Trane WSHP Installation and Maintenance Manual

Page 1
Installation, Operation, and Maintenance
Axiom™ High Efficiency Vertical Stack — GET
¾-3Tons-60Hz
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
November 2013
WSHP-SVX10B-EN
Page 2

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note thatwarnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potentialhazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions. Read this manual thoroughlybefore operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non­approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
WARNING
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
© 2013Trane All rights reserved WSHP-SVX10B-EN
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal ProtectiveEquipment (PPE) recommended for the work being undertaken.
ALWAYSrefer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Page 3
Revision Summary
WSHP-SVX10B-EN (15 November 2013)
WPRD Chassis Model Number change
WSHP-SVX10B-EN (18 June 2013)
Add ECM motor
Trademarks
Trane and theTrane logo are trademarks or registered
trademarks ofTrane in the United States and other countries.Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions and Notices
WSHP-SVX10B-EN 3
Page 4
Table of Contents
Model Number Descriptions .............. 5
General Information ..................... 7
Pre-Installation .......................... 8
Dimensions and Weights ................. 9
Installation ............................. 12
Electrical Data .......................... 21
Pre-Start-up ............................ 22
Checklist ............................ 22
Initial Unit Start-up ................... 22
Operating Pressures .................... 23
Start-up ................................ 26
Maintenance ........................... 27
Troubleshooting ........................ 28
Unit Wiring ............................ 30
Warranty ............................... 34
4 WSHP-SVX10B-EN
Page 5

Model Number Descriptions

Vertical High-Rise Cabinet WSHP
Digits 1-3: Unit Configuration
GET = High Efficiency Vertical High Rise
Heat Pump
Digit 4: Development Sequence
E = R-410A
Digits 5-7: Nominal Size (Tons)
009=¾Tons 012=1Tons 015=1¼Tons 018=1½Tons 024 = 2Tons 036 = 3Tons
Digit 8: Voltage (Volts/Hz/Phase)
1 = 208/60/1 2 = 230/60/1 7 = 265/60/1
Digit 9: Heat Exchanger
1 = Copper Water Coil 2 = Cupro-Nickel Water Coil 3 = Copper Water Coil with Isolation
Valve and Low Flow Control
4 = Cupro- Nickel Water Coil with
Isolation Valve and Low Flow Control
5 = Copper Water Coil with Isolation
Valve and High Flow Control
6 = Cupro-Nickel Water Coil with Isolation
Valve and High Flow Control
Digit 10: Current Design Sequence
Digit 11: Refrigeration Circuit
0 = Heating and Cooling Circuit
Digit 12: Blower Configuration
1 = Free Discharge - PSC motor 2 = Ducted Discharge - PSC motor 3 = Free Discharge w/1" Flange -
PSC motor
4 = Free Discharge w/3" Flange -
PSC motor 5 = ECM motor w/o flange 6 = ECM motor w/1" flange 7 = ECM motor w/3" flange 8 = Chassis only/No motor (ECM Control) 9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
A = 20° freezestat B = 35° freezestat
Digit 14: Open Digit
0 = Open S = Special
Digit 15: Supply Air
Arrangement
0 = No Supply Air Arrangement 1 = Back and Front Supply Air 2 = Back and Left Supply Air 3 = Back and Right Supply Air 4 = Front and Left Supply Air 5 = Front and Right Supply Air 6 = Left and Right Supply Air 7 = Back, Front and Right Supply Air 8 = Back, Front and Left Supply Air 9 = Front, Right and Left Supply Air B = Back Supply Air L = Left Supply Air R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air
Arrangement
0 = No Return Air Door (Field Provided) 1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry
2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
D = Deluxe 24V Controls C =Tracer™ ZN510 Controls
Digit 18: Thermostat Sensor Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0 = No Fault Sensors 1 = Condensate Overflow Sensor 2 = Filter MaintenanceTimer 3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted Disconnect
0 = No Unit Mounted Switch C =Toggle Switch Only D =Toggle Switch with Fuses
Digit 24: Filter Type
1 = 1-inchThrowaway Filter
Digit 25: Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digit 26: Factory Configuration
3 = R-410A Cabinet
Digit 27: Paint Color
8 = Polar White
Digit 28: Outside Air Option
0 = No Outside Air
Digit 29: Piping Arrangement
B = Back Riser Location L = Left Hand Riser Location R = Right Hand Riser Location
Digit 30: Riser Type
0 = No Riser L =Type L Riser M=Type M Riser
Digit 31: Supply Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2 Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
Digit 32: Return Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2" Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
Digit 33: Condensate Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2" Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
WSHP-SVX10B-EN 5
Page 6
Model Number Descriptions
Digit 34, 35, 36: Riser Length
000 = No Riser 096 = 96" Riser Length 097 = 97" Riser Length 098 = 98" Riser Length 099 = 99" Riser Length 100 = 100" Riser Length 101 = 101" Riser Length 102 = 102" Riser Length 103 = 103" Riser Length 104 = 104" Riser Length 105 = 105" Riser Length 106 = 106" Riser Length 107 = 107" Riser Length 108 = 108" Riser Length 109 = 109" Riser Length 110 = 110" Riser Length 111 = 111" Riser Length 112 = 112" Riser Length 113 = 113" Riser Length 114 = 114" Riser Length 115 = 115" Riser Length 116 = 116" Riser Length 117 = 117" Riser Length 118 = 118" Riser Length 119 = 119" Riser Length 120 = 120" Riser Length
Vertical High-Rise Chassis WSHP
Digits 1-3: Unit Configuration
GET = High Efficiency Vertical High Rise Heat Pump (cabinet with blower/motor)
Digit 4: Development Sequence
E = R-410A
Digits 5-7: Nominal Size (Tons)
009=¾Tons 012=1Tons 015=1¼Tons 018=1½Tons 024 = 2Tons 036 = 3Tons
Digit 8: Voltage (Volts/Hz/Phase)
1 = 208/60/1 2 = 230/60/1 7 = 265/60/1
Digit 9: Heat Exchanger
1 = Copper Water Coil 2 = Cupro-Nickel Water Coil 3 = Copper Water Coil with Isolation
Valve and Low Flow Control
4 = Cupro- Nickel Water Coil with Isolation
Valve and Low Flow Control
5 = Copper Water Coil with Isolation
Valve and High Flow Control
6 = Cupro-Nickel Water Coil with Isolation
Valve and High Flow Control
Digit 10: Current Design Sequence
Digit 11: Refrigeration Circuit
0 = Heating and Cooling Circuit
Digit 12: Blower Configuration
1 = Free Discharge - PSC motor 2 = Ducted Discharge - PSC motor 3 = Free Discharge w/1" Flange -
PSC motor
4 = Free Discharge w/3" Flange -
PSC motor 5 = ECM motor w/o flange 6 = ECM motor w/1" flange 7 = ECM motor w/3" flange 8 = Chassis only/No motor (ECM Control) 9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
0 = None or Standard
A = 20° Freezestat
B = 35° Freezestat
Digit 14: Open Digit
0 = Open
Digit 15: Supply Air
Arrangement
0 = No Supply Air Arrangement 1 = Back and Front Supply Air 2 = Back and Left Supply Air 3 = Back and Right Supply Air 4 = Front and Left Supply Air 5 = Front and Right Supply Air 6 = Left and Right Supply Air 7 = Back, Front and Right Supply Air 8 = Back, Front and Left Supply Air 9 = Front, Right and Left Supply Air B = Back Supply Air L = Left Supply Air R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air
Arrangement
0 = No Door (Chassis Only) 1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry 2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
0 = Basic Controls for WPRD Retrofit
Chassis D = Deluxe 24V Controls C =Tracer™ ZN510 Controls
Digit 18: Thermostat Sensor Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0= No Fault Sensors 1 = Condensate Overflow Sensor 2 = Filter Maintenance Timer 3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted Disconnect
0 = No Unit Mounted Switch C = Switch Only D = Switch with Fuses
Digit 24: Filter Type
1 = 1-inchThrowaway Filter
Digit 25: Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digit 26: Factory Configuration
2 = R-410A Chassis R = WPRD Retrofit Chassis
Digit 27: Paint Color
8 = Polar White
Digit 28: Outside Air Option
0 = No Outside Air
Digit 29: Piping Arrangement
B = Back Riser Location L = Left Hand Riser Location R = Right Hand Riser Location
Digit 30: Riser Type
0 = No Riser (Chassis Only)
Digit 31: Supply Riser
0 = No Riser (Chassis Only)
Digit 32: Return Riser
0 = No Riser (Chassis Only)
Digit 33: Condensate Riser
0 = No Riser (Chassis Only)
Digit 34, 35, 36: Riser Length
000 = No Riser (Chassis Only)
6 WSHP-SVX10B-EN
Page 7

General Information

Blower/Motor
The blower and motor is located inside the unit cabinet. The blower and motor may be removed from the cabinet
through the chassis opening. After removing the chassis, the blower assembly is strapped into the unit cabinet through a single metal, flexible bracket. We refer to this bracket as a housing belly bracket. After detaching one screw at the bottom/front edge of the bracket, the housing and motor are free to be lifted from the fan deck.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Controls
A 75 VA transformer is factory supplied on this unit configuration. See wiring diagram on chassis access panel for field wiring connection to the 24V mechanical thermostat.
Deluxe 24V Controls
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board.The
Trane microprocessor board is factory wired to a terminal
strip to provide all necessary terminals for field connection.The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, unit safety control, diagnostics and a generic relay (which may be available for field use). See
p. 14 for diagnostic information.
Power wiring is made at the contactor.The wiring is fed through the left or right conduittube, and intothe cabinet’s control box (contactor).
Schrader Connections
Connections for the low and high side of the refrigeration system are located conveniently on the chassis’ front beneath a sheet metal plate.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.
Unit Nameplate
The unit nameplate is located at the front of the unit. It
includes the unit model number, serial number, electrical characteristics,refrigerant charge, and otherpertinent unit data.
Water Connections
½" or ¾" water connections are located on the chassis’s upper section and clearly labeled for water-in/out hose to riser hook-up.
Water-to-Refrigerant Coils
The co-axial water-to-refrigerant heat exchanger for the ¾
ton through 3 ton equipment is constructed of copper or cupro-nickel (option) for the water section and stainless steel for the refrigeration section.
The heat exchanger is leak tested to assure there is no
cross leakage between the water and refrigerant gas.
ZN510 Controls
Units incorporating the ZN510 control option design will include a digital LonTalk™ certified control board.The control board will support such options as: random start delay, heating/cooling status,occupied/unoccupied mode and fan/filter status.
Power wiring is made at the contactor.The wiring is fed through the left or right conduittube, and intothe cabinet’s control box (contactor). See manual WSHP-IOP-2 for diagnostic information.
Sound Attenuation
Sound attenuation is applied as a standard feature in the product design.The enhanced reduction package includes a heavy gage base plate, and gasket/insulation around the compressor enclosure.
An optional deluxe sound reduction package is also available. It includes a heavy gage base plate, gasket and insulation around the compressor enclosure, and vibration isolation between the chassis and cabinet. An additional dampening treatment is applied around the compressor enclosure to achieve greater acoustical reductions.
WSHP-SVX10B-EN 7
Page 8

Pre-Installation

WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers could result in respiratory, skin or eye irritation.

Jobsite Inspection

Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the billof lading is signed at the jobsite, the unit(s) are now the property of the SOLDTO party and future freight claims MAY NOT be accepted by the freight company.
4. Verify that the refrigerant charge has been retained during shipment by use of gauges. Schrader taps are located external to the cabinet on the ¾-3 ton equipment.
5. After assuring that charge has been retained, reinstall the schrader caps to assure that refrigerant leakage does not occur.

