Trane Thermostats, X13511535-01, X13511536-01, X13511537-01 Installation And Operation Manual

Thermostats
Standard and Programmable Versions
March 2012 BAS-SVX36C-EN
Installation and Operation
SAFETY WARNING
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
2 BAS-SVX36C-EN
Copyright
© 2012Trane. All rights reserved.
This document and the information in it are the property ofTrane and may not be used
or reproduced in whole or in part, without the written permission ofTrane.Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this
document:
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided,
could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property- damage-only accidents.
Table of Contents
BAS-SVX36C-EN 3
Introduction ............................................................ 5
Product Features and Capabilities ....................................6
Dimensions ....................................................... 7
Pre-Installation .........................................................9
Location Considerations ............................................9
Height Requirements ...............................................9
Mounting Surfaces ................................................. 9
Maximum Wire Lengths ........................................... 10
Thermostat to HVAC Equipment ................................10
Remote Sensor to Programmable Thermostat .....................10
Installation ............................................................ 11
Mounting the Back Plate ...........................................11
Wiring ........................................................... 12
General Practice .............................................. 12
Terminal Identification ........................................ 13
Wiring Diagrams ............................................. 14
1-Heat/1-Cool Thermostat ................................... 14
3-Heat/2-Cool Non-Programmable Thermostat .................. 15
Programmable Thermostat .................................. 19
Replacing the Cover ............................................... 24
Applying Power ................................................... 25
Configuration .........................................................26
Operation ............................................................. 33
Icon Descriptions .................................................33
Overview of Operation ............................................. 33
Non-Programmable Thermostats ................................... 34
Changing the System Mode .................................... 34
Showing or Changing the Heating or Cooling Temperature Setpoint . . 34
Changing the Fan Mode ....................................... 35
Programmable Thermostats ........................................ 35
Programming ................................................ 35
Setting the Time ........................................... 35
Scheduling ...............................................36
Day-to-Day Operation ......................................... 39
Showing the Setpoint or Temperature on Display ............... 39
Timed Override (TOV) Mode .................................40
Locking or Unlocking Modes ................................40
Operational and Programming Reference Information ....................41
Deadband ........................................................ 41
4 BAS-SVX36C-EN
Heat and Cool Cycling Rate ......................................... 41
Minimum Compressor Off Time ....................................41
Configuration and Programming Retention ........................... 42
Extended Fan-on Time (Heat or Cool) ................................ 42
Compressor and Auxiliary Heat Lockout .............................42
Auxiliary Heat Control ............................................. 42
Economizer/TOD .................................................. 42
Troubleshooting ....................................................... 43
Error Codes ...................................................... 43
System Test Mode ................................................43
Troubleshooting Table ............................................. 47
Thermostat Specifications .............................................. 48
BAS-SVX36C-EN 5
Introduction
This document provides installation, operation, and troubleshooting information for threeTrane
models of push-button thermostat:
• TheTrane Programmable 3-Heat/2-CoolThermostat:
– Trane PLM # X13511537-01
– Trane Clarksville part # BAYSTAT150A
– Service parts #THT02774
• TheTrane (non-programmable) 3-Heat/2-CoolThermostat:
– Trane PLM # X13511536-01
– Trane Clarksville part # BAYSTAT155A
– Service parts #THT02773
• TheTrane (non-programmable) 1-Heat/1-CoolThermostat:
– Trane PLM # X13511535-01
– Trane Clarksville part # BAYSTAT151A
– Service parts #THT02772
Note: To identify the thermostat type, locate theTrane PLM # and theTrane PLM #/Trane Clarksville
# on the thermostat circuit board.
The information contained in this document applies to either one or two models or to all.
Differences are noted where appropriate. If no difference between models is noted, assume that all thermostat models share the information.
6 BAS-SVX36C-EN
Introduction
Product Features and Capabilities
The table below shows the functional differences between the three thermostat models.
Thermostat Function or Feature
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(p/n X13511536-01)
Programmable
Thermostat
(p/n X13511537-01)
A liquid crystal display (LCD) with symbols for temperature, setpoints, and system operating modes. The programmable thermostat also has day of the week, time of day, and occupancy settings.
 
System modes: Heat, Cool, Auto, Off. Both types of 3-Heat/2-Cool thermostat also have Emergency Heat mode.
 
System Configuration Options. See “Configuration,” p. 26 for more information:
• 1-heat/1-cool, conventional  
• 1-heat/1-cool, heat pump without auxiliary heat
 
• 1-heat only, conventional without fan
 
• 1-heat only, conventional with fan
 
• 1-cool, conventional
 
• 2-heat/1-cool, heat pump with auxiliary heat
• 2-heat/2-cool, conventional
• 2-heat/1-cool, conventional
• 1-heat/2-cool, conventional
• 2-heat/2-cool, heat pump without auxiliary heat
• 3-heat/2-cool, heat pump with auxiliary heat
A heating and cooling setpoint range of 40
º
F to 90ºF (4.5ºC to 32ºC)  
Two fan modes: On, Auto
 
Additional configurable options (See “Configuration,” p. 26)
 
Terminals and configuration options for a remote temperature sensor. Options include:
• Displaying the remote/outdoor temperature on the LCD
• Using the remote/outdoor temperature to lockout the compressor or auxiliary heat
• Using the remote/outdoor temperature instead of the built-in sensor
Scheduling function with two or four periods per day and the following day/week options:
• 5/2 day schedule: weekdays share a schedule; Saturday and Sunday share a schedule
• 5/1/1 day schedule: weekdays share a schedule; Saturday and Sunday have their own, independent schedules
• 1 day schedule: Every day shares the same schedule
• 7 day schedule: Each day has its own, independent schedule
Temporary override function with configurable override time limit
BAS-SVX36C-EN 7
Introduction
Dimensions
Figure 1 and Figure 2 provide dimensions for each type of thermostat.The two non-programmable
thermostats have the same dimensions; the programmable thermostat has slightly different dimensions.
Figure 1. Programmable Thermostat Dimensions
3.25 in.
(83 mm)
1.08 in.
(27.5 mm)
4.7 in.
(119 mm)
0.3 in.
(8 mm)
Typ.P Radius 0.08 in. (2 mm)
3.4 in.
(86 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
Typ. Radius
0.08 in. (2 mm)
8 BAS-SVX36C-EN
Introduction
Figure 2. 1-Heat/1-Cool or 3-Heat/2-Cool (non-programmable)Thermostat Dimensions
3.07 in.
(78 mm)
1.1 in.
(28 mm)
4.7 in.
(119 mm)
0.3 in.
(8 mm)
Typ.P Radius 0.08 in. (2 mm)
3.4 in.
(86 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
Typ. Radius
0.08 in. (2 mm)
BAS-SVX36C-EN 9
Pre-Installation
This section provides the following pre-installation information:
Location considerations
Height requirements
Mounting surfaces
Maximum wire length
Location Considerations
When selecting a location, avoid the following:
Areas of direct sunlight
Areas in the direct airstream of air diffusers
Exterior walls and other walls that have a temperature differential between the two sides
Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment
Drafty areas
Dead spots behind doors, projection screens, or corners
Walls that are subject to high vibration
Areas with high humidity
High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 in. (137 cm) above the floor. If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48 inches.
Note: Consult section 4.27.3 of the 2002Americans with DisabilityAct guideline, and local building
codes, for further details regarding wheelchair requirements.
Mounting Surfaces
The thermostat can be mounted to any sturdy, vertical surface. Plastic threaded anchors and
M3.5 x 20 mm screws are provided for mounting to plaster or wallboard; 6-32 x 3/4 inch machine screws are provided for mounting directly to a standard electrical device box. Other fastener varieties may be required for other surface types.
When replacing a horizontally mounted thermostat and there is an adapter kit available to cover
any opening in the wall. Contact your localTrane office for more information.
10 BAS-SVX36C-EN
Pre-Installation
Maximum Wire Lengths
Thermostat to HVAC Equipment
The thermostat may not function properly if the total resistance of any of the thermostat to HVAC
equipment wires exceeds 2.5 ohms.To ensure that wire length does not cause excess resistance, refer to Table 1 and ensure that the wires from the thermostat to the HVAC equipment are not too long.
