TREND LonMark IQL13+ Series Installation Instructions Manual

Page 1
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
1 - 1
1
Installation Instructions - Sheet 1
IQL13+/xxx LonMark Terminal Unit Controllers
Important: Retain these instructions
1.3 Installation - Fixing
CONTENTS
1.1 Unpacking 1-1
1.2 Storage 1-1
SHEET 1: Installation Instructions - Sheet 1
1.1 Unpacking
Sheet 2: Fixing/Configuration
Sheet 1: Fixing
IQL13+/xxx Installation Instructions TG200383
H O
2
+50 °C
(122 °F)
0
-10 °C
(14 °F)
90 %RH
It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989.
1 3 +
L
L A N
N I D
S t ra t e g y
: : : : :
O / S
S e r ia l N o
2 3 0 V a c
~
2 4V
C O M
2 1 22 2 3 2 4 2 5 2 6 2 7 2 81 2 3
C O M
1 2 3 54 6 7
4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 15 1 6 1 7 1 8 19 2 0
1
2 3 4
5
~
2 4V
L O N
2 9 3 0 31 3 2
L O N O K
S R V P IN
C
2 4 V ac
129 mm (5.08”)
75 mm (3”)
205 mm (8.07”)
Dimensions
63 mm (2.48”)
1
1.3 Installation - Fixing 1-1
2.1 Installation - Fixing (continued) 2-1
2.2 Installation - Configuration 2-2
3. Installation - Configuration (continued) 3-1
1 3 +
L
LA N
NID
Str ate gy
: : : : :
O/ S
Se rial No
23 0 V ac
~
24V
CO M
21 22 23 24 25 26 27 281 2 3
CO M
1 2 3 54 6 7
4 5 6 7 8 9 10 11 12 1 3 1 4 1 5 1 6 17 18 19 20
1
2 3 4
5
~
24V
LO N
29 30 3 1 3 2
LON OK
SRV PIN
C
24 Vac
b
a
Requirements
2
Note that this product may involve Lonworks system integration as referred to in section 2.2 step 4: this procedure should only be performed by an installer with LonWorks engineering expertise.
!
Sheet 3: Configuration
1.2 Storage
Page 2
IQL13+/xxx Installation Instructions - Sheet 1
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
1 - 2
1.3 Installation - Fixing (continued)
4 holes
1 3 +
L
L A N
N ID
S tr a te g y
: : : : :
O /S
S e ria l N o
2 3 0 V a c
~
24 V
C OM
2 1 2 2 2 3 24 2 5 2 6 27 2 81 2 3
C OM
1 2 3 54 6 7
4 5 6 7 8 9 1 0 1 1 12 1 3 14 1 5 1 6 1 7 1 8 1 9 2 0
1
2 3 4
5
~
24 V
L O N
2 9 3 0 3 1 32
LO N O K
S RV P IN
C
24 V a c
6 mm (0.24”)
Mounting
13 +
L
LAN
NID
Stra tegy
: : : : :
O/S
Seri al No
230 Vac
~
24V
COM
21 2 2 23 24 2 5 26 27 281 2 3
COM
1 2 3 54 6 7
4 5 6 7 8 9 10 11 12 13 14 1 5 16 17 1 8 19 20
1
2 3 4
5
~
24V
LO N
29 30 31 32
LON OK
SRV PIN
C
24 Va c
c
13 +
L
LAN
NID
Stra tegy
: : : : :
O/S
Seri al No
230 Vac
~
24V
COM
21 2 2 23 24 2 5 26 27 2 81 2 3
COM
1 2 3 54 6 7
4 5 6 7 8 9 10 1 1 12 13 14 15 16 17 18 19 20
1
2 3 4
5
~
24V
LO N
29 30 3 1 32
LON OK
SRV PIN
C
24 Va c
114 mm
(4.49”)
3
Lift Hinged Cover
4
189 mm (7.44”)
a
bc
d
H O
2
+45 °C
(113 °F)
