TREND T-FG User Manual

Flue Gas Temperature Sensor
Important: Retain these instructions
UNPACKING
INSTALLATION
Installation Instructions
T/FG
1
2
a
Dimensions
380 mm (14.96”)(/L)
230 mm (9.06”) (/S)
Location
1 m ( 1 yd) cable
<100 °C (212 °F)
<400 °C (752 °F)
85 mm (3.35”)
b
<1 m (1 yd)
>50 mm (2”)
55 mm (2.17”)
75 mm (2.95”)
94 mm (3.7”)
117 mm (4.61”)
<70 °C (158 °F)
c
Protection :IP67, NEMA6
(2.24”)
115 mm
T/FG Flue Gas Temperature Sensor Installation Instructions TG100245A Issue 2/C 13/03/07
1
T/FG Installation Instructions INSTALLATION (continued)
Separate compression fitting
3
Mount sensor
4
either (for thicker material)
a tap hole b screw in fitting
drill and tap 1/8” BSPT
>6 mm (0.24”)
or (for thinner material)
a
drill Ø
6.5 mm (0.26”)
<6 mm (0.24”)
b
Ø 4 mm
3 off self tapping screws
19 mm (¾”)
compression fitting
duct mounting flange
c
Adjust depth of probe
5
either or
>50 mm (2”) >50 mm (2”)
2
T/FG Flue Gas Temperature Sensor Installation Instructions TG100245A Issue 2/C 13/03/07
Installation Instructions T/FG INSTALLATION (continued)
Mount Electronics housing
6
85 mm (3.35”)
2 x No.6 (M3.5) screws
Remove lid
7
a
b
Insert cable through gland
8
a
Wire to Controller
9
5
-
+
+
-
1
T/FG Flue Gas Temperature Sensor Installation Instructions TG100245A Issue 2/C 13/03/07
Terminate screen at IQ end only
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect to C (+24V), instead connect to AUX+ (+24V).
b
-
5
+
4 3 2 1
IQSensor SIG 24 Vdc
Analogue input channel linked for current (I)
I
3
T/FG Installation Instructions INSTALLATION (continued)
10
12
Replace lid
11
a
Configure IQ
or
IQ
b
IQ
IQ Configuration Manual 90-1533
Set up IQ Sensor type
It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or geater, or IQ3 series controllers use the following SET Unique Sensor Reference:
Alternatively, and for fahrenheit scaling, enter scaling manually as defined in the adjacent table with scaling mode 5 (characterise). For all other IQ controllers see the Sensor Scaling Reference Card TB100521A.
PRT I 0+400 (°C)
stinU Y E U L P I1 I2 O1 O2
C°24004024020 004 F°2425723240223257
13
Test System
IQ
Δ T
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
4
T/FG Flue Gas Temperature Sensor Installation Instructions TG100245A Issue 2/C 13/03/07
DISPOSAL
WEEE Directive :
At the end of their useful life the packaging and product should be disposed of by a suitable
Do not dispose of with normal household waste. Do not burn.
recycling centre.
Loading...