High Efficiency
Horizontal and Vertical
Water-Source Comfort System
Axiom
1/2 - 5 Tons — 60 HZ— Model GEH/GEV
TM
March 2005
WSHP-PRC001-EN
Introduction
Imagine a full range of comfort utilizing efficiency, sound attenuation, integrated controls, and superior
maintenance accessibility... Trane
imagined it, and designed an advanced mechanical system.
Introducing models GEH and GEV water source comfort solutions.
Model GEH (pictured below) is a ceiling hung product that provides a sleek,
innovative shape, along with convertibility of the supply-air and the return-air arrangement; serviceability to
maintenance components; indoor air
quality standards; sound attenuation;
and best of all, higher efficiencies with
certified ARI-ISO 13256-1 performance and ASHRAE 90.1 standards.
Trane’s new design incorporates system advantages such as:
The horizontal and vertical configuratios range in capacities from 1/2 to 5
tons.
The innovative designs offers superior
field flexibility at the jobsite along with
service accessibility.
Model GEH Cabinet
The GEH cabinet design includes a
modular platform that utilizes similar
parts and assemblies throughout the
product line. It is constructed of heavy
gauge (non-painted) galvanized metal
for maximum durability and corrosive
resistive exterior.
The cabinet front allows service access for the controls and refrigeration
circuitry. Water-in/out connection and
high/low voltage hook-up is accomplished at the 45-degree corners on
the front-side of the equipment.
The unit offers six product variations
of return-air and supply-air combinations which may be order-specific or
job-site modified. See Figure 1 component platform location.
Model GEV Cabinet
The vertical design, model GEV
includes a 3 1/3-ton configuration
physically sized for condominium
installations.
The cabinet design contains a modular
platform utilizing similar parts and
assemblies to the horizontal to provide
a repetitious look and feel for
installation and maintenance
personnel. It is constructed of heavy
gauge (non-painted) galvanized metal
for maximum durability and corrosive
resistive exterior.
The cabinet front allows service access
for the controls and refrigeration
circuitry. Water-in/out connection,
drain connection, and high/low
voltage hook-up is accomplished at
the 45-degree chamfered corners on
the front-side of the equipment. The
vertical design offers four product
variations of return-air and supply-air
combinations.
The GEV model’s supply air
arrangement may be field converted
through a service kit to aid in stocking
of a single unit variation. See
Figure 2 for component platform
location.
Figure 1: Component platform location
Figure 2: Component platform location
4WSHP-PRC001-EN
Features and
Benefits
1
FRONT
4
FRONT
UNIT
UNIT
2
5
UNIT
FRONT
UNIT
FRONT
Figure 3: Airflow combinations of
GEH 1/2 through 5-tons
3
6
UNIT
FRONT
UNIT
FRONT
Supply/Return Air Combinations
The GEH model configuration may be
built to order or modified on-site to
meet unique installation requirements. The six combinations include:
1 Left return-air with left supply-air
combination
2 Left return-air with rear supply-air
combination
3 Left return-air with right supply-air
combination
4 Right return-air with left supply-air
combination
5 Right return-air with rear
supply-air combination
6 Right return-air with right
supply-air combination
1
UNIT
FRONT
UNIT
FRONT
2
UNIT
FRONT
3
4
UNIT
FRONT
Figure 4: Airflow combinations of
GEV 1/2 through 5-ton
See Figure 3 for the six field convertible combinations.
GEV Flexibility
The GEV model is also capable of
on-site modifications. With the vertical
configuration, the supply-air is easily
converted from a top supply-air to a
back supply-air with a service retrofit kit. The return-air option is order specific. The four combinations include:
1 Right return-air with top supply-air
combination
2 Right return-air with back supply-air
combination
3 Left return-air with top supply -air
combination
4 Left return-air with back supply-air
combination
See Figure 4 for the four supply-air/return-air combinations.
WSHP-PRC001-EN5
Features and
Benefits
Hanging Device
The hanging bracket resides in the
chamfered corner of the horizontal 1/2
to 5 ton equipment. This partially-concealed bracket design eliminates added height, width, or length to the
product. The brackets are factory
mounted to shorten job installation requirements.
The structural integrity of the design
helps assure no bracket deflection or
unit bowing from the unit’s weight.
Field return-air hook-up and filter
maintenance are more simplistic. Isolation for the hanging bracket is provided with a neoprene rubber
grommet design. This isolation device
helps prevent sound vibration from
reaching the structural support members of the building during compressor start and stop. See Figure 5 for
isolation device.
Drain Pan
The unit drain pan is composed of
plastic, corrosive resistive material.
The pan is positively sloped to comply
with ASHRAE 62 for (IAQ) indoor air
quality conformity.
Access to the drain pan is provided
through two access panels for cleaning purposes. See Figure 6 for plastic
drain pan.
Cabinet Insulation
The cabinet insulation design meets
UL 181 requirements. The air stream
surface of the insulation is fabricated
of a non-biodegradable source.
Refrigeration Piping
The unit’s copper tubing is created
from a 99% pure copper formation that
conforms to the American Society of
Testing (ASTM) B743 for seamless,
light-annealed processing.
The unit’s copper refrigeration system
is designed to be free from contaminants and conditions such as drilling
fragments, dirt, or oil. This excludes
the possibility of these contaminants
from damaging the compressor motor.
Compressor
The unit’s design includes a wide variety of compressor motors to accommodate dedicated voltages and
tonnage sizes. The 1/2 ton through
1 1/2 ton products embody a rotary
compressor design, where as unit sizes ranging from 2 ton through 4 ton include a reciprocating compressor
style, while the 5 ton unit contains a
scroll compressor. These different
styles allow Trane to provide the voltage variations along with noise reduction required in today’s applications.
See Figure 7 for reciprocating compressor.
Schrader Connections
The connections for the low and high
side of the refrigeration system are located directly beside the control box at
the front, service access panel. See
Figure 8 for schrader connection lo-
tion.
Figure 5: Hanging bracket design
Figure 6: Plastic drain pan
Figure 7: Reciprocating compressor
Figure 8: Schrader connections
6WSHP-PRC001-EN
Features and
Benefits
Figure 9: Coaxial water coil
Figure 10: Water connection device
Figure 11: Thermal expansion valve
Co-axial Water-to-Refrigerant Coil
The unit’s internal heat exchanging
water coil is engineered for maximum
heat transfer.
