Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
November 2013
WSHP-SVX10B-EN
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note thatwarnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potentialhazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughlybefore operating or servicing
this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situationthat could resultin
equipment or property-damage only
Contains Refrigerant!
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of nonapproved refrigerants, refrigerant substitutes, or
refrigerant additives could result in death or serious
injury or equipment damage.
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
WARNING
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all Personal ProtectiveEquipment (PPE)
recommended for the work being undertaken.
ALWAYSrefer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to follow recommendations could result in death
or serious injury.
WARNING
Page 3
Revision Summary
WSHP-SVX10B-EN (15 November 2013)
•WPRD Chassis Model Number change
WSHP-SVX10B-EN (18 June 2013)
•Add ECM motor
Trademarks
Trane and theTrane logo are trademarks or registered
trademarks ofTrane in the United States and other
countries.Trane is a business of Ingersoll Rand. All
trademarks referenced in this document are the
trademarks of their respective owners.
PSC motor
5 = ECM motor w/o flange
6 = ECM motor w/1" flange
7 = ECM motor w/3" flange
8 = Chassis only/No motor (ECM Control)
9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
A = 20° freezestat
B = 35° freezestat
Digit 14: Open Digit
0 = Open
S = Special
Digit 15: Supply Air
Arrangement
0 = No Supply Air Arrangement
1 = Back and Front Supply Air
2 = Back and Left Supply Air
3 = Back and Right Supply Air
4 = Front and Left Supply Air
5 = Front and Right Supply Air
6 = Left and Right Supply Air
7 = Back, Front and Right Supply Air
8 = Back, Front and Left Supply Air
9 = Front, Right and Left Supply Air
B = Back Supply Air
L = Left Supply Air
R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air
Arrangement
0 = No Return Air Door (Field Provided)
1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry
2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
D = Deluxe 24V Controls
C =Tracer™ ZN510 Controls
Digit 18: Thermostat Sensor
Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0 = No Fault Sensors
1 = Condensate Overflow Sensor
2 = Filter MaintenanceTimer
3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted
Disconnect
0 = No Unit Mounted Switch
C =Toggle Switch Only
D =Toggle Switch with Fuses
PSC motor
5 = ECM motor w/o flange
6 = ECM motor w/1" flange
7 = ECM motor w/3" flange
8 = Chassis only/No motor (ECM Control)
9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
0 = None or Standard
A = 20° Freezestat
B = 35° Freezestat
Digit 14: Open Digit
0 = Open
Digit 15: Supply Air
Arrangement
0 = No Supply Air Arrangement
1 = Back and Front Supply Air
2 = Back and Left Supply Air
3 = Back and Right Supply Air
4 = Front and Left Supply Air
5 = Front and Right Supply Air
6 = Left and Right Supply Air
7 = Back, Front and Right Supply Air
8 = Back, Front and Left Supply Air
9 = Front, Right and Left Supply Air
B = Back Supply Air
L = Left Supply Air
R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air
Arrangement
0 = No Door (Chassis Only)
1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry
2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
0 = Basic Controls for WPRD Retrofit
Chassis
D = Deluxe 24V Controls
C =Tracer™ ZN510 Controls
Digit 18: Thermostat Sensor
Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0= No Fault Sensors
1 = Condensate Overflow Sensor
2 = Filter Maintenance Timer
3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted
Disconnect
0 = No Unit Mounted Switch
C = Switch Only
D = Switch with Fuses
B = Back Riser Location
L = Left Hand Riser Location
R = Right Hand Riser Location
Digit 30: Riser Type
0 = No Riser (Chassis Only)
Digit 31: Supply Riser
0 = No Riser (Chassis Only)
Digit 32: Return Riser
0 = No Riser (Chassis Only)
Digit 33: Condensate Riser
0 = No Riser (Chassis Only)
Digit 34, 35, 36: Riser Length
000 = No Riser (Chassis Only)
6WSHP-SVX10B-EN
Page 7
General Information
Blower/Motor
The blower and motor is located inside the unit cabinet.
The blower and motor may be removed from the cabinet
through the chassis opening. After removing the chassis,
the blower assembly is strapped into the unit cabinet
through a single metal, flexible bracket. We refer to this
bracket as a housing belly bracket. After detaching one
screw at the bottom/front edge of the bracket, the housing
and motor are free to be lifted from the fan deck.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Controls
A 75 VA transformer is factory supplied on this unit
configuration. See wiring diagram on chassis access panel
for field wiring connection to the 24V mechanical
thermostat.
Deluxe 24V Controls
Units containing the Deluxe 24V control design will
incorporate a microprocessor-based control board.The
Trane microprocessor board is factory wired to a terminal
strip to provide all necessary terminals for field
connection.The deluxe board is equipped with a random
start relay, anti-short cycle timer, brown out protection,
compressor disable, unit safety control, diagnostics and a
generic relay (which may be available for field use). See
p. 14 for diagnostic information.
Power wiring is made at the contactor.The wiring is fed
through the left or right conduittube, and intothe cabinet’s
control box (contactor).
Schrader Connections
Connections for the low and high side of the refrigeration
system are located conveniently on the chassis’ front
beneath a sheet metal plate.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and run tested for proper control
operation.
Unit Nameplate
The unit nameplate is located at the front of the unit. It
includes the unit model number, serial number, electrical
characteristics,refrigerant charge, and otherpertinent unit
data.
Water Connections
½" or ¾" water connections are located on the chassis’s
upper section and clearly labeled for water-in/out hose to
riser hook-up.
Water-to-Refrigerant Coils
The co-axial water-to-refrigerant heat exchanger for the ¾
ton through 3 ton equipment is constructed of copper or
cupro-nickel (option) for the water section and stainless
steel for the refrigeration section.
The heat exchanger is leak tested to assure there is no
cross leakage between the water and refrigerant gas.
ZN510 Controls
Units incorporating the ZN510 control option design will
include a digital LonTalk™ certified control board.The
control board will support such options as: random start
delay, heating/cooling status,occupied/unoccupied mode
and fan/filter status.
Power wiring is made at the contactor.The wiring is fed
through the left or right conduittube, and intothe cabinet’s
control box (contactor). See manual WSHP-IOP-2 for
diagnostic information.
Sound Attenuation
Sound attenuation is applied as a standard feature in the
product design.The enhanced reduction package includes
a heavy gage base plate, and gasket/insulation around the
compressor enclosure.
An optional deluxe sound reduction package is also
available. It includes a heavy gage base plate, gasket and
insulation around the compressor enclosure, and
vibration isolation between the chassis and cabinet. An
additional dampening treatment is applied around the
compressor enclosure to achieve greater acoustical
reductions.
WSHP-SVX10B-EN7
Page 8
Pre-Installation
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers could result in respiratory,
skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a
unit:
1. Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit
nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once the billof lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.
4. Verify that the refrigerant charge has been retained
during shipment by use of gauges. Schrader taps are
located external to the cabinet on the ¾-3 ton
equipment.
5. After assuring that charge has been retained, reinstall
the schrader caps to assure that refrigerant leakage
does not occur.
Jobsite Storage
NOTICE:
Microbial Growth!
Wet interior unit insulation can become an
amplification site for microbial growth (mold), which
may cause odors and damage to the equipment and
building materials. If there is evidence of microbial
growth on the interior insulation, the insulation should
be removed and replaced prior to operating the system.
This unit is intended for indoor useonly.To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources from growing, the unitshould be
stored indoors. If indoor storage is not possible, the
following provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.
2. Cover the unit(s) with a water proof tarp to protect
them from the elements.
3. Make provisionsfor continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces. Wet interior unit insulation can become an
amplification site for microbial growthwhich has been
determined to be a cause of odors and serious health
related indoor air quality problems.
4. Store refrigeration units (chassis) units in the normal
UP orientation to maintain oil in the compressor.
Cabinet configurations may be stored as crated.
5. Do not stack units.
8WSHP-SVX10B-EN
Page 9
Dimensions and Weights
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
Locate the unit in an indoor area.The ambient
temperature surrounding the unit must not be less than
45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and
technician safety.The unit chassis should be easily
removed from the cabinet in all applications.There must
be enough space for service personnel to perform
maintenance or repair. Provide sufficient room to make
water, and electrical connection(s). Local and national
codes should be followed in providing electrical power
connections.
