Rotating shafts and electrical equipment can
be hazardous. Therefore, it is strongly
recommended that all electrical work conform
to National Electrical Code (NEC) and all local
regulations. Installation, start-up and
maintenance should be performed only by
qualified personnel. Failure to follow the NEC
or local regulations could result in death or
serious injury.
Factory recommended procedures, included in this manual, should be
followed. Always disconnect electrical power before working on the
unit.
Although shaft couplings or belt drives are generally not furnished by
the manufacturer, rotating shafts, couplings and belts must be protected
with securely mounted metal guards that are of sufficient thickness to
provide protection against flying particles such as keys, bolts and
coupling parts. Even when the motor is stopped, it should be considered alive as long as its controller is energized. Automatic circuits may
start the motor at any time. Keep hands away from the output shaft until
the motor has completely stopped and power is disconnected from the
controller.
Motor control equipment and electronic controls are connected to
hazardous line voltages. When servicing drives and electronic controls,
there will be exposed components at or above line potential. Extreme
care should be taken to protect against shock. Stand on an insulating
pad and make it a habit to use only one hand when checking components. Always work with another person in case of an emergency.
Disconnect power whenever possible to check controls or to perform
maintenance. Be sure equipment is properly grounded. Wear safety
glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1.The drive must be disconnected from the AC line before any
service work is done.
2.The STOP/OFF key on the local control panel of the drive does
not disconnect the equipment from the AC line and is not to be
used as a safety switch.
3.Correct protective grounding of the equipment must be established. The user must be protected against supply voltage and the
motor must be protected against overload in accordance with
applicable national and local regulations.
4.Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1.While the drive is connected to the AC line, the motor can be
brought to a stop by means of external switch closures, serial bus
commands or references. If personal safety considerations make it
necessary to ensure that no unintended start occurs, these stops
are not sufficient.
2.During programming of parameters, the motor may start. Be
certain that no one is in the area of the motor or driven equipment
when changing parameters.
3.A motor that has been stopped may start unexpectedly if faults
occur in the electronics of the drive, or if an overload, a fault in the
supply AC line or a fault in the motor connection or other fault
clears.
4.If the LOCAL/HAND key is activated, the motor can only be
brought to a stop by means of the STOP/OFF key or an external
safety interlock.
Motor Overload Protection
NOTE
Person installing drive is responsible to provide
proper grounding and branch circuit protection
for incoming power and motor overload
according to National Electrical Code (NEC) and
local codes.
WARNING
!
Hazardous Voltage!
Touching electrical parts may be fatal, even after equipment has been
disconnected from the AC input line. To be sure that capacitors have fully
discharged, wait 14 minutes for 208 V and 480 V units and 30 minutes for 600 V
units over 25 hp after power has been removed before touching any internal
component. Failure to wait for capacitors to fully discharge before touching
internal components could result in death or serious injury.
The electronic thermal relay (ETR) in UL listed TR1s provides Class
20 motor overload protection in accordance with the NEC in single
motor applications when parameter 117 is set for ETR TRIP and
parameter 105 is set for the rated motor current.
Page 3
Never ignore warnings, cautions and notes in this manual. They are provided to alert anyone installing,
operating, or maintaining this equipment to potential hazards or ineffective practices. Notes are used to
call special attention to information which, if ignored or not clearly understood, in most cases will result
in degraded or less then optimum equipment operation.
Become familiar with all warnings, cautions, and notes in this manual. These are important guidelines
intended for your safety and for full utilization of the operational features of the equipment.
WARNING
!
CAUTION
!
CAUTION
NOTE
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation which, if not avoided, may result in injury. It may
also be used to alert against unsafe practices.
In dic ates a situa tio n wh ich , if ignored, could result in substantial equipment or property
damage.
Contains important information that, if not clearly understood or ignored, could result in
degraded or less than optimum equipment operation.
3
Page 4
Page 5
Table of Contents
General ................................................................................................................................................................................................................... 7
Standard Service Conditions ................................................................................................................................................................................... 8
UL, C-UL, and CE Conformity ................................................................................................................................................................................. 8
Input Power Delay ................................................................................................................................................................................................ 11
Power Connections ............................................................................................................................................................................................... 12
Input Power Connection ........................................................................................................................................................................................ 13
Motor Wiring Connection ........................................................................................................................................................................................ 13
Terminal Tightening Torque for Optional Auxiliary Control Panels ........................................................................................................................... 14
External DC Bus Connection ................................................................................................................................................................................. 17
High Voltage Form C Relay ................................................................................................................................................................................... 17
Control Connections .............................................................................................................................................................................................. 18
Electrical Installation, Control Terminals .................................................................................................................................................................. 18
Drive Inputs and Outputs ....................................................................................................................................................................................... 18
Programming Control Terminals............................................................................................................................................................................. 19
Control Terminal Functions .................................................................................................................................................................................... 19
Typical Control Connections .................................................................................................................................................................................. 21
Electrical Installation, Control Wiring ....................................................................................................................................................................... 22
DIP Switches 1 through 4 ...................................................................................................................................................................................... 22
Ground Leakage Current .........................................................................................................
Extra Safety Protection .......................................................................................................................................................................................... 23
Application Control Connection Examples .............................................................................................................................................................. 24
Control Panel ........................................................................................................................................................................................................ 25
Keys for Parameter Changes ................................................................................................................................................................................ 25
Local Control......................................................................................................................................................................................................... 26
Changing Numeric Values in a List......................................................................................................................................................................... 28
Quick Menu ........................................................................................................................................................................................................... 29
To Enter or Change Quick Menu Parameter Data .................................................................................................................................................. 29
Example of Changing Parameter Data ................................................................................................................................................................... 29
Manual Initialization of Parameters.......................................................................................................................................................................... 30
TR1 Series VFD Start-Up...................................................................................................................................................................................... 31
Setting Up Drive for Motor Start ............................................................................................................................................................................. 31
HAND Operational Tests........................................................................................................................................................................................ 31
AUTO Operational Tests ........................................................................................................................................................................................ 31
Final Adjustments ................................................................................................................................................................................................... 31
Description of Parameters ...................................................................................................................................................................................... 32
Operation and Display
Parameters 000 through 017 ......................................................................................................................................................................... 32
Setup Configuration and Copying Parameters ........................................................................................................................................................ 32
Setup of User-defined Readout.............................................................................................................................................................................. 33
Load and Motor
Parameters 100 through 118.......................................................................................................................................................................... 38
Procedure for Automatic Motor Adaptation: ............................................................................................................................................................. 40
DC Braking ........................................................................................................................................................................................................... 42
Motor Thermal Protection....................................................................................................................................................................................... 43
References and Limits
Parameters 200 through 228 ......................................................................................................................................................................... 44
Reference Type .................................................................................................................................................................................................... 48
Parameters 300 through 328 ......................................................................................................................................................................... 52
Analog Inputs ........................................................................................................................................................................................................ 55
Feedback Signals in Open Loop ............................................................................................................................................................................ 68
PID for Process Regulation.................................................................................................................................................................................... 69
Differentiator Gain Limit .......................................................................................................................................................................................... 70
Optimization of the Process Regulator ..................................................................................................................................................................... 70
Parameters 500 through 571 ......................................................................................................................................................................... 75
Programming Custom Display Text ........................................................................................................................................................................ 80
Warning Words, Extended Status Word and Alarm Word ........................................................................................................................................ 82
Serial Communication for FC Protocol .................................................................................................................................................................... 83
Packet Communication ........................................................................................................................................................................................... 83
Service Functions
Parameters 600 through 631 ......................................................................................................................................................................... 88
Relay Card Functions
Parameters 700 through 711.......................................................................................................................................................................... 93
Electrical Installation of the Relay Card ................................................................................................................................................................... 93
Status Messages ................................................................................................................................................................................................... 94
Warnings and Alarms............................................................................................................................................................................................. 96
SOFTWARE VERSION NOTICE: The software version number can be read in parameter
6
624, Software Version.
