Trane YSC060, YSC120, YSC060AD, YSC072AD, YSC090AD Installation Operation & Maintenance

...
®
Installation Operation Maintenance
Packaged Gas/Electric YSC060 - YSC120 50 Hz
RT-SVX31A-EN
Introduction
Literature Change History
Y_C-IOM-2 (March 2004) Added Phase Monitor
Y_C-IOM-2 (March 2003) Orginal issue YSC060 - YSC120 mod­els.
Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installa­tion, operation, and maintenance pro­cedures for air cooled systems. By carefully reviewing the information within this manual and following the in­structions, the risk of improper opera­tion and/or component damage will be minimized.
It is important that periodic mainte­nance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure oc­cur, contact a qualified service organi­zation with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
Model Number Description
All products are identified by a multiple­character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identi­fication code is provided below. Its use will enable the owner/operator, install­ing contractors, and service engineers to define the operation, specific compo­nents, and other options for any spe­cific unit.
When ordering replacement parts or re­questing service, be sure to refer to the specific model number and serial num­ber printed on the unit nameplate.
CAUTION
Equipment Damage From Ultraviolet (UV) Lights!
The manufacturer does not recom­mend field installation of ultraviolet lights in its equipment for the in­tended purpose of improving indoor air quality. High intensity C-band ultraviolet light is known to severely damage polymer (plastic) materials and poses a personal safety risk to anyone exposed to the light without proper personal protective equip­ment. Polymer materials commonly found in HVAC equipment that may be susceptible include insulation on electrical wiring, fan belts, thermal insulation, various fasteners and bushings. Degradation of these materials can result in serious damage to the equipment.
©American Standard Inc. 2007 All rights reserved
The manufacturer accepts no responsibility for the performance or operation of our equipment in which ultraviolet devices were installed outside of the manufacturer’s factory or its approved suppliers.
RT-SVX31A-EN
Contents
Introduction
Literature Change History ................. 2
Overview of Manual .......................... 2
Model Number Description ............... 2
Unit Nomenclature ............................ 4
General Information
Unit Nameplate ................................. 5
Compressor Nameplate .................... 5
Unit Description................................. 5
Economizer Control Actuator
(optional) ........................................... 5
ReliaTel Trane Communication Interface
(optional) ........................................... 5
ReliaTel LonTalk Communication Interface
(optional) ........................................... 5
ReliaTel Options Module
(optional) ........................................... 5
System Input Devices
and Functions .............................6 & 7
Pre - Installation
Unit Inspection .................................. 8
Unit Storage ...................................... 8
Unit Installation Clearances .............. 9
Unit Dimensions .............................. 10
Unit / Accessory Weights ................ 12
Rigging and Center-of-Gravity Data 12
Installation
Foundation ...................................... 13
Unit Supply & Return Air Openings. 14
Ductwork ......................................... 15
Roof Curb........................................ 15
Rigging ............................................ 16
Factory Installed Economizer.......... 16
Temperature Limit Switch Usage
for Gas Heat Units...........................17
Gas Heat Technical Data ................ 17
Horizontal Discharge Conversion
YSCO60 .......................................... 18
YSC072 - 120 ................................. 19
TCO-A Instructions:......................... 20
Requirements for Gas Heat ............ 21
Condensate Drain Configuration..... 21
Condensate Trap Installation .......... 21
Filter Installation .............................. 22
Main Unit Power Wiring .................. 22
Field Installed Control Wiring .......... 22
Control Power Transformer............. 22
Controls using 24 VAC ....................22
24V AC Conductors with Reliatel .... 23
Controls using
DC Analog Input/Outputs ................ 23
Customer Low Voltage Routing- ..... 24
Typical Field wiring
for Optional Controls- ...................... 25
Sp ace Temperature Averaging ........26
Temperature vs Resistance.............27
Sizing Natural Gas Pipe
Mains & Branches ........................... 27
Voltage Imbalance...........................28