Figure 1.Mechanical clearances
RSD
ALLOW 36" (914 mm)
AT UNIT FRONT FOR
CHASSIS REMOVAL
WSHP-SVX10B-EN9
Page 10
Dimensions and Weights
Figure 2.GET 009-036
Table 2.GET 009-036
GETABCDEF
009, 012
015-018
024-036
16¼"
(413)
18"
(457)
24"
(610)
10WSHP-SVX10B-EN
16¼"
(413)
20"
(508)
24"
(610)
8 1/8"
(206)
10"
(254)
12"
(305)
39 1/8"
(994)
40 5/8"
(1032)
49 5/8"
(1260)
14¾"
(375)¾"(19)
18¾"
(476)¾"(19)
22 5/8"
(575)¾"(19)
Page 11
Dimensions and Weights
Return Air (hinged) Acoustical Door
The hinged acousticaldoor is recessedinto the wall so that
the door is flush with the surface of the wall.
The opening through the wall for the door assembly must
be centered with the return-air opening of the unit cabinet.
For full installing instructions of the return-air acoustical
door, see p. 14.
Figure 3.Return air (hinged) acoustical door
3 1/2” ±3/8”
SHEETROCK
A
RETURN AIR OPENING
FLANGE ON CABINET
B
RETURN AIR
DOOR FLANGE
RETURN AIR OPENING
FLANGE ON CABINET
Table 3.Return air hinged acoustical door
Unit SizeAB
2“ X 4” STUD
1“ X 1” CLOSED
CELL INSULATION
CABINET
1“ X 1” CLOSED
CELL INSULATION
1 1/4”
+1/2”/-0”
009
012
015
018
024
036
A
19¼”
(489)
23¼”
(591)
27 1/8”
(689)
44 1/8”
(1121)
45¼”
(1149)
54 5/8”
(1387)
SHEETROCK
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR
DOOR FRAME
SHEETROCK
FLOOR
SHEET ROCK
OPENING
3 1/2” ±3/8”
K
2 X 4 STUD
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN-AIR OPENING
FLANGE ON CABINET
2 1/4“
4 5/8“
CABINET
SHEETROCK
Note:
Finished wall and framing should not
touch the unit cabinetry.
B
5“
2“ X 4”
STUD
CABINET
1 1/4”
+1/2”/-0”
TOP VIEW
1 1/2” X 2 3/8”
3 1/2” ±3/8”
SIDE VIEW
WSHP-SVX10B-EN11
Page 12
Installation
General Installation Checks
The checklist below is a summary of the steps required to
successfully install a unit.This checklist is intended to
acquaint the installing personnel with procedures
required in the installation process. It does not replace the
detailed instructions called out in the applicable sections
of this manual.
1. Remove packaging and inspect the unit. Check the unit
for shipping damage and material shortage; file a
freight claim and notify appropriate sales
representation.
Note: The unit cabinet is packaged in a wooden crate. A
pry bar and/or hammer will be needed for
packaging removal.
Note: The chassis sits inside a cardboard tray with an
upper box for protection.Typically four chassis will
be shrink-wrapped to a single pallet.
2. Verify the correct model, options and voltage from the
unit nameplate.
3. Verify the installation location of the unit will provide
the required clearance for proper operation.
4. Remove refrigeration access panel and inspect the
unit. Be certain the refrigerant tubing has clearance
from adjacent parts.
Main Electrical
3. Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect switch
and to the unit power block (1TB1) in the unit’s cabinet
control box for equipment.
4. Install proper grounding wires to an earth ground.
Note: All field-installed wiring must comply with NEC
and applicable local codes.
Low VoltageWiring (AC & DC)
Requirements
Connect properly sized control wiring to the proper
termination points between the field supplied thermostat
and the terminal plug in the equipment’s junction box.
Unit Placement
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
Figure 4.Stacking illustration
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
1. Verify the power supply complies with the unit
nameplate specifications.
2. Inspect all control panel components; tighten any
loose connections.
FLOOR
3" SWAGE
FLOOR
12WSHP-SVX10B-EN
Page 13
Installation
If unit cabinet assembly includes factory provided risers,
and "no" field provided between-the-floor riser
extensions, please move to Step 1.
Note: Risers are designed to accommodate a maximum
of 1½" to 3" expansion and contraction. If the total
calculated riser expansion exceeds 3", expansion
devices must be field provided.
If unit cabinet assembly includes factory provided risers
and field provided between-the-floor riser extensions are
required, install the extensions before installing the
cabinet.
1. Install drain valve, shut-off/balancing valves, flow
indicators and drain at the base of each supply and
return riser to enable system flushing at start-up,
balancing and service/maintenance.
2. Lift cabinet into space while aligning it into the
3"swage of the riser below.
Note: Take extra care as not to scrape or dent risers
during positioning.The riser should fall
approximately 2" into the 3" swage.This will allow
for the variation in floor-to-floor dimensions, and
keep the riser joints from bottoming out.
3. Level the cabinet.
4. Plumb risers in two planes to assure proper unit
operation and condensate drainage.
5. Anchor all units into place.
6. For field provided risers, center the supply/return
stubouts into the unit expansion slots.The stubouts
should be perpendicular to the cabinet panel.
7. Verify all risers are vertical and that they penetrate the
swaged joint at least 1". Riser should not be allowed to
bottom out.
8. Braze riser joints. Softsolder or low-temperature alloys
should not be used in this application.
9. If risers are field provided, it is recommended that the
risers be anchored to the building structure with a
minimum of one contact point. For expansion and
contraction reasons, do not fasten risers rigidly to the
building.
10. Seal access holes made through the cabinet for piping
with suitable material to help eliminate air leakage.
11. S e e “Cleaning and Flushing theWater Loop,” p. 16 for
system flushing.
Note: Remove shipping straps from risers.
Water Connection
For vibration isolation, it is recommended that flexible
steel braided hoses be installed instead of hard piping
between the vertical risers and the unit chassis.
Trane offers 4-types of hose kit variations:
•Stainless steel braided flexible hose with manual shutoff (ball) valves
•Stainless steel braided flexible hose with manual
circuit-setter valve
•Stainless steel braided flexible hose with automatic
balancing valve
Additional accessories, such as a strainer are
recommended for use to eliminate contaminants from
entering the co-axial water-to-refrigerant heat exchangers.
Note: Hoses should be no longer than 24”
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Verify that the power supply available is compatible with
the unit’s nameplate. Use only copper conductors to
connect the power supply to the unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors may
result in equipment damage.
WSHP-SVX10B-EN13
Page 14
Installation
Main Unit Power Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
A field supplied disconnect switch must be installed at or
near the unit in accordance with the NationalElectric Code
(NEC latest edition).
Location of the applicable electric service entrance for
HIGH (line voltage) may be found in Figure 5, p. 14.
Figure 5.Power wire entrance
Route power wire to the cabinet control box through the
factory installed conduit at the top of the unit
cabinetry.Thehigh voltage connection ismade at the1PB1
power block in the cabinet control box. Refer to the
customer connection diagram that is shipped with the unit
for specific termination points.
Provide proper grounding for the unit in accordance with
the local and national codes.
Drywall Installation
Before installing drywallaround cabinet, coverthe cabinet
supply and return openings with plastic or cardboard to
help prevent dust or construction debris from reaching
unit components. Warranties will be voided if paint or
foreign debris is allowed to contaminate internal unit
components.
The location of the drywall may be dependent upon the
type of return air access design.
For units containing a field provided return air access
assembly, the contractor must calculate location of
drywall to allow for frame mounting.
Units Utilizing Hinged Acoustic Door
Assembly
Figure 6.Mock-up of stud placement
1. Locate the side studs a
minimum of 1¼” and a
maximum of 1 3/8” from the
cabinet to the side of the stud.
This critical dimension,
combined with "distance
between studs" is used to
determine the side-to-side
opening for thedoor,dimension
A.The distances provided in the
table are a "minimum"
dimension. Allow 3½” from the
front of the cabinet to the sheet
rock surface, Figure 7, p. 15 - top
view, Figure 6, p. 14 - mock-up
of stud placement.