Page 7
General
The specific installation instructions may vary depending upon the
model of TR1 Series VFD being installed. When this occurs, the model
can be identified by a TR1 Type 6XXX number. This number can be
found on the red nameplate on the outside left side of the drive
enclosure, or the outside right side of a drive with an auxiliary
enclosure.
The drive must always be installed vertically. To ensure that no injury
or damage occurs, the drive must always be firmly attached to the wall
or the floor before further installation work is carried out.
Clearances
The drive is cooled by air circulation. For proper cooling, the minimum
distances above and below the unit must be maintained as shown in the
table below. For units in an auxiliary enclosure with the drive mounted
on a backpanel, the required clearances are measured from the top
and bottom of the drive, not the backpanel.
Backplate Requirements
Mount directly to the wall all drives without a backplate. This ensures
that air flow is in contact with the heatsink all the way from the bottom of
the drive. If this is not possible, a metal plate at least as large as the
back of the drive may need to be firmly mounted to the back of the drive
(see tables below). A backplate assembly is available from Trane.
X
X
Drive SizeTop Cleara nceBottom Clearance
1 to 3 hp, 200-240 V
1 to 10 hp, 380-460, 550-600 V
5 to 30 hp, 200-240 V
15 to 75 hp, 380-460, 550-600 V
40 to 60 hp, 200-240 V
100 to 125 hp, 380-460, 550-600 V
150 to 300 hp, 380-460, 550-600 V12" (300mm)12" (300mm)
350 to 600 hp, 380-460 V16" (400mm)Floor mou nt
4" (100mm)4" (100mm)
8" (200mm)8" (200mm)
9" (225mm)9" (225mm)
All drives can be mounted with no side clearance. Sufficient space must
be provided in front of the drive for door swing on units with a hinged
door. TR1 drives 350 hp and above require 25 inches (605 mm) front
space for access. In addition, sufficient room must be available for
installation and service access. On units with an auxiliary enclosure,
the auxiliary enclosure door will have a greater door swing than the
drive. See the dimensional drawings of the auxiliary enclosure which
are included with the drive.
Drives without a backplate must be mounted directly to a solid wall with
no spacers between the drive and the wall. Free-standing drives without
a backplate require a backplate to be mounted.
NEMA 1
Backplate Required
Drive Size Power
5 to 30 hp 200-240 V
15 to 75 hp 380-460 V
150 to 300 hp 380-460 V
15 to 75 hp 550-600 V
200 to 300 hp 550-600 V
NEMA 12
Backplate Required
Drive Size Power
1 to 30 hp 200-240 V
1 to 75 hp 380-460 V
7
Page 8
Plenum Mounting
The drive is UL rated for plenum mounting as well as auxiliary panels
that may be supplied with the drive. If the equipment is to be mounted in
the plenum, allow sufficient access for servicing. All normal clearance,
temperature, humidity limitations and local codes apply.
Standard Service Conditions
The mechanical and electrical components of the TR1 Series VFDs can
be adversely affected by the environment. High temperatures and
harsh environments may reduce life of drive if proper precautions are
not taken.
Grounding Plate
Drives up to 3 hp, 200 to 240 V, and up to 10 hp, 380 to 460 V and
550 to 600 V with a NEMA 1 enclosure have a plastic bottom cover with
provision for conduit entry. To meet UL requirements, the metal
grounding plate must be in place above the plastic bottom cover. The
plate must be grounded to the chassis and the conduit grounded to the
plate. If the grounding plate is not factory installed, it must be installed in
the drives that have a plastic bottom panel to ensure proper grounding
of the conduit to the enclosure. Connect the ground wire from the
grounding plate to the ground tab marked with the ground symbol.
This tab is located near the AC line terminal strip. Mount the bottom
cover on the control unit.
Shielded Wires
Wires to control signals should be shielded to reduce radiofrequency
noise interference. When RFI is a concern, shielded cable should be
used between the drive and the motor.
If unshielded control wires are used, control inputs are subject to signal
disturbances. Such disturbances may affect drive operation. Extreme
noise levels may disturb the microprocessor of the control card.
The shield of the control wires must be grounded at the cable clamp at
the bottom of the drive, but the shield must continue with the cable all the
way up to the control card. The shield is not to be connected to any of
the terminals on the control card. For safety reasons, the insulation
around the shield should only be removed where it is connected to the
cable clamp. The insulation should be left on the shield between the
clamp and the terminals.
Airborne Liquids
Rain, steam, oil, water vapor, high humidity, and such may cause
corrosion of drive components. In such environments, use NEMA 12
enclosures. NEMA 12 enclosures limit the exchange of outside air into
the drive enclosure. Extremely harsh environments may require a
higher levels of protection.
Solids
Dust, dirt, metal drill shavings, foreign objects and the like may cause
mechanical, electrical or thermal failure in the drive. A NEMA 1
enclosure provides a reasonable degree of protection against falling
particles but will not prevent the drive fan from pulling dirty air into the
drive. A typical indicator of excessive levels of airborne particles is dust
around the fan. In dusty environments, use NEMA 12 enclosures.
Corrosive Chemicals
In environments with high temperatures and humidity, corrosive gases
such as sulfur, nitrogen and chlorine compounds cause corrosion to
occur in the drive. Such chemical reactions rapidly affect and damage
electronic components. An indication of corrosion is blackened copper
or oxygenation of steel or aluminum. In such environments, it is
recommended that the equipment be mounted in a cabinet with fresh air
ventilation and that corrosive compounds be kept away from the drive.
A non-ventilated cabinet fitted with an air conditioner as a heat
exchanger may be used. Conformal coated circuit boards may be
specified to reduce the corrosive effects of a harsh environment.
Maximum Relative Humidity
Generally speaking, all conductors coming from a shieldedcontrol
cable must be as short as possible. Long conductor ends attract noise.
The shield must be connected to the chassis by means of the cable
clamp. Long pigtails on the shield reduce the effectiveness of the shield.
8
95% non-condensing
Ambient Temperature
14°F to 104°F (-10°C to 40°C)
14°F to 122°F (-10°C to 50°C) for 200-240 V units of 40 hp or less
and 380-600 V units of 125 hp or less when used with motor leads of
50 ft (15m) or less
UL, C-UL, and CE Conformity
All 200-240 V and 380-460 V TR1 Series VFDs are CE marked. All
drives and option packages are UL and C-UL listed.
To comply with UL508C, input fuses shown in the tables below must be
installed in the power supply to drives which are 208 V above 30 hp,
and 380/460 V and 600 V drives above 75 hp. The fuse ratings in the
tables below are the recommended maximum ratings.
NOTE
Any UL listed Class T fuse with equivalent
voltage and current rating may be used in place
of JJS and JJN fuse types.
Trane recommends input fuses on all drives. If specified as a drive
option, input fuses will be installed by The Trane Company in an
enclosure external to the drive, which may include other optional
features. If not supplied, they must be provided by the drive installer as
part of installation.
600220JJN or JJS
600320JJN or JJS
600440JJN or JJS
600650JJN or JJS
600880JJN or JJS
6011100JJN or JJS
6016150JJN or JJS
6022200JJN or JJS
6027225JJN or JJS
6032300JJN or JJS
6042400JJN or JJS
6052200FW X or FWH
6062250FW X or FWH
Rating (Am ps)Bussmann Type
600 Volt Input
Maximum Fuse
TR1 Type
600210JJS
600310JJS
600415JJS
600620JJS
600825JJS
601135JJS
601650JJS
602260JJS
602780JJS
603290JJS
6042110JJS
6052150JJS
6062175JJS
6072100JJS
6100125FW P
6125175FW P
6150200FW P
6175250FW P
6225350FW P
6275400FW P
200-240 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 250 V maximum.