Jobsite Storage

NOTICE:
Microbial Growth!
Wet interior unit insulation can become an
amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, the insulation should be removed and replaced prior to operating the system.
This unit is intended for indoor useonly.To protect the unit
from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unitshould be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisionsfor continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growthwhich has been determined to be a cause of odors and serious health related indoor air quality problems.
4. Store refrigeration units (chassis) units in the normal UP orientation to maintain oil in the compressor. Cabinet configurations may be stored as crated.
5. Do not stack units.
8 WSHP-SVX10B-EN
Page 9

Dimensions and Weights

WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Table 1. Unit weights
Size
009 135 115 012 135 115 015 175 150 018 175 150 024 225 195 036 225 195
009 88 78 012 107 97 015 112 102 018 117 107 024 174 164 036 190 180
Shipping weight with
pallet (lb)
Cabinet
Chassis
Shipping weight
without pallet (lb)

Unit Location and Clearances

Locate the unit in an indoor area.The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and technician safety.The unit chassis should be easily removed from the cabinet in all applications.There must be enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, and electrical connection(s). Local and national codes should be followed in providing electrical power connections.
Figure 1. Mechanical clearances
RSD
ALLOW 36" (914 mm) AT UNIT FRONT FOR CHASSIS REMOVAL
WSHP-SVX10B-EN 9
Page 10
Dimensions and Weights
Figure 2. GET 009-036
Table 2. GET 009-036
GET A B C D E F
009, 012
015-018
024-036
16¼" (413)
18"
(457)
24"
(610)
10 WSHP-SVX10B-EN
16¼" (413)
20"
(508)
24"
(610)
8 1/8"
(206)
10"
(254)
12"
(305)
39 1/8"
(994)
40 5/8"
(1032)
49 5/8"
(1260)
14¾" (375)¾"(19)
18¾" (476)¾"(19)
22 5/8"
(575)¾"(19)
Page 11
Dimensions and Weights

Return Air (hinged) Acoustical Door

The hinged acousticaldoor is recessedinto the wall so that
the door is flush with the surface of the wall.
The opening through the wall for the door assembly must
be centered with the return-air opening of the unit cabinet. For full installing instructions of the return-air acoustical door, see p. 14.
Figure 3. Return air (hinged) acoustical door
3 1/2” ±3/8”
SHEETROCK
A
RETURN AIR OPENING
FLANGE ON CABINET
B
RETURN AIR
DOOR FLANGE
RETURN AIR OPENING
FLANGE ON CABINET
Table 3. Return air hinged acoustical door
Unit Size A B
2“ X 4” STUD
1“ X 1” CLOSED CELL INSULATION
CABINET
1“ X 1” CLOSED CELL INSULATION
1 1/4”
+1/2”/-0”
009 012
015 018
024 036
A
19¼” (489)
23¼” (591)
27 1/8”
(689)
44 1/8”
(1121)
45¼”
(1149)
54 5/8”
(1387)
SHEETROCK
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR
DOOR FRAME
SHEETROCK
FLOOR
SHEET ROCK
OPENING
3 1/2” ±3/8”
K
2 X 4 STUD
RETURN-AIR OPENING FLANGE ON CABINET
RETURN-AIR OPENING FLANGE ON CABINET
2 1/4“
4 5/8“
CABINET
SHEETROCK
Note: Finished wall and framing should not touch the unit cabinetry.
B
5“
2“ X 4” STUD
CABINET
1 1/4”
+1/2”/-0”
TOP VIEW
1 1/2” X 2 3/8”
3 1/2” ±3/8”
SIDE VIEW
WSHP-SVX10B-EN 11
Page 12

Installation

General Installation Checks

The checklist below is a summary of the steps required to
successfully install a unit.This checklist is intended to acquaint the installing personnel with procedures required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual.
1. Remove packaging and inspect the unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representation.
Note: The unit cabinet is packaged in a wooden crate. A
pry bar and/or hammer will be needed for packaging removal.
Note: The chassis sits inside a cardboard tray with an
upper box for protection.Typically four chassis will be shrink-wrapped to a single pallet.
2. Verify the correct model, options and voltage from the unit nameplate.
3. Verify the installation location of the unit will provide the required clearance for proper operation.
4. Remove refrigeration access panel and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.

Main Electrical

3. Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect switch and to the unit power block (1TB1) in the unit’s cabinet control box for equipment.
4. Install proper grounding wires to an earth ground.
Note: All field-installed wiring must comply with NEC
and applicable local codes.

Low VoltageWiring (AC & DC) Requirements

Connect properly sized control wiring to the proper termination points between the field supplied thermostat and the terminal plug in the equipment’s junction box.

Unit Placement

WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Figure 4. Stacking illustration
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
1. Verify the power supply complies with the unit nameplate specifications.
2. Inspect all control panel components; tighten any loose connections.
FLOOR
3" SWAGE
FLOOR
12 WSHP-SVX10B-EN
Page 13
Installation
If unit cabinet assembly includes factory provided risers, and "no" field provided between-the-floor riser extensions, please move to Step 1.
Note: Risers are designed to accommodate a maximum
of 1½" to 3" expansion and contraction. If the total calculated riser expansion exceeds 3", expansion devices must be field provided.
If unit cabinet assembly includes factory provided risers and field provided between-the-floor riser extensions are required, install the extensions before installing the cabinet.
1. Install drain valve, shut-off/balancing valves, flow indicators and drain at the base of each supply and return riser to enable system flushing at start-up, balancing and service/maintenance.
2. Lift cabinet into space while aligning it into the 3"swage of the riser below.
Note: Take extra care as not to scrape or dent risers
during positioning.The riser should fall approximately 2" into the 3" swage.This will allow for the variation in floor-to-floor dimensions, and keep the riser joints from bottoming out.
3. Level the cabinet.
4. Plumb risers in two planes to assure proper unit operation and condensate drainage.
5. Anchor all units into place.
6. For field provided risers, center the supply/return stubouts into the unit expansion slots.The stubouts should be perpendicular to the cabinet panel.
7. Verify all risers are vertical and that they penetrate the swaged joint at least 1". Riser should not be allowed to bottom out.
8. Braze riser joints. Softsolder or low-temperature alloys should not be used in this application.
9. If risers are field provided, it is recommended that the risers be anchored to the building structure with a minimum of one contact point. For expansion and contraction reasons, do not fasten risers rigidly to the building.
10. Seal access holes made through the cabinet for piping with suitable material to help eliminate air leakage.
11. S e e “Cleaning and Flushing theWater Loop,” p. 16 for system flushing.
Note: Remove shipping straps from risers.

Water Connection

For vibration isolation, it is recommended that flexible steel braided hoses be installed instead of hard piping between the vertical risers and the unit chassis.
Trane offers 4-types of hose kit variations:
Stainless steel braided flexible hose with manual shut­off (ball) valves
Stainless steel braided flexible hose with manual deluxe shut-off (ball) valves
Stainless steel braided flexible hose with manual circuit-setter valve
Stainless steel braided flexible hose with automatic balancing valve
Additional accessories, such as a strainer are recommended for use to eliminate contaminants from entering the co-axial water-to-refrigerant heat exchangers.
Note: Hoses should be no longer than 24”

Field Installed Power Wiring

WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Verify that the power supply available is compatible with
the unit’s nameplate. Use only copper conductors to connect the power supply to the unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
WSHP-SVX10B-EN 13
Page 14
Installation

Main Unit Power Wiring

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
A field supplied disconnect switch must be installed at or near the unit in accordance with the NationalElectric Code (NEC latest edition).
Location of the applicable electric service entrance for HIGH (line voltage) may be found in Figure 5, p. 14.
Figure 5. Power wire entrance
Route power wire to the cabinet control box through the factory installed conduit at the top of the unit cabinetry.Thehigh voltage connection ismade at the1PB1 power block in the cabinet control box. Refer to the customer connection diagram that is shipped with the unit for specific termination points.
Provide proper grounding for the unit in accordance with the local and national codes.

Drywall Installation

Before installing drywallaround cabinet, coverthe cabinet supply and return openings with plastic or cardboard to help prevent dust or construction debris from reaching unit components. Warranties will be voided if paint or foreign debris is allowed to contaminate internal unit components.
The location of the drywall may be dependent upon the
type of return air access design.
For units containing a field provided return air access assembly, the contractor must calculate location of drywall to allow for frame mounting.
Units Utilizing Hinged Acoustic Door
Assembly
Figure 6. Mock-up of stud placement
1. Locate the side studs a minimum of 1¼” and a maximum of 1 3/8” from the cabinet to the side of the stud.
This critical dimension,
combined with "distance between studs" is used to determine the side-to-side opening for thedoor,dimension A.The distances provided in the table are a "minimum" dimension. Allow 3½” from the front of the cabinet to the sheet rock surface, Figure 7, p. 15 - top view, Figure 6, p. 14 - mock-up of stud placement.
2. The height of thedoor assembly must be positionedto recess the door 2¼” from the cabinet’s return-air opening, Figure 7, p. 15 - side view blow-up.

Control PowerTransformer

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury
The 24V control power transformers are to be used only
with the accessories called out in this manual.
Transformers rated greater than 75VA are equipped with
internal circuit breakers. If a circuit breaker trips, turn OFF all power to the unit before attempting to reset it.
The transformer is located in the chassis control box.
14 WSHP-SVX10B-EN
Page 15
Installation
Figure 7. Drywall installation for hinged acoustic door
3 1/2” ±3/8”
2“ X 4” STUD
SHEETROCK
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR
DOOR FRAME
SHEETROCK
1 1/2” X 2 3/8”
SHEET ROCK
OPENING
3 1/2” ±3/8”
K
FLOOR
3 1/2” ±3/8”
A
B
2 X 4 STUD
RETURN-AIR OPENING FLANGE ON CABINET
RETURN-AIR OPENING FLANGE ON CABINET
2 1/4“
CABINET
RETURN AIR OPENING
FLANGE ON CABINET
RETURN AIR OPENING
FLANGE ON CABINET
5“
4 5/8“
B
SHEETROCK
RETURN AIR
DOOR FLANGE
SHEETROCK
Note: Finished wall and framing should not touch the unit cabinetry.
CABINET
SIDE VIEW
1“ X 1” CLOSED CELL INSULATION
CABINET
1“ X 1” CLOSED CELL INSULATION
2“ X 4” STUD
1 1/4”
+1/2”/-0”
1 1/4”
+1/2”/-0”
TOP VIEW
A
Note: When placing the sheet rock panel, make certain
the opening for the door is centered with the return-air opening in the cabinet (±1/8").
Figure 8. Door opening
5. Secure the door frame to the side studs using the holes located in the door frame and field provided screws.
Note: If the gap between the door
frame, and the side stud is over 1/16-inch, place a shim in between the door frame and the stud to prevent the door frame from bending/denting.
Figure 9. Air panel gasket
6. Place the air panel into the door opening.The gasket on the back side of the air panel should seal around the coil perimeter.
Figure 10. Secure to door frame
7. After verifying that the air panel gasket is sealed to the coil, secure the air panel to the door frame using the slotslocated on the sides of the air panel.
3. Locate dimensionsA and B forsheet rock opening size. The position of the sheet rock opening must be
centered side-to-side with the return-air opening in the cabinet. Ensure the bottom of the sheet rock opening is 2¼” below the return-air opening in the cabinet.This allows the door recess to rest on the bottom of the sheet rock opening for proper vertical placement ofthe door.
Table 4. Sheet rock opening size
Unit Size A B
09
012 015
018 024
036
19¼” (489)
23¼” (591)
27 1/8”
(689)
44 1/8”
(1121)
45¼”
(1149)
54 5/8”
(1387)
4. Place the door frame into the sheet rock opening. A
positive seal is critical between the back of the door frame and the front of the cabinet. Ensure that the
8. Install Filter.
9. Vacuumall dust and constructiondebris from unit after cutting out supply/return openings.

