TREND GVCPI User Manual

CLOSED POSITION SWITCH FOR GV SERIES SOLENOID VALVES
APPLICATION
The closed position switch can be used at GV series solenoid valves to indicate the position of the main valve.
(1“) valves
GVCPI-32-40: for GVS32, 32 mm (1¼“) and GVS40, 40 mm
(1½“) valves
GVCPI-50: for GVS50, 50 mm (2“) valve GVCPI-65S: for GVS65, 65 mm (2½“) valve GVCPI-65F-80: for GVF65, 65 mm (2½“) and GVF80, GVS80
80 mm (3“) valves
GVCPI-100: for GVF100, 100 mm (4“) valve
GVCPI
DATA SHEET
WARNING
Take care that the installer is a trained and
experienced service man.
Turn off gas supply before starting installation.
Disconnect power supply to prevent electrical
shock and/or equipment damage.
INSTALLATION
1. Check that the switch has the correct model number corresponding to the valve body size to ensure a proper fit of switch to valve.
2. Remove the 1/4" plug at the bottom of the valve body.
3. Ensure that the O-ring is applied to the brass mounting nut, to effect a proper seal.
4. Tighten the switch to the valve body by using a 17 mm wrench.
5. Realign the switch housing to the valve body.
6. Perform a leakage test, to ensure the proper seal of the switch to the valve body.
ADJUSTMENT
1. Ensure that the valve is in the closed position.
2. Ensure that the switch is in the open position, with the contacts at the terminals 1 and 3 in the open position.
3. Turn the adjustment screw at the bottom of the switch unit clockwise till the switch closes, with the contacts at terminal 1 and 3 in closed position.
4. Turn the adjustment screw an additional 1/2 turn clock­wise, to achieve some overtravel at the switch.
5. Operate the solenoid valve several times to ensure pro­per functioning of the switch.
SPECIFICATIONS
Operational voltage: Electrical rating at 250V: Max. current 3A
Electrical connection: Plug connection according PG 9
Enclosures: IP65
Ambient temperatures:
-15 °C..60 °C
GVCPI Data Sheet TA200889 Issue 1/A 05/09/05 1
WIRING
Follow the instructions, supplied by the appliance manufacturer.
Electric circuit of switch terminals
EN2C-0053SZ20 R0705
GVCPI Data Sheet
DISPOSAL
WEEE Directive :
At the end of their useful life the packaging and product should be disposed of by a suitable
Do not dispose of with normal household waste. Do not burn.
recycling centre.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com