380-460 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 500 V maximum.
550-600 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 600 V maximum.
Rating (Amps)Bussmann Type
10
Page 11
Internal Drive Fuses
The table below specifies fuses used internally in the TR1 series
drives. Use the specified fuse or an exact replacement only.
Terminal Identification
The connectors for input and output power, auxiliary relay connections,
and external DC bus are identified in the tables below.
Do not connect input power to drive output
motor terminals. Connecting input power to
motor terminals will result in drive failure when
power is applied.
On drives with an auxiliary enclosure, some or all of the power
connections at the drive will be factory made. Custom input and output
terminals may be inside the auxiliary enclosure. See the drawings
supplied with the drive for details on custom terminal blocks and conduit
entry locations for the auxiliary enclosure.
Input Power Delay
To ensure that the input surge suppression circuitry performs correctly,
a time delay between successive applications of input power must be
observed.
The table below shows the minimum time that must be allowed between
applications of input power.
Input voltage380 V415 V460 V600 V
W aiting time48 sec65 s ec89 sec133 sec
11
Page 12
Power Connections
A
A
1. Make all power connections with 75o C rated copper wiring.
2. Conduit entry must be from the bottom on all drives. Conduit entries
are provided on smaller drives. For drives with auxiliary
enclosures, refer to the dimensional drawings provided for conduit
entry locations.
3. To meet UL requirements, install the metalgrounding plate in all
drives that have a plastic bottom. Install the grounding plate just
above the plastic bottom. Ground the metal plate to the chassis and
ground the conduit to the metal plate.
4. The conduit entries provide strain relief for the wires in drives
mounted in NEMA 1 or NEMA 12 enclosures. With chassis
mounted drives, the power and control wires must have strain
relief supplied by the installer. D
provide strain relief.
Run output motor cables from multiple drives
separately. Induced voltage from output motor
cables run together can charge equipment
capacitors even with the equipment turned off
and locked out. Failure to run output motor
cables separately could result in death or
serious injury.
60022.310
60032.610
60043.810
60065.910
60088.810
601111.110
601616.66
602221.46
602726.36
603231.22
604239.92
605250.61/0
606260.41/0
6072751/0
610092.43/0
61251173/0
61501344/0
61751792 x 4/0
62252262 x 4/0
62752702 x 4/0
550 - 600 VAC Input Current/Wire Gage
Maximum
WG
Maximum
AWG
12
All current ratings are in amps.
Page 13
NOTE
Run input power, motor wiring and control
wiring in three separate metallic conduits or
raceways for high frequency noise isolation.
Failure to isolate power, motor and control
wiring could result in less than optimum drive
and associated equipment performance.
WARNING
!
Grounding Hazard!
For operator safety, it is important to ground
drive properly. Follow the grounding guidelines
provided. Failure to follow grounding guidlines
could result in death or serious injury.
Input Power Connection
For drives with no auxiliary enclosure, connect input power to drive
terminals L1, L2, and L3, (terminal numbers 91, 92, and 93). If an auxiliary
enclosure is provided, input power connections are made in the auxiliary
enclosure. Refer to the connection diagrams shipped with the drive.
Size wiring to the input current of the drive as shown in the tables
below. Maximum AWG wire size is also provided. Local codes must be
complied with for cable sizes.
Motor Wiring Connection
For drives with no auxiliary enclosure, connect the motor to drive
terminals U, V, and W (terminal numbers 96, 97, and 98). Terminal 99
is earth ground. If an auxiliary enclosure is provided, refer to the
connection diagrams shipped with the drive. Ground the shield on the
motor wire, if used, at both the drive and the motor.
Grounding
Ground the drive properly. Use a ground wire at least 7 AWG (10mm2).
Connect the ground wire directly to a reliable earth ground. Do not use
the conduit connecting to the drive as a replacement for a ground wire. Do
not ground one drive to another in a daisy chain fashion.
Electronic Thermal Protection
The electronicthermal relay is UL approved for single motor thermal
protection as long as the following is complied with:
1.Parameter 117, Thermal Protection, is set to ETR TRIP.
2.Parameter 105, Motor Current, is set for the full-load nameplate
motor current.
13
Page 14
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the
motor(s) and ground to the values shown in the tables below. Drives
with 200 to 240 volts of 88 amps and less, and drives with 380 to 600
volts of 90 amps and less, have removable terminal blocks with
screws. Larger drives have fixed bolts. (See the drive nameplate for
maximum drive output current.)
550 to 600 VAC Auxiliary Control Panel Tightening Torques
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
16
Page 17
Multiple Motors
The TR1 can control several motors at once, all changing speed
together. The sum of the nameplate currents of all the motors must not
exceed the current rating of the drive.
External DC Bus Connection
Terminals 88 and 89 access the DC bus of the drive. They can provide
DC backup power for the drive or to connect to a 12-pulse input
rectifier.
CAUTION
Motor Damage!
When multiple motors are used, the drive
electronic thermal relay cannot be used to
provide individual motor protection. A separate
motor overload must be supplied for each
motor. Failure to provide individual motor
protection when multiple motors are used could
result in motor or equipment damage.
If the multiple motors are of significantly different sizes, starting problems
may occur. This is because the higher electrical resistance of smaller
motors will require more start voltage than larger motors.
NOTE
Automatic†Motor Adaptation and Automatic
Energy Optimization cannot be used for
multiple motor installations.
WARNING
!
Hazardous Voltage!
Terminals 88 and 89 will be at approximately
150% of line voltage and remain at high voltage
for up to 30 minutes after power has been
removed from the drive. To be sure that
capacitors have fully discharged, wait 14
minutes for 208 V and 480 V units and 30
minutes for 600 V units after power has been
removed before touching terminals 88 and 89.
Failure to wait for capacitors to fully discharge
before touching DC bus terminals could result
in death or serious injury.
CAUTION
Equipment Damage!
Do not connect anything to terminals 88 and 89
without first consulting with Trane. Failure
consult with Trane could result in motor or
equipment damage.
High Voltage Form C Relay
The connections for the high-voltage relay are terminals 01, 02, 03.
The high-voltage relay is programmed in parameter 323, Relay
Output 1.
1+3 normally closed, 1+2 normally open
Max. 240 VAC, 2 Amp
Min. 24 VDC, 10 mA or
24 VAC, 100 mA
Max. wire gage:10 AWG (4 mm
Terminal Torque:5 in-lbs ( 0.5 - 0.6 Nm)
2
)
17
Page 18
Control Connections
All terminals for the low voltage control wires are located under the
protective cover below the keypad. Remove the cover with a
screwdriver or other pointed object as shown bellow.
Drive Inputs and Outputs
The drive operates by receiving control signals. Control input gets to
the drive in three possible ways. One way is from input signals through
the wiring connected to the drive control terminals. The drive control
terminals are located below the LCP keypad.
Another control source is through serial communication from a serial
bus. A serial communication protocol supplies commands and
references to the drive and reads status and data from the drive. The
serial bus connects to the drive through the RS-485 serial port. Use of
serial communication may require installation of a corresponding option
card.
A building management system, remote sensors, a speed command
from associated equipment, or a PLC (programmable logic controller)
are examples of possible remote drive controllers.
The third way for drive control input is through the keypad on the front
of the drive when operating in local (hand) mode. These inputs include
start, stop, reset, and speed reference.
