requirements
ab
T / P O
M A N U F A C T U R E D I N E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
105 mm (4.13”)
domed brass probe
Fix to Wall
3
drill 2 pilot holes
a
85 mm (3.35”)
tighten screws
b
T / P O
2 off No 6 (M3.5) screws
T / P O
M AN U FA C TU R ED I N EU
TR EN D CO NT RO L SY ST EM S
LT D U K
LT D U K
T / P O
TR EN D CO NT RO L SY ST EM S
M AN U FA C TU R ED I N EU
LT D U K
TR EN D CO NT RO L SY ST EM S
M AN U FA C TU R ED I N EU
T / P O
c
ef
g
T /P O
MA NU FAC TU RED IN EU
TRE ND CON TRO L SY STE MS
LTD UK
ambient limits
-40 °C
(-40 °F)
measurement range
-30 °C
(-22 °F)
0 %RH
H O
Protection :IP67, NEMA6
2
d
+50 °C
(+122 °F)
+50 °C
(+122 °F)
95 %RH
T/PO Installation Instructions TG100241A Issue 4/B 14/02/07
1

T/PO Installation Instructions
Installation (continued)
Remove Lid
4
a
Lift Board
5
Insert Cable
6
either use M20 flexible conduit
b
Caution: This unit contains static
damage to the units. BS EN100015/1
Basic Specification: protection of
electrostatic sensitive devices.
or use M16 cable gland
sensitive devices. Suitable
anti-static precautions
should be taken throughtout
the operation to prevent
Wire to Controller
7
polarity independent
IQ system TP/I/22/HF/200
(Belden 8761) cable
recommended.
Terminal size 0.5 to 2.5 mm
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to
C (+24V), instead connect to AUX+ (+24V).
2
2
Sensor
Terminate screen at IQ end only
Sensor
(14 to 20 AWG)
T/PO Installation Instructions TG100241A Issue 4/B 14/02/07
IQ1xx, IQ2xx
24 Vdc
IN
IQ3
0 (0 V)
N (in)
+ (24 V)
Analogue input
channel linked
for current (I)
I

Installation Instructions T/PO
Installation (continued)
Replace Board
8
Replace Lid
9
a
Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or
conduit connection fully tightened.
10
Configure IQ
or
I Q
b
I Q
IQ Configuration
Manual 90-1533
T/PO Installation Instructions TG100241A Issue 4/B 14/02/07
3

T/PO Installation Instructions
Installation (continued)
Set up IQ Sensor Type
11
It is recommended to use SET (Software Tool) for the setting of the sensor type module.
For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers,
select the appropriate SET Unique Sensor Reference from the following:
Alternatively enter scaling manually as defined in table below.
For all other IQ controllers see Sensor Scaling Reference Card TB100521A
tYpe Sensor digI/P Driver Function loGic Loop scHedule seQnc Analog
digBit Knob sWitch Time Zone Oss User addRess intcoN calarM reView Plot
calEndar
Yn<CR>
TYPE n
:=?
S=5 (characterise)
Y= , E= , U= , L= , P= , I1= , I2= , O1= , O2=
X <CR>
PRT I -40+50 (°C)
PRT I -40+122 F (°F)
= ?
Y
E
U
L
P
x
1
2
epyttupni)tnerruc(2
tnenopxE3
stinUC°F°
reppU05221
rewoL04-04-
stnioP22
xIxOxO
404-04-
0205221
12
Test System
T /P O
M A N UF A C T UR E D I N E U
TR E ND C O N TR O L S Y ST E MS
LT D U K
IQ
Δ T
Disposal
WEEE Directive :
At the end of their useful life the packaging
and product should be disposed of by a
Do not dispose of with normal household waste.
Do not burn.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.