Trane WTK507, WTK509, WTK Series, WTK512, WTK518 Installation Manual

...
Installation Manual
Split Water-Cooled Condensing Units 7,000 - 60,000 Btu/h WTK Series 50 Hz
50Hz Models Cooling Only
April 2004
WTK-SVN001-EN
General Information
Introduction
This Installation Manual is given as a guide to good practice in the installation by the installer of mini-split system. Installation procedures should be performed in the sequence that they appear in this manual. For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company. Read these Installation Manual completely before installing the condensing unit.
About the Unit
The units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to units that are designed to operate in cooling mode only.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your Trane sales representative.
Reception
On arrival, inspect the unit before signing the delivery note. Verify that the nameplate data matches the date on the sales order, submittal data and delivery note (including electrical data) to insure the proper unit was shipped. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time. The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installer does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical board and motors if the unit is stored before it is installed. The Trane Company will not assume any responsibility for unit damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
About this Manual
Cautions and warnings appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
2
© American Standard Inc. 2003
WTK-SVN001-EN
Contents
General Information 2
Model Nomenclature 4
Location and Preparation of Unit 5
Refrigerant Tube Size Selection 5
Connection of Refrigerant Tubing
(Flaring and Brazing Procedure) 6
Water Pipe Connection 8
Gas Leakage Inspection 9
Air Evacuation and Refrigerant Charge 10
Wiring and System Inspection
before Test Run 11
Condenser Cleaning 11
Wiring Diagram 12
Dimensional Data 14
WTK-SVN001-EN
3
Model Nomenclature
W T K 5 0 7 A B 0 0 B A
123456789101112
Digit No. 1 = Product Type
W=Split Water Cooled Condensing Unit
Digit No. 2
T=Cooling Only W=Heat Pump
Digit No. 3 = Refrigerant Circuit(s)/Compressor(s)
K=Single Refrigerant Circuit/Compressor D=Dual Refrigerant Circuits/Compressors T=Tr iple Refrigerant Circuits/Compressors (Others to be determined as needed.)
Digit No. 4 = Refrigerant Connection Type
0=Sweat (Brazed) 5=Flared (Tubing) 7=Quick Connect
Digit No. 5 and No. 6 = Nominal Capacity
Btu/h X 1000 (Note: Exact system capacities/performance when matched with selected indoor unit are specified in Product Catalogs.)
Digit No. 7 = Major Development Sequence Digit No. 8 = Electric Power Supply Characteristics
A=220V/1ph/50Hz or 200-220V/1ph/50Hz B=240V/1ph/50Hz or 220-240V/1ph/50Hz 1=220V/1ph/60Hz or 200-240V/1ph/60Hz 3=200-240V/3ph/60Hz D=380-415V/3ph/50Hz 4=460V/3ph/60Hz
Digit No. 9 and 10 = Factory Installed Options
(Note: The Alphabetic Letter “O” is not used in digit 9 or 10, Only the Number “0” is used.) 00 = No option 0E = 3 minute time delay (for use w/ MCD) 0F = Hi/Lo Pressure Cut Off 0G = 3 minute time delay + Hi/Lo Pressure Cut Off
0S = Special request to be provided in wording and to be approved by factory i.e. service valve at the water side, insulation on suction line, emergency stop.
Digit No. 11 = Minor Design Sequence/Series - Design Change
Alphabetic Letter, “A” through “Z”
Digit No. 12 = Service Digit
4
WTK-SVN001-EN
Location and Preparation of Unit
Installation of Condensing Unit at
More than 15 cm
the appropriate places
• The place where is not near the gas area of potentially hazardous situations.
More than 10 cm
•Isolated place to avoid noise and heat disturbing to neighbourhood
• Convenient places for inspection
More than 35 cm
or reparation
Refrigerant Tube Size Selection
To select tube size is necessary to consider many factors such as: velocity of refrigerant, number of tube connector, bended joint and length of refrigerant tube. Therefore, for quick selection size of refrigerant tube, see the detail below:-
Refrigerant tube size for Trane
More than 35 cm
Air-conditioning (size 7,000-60,000 Btu/h)
Figure 1
Domestic
Tubing Length (m) /Tubing size (inch) Minimum 12 m 13 - 18 m 19 - 24 m 25 - 30 m 31 - 36 m
Model Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line
WTK507 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK509 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK512 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK518 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK524 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK530 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK536 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
WTK048 1/2 7/8 1/2 7/8 1/2 7/8 1/2 7/8 1/2 1 1/8
WTK060 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
More than 35 cm
Export
Tubing Length (m) /Tubing size (inch) Minimum 12 m 13 - 18 m 19 - 24 m 25 - 30 m 31 - 36 m
Model Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line
WTK507 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK509 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK512 1/4 1/2 1/4 1/2 1/4 1/2 1/4 1/2 1/4 1/2
WTK518 1/4 1/2 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK524 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK530 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK536 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
WTK048 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8
WTK060 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8
WTK-SVN001-EN
5
Loading...
+ 11 hidden pages