Electrical Phasing ........................... 28
(Three Phase Motors) ..................... 28
Pre - Start
Service Test Guide for
Component Operation..................... 30
Verfiying Proper Airflow................... 31
Economizer Start-up........................32
Compressor Start-Up ...................... 32
Scroll Compressors......................... 32
Gas Heat Units................................ 32
Final System Setup
Final System Setup ......................... 33
Maintenance
Fan Belt Adjustment -......................34
Belt Tension Gauge......................... 35
Filters .............................................. 36
Cooling Season............................... 36
Heating Season .............................. 36
Annual Maintenance ....................... 37
Final Process .................................. 37
Sample Maintenance Log ............... 38
Trouble Shooting
ReliaTel Control...............................39
System Status Checkout Procedure 39
LED 4 (Service)............................... 39
System failure ................................. 39
Heating Failure................................ 39
Cooling Failure ................................ 40
Service Failure ................................ 40
Simultaneous Heat and Cool Failure40
Cool Failure..................................... 40
Cooling and Ignition Lockouts ......... 40
Zone Temperature Sensor
(ZTS) Service Indicator ................... 40
Fan Failure Switch .......................... 41
Zone Temperature Sensor
(ZTS) Test ....................................... 41
Zone Temperature Thermistor
(ZTEMP) ......................................... 41
Cooling Set Point (CSP) and
Heating Set Point (HSP) ................. 41
Testing
serial communication voltage.......... 41
Wiring Schematic
Control Schematic........................... 43
Power Schematic ............................ 44
RT-SVX31A-EN
3
Model Number Description
Unit Nomenclature
Digit 1 - Product Type
Y = Packaged Gas/Elect
Digit 2 - Unit Efficiency Level
S = Standard
Digit 3 - Airflow Configuration
C = Convertible
Digit 4, 5, 6 - Cooling Capacity
060 = 5 Ton ( 17.6 KW ) 072 = 6 Ton ( 21.1 KW ) 090 = 7 1/2 Ton ( 26.4 KW ) 102 = 8 1/2 Ton ( 29.9 KW ) 120 = 10 Ton ( 35.1 KW )
Digit 7 - Major Design Sequence A
Digit 8 - Electrical Characteristics
D = 380-415/50/3
Digit 9 - Unit Control
R = Relia Tel
Digit 10 - Heat Capacity
H = Gas Heat - High L = Gas Heat - Low
Digit 11 - Minor Design Sequence
*
Digit 12, 13 - Service Digit Sequence
**
Digit 14 - Factory Installed Options
-Fresh Air Section
0 = No Fresh Air A = Manual OA, 0 - 25% B = Motorized OA, 0 - 50% C = Economizer Dry Bulb D = Economizer with Barometric Relief E = Economizer, Reference Enthalpy F = Economizer, Reference Enthalpy, with Barometric Relief G = Economizer Comparative Enthalpy H = Economizer, Comparative Enthalpy, with Barometric Relief
Digit 15 - Factory Installed Options
-Supply Fan
0 = Standard Drive 1 = Oversize Motor
Digit 16 - Factory Installed Options
-Hinged Service Access
0 = Standard Panels A = Hinged Service Panels
Digit 17 - Factory Installed Options
-Condenser Coil Protection
0 = Standard 1= Hail Guard 2 = Epoxy Coated Condenser Coil 3 = Epoxy Coated Condenser Coil and Hail Guard 4 = CompleteCoat Condenser Coil 5 = CompleteCoat Condenser Coil and Hail Guard
Digit 18 - Factory Installed Options
-Through The Base
0 = Without Through The Base Connection
Digit 19 - Factory Installed Options
-Disconnect Switch/Circuit Breaker
0 = Without Disconnect Switch/Circuit Breaker 3 = With Phase Monitor
Digit 20 - Factory Installed Options
-Convenience Outlet
0 = Without Convenience Outlet
Digit 21 - Factory Installed Options
-Communications
0 = Without Communications Options 1 = Trane Communications Interface 2 = LoneTalk Communications Interface
Digit 22 - Factory Installed Options
-Refrigeration System
0 = Without Refrigeration System Op­tion
Digit 23 - Factory Installed Options
-Refrigeration Controls
0 = Without Refrigeration Controls
Digit 24 - Factory Installed Options
-Smoke Detector
0 = Without Smoke Detector
Digit 25 - Factory Installed Options
-System Monitoring Controls
0 = Without Monitoring Controls 1 = Clogged Filter Switch 2 = Fan Failure Switch 3 = Discharge Air Sensing Tube 4 = Clogged Filter Switch and Fan Failure Switch 5 = Clogged Filter Switch and Discharge Air Sensing Tube 6 = Fan Failure Switch and Discharge Air Sensing Tube 7 = Clogged Filter Switch, Fan Failure Switch and Discharge Air Sensing Tube
RT-SVX31A-EN4
General Information
Unit Nameplate
A Mylar unit nameplate is located on the unit’s corner support next to the fil­ter access panel. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the side of the compressor.
