Trane Tracer, ZN510 User Manual

WSHP-IOP-2 May 1998
Installation, Operation, and Programming
Tracer™ ZN510 Controller
Literature History
The Trane Company has a policy of continuous product improvement and it reserves the right to change specifications and design without notice.
Library Service Literature
Product Section Unitary
Product Water-Source Heat Pumps
Model 000
Literature Type
Sequence 1
Date April 1998
File No. SL-UN-000-WSHP-IOP-2-0498
Supersedes New
Related Literature
z CNT-IOP-1 ZN510 1 Controller:
Installation, Operation, and Pro­graming
z WSHP-PD-1 Water-Source Heat
Pump Controller Product Data Sheet
WSHP-IOP-2
Installation, Operation, and Programming
z WMCA-PD-1 ZN510 Loop Con-
troller Product Data sheet
z WSHP-IOP-3 ZN510 Water-
Source Heat Pump Controller Installation, Operation, and Pro­gramming Guide
z WMCA-IOP-1 ZN510 Controller
Installation, Operation, and Pro­gramming Guide
© 1998, American Standard Company

Table of Contents

Start-up Procedure 4 Power-up Sequence 5 Unit Identification Tag 6 Unit Operation 7
General Information 7 Communication 7 Power 8 Binary Outputs 8 Analog Outputs 9 Binary Inputs 9 Analog Inputs 12
Zone Sensors 15 Heating or Cooling Control
Mode Operation Single or Dual Compressor
Operation Data Sharing 20 Configuration 21 Troubleshooting 22 Diagnostics 27 ZN510 Controller Replacement 28 Wiring Diagram 29 Hardware Specifications 31 Appendix 33
18
19

Start-up Procedure

Installation of New Units
1. Follow all instruction for
installation of water source heat pumps as detailed in the IOM (Installation Operation Maintenance manual).
2. Disconnect power or disable
the circuit breaker to unit.
3. Run communication link wire to
field terminal strips 14 and 16. (See wiring diagram in the unit).
4. Install zone sensor to low
voltage control terminals 1 through 6. (See wiring diagram in the unit and zone sensor submittals).
Zone Sensor Placement
Zone sensor location is an important element of effective room control and comfort.
The best sensor location is typically on a wall, remote from the Readings at this location assure that the desired setpoint is achieved across the space, not just near the unit itself. It may be necessary to subdivide the zone with multiple units to ensure adequate control and comfort.
HVAC unit.
5. Verify that water connections
have been made to unit, then ensure that water is circulating through the unit.
6. Reapply power.
7. Check for STATUS GREEN LED
operation to ensure power and communication has been made
to the ZN510
Peel IDENTIFICATION TAG from unit and place in the ZN510 IOP, on a copy of Sheet 6 of this document, or on building plans for future location use. The actual room location on the tag may be hand written.
The following are typical areas where the zone sensor should not be mounted:
z Near drafts or “dead spots”
(e.g., behind doors or corners)
z Near hot or cold air ducts
z Near radiant heat (e.g., heat
emitted from appliances or the sun)
z Near concealed pipes or
chimneys
z On outside walls or other non-
conditioned surfaces
.
z In air flows from adjacent zones
or other units
4

Power Up Sequence

Power Up Sequence
When 24 VAC power initially is applied to the ZN510 controller, the following sequence occurs:
1. All outputs are controlled off.
2. The controller reads all inputs
to determine their initial values.
Note: Because the space tempera­ture can be hardwired to the con­troller or communicated, the controller waits for several minutes to check for the presence of a com­municated value.
3. A random start time is hard
coded on every board and cannot be disabled. The board generates a random time delay between 0 and 25 seconds. Once this time expires, the power up control wait time (if configured) will wait for 120 seconds. The power up control wait allows ample time for a communicated request to arrive. If the power up control wait time expires, and the controller does not receive a communicated occupancy command, the unit assumes stand alone operation.
4. Normal operation begins.
5
Unit Identification Tag
The unit identification tag is factory mounted and provided for easy identification of an installed unit. It contains model number, tagging, and location information. See Figure 1.
The top portion of the unit identification tag remains permanently affixed to the unit for identity purposes. The bottom portion of the tag provides pertinent information that is removable to be placed on building plans or in the ZN510 IOP on page 33. This provides identification history about the unit’s location for quick reference.
These tags provide information about unit location, unit serial number, and NID (neuron identification number). The NID is similar to the serial number of the unit but is specific to the identification of the ZN510 Board. The location identification is a customer defined, clear English description, of the unit’s physical location. This is a 27 character description of the location. For example, if the location identification for a unit is “Conference Room 101”, the ZN510 and Rover (the Trane Comm 5 service tool) will recognize this clear English description so maintenance can be performed on the appropriate unit. If location identification is not defined, it will default to the unit serial number. This provides some information so the user has multiple references to the unit. The blank location is provided for field modification in case the unit is moved from the initial location.
Unit Identification Tag
Figure 1: Unit Identification Tag
Note: Fold and tear carefully along dashed
removable line.
6