Electrical Installation, Control Terminals
Torque control terminals to 5 in-lbs (0.5-0.6 N-m)
Max. wire size: 16 AWG (1.5mm
The diagram below shows the location of the control terminals. The
programming section of the manual covers the programmable terminals
in greater depth.
2
)
Input Signals
The drive can receive two types of remote input signals: digital or
analog. Digital inputs are wired to terminals 16, 17, 18, 19, 20
(common), 27, 29, 32, and 33. Analog inputs are wired to terminals 53,
54, and 55 (common), or terminal 60.
Analog signals can be either voltage (0 to +10 VDC) connected to
terminals 53 and 54, or current (0 to 20 mA or 4 to 20 mA) connected
to terminal 60. Analog signals can be varied like dialing a rheostat up
and down. The drive can be programmed to increase or decrease
output in relation to the amount of current or voltage. For example, a
sensor may supply a variable current. The drive output, in turn,
regulates the speed of the motor connected to the drive in response to
that analog signal.
Digital signals are a simple binary 0 or 1 which, in effect, act as a
switch. Digital signals are controlled by a 0 to 24 VDC signal. A voltage
signal lower than 5 VDC is a logic 0. A voltage higher than 10 VDC is a
logic 1. Zero is open, one is close. Digital inputs to the drive are
switched commands such as start, stop, reverse, coast, reset, and so
on. (Do not confuse these digital inputs with serial communication
formats where digital bytes are grouped into communication words and
protocols.)
18
The RS-485 serial communication connector is wired to terminals (+)
68 and (-) 69. Terminal 61 is common and may be used for terminating
shields only when the control cable is run between VLT drives, not
between drives and other devices.
Page 19
Output Signals
The drive also produces output signals that are carried through either
the RS-485 serial bus or terminals 42 and 45. Output terminals 42 and
45 operate in the same manner as the inputs. These terminals can be
programmed for either a variable analog signal in mA or a digital signal
(0 or 1) in 24 VDC. In addition, the terminals can provide a pulse
reference of 0 to 32,000 pulses. Output analog signals generally report
the drive frequency, current, torque and so on to an external controller
or system. Digital outputs can be control signals used to open or close
a damper, for example, or send a start or stop command to auxiliary
equipment.
Additional terminals are 01, 02, and 03, which are a Form C relay
output. Terminals 04 and 05 are a 1 A low voltage relay output.
Terminals 12 and 13 provide 24 VDC low voltage power, often used to
supply power to the digital input terminals (16-33). Those terminals
must be supplied with power from either terminal 12 or 13, or from a
customer supplied external 24 VDC power source. Improperly
connected control wiring can be the cause of a motor not operating or
the drive not responding to a remote input.
Programming Control Terminals
Control terminals must be programmed. Each terminal has specific
functions it is capable of performing and a numbered parameter
associated with it. See the table below for associated parameter
numbers. The setting selected in the parameter enables the function of
the terminal.
It is important to confirm that the control terminal is programmed for the
correct function. See Control Panel for details on operator interface and
changing parameters.
In addition, the input terminal must be receiving a signal. Confirm that
the control and power sources are wired to the terminal. Then check
the signal.
Control Terminal Functions
The following is a description of the functions of the control terminals.
Many of these terminals have multiple functions determined by
parameter settings.
Terminal No.Function
01, 02, 03FormC relay output. Maximum 240 VAC, 2 A.
Minimum 24 VDC, 10 mA or 24 VAC, 100 mA.
(Location of Form C relay output varies with unit
type. See connection diagram with unit for
location.)
04, 0530 VAC, 42.5 VDC, 1 A relay output can be used
for indicating status and warnings.
12, 13Voltage supply to digital inputs and external
transducers. For the 24VDC to be used for digital
inputs, switch 4 on the control card must be closed,
position on. The maximum output current is 200 mA.
16 - 33Digital inputs. R
>10V = logical 1. See parameters 300 through
307, Digital Inputs.
20Common for digital inputs.
39Common for analog and digital outputs.
42, 45Analog and digital outputs for indicating frequency,
reference, current and torque. The analog signal
is 0 to 20 mA, or 4 to 20 mA at a maximum of
500Ω. The digital signal is 24VDC at a minimum
of 600Ω. See parameters 319-322, Analog/digital
Outputs.
5010 VDC, 17mA maximum analog supply voltage to
potentiometer and thermistor.
=2kohm. <5V = logical 0,
Signals can be checked in two ways. Relay status can be selected in
the display using the [DISPLAY MODE] key (see Display Modes), or a
voltmeter may be used to check for voltage at the control terminal.
In summary, for proper drive functioning, the drive control terminals
must be:
Control terminals must be programmed. Each terminal has specific functions it is capable of performing and a numbered parameter associated with it. The setting
selected in the parameter enables the function of the terminal.
53, 540 to 10 VDC voltage input, R = 10 kΩ.
55Common for analog inputs. This common is
isolated from the common of all other power
supplies. If, for example, the drives 24 VDC
power supply is used to power an external
transducer which provides an analog input signal,
terminal 55 must be wired to terminal 39.
Control Terminals and Associated Parameter
19
Page 20
Control Terminal Functions (continued)
Terminal No.Function
600 to 20 mA or 4 to 20 mA, analog current input,
R=188 Ω. See parameters 314 through 316.
61Shield for serial communication.
68, 69RS-485 interface and serial communication. When
the drive is connected to an RS-485 serial
communication bus, DIP switch settings on the
control card may have to be reset. See DipSwitches 1 through 4 in this manual.
20
Electronic Control Terminals
Page 21
Typical Control Connections
Shown below are typical interfaces between the TR1 and other
components in an HVAC system. The terminal numbers and the
functions of the terminals are identical on all TR1s. An optional relay
card, not shown, can provide four additional Form C output relays.
The RS-485 connections allow direct communication through the
drives built-in serial communication protocols.
Typical TR1 Wiring
3 Phase
Power
Input
External
DC Bus
Connection
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
Preset Speed*
91 (L1)
92 (L2)
93 (L3)
99 (PE)
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
60 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN)
29 (D IN)
SW4
Switch Mode
Power Supply
10 V DC
17 mA
+-
EIA-485
Interface
24 V DC
200 mA
+-
5 V
SW2SW3
(COM EIA-485) 61
(U) 96
(V) 97
(W) 98
(PE) 95
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
(RELAY) 04
(RELAY) 05
(COM A OUT) 39
(A OUT) 42
0 V
(A OUT) 45
(P EIA-485) 68
(N EIA-485) 69
Motor
Fault Indication*
240 V AC, 2 A
Run Indication*
30 V AC, 1 A
Output Current Indication*
4 - 20 mA
Output Speed Indication*
4 - 20 mA
+
EIA-485
-
Setup Select*
Setup Select*
32 (D IN)
33 (D IN)
* The operation of all control inputs and outputs is programmable.
* Typical terminal functions are shown.
21
Page 22
NOTE
Run input power, motor wiring and control
wiring in three separate metallic conduits or
raceways for high frequency noise isolation.
Failure to isolate power, motor and control
wiring could result in less than optimum drive
and associated equipment performance.
Electrical Installation, Control Wiring
Torque: 5 - 6 in-lbs
Screw size: M3
Shielded control wires are recommended. To reduce interference from
electrical noise, ground the cable shield at a cable clamp, as shown
below, at both ends. Connect the shield to the grounded clamp. Very
long control wires may create 60 Hz interference. To resolve this,
connect one end of the shield to earth with a 0.1µF capacitor, keeping
the leads as short as possible. If interference persists, disconnect the
grounded shield connection at the end opposite to the drive.
DIP Switches 1 through 4
DIP switches are located on the control card.