The copper or cupro-nickel seamless
tubing is a tube within a tube design.
The inner-water tube contains a deep
fluted curve to enhance heat transfer
and minimize fouling and scaling. It is
available in either copper or cupro-nickel (selectable option) coil.The
outer refrigerant gas tube is made
from steel material. The coil is leak
tested to assure there is no cross leakage between the water tube and the
refrigerant gas (steel tube) coil. Co-ax-
ial heat exchangers are more tolerant
to freeze rupture. See Figure 9 for
co-axial water coil.
Compressor and Co-axial Coil
Isolation
Vibration isolation of the compressor
and co-axial water coil is accomplished by increasing the rigidity and
stiffness at the base. The platform provides double isolation to the compressor and single isolation to the co-axial
water coil for additional attenuation
during compressor start and stop.
Water Connections
The water-in/water-out connections to
the co-axial water coil are located on
the right-hand chamfered corner of
the unit. The fittings are mounted flush
to the chamfered wall to help limit
shipping damage.
The water connection devices are constructed of copper or bronze material
and include a National Female Pipe
Thread (NFPT) junction. The connections are attached to the unit’s chamfer corner to alleviate the need for a
back-up wrench during installation.
See Figure 10 for water connection device.
lows the unit to operate with an entering fluid temperature from 25 F to 110
F, and entering air temperatures from
40 F to 90 F. The valve is designed to
meter refrigerant flow through the circuitry to achieve desired heating or
cooling.
The expansion valve device allows the
exact amount of refrigerant required
to meet the coil load demands. This
precise metering by the TXV increases
the efficiency of the unit. See Figure 11
for thermal expansion valve.
Reversing Valve
A system reversing valve (4-way
valve) is included with all heating/
cooling units. This valve is piped to be
energized in the cooling mode to allow
the system to provide heat if valve failure were to occur. Once the valve is
energized for cooling, it will remain
energized until the control system is
turned to the OFF position, or a heating cycle is initiated.
Units with the cooling only option will
not receive a reversing valve. See Fig-ure 12 for reversing valve.
Expansion Valve
All Trane water-source systems include an expansion valve flow metering device.
Figure 12: Reversing valve
WSHP-PRC001-EN7
This thermal expansion valve (TXV) al-
Features and
Benefits
Blower Motor
The supply-air (blower) motor is a
multi-speed motor with internal thermal overload protection. The motor
bearings are permanently lubricated
and sealed. Standard motors are rated
from .20 ESP. Optional high static motors are rated from .40 to 1.40 ESP. All
motors are factory wired to the option
selected. A high, medium, and low
speed tap is provided for field customization on most voltages. The speed
tap modification can be made in the
control box of the unit. See Figure 13
for blower motor.
Note: The 380, 415, 460 and 575 volt
designs are provided in a dual or
three-speed version only. See fan performance section for factory ratings
(Page 66).
Serviceability to the motor is made
through either of the two air-side access doors for the horizontal configuration, and through one air-side
access door on vertical configuration.
The motor and blower wheel are removable by an orifice ring mounted to
the fan housing.
Blower Housing
The blower housing is constructed of
non-corrosive galvanized steel. A factory-mounted orifice ring is provided
for ease of motor serviceability on the
1/2 through 5-ton direct drive units.
All air-side panels are interchangeable
with one another for ease of field convertibility of the supply-air on the GEH
model.
Air-Side Filter
The air-side filter incorporates a 1-inch
thick (nominal) or 2-inch thick (nominal) disposable fiberglass option.
These filters include an average synthetic dust weight arrestance of approximately 75%. This dust holding
capability includes a colorless, odorless adhesive to retain dirt particles
within the filter media after fiber contact. See Figure 14 for filter media.
Air-to-Refrigerant Coil
The air-to-refrigerant heat exchanger
is constructed of staggered copper
tubes with die-formed corrugated
lanced aluminum fins. The fins are
then mechanically bonded to the
tubes through expansion.
The coil is placed internal of the unit
design for the GEH model to provides
an optional dual filtration application.
With dual filtration to the GEH unit,
maintenance to the filter is significantly less than with a single filtration system. This design also offers maximum
flexiblity of the supply and return air
configurations.
The maximum working pressure for
both the GEH and GEV coils is 450
psig. It is designed for maximum capacity with an additional benefit of
physical unit size reduction.
Coil specifications for both GEH and
GEV models may be found on in the
General Data section on page 36 of
this catalog. See Figure 15 for internal
air to refrigerant coil placement.
lengthwise unit base stiffenerslengthwise unit base stiffeners
3/32-inch foam gasket sealant placed
around the compressor and end panel
perimeter
Sound Attenuation Package
Testing of conventional units has identified that the sound radiated by the
casing of the unit is an important component of the sound that reaches occupants, especially when the unit is
located directly over the occupied
space.
This sound reduction package reduces
radiated noise from the cabinet. Trane
double-isolates the compressor and
single-isolates the co-axial coil in the
unit. This design absorbs the vibration
that contributes to radiated sound
For sound critical spaces, an
enhanced sound package as described
in Table 1 provides additional attenuation.
Complete sound data taken in accordance with ARI 260 is available for all
units. The test data reflects
multi-speed fan motor along a single
system curve.
Dual Filtration
Flexibility of the GEH allows for dual
filtration in a free return application.
With the field installed dual filtration
accessory, filter maintenance of the
unit is significantly less.
The accessory package includes both
the bottom and top filter rack, and
one, 1-inch or 2-inch filter. Table 2
provides dual filtration accessory
numbers appropriate to unit size.
Table 2: Dual filter accessory kit
numbers
Unit Size
1-inch
Filter
006-0154474 0630 01004474 0634 0100
018-0304474 0631 01004474 0635 0100
036, 0424474 0632 01004474 0636 0100
048, 0604474 0633 01004474 0637 0100
1-i n ch
Filter Kit Part
No.
2-inch
Filter Kit Part
No.
Figure 16: Dual filtration accessory
WSHP-PRC001-EN9
Boilerless Control/Electric Heat
(option)
In cooling dominant regions where
heat may be used 15 to 30 days out of
the winter season, eliminating the
boiler may be an economical advantage to the building owner. Eliminating a boiler from the system reduces
costs associated with the mechanical
system installation, as well as the
maintenance and service of the boiler.