Remote Sensor to Programmable Thermostat
Because remote temperature sensors measure resistance, very long cable runs can cause slight errors in the measurement. For the highest temperature reading accuracy, avoid exceeding the maximum recommended wire lengths shown in Table 2.
Note: For 22 AWG (0.33 mm2) copper wires, the rate of error can be up to 0.5 °F (0.3 °C) per 100 ,
which typically requires wire lengths in excess of 5000
ft (1500 m).
Table 1. Maximum Thermostat to HVAC Equipment Wire Lengths
Copper wire size Maximum recommended wire length
22 AWG (0.33 mm2) 150 ft (46 m)
20 AWG (0.50 mm
2
) 240 ft (73 m)
18 AWG (0.75 mm
2
) 385 ft (117 m)
Table 2. Maximum Recommended Remote SensorWire Length
Copper wire size
Maximum recommended remote sensor wire length
22 AWG (0.33 mm2) 1000 ft (300 m)
20 AWG (0.50 mm
2
) 1500 ft (450 m)
18 AWG (0.75 mm
2
) 2500 ft (750 m)
BAS-SVX36C-EN 11
Installation
This section provides installation instructions.
Before you begin, read through the pre-installation information, beginning on p. 9, and also verify the following conditions are met:
A wire access hole is available at the thermostat location.
• The wires are accessible through the hole.
• The wires are attached to the appropriate terminals on the HVAC equipment.
• There is continuity (and not more than 2.5 ohms resistance) between the thermostat location and
the HVAC equipment.
• The wires are accurately labeled or identified by color.
Mounting the Back Plate
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
To mount the back plate:
1. Shut off power to the HVAC equipment.
Note: If
the security screw is installed, remove it before attempting to remove the cover.
See Figure 3.
Figure 3.
Security screw
Security Screw Location (if used)
2. Remove the cover by firmly pressing the thumb tab at the bottom of the cover and pulling the co
ver away from the back plate.
3. Feed the wires through the opening in the back plate.
12 BAS-SVX36C-EN
Installation
Figure 4. Feeding Wires through Back Plate
4. If you are mounting the back plate directly to a wall surface, hold the back plate against the surface and mark the fastener locations.
5. Secure the back plate using appropriate fasteners. (See “Mounting Surfaces,” p. 9.) The thermostat must be level and plumb for accurate temperature control and to ensure proper air mo
vement through the thermostat enclosure.
Wiring
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
General Practice
To wire the thermostat:
1. Connect the wires to the terminal block(s) packaged in the box with the thermostat. (The programmable
thermostat has two terminal blocks, the non-programmable thermostats have
only one):
R
emove approximately 1/4 inch (6 mm) of insulation from the wires.
Use the terminal block screws to securely fasten each wire into the terminal block.
Refer to the section, “Terminal Identification,” p. 13 and the wiring diagrams on the pages
that follow to determine the correct terminal for each wire.
Note: In
some cases the terminal labels (Y, G, R, etc.) correctly correspond to first letter of the color wire to which they are connected. However, you must verify which equipment terminals are connected at the other ends of the wires before connecting the wires to the thermostat.
BAS-SVX36C-EN 13
Installation
2. Align the pins on the circuit board with the holes onthe bottom of theterminal blocksand gently push the wired terminal blocks into place on the circuit board. See Figure 5.
Figure 5. Attaching the wired terminal blocks to the pins on the circuit board
C G Y W Rc R
W2(W1)
Y2
S1
S2
R
Rc
Y
G
C
W(O/B)
A
W2 Y2 A S1 S2
Rc R Y C O/B G
AuxE
Y2 L
R
Rc
Y
G
W2(AuxE)
Y2
L
C
W (O/B)
Rc R Y C W G
R
Rc
Y
G
C
W
Programmable thermostat 3-Heat/2-Cool thermostat 1-Heat/1-Cool thermostat
s
3. Push the excess wire through the hole in the wall cavity or into the junction box.
Important: Do
not coil excess wire between the thermostat and the back plate.
4. Use nonflammable insulation to prevent air movement between the wall cavity and the thermostat.
Terminal Identification
The table below defines the terminals for each of the thermostat types.
Terminal Label Terminal Description
Where present:
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(p/n X13511536-01)
Programmable
Thermostat
(p/n X13511537-01)
C Common  
G Fan Relay
 
Y Stage 1 compressor control
 
W (O/B) Heat relay (Changeover valve)
(1)
(1) Text (in parentheses) applies to heat pump systems.
 
Rc 24Vac cooling These terminals are shipped with a jumper connected
between them. Remove the jumper if the 24Vac power supplies are separate.
 
R 24Vac heating
 
W2 (W1)
or
W2 (Aux/E)
Second stage heat (Auxiliary heat or emergency heat relay.)
(1)
Y2 Stage 2 compressor control
A Economizer
S1 External sensor
S2 External sensor
(L) (Emergency heat indicator)
(1)
14 BAS-SVX36C-EN
Installation
Wiring Diagrams
The following diagrams show all of the common wiring scenarios you are likely to encounter.
1-Heat/1-Cool Thermostat
Use Table 3 and the diagrams that follow to correctly wire the thermostat for your system type.
Figure 6. 1H/1C Thermostat, 1H/1C Conventional (option 0)
Single Transformer:
(jumper installed)
Rc
R
Y
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor
Rc
R
Y
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
(jumper removed)
Figure 7. 1H/1C Thermostat, 1H/1C Heat Pump Without Auxiliary Heat (Option 1)
(jumper installed)
Rc
R
Y
C
O/B
G
Fan
L2
L1 (hot)
24 Vac
Changeover Valve
Compressor
Table 3. SystemType Options for 1H/1C Non-Programmable Thermostats
System Type
Value for Option 01 See Diagram
1-heat/1-cool, conventional 0 Figure 6
1-heat/1-cool, heat pump without auxiliary heat 1 Figure 7
1-heat only, conventional without fan 2 Figure 8
1-heat only, conventional with fan 3 Figure 9
1-cool, conventional 4 Figure 10
BAS-SVX36C-EN 15
Installation
Figure 8. 1H/1C Thermostat, 1H Only, Conventional Without Fan (Option 2)
(jumper installed)
Rc
R
Y
C
W
G
L2
L1 (hot)
24 Vac
Heat
Figure 9. 1H/1C Thermostat, 1H Only, Conventional With Fan (option 3)
(jumper installed)
Rc
R
Y
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Figure 10. 1H/1C Thermostat, 1C Only, Conventional (option 4)
(jumper installed)
Rc
R
Y
C
W
G
Fan
L2
L1 (hot)
24 Vac
Compressor
3-Heat/2-Cool Non-ProgrammableThermostat
Use Table 4 and the diagrams that follow to correctly wire the thermostat for your system type.