0
0 °C
(32 °F)
90 %RH
13 +
L
LAN
NID
Stra tegy
: : : : :
O/S
Seri al No
230 Vac
~
24V
COM
21 2 2 23 24 25 26 27 281 2 3
COM
1 2 3 54 6 7
4 5 6 7 8 9 10 11 12 1 3 14 1 5 16 17 1 8 19 2 0
1
2 3 4
5
~
24V
LO N
29 30 31 32
LON OK
SRV PIN
C
24 Va c
1 3 +
L
LA N
NI D
St rat eg y
: : : : :
O/ S
Se ria l N o
23 0 Va c
~
24V
CO M
21 22 2 3 24 25 2 6 27 2 81 2 3
CO M
1 2 3 54 6 7
4 5 6 7 8 9 10 1 1 12 13 1 4 15 1 6 17 1 8 1 9 20
1
2 3 4
5
~
24V
LO N
29 3 0 31 3 2
LO N OK
SR V PIN
C
24 Vac
If not installed well outside normal reach (e.g behind false ceiling)
e
Protection: IP20, NEMA 1
Requirements (continued)
2
f
Avoid locations where corrosive fumes or explosive vapours are present. Avoid electrical noise interference
either surface mount
or DIN rail mount
1 3 +
L
L A N
N ID
S tr at eg y
: : : : :
O /S
S e ria l N o
2 3 0 V a c
~
24 V
C OM
2 1 2 2 2 3 2 4 2 5 2 6 27 2 81 2 3
C OM
1 2 3 54 6 7
4 5 6 7 8 9 1 0 1 1 1 2 13 1 4 1 5 16 1 7 1 8 1 9 2 0
1
2 3 4
5
~
24 V
L O N
2 9 3 0 31 3 2
LO N O K
SR V PI N
C
24 V ac
1 3 +
L
L A N
N ID
S tr at e gy
: : : : :
O /S
S e ria l N o
2 3 0 V a c
~
24 V
C OM
2 1 2 2 2 3 2 4 25 26 2 7 2 81 2 3
C OM
1 2 3 54 6 7
4 5 6 7 8 9 1 0 1 1 12 1 3 1 4 15 1 6 1 7 18 19 20
1
2 3 4
5
~
24 V
L O N
2 9 3 0 3 1 3 2
LO N O K
SR V PI N
C
24 V a c
ab c d
WARNING: Failure to use a screwdriver to open the cover will cause damage to the unit.
Page 3
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
1 - 3
Installation Instructions - Sheet 1 IQL13+/xxx
L o n AS C N L o n B L o n AS C N L o n B
L I N C
L O N T E R M I N A T O R
1
A
1
L O N R O U T E R
2
3
4
B
1
2
3
4
I Q L
x
y
A
1
L O N R O U T E R
2
3
4
B
1
2
3
4
L O N T E R M I N A T O R
1
L O N T E R M I N A T O R
1
z
w
I Q L
x
y z
w
I Q L
x
y z
w
I Q L
x
y z
w
Connect Power
5
DO NOT APPLY
POWER
O
I
1 3 +
L
L A N
N I D
S t ra t e g y
: : : : :
O / S
LNE
2 3 0 V a c
1 2 3
Clean earths consisting of short (<300 mm, 12”) stranded copper wire (>=1.5 mm2, 16 AWG) to a substantial earthed metal part (e.g. cable tray) are recommended
Terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
1.3 Installation - Fixing (continued)
1 3 +
L
L A N
N I D
S t ra te g y
: : : : :
O / S
6
T e r m i n a t o r
T e r m in a t o r
T e r m i n a t o r
Lon - FTT (free topology)
Star topology
Bus topology
Loop topology
*Terminate Lon bus at one end only
polarity independent
Connect Lon
Lon
Lon
L O N
2 9 3 0 3 1 3 2
*
*
*
Do not allow wires to cross on a loop
continued over page
2 4 V a c
1 2 3
24Vac
WARNING: This apparatus must be earthed (via earth
terminal).