Supply Air Ductwork

A 2" (50.8 mm) duct flange may be required to help
eliminate supply air from recirculating back into the return air, air-to-refrigerant coil prior to discharging into the space.
Equipment containing a top discharge, ducted design: install field ductwork to the unit providing a water tight flexible connector at the unit.This helps prevent operating sounds from transmitting through the ductwork. Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to help reduce static pressure.
gasket material seals properly.
WSHP-SVX10B-EN 15
Page 16
Installation

Chassis Installation

Figure 11. Shipping bolts (see arrows)
1. Remove three 18-inch bolts on the chassis and discard.
2. Rotate the triangular metal plate tocover the bolt holes in the chassis. Secure with two sheet metal screws.
(a) Not all units will include shipping bolts.
Figure 12. Bracket removal for deluxe sound package
3. Remove one shipping bracket (one on each side) attached to the chassisslide rails and discard.
Note: Remove this
bracket only if the deluxe sound package design is selected.
4. Connect water coil pipe to the system riser with a flexible steel hose assembly.
5. Verify that the shut-off/balancing valve in the return line/supply line are closed.
6. Place shut-off valves in appropriate location (see sticker on the equipment for best placement recommendation) to allowchassisto slide easily in/out of unit cabinet.
7. Flush system. See “Cleaning and Flushing the Water
Loop,” p. 16,” for flushing instructions.
8. Open the unit water valves and check piping for leaks.
9. Connect electrical to unit chassis via the quick connect mating plugs.
Note: Four plugs are included (motor, optional
condensate overflow, power and thermostat).
Figure 13. Install chassis centered
10. Slide chassis into the cabinet. Center the chassis left to right to minimize sound transmission.
11. Verify unit’s air filter has shipped with the cabinet.
12. Install cabinet’s front cover to the hinged door.
Important: Ensure the gasket material creates a
positive seal around the entire coil to avoid coil bypass. If a field supplied door is used, ensure the front cover is attached to the building structure and not the unit cabinet.

Supply Grille Installation

See Table 5, p. 16 for supply air dimensions.
Table 5. Supply air opening size
Top
Single Grille
GET
100% CFM
009, 012 14”W x 14”H 10”W x 6”H 015, 018 16”Wx12”H 14”Wx12”H 12”Wx8”H 16”Wx14”H
024 22”Wx18”H 14”Wx12”H 12”Wx8”H 16”Wx14”H 036
Not
Recommended
Two Grille
50% CFM
16”Wx14”H 14”Wx12”H 17”Wx17”H
Three Grille
33% CFM
Not
Recommended
Discharge
up to
100% CFM
14”W x 10”H
1. Install the supply grille(s) into the cabinet discharge opening. Ensure there are no air gaps between the cabinet supply air and the grille.This helps prevent recirculation of supply air into the return air opening behind the drywall.
2. Secure grille(s) into the drywall via two screws.

Cleaning and Flushing the Water Loop

After the piping system is complete, the flexible hose
connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). An extra pipe may be necessary to connect the hose kits. See “Using Antifreeze,” p. 17 for antifreeze/ water mixture by volume.
1. Water circulation system should be filled with clean water using the water make up connections.
Note: Air vents should be opened during filling.
2. With the air vents closed, start the circulating pump and then crack the air vents to bleed off the trapped air, assuring circulation through all components of the system.
Note: Make up water must be available to the system to
replace the volume formerly occupied by the air that is bled off.
Note: System water pressure needs to be relieved prior to
opening system.
3. With theair vented and the water circulating, the entire system should be checked for leaks with repairs made as required.
4. Operate the supplementary heat system making checks per manufacturer’s instructions. During this operation, visual checks should be made for leaks that
16 WSHP-SVX10B-EN
Page 17
Installation
may have occurred due to increased heat. Repair as required.
5. Open the system at the lowest point for the initial blow down (making sure the make up water is equal to the water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 hours.
6. Shut down pumps and supplementary heat system. Reconnect the hoses placing the water-to-refrigerant heat exchanger in the water circulating system.
Note: Vents should be open when the pumps and
supplementary heat system are shut down.
Figure 14. Flushing the water loop
CONNECTION
HOSE
WATER-SOURCE
HEAT PUMP
CIRCULATING
TEMPORARY
CONNECTION
FOR SYSTEM
FLUSHING
PUMP

Low VoltageWiring

Factory ordered thermostats and zone sensors are pre­wired with a quick connecting plug.
1. After installing the cabinet assembly, simply plug the male portion of thermostat/zone sensor plug into the female portion of the plug located inside the unit’s junction box.
2. Mount the thermostat or zone sensor on the finished drywall.
Thermostat/zone sensor connection is shown inFigure 15,
p. 17.
Low VoltageWiring for Field Provided
Thermostats/Zone Sensors
Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/conductor for the length of the run.
NOTICE:
Component Failure!
Resistance in excess of 3-ohms per conductor could result in component failure due to insufficient AC voltage supply.
GROUND-LOOP
OR
COOLING TOWER/BOILER

Using Antifreeze

In areas of the countrywhere entering water temperatures drop below 45°F or where piping is being run through areas subject to freezing, the loop must befreeze protected by using an approved antifreeze solution to prevent the earth loop water from freezing inside the heat exchanger. Methanol and glycols are the most commonly used antifreeze solutions. Consult your geothermal unit supplier for locally approved solutions in your area. Propylene glycol is not recommended in installations where the water temperature are expected to fall below 30°F. At extreme temperatures, the viscosity increases to the point where normal loop circulating pumps may not maintain proper flow. If propylene glycolis the only locally approved solution for anti-freeze, good engineering practices should be used to achieve the desired flow. Calculate the approximate volume of water in the system by using the requirements detailed inTable 8, Water
Volume. Add three gallons to this total to allow for the
water contained in the hose kit and geothermal unit.
Table 6. Antifreeze requirements based on volume
Check all loads and conductors for grounds, shorts, and mis-wiring.
Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
Table 7. 24V AC conductors
Distance from unit
to Control
000-460 feet 18 gauge 461-732 feet 16 gauge
733-1000 feet 14 gauge
Recommended
Wire Size
Figure 15. Zone sensor connection
Six (6) Pin Connector/Harness
Red = 24V
Black = Fan
Orange = RV
• Yellow = Compressor
Blue = Common
Type of
Antifreeze
Methanol
Propylene Glycol
WSHP-SVX10B-EN 17
Minimum Temperature for Freeze
Protection
10°F 15°F 20°F 25°F 30°F
25% 21% 16% 10% 3%
————6%
Page 18
Installation
Table 8. Deluxe controller diagnostic LEDs
Color: Green Color: Red Controller Mode
LED1 LED2 LED3
OFF OFF OFF Control OFF
ON ON ON
FLASH
ON ON
ON
ON
ON ON
OFF OFF Normal/Compressor OFF OFF FLASH Anti-short Cycle OFF ON Normal/Compressor ON
ON OFF Brownout Condition FLASH ON Soft Lockout (low pressure) FLASH FLASH Soft Lockout (high pressure)
ON ON
ON FLASH
FLASH OFF
ON OFF Compressor Disable
Manual Lockout (low
pressure)
Manual Lockout (high
pressure)
Manual Lockout (condensate
overflow)

PSC Blower Motor Speed Retrofit

PSC motors installed in the unit have multiple speed configurations.To modify the rpm of the motor, the following steps may be followed.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Figure 16. ECM control board and dip switch setting
Dip Switch to select profile
123456 78
On
Off
12345678
On
Off
1 2 3 45678
On
Off
12345678
On
Off
Profile A
Profile B
Profile C
Profile D
1. Locate the blower motor relay inside the chassis control box.
2. Remove the undesired speed tap.
3. Select desired speed tap wire by using information from Table 9, p. 18.
4. Connect desired tap wire to the 1K4 relay at spade 4.
5. Reconnect power to the unit.
Table 9. Lead change
Lead Colors
Lead Speed High Low
Blower
1G 9A
Note: Units with the optional ECM motor are shipped
from the factory on Profile B.
To adjust the CFM, disconnect the power to the unit. Set
the DIP switch located in the control box to the desired profile setting. See Figure 16. Connect the power to the unit. If the power is not disconnected when the DIP switch is set, the motor will not be programmed to the new setting.
Profile A = 110% of rated air flow
ProfileB=100%ofrated air flow
Profile C = 90% of rated air flow
Profile D = 805 of rated air flow