Hazard Identification
Warnings are provided throughout this manual to indicate to installing contractors, operators, and service
personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious in­jury.
Cautions are provided throughout this manual to indicate to installing contractors, operators, and service
personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrig­erant and compressor oil, and run tested for proper control operation.
The condenser coils are aluminum fin, mechanically bonded to copper tubing.
Direct-drive, vertical discharge con­denser fans are provided with built-in thermal overload protection.
The ReliaTel™ Control Module is a mi­croelectronic control system that is re­ferred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/In­tegral control algorithms perform spe­cific unit functions that governs unit op­eration in response to; zone tempera­ture, supply air temperature, and/or hu­midity conditions depending on the ap­plication. The stages of capacity control for these units are achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory wired to the re­spective internal components. The RTRM receives and interprets informa­tion from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable re­quest for cooling.
Economizer Control Actuator (Optional)
ReliaTel™ Control
The ECA monitors the mixed air tem­perature, return air temperature, mini­mum position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds (2.82 N-m) of torque and is powered by 24 VAC.
RTCI - ReliaTel™ Trane Communication Interface (Optional)
This module is used when the applica­tion calls for an ICS ment type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is neces­sary.
TM
building manage-
RLCI - ReliaTel™ LonTalk Communication Interface (Optional)
This module is used when the applica­tion calls for an ICS ment type control system that is LonTalk. It allows the control and moni­toring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruc­tion that ships with each kit when field installation is necessary.
TM
building manage-
RTOM - ReliaTel™ Options Module (Optional)
The RTOM monitors the supply fan proving, clogged filter, supply air tem­perature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke de­tector. Refer to system input devices and functions for operation.
5RT-SVX31A-EN
General Information
System Input Devices & Functions
The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat se­lected to interface with the RTRM.
The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematic for the specific module connections.
The following controls are available from the factory for field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch can be con­nected to sense indoor fan operation: FFS (Fan Failure Switch) If air flow through the unit is not proven by the dif­ferential pressure switch connected to the RTOM (factory set point 0.07 “ w.c.(17.4 Pa)) within 40 seconds nomi­nally, the RTRM will shut off all me­chanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash. The system will remain locked out until a reset is ini­tiated either manually or through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is con­nected to the RTOM. A diagnostic SER­VICE signal is sent to the remote panel if the pressure differential across the fil­ters is at least 0.5" w.c. (124.5 Pa). The contacts will automatically open when the pressure differential across the fil­ters decreases to approximately 0.4" w.c. (99.6 Pa). The clogged filter output is energized when the supply fan is op­erating and the clogged filter switch has been closed for at least 2 minutes. The system will continue to operate regard­less of the status of the filter switch.
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB.
If this circuit is open before the com­pressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is im­mediately turned “Off”. The compres­sor will not be allowed to restart for a minimum of 3 minutes should the con­tacts close.
