TREND HT-D User Manual

Duct Humidity and Temperature Sensors
Important: Retain these instructions
1 Unpacking
2 INSTALLATION
Installation Instructions
HT/D
HT/D Installation Instructions TG200988
1
2
c
Dimensions
33 mm (1.3”)
Location
electronics
-5 °C (23 °F)
-20 °C (-4 °F)
0 °C (32 °F)
V > 10 m/s, 33’/s
+50 °C (122 °F)
+60 °C probe (140 °F)
+40 °C measurement (104 °F)
12 mm diam (0.47”)
263 mm (10.35”)
ba
HO
2
Protection :IP65
M16 gland
0 %RH
100 %RH non-condensing
97 mm (3.82”)
H T / D
T r e n d C o n t r o l S y s t e m s
94 mm (3.7”)
105 mm (4.31”)_
85 mm (3.35”) centres57 mm (2.74”)
Prepare duct
3
either for screwing directly to duct
Ø 15 mm (0.59”)
a
42.5 mm (1.67”)
b
2 pilot holes
42.5 mm (1.67”)
c
or for using optional mounting flange
a c
4 holes Ø 4 mm (0.16”)
HT/D Duct Humidity and Temperature Sensors Installation Instructions TG200988 Issue 1/A 30/01/08
45 mm
(1.77”)
Ø circle
Ø 23 mm
(0.91”)
e
b
foam washer
f
d
1
HT/D Installation Instructions
2 INSTALLATION (Continued)
Remove lid
4 5
a
b
Wire to Controller
7
HT/D
Remove Connector
I-P I-N TH TH
Insert cable through gland
6
either use flexible conduit
or use M16 cable gland
IQ1 & IQ2
C (+24V)
} humidity
IN C
} temperature
IN
terminate screens at IQ end
2 analog input channels
linked for current (I)
linked for thermistor (T)
N
N+1
IQ3
humidity
temperature
linked for current (I)
linked for thermistor (T)
0 (0V) N (in)
I-P I-N TH TH
+ (+24V)
0 (0V) N+1 (in) + (+24V)
terminate screens at IQ end
HT/D/2%
IQ1 & IQ2
C (+24V) I-P I1N I2N
IN
C (+24V)
IN
} humidity
} temperature
2 analog input channels
linked for current (I)
linked for current (I)
terminate screen at IQ end
N
temperature
N+1
IQ3
humidity
linked for current (I)
linked for current (I)
0 (0V) N (in)
I-P I1N I2N
+ (+24V)
0 (0V) N+1 (in) + (+24V)
terminate screen at IQ end
Note that when connecting to IQ3, in order to provide sufficient supply current to the sensor, the sensor I-P terminal must be connected to both channels’ 24 V terminals.
Replace Connector
8
2
HT/D Duct Humidity and Temperature Sensors Installation Instructions TG200988 Issue 1/A 30/01/08
Replace Lid
9
Installation Instructions HT/D
2 INSTALLATION (Continued)
Mount Sensor
10
or if using optional mounting flange
either if screwing directly to duct
abadjust depth
b
2 x No 6 x 20 mm screws DIN 7481
Configure IQ
11
or
IQ
Set up IQ Sensor types
12
It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the following SET Unique Sensor References should be used:
Humidity HT/D, HT/D/2% :Humidity I Temperature HT/D/2% :PRT I 0+40 (°C)
Temperature HT/D :Thermistor HTST DT (°C)
PRT I +32+104 F (°F)
Thermistor HTST DT F (°F)
IQ
IQ Configuration Manual
90-1533
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in appropriate tables below. Note that for IQ3 the scaling mode and exponent (E) do not need to be set up. For all other IQ controllers see Sensor Scaling Reference Card TB100521A
Temperature (thermistor) HT/D
(0 to +40 °C, 32 to 104 °F)
Test System
13
stinU
Y
E*
U
L
P
xxI)C°(xO)F°(xO
1
2
3
4
5
6
C°F°
epyttupnI
tnenopxE
reppU
rewoL
stnioP
146.205221
74.304401
64.40368
366.60105
866.7023
201.85-32
3
05221
5-32
6
Temperature (current) HT/D/2%
)stlovrotsimreht(1
(0 to +40 °C, 32 to 104 °F)
Humidity (current)
HT/D and HT/D/2%
(0 to 100 %RH)
C°F°
stinU
epyttupnI
Y
U
L
P
xxIxO
2
tnenopxE
E*
reppU
rewoL
stnioP
4023
1
0204401
Y
E
U
P
xxIxO
reppU
rewoL
L
stnioP
1 40
2 02001
epyttupnI
tnenopxE
)tnerruc(2
3
04401
023
2
)Amrruc(2
3
001
0
2
Δ T
IQ
Δ H
3 FAULT FINDING
stluaFsesuaCelbissoPseidemeR
emitesnopsergnoLdetullopretliFretlifecalpeR
eruliafetelpmoCylppusrewopoNelbacdna
hgih
ootgnidaerytidimuH
HT/D Duct Humidity and Temperature Sensors Installation Instructions TG200988 Issue 1/A 30/01/08
ylppusrewopkcehC
eborprosnesnonoitasnednoCyrassecenfiretlifecalperdnaeborpyrD
3
HT/D Installation Instructions
D O W N U P
4 MAINTENANCE
Over time, the sensing element may become covered in dust. The dust can be removed using compressed air. Under no circumstances should water or cleansing agents be used on the sensing elements.