2. The height of thedoor assembly must be positionedto
recess the door 2¼” from the cabinet’s return-air
opening, Figure 7, p. 15 - side view blow-up.
Control PowerTransformer
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury
The 24V control power transformers are to be used only
with the accessories called out in this manual.
Transformers rated greater than 75VA are equipped with
internal circuit breakers. If a circuit breaker trips, turn OFF
all power to the unit before attempting to reset it.
The transformer is located in the chassis control box.
14WSHP-SVX10B-EN
Page 15
Installation
Figure 7.Drywall installation for hinged acoustic door
3 1/2” ±3/8”
2“ X 4” STUD
SHEETROCK
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR
DOOR FRAME
SHEETROCK
1 1/2” X 2 3/8”
SHEET ROCK
OPENING
3 1/2” ±3/8”
K
FLOOR
3 1/2” ±3/8”
A
B
2 X 4 STUD
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN-AIR OPENING
FLANGE ON CABINET
2 1/4“
CABINET
RETURN AIR OPENING
FLANGE ON CABINET
RETURN AIR OPENING
FLANGE ON CABINET
5“
4 5/8“
B
SHEETROCK
RETURN AIR
DOOR FLANGE
SHEETROCK
Note:
Finished wall and framing should not
touch the unit cabinetry.
CABINET
SIDE VIEW
1“ X 1” CLOSED
CELL INSULATION
CABINET
1“ X 1” CLOSED
CELL INSULATION
2“ X 4”
STUD
1 1/4”
+1/2”/-0”
1 1/4”
+1/2”/-0”
TOP VIEW
A
Note: When placing the sheet rock panel, make certain
the opening for the door is centered with the
return-air opening in the cabinet (±1/8").
Figure 8.Door opening
5. Secure the door frame to the side
studs using the holes located in
the door frame and field provided
screws.
Note: If the gap between the door
frame, and the side stud is
over 1/16-inch, place a shim in
between the door frame and
the stud to prevent the door
frame from bending/denting.
Figure 9.Air panel gasket
6. Place the air panel into the door
opening.The gasket on the back
side of the air panel should seal
around the coil perimeter.
Figure 10. Secure to door frame
7. After verifying that the air panel
gasket is sealed to the coil, secure
the air panel to the door frame
using the slotslocated on the sides
of the air panel.
3. Locate dimensionsA and B forsheet rock opening size.
The position of the sheet rock opening must be
centered side-to-side with the return-air opening in the
cabinet. Ensure the bottom of the sheet rock opening is
2¼” below the return-air opening in the cabinet.This
allows the door recess to rest on the bottom of the
sheet rock opening for proper vertical placement ofthe
door.
Table 4.Sheet rock opening size
Unit SizeAB
09
012
015
018
024
036
19¼”
(489)
23¼”
(591)
27 1/8”
(689)
44 1/8”
(1121)
45¼”
(1149)
54 5/8”
(1387)
4. Place the door frame into the sheet rock opening. A
positive seal is critical between the back of the door
frame and the front of the cabinet. Ensure that the
8. Install Filter.
9. Vacuumall dust and constructiondebris from unit after
cutting out supply/return openings.
Supply Air Ductwork
A 2" (50.8 mm) duct flange may be required to help
eliminate supply air from recirculating back into the return
air, air-to-refrigerant coil prior to discharging into the
space.
Equipment containing a top discharge, ducted design:
install field ductwork to the unit providing a water tight
flexible connector at the unit.This helps prevent operating
sounds from transmitting through the ductwork. Elbows
with turning vanes or splitters are recommended to
minimize air noise due to turbulence and to help reduce
static pressure.
gasket material seals properly.
WSHP-SVX10B-EN15
Page 16
Installation
Chassis Installation
Figure 11. Shipping bolts (see arrows)
1. Remove three 18-inch
bolts on the chassis
and discard.
2. Rotate the triangular
metal plate tocover the
bolt holes in the
chassis. Secure with
two sheet metal
screws.
(a) Not all units will include shipping bolts.
Figure 12. Bracket removal for deluxe sound package
3. Remove one shipping
bracket (one on each
side) attached to the
chassisslide rails and
discard.
Note: Remove this
bracket only if the
deluxe sound
package design is
selected.
4. Connect water coil pipe to the system riser with a
flexible steel hose assembly.
5. Verify that the shut-off/balancing valve in the return
line/supply line are closed.
6. Place shut-off valves in appropriate location (see
sticker on the equipment for best placement
recommendation) to allowchassisto slide easily in/out
of unit cabinet.
7. Flush system. See “Cleaning and Flushing the Water
Loop,” p. 16,” for flushing instructions.
8. Open the unit water valves and check piping for leaks.
9. Connect electrical to unit chassis via the quick connect
mating plugs.
Note: Four plugs are included (motor, optional
condensate overflow, power and thermostat).
Figure 13. Install chassis centered
10. Slide chassis into the cabinet.
Center the chassis left to right to
minimize sound transmission.
11. Verify unit’s air filter has shipped with the cabinet.
12. Install cabinet’s front cover to the hinged door.
Important: Ensure the gasket material creates a
positive seal around the entire coil to avoid
coil bypass. If a field supplied door is used,
ensure the front cover is attached to the
building structure and not the unit cabinet.
Supply Grille Installation
See Table 5, p. 16 for supply air dimensions.
Table 5.Supply air opening size
Top
Single Grille
GET
100% CFM
009, 012 14”W x 14”H 10”W x 6”H
015, 018 16”Wx12”H14”Wx12”H12”Wx8”H16”Wx14”H
02422”Wx18”H14”Wx12”H12”Wx8”H16”Wx14”H
036
Not
Recommended
Two Grille
50% CFM
16”Wx14”H14”Wx12”H17”Wx17”H
Three Grille
33% CFM
Not
Recommended
Discharge
up to
100% CFM
14”W x 10”H
1. Install the supply grille(s) into the cabinet discharge
opening. Ensure there are no air gaps between the
cabinet supply air and the grille.This helps prevent
recirculation of supply air into the return air opening
behind the drywall.
2. Secure grille(s) into the drywall via two screws.
Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose
connectors should be doubled back to complete the water
circuit external to the unit (avoiding trash settle-out in the
condenser). An extra pipe may be necessary to connect
the hose kits. See “Using Antifreeze,” p. 17 for antifreeze/
water mixture by volume.
1. Water circulation system should be filled with clean
water using the water make up connections.
Note: Air vents should be opened during filling.
2. With the air vents closed, start the circulating pump
and then crack the air vents to bleed off the trapped air,
assuring circulation through all components of the
system.
Note: Make up water must be available to the system to
replace the volume formerly occupied by the air
that is bled off.
Note: System water pressure needs to be relieved prior to
opening system.
3. With theair vented and the water circulating, the entire
system should be checked for leaks with repairs made
as required.
4. Operate the supplementary heat system making
checks per manufacturer’s instructions. During this
operation, visual checks should be made for leaks that
16WSHP-SVX10B-EN
Page 17
Installation
may have occurred due to increased heat. Repair as
required.
5. Open the system at the lowest point for the initial blow
down (making sure the make up water is equal to the
water being dumped). Continue blow down until the
water leaving the drain runs clear, but not less than 2
hours.
6. Shut down pumps and supplementary heat system.
Reconnect the hoses placing the water-to-refrigerant
heat exchanger in the water circulating system.
Note: Vents should be open when the pumps and
supplementary heat system are shut down.
Figure 14. Flushing the water loop
CONNECTION
HOSE
WATER-SOURCE
HEAT PUMP
CIRCULATING
TEMPORARY
CONNECTION
FOR SYSTEM
FLUSHING
PUMP
Low VoltageWiring
Factory ordered thermostats and zone sensors are prewired with a quick connecting plug.
1. After installing the cabinet assembly, simply plug the
male portion of thermostat/zone sensor plug into the
female portion of the plug located inside the unit’s
junction box.
2. Mount the thermostat or zone sensor on the finished
drywall.
Thermostat/zone sensor connection is shown inFigure 15,
p. 17.