If four consecutive open conditions occur during the first three minutes of operation, the compressor for that cir­cuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor.
Low Pressure Control ReliaTel Control
When the LPC is opened for 1 con­tinuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes.
If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communi­cated to ICS manual reset will be required to restart the compressor.
High Pressure Control (Optional) ReliaTel Control
The high pressure controls are wired in series between the compressor out­puts on the RTRM and the compres­sor contactor coils. If the high pres­sure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.
On dual circuit units, if the high pressure control opens, the compressor on the
TM
if applicable, and a
affected circuit is locked out. A manual re­set for the affected circuit is required.
ReliaTel Control
The power exhaust fan is started when­ever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on.
The setpoint panel is located in the re­turn air section and is factory set at 25%.
Lead/Lag Control (Dual Circuit Only) ReliaTel Control Only
Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/ Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compres­sor or refrigeration circuit switches. When the RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor.
Zone Sensor Module (ZSM) (BAYSENS006B)
This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS008B)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS017B.
RT-SVX31A-EN6
General Information
Zone Sensor (BAYSENS010B)
This electronic sensor features four sys­tem switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’s. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS017B.
Programmable Zone Sensor ­(BAYSENS019B)
This 7 day programmable sensor fea­tures 2, 3 or 4 periods for Occupied or Unoccupied programming per day. If the power is interrupted, the program is retained in permanent memory. If power is off for an extended period of time, only the clock and day may have to be reset.
The Zone Sensor allows selection of 2, 3 or 4 system modes (Heat, Cool, Auto, and Off), two fan modes (On and Auto). It has dual temperature selection with programmable start time capability.
The occupied cooling set point ranges between 45 F (7.2 C)and 98 F (35.6 C) degrees. The heating set point ranges between 43 F (6.1 C) and 96 F ( 35.6 C) degrees.
A liquid crystal display (LCD) displays zone temperature, temperature set points, day of the week, time, and op­erational mode symbols.
The Option Menu is used to enable or disable applicable functions, i.e.; Morn­ing Warm-up, Economizer minimum po­sition override during unoccupied sta­tus, Fahrenheit or Centigrade, Supply air tempering, Remote zone tempera­ture sensor, 12/24 hour time display, Smart fan, and Computed recovery.
During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts
AC with one set of single pole double throw contacts is activated.
Status Inputs (4 Wires Optional) The ZSM can be wired to receive four (4) operating status signals from the RTRM (HEAT, COOL, SYSTEM “ON”, SER-VICE). Four (4) wires from the RTRM should be connected to the appropriate terminals (7, 8, 9 & 10) on the ZSM.
Remote Zone Sensor (BAYSENS013B)
This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated Comfort management system.
TM
building
Remote Zone Sensor (BAYSENS014B)
This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated ComfortTM build­ing management system.
Remote Zone Sensor (BAYSENS016A)
This bullet type temperature sensor can be used for; outside air (ambient) sens­ing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered. Wir­ing procedures vary according to the particular application and equipment in­volved. Refer to the unit’s wiring dia­grams for proper connections.
Remote Zone Sensor (BAYSENS017B)
This electronic sensor can be used with BAYSENS006B, 008B, 010B, 019B Re­mote Panels. When this sensor is wired to a BAYSENS019B Remote Panel, wiring must be 18 AWG (.75mm Shielded Twisted Pair (Belden 8760 or
2
)
equivalent). Refer to The specific Re­mote Panel for wiring details.
BAYSTAT036A
Single Stage - 1 Heat/1 Cool
BAYSTAT037A
Multi Stage - 2 Heat/2 Cool - Can be Used for Economizer Operation
BAYSENS025A
Remote sensor for BAYSTAT036A and BAYSTAT037A
Phase Monitor (Optional)
ReliaTel Control Only
This sensor monitors voltage between the 3 conductors of the 3 phase power supply. Two LED lights are provided. The green light indicates that a bal­anced 3 phase supply circuit is prop­erly connected. The red light indicates that unit operation has been pre­vented. There are two conditions that will prevent unit operation.The power supply circuit is not balanced with the proper phase sequence of L1,L2,L3 for the 3 conductors of a 3 phase circuit. The line to line voltage is not between 180 volts and 633 volts.
