T/FS Frost Protection Thermostat
Data Sheet
T/FS
Frost Protection Thermostat
Description
Capillary thermostat suitable for the prevention of freezing of
liquid filled heat exchangers or pipes, and similar applications.
Switching action is responsive to the lowest temperature along
the sensing element. IP54 (NEMA 3) housing with tamper-proof
cover.
Physical
120 mm (4.72”)
Manual Reset Button
(T/FS-M option)
Temperature Setpoint
indicator
6 m (6.5 yds)
Capillary (supplied
coiled)
130 mm (5.12”)
Features
• 6 metre (6.5 yds) capillary
• Manual or automatic reset option
• Adjustment range -10 °C to +12°C (14 °F to 54 °F)
• IP54 (NEMA 3) housing
• Integral mounting bracket
60 mm (2.36”)
ø 6 mm
(0.24”)
70 mm (2.76”)
Cable gland
130 mm (5.12”)
T/FS Frost Protection Thermostat Data Sheet 91-2777 Issue 2 03/04/08
ACC/FC
5 mm (0.2”)
50.5 mm (1.99”)
50.4 mm (1.98”)
1
![](/html/0b/0b5d/0b5d6c1e05d33e1c36097bd158772f7b3b2d161a2af46c2f5d6b0b13c3e30ef7/bg2.png)
T/FS Data Sheet
INSTALLATION
(1) Mount frost stat in a reasonably clean location, free from
damp and condensation, using mounting bracket supplied
(120 mm, 4.72” fixing centres).
(2) Install the complete length of the element so that it spans
the face area of the heat exchanger, as shown in the
diagram, so that it is exposed to all areas where low
temperatures are likely to be encountered.
Thermostat Element Duct
Temperature of thermostat body
must be greater than
temperature setting point
Typical Mounting Arrangement
The element is usually installed on the downstream side
of the heat exchanger and must be fixed in a vertical
plane.
The capillary has to be positioned with a large bend
radius, never less than 25 mm (~1”). It is recomended to
use the fixing clips (ACC/FC).
The T/FS has a 250 Vac, 15 A switching capacity. It should be
incorporated directly into the Air Handling Unit Control circuits to
protect heating and cooling exchanges and ductwork fabric
Alternatively, the T/FS can be used to provide an input to the IQ
system controller to initiate a frost protection control strategy.
If the capillary is damaged with a leak of gas the frost stat
simulates a low temperature and sets the switch accordingly.