Earth 24 Vac supply neutral at transformer
/24VAC option /230 option
IQL consumption
<= 12.1 VA (2.5 VA +
power to triac outputs)
IQL consumption
<= 13 VA (3 VA + power
to triac outputs)
100 mF, 50 V min
100 mF, 50 V min
Terminator
e.g. LONTERMINATOR
Maximum 64 nodes per Lon segment Maximum 40 IQLs (and LONCs) per virtual Lan
Recommend terminate at LINC or Router
Page 4
IQL13+/xxx Installation Instructions - Sheet 1
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
1 - 4
T
ST/ET
9888
/
8
K/ST/ET
998 8
/
8
EK/ST/ET
9998
/
8
FEK/ST/ET
9999
/
8
K/LQI/DR
9
S
9
/
8
/
8
SOK/LQI/DR
9
S
998
/
8
FSOK/LQI/DR
9
S
999
S
/
8
Pushbutton or PIR input
Window o
r
Alarm
contact
Local
Space
Temperature
Sensor
Local Setpoint
Adjust
Potentiometer
Fan Speed Select
Auto
Off
C O M
2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8
C O M
1
2 3 4
5
C
Connect Inputs and Outputs
7
If non standard strategy, follow special installation instructions and jump to section 2.1 step 14
Connect Inputs
8
1 3 +
L
L A N
N ID
S tr at e gy
: : : : :
O /S
Non-standard Strategy Installation Instructions
IQL13+/xxx Installation Instructions, TG200383 ­Sheet 2
Configure/Commission
9
6
1.3 Installation - Fixing (continued)
Connect Lon (continued)
If used with LPT-10 (powered bus), cable lengths differ - see “Link Power Transceiver User’s Guide (078-0105-01C)”.
LINC
LINC
IQ Outstations
LonMark
Device
Lonworks bus
IQL
IQ Outstation
Normal IQ System current loop Lan cable is not recommended Do not use screened cable
Terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
2
1
2
3
6
54
TB/TS
/K
/E
/F
C O M
2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8
C O M
1
2 3 4
5
C
Sensors TB/TS, TB/TS/K, TB/TS/KE, TB/TS/KEF recommended; wire as shown below.
Room Display Module (RD-IQL/K, /KOS, /KOSF) provides monitor and control; wired as shown below:
RD-IQL
2 6 2 7
4
C
polarity independent
Note that the IQL must be correctly set up to use the RD-IQL, see section 3 step 15
T
input included in TB or RD
S separate input may be used / Input either cannot be connected, or will be ignored
Connection of separate device to input required
PIR
Terminal size 0.5 to
2.55 mm
2
(14 to
20 AWG)
Pushbutton or PIR input type selected by configuration parameter W6
PIR
Note that terminal types COM and C should not be connected together
elbaChtgnelsubxaMedonotedonxaM
20158nedleB)sdy545(m005)sdy545(m005
metsysQI
002/FH/61/0/1/PT
)1748nedleB(
)sdy
545(m005)sdy034(m004
GWA22,VIleveLLU)sdy545(m005)sdy034(m004
8.0x2x2Y)tS(YJ)sdy545(m005)sdy053(m023
,5.taCA86
25AIT
GWA42
)sdy094(m054)sdy072(m052
Page 5
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
2 - 1
2
Installation Instructions - Sheet 2
IQL13+/xxx LonMark Terminal Unit Controllers
Heat/Cool Damper
Raise
Lower
Common
not used
~
2 4 V
54 6 7
1 5 1 6 1 7 1 8 1 9 2 0
<
~
2 4 V
<
not used
Raise
Lower
Common
Heat or Cool
Valve
~
2 4 V
54 6 7
1 5 1 6 1 7 1 8 1 9 2 0
<
~
2 4 V
<
Raise
Lower
Common
Raise
Lower
Common
Cool Valve
Heat Valve
~
2 4 V
54 6 7
1 5 1 6 1 7 1 8 1 9 2 0
<
~
2 4 V
<
Heat or Cool
Valve
not used
~
2 4 V
54 6 7
1 5 1 6 1 7 1 8 1 9 2 0
<
~
2 4 V
<
1 3 +
L
L A N
N I D
S t r a t e gy
: : : : :
O / S
Cool Valve
Heat Valve
~
2 4 V
54 6 7
1 5 1 6 1 7 1 8 1 9 2 0
<
~
2 4 V
<
SHEET 2: Installation Instructions - Sheet 2
Fixing
10
IQL13+/xxx Installation Instructions,
TG200383 - Sheet 1
11
(24 Vac, 400 mA maximum shared between
24 Vac auxiliary output and all triac outputs used)
/AR2 /WR2
/WR4
2.1 Installation - Fixing (continued)
/WT2
/WT4
1
Connect Heat/Cool Outputs
terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
Connect Fan Outputs
12
1 3 +
L
L AN
N ID
S tra te g y
: : : : :
O /S
WARNING: The wires may be connected to
hazardous voltages. Disconnect power before attempting any wiring.