ECM Motor CFM Settings

To adjust the CFM, disconnect the power to the unit. Set
the DIP switch located in the control box to the desired profile setting. See Figure 16. Connect the power to the unit. If ht epower is not disconnected when the DIP switch is set, th emotor will not be programmed ot the new setting.
18 WSHP-SVX10B-EN
Page 19
Installation
Table 10. PSC blower motor external static pressure without return air door (RAD) with filter
External Static Pressure (in. of wg)
Model
Speed
Ducted
No
GET 009
GET 012
GET 015
GET 018
GET 024
GET 036
Model NoSpeed
GET 015
GET 018
GET 024
GET 036
Model NoSpeed
GET 036
(a)The NO “Ducted” option is for non-ducted (free return) units. Units specified as “non-ducted” (free return) are factory wired to low-speed. Units specified
as “ducted” are factory wired to high-speed.
(a)
Tap
High Yes 408 421 0.108 388 0.107 354 0.106 320 0.104 283 0.103 244 0.102
Low Yes 355 0.073 332 0.072 307 0.070 278 0.068 245 0.067
High No 357 0.073 333 0.071 309 0.070 282 0.069 253 0.067
Low No 272 307 0.061 297 0.060 280 0.059 258 0.058
High Yes 453 453 0.140 433 0.137 412 0.134 390 0.130 367 0.127 342 0.124 316 0.121 288 0.118
Low Yes 401 0.112 383 0.109 362 0.106 340 0.103 318 0.100 295 0.097
High No 418 0.125 400 0.122 379 0.120 356 0.117 332 0.113 309 0.110 286 0.107
Low No 304 345 0.097 331 0.095 313 0.092 292 0.090
High Yes 648 652 0.191 634 0.187 616 0.183 598 0.179 579 0.175 558 0.170
Low Yes 560 0.155 539 0.153 523 0.152 511 0.149 499 0.146 487 0.143 472 0.139 455 0.135
High No 553 0.169 538 0.167 524 0.165 510 0.162 496 0.159 481 0.155 464 0.151 444 0.147
Low No 432 445 0.135 433 0.135 422 0.134
High Yes 780 785 0.330
Low Yes 665 0.253 644 0.249 625 0.246 608 0.242 592 0.237 575 0.232 556 0.227 537 0.221
High No 696 0.361 675 0.354 654 0.348 632 0.342 610 0.336 588 0.330 566 0.324 544 0.318
Low No 520 544 0.271 526 0.266 506 0.262
High Yes 984 988 0.402 955 0.392 920 0.382
Low Yes 908 0.344 895 0.335 876 0.327 854 0.318 829 0.310 803 0.301 778 0.293 754 0.285
High No 850 0.317 827 0.310 806 0.303 787 0.297 768 0.291 750 0.286 730 0.280 710 0.274
Low No 656 799 0.292 781 0.286 764 0.280 746 0.275 727 0.269 709 0.264 690 0.258 671 0.252
High Yes 1404 1420 0.686 1396 0.674
Low Yes 1303 0.651 1293 0.638 1282 0.625 1270 0.614 1256 0.603 1240 0.592 1222 0.582 1202 0.572
High No 1330 0.642 1304 0.630 1277 0.618 1248 0.606 1219 0.593 1188 0.581 1155 0.568 1122 0.555
Low No 936 1059 0.523 1051 0.516 1042 0.510 1033 0.503 1022 0.496 1011 0.488 998 0.480 984 0.472
Tap
High Yes 648 535 0.165 510 0.160 480 0.154 445 0.148 404 0.141
Low Yes 433 0.130 405 0.125
High No 421 0.142
Low No 432
High Yes 780 758 0.323 729 0.317 697 0.311 661 0.305 620 0.300 573 0.295 518 0.291
Low Yes 517 0.215
High No 521 0.312 497 0.305
Low No 520
High Yes 984 884 0.371 847 0.359 810 0.348 774 0.336 739 0.324 706 0.312 676 0.299 649 0.287
Low Yes 732 0.277 712 0.268 693 0.260 675 0.251 658 0.243 641 0.234
High No 689 0.267 666 0.260 642 0.251
Low No 656 651 0.246
High Yes 1404 1371 0.662 1346 0.650 1320 0.638 1293 0.625 1265 0.613 1236 0.601 1206 0.588 1175 0.575
Low Yes 1181 0.562 1160 0.553 1138 0.543 1117 0.533 1097 0.522 1076 0.511 1055 0.498 1031 0.486
High No 1086 0.542 1048 0.528 1007 0.515 965 0.501 919 0.487
Low No 936 967 0.464 949 0.454 927 0.444
Tap
High Yes 1404 1142 0.563 1107 0.550 1071 0.536 1032 0.523 991 0.509 947 0.495 900 0.481
Low Yes 1003 0.472 967 0.456 919 0.440
High No
Low No 936
Unit
Ducted
Unit
Ducted Unit
CFM 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Max Min CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW
External Static Pressure (in. of wg)
CFM 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75
Max Min CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW
External Static Pressure (in. of wg)
CFM 0.80 0.85 0.90 0.95 1.00 1.05 1.10
Max Min CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW
WSHP-SVX10B-EN 19
Page 20
Installation
Table 11. ECM Blower motor external static pressure without return air door (RAD) with filter
External Static Pressure (in. of wg)
Model
GET 009
GET 012
GET 015
GET 018
GET 024
GET 036
Note: The ECM motor is programmed for constant CFM. The CFM is factory set on Profile B.
No.
Speed
Profile
A 374 0.025 0.037 0.050 0.062 0.075 0.087 0.098 0.110 0.121 0.133 0.144 0.155 0.165 0.176 0.176 B 344 0.023 0.035 0.046 0.057 0.068 0.079 0.090 0.100 0.110 0.120 0.130 0.140 0.149 0.159 0.159 C 313 0.021 0.032 0.042 0.052 0.062 0.071 0.081 0.090 0.099 0.108 0.117 0.126 0.134 0.143 0.143 D 285 0.017 0.027 0.036 0.045 0.054 0.063 0.071 0.080 0.088 0.096 0.104 0.112 0.120 0.127 0.127 A 419 0.027 0.042 0.057 0.071 0.086 0.100 0.114 0.128 0.142 0.155 0.168 0.181 0.193 0.206 0.206 B 382 0.025 0.038 0.052 0.065 0.077 0.090 0.103 0.115 0.127 0.139 0.151 0.162 0.173 0.184 0.184 C 342 0.023 0.034 0.046 0.057 0.069 0.080 0.091 0.102 0.112 0.122 0.133 0.142 0.152 0.161 0.161 D 303 0.019 0.029 0.039 0.049 0.059 0.068 0.078 0.087 0.096 0.105 0.114 0.123 0.131 0.139 0.139 A 594 0.062 0.072 0.081 0.090 0.100 0.109 0.119 0.128 0.138 0.148 0.158 0.168 0.179 0.191 0.202 B 540 0.044 0.054 0.064 0.073 0.083 0.092 0.101 0.111 0.121 0.131 0.141 0.151 0.162 0.173 0.185 C 486 0.032 0.042 0.051 0.060 0.069 0.079 0.088 0.097 0.106 0.116 0.126 0.136 0.146 0.157 0.168 D 432 0.025 0.034 0.042 0.051 0.059 0.068 0.076 0.085 0.093 0.102 0.111 0.120 0.130 0.140 0.150 A 712 0.097 0.109 0.121 0.134 0.148 0.163 0.178 0.193 0.208 0.223 0.239 0.253 0.268 0.282 0.282 B 648 0.077 0.087 0.098 0.110 0.123 0.136 0.150 0.163 0.177 0.191 0.205 0.218 0.230 0.242 0.242 C 584 0.056 0.066 0.076 0.087 0.099 0.111 0.123 0.135 0.148 0.160 0.172 0.183 0.194 0.204 0.204 D 522 0.039 0.048 0.058 0.069 0.080 0.091 0.102 0.114 0.125 0.136 0.147 0.157 0.166 0.175 0.175 A 903 0.100 0.118 0.135 0.152 0.168 0.185 0.201 0.216 0.232 0.247 0.261 0.276 0.290 0.303 0.303 B 827 0.081 0.096 0.111 0.125 0.140 0.154 0.168 0.182 0.196 0.209 0.222 0.236 0.248 0.261 0.261 C 746 0.060 0.073 0.085 0.098 0.110 0.123 0.136 0.148 0.161 0.173 0.185 0.198 0.210 0.222 0.222 D 659 0.041 0.052 0.063 0.074 0.085 0.097 0.109 0.121 0.133 0.145 0.157 0.169 0.182 0.194 0.194 A 1293 0.285 0.306 0.328 0.349 0.370 0.392 0.413 0.433 0.454 0.475 0.496 0.516 0.537 0.557 0.557 B 1178 0.214 0.233 0.253 0.272 0.292 0.311 0.330 0.349 0.369 0.388 0.406 0.425 0.444 0.463 0.463 C 1063 0.158 0.175 0.193 0.210 0.227 0.245 0.262 0.279 0.296 0.313 0.331 0.348 0.365 0.382 0.382 D 950 0.117 0.133 0.148 0.163 0.178 0.193 0.208 0.223 0.238 0.254 0.269 0.284 0.299 0.314 0.314
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70
CFM kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Table 12. Pressure drop due to return air door (RAD)
Model No. CFM DP CFM DP CFM DP
GET 009 272 0.04 340 0.05 408 0.08 GET 012 303 0.04 380 0.07 456 0.11 GET 015 432 0.06 540 0.09 648 0.12 GET 018 520 0.08 650 0.12 780 0.16 GET 024 656 0.06 820 0.08 984 0.12 GET 036 936 0.10 1170 0.16 1404 0.23
Note: The pressure drop across the RAD door should be included in the TOTAL ESP when determining airflow and fan motor power usage. If the door is supplied
by another vendor, the pressure drop across that door must be included in the TOTAL ESP when determining airflow and fan motor power usage.
20 WSHP-SVX10B-EN
Page 21

Electrical Data

Table 13. Electrical performance
Model No.
GET 009
GET 012
GET 015
GET 018
GET 024
GET 036
Motor
Option Unit Volts
208/60/1 4.3 3.7 16.0 0.60 1/20 5.23 15
PSC Motor
ECM Motor
PSC Motor
ECM Motor
PSC Motor
ECM Motor
Free
Discharge
PSC Motor
ECM Motor
Ducted
PSC Motor
PSC Motor
ECM Motor
PSC Motor
ECM Motor
230/60/1 4.1 3.5 17.0 0.60 1/20 4.98 15 265/60/1 3.3 2.8 13.0 0.50 1/20 4.00 15 208/60/1 4.3 3.7 16.0 0.55 1/3 5.18 15 230/60/1 4.1 3.5 17.0 0.55 1/3 4.93 15 265/60/1 3.4 2.8 13.0 0.55 1/3 4.05 15 208/60/1 7.0 6.3 30.0 0.70 0.13 8.58 15 230/60/1 7.0 6.3 30.0 0.70 0.13 8.58 15 265/60/1 5.6 5.0 23.0 0.60 0.13 6.85 15 208/60/1 6.9 6.3 30.0 0.60 1/3 8.48 15 230/60/1 6.9 6.3 30.0 0.60 1/3 8.48 15 265/60/1 5.6 5.0 23.0 0.60 1/3 6.85 15 208/60/1 8.6 7.9 36.0 0.70 1/8 10.58 15 230/60/1 8.6 7.9 36.0 0.70 1/8 10.58 15 265/60/1 7.0 6.4 30.0 0.60 1/8 8.60 15 208/60/1 8.5 7.9 36.0 0.60 1/2 10.48 15 230/60/1 8.5 7.9 36.0 0.60 1/2 10.48 15 265/60/1 7.0 6.4 30.0 0.60 1/2 8.60 15 208/60/1 10.3 9.6 42.0 0.70 1/8 12.70 20 230/60/1 10.3 9.6 42.0 0.70 1/8 12.70 20 265/60/1 8.3 7.7 35.0 0.60 1/8 10.23 15 208/60/1 10.2 9.6 42.0 0.60 1/2 12.60 20 230/60/1 10.2 9.6 42.0 0.60 1/2 12.60 20 265/60/1 8.3 7.7 35.0 0.60 1/2 10.23 15 208/60/1 11.3 9.6 42.0 1.70 1/5 13.70 20 230/60/1 11.3 9.6 42.0 1.70 1/5 13.70 20 265/60/1 8.8 7.7 35.0 1.10 1/5 10.73 15 208/60/1 15.7 13.5 58.3 2.20 1/3 19.08 30 230/60/1 15.7 13.5 58.3 2.20 1/3 19.08 30 265/60/1 10.8 9.0 54.0 1.80 1/3 13.05 20 208/60/1 14.5 13.5 58.3 0.95 1/2 17.83 30 230/60/1 14.5 13.5 58.3 0.95 1/2 17.83 30 265/60/1 10.0 9.0 54.0 0.95 1/2 12.20 20 208/60/1 17.7 14.1 77.0 3.60 1/2 21.23 35 230/60/1 17.7 14.1 77.0 3.60 1/2 21.23 35 265/60/1 15.0 12.2 72.0 2.77 1/2 18.02 30 208/60/1 16.1 14.1 77.0 2.00 3/4 19.63 30 230/60/1 16.1 14.1 77.0 2.00 3/4 19.63 30 265/60/1 14.2 12.2 72.0 2.00 3/4 17.25 25
Total
FLA
Comp RLA
(ea)
Comp
LRA
Blower
Motor FLA
Blower
Motor HP
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
WSHP-SVX10B-EN 21
Page 22

Pre-Start-up

Checklist

Before energizing the unit, the following system devices must be checked:
____ Is the high voltage power supply correct and in accordance with the nameplate ratings?
____ Is the field wiring and circuit protection the correct size?
____ Is the low voltage control circuit wiring correct per the unit wiring diagram?
____ Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from the water-to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accordance with the Closed-Loop/ Ground Source Heat Pump Systems Installation Guide).
____ Is vibrationisolation provided? (i.e. unitisolation pad, hose kits)
____ Is unit serviceable? (See “Unit Location and
Clearances,” p. 9.)
____ Are the low/high-side pressure temperature caps secure and in place?
____ Are all the unit access panels secure and in place?
____ Is the thermostat in the OFF position?
____ Is the water flow established and circulating through all the units?
____ Is the duct work (if required) correctly sized, run, taped, insulated and weather proofed with proper unit arrangement?
____ Is the condensate line properly sized, run, trapped and pitched?
____ Does the indoor blower turn freely without rubbing?
____ Has all work been done in accordancewith applicable local and national codes?
____ Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?
____ Are the compressor bolts removed from the chassis?
____ Have the chassis isolation rails been released?
____ Is there a good seal between the front air panel and the coil?
2. Reduce the temperature control setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing
pressure/temperature plugs and comparing to tables contained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9°F-12°F); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
3. Check the cooling refrigerant pressures against values in Table 14, p. 23.
4. Turn the thermostat switch to the OFF position. Unit
should stop running and the reversing valve should de-energize.
5. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
6. Turn the thermostat to the lowest setting. Set the thermostat system switch to the HEAT position.
7. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A
water temperature decrease of approximately 5°F-9°F leaving the heat exchanger should be noted. The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
8. Check the heating refrigerantpressures against values in Table 14, p. 23.
9. Set the thermostat to maintain the desired space temperature.
10. Instruct the owner on system operation.

