It is recommended that the installation should
comply with the HSE Memorandum of Guidance
on Electricity at Work Regulations 1989.
For USA install equipment in accordance with
the National Electric Code.
EINCs do NOT support automatic addressing, and MUST NOT be installed on an Ethernet network where automatic
addressing is being used.
Connect Current Loop
7
4 wire
Terminal size 0.5 to 2.55
m2 (14 to 20 AWG)
T R
2 wire
T RT R
R
R
R
R
T
T
Maximum Cable distance
Additional terminals
T
T
R
T R
R
X
Terminal size 0.5 to 2.55
m2 (14 to 20 AWG)
Note only 1 INC type node on a single Lan.
Cable1k2 baud9k6 baud19k2 baud38k4 baud *No. of Wires
Belden 91821000 m (1090 yds) 1000 m (1090 yds) 700 m (765 yds) 500 m (545 yds)2
Belden 92071000 m (1090 yds) 1000 m (1090 yds) 500 m (545 yds) 350 m (380 yds)2
IQ System
TP/1/1/22/HF/200
1000 m (1090 yds) 700 m (765 yds)350 m (380 yds) 250 m (270 yds)2
(Belden 8761)
IQSystem
TP/2/2/22/HF/200
1000 m (1090 yds) 500 m (545 yds)250 m (270 yds) 125 m (135 yds)4
XCITE/XA crossover adaptor
order separately (XCITE/XA/5
pack of 5)
Local PC (Ethernet) connection can be either to adjacent Ethernet
hub using standard cable only, or directly to EINC using standard
cable and crossover adaptor, XCITE/XA.
SET Manual TE200147
IP Tool Manual TE200638
OK
Check network cabling for
short circuits with a
multimeter (NOT Megger)
to address switch setting
All EINCs on same channel
must be on same subnet to
create internetwork
All IQ system devices must
use same port to
intercommunicate
MUST be set up for
communications outside own
subnet
Always set up for
supervisors/display panels
1
1
2
3
4
Installation Instructions - Sheet 2NBOX/EINC
1.4 INSTALLATION - CONFIGURATION (Continued)
Configure Addressing Details with IPTool (Continued)
15
ParameterSettingDefaultFunctionConditionNote
CNC
Address
Virtual CNCx
(x = 1 to 4)
Remote Trend
Device x
(remote EINCs)
(x = 1 to 20)
Device Modenetworkedunconfigurednetworked/stand alone on Ethernet
Port address Ethernet port 1 to 32767disabledEthernet port of virtual CNC
alarm IP
address
IP Address
Subnet Mask
1. Change if address clash on Ethernet or if routers between EINCs.
2. May change UDP port if port already used on Ethernet, or if multiple internetworks (i.e. sites) required on subnet (see Data Sheet).
3. Enables EINC virtual CNC to access Ethernet PC across router, or EINC to find other IQ system Ethernet devices across
router.
4. Also used by IQ system Supervisors and software tools to access EINC (Device address always 126).
5. Virtual CNCs inoperative until address set up.
6. Set up each virtual CNC used, separately.
7. Same port number to be set up in supervisor to communicate with virtual CNC.
8. Use virtual CNC in alarm mode to send alarms to Ethernet 962 v3 or greater/963 which connects via TCP dial up.
9. Lowest IP address (IQ3xcite or EINC) on each subnet across router to be set up; as many as possible in each subnet recommended.
10. If using 'updatelist' facility (not recommeded for mixed EINC/IQ3xcite system) also set up this EINC's details (and other
EINC's on this EINC's subnet, if not broadcast).
11. Out of the factory mode is ‘unconfigured’ which changes to ‘networked’ on first write to EINC by IPTool.
node address 1, 4 to 9, 11 to
119
IP address
e.g. 171.193.6.106
IP address
0.0.0.0 to 255.255.255.255
Mask
0.0.0.0 to 255.255.255.255
4
disabled
empty list
empty list
Node address of virtual CNC on virtual
Trend Lan
IP address of target device (e.g.
supervisor)
IP address of IQ system Ethernet device
other side of router
Subnet mask of IQ system Ethernet
device other side of router
If virtual CNC is to be used5,6
If virtual CNC is to be used
and if default needs to be
changed
if CNC used in alarm mode6,8
If network to span router
Set to stand alone if only IQ
system device on Ethernet
6,7
9,
10
11
16
Configure Optional Settings Using SET
Enter configuration mode using SET. The top level
a
prompt will be displayed as below.
b
Configure the optional settings the relevant upper
SET Manual TE200147
EINC L Data Sheet TA200137
case letter and pressing ENTER. If a value has been
changed X+ENTER will confirm it and return to the
top menu, whereas Q+ENTER will quit and return
with the value unchanged. The table below describes
the settings.
Note that it may be necessary to set up a virtual CNC in the
EINC if one is not available elsewhere on the network.
ParameterSettingFunctionConditionNote
addRess
User
remoteEincs send as BroadcastY (1) or N (0)
uPdatelist
iDentifier
local
network
alarms to
ethernet
alarms to
alarm language tyPe0 to 9 (digit)Selects language of network alarmsIf language to be changed2
Copy your remote EINC
list to other EINCs (Y/N)
Address
Remote
lan
addrEss
remoTe
lan
PinnumberProtects changes in configuration mode
generator numberrandom number for default PIN generation
1If set to zero - no alarms reported.
2Language type values:0=English, 1=Spanish, 2=Finnish, 3=Swedish, 4=Norwegian, 5=Danish, 6=German, 7=Italian, 8=Portuguese, 9=French.
3Broadcast preferable as it enables the internetwork link to be made via the subnet of EINCs across router, rather than one EINC. However,
normally stopped by router.
4This facility allows remoteEincs list in one EINC to be set up, and then the list (including Broadcast status) to be copied to all other EINCs
so that internetwork across routers can be formed (not recommended for mixed EINC/IQ3 system).
15 alphanumeric
characters - not
/\({;?* characters
node address 1, 4-9,
11-119
Lan number
1, 4-9, 11-119
node address 1, 4-9,
11-119
Lan number
1, 4-9, 11-119
Copies remoteEincs list to local subnet and all subnets with
EINC in list
Identifier for LanAlways set for supervisors/Display Panels
node address of EINC alarm target for
Trend current loop network alarms
Lan number of EINC alarm target for
Trend current loop network alarms
node address of EINC alarm target for
Ethernet alarms
Lan number of EINC alarm target for
Ethernet alarms
Broadcast to EINC subnet if Y or directed
to 1 EINC on subnet if N
If current loop network alarms to be reported1
If current loop network alarms to be reported1
If Ethernet alarms to be reported1
If Ethernet alarms to be reported1
Default is blank (unprotected). Set up if security
required.
Read only, give to Technical Suppor t with Ethernet
mac address for default PIN see steps (17 and 19).
Default Y, broadcast. Change if broadcast messages
prohibited by router
If internetwork to span router, and to faciliate setup4
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or changes.