Table 4. SystemType Options for 3H/2C Non-Programmable Thermostats
System Type Value for Option 01
See Diagram
1-heat/1-cool, conventional 0 Figure 11
1-heat/1-cool, heat pump without auxiliary heat 1 Figure 12
1-heat only, conventional without fan 2 Figure 13
1-heat only, conventional with fan 3 Figure 14
1-cool, conventional 4 Figure 15
2-heat/1-cool, heat pump with auxiliary heat 5 Figure 16
2-heat/1-cool, conventional 6 Figure 17
1-heat/2-cool, conventional 7 Figure 18
2-heat/2-cool, heat pump without auxiliary heat 8 Figure 19
3-heat/2-cool, heat pump with auxiliary heat 9 Figure 20
16 BAS-SVX36C-EN
Installation
Figure 11. 3H/2C Non-ProgrammableThermostat, 1H/1C, Conventional (Option 0)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor
Single Transformer:
(jumper installed)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
(jumper removed)
Figure 12. 3H/2C Non-ProgrammableThermostat, 1H/1C, Heat Pump Without Auxiliary heat
(Option 1)
Rc
R
Y
Aux/E
Y2
L
C
O/B
G
Fan
L2
L1 (hot)
24 Vac
Changeover Valve
Compressor
(jumper installed)
Figure 13. 3H/2C Non-ProgrammableThermostat, 1H Only, Conventional Without Fan (Option 2)
Rc
R
Y
W2
Y2
L
C
W
G
L2
L1 (hot)
24 Vac
Heat
(jumper installed)
BAS-SVX36C-EN 17
Installation
Figure 14. 3H/2C Non-ProgrammableThermostat, 1H, Conventional With Fan (Option 3)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
(jumper installed)
Figure 15. 3H/2C Non-ProgrammableThermostat, 1C, Conventional (Option 4)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Compressor
(jumper installed)
Figure 16. 3H/2C Non-ProgrammableThermostat, 2H/1C, Heat Pump With Auxiliary Heat
(Option 5)
Rc
R
Y
Aux/E
Y2
L
C
O/B
G
Fan
L2
L1 (hot)
24 Vac
Auxiliary Heat
Changeover Valve
Compressor
(jumper installed)
Zoning Panels
18 BAS-SVX36C-EN
Installation
Figure 17. 3H/2C Non-ProgrammableThermostat, 2H/1C, Conventional (Option 6)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat 1
Compressor
Heat 2
Single Transformer:
(jumper installed)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat 1
Heat 2
Compressor
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
(jumper removed)
Figure 18. 3H/2C Non-ProgrammableThermostat, 1H/2C, Conventional (Option 7)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor 1
Compressor 2
Single Transformer:
(jumper installed)
Rc
R
Y
W2
Y2
L
C
W
G
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor 1
Compressor 2
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
(jumper removed)
Figure 19. 3H/2C Non-ProgrammableThermostat, 2H/2C, Heat Pump Without Auxiliary Heat
(Option 8)
Rc
R
Y
Aux/E
Y2
L
C
O/B
G
Fan
L2
L1 (hot)
24 Vac
Changeover Valve
Compressor 1
Compressor 2
(jumper installed)
BAS-SVX36C-EN 19
Installation
Figure 20. 3H/2C Non-ProgrammableThermostat, 3H/2C, Heat Pump With Auxiliary Heat
(Option 9)
Rc
R
Y
Aux/E
Y2
L
C
O/B
G
Fan
L2
L1 (hot)
24 Vac
Changeover Valve
Compressor 1
Auxiliary Heat
Compressor 2
Zoning Panels
(jumper installed)
ProgrammableThermostat
Use Table 5 and the diagrams that follow to correctly wire the thermostat for your system type.
Table 5. SystemType Options for ProgrammableThermostats
System Type Value for Option 130
See Diagram
1-heat/1-cool, conventional 1 Figure 21
1-heat/1-cool, heat pump without auxiliary heat 2 Figure 22
1-heat only, conventional without fan 3 Figure 23
1-heat only, conventional with fan 4 Figure 24
1-cool, conventional 5 Figure 25
2-heat/1-cool, heat pump with auxiliary heat 6 Figure 26
2-heat/2-cool, conventional 7 Figure 27
2-heat/1-cool, conventional 8 Figure 28
1-heat/2-cool, conventional 9 Figure 29
2-heat/2-cool, heat pump without auxiliary heat 10 Figure 30
3-heat/2-cool, heat pump with auxiliary heat 11 Figure 31
20 BAS-SVX36C-EN
Installation
Figure 21. ProgrammableThermostat, 1H/1C, Conventional (Option 1)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat
Economizer/TOD
Remote Temperature Sensor
Compressor
L2
L1 (hot)
Single Transformer:
(jumper installed)
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper removed)
Economizer/TOD
Remote Temperature Sensor
Figure 22. ProgrammableThermostat, 1H/1C, Heat Pump Without Auxiliary Heat (Option 2)
Fan
24 Vac
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
Changeover Valve
Compressor
L2
L1 (hot)
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
BAS-SVX36C-EN 21
Installation
Figure 23. ProgrammableThermostat, 1H Only, Conventional Without Fan (Option 3)
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat
L2
L1 (hot)
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Figure 24. ProgrammableThermostat, 1H, Conventional With Fan (Option 4)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat
L2
L1 (hot)
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Figure 25. ProgrammableThermostat, 1C, Conventional (Option 5)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Compressor
L2
L1 (hot)
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
22 BAS-SVX36C-EN
Installation
Figure 26. ProgrammableThermostat, 2H/1C, Heat Pump With Auxiliary Heat (Option 6)
Fan
24 Vac
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
Changeover Valve
Compressor
L2
L1 (hot)
(jumper installed)
Auxiliary Heat
Economizer/TOD
Remote Temperature Sensor
Figure 27. ProgrammableThermostat, 2H/2C, Conventional (Option 7)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat 1
Compressor 1
Heat 2
Compressor 2
L2
L1 (hot)
Single Transformer:
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Fan
L2
L1 (hot)
24 Vac
Heat 1
Heat 2
Compressor 1
Compressor 2
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper removed)
Economizer/TOD
Remote Temperature Sensor
BAS-SVX36C-EN 23
Installation
Figure 28. ProgrammableThermostat, 2H/1C, Conventional (Option 8)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat 1
Compressor
Heat 2
L2
L1 (hot)
Single Transformer:
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Fan
L2
L1 (hot)
24 Vac
Heat 1
Heat 2
Compressor
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper removed)
Economizer/TOD
Remote Temperature Sensor
Figure 29. ProgrammableThermostat, 1H/2C, Conventional (Option 9)
Fan
24 Vac
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
Heat
Compressor 1
Compressor 2
L2
L1 (hot)
Single Transformer:
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Fan
L2
L1 (hot)
24 Vac
Heat
Compressor 1
Compressor 2
L2
L1 (hot)
24 Vac
Cooling Transformer
Heating Transformer
Two Transformers:
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper removed)
Economizer/TOD
Remote Temperature Sensor
24 BAS-SVX36C-EN
Installation
Figure 30. ProgrammableThermostat, 2H/2C, Heat Pump Without Auxiliary Heat (Option 10 )
Fan
24 Vac
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
Changeover Valve
Compressor 1
Compressor 2
L2
L1 (hot)
(jumper installed)
Economizer/TOD
Remote Temperature Sensor
Figure 31. ProgrammableThermostat, 3H/2C, Heat Pump With Auxiliary Heat (Option 11 )
Fan
24 Vac
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
Changeover Valve
Compressor 1
Compressor 2
L2
L1 (hot)
(jumper installed)
Auxiliary Heat
Economizer/TOD
Remote Temperature Sensor
Replacing the Cover
To replace the cover:
1. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover until
it snaps in place.
2. If desired, install the security screw into the bottom of the cover. See Figure 32.
Figure 32.
Security screw
Close cover - insert security screw
BAS-SVX36C-EN 25
Installation
Applying Power
Applying power to the thermostat will initiate a power up sequence.
1. The full screen appears for 1.5 seconds.
2. The firmware version appears for 1.5 seconds:
On
the programmable thermostat, the firmware version shows in the HH:MM digits.
On the non-programmable thermostats, the digits are split between the top and bottom
regions of the screen: the most significant digits are at the top.
3. Power up tests are performed.
If
an error is detected, an error code appears (see “Error Codes,” p. 43).
If no errors are detected, the home screen appears (see Figure 33).
Figure 33. Home screens
.
.
Mo
AM
Programmable
thermostat
Non-programmable
thermostats
26 BAS-SVX36C-EN
Configuration
NOTICE
Adverse Control System Behavior!
Improper configuration could cause unwanted, possibly adverse control system behavior. Be sure to configure the thermostat according to your system type.
To change the installation configuration:
1. Apply electrical power to the thermostat.
2. See the appropriate table for your thermostat type to determine the configuration options you need:
T
able 6, p. 27 for 3-Heat/2-Cool programmable thermostats
Table 7, p. 31 for 3-Heat/2-Cool non-programmable thermostats
Table 8, p. 32 for 1-Heat/1-Cool, non-programmable thermostats
3. Write down your selections or other notes on the table.
4. Enter installer configuration mode:
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec.