Initial Unit Start-up

Start-up with deluxe controls is included below:
TM
Note: Start-up for theTracer
found in WSHP-IOP-2.
1. Set the thermostat to the highest position. Set the thermostat system switch toCOOL withthe fan control to AUTO.The compressor should NOT run.
22 WSHP-SVX10B-EN
ZN510 controller may be
Page 23

Operating Pressures

Use the form on p. 26to log systemand unit temperatures during start-up.
GENERAL:There are many variables (airflow, air temperatures) in an air conditioning systemthat will affect operating refrigerant pressures and temperatures.The
on air flow at the rated SCFM, entering air at 80.6°F DB,
66.2 °FWB in cooling, 68°F DB in heating. (+)Heating data with 35°F EWT is based on the use of an anti-freeze solution having a freezing point 20 °F lower than the minimum expected entering temperature.
chart below shows approximate conditions and is based
Table 14. Operating pressures
Operating Data
Cooling Heating
Entering
Model
GETE009 35 1.80 — 93-107 298-379 6-8 11-15 GETE009 35 2.25 — 96-111 300-382 5-6 12-15 GETE009 45 1.80 138-159 177-226 12-15 11-15 111-128 315-401 6-8 13-17 GETE009 45 2.25 137-157 171-217 9-12 12-15 114-131 316-403 5-7 14-18 GETE009 55 1.80 140-161 203-258 11-14 11-14 129-149 331-421 8-10 15-19 GETE009 55 2.25 139-160 197-250 9-12 12-15 133-153 332-423 6-8 16-20 GETE009 68 1.80 143-164 244-310 11-14 11-14 156-179 354-450 9-11 18-22 GETE009 68 2.25 142-164 237-301 9-11 12-15 161-185 357-454 7-9 18-23 GETE009 75 1.80 144-166 269-342 11-14 11-14 172-197 367-467 10-12 19-24 GETE009 75 2.25 144-165 262-333 9-11 11-15 177-204 372-473 8-10 19-25 GETE009 86 1.80 146-168 313-399 11-14 11-14 199-229 389-496 11-14 21-26 GETE009 86 2.25 146-168 306-389 8-11 11-15 206-237 394-501 9-12 21-27 GETE009 95 1.80 148-170 355-452 11-13 11-14 — GETE009 95 2.25 147-170 347-441 8-11 11-14 — GETE012 35 2.40 — 91-104 279-355 6-8 19-24 GETE012 35 3.00 — 94-108 281-358 4-6 19-24 GETE012 45 2.40 144-166 170-216 11-14 18-23 109-125 294-374 6-8 21-27 GETE012 45 3.00 144-166 164-208 9-11 19-24 111-128 295-375 5-6 21-27 GETE012 55 2.40 145-167 197-251 11-14 18-23 127-146 308-392 7-9 24-31 GETE012 55 3.00 145-167 191-243 9-11 18-23 130-149 311-396 6-7 25-31 GETE012 68 2.40 146-168 240-305 11-14 17-22 153-176 329-419 8-10 27-35 GETE012 68 3.00 146-168 233-296 9-11 18-23 158-181 332-423 7-9 28-36 GETE012 75 2.40 147-169 266-338 11-14 17-21 169-195 341-434 9-11 29-37 GETE012 75 3.00 146-169 259-329 9-11 17-22 174-200 345-438 7-9 29-37 GETE012 86 2.40 148-170 312-397 11-14 16-20 197-226 362-460 10-13 30-39 GETE012 86 3.00 148-170 304-387 9-11 16-21 203-234 365-465 8-10 31-39 GETE012 95 2.40 149-172 357-454 11-14 15-19 — GETE012 95 3.00 149-172 348-443 9-11 15-19 — GETE015 35 2.80 — 90-103 272-346 6-8 19-24 GETE015 35 3.80 — 94-108 275-350 4-6 19-24 GETE015 45 2.80 146-168 173-220 12-15 18-23 108-124 286-364 6-8 21-27 GETE015 45 3.80 145-167 165-210 9-11 19-24 111-128 288-367 5-6 21-27 GETE015 55 2.80 146-169 202-257 12-15 18-23 125-144 299-381 7-9 24-31 GETE015 55 3.80 146-168 193-245 9-11 18-23 130-149 302-385 6-7 25-31 GETE015 68 2.80 148-170 245-312 12-15 17-22 151-174 317-404 9-11 27-35 GETE015 68 3.80 147-170 235-299 9-11 18-23 157-181 321-409 7-9 28-36
continued on next page
Water
Temp °F
Water
Flow GPM
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water Temp
Rise °F
Air Temp
Drop °F DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop °F
Air Temp
Rise °F DB
WSHP-SVX10B-EN 23
Page 24
Operating Pressures
Table 14. Operating pressures (continued)
Operating Data
Cooling Heating
Entering
Model
GETE015 75 2.80 148-171 272-346 12-15 17-21 167-192 328-417 10-12 29-37 GETE015 75 3.80 148-171 261-332 9-11 17-22 174-200 333-423 7-9 29-37 GETE015 86 2.80 150-172 319-406 12-15 16-20 193-222 345-440 11-14 30-39 GETE015 86 3.80 150-172 307-390 9-11 16-21 202-232 351-447 8-11 31-39 GETE015 95 2.80 151-174 364-463 12-15 15-19 — GETE015 95 3.80 151-174 351-446 9-11 15-19 — GETE018 35 3.60 — 89-103 282-358 7-8 19-24 GETE018 35 4.60 — 93-107 284-361 5-6 19-24 GETE018 45 3.60 140-161 174-221 11-14 18-23 107-123 299-380 7-8 21-27 GETE018 45 4.60 140-161 167-213 8-11 19-24 110-126 302-384 5-7 21-27 GETE018 55 3.60 139-160 203-258 11-14 18-23 125-143 317-404 8-10 24-31 GETE018 55 4.60 139-160 196-250 9-11 18-23 128-147 320-407 6-8 25-31 GETE018 68 3.60 140-161 246-313 11-14 17-22 150-173 341-434 9-11 27-35 GETE018 68 4.60 140-161 238-304 9-11 18-23 155-179 343-437 7-9 28-36 GETE018 75 3.60 141-162 272-346 11-14 17-21 166-191 354-450 10-12 29-37 GETE018 75 4.60 141-162 264-336 9-11 17-22 172-198 357-455 8-10 29-37 GETE018 86 3.60 142-163 317-404 11-14 16-20 193-222 373-475 11-14 30-39 GETE018 86 4.60 142-163 309-393 9-11 16-21 201-231 376-479 9-11 31-39 GETE018 95 3.60 143-165 359-457 11-14 15-19 — GETE018 95 4.60 143-165 350-445 9-11 15-19 — GETE024 35 4.70 — 84-97 272-346 6-8 19-24 GETE024 35 6.10 — 87-100 275-350 4-6 19-24 GETE024 45 4.70 136-156 177-226 11-15 18-23 101-116 286-364 6-8 21-27 GETE024 45 6.10 136-156 171-218 9-11 19-24 104-119 288-367 5-6 21-27 GETE024 55 4.70 137-158 205-261 11-14 18-23 118-135 299-381 7-9 24-31 GETE024 55 6.10 137-158 197-251 9-11 18-23 121-139 302-384 6-7 25-31 GETE024 68 4.70 139-160 246-313 11-14 17-22 142-164 318-405 8-11 27-35 GETE024 68 6.10 139-160 238-303 9-11 18-23 147-169 321-409 7-8 28-36 GETE024 75 4.70 140-162 271-345 11-14 17-21 157-181 328-418 9-12 29-37 GETE024 75 6.10 140-161 263-334 9-11 17-22 163-188 332-422 7-9 29-37 GETE024 86 4.70 142-164 314-399 11-14 16-20 183-211 345-439 10-13 30-39 GETE024 86 6.10 142-163 305-388 8-11 16-21 191-219 349-444 8-10 31-39 GETE024 95 4.70 144-166 352-448 11-14 15-19 — GETE024 95 6.10 144-165 343-437 8-11 15-19 — GETE036 35 7.10 — 89-103 283-361 6-8 19-24 GETE036 35 9.10 — 93-107 284-361 5-6 19-24 GETE036 45 7.10 136-157 177-226 11-14 18-23 107-123 297-378 6-8 21-27 GETE036 45 9.10 136-157 171-218 9-11 19-24 109-126 298-379 5-6 21-27 GETE036 55 7.10 138-159 206-262 11-14 18-23 125-144 313-398 7-9 24-31 GETE036 55 9.10 138-158 199-253 9-11 18-23 128-147 313-399 6-7 25-31 GETE036 68 7.10 140-161 248-315 11-14 17-22 151-173 334-425 9-11 27-35 GETE036 68 9.10 140-161 240-306 9-11 18-23 155-178 335-426 7-9 28-36 GETE036 75 7.10 141-162 273-347 11-14 17-21 166-191 347-442 9-12 29-37
Temp °F
Water
Water
Flow GPM
continued on next page
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water Temp
Rise °F
Air Temp
Drop °F DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop °F
Air Temp
Rise °F DB
24 WSHP-SVX10B-EN
Page 25
Operating Pressures
Table 14. Operating pressures (continued)
Operating Data
Cooling Heating
Entering
Model
GETE036 75 9.10 141-162 265-337 9-11 17-22 171-197 347-442 7-9 29-37 GETE036 86 7.10 143-165 316-402 11-14 16-20 193-222 368-468 10-13 30-39 GETE036 86 9.10 143-165 308-392 8-11 16-21 200-230 369-470 8-10 31-39 GETE036 95 7.10 145-167 355-452 11-14 15-19 — GETE036 95 9.10 145-167 347-441 8-11 15-19
Water
Temp °F
Water
Flow GPM
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water Temp
Rise °F
Air Temp
Drop °F DB
Suction

Pressure

PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop °F
Air Temp
Rise °F DB

Water Pressure Drop

Table 15, p. 25 should be used to define feet of head/
pressure drop.
Note: To calculate feet of head, when using gauges that
read in PSIG, multiply PSI by 2.31.
Table 15. Water pressure drops (WPD) in feet of head
Cooling Heating
Unit Size GPM
009 1.1 77 1.8 55 2.1 009 2.1 77 5.3 55 6.1 009 2.6 77 7.9 55 9.0 012 1.5 77 3.9 55 5.2 012 2.8 77 11.9 55 15.3 012 3.5 77 17.6 55 22.5 015 1.9 77 3.9 55 4.7 015 3.5 77 11.8 55 13.8 015 4.4 77 17.5 55 20.3 018 2.3 77 3.2 55 3.9 018 4.2 77 9.7 55 11.5 018 5.3 77 14.3 55 17.0 024 3.0 77 2.9 55 3.6 024 5.6 77 8.6 55 10.5 024 7.0 77 12.8 55 15.4 036 4.5 77 4.7 55 5.7 036 8.4 77 14.2 55 16.9 036 10.5 77 21.1 55 24.9
EWT °F
Ft. Head
Pressure EWT °F
Ft. Head
Pressure

Water Volume

Table 16. Model Flow Option GPM Press Drop (Ft)
GETE009 Low 1.0 5.5 GETE009 High 1.5 6.6 GETE012 Low 1.5 6.6 GETE012 High 2.0 8.1 GETE015 Low 2.5 10.1 GETE015 High 3.5 15.4 GETE018 Low 3.0 12.6
Table 16. Model Flow Option GPM Press Drop (Ft)
GETE018 High 4.0 18.7 GETE024 Low 4.0 7.6 GETE024 High 6.0 11.4 GETE036 Low 6.0 11.4 GETE036 High 8.0 16.7
Table 17, p. 25 is provided for use in calculating glycol
requirements for the unit.
Table 17. Water volume
Unit Model
GET
009 18.7 0.011 0.081 012 24.9 0.014 0.108 015 37.2 0.022 0.161 018 40.9 0.024 0.177 024 62.6 0.036 0.271 036 85.0 0.049 0.368
Water Side
Volume Cubic
In.
Water Side
Volume Cubic
Ft.
Water Side
Volume Gallons

