Trane WTK507, WTK509, WTK Series, WTK512, WTK518 Installation Manual

...
Page 1
Installation Manual
Split Water-Cooled Condensing Units 7,000 - 60,000 Btu/h WTK Series 50 Hz
50Hz Models Cooling Only
April 2004
WTK-SVN001-EN
Page 2
General Information
Introduction
This Installation Manual is given as a guide to good practice in the installation by the installer of mini-split system. Installation procedures should be performed in the sequence that they appear in this manual. For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company. Read these Installation Manual completely before installing the condensing unit.
About the Unit
The units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to units that are designed to operate in cooling mode only.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your Trane sales representative.
Reception
On arrival, inspect the unit before signing the delivery note. Verify that the nameplate data matches the date on the sales order, submittal data and delivery note (including electrical data) to insure the proper unit was shipped. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time. The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installer does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical board and motors if the unit is stored before it is installed. The Trane Company will not assume any responsibility for unit damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
About this Manual
Cautions and warnings appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
2
© American Standard Inc. 2003
WTK-SVN001-EN
Page 3
Contents
General Information 2
Model Nomenclature 4
Location and Preparation of Unit 5
Refrigerant Tube Size Selection 5
Connection of Refrigerant Tubing
(Flaring and Brazing Procedure) 6
Water Pipe Connection 8
Gas Leakage Inspection 9
Air Evacuation and Refrigerant Charge 10
Wiring and System Inspection
before Test Run 11
Condenser Cleaning 11
Wiring Diagram 12
Dimensional Data 14
WTK-SVN001-EN
3
Page 4
Model Nomenclature
W T K 5 0 7 A B 0 0 B A
123456789101112
Digit No. 1 = Product Type
W=Split Water Cooled Condensing Unit
Digit No. 2
T=Cooling Only W=Heat Pump
Digit No. 3 = Refrigerant Circuit(s)/Compressor(s)
K=Single Refrigerant Circuit/Compressor D=Dual Refrigerant Circuits/Compressors T=Tr iple Refrigerant Circuits/Compressors (Others to be determined as needed.)
Digit No. 4 = Refrigerant Connection Type
0=Sweat (Brazed) 5=Flared (Tubing) 7=Quick Connect
Digit No. 5 and No. 6 = Nominal Capacity
Btu/h X 1000 (Note: Exact system capacities/performance when matched with selected indoor unit are specified in Product Catalogs.)
Digit No. 7 = Major Development Sequence Digit No. 8 = Electric Power Supply Characteristics
A=220V/1ph/50Hz or 200-220V/1ph/50Hz B=240V/1ph/50Hz or 220-240V/1ph/50Hz 1=220V/1ph/60Hz or 200-240V/1ph/60Hz 3=200-240V/3ph/60Hz D=380-415V/3ph/50Hz 4=460V/3ph/60Hz
Digit No. 9 and 10 = Factory Installed Options
(Note: The Alphabetic Letter “O” is not used in digit 9 or 10, Only the Number “0” is used.) 00 = No option 0E = 3 minute time delay (for use w/ MCD) 0F = Hi/Lo Pressure Cut Off 0G = 3 minute time delay + Hi/Lo Pressure Cut Off
0S = Special request to be provided in wording and to be approved by factory i.e. service valve at the water side, insulation on suction line, emergency stop.
Digit No. 11 = Minor Design Sequence/Series - Design Change
Alphabetic Letter, “A” through “Z”
Digit No. 12 = Service Digit
4
WTK-SVN001-EN
Page 5
Location and Preparation of Unit
Installation of Condensing Unit at
More than 15 cm
the appropriate places
• The place where is not near the gas area of potentially hazardous situations.