5 A maximum @240 Vac resistive or inductive (cosø>=0.4) 5A @ 30 Vdc (resistive), 2 A @ 24 Vdc (inductive, T<=30 mS)
Arc suppression TG200208
terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
OUT1 OUT2 OUT3
Fan
Autotransformer
Fan
1 2 3
6 7 8 9 1 0 1 1 1 2 1 3 1 4
For a fan without speed control wires, an auxiliary autotransformer can be used to produce control voltages. Use the following diagram:
An autotransformer with built-in self-resetting thermal overload protection is recommended.
Page 6
IQL13+/xxx Installation Instructions - Sheet 2
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
2 - 2
2.2 Installation - Configuration
1 3 +
L
LA N
N ID
S tra te gy
: : : : :
O /S
Connect 24 Vac Auxiliary Output
13
4 5
2 4 V a c
Load
8
Close Hinged Cover
14
2.1 Installation - Fixing (continued)
1 3 +
L
L A N
N I D
S t ra t e g y
: : : : :
O / S
S e r ia l N o
O
I
LINC
LINC
IQ Outstations
LonMark
Device
Lonworks bus
IQL
IQ Outstation
(Check Lon, LINCs)
LON OK (green)
Flashes every 24 s, ON after 1½ mins
Switch On
2
Check IQL/LINC on Lon
3
Flashes every 1 s (Deaf IQL. Check Lon)
a
b
terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
400 mA maximum shared between 24 Vac Auxiliary output and all triac outputs used.
Tear off Label Strip
1
1 3 +
L
LA N
N ID
S tra te gy
: : : : :
O /S
S er ial N o
2 30 V a c
~
24 V
CO M
21 2 2 2 3 24 25 2 6 2 7 2 81 2 3
CO M
1 2 3 54 6 7
4 5 6 7 8 9 10 1 1 1 2 13 14 1 5 1 6 1 7 18 19 2 0
1
2 3 4
5
~
24 V
L O N
29 30 31 32
LO N OK
SR V PI N
C
24 V ac
O / S
L A N
N I D
S t r a t e g y
S e r i a l N o
117
027
00:A0:25:36:51:00
IQL1x WR4 E 06
IQL1xWR4_50100025
IQL1xWR4_50100025
N I D
S e r i a l N o
00:A0:25:36:51:00
S e r i a l N o
N ID
S e ri al N o
0 0 :A 0 : 2 5 :3 6 : 5 1 :0 0
S e ri al N o
IQ L 1 x W R 4 _ 5 0 1 0 00 2 5
L A N
O /S
‘locate’
Page 7
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
2 - 3
Installation Instructions - Sheet 2 IQL13+/xxx
1 3 +
L
L AN
N ID
S tra t eg y
: : : : :
O /S
S er ia l N o
See LonWorks network management tool manual. See IQ System LonWorks Products Engineering Manual (TE200292). LonWorks System Integrator must have LonWorks engineering expertise.
a). When installing IQL in LonWorks tool, press
service button when requested.
b). The IQL network image can be obtained from
www.lonmark.org, or from www.pnet.trend­controls.com.
c). Set up bindings if required (bind network
variables between IQL and LonMark devices).
