TREND NETBLINC User Manual

Page 1
Lon Internetwork Node Controller
!
Important: Retain these instructions
Installation Instructions
NETB/LINC
CONTENTS
1 Unpacking .......................................................................... 1
2 Storage .............................................................................. 1
3 Installation ......................................................................... 1
1 UNPACKING
2 STORING
-10 °C (14 °F)
+50 °C (122 °F)
H O
0
2
95 %RH
3.1 Installation - Mounting........................................................ 1
3.2 Installation - Configuration................................................. 4
4 Replacing the Fuse............................................................ 8
5 Disposal ............................................................................. 8
NETB/LINC Installation Instructions, TG200632
It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989. For USA install equipment in accordance with the National Electric Code.
3 INSTALLATION
3.1 Installation - Mounting
Dimensions
1
50 mm (1.97")
180 mm (7.09")
c
300 mm (11.81")
300 mm (11.81")
300 mm (11.81")
Note that this product may involve LonWorks system integration as referred to in section 3.2 step 19: this procedure should only be performed by an installer with LonWorks engineering expertise.
Requirements
2
a
b
d
0 °C (32 °F)
+45 °C (113 °F)
H O
0 %RH
2
90 %RH
Protection: IP30
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
1
Page 2
NETB/LINC Installation Instructions
3.1 Installation - Mounting (Continued)
Requirements (continued)
2
e NETB/LINC/FTT/24 only for UL rating
The unit is UL rated as 'UL916, accessory to open energy management equipment.'
Remove Side Covers
3
Mount Unit
4
Press down catches
Slide out
WARNING: Removal of the cover exposes
dangerous voltages.
417-IEC-5036
Mounting hole positions
155 mm (6.10")
2
Route Cables
5
Cable holes
267 mm (10.51")
4 screws M4 (No.8)
either
pierce grommet
or
use M20 Copex glands
cable holes
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
Page 3
Installation Instructions NETB/LINC
X
3.1 Installation - Mounting (Continued)
Connect Input Power
NETB/LINC consumption < =6 VA
6
S C N L o n A
J 1 8
L O N
L o n B
S C N
L o n A L o n B
J 8
T -
J 7
T + R -
R +
T -
J 6
T + R ­R + S C N S C N
T R E N D
N E T W O R K
J 1 6
E N
2 3 0 V a c
5 0 / 6 0 H z
L
~
1 8 V A
T h is u n i t m u s t b e e a r th e d
F S I
S U P P L Y F U S E 5 0 m A ( T )
L I N C
WARNING: This apparatus must be earthed (grounded).
(using input power earth, ground, terminal)
Note that the power connector earth (ground) is internally connected to 0V.
Connect Current Loop Network
7
Normally Local Lan if address <100
Note that 3xtend/EINC Ls, EINCs, INCs, LINCs cannot be on same local Lan
Internetwork segment A if address >=100
AC Input power
E
230 Vac
N
or 24 Vac
L
~
Terminal size 0.5 to 2.5 mm (14 to 20 AWG)
O
I
2
DO NOT APPLY
POWER
Network Engineering Manual, 92-1735
elbaCduab2k1duab8k4duab6k9
2819nedleB
7029nedleB
)1678ned
leB(
002/FH/22/1/1/PTmetysQI
)3278nedleB(
m0001
m0001
m0001
m0001
002/FH/22/2/2/PTmetsysQI
y0901(
m0001
)sdy0901(
)sdy0901(
)sdy0901(
)sd
)sdy0901(
m0001
)sdy0901(
m0001
)sdy0901(
m0001
)sdy0901(
Terminal size 0.5 to 2.55 m2 (14 to 20 AWG) Polarity independent
2 wire
T
R T R
T
R T R
T
R T R
R
R
T­T+
R­R+
T­T+
R­R+
X
T
T
SCN SCN
m0001
)sdy0901(
m0001
)sdy0901(
m007
)sdy567(
m005
)sdy545(
internal links
2k91
fo.oN
duab
seriW
m007
2
)sdy
567(
m005
2
)sdy545(
m053
2
)sdy083(
m052
4
)sdy072(
S C N L o n A
J 1 8
L O N
L o n B
S C N
L o n A L o n B
J 8
T -
J 7
T + R -
R +
T -
J 6
T + R ­R + S C N S C N
T R E N D
N E T W O R K
J 1 6
E N
2 3 0 V a c
5 0 / 6 0 H z
L
~
1 8 V A
T h is u n i t m u s t b e e a r th e d
F S I
S U P P L Y F U S E 5 0 m A ( T )
L I N C
4 wire
T R
T R
T R
T R
T
R T R
T R
T R
TT
RR
RR
TT
T-
T+
internal links
R-
R+
T-
T+ R-
R+ SCN
SCN
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
3
Page 4
NETB/LINC Installation Instructions
LonASCN LonB LonASCN LonB
LINC
A
1
IQLROUTER
2
3
4
B
1
2
3
4
IQL
x
y
A
1
IQLROUTER
2
3
4
B
1
2
3
4
z
w
LONC
IQL
xyzw
LonASCN LonB LonASCN LonB
LONC
LonASCN LonB LonASCN LonB
567 891011
45 67 891011
3.1 Installation - Mounting (Continued)
Connect LonWorks
8
elbaChtgnelsubxaMedonotedonxaM
20158nedleB)sdy545(m005)sdy545(m005
dnerT
002/FH/61/0/1/PT
)1748nedleB(
GWA22,VIleveLLU)sdy545(m005)sdy034(m004
8.0x2x2Y)tS(YJ)sdy545(m005)sdy053(m023
865AIT)sdy034(m054)sdy072(m052
GWA42,5.taCA
Normal current loop Lan cable is not recommended. Do not use screened cable.