More than 10 cm
•Isolated place to avoid noise and heat disturbing to neighbourhood
• Convenient places for inspection
More than 35 cm
or reparation
Refrigerant Tube Size Selection
To select tube size is necessary to consider many factors such as: velocity of refrigerant, number of tube connector, bended joint and length of refrigerant tube. Therefore, for quick selection size of refrigerant tube, see the detail below:-
Refrigerant tube size for Trane
More than 35 cm
Air-conditioning (size 7,000-60,000 Btu/h)
Figure 1
Domestic
Tubing Length (m) /Tubing size (inch) Minimum 12 m 13 - 18 m 19 - 24 m 25 - 30 m 31 - 36 m
Model Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line
WTK507 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK509 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK512 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK518 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK524 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK530 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK536 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
WTK048 1/2 7/8 1/2 7/8 1/2 7/8 1/2 7/8 1/2 1 1/8
WTK060 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
More than 35 cm
Export
Tubing Length (m) /Tubing size (inch) Minimum 12 m 13 - 18 m 19 - 24 m 25 - 30 m 31 - 36 m
Model Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line Liquid Line Suction Line
WTK507 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK509 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 1/4 1/2
WTK512 1/4 1/2 1/4 1/2 1/4 1/2 1/4 1/2 1/4 1/2
WTK518 1/4 1/2 3/8 5/8 3/8 5/8 3/8 5/8 3/8 5/8
WTK524 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK530 3/8 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4
WTK536 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
WTK048 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8
WTK060 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8
WTK-SVN001-EN
5
Page 6
Connection of Refrigerant Tubing
Connection the Unit with Flaring Procedure
Flaring (If tubing is procured or cut at the site).
1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30 cm-50 cm (12” to 20”) longer than the tubing length you estimate.
2. Hold each tube downward when cutting, remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare (Figure 2 and Figure 3).
Copper tubing
Reamer
Figure 2
A good flare should have the following characteristics:
-Inside surface is glossy and smooth.
- Edge is smooth.
-Tapered sides are of uniform length.
Cautions Before Connecting Tubes Tightly
1. Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.
2. Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks (Figure 5).
Apply refrigerant lubricant here
4. Tighten the flare nut to the specified tightening torque with torque wrench and adjustable wrench (Figure 7).
5. Repeat the process above for the remaining line.
Specified tightening torque
Tube diameter Torque
mm inch kg - cm lb - in
6.35 mm (1/4”) dia. 150~200 130~170
9.53 mm (3/8”) dia. 350~400 300~340
12.7 mm (1/2”) dia. 500~550 430~470
15.88 mm (5/8”) dia. 600~650 520~570
19.05 mm (3/4”) dia. 700~750 610~650
22.23 mm (7/8”) dia. 800~850 700~740
28.58 mm (1-1/8”) dia. 900~950 800~825
Before After
Figure 3
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
3. Remove the flare nut from the service valve and be sure to insert the flare nut onto tube.
4. Make a flare at the end of copper tube with a flare tool (Figure 4).
Flare nut
Copper
tubing
Flare tool
Figure 5
Connection
3. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match (Figure 6).
Union Flare nut
Figure 6
Indoor
unit pipe
To rque wrench
Wrench
(Adjustable)
Tube connection
Flare nut
Figure 7
Figure 4
6
WTK-SVN001-EN
Page 7
Connection Unit with Brazing Procedure
Connection Unit with Brazing Procedure
1. Cut the copper tube to the require length with the tube cutter. It is recommended to cut approximately 20-30 cm longer than the tube length you estimate and put in the straight line while cutting.
2. After cutting, remove burrs at the end of copper tube with a tube reamer. Hold the end downward and be sure that no copper scraps fall into the tube (Figure 2).
3. There are 2 methods to connect copper tube
- Use tube connector between
copper tube from fan-coil unit and copper tube from condensing unit (Figure 8).
Tube connector
(straight)
- Expand copper tube with the tube enlarging tool (Figure 9).
Tube enlarging
tool
Tube fixing
Copper
tube
Figure 9
tool
4. Clean copper tube surfaces both inside and outside before connection, expansion, or brazing.
5. Insulate the entire gas line.
6. Do not allow uninsulated liquid line to come in direct contact with bare gas line.
7. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that a wet rag be wrapped around the valve body.
8. It is recommended to use braze shield, soak pad in water and place over suction and liquid lines to protect unit finish.
9. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do not forget to keep them tight as shown in figure 10.
Figure 8
Copper tube from
fan coil unit
Copper tube from
condensing unit
Brazing head
COMMET 3
Brazing
wire
Copper tube from
(torch)
connector
(straight)
condensing unit
Figure 10
10. Use a dry nitrogen purge and
brazing alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, through the tubing and out the other port while brazing.
11. Braze using accepted good
brazing techniques.
Tube
WTK-SVN001-EN
7
Page 8
Water Pipe Connection
Installers should prepare the following equipment:
Should have connected water pipe for heat exchange. Should have water pump, cooling tower, pressure gauge, and other equipments related to the water pipe connection. Please make sure that all equipments are according to the standard (see figure 11).
