HMM Series Heat Meters Installation Instructions TG201136 Issue 3, 23/07/2012 3
Installation Instructions HMM Series
3
Mounting (continued)
3 INSTALLATION (continued)
This symbol indicates that the HMM/HC models are fully encapsulated for reliable protection against
condensation on the integrator board.
Protection class: IP68.
Either mount temperature sensor in ball valve or adapter
A B C D
1. For ball valve only, close the ball valve and unscrew the plug screw from the ball valve.
2. For ball valve or adaptor place an O-ring on the mounting pin (A). The second O -ring is spare.
3. Insert the O-ring into the hole of the ball valve or adapter with the mounting pin using turning movements
(B).
4. Position the O- ring in its nal position using the other end of the mounting pin (C).
5. Place the two halves of the plastic screw around the temperature sensor. Press the two halves together
so that the two studs on one half of the plastic screw t into the holes on the other half (D).
6. Insert the temperature sensor with the plastic screw into the ball valve or adaptor and tighten the plastic
screw by hand.
7. Check for leaks.
1. Mount pocket in pipe.
2. Insert probe as far as bottom of pocket and tighten
screw.
3. Fill pocket with thermally conductive oil.
4. Seal pocket.
Fixing Kit
Note that the sensor xing kit (HMAC/SENSORFIXKIT ) is not
required if mounting the sensor in a pocket. The xing kit is only
required if mounting in a ball valve or adapter.
One xing kit is provided with DN15/20 meters (only one is
needed for these as the other sensor is already tted in the body
of the unit).
Two xing kits will be required to be purchased separately for
DN25/40 meters if using ball valves or adapters.
split screw
‘O’-ring
mounting pin
Sensor pocket for DN15/20 (HMAC/POCKET34MM)
L1 = 34 mm, D1 = G
1
/2 B
Sensor pocket for DN25/40 (HMAC/POCKET50MM)
L1 = 50 mm, D1 = G
1
/2 B
Or mount temperature sensor in pocket