It is recommended that the accuracy of the sensor is verified every 12 months. If the sensor falls outside the quoted accuracy, replace the filter and recalibrate as shown below
Replace filter
1
c ACC/HTD/FILTER d
Caution: Do not touch humidity sensing element
3
a
Remove lid
b
Caution: This unit contains static sensitive
damage to the units. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices.
devices. Suitable anti-static precautions should be taken throughtout the operation to prevent
Two point calibration
5
For calibration over whole working range
Start calibration at lower humidity point.
Difference between the two points should be >30%RH
Low Humidity Calibration
1 Remove lid from the calibration chamber (ACC/CAL/HT) and
clean chamber thoroughly.
2 Insert one of the cloths provided with the calibrating liquid. Pour
calibrating liquid (ACC/CAL/HT/35%) onto the fabric. Refit lid and screw tightly.
3 Insert probe into sensor aperture of chamber and tighten collar to
provide air tight seal around the probe. Wait 30 min. 4 Press Down pushbutton for 3 s to start. LED will illuminate. 5 Press Up or Down pushbutton to adjust measured value in 0.1%
steps. 6 Either: Press Up pushbutton for 3 s to stop. Calibrated value
is stored. LED is extinguished.
Or: Press Down pushbutton for 3 s to exit calibration without
storing value. LED is extinguished.
High Humidity calibration
7 Remove lid from the calibration chamber (ACC/CAL/HT) and
clean chamber thoroughly. 8 Insert one of the cloths provided with the calibrating liquid. Pour
calibrating liquid (ACC/CAL/HT/80%) onto the fabric. Refit lid
and screw tightly. 9 Insert probe into sensor aperture of chamber and tighten collar
to provide air tight seal around the probe. Wait 30 min. 10 Press Up pushbutton for 3 secs to start. LED will illuminate. 11 Press Up or Down pushbutton to adjust measured value in 0.1% steps 12 Either: Press Up pushbutton for 3 s to stop. Calibrated value
is stored. LED is extinguished.
Or: Press Down pushbutton for 3 s to exit calibration without
storing value. LED is extinguished.
ba unscrew
See Section 5, Disposal
Keep sensor and humidity
Place probe in humidity chamber
Keep temperature constant
push buttons
Preparation
2
chamber in same room for 4 hours before.
30 mins before.
during calibration.
Locate buttons
4
calibration LED
One point calibration
6
For calibration over limited range about single point
This calibration decreases accuracy over remainder of working range
Single Point Humidity Calibration
1 Remove lid from the calibration chamber (ACC/CAL/HT) and
clean chamber thoroughly.
2 Insert one of the cloths provided with the calibrating liquid. Pour
calibrating liquid (ACC/CAL/HT/35% or /80%) onto the fabric. Refit lid and screw tightly.
3 Insert probe into sensor aperture of chamber and tighten collar to
provide air tight seal around the probe. Wait 30 min.
2 Either: (If chamber humidity >50%RH.) Press Up pushbutton
for 3 s to start. LED will illuminate. Or: (If chamber humidity <50%RH.) Press Down pushbutton for
3 s to start. LED will illuminate.
3 Press Up or Down pushbutton to adjust measured value in 0.1%
steps
4 Either: Press Up pushbutton for 3 s to stop. Calibrated value
is stored. LED is extinguished. Or: Press Down pushbutton for 3 s to exit calibration without
storing value. LED is extinguished.
Replace Lid
7
5 DISPOSAL
Test System
8
Δ T
IQ
Please send any comments on this or any other Trend technical publication to techpubs@trendcontrols.com
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
©Trend Control Systems Limited 2007. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Δ H
Do not dispose of with normal household waste. Do not burn.
WEEE Directive :
At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
4
HT/D Duct Humidity and Temperature Sensors Installation Instructions TG200988 Issue 1/A 30/01/08