How can heat be provided for the few
days of the year when heat is necessary? Through the water-source heat
pump of course. The advantage of the
water-source heat pump is it’s ability
to provide heat recovery within the
closed water-loop. While some
WSHPs may be extracting heat from
the closed water loop, other WSHPs
may be adding heat to the closed
water loop. This creates a perfect system balance for heat sharing or movement from one space to another.
But when water temperatures fall in a
boilerless system, and no further heat
recovery may be made via the closed
loop, heat may be added to the space
through a boilerless control electric
heat option. See Figure 17 for the boil-
erless control, electric heat system
diagram.
With the boilerless electric heat
option, the heat pump encompasses
an internal nichrome open wire heating element (factory mounted and
wired). It is comprised of a single
stage of electric heat designed to
invoice an electric heater in place of
the compressor in the event entering
water temperature falls below 55 F or
a field adjusted temperature setting
between 25 F to 60 F.
Features and
Benefits
Figure 17: Boilerless control, electric heat system
What is NOT available with the boilerless electric heat option?
1 Hot gas reheat
2 Basic 24 volt controls
TM
3 Tracer
4 115 and 575 volt ratings
5 Supplemental or emergency heat applications
ZN510 controls
10WSHP-PRC001-EN
Boilerless Control/Electric Heat
Heating/Cooling Mode
In heating mode, when the water temperature falls below 55 F (factory setting), the electric heater
is energized, locking
out the compressor.
The systems electric
heat source will continue to be
utilized for primary
heating until
the loop
temperature rises
above 60 F.
Once the
entering water temperature rises above 60 F, the boilerless controller returns the unit to
normal compressor heating operation and locks out the electric heater.
This maximizes efficiency from the
unit during the few days requiring
heat from the mechanical system. See
Figure 18 for the factory mounted and
wired boilerless control electric heat
water-source heat pump. Available as
a single point power connection.
If the unit employs a cooling only unit
design, the electric heat contactor is
wired directly to the thermostat for
primary heating, and the compressor
contactor for cooling.
Note: For geothermal applications,
the boilerless controller has an adjustable setting of 25, 35, 45, 55 and 60
degrees.
Features and
Benefits
Figure 18: Boilerless control, electric heat water-source heat pump
WSHP-PRC001-EN11
Features and
Benefits
Figure 19: Model GEH with waterside economizer package
Note: Condensate overflow is not available with
the waterside economizer option.
Figure 20: Waterside economizer system
Waterside Economizer (option)
The beauty of the waterside economizer is it’s ability to take advantage of
any loop condition that results in cool
water temperatures. A prime example
would be during fall, winter and spring
when cooling towers have more capacity than required and could be controlled to lower temperatures for
economizer support.
Another more common inexpensive
means of free comfort cooling includes buildings systems where perimeter heating and core cooling are
needed. In this system, the perimeter
units extract heat from the building
loop while in the heating mode, forcing the building loop temperature to
drop. Where as, the core are of a building may require cooling in summer or
in winter based upon lighting, people
and equipment.
If the water-source system design contained an economizing coil option, the
moderate temperature loop water circulated through a core water-source
system can provide an inexpensive
means to satisfy room comfort without operating the water-source heat
pump’s compressor.
During economizer mode, fluid enters
the unit, and passes by a water temperature sensing bulb. This temperature sensing bulb determines whether
the two position, three-way valve will
direct the water through the waterside
economizing coil, and to the heat
pump condenser, or through the condenser only. If the water temperature
is 55 F or less, fluid will flow into the
economizing coil, while simultaneously halting mechanical operation of the
compressor. Mechanical cooling will
continue on a call for second stage
from the thermostat.
The factory built waterside economizer is available on all 1/2 to 5 ton GEH
models.The 1/2 through 5-ton GEV
may be ordered to accept a field provided waterside economizing package.
12WSHP-PRC001-EN
Features and
Benefits
Hot Gas Reheat (option)
For space conditioning and climate
control, Trane provides an accurate
and cost effective dehumidification
control through a hot gas reheat option. This option is designed to accommodate unit sizes 012, 036, 048, and
060
With this reheat option, the return air
from the space is conditioned by the
air-to-refrigerant coil, then reheated
by the reheat coil to control not only
the space temperature, but to also reduce the relative humidity of the
space. The moisture removal capability of a specific heat pump is determined by the units latent capacity
rating.
When operating in the reheat mode
(meaning the sensible temperature
has been met in the space), the humidistat signals the reheat relay coil to
energize, allowing the high pressure
refrigerant gas to flow from the (1)
compressor, through the (2) reheat
valve, into the (3) reversing valve, or
through the (4) reheat coil for dehumidification. A switching relay has
been provided for the reheat application to adjust the blower motor from
normal operation to low speed when
hot gas reheat is energized.
Note: Trane places an air separation
space between the air-to-refrigerant
coil, and the reheat coil to allow for
maximum moisture removal.
Common Reheat Applications
The hot gas reheat option is designed
to support building applications requiring fresh-air ventilation units delivering unconditioned-air directly to
the space. It also provides dehumidifi-
cation to large latent load spaces such
as auditoriums, theaters and classrooms, or anywhere humidity control
is a problem.
Do’s and Don’ts in Design
The factory installed hot gas reheat
option is only available with Deluxe or
ZN524 controls packages.
A high static blower motor option will
be required to support the hot gas reheat option for the 1/2 through 5 ton
equipment.
Water regulating valves should not be
used with the hot gas reheat option.
Trane places a thermal expansion
valve on all water-source heat pumps,
as well as ground-source heat pumps,
to regulate refrigerant flow vs. water
flow, making the heat pump more efficient to run.
Water-source heat pumps with hot gas
reheat should not be used as a
make-up air unit.
Figure 21: Hot gas reheat heat pump
WSHP-PRC001-EN13
Features and Benefits
Controls
Controls by Trane
Whether involved in a retrofit or new construction application, Trane has the control design to fit your system requirement.
Our control options provide a broad range of packages from the most cost efficient 24 volt standalone to a complete building automation solution, Trane is the right choice in comfort gratification. The following chart provides a brief overview in
the different control combinations.
GraphicDescriptionApplicationICSProtocolWhere to find
Basic 24V
Deluxe 24V
Tracer ZN510
Tracer ZN524
Used in
single circuited
WSHPs with HGR,
WSE, or BEH.
TM
TM
TracerTM Loop
Controller
Tracer Summit®
Compressor lockout relay, low and
high pressure
switches.