IQL13+ Data Sheet TA200205 for Lon network variables (NVs)
Install using LonWorks Network Manager Tool
4
If a binding IQLs to LonMark devices or b LINCs version <3.23 straddle router or c other devices have address conflicts with IQ System devices or d LONROUTERs used on installed system
SRV PIN service button
LINC
Lon
IQL
Lonmark device
If one IQ System Lon device is installed, all must be installed.
2.2 Installation - Configuration (continued)
Lon
LCI
IQL
Note that a PIN may be required to make changes. If the PIN has been forgotten the
users should contact their supplier (installers contact Technical Support) quoting the generator number and neuron id (both from Address module) whereupon a default PIN will be supplied. This will only work for three attempts at entering the PIN. After the default PIN is entered a new PIN should be set up and remembered.
Lon
LCI
IQL
Connect software tool for commissioning
5
if required
Exercise I/O
6
If IqlTool2 available
IqlTool2 Manual TE200185
Use IqlTool2 to monitor inputs and exercise outputs
IqlTool2 Manual
TE200185
LCI Installation
Instructions TG200429
SET Manual TE200147
IqlTool2 (SET)
IqlTool2 runs within SETV5.1 (or later)
RS232 cable supplied with LCI
Lon adapter cable supplied with LCI
IqlTool2 (SET)
Note that IqlTool2 may also be used for mapping the Lon segment, resolving duplicate addresses on Lon, water balancing (/WR2, /WR4, /WT2, /WT4 only), identification via service button, associating with SDU­LON (for other uses see later)
Page 8
IQL13+/xxx Installation Instructions - Sheet 2
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
2 - 4
2.2 Installation - Configuration (continued)
Test input/output functionality
7
Non-standard Strategy Installation Instructions
If non standard strategy follow special installation instructions and jump to section 3 step 15.
01 0 0
01 0 0
2RA/2RW/4RW/2TW/4TW/
01 0 0
1 0 0
0
heat
1 0 0
0
cool
OUT4,5 damper
OUT4,5 damper
OUT4,5
If W2=0 (Winter Mode)
heating
OUT4,5
If W2=1 (Summer Mode)
cooling
OUT4,5
heat valve
OUT6,7
cool valve
OUT4
If W2=0 (Winter Mode)
heating
OUT4
If W2=1 (Summer Mode)
cooling
OUT4
heat valve
OUT6
cool valve
1 0 0
0
1 3 +
L
L AN
N ID
S tr at eg y
: : : : :
O /S
S er ia l N o
S
S
6
Check Strategy, Sensor/Fan/Heat Cool Outputs/Electric Heater
8
IN1
OUT1
heat
1 0 0
0
cool
01 0 0
01 0 0
01 0 0
01 0 0
01 0 0
Configuration (continued)
9
IQL13+/xxx Installation Instructions TG200383 Sheet 3
3
Page 9
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
3 - 1
3
Installation Instructions - Sheet 3
IQL13+/xxx LonMark Terminal Unit Controllers
SHEET 3: Installation Instructions - Sheet 3
3. Installation - Configuration (continued)
Fixing/ Configuration
10
IQL13+/xxx Installation Instructions, TG200383 ­Sheet 2
2
2RA/2RW/4RW/2TW/4TW/
1 3 +
L
L AN
N ID
S tra t eg y
: : : : :
O /S
S er ia l N o
Window
fan off
Check Operation - Window Contact Input
11
IN5
OUT1, 2, 3
if Window Mode (W5=1)
01 0 0
1 0 0
0
heat
1 0 0
0
cool
OUT4,5 damper
OUT4,5
valve closes
01 0 0
OUT4,5
heat valve
01 0 0
OUT6,7
cool valve
OUT4
OUT4
1 0 0
0
heat
1 0 0
0
cool
damper goes
to neutral
01 0 0
valve closes
01 0 0
heat valve
01 0 0
cool valve
OUT6
1 3 +
L
L AN
N ID
S tr a t eg y
: : : : :
O /S
S er ia l No
PIR if in standby
Pushbutton if non-occupied or standby
fan on
Check Operation
- Pushbutton or PIR Input
12
1 3 +
L
L AN
N ID
S tr a t eg y
: : : : :
O /S
S er ia l No
Local adjustment can be provided by TB/TS/K, /KE, /KEF or RD-IQL/K, /KOS, /KOSF (see section 1.3 step 8). Wait 6 secs at each end to calibrate potentiometer
Check Operation
- Local SP Adjust
13
If Fan Speed Auto
If Fan Speed Auto
IN4
OUT1, 2, 3
OUT1, 2, 3
IN2
Pb/PIR input type selected by configuration parameter W6
- see step 15 .