Terminal size 0.5 to 2.55 m2 (14 to 20 AWG)
If used with LPT-10 (powered bus), cable lengths differ - see "Link Power Transceiver User's Guide" (078-0105-01C)".
Lon - FTT (free topology)
*
T e r m i n a t o r
*
T e r m i n a t o r
(m005)sdy034(m004
)sdy545
*
T e r m in a to r
S C N L o n A
J 1 8
L O N
L o n B
S C N
L o n A L o n B
J 8
T -
J 7
T + R -
R +
T -
J 6
T + R ­R + S C N S C N
T R E N D
N E T W O R K
J 1 6
E N
2 3 0 V a c
5 0 / 6 0 H z
L
~
1 8 V A
T h is u n i t m u s t b e ea r t h ed
F S I
S U P P L Y F U S E 5 0 m A ( T )
L I N C
LonWorks
internal
SCN
links
LonA LonB
SCN
LonA LonB
Do not allow wires to cross on a loop
Replace Side Covers
9
slide in
Star topology Bus topologyLoop topology
polarity independent
LonWorks
* Terminate LonWorks bus at one end only using IQLROUTER integrated LonWorks terminator or LONTERMINATOR
Terminator
e.g. LONTERMINATOR
100 mF, 50 V min
100 mF, 50 V min
Recommend terminate at
LINC or Router.
e.g. use IQLRouter integral
terminators
Maximum 64 nodes per LonWorks segment Maximum 40 IQLs (and LONCs) per Lan
Note that if single segment, LONTERMINATOR can be used to terminate LonWorks bus.
3.2 Installation - Configuration
Switch off
1
If appropriate
Open Panel
2
4
replace screws
O
I
NETB/LINC/FTT/24 only for UL rating The unit is UL rated, accessory to open energy management equipment.
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
Page 5
Installation Instructions NETB/LINC
ON
ON
3.2 Installation - Configuration (continued)
Remove Side Covers
3
undo screws
Set LINC Internetwork Address (Lan number)
5
BAUD
1K2
9K6
19K2
64
e.g.
Address = 2 + 16 = 18
press down catches
slide out
WARNING: Removal of the cover exposes dangerous voltages.