They are used for serial communication and the common of digital
inputs 16 through 33. The switch positions shown are the factory
settings.
Sw itc h 1 i s no t used .
Switches 2 and 3 are used for terminating serial communication. On the
first and last drive in a multiple device network, or on the only drive of a
single drive network, switches 2 and 3 must be ON (the default setting).
On all other drives in a multiple device network, set switches 2 and 3 to
OFF.
Switch 4 separates the common for the internal 24 VDC supply from the
common of the external 24 VDC supply. Normally this switch is ON and
the power supply is present at terminals 12 and 13. Set Switch 4 to the
OFF position when an external 24 VDC supply is used.
Ground Leakage Current
It is normal for there to be some leakage current from the drive to earth
ground. Paths of current leakage are shown on the drawing below.
The leakage current will exceed 3.5 mA.
22
Paths of Normal Current Leakage to Ground
Page 23
Galvanic Isolation
Galvanic isolation offers protection from electric shock. All control
terminals of all TR1 drives, and terminals 1 through 3 of the relay
output, offer galvanic isolation. The galvanic isolation in the TR1
conforms to the European standard EN 50178. (See figure below.)
The components that make up the galvanic isolation are:
1.Power supply, including signal isolation.
2.Gate drive for the IGBTs, the trigger transformers and optocouplers.
3.The output current Hall effect transducers.
Galvanic Isolation
Extra Safety Protection
Residual Current Device (RCD) relays for ground fault protection, or
multiple protective grounding, can be used as extra safety protection,
provided that local safety regulations are complied with. In case of a
grounding fault, the fault current may contain a DC component. If RCD
relays, also known as Earth Leakage Circuit Breakers (ELCB), are
used, they may be suitable for protection of 3-phase equipment with a
bridge rectifier and for a brief current surge at power-up.
Electrical Noise
In general, electrical noise can be divided into two forms: wire-borne
electromagnetic interference (EMI), and radiating radio frequency
interference (RFI).
Using shielded motor cables reduces RFI but increases EMI. This is
because shielded wires have a greater capacitance than unshielded
wires. Unshielded input power connections to the drive generate more
noise in the radio frequency range on the AC line. The shield reduces
the radiated noise, but increases the low-frequency electromagnetic
noise on the AC line. But, since the noise current is taken back to the
unit through the shield, only a small electromagnetic field is generated
from shielded motor wires.
With an EMI filter, the noise level on the AC line will be reduced to about
the same level for shielded and unshielded wires alike.
Connect the motor wiring shield, if used, in the enclosure of the drive as
well as at the motor. Use shield brackets to avoid pigtail shield ends.
Even short pigtails increase the shields impedance at higher
frequencies, which reduces the shields effect and increases the noise
produced.
It is generally easier and less complicated to use unshielded motor
wires than shielded cables. If unshielded wires are used, the RFI will
be greater. But, since the strength of the radiated signal decreases with
distance from the signal source, radiated noise is generally not a
problem.
To reduce the noise level from the total system (drive + installation)
make the motor wiring as short as possible.
Provide separate conduits, or raceways, for power, motor and control
wiring to provide the greatest immunity from distortion.
Since leakage current is greater than 3.5 mA, reinforced grounding
must be provided if compliance with EN 50178 is required. The relays
must be suitable to meet the following requirements:
1) protecting equipment with a DC content (Din VDE 0664) in the fault
current (3-phase rectifier)
2) power-up with short pulse-shaped charging current to ground
3) high leakage currents
RCD fault relays type B comply with these requirements according to
the norm IEC 755-2.
23
Page 24
Application Control Connection Examples
Two-wire Start/Stop
In Auto mode, closing the contact to terminal 18 will make the drive run.
In any mode, opening the safety interlock contact to terminal 27 will stop
the drive.
Set Parameter 302 to Start.
Set Parameter 304 to Safety Interlock.
Digital Speed Up/down
Closing the switch to terminal 32 will make the drive accelerate. Closing
the switch to terminal 33 will make the drive decelerate.
Run Permissive
After receiving a run command,
the drive will apply power to the
damper motor and wait until it
receives permission via the
switch that is connected to
terminal 16.
Set Parameter 300 to Run Permissive.
Set Parameter 302 to Start.
Set Parameter 304 to External Fault.
Set Parameter 323 to Start Signal Applied.
Two Feedback Signals
The drive processes two
independent feedback
signals during closed loop
operation. It can respond to
the sum, difference,
average, minimum or
maximum of these signals.
Set Parameter 306 to Speed up.
Set Parameter 307 to Speed down.
Set Parameter 305 to Freeze reference.
Potentiometer Reference
A manual potentiometer is used as a input reference for the drive.
Set Parameter 308, Terminal 53, Analog Input Voltage, to Reference.
Set Parameter 309, Terminal 53, Min. Scaling, to 0 V.
Set Parameter 310, Terminal 53, Max. Scaling, to 10 V.
Set Parameter 308 to Feedback.
Set Parameter 311 to Feedback
Set Parameter 417 for the desired operation.
Transmitter Connection
The drives internal 24
VDC power supply is
used to power an
external 4 to 20 mA
transducer.
Set Parameter 314, Terminal 60, Analog Input Current, to
correspond to the purpose of the 4 to 20mA signal.
Set Parameter 315, Terminal 60, Min. Scaling, to 4 mA
Set Parameter 316, Terminal 60, Max. Scaling, to 20mA.
Because the commons of the +24 VDC power supply and the input
reference follower have separate circuit commons, it is necessary to
connect a jumper between terminals 39 and 55.
24
Page 25
Control Panel
The Local Control Panel (LCP), normally mounted on the front of the
drive, is a complete interface for programming and operating the drive.
The control panel can be removed from the drive and installed up to 10
feet (3 meters) from the drive by using a remote mounting kit.
The control panel has five functions:
1.Display
2.Keys for changing the display
3.Keys for changing programming parameters
4.Indicator lamps
5.Keys for controlling drive operation
The LCP uses a four-line, alpha-numeric, back-lit, LCD display. The
display can show four operating data values and three operating
condition values continuously. During programming, all the information
required for quick, effective parameter setup of the drive will be
displayed. As a supplement to the display, there are three indicator
lamps for power on (ON), warning (WARNING) and alarm (ALARM).
All drive parameters can be changed from the control panel, unless this
ability has been locked out by setting parameter 016, Lock for DataChange, to Locked, or by a digital input to terminals 16 through 33. See
the related parameters for more information.
Keys for Parameter Changes
The keys are divided into groups by function. The keys between the
display and indicator lamps are used for parameter setup, selecting the
display indication during normal operation and controlling the drive
speed during local speed control operation. The keys below the
indicator lamps are used for Start/Stop control and selection of the
operating site.
The DISPLAY MODE key is used to change the mode
of the display or to return to the Display Mode from
either the Quick Menu or the Extend Menu mode.
The QUICK MENU key gives access to the parameters
available for the Quick Menu setup. Parameters in this
menu are the 12 most important setup parameters for
the drive.
The EXTEND MENU key gives access to all parameters.
The CHANGE DATA key is used for changing the value
of a parameter selected either in the Extend Menu or
the Quick Menu mode. The desired parameter is first
selected. Then the CHANGE DATA key is pressed to
enable the editing of the parameter. The underline in the
display will move under the parameters value to show
that it is being edited.
The CANCEL key is used if a change of the selected
parameter is not to be carried out.
The OK key is used for confirming a change of the
parameter selected.
25
Page 26
The + and - keys are used to scroll through parameters
and to change the value of a chosen parameter. These
keys are also used to change the local reference. In
Display Mode, these keys are used to switch between
readouts.