Low VoltageWiring for Field Provided
Thermostats/Zone Sensors
Ensure that the AC control wiring between the controls
and the unit’s termination point does not exceed three (3)
ohms/conductor for the length of the run.
NOTICE:
Component Failure!
Resistance in excess of 3-ohms per conductor could
result in component failure due to insufficient AC
voltage supply.
GROUND-LOOP
OR
COOLING TOWER/BOILER
Using Antifreeze
In areas of the countrywhere entering water temperatures
drop below 45°F or where piping is being run through
areas subject to freezing, the loop must befreeze protected
by using an approved antifreeze solution to prevent the
earth loop water from freezing inside the heat exchanger.
Methanol and glycols are the most commonly used
antifreeze solutions. Consult your geothermal unit
supplier for locally approved solutions in your area.
Propylene glycol is not recommended in installations
where the water temperature are expected to fall below
30°F. At extreme temperatures, the viscosity increases to
the point where normal loop circulating pumps may not
maintain proper flow.
If propylene glycolis the only locally approved solution for
anti-freeze, good engineering practices should be used to
achieve the desired flow.
Calculate the approximate volume of water in the system
by using the requirements detailed inTable 8, Water
Volume. Add three gallons to this total to allow for the
water contained in the hose kit and geothermal unit.
Table 6.Antifreeze requirements based on volume
Check all loads and conductors for grounds, shorts, and
mis-wiring.
Do not run the AC low voltage wiring in the same conduit
with the high voltage power wiring.
Table 7.24V AC conductors
Distance from unit
to Control
000-460 feet18 gauge
461-732 feet16 gauge
733-1000 feet14 gauge
Recommended
Wire Size
Figure 15. Zone sensor connection
Six (6) Pin Connector/Harness
•Red = 24V
•Black = Fan
•Orange = RV
• Yellow = Compressor
•Blue = Common
Type of
Antifreeze
Methanol
Propylene Glycol
WSHP-SVX10B-EN17
Minimum Temperature for Freeze
Protection
10°F15°F20°F25°F30°F
25%21%16%10%3%
————6%
Page 18
Installation
Table 8.Deluxe controller diagnostic LEDs
Color: GreenColor: RedController Mode
LED1LED2LED3
OFFOFFOFFControl OFF
ON
ON
ON
FLASH
ON
ON
ON
ON
ON
ON
OFFOFFNormal/Compressor OFF
OFFFLASHAnti-short Cycle
OFFONNormal/Compressor ON
PSC motors installed in the unit have multiple speed
configurations.To modify the rpm of the motor, the
following steps may be followed.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Figure 16. ECM control board and dip switch setting
Dip Switch
to select profile
123456 78
On
Off
12345678
On
Off
1 2 3 45678
On
Off
12345678
On
Off
Profile A
Profile B
Profile C
Profile D
1. Locate the blower motor relay inside the chassis
control box.
2. Remove the undesired speed tap.
3. Select desired speed tap wire by using information
from Table 9, p. 18.
4. Connect desired tap wire to the 1K4 relay at spade 4.
5. Reconnect power to the unit.
Table 9.Lead change
Lead Colors
Lead SpeedHighLow
Blower
1G9A
Note: Units with the optional ECM motor are shipped
from the factory on Profile B.
To adjust the CFM, disconnect the power to the unit. Set
the DIP switch located in the control box to the desired
profile setting. See Figure 16. Connect the power to the
unit. If the power is not disconnected when the DIP switch
is set, the motor will not be programmed to the new
setting.
•Profile A = 110% of rated air flow
•ProfileB=100%ofrated air flow
•Profile C = 90% of rated air flow
•Profile D = 805 of rated air flow
ECM Motor CFM Settings
To adjust the CFM, disconnect the power to the unit. Set
the DIP switch located in the control box to the desired
profile setting. See Figure 16. Connect the power to the
unit. If ht epower is not disconnected when the DIP switch
is set, th emotor will not be programmed ot the new
setting.
18WSHP-SVX10B-EN
Page 19
Installation
Table 10. PSC blower motor external static pressure without return air door (RAD) with filter
External Static Pressure (in. of wg)
Model
Speed
Ducted
No
GET
009
GET
012
GET
015
GET
018
GET
024
GET
036
Model NoSpeed
GET
015
GET
018
GET
024
GET
036
Model NoSpeed
GET
036
(a)The NO “Ducted” option is for non-ducted (free return) units. Units specified as “non-ducted” (free return) are factory wired to low-speed. Units specified
Table 12. Pressure drop due to return air door (RAD)
Model No.CFMDPCFMDPCFMDP
GET 0092720.043400.054080.08
GET 0123030.043800.074560.11
GET 0154320.065400.096480.12
GET 0185200.086500.127800.16
GET 0246560.068200.089840.12
GET 0369360.1011700.1614040.23
Note: The pressure drop across the RAD door should be included in the TOTAL ESP when determining airflow and fan motor power usage. If the door is supplied
by another vendor, the pressure drop across that door must be included in the TOTAL ESP when determining airflow and fan motor power usage.
Before energizing the unit, the following
system devices must be checked:
____ Is the high voltage power supply correct and in
accordance with the nameplate ratings?
____ Is the field wiring and circuit protection the correct
size?
____ Is the low voltage control circuit wiring correct per the
unit wiring diagram?
____ Is the piping system clean/complete and correct? (A
recommendation of all system flushing
of debris from the water-to-refrigerant heat exchanger,
along with air purging from the water-to-refrigerant heat
exchanger be done in accordance with the Closed-Loop/
Ground Source Heat Pump Systems Installation Guide).
____ Is vibrationisolation provided? (i.e. unitisolation pad,
hose kits)
____ Is unit serviceable? (See “Unit Location and
Clearances,” p. 9.)
____ Are the low/high-side pressure temperature caps
secure and in place?
____ Are all the unit access panels secure and in place?
____ Is the thermostat in the OFF position?
____ Is the water flow established and circulating through
all the units?
____ Is the duct work (if required) correctly sized, run,
taped, insulated and weather proofed with proper unit
arrangement?
____ Is the condensate line properly sized, run, trapped and
pitched?
____ Does the indoor blower turn freely without rubbing?
____ Has all work been done in accordancewith applicable
local and national codes?
____ Has heat transfer fluid been added in the proper mix
to prevent freezing in closed system application?
____ Are the compressor bolts removed from the chassis?
____ Have the chassis isolation rails been released?
____ Is there a good seal between the front air panel and
the coil?
2. Reduce the temperature control setting until the
compressor, reversing valve, solenoid valve, and loop
pump are energized. Adjust water flow utilizing
pressure/temperature plugs and comparing to tables
contained in specification sheet data. Water leaving
the heat exchanger should be warmer than the
entering water temperature (approximately 9°F-12°F);
blower operation should be smooth; compressor and
blower amps should be within data plate ratings; the
suction line should be cool with no frost observed in
the refrigerant circuit.
3. Check the cooling refrigerant pressures against values
in Table 14, p. 23.
4. Turn the thermostat switch to the OFF position. Unit
should stop running and the reversing valve should
de-energize.
5. Leave unit off for approximately FIVE minutes to allow
for pressure equalization.
6. Turn the thermostat to the lowest setting. Set the
thermostat system switch to the HEAT position.
7. Adjust the temperature setting upward until the unit is
energized. Warm air should blow from the register. A
water temperature decrease of approximately 5°F-9°F
leaving the heat exchanger should be noted. The
blower and compressor operation should be smooth
with no frost observed in the refrigeration circuit.
8. Check the heating refrigerantpressures against values
in Table 14, p. 23.
9. Set the thermostat to maintain the desired space
temperature.
10. Instruct the owner on system operation.
Initial Unit Start-up
Start-up with deluxe controls is included below:
TM
Note: Start-up for theTracer
found in WSHP-IOP-2.
1. Set the thermostat to the highest position.
Set the thermostat system switch toCOOL withthe fan
control to AUTO.The compressor should NOT run.
22WSHP-SVX10B-EN
ZN510 controller may be
Page 23
Operating Pressures
Use the form on p. 26to log systemand unit temperatures
during start-up.