417-IEC-5036
ADDRESS
16
32
4
2
1
SET
NOT SET
address
Remove Main Cover
4
push in side prongs
Caution: This unit contains static sensitive
devices. Suitable anti-static precautions should be taken throughout this
operation to prevent damage to the unit. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices
SCN LonA
J18
LON
LonB
SCN
LonA LonB
J4
J8
J14
T-
J7
T+ R-
R+
TX
T-
J6
RX
T+ R­R+ SCN SCN
TREND
NETWORK
J16
Address = D
1, 4 to 9, 11 to 119 0, 2, 3, 10 or >119
ADDRESS
BAUD
19k2
9K6
1K2
163264
124
8
S3
SERVICE
LON OK LAN OK
Lan = D
/
J1
D2 D3
Lan = D
Lan
= D
/
Lift off cover
J5
E N
230 Vac
L
This unit must be earthed
~
FSI
NETB/LINC
Lan = D
/
if address < 100, address defines Lan number on Internetwork (LonWorks internetwork)
Set Network Baud Rate
6
ON
1K2
BAUD
9K6
19K2
ADDRESS
16
32
64
= 19k2 baud
= 9k6 baud
= 1k2 baud
Lan
LINC
Internetwork on Lonworks
if address = > 100, address is for configuration only (Internetwork LonWorks Extension)
SCN LonA
J18
LON
LonB
SCN
LonA LonB
J4
J8
J14
T-
J7
T+ R-
R+
TX
T-
J6
RX
T+ R­R+ SCN SCN
TREND
NETWORK
J16
4
2
1
BAUD
9K6
1K2
ADDRESS
19k2
163264
8
SERVICE
network
Segment A
124
S3
Inter-
LON OK LAN OK
Internetwork Segment B
LINC
on LonWorks
J1
J5
E N
230 Vac
L
This unit must be earthed
~
FSI D2 D3
Baud = C
SET
=C
NETB/LINC
=C
NOT SET
Lan
Inter-
network
Segment A
=C
Internetwork on LonWorks
LINC
Internetwork Segment B
LINC
on LonWorks
=C
if address < 100, baud rate of current loop Lan
if address = > 100, baud rate of current loop Internetwork (Segment A)
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
5
Page 6
NETB/LINC Installation Instructions
LINC
3.2 Installation - Configuration (Continued)
Replace Main Cover
7
Push cover on
Check Current Loop Network
if address < 100, current loop Lan
10
if address = > 100, current loop Internetwork (Segment A)
Lan OK (green)
Lan OK
LINC Faulty
Replace Side Covers
8
X
replace screws
NETB/LINC
slide in
O
I
Switch On
9
O
I
LINC
Lan OK
Check network cabling for short circuits with a multimeter (NOT Megger)
Check baud rate. Power up other nodes until faulty node
is found (OK ). Correct fault.
Check LINC on LonWorks
11
Lan
LINC
13
LINC
LINC
and
or
Configure LINC
LonWorks
Lan
SET
or
address 126, local Lan
LONC
IQL
or
LonWorks
LonWorks
LINC
I/N
Lan
Lon OK (green)
Flashes every 24 s, ON after 1½ mins
(Check LonWorks, LINC, and LINC, or LONC, or IQL)
address 126, Lan number set by address switch
12
The unit is UL rated as 'UL916, accessory to open energy management equipment.'
SET Manual TE200147
top menu :
R
e.g.
to eXit module having changed parameter
select addRess module
Close Panel
NETB/LINC/FTT/24
only for UL rating
X
Note that the LINC can be configured across LonWorks (using another LINC) with TARP is set to Yes (default) in both LINCs (see step 14)
6
to Quit module and discard changes
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
Q
Page 7
Installation Instructions NETB/LINC
3.2 Installation - Configuration (Continued)
Set up following parameters
14
edamebtsumtahtsgnitteS
retemaraPgnitteSnoitcnuFnoitidnoC
sserddAPratnoitulosersserddA
lacol
smrala
rddAs
naletomeRrebmunnaLmralaCNILforebmunn
ten/tni
EdonsserddaedonmralaCNILfosserddaedon
smrala
naleTomerrebmunnaLmralaCNILforebmunnaL
Note that a PIN may be required to make changes in configuration mode. If the PIN has been forgotton the users should contact their supplier (installers contact Technical Support) quoting the generator number (User module) and neuron id (Address module) whereupon a default PIN will be supplied. This will only work during the same configuration mode session i.e. the utility must not be exited between reading the generator and entering the default PIN. After the PIN is entered a new PIN should be set up and remembered.
seY=tluafed,locotorp
serddaedonmralaCNILfosserddaedon
tegrat
aL
tegrat
tegrat
tegrat
lab
olgfforonosehctiwS
segassemnoitulosersserdda
noLyb
pooltnerrucdnesot
smralakrowten
pooltnerrucdnesot
smralakrowten
raladnesot krowtenretni
krowtenretni
Optional Settings
15
Set up the following parameters if required. The table shows setting that may be required for special circumstances
edamebyamtahtsgnitteS
retemaraPgnitteSnoitcnuFnoitidnoCetoNeeS
resUniPrebmunnisegnahcstcetorP
sserddAreifitneDIciremunahpla51
skrownoledocegasseM.rebmunedoc
ezi
sreffuBretuor)setyb(ezisreffub
reViecsnartsenifedrebmun
feD
ton-sretcarahc sretc
arahc*?;{(^
.46=tlua
641=tluafeD
epytrev
iecsnart
CNIL
llA
metsys
)01-TTF(0=tluafeD
emityrter-r skroWnoLmetsysQIeeS
tekcapretni-i
yaled
ssalcecivres-s
Note 1: If PIN is forgotton see note in step 14 2: Message code can only be changed in configuration mode if 'lonworks managed' is set to No (i.e. managed by LINC). If the LINC is installed on LonWorks Management Tool (see step 19 ), 'lonworks managed' is set to YES, and Message code cannot be changed in configuration mode.