Figure 34. Pressing the Configuration Button
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Programmable 3H/
2C configuration
button
Non-programmable
thermostats
configuration button
The configuration wrench icon appears, along with the option number and value:
Figure 35. Configuration Mode
Value
Programmable Thermostat
Non-Programmable Thermostat
Option Number
Note: Configuration mode automatically ends if no buttons are pressed for 10 min.
BAS-SVX36C-EN 27
Configuration
5. Press , ,or to scroll through the options, identified by their numbers, until you reach the option you want to change:
scrolls to a lower-numbered option. or scrolls to a higher-numbered option.
6. Use
or to change the value of the option:
decreases the value.
increases the value.
7. Repeat Step 5 and Step 6 until you have made all necessary changes.
Note: V
alues are saved in permanent memory after setting a value and moving to next
configuration parameter, and also when you exit configuration mode.
8. Do one of the following to exit configuration mode:
Remove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
Do not press any buttons for 10 min.
Press and hold for 2 sec.
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat
No. Name Default Opts. Descriptions
0100 Temperature
indication/ resolution
0 0 °F, 1 degree resolution
1 °F, 0.5 degree resolution 2 °C, 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
0110 Clock format 12 12 12 hour clock
24 24 hour clock 0120 Year 09 09-99 2009 - 2099 0121 Month 1 1-12 Months of the year 0122 Day 1 1-31 Days of the month 0125 Daylight savings 2 0 Disabled
1 US (1987), changeover at 2:00am 2 US (2007), changeover at 2:00am 3 Europe, changeover at 1:00am 4 Manual, changeover at 2:00am
0126 Spring month
(1)
03 01-12 The month in which the Spring daylight savings change occurs 0127 Spring day 08 01-31 The day on which the Spring daylight savings change occurs 0128 Fall month 11 01-12 The month in which the Fall daylight savings change occurs 0129 Fall day 08 01-31 The day on which the Fall daylight savings change occurs 0130 System selection 8 1 1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
2 1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G) 3 1H (Conv) 1st Stage Heat (W), without fan 4 1H (Conv) 1st Stage Heat (W), Fan (G) 5 1C (Conv) 1st Stage Comp (Y), Fan (G) 6 2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat (W1),
Fan (G)
7 2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G) 8 2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan (G) 9 1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan (G)
10 2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G) 11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Auxiliary
Heat (W1), Fan (G)
28 BAS-SVX36C-EN
Configuration
0140 Schedule options 1 0 Non-programmable
1 Programmable
0150 TOD/Economizer
output (terminal A)
0 0 Unused
1 TOD energizes terminal A during occupied period, not during
unoccupied period. 2 Economizer energizes terminal A during a call for cool
0151 Heat fan
operation
0 0 System controls fan
1 Thermostat controls fan
0153 Reversing value
O/B
0 0 O/B terminal energized in cooling
1 O/B terminal energized in heating
0160 CPH 1st stage
compressor
(2)
3 1-5 Cycles per hour for 1st stage compressor - only for systems with cool or heat
pump stage - also changes 2nd stage cool default CPH
0161 CPH 2nd stage
compressor
(2)
3 1-5 Cycles per hour for 2nd stage compressor - only for systems with two cool or
heat pump stages
0162 CPH 1st stage
conventional heat
(2)
5 1-10 Cycles per hour for 1st stage conventional heat - only for systems with heat
stages - also changes 2nd stage heat default CPH
0163 CPH 2nd stage
conventional heat
(2)
9 1-10 Cycles per hour for 2nd stage conventional heat - only for systems with two
conventional heat stages
0164 CPH for auxiliary
heat
(2)
9 1-10 Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
0165 CPH for
emergency heat
(2)
9 1-10 Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages
0170 Continuous
backlight
0 0 Backlight “ON” time is limited
1 Backlight does not turn off
0180 Changeover 1 0 Manual changeover (heat/cool/off) - manually changeover the thermostat
between heat, cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
0181 Deadband
(3)
3 2 2° F (1° C)
3 3° F (1.5° C) 4 4° F (2.0° C) 5 5° F (2.5° C) 6 6° F (3.0° C) 7 7° F (3.5° C) 8 8° F (4.0° C) 9 9° F (4.5° C)
0182 Minimum
compressor off time
5 0-5 Minutes for compressor off time - for systems with cool or heat pump stages
- (Minutes specified here are added to the 5 min base off time.)
0190 Power supply
frequency
0 0 60Hz
1 50 Hz
0210 Temperature
sensor selection
0 0 Internal for H/C - display can show only local temperature and setpoint
1 Internal for H/C - remote (connected to S1 & S2)
(4)
for display - display can
show local and remote temperature, and setpoint 2 Internal for H/C, remote (connected to S1 & S2)
(4)
for compressor and auxiliary lockout; display can show local and remote temperature, and setpoint - (Disabled for conventional systems.)
3 Remote (connected to S1 & S2)
(4)
for H/C, internal disabled; display can show
remote indoor temperature and setpoint
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
BAS-SVX36C-EN 29
Configuration
0220 Heat pump
compressor lockout point
(5)
0 0 None
15 15° F (–9.5° C) 20 20° F (–6.5° C) 25 25° F (–4.0° C) 30 30° F (–1.0° C) 35 35° F (1.5° C) 40 40° F (4.5° C) 45 45° F (7.0° C)
0221 Heat pump aux
lockout point
0 0 None
40 40° F (4.5° C) 45 45° F (7.0° C) 50 50° F (10.0° C) 55 55° F (13.0° C) 60 60° F (15.5° C)
0230 Temp occupied
duration limit for TOV override
3 0 0 hours (Note: TOV function is still available)
1 1 hour 2 2 hours 3 3 hours 4 4 hours
0231 Number of
periods
2 2 Two scheduling periods per day
4 Four scheduling periods per day
0232 Period occupied/
unoccupied definitions
4 If Option #0231 is set to 2:
Day Night
0 Unoccupied Unoccupied 1 Unoccupied Occupied 2 Unoccupied Unoccupied 3 Unoccupied Occupied 4 Occupied Unoccupied 5 Occupied Occupied 6 Occupied Unoccupied 7 Occupied Occupied 8 Unoccupied Unoccupied
9 Unoccupied Occupied 10 Unoccupied Unoccupied 11 Unoccupied Occupied 12 Occupied Unoccupied 13 Occupied Occupied 14 Occupied Unoccupied 15 Occupied Occupied
If Option #0231 is set to 4:
Morning Day Evening Night 0 Unoccupied Unoccupied Unoccupied Unoccupied 1 Unoccupied Unoccupied Unoccupied Occupied 2 Unoccupied Unoccupied Occupied Unoccupied 3 Unoccupied Unoccupied Occupied Occupied 4 Unoccupied Occupied Unoccupied Unoccupied 5 Unoccupied Occupied Unoccupied Occupied 6 Unoccupied Occupied Occupied Unoccupied 7 Unoccupied Occupied Occupied Occupied 8 Unoccupied Unoccupied Unoccupied Unoccupied 9 Occupied Unoccupied Unoccupied Occupied
10 Occupied Unoccupied Occupied Unoccupied 11 Occupied Unoccupied Occupied Occupied 12 Occupied Occupied Unoccupied Unoccupied 13 Occupied Occupied Unoccupied Occupied 14 Occupied Occupied Occupied Unoccupied 15 Occupied Occupied Occupied Occupied
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
30 BAS-SVX36C-EN
Configuration
0233 Scheduling mode
day options
0 0 1 day - Mo-Su share the same schedule
1 5+1+1 days - Mo-Fr share a schedule; Sa and Su each have an independent
schedule 2 5+2 days - Mo-Fr share a schedule; Sa-Su share a schedule 3 7 days - Each day has an independent schedule
0240 Heat
temperature range stops
(6)
90 40 - 90 40° F to 90° F
4 - 32 4° C to 32° C
0241 Cool temperature
range stops
(7)
50 50 - 99 50° F to 99° F
10 - 37 4° C to 32° C
0260 Temperature
display offset
(8)
0 -3 –3° F (–1.5° C)
-2 –2° F (–1.0° C)
-1 –1° F (–0.5° C) 0 None 1 1° F (0.5° C) 2 2° F (1.0° C) 3 3° F (1.5° C)
0270 Extended fan-on
time heat
(9)(10)
0 0 Off
90 90 sec
0271 Extended fan-on
time cool
(9)(7)
0 0 Off
40 40 sec
0300 Restore factory
defaults
0 0 No - do not restore
1 Yes - reset all installer options to default except calendar, and system
selection - options 0120-0122 and 0125-0130 do not reset.