GENERAL:There are many variables (airflow, air
temperatures) in an air conditioning systemthat will affect
operating refrigerant pressures and temperatures.The
on air flow at the rated SCFM, entering air at 80.6°F DB,
66.2 °FWB in cooling, 68°F DB in heating. (+)Heating data
with 35°F EWT is based on the use of an anti-freeze
solution having a freezing point 20 °F lower than the
minimum expected entering temperature.
chart below shows approximate conditions and is based
For the operating temperature drop (heating) and rise
(cooling), refer to Table 14, p. 23 for the proper water
temperature change. Depending on the unit size, entering
water temperature and water flow rate, the cooling
temperature rise is from 8°F-16°F. Based on the same
criteria for heating, the temperature drop is from 2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with
the P/T port adapter, measure the pressure difference
between the water-in and water-out connections. Compare
the pressure differential to Table 15, p. 25 to determine
flow.
WSHP-SVX10B-EN25
Page 26
Start-up
Installing Contractor: Use this form to thoroughly checkout the system and units before and during start-up. (This
form need not be returned to the factory unless requested
during technical service support).
Job Name:
Model Number:
Date:
Serial Number:
In order to minimize troubleshooting and costly system
failures, complete the following checks and data entries
before the system is put into full operation.
MODEHeatCool
Entering fluid temperature
Leaving fluid temperature
Temperature differential
Return-air temperature DB/WB
Supply-air temperature DB/WB
Temperature differential
Water coil heat exchanger (Water
Pressure IN)
Water coil heat exchanger (Water
Pressure OUT)
Pressure Differential
COMPRESSOR
Amps
Volts
Discharge line temperature (after
10 minutes)
FF
FF
FF
FF
FF
FF
PSIGPSIG
PSIGPSIG
PSIGPSIG
PSIGPSIG
PSIGPSIG
FF
26WSHP-SVX10B-EN
Page 27
Maintenance
Preventive Maintenance
Maintenance on the unit is simplified with the following
preventive suggestions:
Filter maintenance must be performed to assure proper
operation of the equipment. Filters should be inspected at
least every three months, and replaced when it is evident
they are dirty. Filter sizing includes:
Table 18. Filter sizing
Model GETFilter Size (nominal)
009, 01214 x 20 (356 x 508)
01518 x 20 (457 x 508)
01818 x 25 (457 x 635)
024, 03620 x 30 (508 x 762)
WARNING
Hazardous Chemicals!
Cleaning agents can be either acidic or highly alkaline.
Handle chemical carefully. Proper handling should
include goggles or face shield, chemical resistant
gloves, boots, apron or suit as required. For personal
safety refer to the cleaning agent manufacturer’s
Materials Safety Data Sheet and follow all
recommended safe handling practices. Failure to follow
all safety instructions could result in death or serious
injury.
It should be noted that the water quality shouldbe checked
periodically.
Table 19. Water quality table
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Check the contactors and relays withinthe control panel at
least once a year. It is good practice to check the tightness
of the various wiring connections within the control panel.
A strainer (60 mesh or greater) must be used on an open
loop system to keep debris from entering the unit heat
exchanger and to ensure a clean system.
For units on well water, it is important to check the
cleanliness of the water-to-refrigerant heat exchanger.
Should it become contaminated with dirt and scaling as a
result of bad water, the heat exchanger will haveto be back
flushed and cleaned with a chemical that will remove the
scale.This service should be performedby an experienced
service person.
Scaling
Calcium and magnesium (total
hardness)
Corrosion
pH7-9.5
Hydrogen SulfideLess than 1 ppm
SulfatesLess than 25 ppm
ChloridesLess than 125 ppm
Carbon DioxideLess than 75 ppm
Total dissolved solids (TDS)Less than 1000 ppm
Biological Growth
Iron BacteriaLow
Erosion
Suspended SolidsLow
Less than 350 ppm
WSHP-SVX10B-EN27
Page 28
Troubleshooting
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures.When possible, disconnect all electrical
power including remote disconnect and discharge all
energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
PreliminaryTrouble Inspection
•If operational difficulties are encountered, be sure to
perform the preliminary checks before referring to the
Table 20, p. 29.
•Verify that the unit is receiving electric supply power.
•Ensure that the fuses in thefused disconnect are intact.
•After completing the preliminary checks, inspect the
unit for other obvious problems such as leaking
connection, broken or disconnected wires, etc. If
everything appears to be in order, but theunit still fails
to operate properly, refer to the troubleshooting chart
on p. 29.
General Operation
The standard model is designed for indoor installation.
When the unit is installed in an unconditioned space, the
unit may not start in cool weather (approximately 45°F). It
may then benecessary to start the unitin the coolingmode
for three to five minutes.The unit may then be shut-off
(there will be a two minute time-out of the unit), and
restarted in the heating mode.The freeze protection
thermostat should also be checked as it may be adversely
affected by ambient temperature.
Like any other type of mechanical equipment, the unit
performs best when it is well maintained.
Operation with a Conventional
Thermostat
The unit is equipped with safety controls, including high
pressure control, low pressure control and a freeze
protection thermostat, set to shut off the compressor
under abnormal temperatureor pressure conditions. Ifthe
safeties shut off the compressor, a lockout relay prevents
short cycling from the abnormal condition. When
conditions are corrected, the lockout control can be reset
by setting the thermostat system switch to OFF wait a few
minutes for the system pressure to equalize, and then
return to HEAT or COOL. If the condition continues, an
authorized service person should check out the unit.
28WSHP-SVX10B-EN
Page 29
Table 20. Troubleshooting checklist
ProblemHeating CoolingCauseCorrection
No response to any thermostat setting
Unit short cyclesXXThermostat or sensor improperly locatedRelocate
Blower runs, but compressor does not
Insufficient capacity
High pressure switch open
High head pressure
Low suction pressure
Troubleshooting
XXMain power offCheck fuses
XXDefective control transformerReplace
XXBroken or loose connectionRepair
XXDefective thermostatReplace
XXTransformerReset Transformer
XXDefective compressor overloadReplace (if external)
XXDefective compressor contactorReplace
XXSupply voltage too lowCorrect
XXDefective compressor capacitorReplace
XXDefective windingsReplace
XXLimit switches openCheck cause/Replace or repair
XXDirty filterReplace/clean
XXBlower RPM too low Correct
XX
XIntroduction of excessively cold return-airCorrect
XXLow on refrigerant charge
XXRestricted thermal expansion valveReplace
XXDefective reversing valveSee WSHP-IOM-# for touch test chart
XXThermostat improperly locatedRelocate
XXUnit undersizedRecalculate heat gains/losses
XXInadequate water flowIncrease GPM
XXScaling in heat exchanger Clean or replace
XWater too coldIncrease temperature
XInadequate air flowCheck, clean blower and coil
XDirty filterClean/replace
XXOvercharged with refrigerantDecrease charge
XXDefective pressure switchCheck or replace
XXOvercharge of refrigerantDecrease charge
XXNon-condensable in systemEvacuate and recharge by weight
XXWater too hotDecrease temperature
XDirty filterClean / replace
XInadequate air flowCheck, clean blower and coil
XXUnderchargedLocate leak, repair and recharge
XXRestricted thermal expansion valveRepair / replace
XInadequate GPMIncrease GPM
Loss of conditioned air due to leaks in
ductwork
XIntroduction of excessively hot return-airCorrect
Locate leak, repair and recharge by
XWater too hotDecrease temperature
XInadequate GPMIncrease water flow to unit
XWater too hotDecrease temperature
XTrash in heat exchangerBackflush
XLow water flowIncrease GPM
XInadequate air flowCheck, clean blower and coil
XDirty filterClean/replace
Repair leaks
weight (not by superheat)
WSHP-SVX10B-EN29
Page 30
Unit Wiring
Figure 17. Tracer ZN510/1 Ph
208/60/1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
L2L1
1PB1
2H
1H
1S4
21A
SEE
INSET
B
21E23E24F
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
ARE SHOWN AT 25° C (77° F), AT
ATMOSPHERIC PRESSURE, AT 50% RELATIVE
HUMIDITY, WITH ALL UTI LITIES TURNED OFF,
AND AFTER A NORMAL SHUTDOWN HAS
OCCURRED.
DASHED LI NE S INDICATE RECOMMENDED FIELD
2.