edomnoitarugifnoc
sihtrofreifitnedi
sLQI/sCNOL/sCNIL
tsellamsseificeps
noreffubretuor
slenap
edocemasesutsum
sliate
drof
* Note that to speed up communications,TARP should be changed to No unless there is more than one LINC physically
sselnuoNotegnahC*
connected by LonWorks.
CNILdnocesotdetcennoc
Installation on a LonWorks Management Tool sets TARP to Yes and it can no longer be changed in configuration mode (see step 18).
noLmorfsm
noLmorfsmraladnesot
.)detcetorpnu(knalbsitluafeD
.deriuqerytirucesfiputeS
yalpsid,srosivrepusrofputeS
desugniebedocegassemfI
ebtsum-sresurehtoyb
metsysQIotevisulcxe
dnasCNILetarapessretuorfI
nahtrellamsezisreffubevah
tsellamsottes-setyb641
)66=muminim(.ezisreffub
0MORFEGNAHCTONOD
ediuGgnireenignEstcudorP
1
2
Note Neuron ID
16
Exit Configuration
17
X
Æ "Exit from Utility"
addRess/ neuron chip id 00:00:00:00:00:00
Install on LonWorks Network Management Tool (LMT)
18
If a binding IQLs to LonMark Devices or b LINCs version <3.23 straddle router or c other devices have address conflicts with IQ system devices or d LONROUTERS used on system already installed on LMT
If one IQ system Lon device is installed on LMT, all must be installed
Note that if a 3xtend/EINC L is installed in the LonWorks segment, IQ system devices cannot be installed on a LMT because 3xtend/EINC L does not support installation on a LMT.
a). When installing LINC On
LonWorks tool enter neuron ID from step 16 - or press service button.
SCN LonA
J18
LON
LonB
SCN
LonA LonB
J4
J8
J14
T-
J7
T+ R-
R+
TX
T-
J6
RX
T+ R­R+ SCN SCN
TREND
NETWORK
J16
service button
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06
J1
J5
ADDRESS
BAUD
19k2 9K6
1K2
163264
124
8
S3
SERVICE
D2
LON OK
D3
LAN OK
b). The LINC network image can be retrieved by uploading
E N
230 Vac
L
This unit must be earthed
~
FSI
the XIF file from LINC to tool.
See LonWorks network management tool manual. See IQ system LonWorks Products Engineering Guide (TE200292). Lonworks System Integrator must have Lonworks engineering expertise.
7
Page 8
NETB/LINC Installation Instructions
3.2 Installation - Configuration (Continued)
Check LINC Operation
19
If LonWorks Internetwork (LINC address <100)
If Internetwork LonWorks Extension (LINC address =>100)
Lan
LINC
LINC
4 Replacing the Fuse
Switch off
1
Remove Side Covers
3
undo screws
terse text comms
or or
LONC
LonWorks
IQL
O
I
press down catches
slide out
Lan
I/N
LINC
LINC
or or
Open Panel
2
NETB/LINC/FTT/24 only for UL rating
The unit is UL rated as 'UL916, accessory to open energy management equipment.'
WARNING:
Removal of the cover exposes dangerous voltages.
terse text comms
LONC
IQL
LonWorks
417-IEC-5036
Replace Fuse
4
Fuse: 20 mm, (T) anti-surge 230 Vac: 50 mA 24 Vac: 630 mA
Replace Side Covers
5
replace screws
slide in
Close Panel
6
NETB/LINC/FTT/24 only for UL rating
The unit is UL rated as 'UL916, accessory to open energy management equipment.'
7
SC N Lo nA
J1 8
LO N
Lo nB
SC N
Lo nA Lo nB
J8
T-
J7
T+ R-
R+
T-
J6
T+ R­R+ SC N SC N
T R E N D
N E T W O R K
J1 6
Switch On
E N
2 30 V a c
50 /6 0 Hz
L
~
18 V A
Th is un it m us t b e ear th ed
FS I
S U P P L Y F U S E 5 0 m A (T )
L I N C
5 Disposal
O
I
WEEE Directive :
At the end of their useful life the packaging, and product, should be disposed of by a
suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
8
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/1 1/06