see table section 2.2 step 8
Pushbutton can be provided by TB/TS/KE, /KEF, or RD-IQL/KOS, /KOSF (see section 1.3 step 8)
1 0 0
0
heat
1 0 0
0
cool
see table section 2.2 step 8
Page 10
IQL13+/xxx Installation Instructions - Sheet 3
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
3 - 2
3. Installation - Configuration (continued)
Set up Strategy Parameters
15
if required
Use IqlTool2 (see section 2.2 step 5 ) and text communications
For standard strategies use table below, else refer to non-standard strategy installation instructions
If required the strategy type may be changed (e.g. /AR2 to /WR2) :
IQL13+/xxx data sheet TA200284
Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.
* Default depends on strategy
If used with RD-IQL (see section 1.3 step 8), the following must be configured: Local Space Temp Type
S9(Y=6), Local SP Adjust Type S10(Y=6), Local Fan Speed Type S11(Y=6), O=Pb I=PIR W6(S=O) default, Remote Fan Spd K7(V=4) default, followed by R(z=1) to write changes to flash and reset.
Configuration for RD-IQL is facilitated by IqlTool2.
If the sensor on IN1 is to be used, leave local Space Temp type at default, S9(Y=1). If the fan speed switch
on IN3 is to be used, leave Local Fan Speed type at default, S11(Y=3).
Check Operation - Fan Speed Select
14
1 3 +
L
L A N
N ID
S tr a te g y
: : : : :
O /S
S e ri al N o
A u t o
O f f
IN3
OUT1, 2, 3
If Occupied and Remote Fan Speed (K7) Auto
Fan Speed Switch can be provided by TB/TS/KEF or
RD-IQL/KOSF (see section 1.3 step 8)
retemaraPlebaLnoitcnuFtluafeD
)V(1KtniopteSetomeRyletomerdetsujdaebnactnioptesesaB C°02 )V(2KpmeTecapSetomeR de
tcennocsidrosneslacolfiro,rosnesnoLotdnuobfidesU C°02 )V(3KdnbdaeDCCOccOgnirudtnioptesdnuoradnabdaeD C°1 )V
(4KdnbdaeDybdnatSybdnatSgnirudtnioptesdnuoradnabdaeD C°2
)V(5KdnbdaeDCCONccoNgnirudtnioptesdnuoradnabdaeD
21 )V(6KccOetomeRybdnatS=3,ssapyB=2,ccoN=1,ccO=0etatssteS deipuccO=0 )V(7KdpSnaFetomeRotuA=4,hgiH=3,deM=2,wo
L=1,ffo=0deepssteS otuA=4
)V(8KtesffOPSetomeR detcennocsidsitsujdalacolfirorosneSnoLaotdnuobfidesU C°0
)V(5
1KegnartesffO.toptsujdaPSlacoLfoegnarsenifeD C°2
)S(1WepiP2=IepiP4=O )2TW,2RW(I=1W)2RA,4TW,4RW(O=1Wegnahcyg
etartS* )S(2WedoMremmuS )2TW/,2RW/rofdesuylno()ylnolooc(remmuSro)ylnotaeh(retniW retniW=O )S(3WelbasiDcelEIot
tesfiretaeHcirtcelEelbasiD celEelbane=O )S(4WriA=IretaW=O)RA(I=4W)TW,RW(O=4WegnahcygetartS* )S(5WedomwodniWOo
ttesfitcatnocmrala,IottesfitcatnocwodniW tcatnocmrala=O
)S(6WRIP=IbP=OOottesfinottubhsuP,IottesfiRIP nottu