24 volt microprocessor designed to
provide control of
the entire unit, as
well as multiple
relay offerings to
maximize system
performance. Can
connect to a 24V
thermostat.
Direct Digital Control board designed
to provide control
of the entire unit as
well as outputs for
unit status and fault
detection.
Direct Digital Control board designed
to provide control
of the entire unit as
well as outputs for
unit status and fault
detection.
Microprocessor-based controller that coordinates
the water side
(boiler, pumps,
cooling tower, etc.)
of a water-source
heat pump system.
Microprocessor
based controller
that coordinates full
building automation from HVAC to
lighting.
Retrofit market where single and multiple unit
replacement occurs.
New building design where
field provided controls are
specified.
Retrofit market where single and multiple unit
replacement occurs.
Multi-unit installation
where units may be daisychained directly to the
Trane Tracer
troller.
Retrofit market where overall system upgrade is specified.
Multi-unit (100+) installation where units are linked
by a common twisted pair
of wire for a communication link.
Retrofit market where overall system upgrade is specified.
Multi-unit (100+) installation where units are linked
by a common twisted pair
of wire for a communication link.
Wherever the Tracer ZN510
controls or 24 volt electro-mechanical
controls are specified for
complete control of the
water loop and pumps.
Where any controller is
specified.
TM
Loop Con-
NoNon ApplicablePage 15
NoNon ApplicablePage 16
Yes
YesSCC LonTalk
YesLonTalk
YesBA Cn et
SCC LonTalk
open protocol
(Comm5)
open protocol
(Comm5)
compatible
(Comm5)
(Comm 2,3,4,5)
®
Page 18
Page 18
WSHP-MG-3
EMTW-SVN01B-EN
EMTW-SVP01B-EN
EMTW-SVU01B-EN
HGR = Hot Gas Reheat
WSE = Waterside Economizer
BEH = Boilerless Electric Heat
14WSHP-PRC001-EN
Features and Benefits
Basic Controls
Figure 22: Basic 24 volt control box
Figure 23: Safety devices
Figure 24: 24 volt stand-alone system
Basic 24 Volt Controls
The basic 24 V electromechanical unit control provides component protection devices for maximum system reliability. Each device is
factory mounted, wired and tested.
See Figure 22 for the unit control box.
Safety Devices
System safety devices are provided
through the use of low/high pressure
switches in the refrigeration circuit to
help prevent compressor damage.
The switch and sensor are set to activate at refrigerant pressures of 20 psig
to fit most applications.
In cases where a low charge, or excessive loss of charge occurs, each compressor comes equipped with an
external overload device to halt the
compressor operation.
The high pressure switch prevents
compressor operation during high or
excessive discharge pressures that exceed 395 psig.
A lockout relay provides the mechanical communication of the low and high
pressure switches to prevent compressor operation if the unit is under
low or high refrigerant circuit pressure, or during a condensate overflow
condition. The lockout relay may be reset at the thermostat, or by cycling
power to the unit.
General alarm is accomplished
through the lockout relay and is used
in driving light emitting diodes. This
feature will drive dry contacts only,
and cannot be used to drive field installed control inputs.
See Figure 23 for unit safety devices
on the basic 24V control unit.
Stand-alone System
The 24 volt electro-mechanical design
may be applied as a stand-alone
control system. The stand-alone
design provides accurate temperature
control directly through a
wall-mounted mercury bulb or
electronic thermostat. This system
set-up may be utilized in a
replacement design where a single
unit retrofit is needed. It may be easily
interfaced with a field provided control
system by way of the factory installed
18-pole terminal strip.
This stand-alone control is frequently
utilized on small jobs where a building
controller may not be necessary, or
where field installed direct digital
controls are specified. This type of
control design does require a constant
flow of water to the water source heat
pump. With a positive way to sense
flow to the unit, the units safety
devices will trigger the unit off.
The stand-alone system design
provides a low cost option of
installation while still allowing room
control for each unit. See Figure 24 for
24 volt stand-alone system controls.
WSHP-PRC001-EN15
Features and Benefits
Deluxe Controls
Deluxe 24V Electronic Controls
The deluxe 24V electronic unit control
provides component protection
devices similar to the basic design, but
contains upgraded features to
maximize system performance to
extend the system life. Each device, is
factory mounted, wired, and tested in
the unit. See Figure 25 for unit control
box.
Small Building Control
The deluxe 24V electro-mechanical
design may be applied as a
stand-alone control system or as a
multi-unit installation system. With a
stand-alone design, units run
independently of one another with a
mercury bulb or electronic digital
thermostat.
With a multiple unit installation, the
units may be daisy-chained directly to
the Trane Tracer loop controller (TLC),
pump(s), boiler, and tower for a
complete networked water-source
system. The TLC provides a night
setback output, and a pump request
input for system optimization.See
Figure 26 for 24 volt deluxe control
system.
Figure 25: Deluxe 24 volt control box
Figure 26: 24 volt deluxe control system
16WSHP-PRC001-EN
Features and Benefits
Deluxe Controls
Microprocessor Design
The 24 volt deluxe design is a
microprocessor-based control board
conveniently located in the control
box. The board is unique to Trane
water-source products and is
designed to control the unit as well as
provide outputs for unit status and
fault detection.
The Trane microprocessor board is
factory wired to a terminal strip to
provide all necessary terminals for
field connections. See Figure 27 for
the deluxe 24V control board.
Figure 27: Deluxe 24V control board
Deluxe 24V features include:
Random Start
The random start relay provides a time
delay start-up of the compressor when
cycling in the occupied mode. A new
start delay time between 3 and 10
seconds is applied each time power is
enabled to the unit.
Anti-short Cycle Timer
The anti-short cycle timer provides a
three minute time delay between
compressor stop and compressor
restart.
Brown-out Protection
The brown-out protection function
measures the input voltage to the
controller and halts the compressor
operation. Once a brown-out situation
has occurred, the anti-short cycle
timer will become energized. The
general fault contact will not be
affected by this condition. The voltage
will continue to be monitored until the
voltage increases. The compressors
will be enabled at this time if all
start-up time delays have expired, and
all safeties have been satisfied.
Compressor Disable
The compressor disable relay provides a temporary disable in compressor operation. The signal would be
provided from a water loop controller
in the system. It would disable the
compressor because of low water
flow, peak limiting or if the unit goes
into an unoccupied state. Once the
compressor has been disabled, the anti-short cycle time period will begin.
Once the compressor disable signal is
no longer present, and all safeties are
satisfied, the control will allow the
compressor to restart.