WIRING BY OTH E RS . FIELD WIRING T O B E RA TE D
FOR 600 VOLTS. DASHE D LINE ENCLOSURE
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. SOLID
LINES INDI CATE WIRING BY THE TRANE CO.
3.
NUMBERS ALONG THE RIGH T SIDE OF THE
SCHEMATIC DESIGNATE THE LOCATION OF THE
CONTACTS BY LINE NUMBER.
4.
ALL FIE LD WIRING MU ST BE IN A CCORDANCE WITH
THE NATIONAL ELECTRIC CODE (NEC), STATE AND
LOCAL REQUIR EMENTS.
VERIFY TEST JUMPER HAS BEEN REMOVED TO
6
PREVENT CONTROL TIMING ERRORS.
21B
A,C
P10-1 J10-1P7-1
SINGLE
STAGE
ROOM
T'STAT
2F
21C
EQUIPMENT
GROUND
1F1
1F
1F2
9A
3F
P20-2
P20-1
J20-2
J20-1
MTR-5
MTR-4
GRN
MTR-3
1TB1-1 & 2
23A
SEE
INSET
B
SEE
INSET
B
22B
P10-2 J10-2
22C
R G O W Y
1A
2A
9C
3J
21
P7-3 J7-3
23B
P10-3 J10-3
23C
3B 3ACHASSIS
P11-3 J11-3
P11-1 J11-1
P11-2 J11-2
B
SEE
INSET
B
3B2
M
1
COM
TO 1U5 BRD
15 PIN PLUG
SEE INSET B FOR
CONTROL WIRING
23A
24C
P10-4 J10-4
24D
COMN
GROUND
2CCH-1
WW
1K1
1B
2B
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
1TB1-1&2
6E
FIELD INSTALLED
ISOLATION VALVE
CLOSE
FOR TWO WIRE N. C VA LVE,
DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
D
D
208/60/1
1T1
24V
A
23C
21C
26H26G
24C24B
SEE
INSET
B
26M
P7-4 J7-4
26H
P10-5 J10-5
12
26K
CONNECTION FOR 24VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D
FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP
RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATE D GENERAL AL A R M CO NT ACTS. CONTACTS CLOSE
11
WHEN CONTRO L 1U 2 GO E S INTO MANUAL L OC K O UT MODE.
CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRED FOR HARD WIRED DIGITAL THERMOST A TS.
12
CAUTION
USE COPP ER CONDUCTORS ONLY !
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE D AMAGE TO THE
EQUIPMENT.ENDOMMAGER L' ÉQUIPEMENT.
1C3
4B
2B1
C
2B1C1
M
5B
1
S
6B
R
1K1
50A
OPEN
COM
2L1
21C
24B
2B1S1
2B1S2
49B47C
ATTENTION
N'UTILISE R Q U E DE S CONDUCTEURS E N CUIVRE !
LES BORNES DE L'UNITÉ NE SONT PA S CONÇUES
POUR RECEVO IR D'AUTRES TYPES DE CONDUCTEURS.
NORMAL / COMP OFF
ANTI-SHORT CYCL E
NORMAL / COMP ON
BROWNOUT CONDIT IION
SOFT LOCKOUT LP
SOFT LOCKO UT HP
MANUAL LOCKOUT LP
MANUAL LOCKOU T HP
MANUAL LOCKOUT
CONDENSATE LEVEL
COMPRESSOR DISABLE
DEVICE PREFIX LO CATION CODE
AREA1LOCATION
CONTROL PANEL
COMPRESSOR SECTION2
INDOOR FAN AN D CO IL SECTION3
4 WATER COIL SECTION
5 RETURN AN D FR ESH AIR SECTION
FIELD INSTALLED DEVICE6
LEAD COLORS
LEAD
HIGHSPEED
1U2
46A
LED1
47A
LED2
LED3
48A
49A
6
INSET B
J16
P16
P17
J17
TO BLOWER MOTOR 3B2 15 PIN PLUG
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR O TR OS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.
DEVICE
DESIGNATION
1C3START ASSIST5
1F1,
FUSE
COMPRESSOR CONTACTOR1K1
POWER BLOCK
1PB1
1S4
FUSED UNIT SWITCH
1TB1 CUSTOMER LOW V. TERM BLOCK
CRANKCASE HEATER2CCH-14
CONTROL POWER TRANSFORMER
1T1
COMPR CONTROL MODULE34
1U2
COMPRESSOR MOTOR2B1
COMPRESSO R RUN CAPACITOR2B1C18
LOW
HIGH PRESS U RE CUTOUT2B1S136
FREEZE PROTECTI ON SWITCH38
2S1
2L1R EVE RSING VALVE COIL
2B1S2 LOW PRESSURE SWITCH39
3B2E VAP FAN MOTOR
OVERFLOW SWITCH
3S335
ECM CONTROLLER
1U5
,C,E,G,M
G
M
44A
45A
1U5
P1
J9-5 P9-5
J9-6 P9-6
98
44B
44C
45B
45C
21E
23E
P15-4
P15-5
P15-3
21D
23D
ROW3 W2 W1 YYLO BGBK
R
PRECAUCIÓN
24F
24E
LEGEND
DESCRIPTION
26M
22B
P15-1
P15-2
26L
22D
LINE
NUMBER
6,
71F2
6,7,37
3
4
21
19
6,7,8
26
15
55
3S3
DRAWN BY
REPLACES
REVISION DATE
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS DRA WING IS PRO PR IETARY AND
CONTENTS DISCLOSED TO OUTSIDE
CONSENT OF THE TRANE COMPANY
PARTIES WITHOUT THE WRITTEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
P2
SCHEMATIC DIAGRAM
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
30WSHP-SVX10B-EN
Page 31
Figure 18. Deluxe 230V/60 Hz/1 Ph
Unit Wiring
208/60/1
1
2
3
4
5
6
7
1PB1
L2L1
2H
1H
1S4
1F
2F
8
9
10
11
12
13
14
15
16
17
FIELD INSTALLED
ISOLAT ION VALVE
1TB1-1&2
CLOSE
FOR TWO WIRE N.C VALVE,
DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
18
19
20
21
A,C
22
23
24
25
26
27
28
29
30
31
22A
21A
32
33
34
35
P7-1
22B
21B
36
37
38
39
40
41
P10-1 J10-1
SINGLE
STAGE
ROOM
T'STAT
21C
42
43
44
45
46
47
48
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
49
ARE SHOWN AT 25° C (77° F), AT
ATMOSPHERIC PRESSURE, AT 50% RELATI V E
HUMIDITY, WIT H ALL UTILITIES TURNED OFF,
50
AND AFTE R A NO RMAL SHUTDO W N H AS
OCCURRED.
51
DASHED LINES INDICATE RECOMMENDED FIELD
2.
WIRING BY OTHERS. FIE L D WIRIN G T O BE RA T ED
52
FOR 600 VOLTS. DASH ED LINE ENCLOSURE
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. SOL I D
53
LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE
54
SCHEMATIC DESIGNATE THE LO CATI ON OF THE
CONTACTS BY LINE NUMBER.
55
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D
56
LOCAL REQUIREMENTS.
57
VERIF Y TEST JUMPER HAS BEEN REMOVED TO
6
PREVEN T CONTROL TI MING ERRORS.
58
59
60
3B3ACHASSIS
P11-3 J11-3
EQUIPMENT
GROUND
1F1
1A
1F2
2A
50A
OPEN
COM
1TB1-1 & 2
21
23A
P7-3 J7-3
P7-2 J7-2
23B
P10-3 J10-3
P10-2 J10-2
22C
23C
R G O W Y
P11-1 J11-1
P11-2 J11-2
1K1
B
23A
24C
P10-4 J10-4
24D
COMN
GROUND
2CCH-1
WW
1K1
1B
2B
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
,C
1K4
C,D
42
6E
D
D
208/60/1
1T1
24V
22A
1K4
A
C
1313
23C
21C
26H26G
24C24B
P7-4 J7-4
26H
P10-5 J10-5
12
26K
CONN ECTIO N FOR 2 4VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D
FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP
RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE
11
WHEN CONTROL 1U2 GOES INTO MANUAL LOCKOUT MODE.
CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRE D FO R HA R D WIRED DIGI TAL THERMO S T A T S.
12
WIRE S 23C & 26J ARE ONLY USED ON SIZE 024 & 036.
13
ON AL L OTHER SIZ ES WIR ES 23A & 26F CONNECT TO 2L1.
USE COPPER CONDUCTORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED T O ACCEPT
OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CAUSE DAMAGE TO THE
EQUIPMENT.ENDOMMAGER L'ÉQUIPEMENT.
CAUTION
1C3
4B
2B1
C
2B1C1
1G
M
5B
1
S
6B
R
J1-1
J1-3
C
J1-2 P1-2
2L1
21C
24B
2B1S1
2B1S2
49B47C
ATTENTION
N'UTILI SE R QUE DES CONDUCT E URS EN CUIVRE!
LES BORNE S DE L'UNITÉ NE SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CON DUCTEURS.
NORMAL / CO MP OFFONOFFOFF
ANTI-SHORT CYCLE
NORMAL / CO MP ON
BROWNOUT CO NDITIION
SOFT LOCKOUT LP
SOFT LOCKOUT HP
MANUAL LOCKOUT LP
MANUAL LOCK OUT HP
MANUAL LOCKOUT
CONDENSATE LE VEL
COMPRESSOR DI SABL E
DEVICE PREFIX LOCATION CODE
AREA1LOCATION
CONTROL PANEL
COMPRESSOR SECTION2
INDOOR FAN AND CO IL SECTION3
4 WAT ER COIL SECTION
5
RETURN AND FR ES H AIR SECTION
FIELD INSTALLE D DEVICE6
LEAD COLORS
LEAD
BLU RED
HIGHSPEED
3B2
M
1
GRN
COM
1U2
46A
LED1
47A
LED2
LED3
48A
49A
6
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS
PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
DEVICE
DESIGNATION
1C3START ASSIST5
1F1,
FUSE
COMPRESSOR CONTACT OR1K1
1K4
BLOWER REL AY
1PB1POWER BLOCK
1TB1CUSTOMER LOW V. TER M BL OCK
CRANKCAS E H EATER2CCH-14
CONTROL POWER TR ANSFORMER1T119
COMPR CONTROL MODULE34
1U2
COMPRESSOR MOTOR2B1
COMPRESS O R RU N CAPACITOR2B1C18
LOW
HIGH PRESSURE CUTOUT2B 1S136
FREEZE PROTECTION SWITCH
2S1
2L1REVER S I NG VALVE COIL26
2B1S2 LOW PRESSURE SWITCH
3B2EVAP FAN MOTOR
3B2C2
EVAP FAN M T R RUN CAPACITOR
OVERFLOW SWITCH
3S335
,C,E,G,M
G
M
44A
45A
J9-5 P9-5
J9-6 P9-6
44B
45B
PRECAUCIÓN
LEGEND
DESCRIPTION
3S3
44C
LINE
NUMBER
6,
6,7,37
13,22
3
21
6,7,8
38
39
15
15
71F2
45C
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS DRAWING IS PROPRIETARY AND
CONTENTS DISCLOSE D T O OUTSIDE
CONSENT OF THE TRAN E COMPANY
PARTIE S WITHOUT THE WR I TTEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
SCHEMA TIC DIAGRA M
2311-0376
WALL MOUNT T'STAT
208/60/1
DELUXE UNIT
HEAT PUMP
GET
REV
G
WSHP-SVX10B-EN31
Page 32
Unit Wiring
Figure 19. Tracer ZN510/1 Ph with ECM motor
208/60/1
1
2
3
4
5
6
7
8
9
10
11
1PB1
L2L1
2H
1H
1S4
1F
1F2
2F
9A
P20-2
J20-2
12
13
14
15
GRN
16
17
18
19
20
21
INSET B
K,X,P
22
23
24
25
26
27
28
29
P64A
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
49
ARE SHOWN AT 25° C (77° F), AT
ATMOSPHERIC PRESSURE, AT 50% RELATI V E
HUMIDITY, WIT H ALL UTILITIES TURNED OFF,
50
AND AFTE R A NORMAL SHU TD O W N H AS
OCCURRED.
51
DASHED LINES INDICATE RECOMMENDED FIELD
2.
WIRING BY OTHERS. FIE L D WIRING TO BE R ATED
52
FOR 600 VOLTS. DASH ED LINE ENCLOSURE
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. SOLID
53
LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE
54
SCHEMATIC DESIGNATE THE LO CATI ON OF THE
CONTACTS BY LINE NUMBER.
55
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D
56
LOCAL REQUIREMENTS.
57
58
COMMU NICAT ION WI RE MUST BE TRANE PART NO.
6
59
400-20-28, OR WINDY C ITY OR CONNECT AIR
"LEVEL 4" CABLE. MAXIMUM OF 4500 FOOT
AGGREGATE RUN.
60
CAUTIO N! DO NOT RUN POWER IN THE SAME
CONDUIT OR W I R E BU ND L E WITH COMMUNICATI ON
LINK. FOR ADDITIONAL INFROMATION REFER TO
EMTX-EB-68.
EQUIPMENT
GROUND
1F1
26M
1TB1-1 & 2
J9-3 P9-3
21K
3F
P20-1
J20-1
MTR-5
MTR-4
MTR-3
9C
3J
21
3B 3ACHASSIS
P11-3 J11-3
1A
P11-1 J11-1
2A
P11-2 J11-2
3B2
M
1
COM
TO 1U5 BR D
15 PIN PLUG
SEE INSET B FO R
CONTROL WIRI NG
B
21R
CONDENSATE
OVERFLOW
OPTIONAL
GROUND
2CCH-1
WW
1K1
1B
2B
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
1TB1-3&4
6E
FIELD INSTALLED
ISOLAT ION VALVE
CLOSE
FOR TWO WIRE N.C VALVE,
DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 6VA AT 24V
D
D
208/60/1
1T1
24V
A
21M
P9-1
2B1S1
2B1S2
P9-4 J9-4
JX15-1
P15-1
P7-5 J7-5
45B
P7-6 J7-6
CAUTION
2S1
63A
46B
47B48B
2L1
64B
22B
3S3
OCCUPANCY
CONNECTIONS
6
COMM LINK
USE CO P PER CON DUCT ORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED TO ACCEPT
OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CA USE DAMAGE TO THE
EQUIPMENT.ENDOMMAGER L'ÉQUIPEMENT.
1C3
4B
2B1
C
5B
6B
S
R
1TB1-1&2
COM
OPEN
M
1
21M
1K1
2B1C1
P9-2
49B
26U
24VGND
J2-1
BI1
44A44B
BI2
45A
BI3
TB1-2
POWER
J2-2
BINARY INPUT
J2-3
J2-4
J2-5
J2-6
TB2-1
TB2-2
ATTENTION
N'UTILISER QUE DES CO NDUC T E UR S EN CUI VRE!
LES BORNE S DE L'UNITÉ N E SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CON DUCT EURS.