(1) Only available if option #0125 is set to 4. (2) See “Heat and Cool Cycling Rate,” p. 41. (3) See “Deadband,” p. 41. (4) If an external sensor is attached to the S1 and S2 terminals, it must be 10K
negative temperature coefficient.
(5) Only available for heat pump systems with more heat than cool stages and remote outdoor sensor. A 5 °F (2.5 °C) dead
band between options #0220 and #0221 will be enforced automatically. (6) Only applies to systems with heat stages. (7) Only applies to systems with cool stages. (8) Only applies to control temperature and display temperature for internal and indoor remote sensor. Does not apply to out-
door temperature for display. (9) See “Extended Fan-on Time (Heat or Cool),” p. 42. (10)Only available when option #0151 is set to 1.
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
BAS-SVX36C-EN 31
Configuration
Table 7. Installation Options for 3-Heat/2-Cool Non-ProgrammableThermostat
No. Name Default Opts. Descriptions
01 System type 0 0 1H/1C, conventional - 1st stage heat (W), 1st stage
compressor (Y)
1 1H/1C, heat pump without auxiliary heat - 1st stage compressor (Y),
changeover (O/B) 2 1H, conventional without fan - 1st stage heat (W) 3 1H, conventional with fan - 1st stage heat (W), fan (G) 4 1C, conventional - 1st stage compressor (Y) 5 2H/1C, heat pump with auxiliary heat - 1st stage compressor (Y), changeover
(O/B), auxiliary heat (Aux/E) 6 2H/1C, conventional - 1st & 2nd stage heat (W,W2), 1st stage compressor (Y) 7 1H/2C, conventional - 1st stage heat (W), 1st & 2nd stage compressor (Y, Y2) 8 2H/2C, heat pump without auxiliary heat - 1st & 2nd stage compressor (Y,
Y2), changeover (O/B) 9 3H/2C, heat pump with auxiliary heat - 1st & 2nd stage compressor (Y, Y2),
changeover (O/B), auxiliary heat (Aux/E)
02 Changeover
valve
0 0 O/B terminal energized in cooling
1 O/B terminal energized in heating
03 Fan control
(1)
0 0 Gas or oil furnace, equipment controls fan for heating
1 Electric furnace, thermostat controls fan in heating
04 Stage 1 heat
cycle rate
(2)
5 1-10 Cycles per hour for 1st stage conventional heat - only available on systems
with conventional heat
05 Stage 1
compressor cycle rate
(2)
3 1-5 Cycles per hour for 1st stage compressor - only available on systems with cool
stages
06 Manual/Auto
changeover
0 0 Manual changeover (heat/cool/off) - manually changeover between heat,
cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover 2 Auto changeover only (auto) - no manual changeover
07 Temperature
indication/ resolution
0 0 °F with 1 degree resolution
1 °F with 0.5 degree resolution 2 °C with 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
08 Compressor
protection
5 0-5 Minutes for compressor off time - only available on heat pump systems or
systems with cool stages - (Minutes specified here are added to the 5 min
base off time.)
09 Heat
temperature range stop
90 40-90 Heating high temperature range stop in °F. (4.5-32°C)
10 Cool temperature
range stop
50 50-99 Cooling low temperature range stop in °F. (10-37°C)
11 Power supply
frequency
0 0 60 Hz
1 50 Hz
12 Deadband
(3)
3 2 2°F (1.0°C)
3 3°F (1.5°C) 4 4°F (2.0°C) 5 5°F (2.5°C) 6 6°F (3.0°C) 7 7°F (3.5°C) 8 8°F (4.0°C) 9 9°F (4.5°C)
13 Stage 2 heat
cycle rate
(2)
9 1-10 Cycles per hour for 2nd stage conventional heat - only available for
conventional systems with at least two stages conventional heat
14 Auxiliary heat
cycle rate
(2)
5 1-10 Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
15 Emergency heat
cycle rate
(2)
5 1-10 Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages.
16 Stage 2
compressor cycle rate
(2)
3 1-5 Cycles per hour for 2nd stage compressor - only for systems with two cool
stages
17 Auxiliary heat
control
0 0 Comfort
1 Economy
18 Restore factory
defaults
0 0 No - do not reset
1 Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
(1) These options only available on systems with fans. (2)
See “Heat and Cool Cycling Rate,” p. 41.
(3) See “Deadband,” p. 41. For auto or manual systems (see Option 01).
32 BAS-SVX36C-EN
Configuration
Table 8. Installation Options for 1-Heat/1-Cool Non-ProgrammableThermostat
No. Name Default Opts. Descriptions
01 System type 0 0 1H/1C, conventional -1st stage heat (W), 1st stage compressor (Y)
1 1H/1C, heat pump - 1st stage compressor (Y), changeover (O/B) 2 1H, conventional, without fan - 1st stage heat (W) 3 1H, conventional with fan -1st stage heat (W), fan (G) 4 1C, conventional - 1st stage compressor (Y)
02 Changeover
valve
0 0 O/B terminal energized in cooling
1 O/B terminal energized in heating
03 Fan control
(1)
(1) These options only available on systems with fans.
0 0 Gas or oil furnace, equipment controls fan for heating
1 Electric furnace, thermostat controls fan in heating
04 Stage 1 heat
cycle rate
(2)
(2) See “Heat and Cool Cycling Rate,” p. 41.
5 1-10 Cycles per hour for 1st stage conventional heat - only available on systems
with conventional heat
05 Stage 1
compressor cycle rate
(2)
3 1-5 Cycles per hour for 1st stage compressor - only available on systems with cool
stages
06 Manual/Auto
changeover
0 0 Manual changeover (heat/cool/off) - manually changeover between heat,
cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover 2 Auto changeover only (auto) - no manual changeover
07 Temperature
indication/ resolution
0 0 0°F with 1 degree resolution
1 °F with 0.5 degree resolution 2 °C with 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
08 Compressor
protection
5 0-5 Minutes for compressor off time - only available on heat pump systems or
systems with cool stages - (Minutes specified here are added to the 5 min base
off time.)
09 Heat
temperature range stop
90 40-90 Heating high temperature range stop in °F. (4.5-32°C)
10 Cool temperature
range stop
50 50-99 Cooling low temperature range stop in °F. (10-37°C)
11 Power supply
frequency
0 0 60 Hz
1 50 Hz
12 Deadband
(3)
(3) See “Deadband,” p. 41. For auto or manual systems (see Option 01).
3 2 2°F (1.0°C)
3 3°F (1.5°C) 4 4°F (2.0°C) 5 5°F (2.5°C) 6 6°F (3.0°C) 7 7°F (3.5°C) 8 8°F (4.0°C) 9 9°F (4.5°C)
18 Restore factory
defaults
0 0 No - do not reset
1 Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
BAS-SVX36C-EN 33
Operation
This section provides general descriptive and procedural information intended for typical daily
operators of the thermostat.
Icon Descriptions
Figure 36 describes the icons visible on the front of the thermostat.
Note: Except when the thermostat is powering up, when all of the icons are shown for 2 sec, only
some of the icons will be visible at once.
Figure 36. Thermostat Icons
Overview of Operation
If configured properly,both programmable and non-programmable thermostats will control HVAC equipment to maintain room temperature automatically.
AM PM
DAYS
HOURS
Mo Tu We Th Fr Sat Su
.
.
Large numeric display - Shows current temperature but
can indicate other information.
Temperature units - F or C.
Setpoint indicator - upper arrow
indicates cooling setpoint; lower arrow
indicates heating setpoint.
Heating mode indicator - heating, cooling,
automatic heating/cooling, or off.
Period indicator - morning, day, evening, night.
Time of day - 12 hour clock with AM and PM
indicator or 24 hour clock.
Configuration/test indicator - solid for
configuration mode; flashing for test mode.
Space unoccupied indicator.
