Trane TR1 Series VFD Installation Instruction

Page 1
TR1
Series VFD
Variable Frequency Drive
Auxiliary Relay
Option Card
Installation Instructions
October, 2003 TR1-SVN02A-EN
Page 2
DANGER
!
The TR1 Series VFD contains dangerous voltages when connected to line voltage. After disconnecting from the line, wait at least 15 minutes, 30 minutes for 550-600V units, before touching any electrical compo­nents. Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the TR1 may cause equipment failure, serious injury or death. Follow this manual, National Electri­cal Codes and local safety codes.
WARNING
!
Many electronic components of the TR1 Series VFD are sensitive to Electrostatic Discharge (ESD). Voltages so low that they cannot be felt, seen or heard, can reduce the life, affect performance, or completely destroy sensitive electronic components.
When performing service, proper ESD equipment should be used to prevent pos­sible damage from occurring.
2
CAUTION
!
It is the responsibility of the user or the person installing the TR1 Series VFD to provide proper grounding, as well as motor overload and branch circuit protection according to the National Electrical Code and local codes.
Page 3
Single Relay Option Card
The ratings of the relay contacts are the same as the standard Form C relay. Output terminals are located on the single relay option card. The terminals are 110, 111, and 112. Input to the relay is through terminals 113 and 114, also located on the option card. Input to the coil in the relay is 24 VDC, 10 mA nominal. The input to the relay is polarity sensitive. The Form C relay on the option card may be driven by either the standard Form A relay or one of the transistorized outputs.
Specifications
Auxiliary Relay Card Option Output
Terminals Function Rating
110-111-112 Relay output Form C contact (n.o. and n.c.)
240 VAC, 2 amps 24 VDC 10 mA, 24 VAC 100 mA minimum
113-114 Coil 24 VDC 10 mA nominal. Polarity
sensitive.
TR1 Series VFD Standard Output
Terminals Function Rating
01-02-03 Relay output Form C contact (n.o. and n.c.)
240 VAC, 2 amps 24 VDC 10 mA, 24 VAC 100 mA minimum
04-05 Relay output Form A contact (n.o. contact)
50 VAC, 1 amp 75 VDC, 1 amp
42-39 Analog output 0/4-20 mA analog signal (Max. 500
ohm load) or 24 VDC logic signal (Max. 600 ohm load)
45-39 Analog output 0/4-20 mA analog signals or 24 VDC
logic signals
3
Page 4
NEMA 1 Installation
DANGER
!
Remove power to drive and wait at least 15 minutes to discharge voltage.
1
3
ä
2
4
Page 5
NEMA 1 Installation (continued)
Position option card to back side of cassette. Slide edge of card into slot in side of cassette. Secure option card by pressing it flush to cassette. Insert two self-tapping screws provided in holes in upper left and bottom center of card. Tighten to 7 in-lb. (0. 8 N-m).
4
Back side of cassette
End view
5
Page 6
NEMA 1 Installation (continued)
Connect two ribbon cables. Hinge cassette from top. Reinsert screws and tighten to 8 in-lb. (0.9 N-m). Plug in control terminal strips. Wire option card as described in Wiring.
5
6
6
Page 7
NEMA 12 Installation
DANGER
!
Remove power to drive and wait at least 15 minutes to discharge voltage.
1
2
7
Page 8
NEMA 12 Installation (continued)
Position option card to back side of cassette. Slide edge of card into slot in side of cassette. Secure option card by pressing it flush to cassette. Insert two self-tapping screws provided in holes in upper left and bottom center of card. Tighten to 7 in-lb. (0. 8 N-m).
Connect two ribbon cables. Hinge cassette from top. Reinsert screws and tighten to 8 in-lb. (0.9 N-m). Plug in control terminal strips. Wire option card as described in Wiring.
4
3
Back side of cassette
8
5
End view
Page 9
Wiring
The single relay option card can be driven by relay 2, or by either of the two analog outputs.
To Drive from Relay 2:
Wire as shown below. Install a jumper between terminals 5 and 12. Program relay using parameter 326.
Output Relay 2
113
61 68 69
114
16 17 18 19 20 27 29 32 33
®
TR1 VFD
VLT 5000
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Internal Relay
Relay Option
Tighten terminals on drive terminal strip to 5 in-lbs (0.6 N-m). Tighten terminals on option card to 3.5 in-lbs (0.4 N-m).
Contacts
9
Page 10
Wiring (continued)
To Drive from Analog Output 42:
Wire as shown in figure 2 below. Program the relay using parameter 319.
To Drive from Analog Output 45:
Wire as shown in figure 3 below. Program the relay using parameter 321.
Output 42
16 17 18 19 20 27 29 32 33
®
TR1 VFD
VLT 5000
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Internal Relay
Relay Option
Contacts
113
61 68 69
114
Output 45
16 17 18 19 20 27 29 32 33
®
VLT 5000
TR1 VFD
04 05 12 13 39 42 45 50 53 54 55 60
112
111
110
Relay Option
113
Internal Relay Contacts
61 68 69
114
Tighten terminals on drive terminal strip to 5 in-lbs (0.6 N-m). Tighten terminals on option card to 3.5 in-lbs (0.4 N-m).
10
Page 11
Trane A business of American Standard Companies www.trane.com
For more information contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number TR1-SVN02A-EN
File Number SV-VEN-TR1-SVN002-EN-1003
Supersedes New
Stocking Location Commercial Communications, Inc.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.