Unit Operation

General Information
The ZN510 controller is a microprocessor-based direct digital controller that controls a variety of water source heat pump equipment including:
z Standard efficiency horizontal
and vertical units up to 10 tons.
z High efficiency horizontal and
vertical units.
Figure 2: Communication connections
Communication
The ZN510 controller communicates via Trane’s Comm5 protocol. Typically, a communication link is applied between unit controllers and a building automation system. Communication is also possible
with Trane’s service tool Rover
.
ZN510 provides a total of six 1/4-inch quick-connect terminals for connection to the Comm5 communication link. These connections include:
z Two terminals (TB2-1, TB2-2)
z Console water source heat
pumps.
ZN510 is designed to provide accurate and reliable zone temperature control by using custom proportional integral (PI) algorithms. The controller is factory installed and configured to support:
z Single fan speed.
are provided for direct con­nection of Rover to the ZN510 Board or provided as spare ter­minals.
z Two terminals (TB2-3, TB2-4)
are connected to the field terminal strip (1TB1-14, 1TB1-16) for connection to the communication link (daisy chain).
z Up to two compressors.
z Reversing valve.
z 2-position outdoor air damper
or generic binary output.
Peer-to-peer communication across controllers is possible even when a building automation system is not present. ZN510 is also adaptable as a standalone system.
z Two terminals (TB2-5, TB2-6)
are connected to the field terminal strip (1TB1-5, 1TB1-6) which should be connected to the zone sensor communication jack. This provides direct connect of Rover to the commu­nication link without having to connect directly to the ZN510 board or provided as spare ter­minals.
z The field terminal strip 1TB1
provides screw terminations for all field connections.
TB2-1
COMM COMM COMM
Space Communication Connection
20 pole low voltage terminal strip screw connections for field hook-up
Figure 3: Communication Wiring
7
TB2-2
TB2-3
1TB1-14
Communication Link
1TB1-16
TB2-4
TB2-5
TB2-6
1TB1-5
1TB1-6
Zone Sensor
Unit Operation
Power
The ZN510 controller is powered by 24
VAC. A total of two 1/4-inch quick-
connect terminals are provided for 24 VAC connection to the board. See
Figure 4 for ZN510 power requirement.
Note: Power for field installed ancil­lary devices is not available from the board. It must be tapped at trans­former. See Table 21 for excess power available.
Binary Outputs
The ZN510 uses five of its binary outputs to control heat pump units. Outputs are load side switching triacs. The triac acts as a switch by either making or breaking the circuit between the load (reversing valve, damper, contactor, relay) and ground.
See Figure 5 for the configuration of the five binary outputs.
Factory Supplied Transformer
Line
Vol tage
24VAC
Figure 4: Power Connections
Field installed 2 position damper actuator
24VAC
1TB1-17
1TB1-18
2-Position Damper Actuator or Generic Binary Output
Binary output 6 (BOP 6) is factory configured to control a normally closed 2-position outdoor air damper. It may be field modified to control a generic output for control by a building automation system. If set up as a generic output, the controller does not use BOP 6 as part of the normal control. A building automation system must issue commands to control the generic binary output.
Note:
z During occupied mode, the
outdoor air damper is closed when the fan is controlled off.
z During unoccupied mode, the
outdoor air damper normally remains closed.
z 2-position damper must not
exceed 10 VA power output from board.
Figure 5: Binary outputs
BOP 1 (Fan)
BOP 2 (Reversing Valve)
J1-1
J1-2
BOP 4 (Not Used)
J1-4
BOP 5 (Compressor 1)
J1-5
BOP 3 (Not available)
J1-3
Binary Outputs
.
Table 1: BOP 6 control of a 2-position outdoor air damper
Model Fan Operation Outdoor Air Damper
Occupied
Occupied warm up or cool down
Occupied standby On or cycling Closed
Unoccupied Cycling Closed
Diagnostic present Diagnostic dependent Closed
On or cycling Off
On or cycling Closed
Open Closed
BOP 6 (Compressor 2)
J1-6
BOP 7
J1-7
8
Unit Operation
Output Overrides
The ZN510 controller includes a manual output test function. Use this feature to manually exercise the outputs in a defined sequence. The purpose of the test sequence, is to verify output and end device operation. Use the manual output test to:
z Verify output wiring and
operation without using Trane’s service tool, Rover.
Analog Outputs
Binary Inputs
The ZN510 controller has three available binary inputs (BI). These inputs are factory-configured for the following functions:
z BI 1= Low temperature
detection (freezestat) (Circuit 2).
z BI 2 = Condensate overflow.
z BI 3 = Occupancy or generic
binary input.