The v and w keys are used to select a parameter
group and also to move the cursor to the desired digit
when changing numerical values.
Indicator Lamps
At the bottom of the control panel is a red alarm LED, a yellow warning
LED, and a green poweron LED.
AUTO START is used if the drive is to be started via the
control terminals and/or serial communication. When a
remote start signal is active, the drive will start if the
AUTO START key has been pressed.
WARNING
!
Unintended Start!
In Auto Mode, a start signal via digital inputs
may cause drive to start at any time. The drive,
motor, and any driven equipment must be in
operational readiness. Failure to be in
operational readiness in Auto Mode could result
in death, serious injury, or equipment or
property damage.
red yellow green
If certain threshold values are exceeded, the alarm and/or warning
lamps will flash and text describing the alarm or warning condition will
be displayed.
Local Control
Below the indicator lamps are keys which are used to determine the
point of control. Each of these keys can be individually enabled or
disabled using parameter 012 through 015. The Hand Start and Auto
Start keys will also be disabled if any of the control terminals are
programmed for either Remote Hand or Remote Auto.
The HAND START key is used if the drive is to be
started from the control panel. Pressing HAND START
will give a start command to the drive.
NOTE
If a minimum speed is set in parameter 201,
Output Frequency, Low Limit, the motor will
start and ramp up to this frequency when HAND
START is pressed. If drive is running in Auto
Mode when the HAND START key is pressed,
drive control will switch to Hand Mode.
The OFF/STOP key is used for stopping the connected
motor in either the Hand or Auto mode. Enable or
disable via parameter 013. If this stop function is
activated, the second line in the LCD display will flash.
The RESET key is used for manually resetting the drive
after a fault trip (alarm). In this case, the top line of the
display will show TRIP (RESET). If the top line of the
display shows TRIP (AUTO START), the drive will
automatically restart. If the top line of the display shows
TRIPLOCK (DISC. MAINS), input power to the drive
must be removed before the trip can be reset.
Display Modes
In Auto operational mode, information is displayed in any of three
programmable displays. Pressing the DISPLAY MODE key enters
display mode and toggles between modes I and II. While in Display
mode, the [+] and [-] keys scroll through all data display options. When
in Mode II, holding down the DISPLAY MODE key enters Mode III
which identifies the units on the top line that the display is showing.
Mode IV is available only in local Hand operation and displays the
local speed reference.
In normal operation, three data readouts can be shown on the first
(top) line of the display. Parameters 008, 009 and 010 select the data
displayed on the top line. One readout is available for the large display
(line 2). Parameter 007, Large Display Readout, selects the data
displayed on line 2. The list on the next page defines the operating data
that can be selected for the display readouts.
During an alarm (fault trip), ALARM and the alarm number are shown
on the large display. An explanation is given in line 3 or in lines 3 and
4. For a warning, WARN. and the warning number are shown with an
explanation in line 3 and/or 4. Both alarms and warnings cause the
display to flash.
Line 4 (bottom line), in normal operation, automatically displays the
operating status of the drive.
The active setup number and an arrow indicating the direction of motor
rotation is shown on the right side of the large display. Clockwise
indicates forward and counterclockwise indicates reverse. The arrow
body is removed if a stop command is given or if the output frequency
falls below 0.01 Hz.
26
Page 27
The table below gives the operating data options for the first and
second lines of the display.
Data Item:Unit:
Resulting reference, %%
Resulting reference unit chosen in par. 415
FrequencyHz
% of maximum output frequency%
Motor currentA
PowerkW
PowerHP
Output energykWh
Hours runhours
User defined readout unit chosen in par. 006
Setpoint 1 unit chosen in par. 415
Setpoint 2 unit chosen in par. 415
Feedback 1 unit chosen in par. 415
Feedback 2 unit chosen in par. 415
Feedback unit chosen in par. 415
Motor voltageV
DC link voltageV
Thermal load on motor%
Thermal load on TR1%
Input status, digital inputbinary code
Input status, analog terminal 53V
Input status, analog terminal 54V
Input status, analog terminal 60mA
Pulse referenceHz
External reference%
Heat sink temperature
Display Mode I:
In Display mode I, the drive is in Auto mode with reference and control
determined via the control terminals. Following is an example in which
the drive is running in setup 1, in Auto mode, with a remote reference,
and at an output frequency of 40 Hz.
o
C
Status line (Line 4): Additional automatic displays for the drive status
line are shown below. See Status Messages section in this manual for
additional information.
80.0% 5.08A 2.15HP
SETUP
40.0Hz
1
AUTO REM. RUNNING
HAND
OFF
LOCAL
STOP
RAMPING
JOGGING
.
.
.
.
STAND BY
The left indicator on the status line displays the active control mode of
the TR1 drive. AUTO is displayed when control is via the control
terminals. HAND indicates that control is local via the keys on the LCP.
OFF indicates that the drive ignores all control commands and will not
run.
The center part of the status line indicates the reference element that is
active. REM. (Remote) means that reference from the control terminals
is active, while LOCAL indicates that the reference is determined via the
[+] and [-] keys on the control panel.
The last part of line 4 indicates the drive's operational status, for
example: RUNNING, STOP, or RUN REQUEST, and so on.
Display Mode II:
This display mode shows three operating data values in the top line
programmed via parameters 008, 009, and 010. Pressing the
DISPLAY MODE key toggles between Display modes I and II.
The text in line 1, FREQUENCY, describes the meter shown in the
large display. Line 2 (large display) shows the current output
frequency (40.0 Hz), direction of rotation (reverse arrow), and active
setup (1). Line 3 is blank. Line 4 is the status line and the information is
automatically generated for display by the drive in response to its
operation. It shows that the drive is in auto mode, with a remote
reference, and that the motor is running.
FREQUENCY
40.0 Hz
AUTO REMOTE RUN
SETUP
1
100% 7.8A 5.9HP
SETUP
50.0 Hz
1
AUTO REMOTE RUN
27
Page 28
Display Mode III:
Press and hold the [DISPLAY MODE] key while in ModeII. Mode III is
visible as long as the key is depressed. The top line changes to identify
the data names and units displayed. Lines 2 and 4 are unchanged.
When the key is released, the display returns to Mode II.
Changing Numeric Values
If the chosen parameter represents a number value, the flashing digit
can be changed by means of the [+]and [-] keys. Position the cursor
by using the [<]and [>] keys, then change the data value using the [+]
and [-] keys.
REF% CURR.A POW.HP
SETUP
50.0 Hz
1
AUTO REMOTE RUN
Display Mode IV:
This display mode is available when local reference is selected. In this
display mode, the speed reference is increased or decreased via +/- keys.
The first line shows the present speed reference. The second line
shows the present drive output frequency. The third line show a bar
graph of the relative value of the present drive output frequency in
relation to the maximum frequency.
USE +/- 56Hz
SETUP
40.0Hz
1
0 ••-----60
FREQUENCY
SETUP
24.2 Hz
1
205 MAX. REFERENCE
000060.000 Hz
The selected digit is indicated by a flashing cursor. The bottom display
line gives the data value that will be entered (saved) by pressing the
OK button. Use CANCEL to ignore the change.
Changing Functional Values
If the selected parameter is a functional value, the selected text value
can be changed by means of the [+] and [-] keys.
MOTOR CURRENT
SETUP
3.90 A
1
210 REFERENCE
TYPE SUM
HAND LOCAL RAMPING
Changing Data
Regardless of whether a parameter has been selected under the Quick
Menu or the Extend Menu, the procedure for changing data is the
same. Pressing the CHANGE DATA key gives access to changing the
selected parameter. Line 3 displays the parameter number and title.
The underlined function or number flashing in line 4 on the display is
subject to change.
