Trane XT302C User Manual

XT302C Deluxe Programmable
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M17106
Heat-Cool Thermostat
18-HD25D7-5
INSTALLER'S GUIDE
APPLICATION
The XT302C Deluxe Programmable Heat-Cool Thermostat provides electrnic control of 24 Vac single-zone multistage systems. Refer to Table 1 for a general description of the thermostat. This thermostat requires a common wire to supply power.
Table 1. Description of XT302C.
Model System Changeover System Selection Fan Selection Comments
XT302C Multistage Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by
keyboard.
RECYCLING NOTICE
If this thermostat is replacing a thermostat that contains mercury in a sealed tube, do not place your old thermostat in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
INSTALLATION
When Installing this Thermostat...
1. Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. Avoid installing the thermostat where it can be affected by the following:
• Drafts, or dead spots behind doors and in corners.
• Hot or cold air from ducts.
• Radiant heat from sun or appliances.
• Concealed pipes and chimneys.
• Unheated (uncooled) areas such as an outside wall behind the thermostat.
Wallplate Installation
Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate for appearance only (the thermostat will function properly even when not level).
Fig. 1. Typical location of thermostat.
® U.S. Registered Trademark Copyright © American Standard Inc. 1999
69-1213-1
XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT
THERMOSTAT
WALL
B RW2
Y1 Y2 G
W1
HH
OT OT
WIRES THROUGH WALL
WALL ANCHORS (2)
MOUNTING HOLES
MOUNTING SCREWS
M15044
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two 3/16
inch holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
BLUE
YELLOW
COMPRESSOR CONTACTOR 2
COMPRESSOR CONTACTOR 1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
BROWN
WHITE
HEAT STAGE 1
BLACK
HEAT STAGE 2
GREEN
FAN
RED
HUMIDISTAT OPENS ON RISE TAYSTAT253A
OUTDOOR TEMPERATURE SENSOR TAYSENS100A
TRANSFORMER
Fig. 3. Typical hookup of XT302C in a heat cool system.
FOR STRAIGHT
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
INSERTION STRIP 5/16 IN. (8 MM).
M4826
Fig. 4. Proper wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and wallplate.
See Fig. 5.
2. Press lower edge of case to close and latch.
NOTE: To remove thermostat from wall, first pull out at
bottom of thermostat; remove top last.
L1 (HOT)
L2
M17116
1
WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookup diagram. A letter code is located near each terminal for identification.
WARNING
Electronic Shock or Equipment Damage Hazard. Can shock individuals or cause equipment damage.
Disconnect power before wiring to prevent electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4.
NOTE: Use 18 gauge, color-coded thermostat cable
for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
Pub. No. 18-HD25D7-5
69-1213—1 (T8624)
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
PRESS LOWER
B.
EDGE OF CASE TO LATCH.
M17151
Fig. 5. Mounting thermostat on wallplate.
2
XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT
SET WAKE TIMES AND SETPOINTS
INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
SET CURRENT OR PROGRAM DAY
ENTER INDEFINITE OR TIMED HOLD MODE
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
Run
Program
Hold Temp
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
Set Current
Day/Time
Day
Daylight
Time
Time
Copy
Fig. 6. XT302C key locations and descriptions.
Using Thermostat Keys
The thermostat keys are used to:
• Set current day and time,
• Program times and setpoints for heating and cooling,
• Temporarily override program temperatures,
• Display present setting,
• Configure Installer Setup,
• Check Self-Test,
• Display outdoor temperature (optional accessory),
• Set the system operation, and
• Set the fan operation. See Fig. 6 for keypad explanation.
SETTINGS
System and Fan Settings
The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Figs. 7 and 8. The fan settings can be set for each program period individually. The system selection is for all the program periods.
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET RETURN TIMES AND SETPOINTS
Leave
Wake
Heat/Cool
Settings
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
Set Program
Return Sleep
SystemFilter Fan
SELECT FILTER EXPIRATION IN NUMBER OF DAYS
SET SLEEP TIMES AND SETPOINTS
SET LEAVE TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION (HEAT, COOL, OFF, AUTO)
M17118
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
Set Current
Run
Day/Time
Program
Hold Temp
Leave
Wake
Return Sleep
Set Program
Time
Heat/Cool
Day
Daylight
Time
SystemFilter Fan
Settings
Copy
System
System
Heat
Auto
Off
Cool
Fig.7. System key location and display.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Fan operates with equipment.