Timed override indicator
Button lock indicator
Space occupied indicator
Icons on the non­programmable thermostats have the same function, but no programming/ scheduling-related buttons appear.
Fan mode indicator - auto or on.
34 BAS-SVX36C-EN
Operation
Non-ProgrammableThermostats
Non-programmable thermostats do not have timekeeping or scheduling capabilities.They will continue to maintain heating and/or cooling setpoints until an operator makes changes to the setup.Therefore, only the following tasks may be required performed:
Change the system mode.
Show or change the heating or cooling temperature setpoint.
Change the fan mode.
Note: The
system mode, temperature setpoints, and fan mode can each be individually locked to
prevent users from changing them. If you see a on the display, you may need to unlock
the setting before you change it (see “Locking or Unlocking Modes,” p. 40).
Changing the System Mode
Note: If you are unable to change the system mode, checkthe system type setting and the manual/
auto changeover setting (see “Configuration,” p. 26) to verify that the thermostat is configured with heat and cool modes, and that it permits manually changing them.
Depending upon the model and system type, the thermostat can be set to one of five modes: Cooling, Heating, Emergency Heat, Auto, or Off.
Note: The
1-Heat/1-Cool thermostat does not have Emergency Heat mode.
To change the system mode:
1. Press > .The current mode flashes.
2. Press or to select a mode.
3. Tap or wait 5 sec to save and exit.
Showing or Changing the Heating or Cooling Temperature Setpoint
To change the heating or cooling setpoint:
1. Press or once.This shows the active setpoint.
2. Within 5 sec:
P
ress or to increase or decrease the setpoint.
Press or to change between heat and cool setpoints if both are enabled.
3. Tap or wait 5 sec to save and exit.
Cooling mode cools the room to bring it down to the cooling setpoint.
Heating mode heats the room to bring it up to the heating setpoint.
Emergency Heat mode heats the room according to the heating unit’s emergency heat mode
settings.
Auto mode switches automatically between heating and cooling modes as required.
Off mode prevents the thermostat from requesting any heating or cooling regardless of the
room temperature. Off mode also disables fan selection and prevents the user from changing the setpoint.
BAS-SVX36C-EN 35
Operation
Changing the Fan Mode
Note: If you are unable to see the fan mode, check the system type setting in the installation
configuration options to make sure that it is specified as a system with a fan.
There are two fan modes. Each are indicated by an icon on the display:
T
o change the fan mode:
1. Press > > .The current mode flashes.
2. Press or to change the mode.The selected mode flashes.
Note: If
you are unable to change the mode and flashes, the mode is locked. See “Locking
or Unlocking Modes,” p. 40.
3. Tap or wait 5 sec to save and exit.
ProgrammableThermostats
Programmable thermostats contain all of the functionality of the non-programmable thermostats, but they also keep track of the date, day of week, and time of day for scheduling purposes.
Programming
This section describes how to program the thermostat after it has been installed and configured.
Setting the Time
The time must be set in the thermostat to ensure operation of the schedule.
Note: The
date is set during configuration and the day of the week is calculated automatically
according to the date.
To set the time:
1. Press > > > > > .The hour flashes to indicate that it can be changed.
Note: The thermostat automatically returns to normal operating mode if no buttons are
pressed for 10 sec.
2. Make changes to the hour and minute, as needed:
P
ress or to switch between hours and minutes. The changeable option flashes to
indicate that it can be changed.
Press or to change the value of the option.
3. Press and hold for 2 sec or wait 10 sec to apply the change and exit.
Auto mode turns the fan on and off as needed according to equipment configuration.
On runs the fan continuously.
Mo
AM
36 BAS-SVX36C-EN
Operation
Scheduling
The thermostat can be configured for two periods (day and night) or four periods (morning, day,
evening, and night).The chosen number of periods are applied to each day of the week when you program the thermostat. Each period canhave a unique start time, heat setpoint, cool setpoint, and fan setting.
The groups of days can be one of the following:
1 day = all 7 days of the week follow the same schedule.
5+1+1 days = Monday - Friday all follow the same schedule; Saturday and Sunday each follow their own schedules.
5+2 days = Monday - Fridayall follow the same schedule; Saturday and Sunday follow the same schedule, which is different than the Monday - Friday schedule.
7 days = Each day follows its own schedule.
Note: See “Configuration,” p. 26 to change the number of periods in a day or the grouping of days
in the schedule.
If needed, you can use Table 9 to write down your schedule settings before you begin setting up the schedule.The default schedule is also shown in the table. Unless you program your own schedule settings, the thermostat follows the default schedule for all days of the week.
BAS-SVX36C-EN 37
Operation
Table 9. Weekly Operating Schedule Worksheet
Day Period Start time
Heating
setpoint
Cooling
setpoint Fan Setting
Four period
default settings
Morning 6:00 am 70° F (21.0° C) 78° F (25.5° C) Auto
Day 8:00 am 62° F (16.5° C) 85° F (29.5° C) Auto
Evening 6:00 pm 70° F (21.0° C) 78° F (25.5° C) Auto
Night 10:00 pm 62° F (16.5° C) 82° F (28.0° C) Auto
Two period
default settings
Day 6:00 am 70° F (21.0° C) 78° F (25.5° C) Auto
Night 10:00 pm 55° F (13.0° C) 85° F (29.5° C) Auto
Monday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Tuesday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Wednesday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Thursday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Friday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Saturday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Sunday Morning : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
38 BAS-SVX36C-EN
Operation
To set the schedule:
1. Press > > > .The display shows only the following elements:
2. Press .
Note: At
this point the thermostat is in schedule change mode. It returns to normal operating mode if no buttons are pressed for 45 sec.Tomanually exit schedule change mode, press and hold for 2 sec.
Note: If flashes and you areunable to enter schedule changemode, the mode is locked. See
“Locking or Unlocking Modes,” p. 40.
3. Press or to select the day or days for which you want to set the schedule.The selected day or days flash.
4. Press to accept the selection. , , ,or
starts flashing.
5. Press or to select the period. The selected period starts flashing.
6. Press to accept the selection.The start time starts flashing.
7. Press or to select the start time.Time is increased or decreased in 10 min steps.
8. Press to accept the selection. If there is a heat mode configured, the heat setpoint appears and its icons start flashing.
9. Press or to select the heating setpoint.
Note: The
heating and cooling setpoints cannot be closer together than the deadband, which is specified in installer configuration option #0181 (see “Configuration,” p. 26). If you raise the heating setpoint or reduce the cooling setpoint to a value that would violate the
deadband setting, the opposing setpoint will also adjust to maintain the deadband.
10. Press to accept the selection. If there is a cool mode configured, the cooling setpoint appears and its icons start flashing.
11. Press or to select the cool setpoint.
12. Press to accept the selection. or starts flashing.
13. Press or to select the fan setting.
to
turn it on and off automatically
to keep the fan on continuously
14. Press to accept the selection. This completes the schedule settings for one period of one day of the week.
15. Repeat Step 3 through Step 14 once for each day and period you need to set.
MoTu We Th Fr Sa Su
Mo
AM
BAS-SVX36C-EN 39
Operation
Day-to-Day Operation
After a programmable thermostat is configured and the schedule is programmed, the thermostat
automatically changes the setpoints and fan settings accordingto theschedule.However, there are some operator tasks that you may need or want to perform:
Show setpoint or current temperature.You can temporarily or permanently switch the main display
from current temperature to temperature setpoint. See “Showing the Setpoint or
Temperature on Display,” p. 39.
Set the system mode, which includes turning the system on or off, and switching between heating,
cooling, and automatic heating and cooling. See “Changing the System Mode,” p. 34.
Override the schedule. If an unexpected, one-time temperature setpoint or fan mode change is needed
you can temporarily override the schedule. See “Timed Override (TOV) Mode,” p. 40.
Lock or unlock. You can lock the thermostat buttons to prevent changes to the thermostat set
tings. See “Locking or Unlocking Modes,” p. 40.
Note: It
is possible for a programmable thermostat to be configured to be a non-programmable thermostat. If installation configuration option #140 is set to 0, schedule programming capabilities will be absent.