Flow Checks

For the operating temperature drop (heating) and rise (cooling), refer to Table 14, p. 23 for the proper water temperature change. Depending on the unit size, entering water temperature and water flow rate, the cooling temperature rise is from 8°F-16°F. Based on the same criteria for heating, the temperature drop is from 2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with the P/T port adapter, measure the pressure difference between the water-in and water-out connections. Compare the pressure differential to Table 15, p. 25 to determine flow.
WSHP-SVX10B-EN 25
Page 26

Start-up

Installing Contractor: Use this form to thoroughly check­out the system and units before and during start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name: Model Number: Date: Serial Number:
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
MODE Heat Cool Entering fluid temperature Leaving fluid temperature Temperature differential Return-air temperature DB/WB Supply-air temperature DB/WB Temperature differential Water coil heat exchanger (Water
Pressure IN) Water coil heat exchanger (Water
Pressure OUT) Pressure Differential
COMPRESSOR Amps Volts Discharge line temperature (after
10 minutes)
FF FF FF FF FF FF
PSIG PSIG
PSIG PSIG
PSIG PSIG PSIG PSIG PSIG PSIG
FF
26 WSHP-SVX10B-EN
Page 27

Maintenance

Preventive Maintenance

Maintenance on the unit is simplified with the following preventive suggestions:
Filter maintenance must be performed to assure proper operation of the equipment. Filters should be inspected at least every three months, and replaced when it is evident they are dirty. Filter sizing includes:
Table 18. Filter sizing
Model GET Filter Size (nominal)
009, 012 14 x 20 (356 x 508)
015 18 x 20 (457 x 508) 018 18 x 25 (457 x 635)
024, 036 20 x 30 (508 x 762)
WARNING
Hazardous Chemicals!
Cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
It should be noted that the water quality shouldbe checked periodically.
Table 19. Water quality table
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Check the contactors and relays withinthe control panel at least once a year. It is good practice to check the tightness of the various wiring connections within the control panel.
A strainer (60 mesh or greater) must be used on an open loop system to keep debris from entering the unit heat exchanger and to ensure a clean system.
For units on well water, it is important to check the cleanliness of the water-to-refrigerant heat exchanger. Should it become contaminated with dirt and scaling as a result of bad water, the heat exchanger will haveto be back flushed and cleaned with a chemical that will remove the scale.This service should be performedby an experienced service person.
Scaling
Calcium and magnesium (total
hardness)
Corrosion
pH 7-9.5
Hydrogen Sulfide Less than 1 ppm
Sulfates Less than 25 ppm
Chlorides Less than 125 ppm
Carbon Dioxide Less than 75 ppm
Total dissolved solids (TDS) Less than 1000 ppm
Biological Growth
Iron Bacteria Low
Erosion
Suspended Solids Low
Less than 350 ppm
WSHP-SVX10B-EN 27
Page 28

Troubleshooting

WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures.When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.

PreliminaryTrouble Inspection

If operational difficulties are encountered, be sure to perform the preliminary checks before referring to the
Table 20, p. 29.
Verify that the unit is receiving electric supply power.
Ensure that the fuses in thefused disconnect are intact.
After completing the preliminary checks, inspect the unit for other obvious problems such as leaking connection, broken or disconnected wires, etc. If everything appears to be in order, but theunit still fails to operate properly, refer to the troubleshooting chart on p. 29.

General Operation

The standard model is designed for indoor installation.
When the unit is installed in an unconditioned space, the
unit may not start in cool weather (approximately 45°F). It may then benecessary to start the unitin the coolingmode for three to five minutes.The unit may then be shut-off (there will be a two minute time-out of the unit), and restarted in the heating mode.The freeze protection thermostat should also be checked as it may be adversely affected by ambient temperature.
Like any other type of mechanical equipment, the unit performs best when it is well maintained.
Operation with a Conventional
Thermostat
The unit is equipped with safety controls, including high
pressure control, low pressure control and a freeze protection thermostat, set to shut off the compressor under abnormal temperatureor pressure conditions. Ifthe safeties shut off the compressor, a lockout relay prevents short cycling from the abnormal condition. When conditions are corrected, the lockout control can be reset by setting the thermostat system switch to OFF wait a few minutes for the system pressure to equalize, and then return to HEAT or COOL. If the condition continues, an authorized service person should check out the unit.
28 WSHP-SVX10B-EN
Page 29
Table 20. Troubleshooting checklist
Problem Heating Cooling Cause Correction
No response to any thermostat setting
Unit short cycles X X Thermostat or sensor improperly located Relocate
Blower runs, but compressor does not
Insufficient capacity
High pressure switch open
High head pressure
Low suction pressure
Troubleshooting
X X Main power off Check fuses X X Defective control transformer Replace X X Broken or loose connection Repair X X Defective thermostat Replace X X Transformer Reset Transformer
X X Defective compressor overload Replace (if external) X X Defective compressor contactor Replace X X Supply voltage too low Correct X X Defective compressor capacitor Replace X X Defective windings Replace X X Limit switches open Check cause/Replace or repair X X Dirty filter Replace/clean X X Blower RPM too low Correct
XX
X Introduction of excessively cold return-air Correct X X Low on refrigerant charge
X X Restricted thermal expansion valve Replace X X Defective reversing valve See WSHP-IOM-# for touch test chart X X Thermostat improperly located Relocate X X Unit undersized Recalculate heat gains/losses X X Inadequate water flow Increase GPM X X Scaling in heat exchanger Clean or replace
X Water too cold Increase temperature
X Inadequate air flow Check, clean blower and coil X Dirty filter Clean/replace X X Overcharged with refrigerant Decrease charge X X Defective pressure switch Check or replace
X X Overcharge of refrigerant Decrease charge X X Non-condensable in system Evacuate and recharge by weight X X Water too hot Decrease temperature X Dirty filter Clean / replace X Inadequate air flow Check, clean blower and coil X X Undercharged Locate leak, repair and recharge X X Restricted thermal expansion valve Repair / replace
X Inadequate GPM Increase GPM
Loss of conditioned air due to leaks in
ductwork
X Introduction of excessively hot return-air Correct
Locate leak, repair and recharge by
X Water too hot Decrease temperature
X Inadequate GPM Increase water flow to unit X Water too hot Decrease temperature
X Trash in heat exchanger Backflush X Low water flow Increase GPM
X Inadequate air flow Check, clean blower and coil X Dirty filter Clean/replace
Repair leaks
weight (not by superheat)
WSHP-SVX10B-EN 29
Page 30