Unit Inspection
7RT-SVX31A-EN
General Information
As soon as the unit arrives at the job site
[ ] Verify that the nameplate data
matches the data on the sales order and bill of lading (including electrical data).
[ ] Verify that the power supply complies
with the unit nameplate specifica­tions.
[ ] Visually inspect the exterior of the
unit, including the roof, for signs of shipping damage.
If the job site inspection of the unit re­veals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the dam­age on the “bill of lading” before sign­ing.
[ ] Visually inspect the internal compo-
nents for shipping damage as soon as possible after delivery and before it is stored. Do metal base pans.
not walk on the sheet
Take precautions to prevent conden­sate from forming inside the unit’s electrical compartments and motors if:
a. the unit is stored before it is in-
stalled; or,
b. the unit is set on the roof curb, and
temporary heat is provided in the building. Isolate all side panel ser­vice entrances and base pan open­ings (e.g., conduit holes, S/A and R/ A openings, and flue openings) from the ambient air until the unit is ready for start-up.
Note: Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed under “Starting the Unit”.
The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumula­tion on the unit’s electrical and/or me­chanical components.
Unit Clearances
Figure 1 illustrates the minimum op­erating and service clearances for ei­ther a single or multiple unit installa­tion. These clearances are the mini­mum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating effi­ciency.
Providing less than the recom­mended clearances may result in condenser coil starvation, “short-cir­cuiting” of exhaust and economizer airflows, or recirculation of hot con­denser air.
[ ] If concealed damage is discovered,
notify the carrier’s terminal of dam­age immediately by phone and by mail. Concealed damage must be re­ported within 15 days.
Request an immediate joint inspec­tion of the damage by the carrier and the consignee. Do not remove dam­aged material from the receiving lo­cation. Take photos of the damage, if possible. The owner must provide reasonable evidence that the dam­age did not occur after delivery.
[ ] Notify the appropriate sales repre-
sentative before installing or repair­ing a damaged unit.
Storage
RT-SVX31A-EN8
Pre - Installation
Figure 1
Typical Installation Clearances for Single & Multiple Unit Applications
9RT-SVX31A-EN
Figure 2
Unit Dimensional Data YSC060AD
Unit Clearances
1775
RT-SVX31A-EN10
Figure 2 - Continued
Unit Dimensional Data YSC072AD, YSC090AD
Unit Dimensions
Unit Dimensional Data YS102AD, YSC120AD
11RT-SVX31A-EN
y
Unit / Accessory Weights
Table 1 Typical Unit Weights & Point Loading Data
Net Net
Unit Weight Unit Weight
Model (lbs) ABCDLengthWidth Model (kg) ABCDLengthWidth
YSC060AD* 574 179 140 119 136 32 20 YSC060AD* 260 81 63 54 62 810 510 YSC072AD* 772 249 198 141 184 39 22 YSC072AD* 350 113 90 64 83 990 560 YSC090AD* 923 306 243 165 210 38 21 YSC090AD* 419 139 110 75 95 970 530 YSC102AD* 957 310 252 175 220 40 22 YSC102AD* 434 141 114 79 100 1020 560 YSC120AD* 1060 342 277 197 245 40 22 YSC120AD* 481 155 126 89 111 1020 560
Corner Wt. (lbs) of Gravit
Center Center
(In.)
Corner Wt. (kg) of Gravity (mm.)