The procedure for changing data depends on whether the selected
parameter represents a numerical data value or a function.
The functional value flashes until signing off by pressing the OK button.
The functional value has then been selected. Use CANCEL to ignore
the change.
Changing Numeric Values in a List
A few parameters offer numeric lists of values that can be selected from
or changed. This means that if the numeric value is not listed, a value
may be entered using the procedure for changing numeric values. This
applies to parameter 102, Motor power, parameter 103, Motor voltage,
and parameter 104, Motor frequency.
28
Page 29
Quick Menu
The Quick Menu gives access to the 12 most important setup
parameters of the drive. After programming the Quick Menu items, the
drive will, in many cases, be ready for operation. The Quick Menu
parameters are described in the table below. A detailed description of
the functions are given in the Programming section of this manual. The
Quick Menu is activated by pressing the QUICK MENU key on the
control panel.
Quick MenuParameter
Item NumberName
1001 LanguageSelects language used for all displays.
2102 Motor PowerSets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102, Motor Power, to convert HP to kW.
3103 Motor VoltageSets output characteristics of drive based on voltage of motor.
4104 Motor FrequencySets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency.
5105 Motor CurrentSets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor.
6106 Motor Nominal SpeedSets output characteristics of drive based on nominal full load speed of
motor.
7201 Minimum FrequencySets minimum controlled frequency at which motor will run.
8202 Maximum FrequencySets maximum controlled frequency at which motor will run.
9206 Ramp Up TimeSets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
10207 Ramp Down TimeSets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
11323 Relay 1 FunctionSets function of high voltage Form C relay.
12326 Relay 2 FunctionSets function of low voltage Form A relay.
Description
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the
following procedure.
1.Press Quick Menu key.
2.Use t and u keys to find parameter group to edit.
3.Use + and - keys to find parameter you chose to edit.
4.Press Change Data key.
5.Use + and - keys to select correct parameter setting. Or, to move
to digits within a number, use t and u arrows. Flashing cursor
indicates digit selected to change.
6.Press Cancel key to disregard change, or press OK key to accept
change and enter new setting.
Example of Changing Parameter Data
Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change
the ramp up time to 100 seconds in accordance with the following
procedure.
1.Press Quick Menu key.
2.Press + key until you reach Parameter 206, Ramp Up Time.
3.Press Change Data key.
4.Press t key twice hundreds digit will flash.
5.Press + key once to change hundreds digit from 0 to 1.
6.Press u ke y to move cur sor to t ens digit.
7.Press - key until 6 counts down to 0 and setting for Ramp UpTime reads 100 s.
8.Press OK key to enter new value into drive controller.
NOTE
Programming additional parameter functions
available through Extended Menu key is done
in accordance with same procedure as
described for Quick Menu functions.
29
Page 30
Extended Menu
In some applications, the Quick Menu will not access all additional
parameters necessary to set up the drive. To access all parameters,
including Quick Menu items, use the Extended Menu. The Extended
Menu is enabled by pressing the EXTEND. MENU key. The
Programming section of this manual describes in detail all the
parameters available through the Extended Menu.
Manual Initialization of Parameters
NOTE
Manual initialization using either procedure
described below, or in parameter 620, will reset
the drive to standard default parameters. Any
special application programming performed at
the factory, during start-up or thereafter, will be
lost. As a backup, upload drive settings into the
driveís local control panel (LCP) keypad as
described in parameter 004, LCP Copy.
It is possible to reset parameters back to their original default values at
once. To reset the drive parameters to their read only default values, first
remove power from the drive. Then press and hold the DISPLAY
MODE, the CHANGE DATA and the OK keys down simultaneously
while reapplying power. Continue to hold down the three keys. Shortly
after power is reapplied, the bottom line of the display will read
Initialized. After the display stops changing, release the keys. If
Initialized did not appear, repeat the procedure.
Uploading Parameters
At any time the present parameters may be copied to the local control
panel (LCP). This may be useful when setting up multiple drives. It is
also useful when it is desired to return to a previous set of parameters.
See parameter 004, LCP Copy, for more information.
Manually initializing the drive using either the procedure described
above or parameter 620, Operating Mode, does not change the
values uploaded to the local control panel.
These parameters are not reset by manual initialization:
Parameter 600Operating hours
Parameter 601 Hours run
Parameter 602 kWh counter
Parameter 603Number of power-ups
Parameter 604Number of overtemperatures
Parameter 605Number of overvoltages
Initialization can also be done using Parameter 620.
30
Page 31
TR1 Series VFD Start-Up
Pre-installation Checks
1. Compare drive model number to what was ordered.
2. Ensure each of following are rated for same voltage:
Drive
Power line
Motor
3. Record following motor data:
Voltage
Frequency
Full load current
Full load speed
Power convert HP to kW (See conversion table in parameter
102, Motor Power, in this manual.)
4. Ensure that rated drive current is equal to or greater than total full
load current.
For multiple motor operations, add up full load current ratings of
all motors.
Drive can be at most one size smaller than motor.
If drive rating is less than motor, full motor output cannot be achieved.
5. Check motor wiring:
Any disconnect between drive and motor should be interlocked
to drive safety interlock circuit to avoid unwanted drive trips.
No power factor correction capacitors can be connected between
drive and motor.
Two speed motors must be wired permanently for full speed.
Y-start, r-run motors must be wired permanently for run.
Installation Checks
1. Input fusing in power supply for all drives must be provided (see
Input Fuses section in this manual).
2. Environmental concerns for standard NEMA 1 drive:
Clean air supply
Dry air (max 95% relative humidity, non-condensing)
o
14
F to 104oF ambient temperature operating range, or as rated
3,300 foot maximum elevation with no derating
3. Mounting
Vertical
Drives with heat sink fins exposed in back of unit must be
mounted against a solid surface (see Clearances section in this
manual).
Keep any construction dirt out of drive.
4. Wiring
Wire drive in accordance with instructions and diagrams received
with drive.
Separate conduits must be provided to drive for input power,
output power, and control wiring.
Note that safety interlock and remote run/stop circuitry is 115 VAC
for drives with bypasses.
Use knockouts or conduit entry plates. Avoid metal shavings in cabinet.
Protect signal wires from noise.
Ground each drive individually.
Double check input and output power wiring for correct location.
Setting Up Drive for Motor Start
Enter motor nameplate data into drive through Quick Menu.
1. Parameter 101:
If one motor is connected to drive, set to AEO FUNCTION.
If more than one motor connected to drive, set to MULTIPLE
MOTORS. (Parameter 108, MULTIPLE MOTOR STARTING
VOLTAGE should be adjusted later to provide reliable starts and
minimum starting current.)
2. Parameter 102, MOTOR POWER (in kW) (See conversion table in
parameter 102, Motor Power, in this manual.)
3. Parameter 103, MOTOR VOLTAGE
4. Parameter 104, MOTOR FREQUENCY
5. Parameter 105, MOTOR CURRENT
6. Parameter 106, MOTOR SPEED
7. Parameter 107, (optional) select AUTOMATIC MOTOR ADAPTATION and run AMA in accordance with procedure in parameter
107, Automatic Motor Adaptation, in this manual.
8.Press HAND START key to initiate operation in local control.
HAND Operational Tests
1. Check motor rotation from drive. If incorrect, disconnect input
power from drive and reverse two leads between drive and motor.
2. If a bypass is provided, check motor rotation in bypass mode. If
incorrect, disconnect input power from drive and reverse two input
power leads.
3. Accelerate motor quickly to full speed and verify operation.
4. Decelerate motor quickly to stop and verify operation.
5. Operate motor over entire speed range while closely checking for
resonance.