Set Current
Run
Day/Time
Program
Hold Temp
Leave
Wake
Return Sleep
Set Program
Time
Heat/Cool
Day
Daylight
Time
SystemFilter Fan
Settings
Copy
Fan
Fig. 8. Fan key location and display.
M12956
Fan
M12957
Auto
On
NOTE: Always press the keys with your fingertip or similar
blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
Pub. No. 18-HD25D7-5
3
69-1213—1 (T8624)
XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT
Temperature Settings
Refer to Table 2 for the default program. For 7-Day and 24-Hour Operation, the settings are the same for each day of the week. Refer to the Owners Guide, Pub. No. 22-5127-04, for instructions on changing the default settings.
Table 2. Default Program Settings.
Period Time
Setpoint
Wake 6:00 AM 70°F
(21°C)
Leave 8:00 AM 62°F
(16.5°C)
Return 5:00 PM 70°F
(21°C)
Sleep 10:00 PM 62°F
(16.5°C)
The Leave, Return and Sleep periods may be cleared. For example, the daytime energy-savings period (from Leave to Return) may not be used by the homeowner. To clear any period, follow the instructions in the Owners Guide in the
Heat
Clearing Schedule Period
Comfort-R™ CONTROL
Adaptive Intelligent Recovery™ CONTROL (A HONEYWELL TRADEMARK)
COOLING DROOP
TEMPERATURE DISPLAY
CLOCK FORMAT
SYSTEM SETTING (HEATING AND COOLING SETTING)
OUTDOOR TEMPERATURE DISPLAY
PROGRAMMING
M17110
OFF ON
ON
ON
FARENHEIT (°F)
24-HOUR CLOCK FORMAT
AUTO/MANUAL (SYSTEM AUTOMATICALLY SELECTS HEAT OR COOL; YOU CAN SELECT HEAT, COOL OR OFF.)
NO OUTDOOR TEMPERATURE IS DISPLAYED
7-DAY PROGRAMMING
section.
OFF (CONVENTIONAL RECOVERY)
OFF
CENTIGRADE (°C)
24-HOUR CLOCK FORMAT
MANUAL ONLY (YOU SELECT HEAT, COOL OR OFF.)
NO OUTDOOR TEMPERATURE IS DISPLAYED
24-HOUR PROGRAMMING
Figure 9. Customizing Your Thermostat chart,
from Owners Guide, Pub. No. 22-5127-04.
Cool
Setpoint
78°F (25.5°C)
85°F (29.5°C)
78°F (25.5°C)
82°F (28°C)
Fan
Setting
Auto
Auto
Auto
Auto
AUTO ONLY (SYSTEM AUTOMATICALLY SELECTS HEAT OR COOL)
CONSTANT TEMPERATURE SETPOINT PROGRAMMING
INSTALLER SETUP
The Installer Setup is used to customize the thermostat for specific systems. Some of the options include Comfort-R™ control activation, Fahrenheit vs. Centigrade temperature display, outdoor temperature display (requires outdoor sensor installation), and system changeover. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the XT302C Deluxe Programmable Multistage Thermostat .
NOTE: For most applications, the thermostat factory-
IMPORTANT
Installer Setup Procedure
settings apply. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section.
The chart Customizing Your Thermostat found in the beginning of the Owners Guide (see Fig. 9) must be completed. The homeowner identifies the options you install by referring to this chart.
1. Press and hold the Information , Increase ▲, and Decrease keys at the same time until all display segments and the first setup number displays (all display segments appear for approximately three seconds before the setup number displays). See Figs. 11 and 12.
Set Program
Hold for
Em Ht
Start Time
Aux Ht
Mon
TueWedThuFriSatSun
Wake
LeaveReturnSleep
Set Day/Time
AM
PM
In
System Fan
Off Auto
Em
Heat
Cool
Temporary Setting Enrg
Heat
Recovery
DST
Wait
Cool
Auto
Sav
Room
Outdoor
Repl Batt
Auto
On
M17111
Fig. 10. Display of all the segments of the LCD.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3)
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3)
M10349
Fig. 11. Display of Installer Setup number and option.
Pub. No. 18-HD25D7-5
69-1213—1 (T8624)
4
Loading...
+ 8 hidden pages