Typical Accessory Weights
Net Weights lbs
Accessory 5 Ton 6 - 10 Tons Accessory 5 Ton 6 - 10 Tons
Economizer 26 36 Economizer 12 16 Barometric Relief 7 10 Barometric Relief 3 5 Motorized Outside Air Damper 20 30 Motorized Outside Air Damper 9 14 Manual Outside Air Damper 16 26 Manual Outside Air Damper 7 12 Roof Curb 70 115 Roof Curb 32 52 Oversized Motor 5 8 Oversized Motor 2 4 Coil Guards 12 20 Coil Guards 5 9 Hinged Doors 10 12 Hinged Doors 5 5 NOTES: (1) Net weight should be added to unit weight when ordering factory-installed accessories.
1
Net Weights (kg)
Figure 3
LIFTING AND MOVING INSTRUCTIONS!
DO NOT USE CABLES (CHAINS OR SLINGS) EX­CEPT AS SHOWN. OTHER LIFTING ARRANGE­MENTS MAY CAUSE EQUIPMENT DAMAGE OR SERI­OUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE SAME LENGTH. ADJUST AS NECESSARY FOR EVEN LEVEL LIFT.
Rigging and Center-of-Gravity Data
1
USE SPREADER BARS AS SHOWN IN DIAGRAM. RE­FER TO TABLE 1 FOR UNIT WEIGHT.
RT-SVX31A-EN12
Installation
Foundation
Horizontal Units
If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a “full perimeter” support struc­ture or a slab foundation for support. Refer to Table 1 for the unit’s operating and point loading weights when constructing a footing foundation.
If anchoring is required, anchor the unit to the slab using hold down bolts or iso­lators. Isolators should be installed to minimize the transmission of vibrations into the building.
For rooftop applications, ensure the roof is strong enough to support the com­bined unit and support structural weight. Refer to Table 1 for the unit operating weights. If anchoring is required, anchor the unit to the roof with hold-down bolts or isolators.
Check with a roofing contractor for proper waterproofing procedures.
13RT-SVX31A-EN
Installation
Figure 4-1
YSC060AD Horizontal Unit Supply & Return Air Opening
YSC072AD - 120AD Horizontal Unit Supply & Return Air Opening
Figure 4-1
YSC060AD Downflow Unit Supply & Return Air Openings
YSC072AD - 120AD Downflow Unit Supply & Return Air Openings
Supply
Return
RT-SVX31A-EN14
Installation
Ductwork
Figure 4-1 illustrates the supply and re­turn air openings as viewed from the rear of the unit.
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
When attaching the ductwork to the unit, provide a water tight flexible con­nector at the unit to prevent operating sounds from transmitting through the ductwork.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
Roof Curb
Note: All Gas/Electric units shall be installed on a roof curb that is a minimum height of 5.0 inches ( 127 mm ), or in any other manner such that the distance between the bottom of the intake vents of the gas section and grade of the surface that the unit is installed on is no less than 19.7 inches ( 500 mm ).
Downflow
The roof curbs for these units consists of a “full perimeter” enclosure to sup­port the unit.
Before installing any roof curb, verify;
1. That it is the correct curb for the unit,
2. That it includes the necessary gas­kets and hardware,
3. That the purposed installation loca­tion provides the required clearance for proper operation.
4. Insure that the curb is level and square. The top surface of the curb must be true to assure an adequate curb-to-unit seal.
Step-by-step curb assembly and instal­lation instructions ship with each acces­sory roof curb kit. Follow the instruc­tions carefully to assure proper fit-up when the unit is set into place.
Note: To assure proper condensate flow during operation, the unit (and curb) must be level.
If the unit is elevated, a field con­structed catwalk around the unit is strongly recommended to provide easy access for unit maintenance and ser­vice.
Recommendations for installing the Supply Air and Return Air ductwork join­ing the roof curb are included in the curb instruction booklet. Curb ductwork must be fabricated and installed by the installing contractor before the unit is set into place.
Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter.
If a Curb Accessory Kit is not used:
a. The ductwork can be attached
directly to the factory-provided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit.
b. For “built-up” curbs supplied by
others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
15RT-SVX31A-EN
Loading...
+ 33 hidden pages