Trane SSC-APG002-EN, XR Series, XR 13, XR 15 Application Manual

Application Guide
Trane XR S tyle Condensing Units and Heat Pumps
SSC-APG002-EN
Low Outdoor Ambient Operation Unit Mounting Minimum Clearances
Trane XR Style Outdoor Models
The purpose of this bulletin is to provide application criteria as related to the Trane XR style condensing units and heat pump units.
This bulletin discusses: I. T erms and definitions II. Off season cooling operation III. Compressor crankcase heat requirements for split heat pump systems. IV . Unit mounting V . Minimum operating clearances VI. Clearance from vents VII. Nameplate electrical data
POSITION ST A TEMENT :
Trane has always recommended installing T rane approved, matched indoor and outdoor systems. The benefits of installing approved matched sytems are maximum efficiency , optimum performance, and best overall system reliability
W arnings and Cautions may appear throughout this manual. Read these carefully .
WARNING – Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-
only accidents.
ISSUED BY : Product Application Engineering Department Trane a company of Ingersoll Rand T yler, T exas
Section I - T erms and Definitions: Three phase products:
All 2.5 to 5 ton three phase split system cooling units and heat pumps are shipped from the factory with compressor crankcase heat. Three phase compressor do not require start capacitors or start relays.
Definitions and information:
CCHT - Compressor Crankcase Heater, sometimes called a compressor sump heater .
This device is designed to warm the compressor crankcase (or sump) in order to prevent or deter refrigerant migration during the compressor off cycle. Compressor crankcase heaters are required for low ambient cooling operation. TXV - Thermostatic Exp ansion Valve. This is a type of refrigerant flow control device designed to maintain constant superheat throughout the operating envelope. For low ambient cooling applications, a non-bleed TXV is required. Bleed TXV: This type of TXV will allow the refrigerant pressures between the high side and low side to equalize through the valve during the off cycle. Non Bleed TXV: This type of TXV will not allow the refrigerant pressures between the high side and low side to equalize through the valve during the off cycle. When using this type of valve on single phase units with reciprocating style compressors, compressor start components are required. Check product data specifications for most current infor­mation. Head pressure controller - A device that is field installed on a condensing unit or heat pump designed to maintain system head pressure that will allow safe system operation without indoor coil icing in colder outdoor ambients. The BAYLOAM*** will cycle the condenser fan motor in order to achieve adequate operating head pressure. The control is adjustable. Evaporator Defrost Control - A device that is field installed on the system’s indoor coil in order to prevent the system from running during the cooling cycle when the indoor coil approaches or reaches a temperature in which frost will form on the coil surface. When the indoor coil approaches a safe temperature for cooling operation, the control will close and allow the outdoor unit to restart. This controller makes and breaks the control volt­age to the condensing unit. Quick Start Component - This component may be factory installed or offered as a field installed accessory ( BAYKSKT***). A quick start kit consist of a capacitor with a high microfarad rating and a potential relay. It is installed so that the start capacitor is wired in parallel with the compressor’s run capacitor . Prior to st art-up the potential relay contacts are closed, therefore placing the start capacitor in the compressor circuit, as the com­pressor motor reaches operating speed, electrical current flows through the potential relay’s coil and the the relay contacts are opened, thus taking the start capacitor out of the system until the next compressor start up.
© Trane 2015 Page 3 SSC-APG002-EN
Section II – Off Season Cooling Operation
55°F - 30°F 55°F - 30°F 55°F - 30°F 55°F - 30°F 30°F - 20°F or 30°F - 0°F see lowest approved OD ambient
Air
Conditioner
Heat Pump
55 deg F. As
Manufactu red
Air
Conditioner
AY28X079 3
Heat Pump AY28X084 3
TXV-NB CCHT
BAYLOAM103 BAYLOAM107
Start Kit
Solenoid
Valve (AC) 4
Windshield
Lowest App roved Outdoor Ambient
Cooling Mode
13 SEER X X X X X BAYLOAM103 X X X Approved to 0 d eg F
14 SEER X X X X X BAYLOAM103 X X X
AC Approved to 20 deg F HP Approved t o 10 deg F
15 SEER X X X X X BAYLOAM103 X X X
AC Approved to 20 deg F HP Approved t o 10 deg F
16 SEER 1 , 2 X X X X X BAYLOAM107 1 X X X
AC Approved to 20 deg F HP Approved t o 10 deg F
17 SEER X X X X X BAYLOAM103 X X X
AC Approved to 20 deg F HP Approved t o 10 deg F
Notes: 1 DO NOT apply BAYLOAM to model t onnages wit h variable speed condenser fan motors 2 Models with VS co ndenser fan motors ar e approved to 30 deg F wit h EDC or air hand ler with EEV 3 AY28X*** EDC not required when indoor unit has EEV 4 Liquid line soleno id shall be used for isolation purposes. Also used if liquid line is 1/2" and located before t he evaporator coil if AC is ab ove ID coil See SS-APG006-EN Refrigeration P iping A pplicatio n Guide
©Trane 2015 Page 4 SSC-APG002-EN
Trane outdoor units may be operated in the cooling mode to 55°F outdoor ambient as shipped from the factory when applied with an indoor TXV. Where required, these units with appropriate accessories may be applied to operate at outdoor temperatures below 55°F.