Water Return Pipe
Connect water return pipe with 3/4 inch pipe connector. Keep them far away from water tray and add trap (see figure 12).
Pressure-Reducing/
Water Return
Water Supply
Shutoff Valve
Shutoff Valve
Balancing Valve
Pressure Gauge
Plugged Cleanout Tee
Water Strainer
Thermometer
Plugged Cleanout Tee
Pressure Gauge
Thermometer
Figure 11
1 inch (25.4 mm) steel pipe and pipe connector
101 mm min
Flow Switch
Union
Union
Flexiible Connection
To Unit
Flexiible Connection
Equipment used
1Tee
From Unit
2Plug
70 mm min
3 Steel Elbow
4 140 mm Nipple
1 inch (25.4 mm) PVC pipe or copper pipe and pipe connector
Equipment used
101 mm min
1Tee
1Plug
390o Elbow
70 mm min
1 152 mm Nipple
2 50 mm Nipple
11 NPT to PVC
or copper adapter
Figure 12
8
WTK-SVN001-EN
Page 9
Gas Leakage Inspection
Gas Leakage Inspection
After charging with refrigerant, it is necessary to check gas leakage. Inspecting gas leakage should be done with special precaution. If there is any leakage that we are unable to find, afterwards the system would be damage. For example, if R22 refrigerant loses, cooling coil will be frozen. There are so many methods to inspect leakage, but the easiest and the most economical way is to use nitrogen gas detector and bubble of powder detergent per the following steps:-
•Prepare nitrogen tube with pressure regulator and pressure gauge or manifold gauge.
• Open service valve cover (at the suction side).
• Connect gauge line to the nitrogen tank, but do not open nitrogen valve at the nitrogen tank.
• Check out brazing track and all valves such as flare union.
• Connect the other tails of gauge line to the service valve (at the suction side).
•Slowly open nitrogen valve, let pressure gradually increase until 250 pound/square inches, then put bubble of powder detergent around all connected joints, notice any leakage. Fix the leakage, if any. If there is no leakage, leave 1-2 hours to check whether the pressure stays the same. If the pressure is still reducing, we need to check leakage again. Finally, release nitrogen gas in order to make refrigerant system to be under vacuum.
Caution
• Do not fully open nitrogen valve to 250 psig because valve may be damage.
• Do not forget to check the leakage at the access valve both at the liquid line and at the suction line.
WTK-SVN001-EN
9
Page 10
Air Evacuation and Refrigerant Charge
Evacuation
Air and humidity are the enemy of the air-conditioning system because humidity will react with R22 refrigerant and turns into acid, which will corrode the wire coil and reduce the compressor oil’s efficiency. Evacuation is a must to prevent refrigerant system from air and humidity.
Evacuation Procedure
Connect the middle hose of service gauge to the vacuum pump, then connect the hose at the low side to “service valve” of air-conditioning at suction line. Connect the hose at the high side to “service valve” at liquid line (figure 13).
Fill up R22 refrigerant into the system
To fill up R22 refrigerant is the final step of installation. After leakage check and power wiring, fill up R22 refrigerant to the system.
How to fill up R22 refrigerant
Normally, this needs to be done immediately after air evacuation per the following steps (figure 13)
•Fill up the refrigerant via valve at liquid line until pressure of the liquid line is around 120-150 psig (Don’t forget to evacuate air from liquid line before)
•Turn on evaporator and condensing unit.
•Fill up the refrigerant into suction line at the proper quantity while the unit is working.
• Let machine run for at least 20 minutes. Read pressure from pressure gauge “at both high and low side”, and read current from amp-meter. Usually, suction line pressure should be around 65-70 psig , and liquid line pressure should be around 250-275 psig.
If the pressure readings of both liquid line and suction line are in the range stated above and electric current reading is at full load ampere of condensing unit, it indicates that refrigerant’s volume is sufficient.
• But if suction pressure is lower than normal and electric current is far below full load ampere, it indicates that refrigerant is inadequate. You need to add more refrigerant.
• If suction pressure is higher than normal and electric current is over the full load ampere, and you notice some water spray holds on the compressor, it indicates over cooling system. You need to release some refrigerant.