Generic Relay
The generic relay is provided for field
use. Night setback or pump restart are
two options that may be wired to the
available relay. (Note: Night setback is available as factory wired). An external Class II 24VAC signal will energize
the relay coil on terminals R1 and R2.
Terminals C (common), NO (normally
open), and NC (normally closed) will
be provided for the relay contacts.
Safety Control
The deluxe microprocessor receives
separate input signals from the refrigerant high pressure switch, low suction pressure switch and condensate
overflow.
In a high pressure situation, the compressor contactor is de-energized,
which suspends compressor operation. The control will go into soft lock-out mode initializing a three minute
time delay and a random start of 3 to
10 second time delays. Once these delays have expired, the unit will be allowed to run. If a high pressure
situation occurs within one hour of the
first situation, the control will be
placed into a manual lockout mode,
halting compressor operation, and initiating the general alarm.
In a low temperature situation, the low
pressure switch will transition open
after the compressor starts. If the
switch is open for 45 seconds during
compressor start, the unit will go into
soft lockout mode initializing a three
minute time delay and a random start
of 3 to 10 second time delays. Once
these delays have expired, the unit will
be allowed to run. If the low pressure
situation occurs again within 30 minutes, and the device is open for more
than 45 seconds, the control will be
placed into a manual lockout mode,
halting compressor operation, and initiating the general alarm.
In a condensate overflow
situation, the control will go into man-ual lockout mode, halting compressor
operation, and initiating the general
alarm.
The general alarm is initiated when the
control goes into a manual lockout
mode for either high pressure, low
pressure or condensate overflow conditions.
Diagnostics
Component device connections to the
microprocessor board are referenced
in Figure 27. Three LEDs (light emitting
diodes) are provided for indicating the
operating mode of the controller. See
the unit IOM for diagnostics or troubleshooting through the use of the LEDs.
WSHP-PRC001-EN17
Features and Benefits
ZN510 & ZN524 Controls
Tracer ZN510 & ZN524 Controls
The Tracer ZN510 and ZN524 are direct digital control (DDC) systems specifically designed for single and dual
circuited water-source equipment to
provide control of the entire unit, as
well as outputs for unit status and fault
detection. Each device is factory installed,
commissioned,
and tested to ensure the highest
level of quality in
unit design.
Each of the controller’s features
and options were
selected to coordinate with the unit
hardware to provide greater energy efficiency and
equipment safety
to prolong the
equipment life.
In addition to being factory configured for control of
the unit fan, compressor and reversing
valve, the ZN510 and ZN524 controllers are designed to coordinate the waterside of the water-source system
through the Tracer Loop Controller
(TLC). If applied in a peer-to-peer communication environment, data between similar controllers may be
exchanged without requiring a building automation system.
By teaming the ZN510 and ZN524 with
the TLC, a low first-cost for the mechanical equipment, water loop, and
water pump optimization is provided
to the owner.
For owners who require a full building
integrated "open protocol" system,
The ZN510/ZN524/TLC application is
upgradable to support complete building control through Tracer Summit.
Because the ZN510 and ZN524 is LonTalk certified, it is capable of working
with, and talking to other LonTalk cer-
tified controllers providing the building owner more choices, and the
design engineers more flexibility to
meet the challenges of building automation. See Figure 28 for ZN510 control box.
Figure 28: ZN510 control box
18WSHP-PRC001-EN
Features and Benefits
ZN510 & ZN524 Controls
Direct Digital Controls
When the ZN510 or ZN524 controller is
linked directly to the Tracer Summit,
each Tracer Summit building
automation system can connect a
maximum of 120 Tracer ZN510 or
ZN524 controllers. See Figure 29 for
the Tracer ZN524 board.
Figure 29: Tracer ZN524 controller
Tracer ZN510 and ZN524
functions include:
Compressor Operation
The compressor is cycled on and off to
meet heating or cooling zone demands. Single and dual compressor
units use the unit capacity and pulse
width modulation (PWM) logic along
with minimum on/off timers to determine the compressor’s operation. The
compressor is controlled ON for longer periods as capacity increases and
shorter periods as capacity decreases.
Random Start
To prevent all of the units in a building
from energizing major loads at the
same time, the controller observes a
random start from 0 to 25 seconds.
This timer halts the controller until the
random start time expires.
Reversing Valve Operation
For cooling, the reversing valve output
is energized simultaneously with the
compressor. It will remain energized
until the controller turns on the
compressor for heating. At this time,
the reversing valve moves to a
de-energized state. In the event of a
power failure or controller OFF
situation, the reversing valve output
will default to the heating
(de-energized) state.
Fan Operation
The supply air fan operates at the factory wired speed in the occupied or occupied standby mode. When switch is
set to AUTO, the fan is configured for
cycling ON with heating or cooling. In
heat mode, the fan will run for 30 seconds beyond compressor shutdown in
both occupied and unoccupied mode.
Fan Run Timer
The controller’s filter status is based
on the unit fan’s cumulative run hours.
The controller compares the fan run
time against an adjustable fan run
hours limit and recommends unit
maintenance as required.
Data Sharing
The Tracer ZN510/ZN524 controller is
capable of sending or receiving data
(setpoints, fan request, or space temperature) to and from other controllers
on the communication link. This allows multiple units to share a common
space temperature sensor in both
stand-alone and building automation
applications.
Night Setback
The four operations of the Tracer
ZN510/ZN524 controller include occupied, occupied standby, occupied bypass and unoccupied.
In an occupied situation, the controller uses occupied heating and cooling setpoints to provide heating and
cooling to the building. This occupied
operation is normally used during the
daytime hours when the building is at
the highest occupancy level.
In an occupied standbysituation,
the controllers heating and cooling
setpoints are usually wider than the
occupied setpoints. This occupied
standby operation is used during daytime hours when people are not
present in the space (such as lunchtime or recess). To determine the
space occupancy, an occupancy sensor is applied.
In an unoccupied situation, the controller assumes the building is vacant,
which normally falls in evening hours
when a space may be empty. In the unoccupied mode, the controller uses
the default unoccupied heating and
cooling setpoints stored in the controller. When the building is in unoccupied
mode, individual units may be manually placed into timed override of the
unoccupied mode at the units wall
sensor. During timed override, the
controller interprets the request and
initiates the occupied setpoint operation, then reports the effective occupancy mode as occupied bypass.