bhsup=O )S(7WnoitidnoCtsorFdeipucconufi)2RA/ton(%89otgnitaehsedirrevO tsorfon=O )S(8WnwodtuhSetomeRorezotloo
c/taehstesdna,nafffostuhS nwodtuhson=O
)G(1LniaGpooLtaeH 04
)I(1LlargetnIpooLtaeH snim0
)G(2LniaGpooLlooC 04-
)I
(2LlargetnIpooLlooC snim0
Page 11
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
3 - 3
Installation Instructions - Sheet 3 IQL13+/xxx
Note 1: IqlTool2 facilitates setting of these parameters across the Lon segment Note 2: Changing any of these parameters results in a controller reset (clears down time and and sensor logs) Note 3: Any changes to these parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory. Note 4: IqlTool2 facilitates setting to timekeeper (sets up timemaster Lan and changes own address to 11) Note 5: Message code can only be changed by text comms if 'lonworks managed' (read only) is set to No .
Note 6: If PIN is forgotten see note in section 2.2 step 5
Using IqlTool2 (see section 2.2 step 5) and text communications
Set up System Core Firmware Module Parameters
if required - see conditions
16
3. Installation - Configuration (continued)
retemaraPgnitteSnoitcnuFnoitidnoCetoN
sserdda..(Rsserddanwo-LLQIfosserddaecivedegnarraerotderiuqerfi
sserdda,s
naL
,2,1
4
NaLnwo-NLQIforebmunnaLegnarraerotderiuqerfi
sserdda,snaL
2,1
reifitnedi-DLQIfoetubirttareifitneditxe
t,tnedimralaroF
smmocCI,smmoc
1
2etubirtta-FsetubirttasmmoctxetsmmocCI,smmoctxetroF1
3etubirtta-G 1
sserddamra
lanaLnwo-AnwofonaLdnasserdda
tegratmralanaL
aotsmralanaLtroperot
rosivrepus
1
naLmralanaLnwO-R 1
mralakrowten
retnI-E
sserdda
fonaLdnasserdda
mralakrowtenretnI
tegrat
krowtenretnitroperot
ylno(rosivrepusaotsmrala
QIdes
serddatsewolrof
)naLnoecivedmetsyS
1
naLmralakrowtenretnI-T 1
emityrterskroWnoL-r skroWnoLmetsySQIeeS
gniree
nignEstcudorP
sliatedroflaunaM
2
tekcapretniskroWnoL-i
yaled
2
ssalcecivresskroWnoL-a 2
ezisreffuBretuor-bezis
reffub
)setyb(
641=tluafeD
retuortsellamsseificeps
metsysnoreffub
etarapessretuorfI
dnasCNOL/sCNIL/sLQI
taht
rellamsezisreffubevah
tsellamsottes-setyb641
)66=muminim(.ezisreffub
2
egasseMskroWnoL-m
edoc
.rebmunedoc
46
=tluafeD
ybdesuedoC
lla,sCNOL/sCNIL/sLQI
esutsumsCNOL/sCNIL
edocemas
desugniebedocegassemfI
ebtsum-sresurehtoyb
metsySQIotevisulcxe
5,2
rebmunrotareneg-gtsolfiNIPdnifoT)ylnodaer(
dinoruen-eeuqinu
rofreifitnedi
noruen
o
t;tsolfiNIPdnifoT
edonnoLyfitnedi
)ylnodaer(
emiT..(TsruoH-HemittnerruCrofemitesinorhcnysoT
gniggoldnasmrala
setuniM-N
htnomfoyaD-DetadtnerruCrofetadesinorhcnysoT