Remark: When the interconnecting line is longer than 7.5 m, additional charging is necessary. For the additional amount, follow the table belows.
10
Service
hoses
Liquid
line
Suction
line
Electrical
connection
Figure 13
Liquid
pressure
Suction
pressure
Vacuum pump
R22
Piping Per each additional
size meter of
interconnecting line
Liquid-Suction grams/meter
1/4é-3/8
1/4é-1/2
3/8é-5/8
3/8é-3/4
3/8é-11/
1/2é-7/8
é é é é
é
8
é
23 grams/meter
26 grams/meter
59 grams/meter
60 grams/meter
68 grams/meter
117 grams/meter
WTK-SVN001-EN
Page 11
Wiring and System Inspection before Test Run and Condenser Cleaning
Electric wire and ground wire must comply with each country’s or regional’s regulation.
1. Wiring
Importance
- Check the unit nameplate for electrical rating. Make sure that the wiring is according to local codes and wiring system diagram.
-A separate power supply disconnect and a circuit breaker for overcurrent protection should be provided in the external power supply line.
-Always connect ground wire to condensing unit every time to prevent an electric shock in case of an electric leakage.
-Electric wires shall not contact to refrigerant pipes, compressor, motor and the other moving parts.
- Manufacturer assumes no liability for the problems caused by unauthorized change in the internal wiring.
- Should tighten up wire connection.
-Electric conductor parts must be copper only.
To inspect system before test run.
After finished installing air-conditioning, all system shall be inspected before starting.
• Check that all brazings are correctly made.
• Check that units are correctly installed and there are no other tools near or on top of the unit.
• Check the tubing and connections for leak.
• Check that unit has a proper ground wiring.
• Check for proper voltage and fuse size.
• Check electrical wire size used is as specified.
• Check all field wiring for tight connection.
• Make sure that electrical wires inside the unit do not contact to refrigerant pipes.
•Turn on the unit, check the system carefully.
Condenser Cleaning
After air-conditioning works for a while, it may cause scales at the surface of pipe in the condensing unit, which may cause by cooling water or rust inside cooling tower. Installer can notice from the reduction of water velocity, or the reduction of difference of water temperature in and out, or condensing temperature is higher than normal.
Therefore, to maintain efficiency of condenser, installer must clean up the pipe’s inside surface of condenser to prevent scales.
To clean up condenser with chemical
To clean up condenser with chemical is one of the methods to wipe out scales. To select proper chemical, installer need to consult the water treatment expert.
2. Electric Wire Connection
- See wiring diagram on page 12
-Slipover electric wire at the end
-After connect electric wire, check whether all screws are firmly tightened
The electric wire connection between outdoor and indoor unit should be according to the wiring diagram.
WTK-SVN001-EN
11
Page 12
Wiring Diagram
POWER SUPPLY 220-240V/1ph/50Hz, 200-240V/1ph/60Hz
POWER CIRCUIT
MS-1
RD
BL
L
CR
R
CPR
S
N
MS-2
BLK
C
CONTROL CIRCUIT FOR MODEL WITHOUT HPCO AND LPCO
*2TC
C1
FROM INDOOR UNIT
200-240VAC/1ph/50,60Hz
MS
CONTROL CIRCUIT FOR MODEL WITH HPCO AND LPCO
BYPASS LPCO WHEN UNIT START, BYPASS TIME PERIOD CAN BE SETTING 0-4.5 MINS
1TC
(FOR BY PART LPCO WHEN UNIT START)
BLK
1R-7
1R
1R-8
1R
LPCO
C1
HPCO
1R-1
1R-5
1R-6
G
C2
2R-7
*2TC
2R
2R-8
MS
C2
12
2R
2R-1
2R-2
2R-5
2R-6
FROM INDOOR UNIT
220-240V/1ph/50,60Hz
COLOR CODE
BL BLUE BLK BLACK RD RED
* 2TC AVAILABLE IN OPTIONAL MODEL
** APPLY FOR DOUBLE POLE CONTACTOR ONLY
(FOR SINGLE POLE CONTACTOR,CONNECT ELECTRIC LINE FROM COMPR-C DIRECT TO TERMINAL-N)
NOTES:
1. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM CONDUCTOR.
2. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
3. USE COPPER CONDUCTOR ONLY.
LEGEND
CPR COMPRESSOR MS COMPRESSOR MOTOR CONTACTOR HPCO HIGH PRESSURE CUT-OUT LPCO LOW PRESSURE CUT-OUT TC TIME-DELAYED CONTACT 3 MINUTES
1R LOCK OUT CIRCUIT RELAY 2R LOW PRESSURE SENSOR BYPASS RELAY
TERMINAL
COIL TERMINAL BOARD BY OTHER TERMINAL BOARD BY FACTORY FIELD WIRING FACTORY WIRING RELAY CONTACT NORMALLY OPEN CAPACITOR
LOW PRESSURE SENSING SWITCH HIGH PRESSURE SENSING SWITCH
WTK-SVN001-EN
Page 13
Wiring Diagram
WTK048-060
POWER SUPPLY 380-415V/3ph/50Hz ,460V/3ph/60Hz
G L1
BLK
MS-1
BLK
LPCO HPCO
C1
LEGEND
CPR COMPRESSOR MS COMPRESSOR MOTOR CONTACTOR HPCO HIGH PRESSURE CUT-OUT LPCO LOW PRESSURE CUT-OUT TC TIME-DELAYED CONTACT 3 MINUTES TERMINAL COIL TERMINAL BOARD BY OTHER TERMINAL BOARD BY FACTORY FIELD WIRING FACTORY WIRING RELAY CONTACT NORMALLY OPEN
CAPACITOR
LOW PRESSURE SENSING SWITCH
HIGH PRESSURE SENSING SWITCH
1R
FROM INDOOR UNIT 220V/1ph/50Hz
L2 L3
MS-2
RD
2
CPR
1
87
1R
MS-3
3
*TC
651
*AVAILABLE IN OPTIONAL MODEL
NOTES:
1. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM CONDUCTOR.
2. POWER WIRING AND GROUNDING OF
EQUIPMENT MUST COMPLY WITH LOCAL CODES.
3. USE COPPER CONDUCTOR ONLY.
YL
MS
COLOR CODE
YL YELLOW BLK BLACK RD RED
C2
WTK-SVN001-EN
13
Page 14
Dimensional Data
WTK507-518
400
400
WATER OUTLET
50.8
50.8
302.2
232.2
Ø3/4 FTP DRAIN PIPE
WATER INLET
LIQUID LINE
SUCTION LINE
358.2
293.2
POWER SUPPLY Ø3/4 In.
53.543
69
DOMESTIC
MODEL
REFRIGERANT CONNECTION SIZE (In.) WATER
LIQUID SUCTION CONNECTION SIZE (In.)
WTK507-509 1/4 3/8 3/4
WTK512-518 3/8 5/8 3/4
400
14
EXPORT
MODEL
REFRIGERANT CONNECTION SIZE (In.) WATER
LIQUID SUCTION CONNECTION SIZE (In.)
WTK507-509 1/4 3/8 3/4
WTK512-518 1/4 1/2 3/4
WTK-SVN001-EN
Page 15
109
22
179
49
Dimensional Data
WTK524-060
500
400
WATER INLET
LIQUID LINE
SUCTION LINE
477.6
179
WATER OUTLET
432.6
Ø3/4 FTP DRAIN PIPE
DOMESTIC
EXPORT
POWER SUPPLY Ø5/8 In.
477.6
412.6
43
51.1
200.4
MODEL REFRIGERANT CONNECTION SIZE (In.) WATER
LIQUID SUCTION CONNECTION SIZE (In.)
WTK524-530 3/8 5/8 3/4
WTK536 3/8 3/4 3/4
WTK048-060 1/2 7/8 7/8
MODEL REFRIGERANT CONNECTION SIZE (In.) WATER
LIQUID SUCTION CONNECTION SIZE (In.)
WTK524-530 3/8 5/8 3/4
WTK536 3/8 3/4 3/4
WTK048-060 3/8 1-1/8 7/8
520
WTK-SVN001-EN
15
Page 16
Trane Thailand
7th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road Samrong Tai, Samutprakarn 10130
http://www.trane.com An American Standard Company
Literature Order Number
Supersedes
Stocking Location Bangkok, Thailand
WTK-SVN001-EN0404
WTK-SVN001-EN0303
∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“¡‘ßæ√“¬ µ.”‚√ß„µâ Õ.æ√–ª√–·¥ß ®.¡ÿ∑√ª√“°“√ 10130
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Loading...