Unit Wiring

Figure 17. Tracer ZN510/1 Ph
208/60/1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
L2L1
1PB1
2H
1H
1S4
21A
SEE
INSET
B
21E 23E 24F
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1. ARE SHOWN AT 25° C (77° F), AT ATMOSPHERIC PRESSURE, AT 50% RELATIVE HUMIDITY, WITH ALL UTI LITIES TURNED OFF, AND AFTER A NORMAL SHUTDOWN HAS OCCURRED.
DASHED LI NE S INDICATE RECOMMENDED FIELD
2. WIRING BY OTH E RS . FIELD WIRING T O B E RA TE D FOR 600 VOLTS. DASHE D LINE ENCLOSURE AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOLID LINES INDI CATE WIRING BY THE TRANE CO.
3.
NUMBERS ALONG THE RIGH T SIDE OF THE SCHEMATIC DESIGNATE THE LOCATION OF THE CONTACTS BY LINE NUMBER.
4.
ALL FIE LD WIRING MU ST BE IN A CCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), STATE AND LOCAL REQUIR EMENTS.
VERIFY TEST JUMPER HAS BEEN REMOVED TO
6
PREVENT CONTROL TIMING ERRORS.
21B
A,C
P10-1 J10-1 P7-1
SINGLE STAGE ROOM T'STAT
2F
21C
EQUIPMENT
GROUND
1F1
1F
1F2
9A
3F
P20-2
P20-1
J20-2
J20-1
MTR-5
MTR-4
GRN
MTR-3
1TB1-1 & 2
23A
SEE
INSET
B
SEE
INSET
B
22B
P10-2 J10-2
22C
R G O W Y
1A
2A
9C
3J
21
P7-3 J7-3
23B
P10-3 J10-3
23C
3B 3A CHASSIS
P11-3 J11-3
P11-1 J11-1
P11-2 J11-2
B
SEE
INSET
B
3B2 M 1
COM
TO 1U5 BRD
15 PIN PLUG
SEE INSET B FOR
CONTROL WIRING
23A
24C
P10-4 J10-4
24D
COMN
GROUND
2CCH-1
WW
1K1
1B
2B
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
1TB1-1&2
6E
FIELD INSTALLED ISOLATION VALVE
CLOSE
FOR TWO WIRE N. C VA LVE, DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
D
D
208/60/1
1T1
24V
A
23C
21C
26H 26G
24C 24B
SEE
INSET
B
26M
P7-4 J7-4
26H
P10-5 J10-5
12
26K
CONNECTION FOR 24VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATE D GENERAL AL A R M CO NT ACTS. CONTACTS CLOSE
11
WHEN CONTRO L 1U 2 GO E S INTO MANUAL L OC K O UT MODE. CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRED FOR HARD WIRED DIGITAL THERMOST A TS.
12
CAUTION
USE COPP ER CONDUCTORS ONLY !
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE D AMAGE TO THE EQUIPMENT. ENDOMMAGER L' ÉQUIPEMENT.
1C3
4B
2B1
C
2B1C1
M
5B
1
S
6B
R
1K1
50A OPEN COM
2L1
21C
24B
2B1S1
2B1S2
49B 47C
ATTENTION
N'UTILISE R Q U E DE S CONDUCTEURS E N CUIVRE !
LES BORNES DE L'UNITÉ NE SONT PA S CONÇUES POUR RECEVO IR D'AUTRES TYPES DE CONDUCTEURS.
L'UTILISATIO N DE TOUT AUTRE CON DUCTEUR PEUT
CONTROL DIAGNOSTIC CODES (1U2)
LED1
LED2
COLOR-RED
COLOR=GRN
OFF
OFF ON OFF OFF ON OFF FLASH ON OFF ON
FLASH ON OFF
ON FLASH ON ON FLASH FLASH ON ON ON ON ON FLASH ON FLASH OFF
ON ON OFF
1TB1-3 & 4
26
46B
P9-1 J9-1
47B
P9-2 J9-2
2S1
48B
P9-3 J9-3
49B
P9-4 J9-4
7
LED3
CONTROLLER MO DE
COLOR=RED
CONTROL OFF
OFF
NORMAL / COMP OFF ANTI-SHORT CYCL E NORMAL / COMP ON BROWNOUT CONDIT IION SOFT LOCKOUT LP SOFT LOCKO UT HP MANUAL LOCKOUT LP MANUAL LOCKOU T HP MANUAL LOCKOUT CONDENSATE LEVEL COMPRESSOR DISABLE
DEVICE PREFIX LO CATION CODE
AREA1LOCATION
CONTROL PANEL COMPRESSOR SECTION2
INDOOR FAN AN D CO IL SECTION3 4 WATER COIL SECTION 5 RETURN AN D FR ESH AIR SECTION
FIELD INSTALLED DEVICE6
LEAD COLORS
LEAD
HIGHSPEED
1U2
46A
LED1
47A
LED2 LED3
48A
49A
6
INSET B
J16
P16
P17
J17
TO BLOWER MOTOR 3B2 15 PIN PLUG
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR O TR OS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.
DEVICE
DESIGNATION
1C3 START ASSIST 5
1F1,
FUSE COMPRESSOR CONTACTOR1K1
POWER BLOCK
1PB1 1S4
FUSED UNIT SWITCH
1TB1 CUSTOMER LOW V. TERM BLOCK
CRANKCASE HEATER2CCH-1 4 CONTROL POWER TRANSFORMER
1T1
COMPR CONTROL MODULE 34
1U2
COMPRESSOR MOTOR2B1 COMPRESSO R RUN CAPACITOR2B1C1 8
LOW
HIGH PRESS U RE CUTOUT2B1S1 36 FREEZE PROTECTI ON SWITCH 38
2S1 2L1 R EVE RSING VALVE COIL
2B1S2 LOW PRESSURE SWITCH 39
3B2 E VAP FAN MOTOR
OVERFLOW SWITCH
3S3 35
ECM CONTROLLER
1U5
,C,E,G,M
G
M
44A
45A
1U5
P1
J9-5 P9-5
J9-6 P9-6
98
44B
44C
45B
45C
21E
23E
P15-4
P15-5
P15-3
21D
23D
ROW3 W2 W1 YYLO BGBK
R
PRECAUCIÓN
24F
24E
LEGEND
DESCRIPTION
26M
22B
P15-1
P15-2
26L
22D
LINE
NUMBER
6,
71F2
6,7,37
3
4
21
19
6,7,8
26
15
55
3S3
DRAWN BY
REPLACES
REVISION DATE
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS DRA WING IS PRO PR IETARY AND
CONTENTS DISCLOSED TO OUTSIDE
CONSENT OF THE TRANE COMPANY
PARTIES WITHOUT THE WRITTEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
P2
SCHEMATIC DIAGRAM
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
30 WSHP-SVX10B-EN
Page 31
Figure 18. Deluxe 230V/60 Hz/1 Ph
Unit Wiring
208/60/1
1
2
3
4
5
6
7
1PB1
L2L1
2H
1H
1S4
1F
2F
8
9
10
11
12
13
14
15
16
17
FIELD INSTALLED ISOLAT ION VALVE
1TB1-1&2
CLOSE
FOR TWO WIRE N.C VALVE, DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
18
19
20
21
A,C
22
23
24
25
26
27
28
29
30
31
22A
21A
32
33
34
35
P7-1
22B
21B
36
37
38
39
40
41
P10-1 J10-1
SINGLE STAGE ROOM T'STAT
21C
42
43
44
45
46
47
48
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
49
ARE SHOWN AT 25° C (77° F), AT ATMOSPHERIC PRESSURE, AT 50% RELATI V E HUMIDITY, WIT H ALL UTILITIES TURNED OFF,
50
AND AFTE R A NO RMAL SHUTDO W N H AS OCCURRED.
51
DASHED LINES INDICATE RECOMMENDED FIELD
2. WIRING BY OTHERS. FIE L D WIRIN G T O BE RA T ED
52
FOR 600 VOLTS. DASH ED LINE ENCLOSURE AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOL I D
53
LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE
54
SCHEMATIC DESIGNATE THE LO CATI ON OF THE CONTACTS BY LINE NUMBER.
55
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D
56
LOCAL REQUIREMENTS.
57
VERIF Y TEST JUMPER HAS BEEN REMOVED TO
6
PREVEN T CONTROL TI MING ERRORS.
58
59
60
3B 3A CHASSIS
P11-3 J11-3
EQUIPMENT
GROUND
1F1
1A
1F2
2A
50A OPEN COM
1TB1-1 & 2
21
23A
P7-3 J7-3
P7-2 J7-2
23B
P10-3 J10-3
P10-2 J10-2
22C
23C
R G O W Y
P11-1 J11-1
P11-2 J11-2
1K1
B
23A
24C
P10-4 J10-4
24D
COMN
GROUND
2CCH-1
WW
1K1
1B
2B
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
,C
1K4
C,D
42
6E
D
D
208/60/1
1T1
24V
22A
1K4
A
C
13 13
23C
21C
26H 26G
24C 24B
P7-4 J7-4
26H
P10-5 J10-5
12
26K
CONN ECTIO N FOR 2 4VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE
11
WHEN CONTROL 1U2 GOES INTO MANUAL LOCKOUT MODE. CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRE D FO R HA R D WIRED DIGI TAL THERMO S T A T S.
12
WIRE S 23C & 26J ARE ONLY USED ON SIZE 024 & 036.
13
ON AL L OTHER SIZ ES WIR ES 23A & 26F CONNECT TO 2L1.
USE COPPER CONDUCTORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED T O ACCEPT OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CAUSE DAMAGE TO THE EQUIPMENT. ENDOMMAGER L'ÉQUIPEMENT.
CAUTION
1C3
4B
2B1
C
2B1C1
1G
M
5B
1
S
6B
R
J1-1
J1-3
C
J1-2 P1-2
2L1
21C
24B
2B1S1
2B1S2
49B 47C
ATTENTION
N'UTILI SE R QUE DES CONDUCT E URS EN CUIVRE!
LES BORNE S DE L'UNITÉ NE SONT PAS CONÇUES POUR RECEVOIR D'AUTRES TYPES DE CON DUCTEURS.
L'UTILISATION DE TOUT AUTRE COND UCTEUR PEUT
CONTROL DIAGNOSTIC CODES (1U2)
LED2
LED1
COLOR=GRN
COLOR-RED
OFF
OFF
ON OFF F LASH ON OFF ON
FLASH ON OFF
ON FLASH ON ON F LASH FLASH ON ON ON ON ON FLASH ON F LASH OFF
ON ON OFF
RED9A
YEL
YEL
3B2C2
BRN
BLK
1TB1-3 & 4
26
46B
P9-1 J9-1
47B
P9-2 J9-2
2S1
48B
P9-3 J9-3
49B
P9-4 J9-4
7
LED3
COLOR=RED
CONTROLLER MODE
OFF CONTROL OFF
NORMAL / CO MP OFFON OFF OFF ANTI-SHORT CYCLE NORMAL / CO MP ON BROWNOUT CO NDITIION SOFT LOCKOUT LP SOFT LOCKOUT HP MANUAL LOCKOUT LP MANUAL LOCK OUT HP MANUAL LOCKOUT CONDENSATE LE VEL COMPRESSOR DI SABL E
DEVICE PREFIX LOCATION CODE
AREA1LOCATION
CONTROL PANEL COMPRESSOR SECTION2
INDOOR FAN AND CO IL SECTION3 4 WAT ER COIL SECTION 5
RETURN AND FR ES H AIR SECTION
FIELD INSTALLE D DEVICE6
LEAD COLORS
LEAD
BLU RED
HIGHSPEED
3B2
M 1
GRN
COM
1U2
46A
LED1
47A
LED2 LED3
48A
49A
6
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
DEVICE
DESIGNATION
1C3 START ASSIST 5
1F1,
FUSE COMPRESSOR CONTACT OR1K1
1K4
BLOWER REL AY
1PB1 POWER BLOCK
1TB1 CUSTOMER LOW V. TER M BL OCK
CRANKCAS E H EATER2CCH-1 4 CONTROL POWER TR ANSFORMER1T1 19 COMPR CONTROL MODULE 34
1U2
COMPRESSOR MOTOR2B1 COMPRESS O R RU N CAPACITOR2B1C1 8
LOW
HIGH PRESSURE CUTOUT2B 1S1 36 FREEZE PROTECTION SWITCH
2S1 2L1 REVER S I NG VALVE COIL 26
2B1S2 LOW PRESSURE SWITCH
3B2 EVAP FAN MOTOR
3B2C2
EVAP FAN M T R RUN CAPACITOR
OVERFLOW SWITCH
3S3 35
,C,E,G,M
G
M
44A
45A
J9-5 P9-5
J9-6 P9-6
44B
45B
PRECAUCIÓN
LEGEND
DESCRIPTION
3S3
44C
LINE
NUMBER
6, 6,7,37
13,22
3
21
6,7,8
38
39
15 15
71F2
45C
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS DRAWING IS PROPRIETARY AND
CONTENTS DISCLOSE D T O OUTSIDE
CONSENT OF THE TRAN E COMPANY
PARTIE S WITHOUT THE WR I TTEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
SCHEMA TIC DIAGRA M
2311-0376
WALL MOUNT T'STAT
208/60/1
DELUXE UNIT
HEAT PUMP
GET
REV
G
WSHP-SVX10B-EN 31
Page 32
Unit Wiring
Figure 19. Tracer ZN510/1 Ph with ECM motor
208/60/1
1
2
3
4
5
6
7
8
9
10
11
1PB1
L2L1
2H
1H
1S4
1F
1F2
2F
9A
P20-2 J20-2
12
13
14
15
GRN
16
17
18
19
20
21
INSET B
K,X,P
22
23
24
25
26
27
28
29
P 64A
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1.
49
ARE SHOWN AT 25° C (77° F), AT ATMOSPHERIC PRESSURE, AT 50% RELATI V E HUMIDITY, WIT H ALL UTILITIES TURNED OFF,
50
AND AFTE R A NORMAL SHU TD O W N H AS OCCURRED.
51
DASHED LINES INDICATE RECOMMENDED FIELD
