Trane Thermostats, X13511535010, X13511536010, X13511537010, X13511538010 Product Data Sheet

Trane™ Thermostats
Programmable and Non-programmable
July 2011 BAS-PRC036-EN
Product Data Sheet
Trane offers a line of programmable and non-programmable commercial thermostats for conventional (rooftop) air conditioners and heat pumps. Features and benefits include:
Intuitive Liquid Crystal Display— are easy to use and read for all users and languages.
Configurable— permits usage in conventional (RTU) systems or heat pumps with and without auxiliary heat.
Dehumidification— only with touch screen model.
Part Numbers
Model
X Code Clarksville
Global
Parts
Thermostat, non-programmable, 1-heat/1-cool X13511535010 BAYSTAT151A THT02772
Thermostat, non-programmable, 3-heat/2-cool X13511536010 BAYSTAT155A THT02773
Thermostat, programmable, 3-heat/2-cool X13511537010 BAYSTAT150A THT02774
Thermostat, programmable, touch screen, 3-heat/2-cool/dehumidification X13511538010 BAYSTAT152A THT02775
2 BAS-PRC036-EN
Specifications
Dimensions
Category Specification/Description
Input power: 24Vac, 50 Hz or 60 Hz (18 Vac to 32 Vac)
Wire size: 18 to 22 AWG
Output terminal ratings: 1A resistive load @ 30 Vac
Temperature display
ranges:
• Non-programmable: 32°F to 99°F (0°F to 37°C)
• Programmable Push Button: +15 to +122
º
F (-9.5 to +50 ºC)
• Programmable Touch Screen -45°F to 199°F (-42.8°C to 92.8°C)
Temperature setpoint
ranges:
• Heat Setpoint: 40°F to 90°F (4.5°C to 32
°
C)
• Cool Setpoint: 50°F to 99°F (10°C to 37°C)
Display type: LCD
System modes:
• Heat
• Cool
• Auto
• Off
• Emergency Heat (NO Emergency Heat on 1H/1C non-programmable model)
Fan modes:
•On
• Auto
Only Programmable:
Remote temperature
sensor:
The thermostat includes terminals for a remote temperature sensor. They can be used for display, H/C control, or heat pump compressor lockout. The remote sensor must be 10K type 2. Recommended sensors include: Zone Temperature Sensor BAYSENS077A (X1351152801, SEN01488) or Duct Temperature Sensor BAYSTAT170A (41901133, SEN01287)
Scheduling options:
5/2 day; 5/1/1 day; 1 day; 7 day. Two (Day/Night) or four (Morning/Day/Evening/Night) configurable periods per day.
Temporary override: Users can temporarily change the temperature setpoints, fan mode, and/or occupancy setting from the programmed schedule.
Lockout:
System, fan, and/or schedule settings can be locked out individually on the programmable push button model. The touch screen locks out all functions at the same time except for Clean Screen and Filter Change functions.
Only Touch Screen:
Remote humidity sensor:
Touch screen thermostat has an internal humidity sensor and is capable of including a remote humidity sensor. The remote humidity sensor must be a 4–20 mA, 24 Vdc type. Recommended humidity sensors: Wall Mount BASYSENS036A (X1379044401, SEN01177) and Duct Mount 4190 7020 (X1379044501).
Humidity display range: 0% to 99% (1% steps)
Humidity setpoint range: 30% to 80% (1% steps)
Dimension Programmable
Non-
Programmable
Programmable
Touch-screen
H 4.7 in. (119 mm) 4.7 in. (119 mm) 3.3 in. (85 mm)
W 3.3 in. (83 mm) 3.1 in. (78 mm) 5.9 in. (150 mm)
D 1.1 in. (28 mm) 1.1 in. (28 mm) 1.3 in. (33 mm)
M 3.3 in. (85 mm) 3.3 in. (85 mm) 3.3 in. (85 mm)
W
H
D
M
Two (2) slots for standard #8-32 (M4), 2”x4” junction box mounting screws.
Loading...