gniggoldnasmrala
3
htnoM-M 3
raeY-Y 3
metsysfonaL-l
retsam
emit
stegrepeekemitLQI
taQImorfcnysemit
naLsihtno11sserdda
sihtfIrepeekemiteblliwLQI
'l orez-nonsiretemarap'
11=sserddanwodna
4,3
resU..(1UNIP-PQInirebmunNIPmorftcetorpoT
segnahcdesirohtuanu
6,3
level-lNIPfolevelytiroh
tuaorezfinoitcetorpoN3
Set up Lan System
17
LINC Installation Instructions TG103062
LINC
IQ
Lon
IQL
Check Lan
if required
IQ System LonWorks Products Engineering Manual - TE200292
Use PowerTool or Wupdn and terse text communications
PowerTool or Wupdn
Page 12
IQL13+/xxx Installation Instructions - Sheet 3
IQL13+/xxx Installation Instructions TG200383 Issue 3/B 19/08/04
3 - 4
Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
P.O. Box 34, Horsham, West Sussex, RH12 2YF United Kingdom Website www.trend-controls.com
Fax (UK) +44 (0)1403 241608Fax (International) +44 (0)1403 210982Telephone +44 (0)1403 21888
Registered office, Novar House 24 Queens Road Weybridge Surrey KT13 9UX Registered in England No 1664519Email trendinfo@novar.com
IQL
A1
A16
IC Comms
B1,0
B2,7
LINC
IQ
B18,0
B19,7
Lon
K1
W1
S1
K8
W8
I1
I16
S16
A17
A24
Nx
Nx
IC Comms ‘direction’ in IQ must be:
Global To, Min, Max, Sum, or Average (directions 2 to 6)
see IQ Configuration Manual 90-1533
Set up IC Comms from IQ
if required
19
IQL
LINC
IQ
Lon
Terse Text Comms
K1
W1
S1
K2 K8
W7
W8
I1 I8
S8
Set up Communications from Supervisor
if required
20
Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.
3. Installation - Configuration (continued)
IQL
IC Comms
LINC
IQ
Lon
Nx
K1
W1
S1
K2 K8
W7 W8
I1 I8
S8
Nx
LCI
IC Comms Module Nx(.. - (x=1 to y; y=4 for standard strategies)
Set up IC Comms from IQL
if required
18
retemaraPnoitcnuF
sserddaecivedetomeR-A
seificepsorez-nonfI.smmoc'otlabolg',orezfI
smmoc'otatad'rofsserdd
aecivedtegrat
etubirttA-B
,QItegratfoetubirtta,ylnosmmoc'otlabolg'roF
on'0(eludomsserddanietubirttasecne
refer
etubirtta'2,'reifitnedi'1,naLnosQIlla-,'etubirtta
)'3etubirtta'3,'2
naLetomeR-N
,orezsserdda,orezna
Lfi;rebmunnaLQItegraT
labolglabolgseificeps
lavretnI-I)setunim(gnidnesneewteblavretnI
egnahctnacifingiS-S
gnidneserofebegnahctsumeugolanatnuomA
gnirtsmetiecruoS-M ))V(1S.g.e(tnesgniebretemarapdnametI
rebmunelud
omnoitanitseD-E smmocCIgniviecereludomnoitanitsedfo.oN
epytnoitanitseD-T )K,W.g.e(smmocgniviecereludomnt
sedfoepyT
Use IqlTool2 (see section 2.2 step 5) and text communications
e.g. 963 (drag and drop values)
Note that standard strategy pages are available for 963 from Partnernet