L'UTILISATION DE TOUT AUTRE COND UC TEUR PEUT
LEGEND
DESCRIPTION
FUSE
COMPRESSOR CONTACTOR1K1
CRANKCAS E HEATER2CCH-14
CONTROL POWER TR ANSFORMER1T119
COMPRESSOR MOTOR2B1
COMPRESS O R RU N CAPACITOR2B1C18
FREEZE PROTECTION SWITCH
OVERFLOW SWITCH
ZN510 CONTROLLER
ECM CONTROLLER
LEAVING WATER TEMP SENSOR4RT3
NUMBER
6,
6,7,23
LINE
71F2
3
4FUSED UNIT SWITCH1S4
21
6,7,8
26
26
15
38
37
34
55
40
DEVICE PREFIX LO CATION CODE
AREA1LOCATION
CONTROL PANEL
COMPRESSOR SECTION2
INDOOR FAN AND CO IL SECTION3
4 WATER COIL SECTION
5
RETURN AND FRES H AIR SECTION
FIELD INSTALLE D DEVICE6
LEAD
LEAD COLORS
HIGHSPEED
DEVICE
DESIGNATION
1C3START ASSIST5
1F1,
1PB1POWER BLOCK
1TB1CUSTOMER LOW V. TERM BLOCK
2B1S1
2B1S1 HIGH PRESSURE CUT OUT26
LOW
2S1
2L1REVERSI N G VALVE COIL29
2B1S2 LOW PRESSURE CUTOUT
3B2EVAP FAN MOTOR
3RT4 DISCHARGE AIR SENSOR
3S3
1U4
1U5
INSET B
1TB1-3 & 4
26
21E
,U
26U
P14-2
2
34567
BINARY OUTPUTS
TB3-3
TB3-4
SET
FAN GND
75A
69A
20B64A
P14-5
TB3-6
J7-1 P7-1
J7-2 P7-2
J7-3 P7-3
J7-4 P7-4
83A
J3-4
82A
J3-3
ANALOG INPUT
J3-2
AI1AI2
J3-1
75B
J10-1 P10-1
69B
J10-2 P10-2
68B
J10-3 P10-3
67B
J10-4 P10-4
4RT3
3RT4
75C
69C
68C
67C
DISCHARGE AIR
SENSOR
LEAVING WATER
SENSOR
FAN MODE
SET POINT
COMMON
ZONE TEMP
ZONE
SENSOR
63A
21K
TB1-1
P14-1
J1
1
1U4
ZONE SENSORCOMM LINK
TB3-2
TB2-3
TB2-4
TB3-1
TB2-5
TB2-6
GNDZONE
68A
67A
6
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS D RAWIN G IS PROPRIETARY AND
CONTENTS DISCLOSED TO OUTSIDE
CONSENT OF THE TRAN E C OMPANY
PARTIE S WITHOUT THE WR I T TEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
P2
SCHEMA TIC DIAGRA M
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
INSET B
J16
P16
J17P17
1U5
TO BLOWER M OTOR 3B2 15 PIN PLUG
PRECAUCIÓN
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS
PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
21E
24F
26M
22B
PX15-1
PX15-5
98
P1
R ROW3 W2 W1 YYLO BGBK
PX15-2
PX15-3
21D
23D
26L
24E
22D
32WSHP-SVX10B-EN
Page 33
Figure 20. Deluxe 24V/1 Ph with ECM motor
208/60/1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
L2L1
1PB1
2H
1H
1S4
21A
SEE
INSET
B
21E23E24F
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
ARE SHOWN AT 25° C (77° F), AT
ATMOSPHERIC PRESSURE, AT 50% RELATI V E
HUMIDITY, WIT H ALL UTILITIES TURNED OFF,
AND AFTE R A NORMAL SHU TD O W N H AS
OCCURRED.
DASHED LINES INDICATE RECOMMENDED FIELD
2.
WIRING BY OTHERS. FIE L D WIRING TO BE R ATED
FOR 600 VOLTS. DASH ED LINE ENCLOSURE
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. SOL I D
LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE
SCHEMATIC DESIGNATE THE LO CATI ON OF THE
CONTACTS BY LINE NUMBER.
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D
LOCAL REQUIREMENTS.
VERIF Y TEST J UMPER HAS BEEN REMOVED TO
6
PREVEN T CONTROL TIM ING ERRORS .
21B
P10-1 J10-1P7-1
SINGLE
STAGE
ROOM
T'STAT
2F
P20-2
J20-2
A,C
22B
21C
EQUIPMENT
GROUND
1F1
1F
1F2
9A
3F
P20-1
J20-1
9C
MTR-5
3J
MTR-4
GRN
MTR-3
1TB1-1 & 2
21
23A
SEE
INSET
B
SEE
INSET
B
P10-2 J10-2
22C
R G O W Y
1A
2A
P7-3 J7-3
23B
P10-3 J10-3
23C
3B3ACHASSIS
P11-3 J11-3
P11-1 J11-1
P11-2 J11-2
3B2
M
1
COM
TO 1U5 BR D
15 PIN PLUG
SEE INSET B FO R
CONTROL WIRI NG
GROUND
1B
2B
B
23A
SEE
INSET
B
SEE
INSET
24C
26M
P10-4 J10-4
24D
26K
COMN
2CCH-1
WW
1K1
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
D
D
24V
26H26G
24C24B
P7-4 J7-4
B
26H
P10-5 J10-5
12
CONN ECTIO N FOR 2 4VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D
FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP
RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE
11
WHEN CONTROL 1U2 GOES INTO MANUAL LOCKOUT MODE.
CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRE D FO R HARD WIRED DI GITAL THER M O S T A T S.
12
USE COPPER CONDUCTORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED TO ACCEPT
OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CAUSE DAMAGE TO THE
EQUIPMENT.ENDOMMAGER L'ÉQUIPEMENT.
CAUTION
1C3
4B
2B1C1
5B
6E
6B
FIELD INSTALLED
ISOLAT ION VALVE
1TB1-1&2
CLOSE
FOR TWO WIRE N.C VALVE,
DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
208/60/1
1T1
A
23C
2L1
21C
49B47C
N'UTILIS E R QUE DES CONDUCT E URS EN CUIVRE!
LES BORNE S DE L'UNITÉ NE SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CON DUCTEURS.
INDOOR FAN AND CO IL SECTION3
4 WATER COIL SECTION
5
RETURN AND FRES H AIR SECTION
FIELD INSTALLE D DEVICE6
46A
47A
48A
CONTROL OFF
NORMAL / CO MP OFF
ANTI-SHORT CYCLEONOFFFLASH
NORMAL / CO MP ON
BROWNOUT CO NDITIION
SOFT LOCKOUT LP
SOFT LOCKOUT HP
MANUAL LOCKOUT LP
MANUAL LOCK OUT HP
MANUAL LOCKOUT
CONDENSATE LE VEL
COMPRESSOR DI SABLE
LEAD
LED1
LED2
LED3
49A
INSET B
J16
P16
J17P17
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS
PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
CONTROLLER MODE
LEAD COLORS
HIGHSPEED
LOW
,C,E,G,M
1U2
44A
45A
6
1U5
P1
TO BLOWER M OTOR 3B2 15 PIN PLUG
PRECAUCIÓN
DEVICE
DESIGNATION
1C3START ASSIST5
1F1,
1PB1POWER BLOCK
1TB1 CUSTOMER LOW V. TERM BLOCK
1U2
2S1
2L1REVERS I N G VALVE COIL26
2B1S2 LOW PRESSURE SWITCH
3B2EVAP FAN MOTOR
3S335
1U5
LEGEND
DESCRIPTION
FUSE
COMPRESSOR CONTACTOR1K1
CRANKCASE HEATER2CCH-14
CONTROL POWER TR ANSFORMER1T119
COMPR CONTROL MODULE34
COMPRESSOR MOTOR2B1
COMPRESS O R RU N CAPACITOR2B1C18
HIGH PRESSURE CUTOUT2B1S136
FREEZE PROTECTION SWITCH
OVERFLOW SWITCH
ECM CONTROLLER55
G
M
J9-5 P9-5
J9-6 P9-6
98
44B
45B
21E
23E
P15-4
P15-5
21D
23D
ROW3 W2 W1 YYLO BGBK
R
3S3
44C
45C
24F
26M
22B
P15-1
P15-2
P15-3
26L
24E
22D
P2
Unit Wiring
LINE
NUMBER
6,
71F2
6,7,37
3
4FUSED UN IT SWI T CH1S4
21
6,7,8
38
39
15
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS D RAWIN G IS PROPRIETARY AND
CONTENTS DISCLOSE D T O OUTSI DE
CONSENT OF THE TRAN E C OMPANY
PARTIE S WITHOUT THE WR I T TEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
SCHEMA TIC DIAGRA M
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
WSHP-SVX10B-EN33
Page 34
Warranty
Standard Warranty
The standard water-source heat pump warranty isTrane’s
parts-only warranty, running 12-months from startup, not
to exceed 18-months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth
year warranty.The time starts at the end of standard 1-year
coverage through the fifth year.
These extended warranties apply only to new equipment
installed in domesticTrane Commercial Systems Group
sales territories and must be ordered prior to start-up.
34WSHP-SVX10B-EN
Page 35
Page 36
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of
advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit
www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.