Unit requires a compressor crankcase heater and start accessory only if it is not factory installed. Compressor Crankcase Heaters: Reciprocating Compressor: BAYCCHT300
Large Scroll Compressor: BAYCCHT301RES Small Scroll Compressor: BAYCCHT302RES
As noted in the above table, systems may be operated lower than 55°F by applying the BAYLOAM103 or BAYLOAM107 and other accessories. The BAYLOAM*** controller cycles the outdoor fan motor as needed to maintain liquid line temperature as set by the DIP switches located on the control. There is no need to change the outdoor motor on approved products since the controller does not vary the frequency to the motor. However the BAYLOAM*** CANNOT be applied to those model tonnages with a variable speed condenser fan motor.
Windshields:
If low ambient cooling operation is required, windshields are a must in order to block prevailing winds from impacting system performance at low outdoor temperatures. Reference figure 1.
Figure 1 - Windshield Construction Information
SHIELD DESIGN FOR HIGHLY DIRECTIONAL WINDS
SERVICE ACCESS AREA SEE NOTES
UNIT
12" MIN.
PREVAILING WIND DIRECTION
SOLID PANEL
UNIT
4" MINIMUM
24" MAXIMUM
SHIELD DESIGNED FOR NON-DIRECTIONAL WINDS
SERVICE ACCESS AREA SEE NOTES
REMOVEABLE PANEL OR GATE FOR SERVICE
2 1/2" MIN.
UNIT
12" MIN.
SHADOW BOX FENCE 33% MIN. FREE AREA EACH SIDE
UNIT
NOTE:
National Electrical Code requires minimum three feet clearance from the service panel. Some local building departments will allow a removeable panel in front of the unit service access area. Otherwise the distance between the windshield and the unit’s service access is required to be a minimum of three feet. Reference page 16 of this document for National Electric Code information
.
2" MINIMUM
4" MAXIMUM
Low ambient cooling utilizing the frost control in GAM5A and T AM4 indoor units:
The T AM4 and T AM7 fan coil units utilize an electronic expansion valve (EEV). W ith this enhancement the controls that monitor the EEV also allow us to take advantage of monitoring coil temperature.
How it works: The on-board electr onic controls include a r elay that will open when the indoor coil begins to fr ost. When this occurs, the contacts to the YO circuit will open and de-energize the outdoor unit, provided figure 2 and 3 are followed. When the YO circuit opens the outdoor unit is taken off line; however,
the indoor blower continues to operate, thus clearing the indoor coil of frost build-up.
Low ambient cooling utilizing thermostatic control found in the A Y28X079 and A Y28X084.
How it works: These controls ar e thermally contr olled contacts with a capillary style sensor. The capillary tube is inserted into the coil fins in between the tube rows. When the sensor detects 25F, the contacts open. The contacts close when the coil temperature reaches 60F. When wired as shown in figures 4 and 5, the outdoor unit is de-energized when the EDC contact opens and re-energizes when the EDC
contact closes.
© Trane 2015 Page 5 SSC-APG002-EN
Typical wiring the frost control located in TAM4 or TAM7 fan coil unit
Figure 2
Cooling split system and T AM4 or T AM7 fan Coil Unit
GAM5 or TAM7 Air handling unit
Cooling
unit
Y
B
*NOTE:
Y2 and BK is present on TAM7 units and not present on GAM5 or TAM4.
W3 W2 W1
BK (see note*) G
Y2 (see note*) YI (in) YO (out
O
R B
Figure 3
Heat pump split system and T AM4 or T AM7 fan coil unit
GAM5 or TAM7 Air handling unit
Thermostat
W
G
Y
R
B
Thermostat
W3
Brown X2
Heat pump
unit
W2 W1
BK (see note*)
X2 W
G
G
Y2 (see note*)
Y
O
R B
Yellow
Orange
Red
Blue
YI (in) YO (out
O
R B
Warning! High voltage present in the outdoor unit and indoor unit. Assure high voltage power is disconnected using lockout / tag-out procedures if applicable prior to connecting low voltage wiring.