devices. Suitable anti-static precautions
should be taken throughout this
operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of
electrostatic sensitive devices.
Fix Main Screw
6
adrill hole
8
aspot holes
dhang on screw
Fix Screws
binsert screw
Ø 6 mm
blift off screw
7
efix screws
Hang on Screw
cdrill holes
306 mm
322 mm
1 - 2
Ø 6 mm
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
Page 3
Installation Instructions - FixingIQ241/242
1.3 Installation - Fixing (continued)
9
Replace Lid
ahook on lid
bclose lid
ctighten fasteners
Fit ENCLS/CMTRAY
11
14
if required
if fitting ENCLS/CMTRAY
ENCLS/CMTRAY Installation
Instructions TG103131
pierce grommet
Connect power
A switch or circuit breaker must be included in the supply to the unit and be
in close proximity to it, and must be clearly marked as the disconnecting
device for the unit
if /230
230 Vac +15, -10%, 50 to 60 Hz
IQ241/242 consumption >60 VA
if /24VAC or /24VDC
24 Vac +15 -10%, 50 to 60 Hz
24 Vdc +25, -10% (24 V to 36 V)
IEC
O
I
DO NOT
SWITCH
ON
WARNING:
This apparatus must
be earthed.
(via power connector)
12
Mat-N-Loc
Route Cables
if CMTRAY fitted
or
use copex glands
if /24VAC
24 Vac: Isolated
transformer winding
supply 1 controller only
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
3
Page 9
SHEET 3: Installation Instructions - Options
3.1 Replacing the Battery (continued)
Installation Instructions - Options
IQ241/242
Series Controllers
8
Continue
Continued from
IQ241/242
Installation
Instructions
Sheet 2
Replace Battery
11
SAFT LM2450 3 V
Remove Lid
9
a undo screws
b lift lid
c remove lid
3
Caution: This unit contains static sensitive devices. Suitable
anti-static precautions should be taken throughout
this operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of
electrostatic sensitive devices.
Close Hinged Plate
12
Lift Hinged Plate
10
Warning: The lithium battery must not be recharged,
+
disassembled, burnt or short circuited.
Misuse may cause explosion or fire.
Dispose of carefully. Refer to Health and
Safety Executive Guidance Note GS43.
Close Flap
14
15
Switch on
16
O
I
Wait
10s
13
ahook on lid
bclose lid
Replace Lid
ctighten screws
17
If not IQ2v3 (IQ2v3 will reset RAM
automatically)
Switch off. Complete Zero Address/
Baud Rate Switch Reset section
steps 2 to 7.
Reset RAM
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
3 - 1
Page 10
IQ241/242Installation Instructions - Options
3.1 Replacing the Battery (continued)
18
IQ241/242
also set time, day, date
Download Strategy
SET
X.IQ2
Close Panel
20
OR
SET Manual TE200147
9 F'D'
Cable/EJ101442
I Q 2 4 1 / 2 4 2
Reconnect Supply to I/O
21
RJ11
O
I
Replace
ENCLS/CMTRAY Cover
19
if ENCLS/CMTRAY fitted
I Q 2 4 1
I Q 2 4 1
3.2 Replacing the Fuse (/24VAC, /24VDC only)
Switch Off, Isolate, Remove Lid, Lift
1
Plate
Complete 'Replacing the Battery' (section 2.3, steps 2 to
10).
Close Plate, Replace Lid,
3
Switch On, Reconnect
Complete 'Replacing the Battery' (section 3.1,
steps 12 to 53, and steps 18 to 20).
3.3Zero Address/Baud Rate Reset
1
Replace Fuse
2
4 A
1¼”
Backup, Switch off, Isolate, Remove cover
Complete 'Replacing the Battery' steps 1 to 5
3 - 2
2
Note the Network Address and Baud Rate
ON
ADDRESS
Address = 2 + 16 = 18
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
= 19k2 baud
1K2
9K6
19K2
= 9k6 baud
1K2
9K6
19K2
= 1k2 baude.g.
1K2
9K6
19K2
SET
NOT SET
Page 11
Installation Instructions - OptionsIQ241/242
3.3Zero Address/Baud Rate Reset (continued)
Set All Switch Poles to Zero
3
ON
ADDRESS
Address = 0 Baud = 0
Reset the Network Baud Rate
6
19k2 baud
1K2
9K6
19K2
9k6 baud
19K2
9K6
= B
1K2
Baud Rate = B
= B
= B
Switch on
4
Wait for Relays
5
Reset the Network Address
7
ON
ADDRESS
e.g Address = 2 + 16 = 18
SET
NOT SET
Address = A
≠ A
O
I
'click'
IQ241/242
= A
≠ A
1k2 baud
1K2
9K6
19K2
Download strategy,
8
Replace cover, Reconnect
supply to I/O
Complete 'Replacing the Battery' steps
18 to 21
Fix to Wall
No. 12
OR
4
= B
Remove
Backplate
address
1, 4 to 9, 11 to 119
0, 2, 3, 10, or > 119
≠ A
3.4 Mounting in an Enclosure, ENCLs/...
Open Door
1
5
Lift Flap and
Remove Lid
Repeat Steps
6 to 9 above
in 'Replacing
the Battery'
section
2
6
Drill Wall
560 mm
560 mm
Fix Main Screw in
Backplate3
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
3 - 3
Page 12
IQ241/242Installation Instructions - Options
3.4 Mounting in an Enclosure, ENCLs/... (continued)
7
10
Hang on Screw
Close Flap
11
Fix Screws
8
Replace
Backplate
12
Replace Lid
9
Repeat step 13 above in
'Replacing the Battery'
section
Close Door
3.5 Connecting a Remote 2 Line Display (if KIT/2xx/RDS has been fitted)
Ensure/RDS
1
Installed
KIT/2xx/RDS Installation
Instructions TG103128
2
Connect
Display
(FPK or HDP)
Test
3
Display Panel
Manual
90-1505
3.6 Disposal
WEEE Directive :
At the end of their useful life the packaging and
product should be disposed of via a suitable
Do not dispose of with normal household waste.
Do not burn.
recycling centre.
4
angle adjust screw
if faint
Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or changes.
P.O. Box 34, Horsham, West Sussex, RH12 2YF United Kingdom
Telephone +44 (0)1403 211888
Registered office. 24 Queens Road Weybridge Surrey KT13 9UX Registered in England No 1664519
3 - 4
IQ241/242 Series Controllers Installation Instructions TG103012 Issue 2/D 07/4/05
Fax (International) +44 (0)1403 210982
Website www.trend-controls.com
Fax (UK) +44 (0)1403 241608