TREND IQLROUTER_..._24VAC User Manual

Important: Retain these instructions
24V
230 VAC
Installation Instructions - Sheet 1
IQLROUTER/.../24VAC
IQL Lon Router
CONTENTS
1.1 Unpacking ............................................. 1-1
1.2 Storage ............................................. 1-1
1 INSTALLATION
1.1 UNPACKING
1.2 STORAGE
-10 °C
(14 °F)
+50 °C
(122 °F)
H O
2
Note that this product may involve Lonworks system integration . This procedure should only be performed by an installer with Lonworks engineering expertise.
!
90 %RH
0
1.3 Installation - Mounting ................................ 1-1
1.4 Installation - Configuration ......................... 2-1
2 Reset IQLROUTER/../24VAC ....................... 2-3
3 Disposal ............................................. 3-4
1
IQLROUTER/24 Installation Instructions TG200791
1
2
It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work
Regulations 1989. For USA install equipment in accordance with the National Electric Code.
Sheet 1 Sheet 2
Dimensions
1
185 mm (7.28”)
152 mm (5.98”)
89 mm (3.5”)
75 mm (3”)
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
45 mm (1.77”)
Requirements
2
a
b
L
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
10
7 8
9
12 13
6
PKT
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
1 - 1
IQLROUTER/../24VAC Installation Instructions - Sheet 1
24V
230VAC
H O
2
24V
230VAC
24 V
230 VAC
24V
230 VAC
24 V
230 VAC
1.3 INSTALLATION - MOUNTING (Continued)
Requirements (Continued)
2
c
L
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
8
10
7
9
1213
6
PKT
12
3 4
5
LON - B
LON - A
A-SVC- B
If not installed well outside normal
d
reach (e.g behind false ceiling)
L
OFF
OFF
FREE OFF
FREE
BUS
BUS
ON
OF F
11
7 8
10
9
12 13
6
PK T
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
BUS
ON
OFF
78 9 6
PKT
12
3 4
5
LON - A
A-SVC -B
FREE O FF
FREE BUS
11 10
121 3
LON - B
g For IQL ROUTER/NOVAR/UL/24VAC only
UL rated as 'UL916, open listed energy management equipment accessory’
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
10
7 8
12 13
9
6
PKT
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
OFF
FREE OFF
FREE
BUS
BUS
ON
OF F
11
7 8
10
9
12 13
6
PK T
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
Mounting
3
e
0 °C
(32 °F)
0
Protection: IP20
+45 °C
(113 °F)
90 %RH
f
Avoid locations where corrosive fumes or explosive vapours are present. Avoid electrical noise interference.
Either surface mount
ab
170 mm
(6.69”)
2 holes
6 mm (0.24”)
or DIN rail mount
a
1 - 2
b
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
c
Installation Instructions - Sheet 1 IQLROUTER/../24VAC
2 4V
23 0V AC
1.3 INSTALLATION - MOUNTING (Continued)
Lift hinged cover
c
4
a
CAUTION: Failure to use a screwdriver to open the cover will cause damage to the unit.
Connect Lonworks Bus
b
5
T e r m i n a to r
2
OF F
FR EE OFF
FR EE
BU S
O N
O FF
7 8
9
6
P KT
1 2
3
4
5
L ON - A
A -SV C- B
BU S
11
10
12 13
L ON - B
8 9 1 0 1 1L o n B
Lon
Lon
Lon
Polarity independent
T e r m in a t o r
Terminal size 0.5 to 2.55 mm (14 to 20 AWG)
Network Side A Network Side B
4 5 6 7
L o n A
Lon
Polarity independent
Lonworks - FTT (free topology) Star topology* Bus topology* Loop topology*
T e r m i n a to r
*Terminate Lonworks bus at one point only
Terminate at IQLROUTER using integrated Lon terminater link A (see step 6).
elbaChtgnelsubxaMedonotedonxaM
20158nedleB)tf0461(m005)tf0461(m005
002/FH/61/0/1/PTdnerT
)1748nedleB(
GWA22,VIleveLLU)tf0461(m005)tf0131(m004
8.0x2x2Y)tS(YJ)tf0461(m005)tf0501(m023
865AIT)tf5741(m054)tf028(m052
GWA42,5.taCA
Terminated using integrated Lon terminater link B (see step 6)
Integrated Lon terminater link A set to OFF (see step 6)
(m005)tf0131(m004
)tf0461
SCN
LonA
Do not allow wires to cross on a loop
LonA
LonB
IQL ROUTER
A
1
4
3
1
2
B
3
2
LINC
LonB
SCN
Maximum 64 nodes per Lonworks segment Maximum 40 IQLs (and LONCs) per virtual Lan
IQL ROUTER
B
A
3
1
2
4
3
1
2
IQL
IQL
y
4
x
IQL
4
x
y
x
IQL
y
y
x
Terminated using integrated Lon terminater link B (see step 6). If used with LPT-10 (powered bus), cable lengths differ - see Link Power Transceiver User’s Guide (078-0105-01C) available from Echelon.
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
1 - 3
IQLROUTER/../24VAC Installation Instructions - Sheet 1
2 4 V
2 4V
2 30 V AC
2 4V
2 30 V AC
1.3 INSTALLATION - MOUNTING (Continued)
SET Lon Terminator Links
6
OFF
O F F F R E E
O F F F R E E
Terminate Lonworks bus at one point only
No terminator. Lonworks bus must be terminated elsewhere.