2. WIRING BY OTHERS. FIE L D WIRING TO BE R ATED
52
FOR 600 VOLTS. DASH ED LINE ENCLOSURE AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOLID
53
LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE
54
SCHEMATIC DESIGNATE THE LO CATI ON OF THE CONTACTS BY LINE NUMBER.
55
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D
56
LOCAL REQUIREMENTS.
57
58
COMMU NICAT ION WI RE MUST BE TRANE PART NO.
6
59
400-20-28, OR WINDY C ITY OR CONNECT AIR "LEVEL 4" CABLE. MAXIMUM OF 4500 FOOT AGGREGATE RUN.
60
CAUTIO N! DO NOT RUN POWER IN THE SAME CONDUIT OR W I R E BU ND L E WITH COMMUNICATI ON LINK. FOR ADDITIONAL INFROMATION REFER TO EMTX-EB-68.
EQUIPMENT
GROUND
1F1
26M
1TB1-1 & 2
J9-3 P9-3
21K
3F
P20-1 J20-1
MTR-5
MTR-4
MTR-3
9C
3J
21
3B 3A CHASSIS
P11-3 J11-3
1A
P11-1 J11-1
2A
P11-2 J11-2
3B2 M 1
COM
TO 1U5 BR D 15 PIN PLUG
SEE INSET B FO R
CONTROL WIRI NG
B
21R
CONDENSATE
OVERFLOW
OPTIONAL
GROUND
2CCH-1
WW
1K1
1B
2B
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
1TB1-3&4
6E
FIELD INSTALLED ISOLAT ION VALVE
CLOSE
FOR TWO WIRE N.C VALVE, DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 6VA AT 24V
D
D
208/60/1
1T1
24V
A
21M
P9-1
2B1S1
2B1S2
P9-4 J9-4
JX15-1
P15-1
P7-5 J7-5
45B
P7-6 J7-6
CAUTION
2S1
63A
46B
47B 48B
2L1
64B
22B
3S3
OCCUPANCY CONNECTIONS
6
COMM LINK
USE CO P PER CON DUCT ORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED TO ACCEPT OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CA USE DAMAGE TO THE EQUIPMENT. ENDOMMAGER L'ÉQUIPEMENT.
1C3
4B
2B1
C
5B
6B
S
R
1TB1-1&2
COM OPEN
M
1
21M
1K1
2B1C1
P9-2
49B
26U
24VGND
J2-1
BI1
44A44B
BI2
45A
BI3
TB1-2
POWER
J2-2
BINARY INPUT
J2-3
J2-4
J2-5
J2-6
TB2-1
TB2-2
ATTENTION
N'UTILISER QUE DES CO NDUC T E UR S EN CUI VRE!
LES BORNE S DE L'UNITÉ N E SONT PAS CONÇUES POUR RECEVOIR D'AUTRES TYPES DE CON DUCT EURS.
L'UTILISATION DE TOUT AUTRE COND UC TEUR PEUT
LEGEND
DESCRIPTION
FUSE COMPRESSOR CONTACTOR1K1
CRANKCAS E HEATER2CCH-1 4 CONTROL POWER TR ANSFORMER1T1 19
COMPRESSOR MOTOR2B1 COMPRESS O R RU N CAPACITOR2B1C1 8
FREEZE PROTECTION SWITCH
OVERFLOW SWITCH
ZN510 CONTROLLER ECM CONTROLLER LEAVING WATER TEMP SENSOR4RT3
NUMBER
6, 6,7,23
LINE
71F2
3 4FUSED UNIT SWITCH1S4
21
6,7,8
26
26
15
38 37
34 55
40
DEVICE PREFIX LO CATION CODE
AREA1LOCATION
CONTROL PANEL COMPRESSOR SECTION2
INDOOR FAN AND CO IL SECTION3 4 WATER COIL SECTION 5
RETURN AND FRES H AIR SECTION
FIELD INSTALLE D DEVICE6
LEAD
LEAD COLORS
HIGHSPEED
DEVICE
DESIGNATION
1C3 START ASSIST 5
1F1,
1PB1 POWER BLOCK
1TB1 CUSTOMER LOW V. TERM BLOCK
2B1S1
2B1S1 HIGH PRESSURE CUT OUT 26
LOW
2S1 2L1 REVERSI N G VALVE COIL 29
2B1S2 LOW PRESSURE CUTOUT
3B2 EVAP FAN MOTOR
3RT4 DISCHARGE AIR SENSOR
3S3
1U4 1U5
INSET B
1TB1-3 & 4
26
21E
,U
26U
P14-2
2
34567
BINARY OUTPUTS
TB3-3
TB3-4
SET
FAN GND
75A
69A
20B64A P14-5
TB3-6
J7-1 P7-1
J7-2 P7-2 J7-3 P7-3
J7-4 P7-4
83A
J3-4
82A
J3-3
ANALOG INPUT
J3-2
AI1 AI2
J3-1
75B
J10-1 P10-1
69B
J10-2 P10-2
68B
J10-3 P10-3
67B
J10-4 P10-4
4RT3
3RT4
75C
69C
68C
67C
DISCHARGE AIR SENSOR
LEAVING WATER SENSOR
FAN MODE
SET POINT
COMMON
ZONE TEMP
ZONE
SENSOR
63A
21K
TB1-1
P14-1
J1
1
1U4
ZONE SENSORCOMM LINK
TB3-2
TB2-3
TB2-4
TB3-1
TB2-5
TB2-6
GNDZONE
68A
67A
6
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS D RAWIN G IS PROPRIETARY AND
CONTENTS DISCLOSED TO OUTSIDE
CONSENT OF THE TRAN E C OMPANY
PARTIE S WITHOUT THE WR I T TEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
P2
SCHEMA TIC DIAGRA M
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
INSET B
J16
P16
J17P17
1U5
TO BLOWER M OTOR 3B2 15 PIN PLUG
PRECAUCIÓN
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
21E
24F
26M
22B
PX15-1
PX15-5
98
P1
R ROW3 W2 W1 YYLO BGBK
PX15-2
PX15-3
21D
23D
26L
24E
22D
32 WSHP-SVX10B-EN
Page 33
Figure 20. Deluxe 24V/1 Ph with ECM motor
208/60/1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
L2L1
1PB1
2H
1H
1S4
21A
SEE
INSET
B
21E 23E 24F
NOTES:
UNLESS OTHERWISE NOTED, ALL SWITCHES
1. ARE SHOWN AT 25° C (77° F), AT ATMOSPHERIC PRESSURE, AT 50% RELATI V E HUMIDITY, WIT H ALL UTILITIES TURNED OFF, AND AFTE R A NORMAL SHU TD O W N H AS OCCURRED.
DASHED LINES INDICATE RECOMMENDED FIELD
2. WIRING BY OTHERS. FIE L D WIRING TO BE R ATED FOR 600 VOLTS. DASH ED LINE ENCLOSURE AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOL I D LINES INDICATE WIRI NG B Y THE TR ANE CO.
3.
NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC DESIGNATE THE LO CATI ON OF THE CONTACTS BY LINE NUMBER.
4.
ALL FIELD WIRIN G MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), ST ATE AN D LOCAL REQUIREMENTS.
VERIF Y TEST J UMPER HAS BEEN REMOVED TO
6
PREVEN T CONTROL TIM ING ERRORS .
21B
P10-1 J10-1 P7-1
SINGLE STAGE ROOM T'STAT
2F
P20-2 J20-2
A,C
22B
21C
EQUIPMENT
GROUND
1F1
1F
1F2
9A
3F
P20-1 J20-1
9C
MTR-5
3J
MTR-4
GRN
MTR-3
1TB1-1 & 2
21
23A
SEE
INSET
B
SEE
INSET
B
P10-2 J10-2
22C
R G O W Y
1A
2A
P7-3 J7-3
23B
P10-3 J10-3
23C
3B 3A CHASSIS
P11-3 J11-3
P11-1 J11-1
P11-2 J11-2
3B2 M 1
COM
TO 1U5 BR D
15 PIN PLUG
SEE INSET B FO R
CONTROL WIRI NG
GROUND
1B
2B
B
23A
SEE
INSET
B
SEE
INSET
24C
26M
P10-4 J10-4
24D
26K
COMN
2CCH-1
WW
1K1
1D
4A
P12-1 J12-1
1K1
6C
P12-2 J12-2
2D1C
D
D
24V
26H 26G
24C 24B
P7-4 J7-4
B
26H
P10-5 J10-5
12
CONN ECTIO N FOR 2 4VAC CLASS 2 COMPRESSOR DISABLE
7
INPUT. FOR TLC APPLICATIONS PUMP RESTART RELAY REQ'D FOR OVERRIDE. USE TERM CD1 & CD2 TO ENERGIZE PUMP RESTART RELAY COIL: MAX LOAD (5 VA).
ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE
11
WHEN CONTROL 1U2 GOES INTO MANUAL LOCKOUT MODE. CONTACTS RATED FOR CLASS 2 24V. TERMINAL AL1 & AL2
REQUIRE D FO R HARD WIRED DI GITAL THER M O S T A T S.
12
USE COPPER CONDUCTORS ONLY!
UNIT TERMINAL S ARE NOT DESIGNED TO ACCEPT OTHER TYP ES OF CONDUCTORS.
FAILURE TO DO SO MA Y CAUSE DAMAGE TO THE EQUIPMENT. ENDOMMAGER L'ÉQUIPEMENT.
CAUTION
1C3
4B
2B1C1
5B
6E
6B
FIELD INSTALLED ISOLAT ION VALVE
1TB1-1&2
CLOSE
FOR TWO WIRE N.C VALVE, DISREGARD CLOSE TERMINAL WIRING.
MAX LOAD 25VA AT 24V
208/60/1
1T1
A
23C
2L1
21C
49B 47C
N'UTILIS E R QUE DES CONDUCT E URS EN CUIVRE!
LES BORNE S DE L'UNITÉ NE SONT PAS CONÇUES POUR RECEVOIR D'AUTRES TYPES DE CON DUCTEURS.
L'UTILISATION DE TOUT AUTRE COND UCTEUR PEU T
C
R
OPEN COM
S
50A
2B1S2
2B1
M
1
1K1
21C
24B
LED1
COLOR=GRN
OFF
ON OFF OFF
ON OFF ON
FLASH ON OFF
ON FLASH ON ON FL ASH FLASH ON ON ON ON ON FLASH ON FL ASH OFF
ON ON OFF
1TB1-3 & 4
26
2B1S1
46B
P9-1 J9-1
47B
P9-2 J9-2
2S1
48B
P9-3 J9-3
49B
P9-4 J9-4
7
ATTENTION
CONTROL DIAGNOSTIC CODES (1U2)
LED3
LED2
COLOR=RED
COLOR-RED
OFF
OFF
DEVICE PREFIX LO CATION CODE
AREA1LOCATION
CONTROL PANEL COMPRESSOR SECTION2
INDOOR FAN AND CO IL SECTION3 4 WATER COIL SECTION 5
RETURN AND FRES H AIR SECTION
FIELD INSTALLE D DEVICE6
46A
47A
48A
CONTROL OFF NORMAL / CO MP OFF ANTI-SHORT CYCLEON OFF FLASH NORMAL / CO MP ON BROWNOUT CO NDITIION SOFT LOCKOUT LP SOFT LOCKOUT HP MANUAL LOCKOUT LP MANUAL LOCK OUT HP MANUAL LOCKOUT CONDENSATE LE VEL COMPRESSOR DI SABLE
LEAD
LED1 LED2 LED3
49A
INSET B
J16
P16
J17P17
¡UTILICE ÚNICAMENT E CONDUCTORES DE COBRE!
LAS TERMI NALES DE LA UNIDAD NO ESTÁ N DISEÑADAS PARA ACEPTA R OT ROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUED E OCASIONAR DAÑO AL EQUIPO.
CONTROLLER MODE
LEAD COLORS
HIGHSPEED
LOW
,C,E,G,M
1U2
44A
45A
6
1U5
P1
TO BLOWER M OTOR 3B2 15 PIN PLUG
PRECAUCIÓN
DEVICE
DESIGNATION
1C3 START ASSIST 5
1F1,
1PB1 POWER BLOCK
1TB1 CUSTOMER LOW V. TERM BLOCK
1U2
2S1 2L1 REVERS I N G VALVE COIL 26
2B1S2 LOW PRESSURE SWITCH
3B2 EVAP FAN MOTOR
3S3 35
1U5
LEGEND
DESCRIPTION
FUSE COMPRESSOR CONTACTOR1K1
CRANKCASE HEATER2CCH-1 4 CONTROL POWER TR ANSFORMER1T1 19 COMPR CONTROL MODULE 34
COMPRESSOR MOTOR2B1 COMPRESS O R RU N CAPACITOR2B1C1 8 HIGH PRESSURE CUTOUT2B1S1 36 FREEZE PROTECTION SWITCH
OVERFLOW SWITCH
ECM CONTROLLER 55
G
M
J9-5 P9-5
J9-6 P9-6
98
44B
45B
21E
23E
P15-4
P15-5
21D
23D
ROW3 W2 W1 YYLO BGBK
R
3S3
44C
45C
24F
26M
22B
P15-1
P15-2
P15-3
26L
24E
22D
P2
Unit Wiring
LINE
NUMBER
6,
71F2
6,7,37
3 4FUSED UN IT SWI T CH1S4
21
6,7,8
38
39
15
REPLACES
REVISION DATE
DRAWN BY
DATE
RCAP5091 02/08/13
5/11/09
LOWE
SIMILAR TO
2309-7379
THIS D RAWIN G IS PROPRIETARY AND
CONTENTS DISCLOSE D T O OUTSI DE
CONSENT OF THE TRAN E C OMPANY
PARTIE S WITHOUT THE WR I T TEN
SHALL NOT BE COPIED OR ITS
AUTOCAD
SCHEMA TIC DIAGRA M
208/60/1
2311-0376
HEAT PUMP
GET
REV
G
WSHP-SVX10B-EN 33
Page 34

Warranty

Standard Warranty

The standard water-source heat pump warranty isTrane’s
parts-only warranty, running 12-months from startup, not to exceed 18-months from shipment.

Extended Warranty

The optional extended warranty is a second through fifth
year warranty.The time starts at the end of standard 1-year coverage through the fifth year.
These extended warranties apply only to new equipment
installed in domesticTrane Commercial Systems Group sales territories and must be ordered prior to start-up.
34 WSHP-SVX10B-EN
Page 35
Page 36
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2013Trane All rights reserved
WSHP-SVX10B-EN 15 Nov 2013
Supersedes WSHP-SVX10B-EN (18 Jun 2013)
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...