The TR1 Series VFD contains dangerous
voltages when connected to line voltage.
After disconnecting from the line, wait at
least 15 minutes, 30 minutes for 550-600V
units, before touching any electrical components. Only a competent electrician should
carry out the electrical installation. Improper
installation of the motor or the TR1 may
cause equipment failure, serious injury or
death. Follow this manual, National Electrical Codes and local safety codes.
WARNING
!
Many electronic components of the TR1
Series VFD are sensitive to Electrostatic
Discharge (ESD). Voltages so low that they
cannot be felt, seen or heard, can reduce the
life, affect performance, or completely
destroy sensitive electronic components.
When performing service, proper ESD
equipment should be used to prevent possible damage from occurring.
2
CAUTION
!
It is the responsibility of the user or the
person installing the TR1 Series VFD to
provide proper grounding, as well as motor
overload and branch circuit protection
according to the National Electrical Code
and local codes.
Page 3
Single Relay Option Card
The ratings of the relay contacts are the same as the standard Form C relay.
Output terminals are located on the single relay option card. The terminals
are 110, 111, and 112. Input to the relay is through terminals 113 and 114,
also located on the option card. Input to the coil in the relay is 24 VDC, 10
mA nominal. The input to the relay is polarity sensitive. The Form C relay on
the option card may be driven by either the standard Form A relay or one of
the transistorized outputs.
Specifications
Auxiliary Relay Card Option Output
TerminalsFunctionRating
110-111-112Relay outputForm C contact (n.o. and n.c.)
42-39Analog output0/4-20 mA analog signal (Max. 500
ohm load) or 24 VDC logic signal
(Max. 600 ohm load)
45-39Analog output0/4-20 mA analog signals or 24 VDC
logic signals
3
Page 4
NEMA 1 Installation
DANGER
!
Remove power to drive and wait at
least 15 minutes to discharge voltage.
1
3
ä
2
4
Page 5
NEMA 1 Installation (continued)
Position option card to back side of cassette. Slide edge of card into
slot in side of cassette. Secure option card by pressing it flush to
cassette. Insert two self-tapping screws provided in holes in upper
left and bottom center of card. Tighten to 7 in-lb. (0. 8 N-m).
4
Back side of cassette
End view
5
Page 6
NEMA 1 Installation (continued)
Connect two ribbon cables. Hinge cassette from top. Reinsert screws and
tighten to 8 in-lb. (0.9 N-m). Plug in control terminal strips. Wire option card
as described in Wiring.
5
6
6
Page 7
NEMA 12 Installation
DANGER
!
Remove power to drive and wait at
least 15 minutes to discharge voltage.
1
2
7
Page 8
NEMA 12 Installation (continued)
Position option card to back side of cassette. Slide edge of card into
slot in side of cassette. Secure option card by pressing it flush to
cassette. Insert two self-tapping screws provided in holes in upper
left and bottom center of card. Tighten to 7 in-lb. (0. 8 N-m).
Connect two ribbon cables. Hinge cassette from top. Reinsert screws
and tighten to 8 in-lb. (0.9 N-m). Plug in control terminal strips. Wire
option card as described in Wiring.
4
3
Back side of cassette
8
5
End view
Page 9
Wiring
The single relay option card can be driven by relay 2, or by either of
the two analog outputs.
To Drive from Relay 2:
Wire as shown below. Install a jumper between terminals 5 and 12.
Program relay using parameter 326.
Output Relay 2
113
61 68 69
114
16 17 18 19 20 27 29 32 33
®
TR1 VFD
VLT 5000
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Internal
Relay
Relay Option
Tighten terminals on drive terminal strip to 5 in-lbs (0.6 N-m).
Tighten terminals on option card to 3.5 in-lbs (0.4 N-m).
Contacts
9
Page 10
Wiring (continued)
To Drive from Analog Output 42:
Wire as shown in figure 2 below. Program the relay using parameter 319.
To Drive from Analog Output 45:
Wire as shown in figure 3 below. Program the relay using parameter 321.
Output 42
16 17 18 19 20 27 29 32 33
®
TR1 VFD
VLT 5000
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Internal
Relay
Relay Option
Contacts
113
61 68 69
114
Output 45
16 17 18 19 20 27 29 32 33
®
VLT 5000
TR1 VFD
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Relay Option
113
Internal
Relay
Contacts
61 68 69
114
Tighten terminals on drive terminal strip to 5 in-lbs (0.6 N-m).
Tighten terminals on option card to 3.5 in-lbs (0.4 N-m).
10
Page 11
Trane
A business of American Standard Companies
www.trane.com
For more information contact your local Trane office
or e-mail us at comfort@trane.com
Literature Order NumberTR1-SVN02A-EN
File NumberSV-VEN-TR1-SVN002-EN-1003
SupersedesNew
Stocking LocationCommercial Communications, Inc.
Trane has a policy of continuous product and product data improvement and
reserves the right to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.