FREE Use to terminate Lonworks bus at IQL Router
OF F
FR EE OF F
O N
O FF
1 2
P K T
3
4
5
A -S V C -B
BU S
7 8
6
1 0
9
L O N - A
FR EE
BU S
1 1
1 2 1 3
L O N - B
Connect Power
7
DO NOT
Switch on
1
2
24Vac
3
Earth (ground) 24 Vac input power neutral at transformer
WARNING: This apparatus must be earthed (grounded) using earth
(ground) terminal.
IQLROUTER/24 consumption =2VA
Close Hinged Cover
8
Sheet 2
9
2
OF F
FR EE OF F
O N
O FF
1 2
P K T
3
4
5
A -S V C -B
BU S
7 8
6
1 0
9
L O N - A
FR EE
BU S
1 1
1 2 1 3
L O N - B
Clean earths (grounds) consisting of short (<300 mm, 12”) stranded copper wire (>=1.5 mm2, 16 AWG) to a substantial earthed (grounded) metal part (e.g. cable tray) are recommended.
Terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
ab
IQLROUTER/../24VAC Installation Instructions ­Sheet 2
1 - 4
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
1.4 INSTALLATION - CONFIGURATION
O N
O FF
OF F
BU S
FR EE OF F
BU S
FR EE
1 2
3
4
5
P KT
2 4V
6
7 8
9
10
11
12 13
L O N - A
L O N - B
A -S VC -B
23 0V A C
O N
O F F
2 4V
23 0V A C
Sheet 1
1
2
IQLROUTER/../24VAC Installation Instructions ­Sheet 1
Installation Instructions - Sheet 2
IQLROUTER/.../24VAC
IQL Lon Router
Switch ON
2
Power Supply
Check Router
3
Power
O
I
check power
1 2
Packet
O N
3
4
5
A -S VC -B
O FF
P KT
IQLROUTER
OF F
FR EE OF F
BU S
11
7 8
6
10
9
L O N - A
2
Service
FR EE
BU S
12 13
L O N - B
...
...
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
Contact Trend
...
Contact Trend
2 - 1
IQLROUTER/../24VAC Installation Instructions - Sheet 2
2 4V
23 0V A C
24V
230 VAC
24 V
230 VAC
1.4 INSTALLATION - CONFIGURATION (Continued)
Install using Lonworks Network Manager Tool
4
if a binding IQLs to LonMark devices or b LINCs version <3.23 straddle router.
or c changing Lon Router from Bridge to Learning
Router, Configured Router, or Repeater
O N
1 2
3
4
5
OF F
FR EE OF F
BU S
O FF
7 8
9
6
P KT
L O N - A
A -S VC -B
FR EE
BU S
11
10
12 13
L O N - B
When installing IQLROUTER in Lonworks tool press service button when requested for each side of network.
See Lonworks network manager tool manual. See the Lonworks
2
Technical Guide (installation and fault finding). Lonworks System Integrator must have Lonworks engineering expertise.
Close Panel (For IQL ROUTER/NOVAR/UL/24VAC only)
5
UL rated as 'UL916, open listed energy management equipment accessory’
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
10
7 8
9
12 13
6
PKT
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
OFF
FREE OFF
FREE
BUS
BUS
ON
OF F
11
7 8
10
9
12 13
6
PK T
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
2 - 2
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
Installation Instructions - Sheet 2 IQLROUTER/../24VAC
2 4V
23 0V A C
O N
O F F
2 4V
23 0V A C
24V
230 VAC
24 V
230 VAC
24V
230 VAC
24 V
230 VAC
2 RESET IQLROUTER/24
If the addresses of IQ System devices have been changed it is necessary to reset the IQL Router to force its routing table to be regenerated. This is done by powering the unit OFF, and then ON.
Open Panel (For IQL ROUTER/NOVAR/UL/24VAC only)
1
OFF
FREE OFF
FREE
BUS
BUS
ON
OF F
11
7 8
10
9
12 13
6
PK T
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
10
7 8
12 13
9
6
PKT
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
UL rated as 'UL916, open listed energy management equipment accessory’
Switch OFF
2
OF F
FR EE OF F
O N
1 2
3
4
5
A -S VC -B
BU S
O FF
7 8
9
6
P KT
L O N - A
FR EE
BU S
11
10
12 13
L O N - B
Switch ON
3
O N
O F F
OF F
FR EE OF F
O N
1 2
3
4
5
A -S VC -B
BU S
O FF
7 8
9
6
P KT
L O N - A
FR EE
BU S
11
10
12 13
L O N - B
Close Panel (For IQL ROUTER/NOVAR/UL/24VAC only)
5
UL rated as 'UL916, open listed energy
OFF
FREE OFF
FREE
BUS
BUS
ON
OF F
11
7 8
10
9
12 13
6
PK T
1 2
3
4
5
LO N - B
LO N - A
OFF
FREE OFF
FREE
BUS
BUS
ON
OFF
11
10
7 8
12 13
9
6
PKT
1 2
3
4
5
LO N - B
LO N - A
A-S VC-B
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
A-S VC-B
management equipment accessory’
2 - 3
IQLROUTER/../24VAC Installation Instructions - Sheet 2 3 DISPOSAL
WEEE Directive :
At the end of their useful life the packaging, and product should be
Do not dispose of with normal household waste. Do not burn.
disposed of by a suitable recycling centre.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)869-8400, Fax: (425)869-8445 www.trend-controls.com
2 - 4
IQLROUTER/../24VAC Installation Instructions TG200791 Issue 1/C 5/5/06
Loading...