In the occupied bypass mode, the controller applies the occupied heating
and cooling setpoint for a 120 minute
time limit.
High and Low Pressure
Safety Controls
The Tracer ZN510/ZN524 controller
detects the state of the high pressure
or low pressure switches. When a fault
is sensed by one of these switches, the
corresponding message is sent to the
controller to be logged into the fault
log. When the circuit returns to normal, the high pressure control and low
pressure control automatically reset. If
a second fault is detected within a thirty-minute time span, the unit must be
manually reset.
Condensate Overflow
When condensate reaches the trip
point, a condensate overflow signal
generates a diagnostic which disables
the fan, unit water valves (if present),
and compressor. The unit will remain
in a halted state until the condensation
returns to a normal level. At this time,
the switch in the drain pan will automatically reset. However, the controller’s condensate overflow diagnostic
must be manually reset to clear the diagnostic and restart the unit.
WSHP-PRC001-EN19
Features and Benefits
ZN510 & ZN524 Controls
Additional Functions of the
ZN524 Controller
When the building owners choice is
Trane Tracer controls, the ZN524 controller is required when any of the following applications are selected on a
single and dual circuited equipment.
• Waterside Economizer
• Hot Gas Reheat
(for Dehumidification)
• Boilerless Control for Electric Heat
• Water Isolation Valve Control
(for Variable Speed Pumping)
Entering Water Temperature
Sampling
The ZN524 controller will sample the
entering water temperature to determine proper control action for units
equipped with boilerless electric heat
or waterside economizer.
Waterside Economizer: Entering
water temperature (EWT) sampling
will automatically occur at power up
when the unit is equipped with a waterside economizer (WSE). The EWT is
used to determine if economizing is
feasible. When the conditions are met,
the isolation valve(s) are driven open
for three minutes and the EWT reading
is taken. The determination as to
whether or not the economizer can be
enabled will be made and the controller will take appropriate action. The
isolation valve will remain open regardless if the WSE or the DX cooling
is enabled.
The unit’s waterside economizer will
contain a 2-position water valve wired
to the ZN524. The economizing water
coil will be optimized to provide 100%
of the unit capacity at 80.6 F/66.2 F return air temperature with 45 F entering
water. The flow rate is established at
86 F entering water temperature and
96 F leaving water temperature.
Low leaving air protection will be furnished to protect the unit against delivering air that is cold enough to
sweat discharge air grilles. Coil icing
protection will also be provided.
Waterside economizer cooling will be
active during occupied, unoccupied
and standby cooling modes.
Boilerless Control Electric Heat
and Supplemental Electric Heat:
The ZN524 supports a single stage of
boilerless electric heat operation or
concurrent heating.
When the unit is configured for boilerless control, the EWT will be used to
determine whether DX heating should
be disabled and the electric heater enabled. When these conditions are met,
the isolation valve(s) are driven open
for three minutes and the entering water temperature reading is taken. The
determination as to whether or not to
utilize electric heat will be made and
the controller will take appropriate action. If boilerless electric heat is enabled, then the isolation valve will be
closed, shutting down the water flow
to the unit.
When the unit is configured for concurrent operation of DX heating (compressor in heat pump mode) and
electric heat, the electric heat will act
as a second stage of heat for single
compressor units, and a third stage of
heat for dual compressor units. Note:
With concurrent (or supplemental)
electric heat, the electric heater is field
provided.
Water Isolation Valves
Variable speed pumping systems are
supported by the ZN524 controller
when water isolation valves are
present. Up to two isolation valves are
supported by the controller (one for
each compressor circuit).
The valves are normally closed unless
DX heating, DX cooling, waterside
economizer or dehumidification is requested. When the isolation valves are
driven open for operation, the outputs
will be driven for 20 seconds to ensure
adequate water flow before the compressor outputs are energized. Once
an isolation valve has been opened, it
will remain open for a 10 minute minimum to reduce excessive cycling of
the valve.
Dehumidification
Dehumidification for the single and
dual circuited water-source heat pump
is applicable with the ZN524 controller. The controller is capable of directing one stage of DX cooling in
conjunction with one stage of reheat
(hot gas reheat).
Dehumidification can only occur when
the controller is in the cooling mode. A
humidity transmitter is used to measure the zone’s relative humidity (RH),
then compares the zone relative humidity to the relative humidity enable/
disable setpoint parameters. The default values for dehumidification enable is 60% RH with the disable point
at 52% RH. These values are configurable.
20WSHP-PRC001-EN
Features and Benefits
ZN510 & ZN524 Controls
Building Control Advantages
The Tracer ZN510/ZN524 controller has the ability to share information with one
or several units on the same communication link. This sharing of information is
made possibe via a twisted pair of wire and a building automation system or
through Trane’s Rover
An advantage of installing a ZN510/ZN524 is its capability to work with other LonTalk certified controllers. This provides greater flexibility to the building owner,
as well as greater flexibility in design.
Integrating the ZN510/ZN524 on water-source equipment, and tying it to a Tracer
Summit system provides a complete building management system. Each Tracer
Summit can connect to a maximum of 120 controllers. With the ICS system, the
Tracer can initiate an alarm on a loss of performance on equipment malfunctions;
allowing problems to be handled in a timely manner before compromising comfort.
This type of application would most commonly be used for a large space(s) that
TM
service tool .
may require more than one unit. In addition to
this application design, the Tracer
ZN510/ZN524 controller provides
a way for units located within the
same space to share the same
zone sensor to prevent units from
simultaneously heating and
cooling in the same space.See
Figure 30 for Tracer ZN510/ZN524
controller system.
Figure 30: Tracer ZN510/ZN524 controller system
WSHP-PRC001-EN21
Application
Considerations
Flexibility
The high efficiency vertical and horizontal water-source heat pump system is versatile for installation in
boiler/cooling tower applications, as
well as ground-source (geothermal)
applications. The system design may
employ either a central pumping design, or a distributed pumping design.
A central pumping design involves a
single pump design, usually located
within a basement or mechanical
room to fulfill pumping requirements
for the entire building system. An auxiliary pump is typically applied to lessen the likelihood of system downtime
if the main pump malfunctions.
A distributed pumping system contains a single pump module connected
directly to the units supply and return.
This module is field installed and
piped to the unit. This design requires
individual pump modules specifically
sized for each water-source heat
pump.
