Trane X13790464-01 Installation and Maintenance Manual

Digital Display Zone Sensor
Literature Order Number: VAV-SVN05B-EN
Ordering number: Single Setpoint: X13790464-01(41901120)
Specifications
Input Power
NEC Class 2, 18-32 Vac 50/60Hz, 24 Vac nominal, 1 VA max
Size
2.8 x 4.5 x 1.2 in. (71.1 x 114.3 x 27.8 mm) including button heights
Mounting
Vertically flush mount or mount on standard vertical 2 x 4 in. (50.8 x 101.6 mm) device box
Communication Jack
Accessible through bottom of cover
Environmental
Operational: Humidity: Storage:
Wiring Diagram
Temperature range 32 to 120°F (0 to 49°C)
5 to 95% non-condensing
Temperature range –4 to 130°F (-20 to 54°C)
TB1
1
2
1
2
3
4
1
Digital Display Zone Sensor Wiring Terminals
2
24V AC*
24V GND*
ZONE TEMP
SENSOR GND
SETPOINT
COMM–
VAV 4.2
VV550 VV551
TB1–1
TB1–2
GND
TB3
ZONE
TB2–1
TB2–2
TB1
24V
TB3–1
TB3–2
GND
TB3–3
SET
TB2
MP501 ZN511 ZN517 ZN521
AC POWER
24V
GND
ZONE SENSORTB2
ZN
GND
SET
COMM 5TB3
+
A
B
AH540 AH541
24VAC
24VAC
GND
INPUTS
IN 1
GND
IN 2
COMM 5
A
B
*Note: Wiring backwards will result in product failure.
Pre-Installation Notes
1. All wiring must be in accordance with NEC and local building codes.
2. Do not run low-voltage wiring in the same conduit with high voltage power wiring.
3. Sharing the 24V Class 2-power source from the UCM is the preferred practice and simplifies installation. See wiring diagram above and wiring requirements under Item 4 at right. Use caution to be sure 24V and GND are connected to the proper terminals when connecting to the UCM.
4. If a separate 24V Class 2 power source is used to power the Digital Zone Sensor, terminals TB1-2 (24V GND) and TB2-2 (Sensor GND) must be jumpered together at the sensor for the sensor to operate. However, the use of a transformer with a supply voltage of greater than 150V to ground as the separate 24V Class 2 power source is not recommended because its output should be grounded to building ground (following NEC requirements for Class 2 devices). This additional grounding can affect the operation and/or damage the Digital Zone Sensor.
5. The sensor display will not be enabled with 24V connection only. Sensor signal wiring to the UCM must be connected for the display to function.
WARNING
6. Sensor must be connected to a UCM and powered up for at least 1 hour to achieve maximum accuracy.
7. “Sensor Setpoint”output can not be verified with an ohm meter. Connection to a UCM is necessary to verify operation.
8. Plug holes through the wall behind the sensor to prevent undesirable airflow.
Model Diagram
2.8"
˚F
˚C
SETPOINT
OVERRIDE
ON
CANCEL
4.5" 3.3"
2.1"
Installation Instructions
1. Choose mounting location. Choose a spot on an interior wall near the return air grille about five feet above the floor. Air should circulate freely and be of average temperature for the zone. Avoid areas such as:
y behind doors. y on outside walls or walls facing uncontrolled areas. y in direct sunlight or near sources of radiant heat that could
affect temperature measurement.
y in-line with discharge air from unit being controlled.
2. Remove cover. Remove zone sensor cover by easing the tip of a small screwdriver into the top rear center slot closest to the wall. Gently move the top of the screwdriver towards you. Excessive force is not recommended for cover removal!
3. Mount base. Remove zone sensor cover from base and mount base on wall or 2 x 4 device box.
4. Connect wires. Connect wires as shown in the wiring diagram. For wire lengths less than 75 feet, an 18 gage, 5 or 6 conductor cable may be used. For wire lengths greater than 75 feet, use 18 gage, 2-conductor cable for the power wiring (TB1), and 18 gage, 3 conductor cable for signal wiring (TB2). Avoid routing wires near sources of electrical noise such as motors, fluorescent lights, LAN wiring, etc. In some high noise environments, signal wires may require shielding. The communication jack should be wired with the cable appropriate for the system being installed.
5. Replace Cover. Place zone sensor cover back on the base and snap securely into place.
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
© 2004 American Standard, Inc. All rights reserved
Operating Instructions
Idle Display
y No action
Continuously displays the current zone temperature or
setpoint
Change Setpoint
y Repeatedly press UP or DOWN arrow button
SETPOINT flashes
Display increases or decreases
Release and system returns to the idle display
Begin Timed Override
y Press and hold the ON button until OVERRIDE appears
Timed override begins
System shows the idle display and OVERRIDE
Cancel Timed Override
y Hold CANCEL button until OVERRIDE disappears
Timed override is cancelled
System returns to the idle display
Service Instructions
Balancing Functions:
The * and ** functions allow balancing functionality at the zone sensor. See table below:
Engage Disengage Display Override Function Depends on Controller Type
Function Function Shows UCM 4.x VV550/551
Press “ON” and “UP” Press “UP” or “DOWN” Drive air valve to Drive air valve to
simultaneously until until normal * maximum primary minimum primary
screen goes blank display returns airflow airflow
Press “ON” and “DOWN” Press “UP” or “DOWN” Drive unit to unoccupied Drive air valve to
simultaneously until until normal ** (Both flow and maximum primary
screen goes blank display returns temperature setpoints) airflow
Change display units (°F or °C)
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows °F and °C (current unit flashing)
y Press UP or DOWN button to select °F and °C
Selected unit begins flashing
System returns to the idle display
Change idle display from room temperature display to continuous setpoint display mode
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows °F and °C (current unit flashing)
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Displays °F or °C (not flashing)
y Press UP or DOWN arrow buttons
SETPOINT flashes
Display times out and returns in the continuous setpoint display mode
Adjust the setpoint offset
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows °F and °C (current unit flashing)
y Hold UP and DOWN arrow buttons until screen goes blank
(con’t., next column)
Adjust the setpoint offset
(con’t.)
y Release buttons
Displays °F or °C (not flashing)
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows the setpoint adjust mode
y Hold UP and DOWN arrow buttons
Setpoint offset value changes
System returns to the idle display
Adjust the room temperature display offset
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows °F and °C (current unit flashing)
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Displays °F or °C (not flashing)
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
SETPOINT flashes
Display shows the setpoint adjust mode
y Hold UP and DOWN arrow buttons until screen goes blank y Release buttons
Display shows temperature offset display
y Press UP or DOWN arrow button
Temperature offset value changes
System returns to the current display mode
Trane A business of American Standard Companies www.trane.com
For more information contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number VAV-SVN05B-EN
File Number SV-TD-VAV-00 0-SVN05B-EN-0804
Supersedes VAV-SVN05A-EN
Stocking Location Electronic Only
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
Loading...