Showing the Setpoint or Temperature on Display
Depending upon the value of configuration option #210, the large numeric display could show any of the following:
Figure 37. Display Options
To switch between the current temperature, “o dr” temperature, and the setpoint temperature,
press and hold the and buttons for 3 sec.The display will toggle as shown in Figure 37.
Value of configuration option #210
Numeric display options (press and for 3 sec to change)
0 The current local temperature, or the current or most recent temperature setpoint
1 or 2 The current local or remote indoor temperature or the current or most recent temperature
setpoint
3 The current indoor temperature, the current or most recent temperature setpoint, or the
current remote outdoor temperature, which only appears for 8 sec before reverting to current indoor temperature or setpoint
.
.
Mo
AM
Current temperature Current (or most
recent) setpoint
Current outdoor temperature
Arrow indicates
setpoint
“o dr” indicates outdoor temperature (after 8 sec, returns to previous mode)
40 BAS-SVX36C-EN
Operation
Timed Override (TOV) Mode
During normal operation, the thermostat controls the HVAC equipment according to the schedule that is programmed into it.To permanently change the temperature setpoint or fan setting, make the change in the programmed schedule (see “Scheduling,” p. 36). However, a timed override can be used to temporarily change the current settings without making any change to the schedule.
To start a temperature setpoint override:
1. Press or .The current temperature setpoint appears.
2. Within 5 sec of Step 1, press to raise the setpoint or to lower the setpoint.The thermostat enters timed override mode, giving you the opportunity to specify the other parameter
s of the override.
3. Press and release or (or , which has the same function as ) to scroll to heating or cooling temperature setpoints, fan mode, override duration, or occupancy setting.
4. When you reach thefunction you want tochangeas part of theoverride,press and make the changes.
5. Once you have specified all needed changes, press and hold for 2 sec or wait 15 sec to save and exit.
6. Press and hold and for 2 sec from the home screen or when in TOV setup mode to exit without enteringTOV mode.
Locking or Unlocking Modes
You can independently lock and unlock the system, fan, and schedule change modes.When a lock
is activated, users cannot change the current mode or schedule settings. If you attempt to make a change, flashes on the display.
To lock a mode:
1. Enter the mode you want to lock:
>
> for system mode
> > for fan mode
> > > for schedule mode (programmable thermostat only)
2. Make sure thatthe mode or schedule you entered is correct; if not, make the necessary changes.
3. Simultaneously press and hold and for 4 sec.When the mode is locked, appears on the display.
To unlock a mode:
1. Enter the mode you want to unlock:
>
> for system mode
> > for fan mode
> > > for schedule mode (programmable thermostat only)
2. Simultaneously press and hold and for 4 sec.When the mode is unlocked, disappears.
BAS-SVX36C-EN 41
Operational and Programming Reference Information
This section provides additional information that may be useful for understanding thermostat
operation or programming.
Deadband
The thermostat automatically maintains a temperature deadband between the heating setpoint
and the cooling setpoint whenever automatic changeover (heat-to-cool or cool-to-heat mode) is enabled.The temperature range of the deadband is 2–9 °F (1.0–4.5°C) and is specified in the installation configuration options (see “Configuration,” p. 26). If you attempt to change a temperature setpoint to within the deadband of its opposing setpoint, the opposing setpoint will automatically be pushed to the next value that satisfies the deadband. (See Figure 38.)
Heat and Cool Cycling Rate
The heat and cool cycling rate, expressed in cycles per hour (CPH) indicates how often heating or
cooling system is turned on when temperature is within the temperature differential from the setpoint, which is 1°F (0.5°C).There are ten options (1–10) for heat stages and five options (1–5) for cool stages.The number selected is the maximum number of times the stage is cycled in 1 hr.
For example, when the system is set to 5 CPH, it runs at 12 min cycles with variable duty cycle. Depending on the heating or cooling load, which is measured by feedback from the sensor thermistor and/or temperature error, the system could run at 50% duty cycle (6 min ON and 6 min OFF), 80% duty cycle (9.6 min ON and 2.4 min OFF), or other variations of the duty cycle.
Note: The
cycling rate described above is only active when the temperature is within the temperature differential. If the temperature is outside of the temperature, the heating and cooling equipment will either be fully on or fully off accordingly. (See Figure 38.)
Figure 38. General Heat and Cool Cycling Rate Diagram
There is one cycling rate setting for each of the thermostat’s available heat and cool stages,
including
auxiliary and emergency heat stages.You can specify them during installation
configuration. See “Configuration,” p. 26.
Minimum Compressor Off Time
To protect the compressor from cycling too frequently, there is an automatic 5 min gap between
cycles.You cannot reduce the gap, but you can add up to 5 min if needed. See “Configuration,”
p. 26.
All heat
stages on
TD
0 %
100 %
TD TDTD
All heat stages
cycling dependent
on load
All heat and cool
stages off
All cool stages
cycling dependent
on load
All cool
stages on
Heat set point
temperature differential
(TD) is ±1°F (0.5°C) centered on set point
Cool set point
temperature differential
(TD) is ±1°F (0.5°C)
centered on set point
Temperature
Output
Adjustable deadband
2–9°F (1–4.5°C)
42 BAS-SVX36C-EN
Operational and Programming Reference Information
Configuration and Programming Retention
The thermostat retains the time and date for a minimum of 5 days with no electricity. If power is
lost for more than 5 days, you will need to reset the time and date when power is restored.
All configuration parameters, system settings, and scheduling are stored in non-volatile memory,
which will retain the data indefinitely with or without power.
Note: You can manually revert to default settings by setting the appropriate installation parameter
(#300 for programmable thermostats or #18 for non-programmable thermostats) to a value of 1, and exiting configuration mode.
Extended Fan-onTime (Heat or Cool)
Note: This feature applies only to the programmable thermostat.
When the thermostat fan is in Auto mode, the fan on time can be extended.
Configuration option #270 extends the fan on time by 90 sec after heat turns off.
Configuration option #271extends the fan on time by 40 sec after cool turns off.
These options may not be available for some system configurations. See “Configuration,” p. 26.
Compressor and Auxiliary Heat Lockout
Note: This feature applies only to the programmable thermostat.
Compressor and auxiliary heat is used for heat pump systems with more heat stages than cool stages. When the temperature from an outdoor sensor is
above the auxiliary lockout point, only the compressor will operate on a call for heat.
below the compressor lockout point, only the auxiliary heat will operate on a call for heat.
between the compressor and auxiliary lockout point, the compressor and auxiliary heat will operate on a call for heat.
There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout
temperatures. Configuration option #220 sets the compressor lockout point; #221sets the auxiliary lockout point. See “Configuration,” p. 26.
Auxiliary Heat Control
Note: This feature applies only to the non-programmable 3-Heat/2-Cool thermostat.
You can set the auxiliary heat control using configuration option #17 to one of two settings:
Comfort - prioritizes comfort over economy. Raising the temperature just a few degrees often will activate the auxiliary heat.
Economy - attempts to reach the temperature setting without activating the auxiliary heat.
Economizer/TOD
Note: This feature applies only to the programmable thermostat.
You can set the Economizer orTOD mode using configuration option #150 to one of two settings:
Economizer Mode - “A” terminal is energized with the thermostat in Occupied mode, Unoccupied mode with a call for cool, or aTimed Override mode (TOV) active.
TOD Mode - “A” terminal is energized with thermostat in Occupied mode or aTimed Override mode (TOV) active.
BAS-SVX36C-EN 43
Troubleshooting
This section describes troubleshooting for the thermostat.
Error Codes
An error code indicates that technical assistance may be required.
Try cycling the power to the thermostat as a first method to clear the error. See Table 10 below and
Table 12, p. 47 for additional information.
Note: On
the display, error codes appear at the bottom of the display.
Note: On
the programmable thermostat, the error code alternates with the time on the display.
SystemTest Mode
You can run diagnostictests on the thermostat to verify that the thermostat is functioning properly
and that the devices in the system are wired properly.
