Trane TR1 Series VFD Installation Instruction

TR1
Series VFD
Variable Frequency Drive
Auxiliary Relay
Option Card
Installation Instructions
October, 2003 TR1-SVN02A-EN
DANGER
!
The TR1 Series VFD contains dangerous voltages when connected to line voltage. After disconnecting from the line, wait at least 15 minutes, 30 minutes for 550-600V units, before touching any electrical compo­nents. Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the TR1 may cause equipment failure, serious injury or death. Follow this manual, National Electri­cal Codes and local safety codes.
WARNING
!
Many electronic components of the TR1 Series VFD are sensitive to Electrostatic Discharge (ESD). Voltages so low that they cannot be felt, seen or heard, can reduce the life, affect performance, or completely destroy sensitive electronic components.
When performing service, proper ESD equipment should be used to prevent pos­sible damage from occurring.
2
CAUTION
!
It is the responsibility of the user or the person installing the TR1 Series VFD to provide proper grounding, as well as motor overload and branch circuit protection according to the National Electrical Code and local codes.
Single Relay Option Card
The ratings of the relay contacts are the same as the standard Form C relay. Output terminals are located on the single relay option card. The terminals are 110, 111, and 112. Input to the relay is through terminals 113 and 114, also located on the option card. Input to the coil in the relay is 24 VDC, 10 mA nominal. The input to the relay is polarity sensitive. The Form C relay on the option card may be driven by either the standard Form A relay or one of the transistorized outputs.
Specifications
Auxiliary Relay Card Option Output
Terminals Function Rating
110-111-112 Relay output Form C contact (n.o. and n.c.)
240 VAC, 2 amps 24 VDC 10 mA, 24 VAC 100 mA minimum
113-114 Coil 24 VDC 10 mA nominal. Polarity
sensitive.
TR1 Series VFD Standard Output
Terminals Function Rating
01-02-03 Relay output Form C contact (n.o. and n.c.)
240 VAC, 2 amps 24 VDC 10 mA, 24 VAC 100 mA minimum
04-05 Relay output Form A contact (n.o. contact)
50 VAC, 1 amp 75 VDC, 1 amp
42-39 Analog output 0/4-20 mA analog signal (Max. 500
ohm load) or 24 VDC logic signal (Max. 600 ohm load)
45-39 Analog output 0/4-20 mA analog signals or 24 VDC
logic signals
3
NEMA 1 Installation
DANGER
!
Remove power to drive and wait at least 15 minutes to discharge voltage.
1
3
ä
2
4