Each binary input may be configured as not used depending on options selected. BI 3 is configured as a normally open occupancy input, but may be field modified for generic binary input which is only supported by a build­ing automation system.
Note: The diagnostic functions related to binary inputs such as low tempera­ture detection and condensate
overflow are fixed sequences.
Each binary input associates an input signal of 0 VAC with open contacts and 24 VAC with closed contacts. See Figure 6 for typical binary input configurations for the heat pump.
z Force compressor operation,
allowing the technician to use refrigerant gauges or other test equipment to verify unit operation.
The test sequence resets unit diagnostics and attempts to restore normal unit operation prior to testing the outputs. If the diagnostics remains after a reset, the status LED indicates the diagnostic condition is still present and has affected the
ZN510 does not use analog outputs.
Low Temperature Detection (Circuit 2)
Condensate Overflow
Field Wired Occupancy Input
J2-1
BI 1
J2-2
J2-3
BI 2BI 3
J2-4
J2-5
J2-6
Figure 6: Binary inputs.
Table 2: Binary input configurations
Binary Input Description
BI 1
BI 2 Condensate Overflow
BI 3
Low Temperature Detection (Cir 2)
Occupancy Normally open Unoccupied Occupied
Generic Normally open Normal Normal
manual output test. See Troubleshooting section for Green LED and Testing Heat Pump Configurations on page 21 & 22.
Binary Inputs
ConfigurationContact
Closure
Normally closed
Normally closed
Normal Diagnostic
Normal Diagnostic
Contact
Open
Note: See Page 10 for specific information concerning BI 1, BI 2 and BI 3.
9
Unit Operation
Low Temperature Detection
The low temperature detection
temperature condition exists for that circuit.
outdoor air damper also operates
normally. diagnostic protects the heat exchanger by using an analog leaving water temperature sensor to protect refrigerant circuit 1 and a binary low temperature detection device to protect refrigerant circuit
2. Each individual refrigerant circuit is disabled when the low
For two compressor units, the controller responds to low temperature detection by allowing the fan to operate, while disabling the compressor for the faulty circuit. The compressor for the normal circuit continues to operate. The
All unit operation is disabled when
the heat pump shuts down both
circuits, due to low temperature
conditions. See Table 3 for more
information.
Table 3: ZN510 response to low temperature detection diagnostic
Description
Low Temperature Detection
(Circuit 1)
Low Temperature Detection
(Circuit 2)
Low Temperature Detection
(Circuits 1 and 2)
Fan
Operation
Enabled
Enabled
Disabled
Compressor Operation
Circuit 1-Disabled Circuit 2-Normal Operation
Circuit 1-Normal Operation Circuit 2-Disabled
Circuit 1-Disabled Circuit 2-Disabled
Damper
Operation
Normal operation
Normal operation
Closed
Note:
z The low temperature detection device automatically resets when the heat exchanger temperature returns to
normal. However, you must manually reset the low temperature detection diagnostic to clear the diagnostic and restart the unit. Refer to page 28 on how to reset a unit.
z If BOP 6 is configured as a generic binary output, the state of the output is not affected by the low temperature
detection diagnostic or by other diagnostics.
Condensate Overflow
A condensate overflow switch detects the condensate condition. The condensate overflow switch is a normally closed device. This switch is physically connected to the binary input 2 (BI 2). When the condensation reaches the trip point, the binary input detects the diagnostic condition. A condensate overflow signal generates a diagnostic which disables the fan, disables all compressors, and closes the 2-position outdoor air damper (when present). The condensate overflow diagnostic does not affect the generic binary output (when present).
Note: The condensate overflow switch, located in the condensate pan, auto­matically resets when the conden­sation returns to normal levels. However, you must manually reset the controller’s condensate over­flow diagnostic to clear the diagnos­tic and restart the unit. Refer to page 28 on how to reset a unit.
Occupancy
ZN510 uses the occupancy binary input for two occupancy-related functions. For standalone controllers (any unit not receiving a communicated occupancy request, typically from a building automation
system), the occupancy binary input
determines the unit’s occupancy
based on the hardwired signal.
Typically, the signal is a dry set of
binary contacts which is either
connected to a switch or timeclock
contacts.
When a hardwired occupancy signal
is open, the unit switches to
occupied mode (if the occupancy
input is configured as normally
open). When a hardwired
occupancy signal is closed, the
controller switches to Unoccupied
mode.
10
Loading...
+ 22 hidden pages