To enter system test mode:
1. Apply electrical power to the thermostat.
2. Enter installer configuration mode:
Table 10. Error Codes
Code Description
E0 Thermistor Error; occurs when the configured thermistor reading is out of range (less
than 14°F (-9.9°C) or greater than 122°F (50°C). If this error occurs:
• All Heat/Cool outputs turn off.
• If the fan mode is Auto, the thermostat turns off the fan.
• If the fan mode is On, the thermostat leaves the fan on.
E3 Permanent data error. Access error or checksum error is detected.
E4 Input voltage out of range - too low or too high. Input voltage is lower than 18Vac or
higher than 34V
ac. The error code display will remain on for 30 sec after the detection
of out of range input voltage.
E5 RTC Error (this error can only appear on the programmable thermostat).
E7 Memory error (write and read 0x55 and 0xAA failed). Only checked during power up test.
44 BAS-SVX36C-EN
Troubleshooting
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec, then release it.
Figure 39. Pressing the Configuration Button
The configuration wrench icon appears, along with the option number and value.
3. Press and hold the configuration button again for at least 3 sec, then release it.The thermostat goes
into system test mode:
The
wrench icon flashes.
The system test number appears in small digits at the lower part of the display.
The test setting value appears in large digits at the top part of the display.
Figure 40. SystemTest Mode
Note: S
ystem test mode automatically ends if no buttons are pressed for 10 min.
While in system test mode, you can scroll from one test to the next, change the value for the
test,
then test or observe the systemfor the expected result.The numbers and values are shown in Table 11 , p . 46. Some values are retained when you scroll to the next number; others are deactivated when you scroll to the next number, as indicated in the table.
4. Press , ,or to scroll through the options, identified by their numbers, until you reach the option you want to change:
or scrolls to the next larger numbered option. scrolls to the next lower-numbered option.
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Programmable 3H/
2C configuration
button
Non-programmable
thermostats
configuration button
Value
Programmable Thermostat
Non-Programmable Thermostat
System Test Number
BAS-SVX36C-EN 45
Troubleshooting
5. Use or to change the value of the option:
decreases the value.
increases the value.
6. Repeat Step 4 and Step 5 until you have conducted all needed tests.
7. Change the value of the power up test (test number 8 for the 1-Heat/1-Cool thermostat; test number
11 for the 3-Heat/2-Cool or programmable thermostat) to 1 to run a power up test after
you exit test mode.
8. Do one of the following to exit test mode:
R
emove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
Do not press any buttons for 10 min.
Press and hold for 2 sec.
46 BAS-SVX36C-EN
Troubleshooting
Table 11. SystemTest Descriptions
Test Number
Description Values
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(p/n X13511536-01)
Programmable
Thermostat
1
(1)
(1) Only values 0 and 1 are available because there are only one heat and one cool stage.
1 1 Heating system 0 = all heating stages off
1 = heat stage 1 on; heat stage 2 off 2 = heat stage 2 on; heat stage 1 off 3 = heat stage 1 and 2 on This setting remains active when you scroll to the next setting.
2
(1)
2 2 Cooling system 0 = all cooling stages off
1 = cool stage 1 on; cool stage 2 off 2 = cool stage 2 on; cool stage 1 off 3 = cool stage 1 and 2 turn on This setting remains active when you scroll to the next setting.
333 Fan system 0 = fan off
1 = fan on This setting remains active when you scroll to the next setting.
NA 4 4 O/B changeover valve 0 = changeover valve off
1 = changeover valve on This setting remains active when you scroll to the next setting.
NA NA 5 TOD/Economizer system 0 = TOD/Economizer off
1 = TOD/Economizer on This setting remains active when you scroll to the next setting.
NA 5 NA Auxiliary Heat 0 = Auxiliary heat and fan turns off
1 = Auxiliary heat and fan turns off This setting remains active when you scroll to the next setting.
NA 6 NA Emergency Heat 0 = Emergency relay, fan, and terminal L output turn off
1 = Emergency relay, fan, and terminal L output turn on This setting remains active when you scroll to the next setting.
586 LCD segments 0 = full segment on
1 = odd segments on; even segments off 2 = even segments on; odd segments off This setting is deactivated when you scroll to the next setting.
NA NA 7 Remote thermistor (S1 & S2)
temperature reading
0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting.
478 Internal thermistor
temperature reading
0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting for the 3H/2C and programmable thermostats, but it remains active when you scroll to the next setting for the 1H/1C thermostat.
699 Major software version Show major software revision number.
This setting is deactivated when you scroll to the next setting.
71010 Minor software version Show minor software version.
This setting is deactivated when you scroll to the next setting.
81111 Power up test 0 = do not run power up test on self-test exit
1 = run power up test on self-test exit This setting retained (and applied) upon exit from self-test mode.
BAS-SVX36C-EN 47
Troubleshooting
Troubleshooting Table
Use Table 12 to diagnose and solve problems you may encounter.
Table 12. Troubleshooting
Problem Solution
Error code E0 ­Thermistor error.
• For non-programmable thermostats and programmable thermostats set to use internal temperature sensor (configuration option #210 set to 0, 1, or 2): Thermistor is defective or local temperature is out of range. Replace or repair thermostat through a qualified Trane supplier.
• For programmable thermostats with configuration option #210 set to 3: Check the sensor terminals S1 and S2 for secure connection. If wires are securely connected, try replacing the sensor.
Error code E4 - Input voltage out of range
• Check the input voltage to the thermostat. It must be within the range of 18Vac to 32 Vac rms.
Error codes E3, E5, or E7 • Cycle the power to the thermostat.
• If it does not recover to normal operation, have it serviced or replaced by a qualified Trane supplier.
Blank display • Check the power supply.
• If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane supplier.
Erratic display appearance or contrast
• Check the power supply.
• Check the frequency configuration (Configuration option #210 for the programmable thermostat or #11 for non-programmable thermostats) to make sure that you are using the correct frequency setting for your power supply.
• If the power supply and frequency setting are ok, have the thermostat serviced or replaced by a qualified Trane supplier.
Buttons do not respond • Make sure the thermostat modes are not locked. See “Locking or Unlocking Modes,”
p. 40.
• Cycle the power to the thermostat.
• If the modes are not locked and cycling the power do not solve the problem, have the thermostat serviced or replaced by a qualified Trane supplier.
“--F” or “--C” flashes • Temperature is outside of the measurable range. The temperature reading should be
correct when the temperature is within the measurable range.
Fan settings are not visible
• Check the system status. If the status is Off, the fan settings will not appear.
• Check the configuration options to verify that the fan is enabled: For programmable thermostats, check options 0130 and 0151; For non-programmable thermostats, check options 01 and 03.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012Trane. All rights reserved.
BAS-SVX36C-EN 13 Mar 2012
Supersedes BAS-SVX36B-EN 30 Sep 2010
Thermostat Specifications
Table 13. Specifications
Programmable Thermostat Non-Programmable Thermostats
Input power 24Vac, 50Hz or 60Hz
(18Vac to 32Vac) (Power supply frequency selected using installation configuration option #190)
24Vac, 50Hz or 60Hz (18Vac to 32Vac) (Power supply frequency selected using installation configuration option #11)
Wire size 18 to 22 AWG 18 to 22 AWG
Output terminal ratings 1A @ 30Vac 1A@ 30Vac
Indoor temperature display range
+15 to +122°F (–9.5 to +50°C) +32 to +99°F (0 to +37°C)
Outdoor (remote) temperature display range
–31 to +122°F (–35 to +50°C)
NA
Storage temperature
–40 to +158°F (–40 to +70°C) –40 to +158°F (–40 to +70°C)
Accuracy ±1.4°F (±0.8°C) over a range of
50 to 90 °F (10 to 32.2°C)
±1.4°F (±0.8°C) over a range of 50 to 90 °F (10 to 32.2°C)
Resolution Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C,
0.1°C
Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C, 0.1°C
Power consumption
< 1VA < 1VA
Housing materials and rating information
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a plenum.
Polycarbonate/ABS blend, UV protected, UL 94­5VA flammability rating, suitable for application in a plenum.
Mounting
3.24 in (8.26 cm) for two mounting screws (supplied)
3.24 in (8.26 cm) for two mounting screws (supplied)
Loading...