Advantages of Geothermal
The advantages of a geothermal heat
pump system could literally cut a business’ heating and cooling costs by 30
to 40-percent. The units are durable,
and typically last longer than conventional systems because they are protected from harsh outdoor weather
conditions, and because the unit is installed indoors and the loop underground. (According to ASHRAE, the
estimated service life for a commercial
water-to-air heat pump is 19-years.)
Geothermal heat pumps have fewer
mechanical components, making
them more reliable and less prone to
failure. Manufacturers of the loop materials guarantee their products for up
to 25-years, with no maintenance required.
Geothermal heat pumps work toward
the preservation of the
environment by reducing the environmental impacts of electric power generation.
A ground source (geothermal)
system consist of a:
• A ground water heat pump
• A closed loop ground heat exchanger made of high density
polyethylene pipe (guaranteed
25- years or more by many manufacturers); and
• A low wattage circulating pump(s)
The fluctuating temperatures of fluid
from the earth are more stable than
air, allowing the equipment to operate
at a lower discharge pressure and use
fewer kilowatts. The constant earth
temperature will heat or cool the fluid
running through buried high density
polyethylene pipe to provide heating
and cooling to a building.
Figure 31: Geothermal energy recovery loop
A geothermal loop can be installed either horizontally or vertically. Vertical
loops require less overall land area to
reject (i.e., sink) the excess heat from
the building. Horizontal loops require
trenches in the ground spanning a
larger overall land area.
Although external piping is the responsibility of the installer and/or piping manufacturer, many electric
utilities and rural electric cooperatives
are offering monetary incentives to install geothermal systems. Utility companies offer the incentives because of
reduced peak loads that flatten out
their demand curve over time, and
save them money. These savings are
ultimately transferred to the consumer. See Figure 31 for geothermal energy recovery loop.
22WSHP-PRC001-EN
Application
Considerations
Central Pumping System
Units that employ a central pumping
system contain single or dual pumps
to fulfill pumping requirements for the
entire building system.
The central system’s supply and return lines should be sized to handle
the required flow with a minimum
pressure drop.
The water-source heat pump (in this
case a high efficiency GEH) may include add-on accessories to help aid in
system balancing, acoustics and safety requirements. Some of these items
may be ordered from the factory, then
field installed. Many are provided by
the contractor.
1
Hose kits are used to connect the
water supply and return line to the
water inlets and outlets. Trane offers various hose kit combinations
to better facilitate system flow
balancing. These flexible
hoses also aid in the reduction of vibration between the
unit and the rigid central piping system.
A two position isolation valve is
often applied to systems which incorporate variable frequency
pumping. This valve is capable of
stopping/starting water flow to the
unit, which in-turn reduces the
pumping requirements for
the entire system.
The central system supply and re-
5
turn lines should be sized to handle the required flow with a
minimum pressure drop.
Note: Pipe will sweat if low temperature water is below the dew
point of the surrounding space.
Trane recommends that these
lines be insulated to prevent damage from condensation when condenser loop is designed to be
below 60 F. Equipment installed in
attic/crawl space temperatures be-
low 40°F may require antifreeze in
the water loop.
For acoustically sensitive areas, a
6
six-inch deep fiberglass insulation
is recommended to be field installed below the horizontal unit.
This field supplied insulation
should be approximately twice the
footprint size of the unit. It provides sound damping of the unit
while in operation.
2
The unit’s (item 2) 3/4-inch
high voltage and (item 3) 1/2-inch
3
low voltage connections are located on the left chamfered corner
of the unit. They are designed to accept conduit.
A field supplied line voltage dis-
4
connect should be installed for
branch circuit protection. Check
local codes for requirements.
WSHP-PRC001-EN23
Application
Considerations
Distributed Pumping System
A distributed pumping system contains either a single or dual pump
module, specifically sized for each water-source heat pump, then connected
directly to the units supply and return
lines.
The distributed system’s supply and
return lines should be sized to handle
the required flow with a minimum
pressure drop.
Hose kits are used to connect the
1
water supply and return line to the
water inlets and outlets. Trane offers various hose kit combinations
to better facilitate system flow balancing. These flexible hoses also
aid in the reduction of vibration between the unit and the rigid central
piping system.
2
The unit’s (item 2) 3/4-inch high
voltage and (item 3) 1/2-inch low
3
voltage connections are located
on the left chamfered corner of
the unit. They are designed to accept conduit.
67
The distributed pumping system
supply and return lines should be
sized to handle the required flow
with a minimum pressure drop.
Note: Pipe will sweat if low tem-
perature water is below the dew
point of the surrounding space.
Trane recommends that these
lines be insulated to prevent dam-
age from condensation when con-
denser loop is designed to be
below 60 F. Equipment installed in
attic/crawl space temperatures be-
low 40°F may require antifreeze in
the water loop.
For acoustically sensitive areas, a
six-inch deep fiberglass insulation
is recommended to be field installed below the horizontal unit.
This field supplied insulation
should be approximately twice the
footprint size of the unit. It provides sound damping of the unit
while in operation.
A field supplied line voltage dis-
4
connect should be installed for
branch circuit protection. Check local codes for requirements.
Trane’s self-contained pump mod-
5
ule and hose kit make a complete pumping package for
distributed pumping systems.
The module is designed for circulating commercial loops that require a maximum flow rate of 20
gpm. Each pump module is fully assembled for connection to water and electrical
points. The kit contains all
of the necessary components for the installation, operation
and maintenance of a closed loop
application. See WSHPC-IN-5
(72-9006-03) for electrical and dimensional requirements
24WSHP-PRC001-EN
Application
Considerations
Installation of the 1/2 through
5-Ton Vertical
Whether securing the 1/2 through
5-ton GEV to a central pumping system, or a distributed pumping system,
Trane recommends a few accessory
considerations to the system installation.
The field supplied line
1
voltage disconnect should
be installed for branch circuit protection.
2
The units (2)3/4-inch high
3
voltage and (3) 1/2-inch
low voltage connections
are located on the left
chamfered corner of the
unit. They are designed to
accept conduit.
Trane recommends that
4
the condensate system be
set-up per negative pressure trapping in consideration of the unit’s
draw-through design.
With this properly trapped
system, when condensate
forms during normal operation, the water level in
the trap rises until there
is a constant outflow.
5
For acoustically sensitive areas, a
1/2-inch thick field provided vibration pad should be installed below
the vertical unit. This field provided piece should be equal to the
overall foot-print size of the unit to
provide sound damping of the
unit while in operation.
6
Hose kits are used to connect the
water supply and return lines to
the water inlet and outlets. Trane
includes various hose kit combinations to better facilitate system
flow balancing. These flexible
hoses, reduce vibration between
the unit and the rigid piping system.
WSHP-PRC001-EN25
Application
Considerations
Installation Made Easy
Installing a horizontal unit inside a corridor to enhance sound attenuation provides value to duct design. Trane takes this
fact one step further.
The new GEH design offers same side return-air/supply-air access to the unit. This access is contained within the overall
dimension of the units length as shown in Figure 32. The duct access to the unit allows the unit to be installed closely
against a corridor wall, while at the same time eliminating space required for the duct design.
Most horizontal unit designs provide an opposite supply air from the return air arrangement, or an end supply arrangement
option. See Figure 33 for end-supply example. An end-supply design increases the overall unit length of the system to accommodate a 90-degree duct turn. This not only requires added space, but also adds cost in both materials and installation.
Additional value to the design is acquired through the same side supply/return-air design. This design eliminates a requirement for a four sided service access. When installing the same side return/supply-air access, a brief 3-inch minimum is all
that is required between the unit and the wall.
Figure 32: Same-side supply/return-airFigure 33: End supply arrangement/ductwork
26WSHP-PRC001-EN
Duct Design for Noise Control
Proper acoustics are often a design
requirement. Most of the problems
that are associated with HVAC
generated sound can be
avoided by properly selecting
and locating the components
of the system. Acoustical
modeling should be used
to find the lowest cost
design to meet a
specific sound
requirement, however,
there are some general do’s
and don’ts that should be
observed.
Figure 34 shows a supply air duct that
is placed too close to the blower to
provide substantial noise attenuation.
It also, represents the effects on sound
that a short supply branch connected
to the discharge may produce. Avoid
these forms of connections when
designing ductwork where noise
attenuation is critical.
The following suggestions will reduce
the amount of sound that reaches the
ocupied space:
Application
Considerations
Figure 34: Improper supply-air ducting
•Design the duct run
with two 90-degree
turns
•Line the first 5 feet of
the supply trunk
•Line elbows and transition pieces, as well
as a short distance
upstream and downstream of the
fittings
•Use flexible connections to isolate vibrations
•Provide multiple discharges
•Keep duct velocity low
See Figure 35 for a positive representation of supply duct work design for
noise attenuation on units over 1 1/2
tons.
WSHP-PRC001-EN27
Figure 35: Desired supply-air ducting
Figure 36: Improper return-air ducting
Application
Considerations
Sound control applies to the return
side of the duct design as well as the
supply side. Figure 36, demonstrates
a poor installation. Note that the
return air opening is close to the
cabinet of the unit.
Figure 37 graphic represents proper
installation of return-air duct. This
includes
•Two 90-degree bends prior to the
intake
•Lining the first 10 feet of the
return air duct
•Locating the return-air intake
away from the unit blower
A duct system with noise control
in-mind can be designed by:
•Keeping air flow velocities low
•Using aerodynamic fittings
•Using a duct liner if metal duct is
applied
Figure 37: Proper return-air ducting
•Avoiding line-of-sight connections between a noise source and
an outlet
•Avoiding line-of-sight connection
between a noise source and an
inlet
•By properly locating balancing
dampers
•Sealing cracks, seams and joints
in the duct run and equipment
panels
•Blocking transmission through
walls, ceiling and floors
•Mounting and supporting the
ductwork with isolation devices
that absorb vibration
•Using flexible duct connections
•Using flexible braided hoses on
the water connections
28WSHP-PRC001-EN
Application
Considerations
Using Water Regulating Valves
The function of the water regulating
valve assembly is to minimize the
amount of water which flows through
the water-source heat pump. These
valves are most often used in systems
where the water is wasted, but may
also be used in boiler/cooling tower involving variable speed pumping. In a
variable speed application, the valves
are used to meter desirable water flow
through the unit when the unit is running, and to stop water flow when the
unit is not running (but may not in-clude a 100% shut-off).
The water regulating valve assembly
consists of two valves piped in parallel. When the water-source heat
pump’s compressor is de-energized,
both valves are closed, allowing no
water to flow through the unit. But,
when the unit compressor is energized, one of the valves is closed and
the other valve will allow water flow
through the unit.
In cooling mode, the valve controlling
the water flow is referred to as a direct
acting valve. As the spring tension increases, the head pressure will also increase. This is due to the decrease in
water flow through the unit. Note, the
valve is being controlled by the head
pressure. As the head pressure increases, the water flow increases, and
vice versa. The valve is controlled by
two pressures. The refrigerant pressure in the high side of the system,
and the spring pressure, acting on the
opposite side of the valve.
Note: The spring tension on the direct
acting valve may be adjusted to maintain a desired head pressure.
When the unit is OFF, or is in the heating mode, the valve closes. This is because the pressure acting on the valve
is out of the spring set-range.
In the heating mode, the valve controlling the water flow is referred to a a reverse acting valve. As the spring
tension increases, the suction pressure will increase. This is due to the increase in water flow through the unit.
Note, the valve is being controlled by
the suction pressure. As the suction
pressure decreases, the water flow increases, and vice versa. The valve is
controlled by two pressures. The refrigerant pressure in the low side of
the system, and the spring pressure,
acting on the opposite side of the
valve.
Note: The spring tension on the reverse acting valve may be adjusted to
maintain a desired suction pressure.
When the unit is OFF, or is in the cooling mode, the valve closes. This is because the pressure acting on the valve
is out of the spring set-range.
Both the direct acting and the reverse
acting valves should be tapped into
the same refrigerant line via a schraeder connection. This line must be a high
pressure line when the unit is in the
cooling mode, and a low pressure line
when the unit is in the heating mode.
The only line that will accommodate
this condition is the vapor line running
between the reversing valve and the
water-to-refrigerant heat exchanger.
Note: In many applications, a water
regulating valve may be used to meter
water flow to the equipment instead of
metering refrigerant flow to the equipment. This is typically applied when
the equipment does not contain a thermal expansion refrigerant metering
device. Trane places a thermal expansion valve on all water-source and
ground-source heat pumps to provide
maximum performance of the equipment. Capillary tube assemblies are
not used on Trane water-source or
ground-source heat pump equipment.
Therefore, a water regulating valve is
not required on most equipment applications.
WSHP-PRC001-EN29
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.