AUTO Operational Tests
1. Ensure that drive follows run/stop and safety interlock commands
from system.
2. Ensure drive follows speed reference, or feedback, from system.
Final Adjustments
1. Use parameters 216 through 220 to reject any resonant points.
2. Lock out keypad functions, as required.
General Troubleshooting
1. Display Messages:
AUTO STARTDrive has tripped off and is in process of
automatically restarting.
TRIPDrive has tripped off. Press RESET to start.
TRIP LOCKEDDrive has tripped off. Remove and apply
power before restarting with RESET.
2. Refer to Warnings and Alarms section in this manual.
3. Check tightness of all connections and wires for proper location.
4. Measure input signals.
5. Check drive input and output for balanced voltage and current.
31
Page 32
Programming
Using the ExtendMenu key, it is possible to access to all
the parameters for the drive.
Description of Parameters
Parameters are grouped by function. The groups are:
Operation and DisplayParameters 001 through 017
Load and MotorParameters 100 through 117
References and LimitsParameters 200 through 228
Input and OutputsParameters 300 through 328
Application FunctionsParameters 400 through 427
Serial CommunicationParameters 500 through 566
Service FunctionsParameters 600 through 631
Relay Card FunctionsParameters 700 through 711
The numbers shown in the square brackets ([ ]) after the parameter
values are used in serial communications to choose the parameter
value from a numerical list. They are not shown on the display panel
when programming the drive locally. The ✭ symbol indicates readonly default factory settings. Special default parameter settings for
various Trane TR1 Series VFD applications are noted under FactorySettngs in this manual.
Operation and Display
Parameters 000 through 017
This parameter group deals with the display, control keys and other
general functions.
001 Language(Language)
Value:
✭ English (ENGLISH)[0]
German (DEUTSCH)[1]
French (FRANCAIS)[2]
Danish (DANSK)[3]
Spanish (ESPAÑOL)[4]
Italian (ITALIANO)[5]
Swedish (SVENSKA)[6]
Dutch (NEDERLANDS)[7]
Portuguese (PORTUGUESA)[8]
Finnish (SUOMI)[9]
Function:
This parameter determines the language used on the display.
Description of choice:
Select the display language.
Setup Configuration and Copying Parameters
The TR1 has four independent parameter setups that can be programmed. Each setup acts independently in controlling the drive.
Example applications would be programming different setups for
day/night or summer/winter operation. Any of the four setups can be
used.
The setup is selected in parameter 002, Active Setup, for programming
and operation. Setups are changed manually by switching between
active setups in parameter 002. It is also possible to change setups
through digital inputs or serial communication by selecting Multi-setup in
parameter 002 and providing an external signal.
The number of the active setup selected is shown on the keypad
display under Setup in the second line of the display.
A short cut to programming more than one setup is possible by using
parameter 003, Setup Copy. This enables copying one setup to
another setup. After copying parameter settings from one setup, just
those parameters unique to the other setups need be changed.
All setups can be transferred from one TR1 drive to another by using
the removable keypad. Parameter 004, LCP Copy, allows this function.
First, upload all parameter values to the keypad. The keypad can then
be removed and plugged into another TR1 drive where all parameter
values can be downloaded. If motor or drive sizes differ, DownloadPower-independent Parameters can be selected in parameter 004 to
omit downloading motor and current dependent data.
This parameter defines the setup number that controls the drive.
All parameters can be programmed in four individual parameter setups,
Setup 1, Setup 2, Setup 3 and Setup 4.
There is also a pre-programmed, read-only setup, called Factory
Setup.
Description of choice:
The Factory Setup contains the parameter values preset at the factory.
This data can be used as a default setup to reset parameters to a
known state.
Setups 1 through 4 are four individual setups that can be selected as
required.
Multi-setup is used if remote switching between different setups is
required. Terminals 16, 17, 29, 32, 33 and the serial communication
port can be used for switching between setups.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
32
Page 33
Setup Change Connection Example
004LCP Copy(LCP COPY)
Value:
✭ No copying (NO COPY)[0]
Upload all parameters
(UPLOAD ALL PARAMET.)[1]
Download all parameters
(DOWNLOAD ALL PARAM.)[2]
Download power-independent parameters
(DOWNLOAD SIZE INDEP.)[3]
Function:
Parameter 004, LCP Copy, is used to copy all parameter setups to or
from the Local Control Panel (LCP). This can be used to store a
backup copy of all parameters in the LCP or to copy all setups from
one drive to another.
Selection of setup using terminals 32 and 33.
See the descriptions of parameters 300 through 307.
Parameter 306 = Selection of Setup, lsb
Parameter 307 = Selection of Setup, msb
Parameter 002 = Multi Setup
003Copying of Setups(Setup Copy)
Value:
✭ No copying (NO COPY)[0]
Copy active Setup to Setup 1
(COPY TO SETUP 1)[1]
Copy active Setup to Setup 2
(COPY TO SETUP 2)[2]
Copy active Setup to Setup 3
(COPY TO SETUP 3)[3]
Copy active Setup to Setup 4
(COPY TO SETUP 4)[4]
Copy active Setup to all (COPY TO ALL)[5]
Function:
A copy is made from the active setup selected in parameter 002, Active
Setup, to the setup or setups selected in parameter 003, Copying of
Setups.
NOTE
Copying is only possible when drive is stopped.
Description of choice:
The copying starts when the required copying function has been
selected and the OK key has been pressed.
Description of choice:
Select Upload All Parameters if all parameter values are to be copied
from the drive to the LCP.
Select Download All Parameters if all parameter values are to be
copied from the LCP to the drive on which the control panel has been
mounted.
Select Download Power-independent Parameters if only the power-
independent parameters are to be downloaded. This allows the
parameters from one drive to be easily copied to another drive of a
different size. Settings in parameters 102, 103, 104, 105, 106, 215,
221, and 222 are not downloaded using this function.
NOTE
Copying is only possible when drive is stopped.
Setup of User-defined Readout
Parameter 005, Maximum Value of User-defined Readout, and
Parameter 006, Unit for User-defined Readout, allow users to design
their own readout which can be seen if the User-defined Readout has
been selected as one of the displayed meters. The range is set in
parameter 005, Maximum Value of User-defined Readout and the unit
is determined in parameter 006, Unit for User-defined Readout. The
choice of unit determines whether the relationship between the output
frequency and the readout is a linear, square or cubed. Units
representing rates (RPM, CFM, GPM, etc.) are linear. Units representing pressure (PSI, in. wg., etc.) are square. Units representing power
(HP, kW, etc.) are cubed.
The display indicates when copying is in progress.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
33
Page 34
005Maximum Value of Custom Readout
(CUSTOM READOUT )
Value:
0.01 to 999,999.99✭100.000
Function:
This parameter determines the value that the user defined meter will
display when the drives output frequency is the value set in parameter
202, Output Frequency High.
Description of choice:
Set the required value for maximum output frequency.
006Custom Readout
(CUST. READ. UNIT)
Value:
No unit[0]GPM[21]
✭%[1]gal/s[22]
rpm[2]gal/min[23]
ppm[3]gal/h[24]
pulse/s[4]lb/s[25]
l/s[5]lb/min[26]
l/min[6]lb/h[27]
l/h[7]CFM[28]
kg/s[8]ft3/s[29]
kg/min[9]ft3/min[30]
kg/h[10]ft3/h[31]
m3/s[11]ft3/min[32]
m3/min[12]ft/s[3 3]
m3/h[13]in wg
m/s[14]ft wg
1
mbar
1
bar
1
Pa
1
MPa
1
MWG
2
kW
1
Squared units (pressure)
2
Cubed units (power)
[15]PSI
[16]lb/in
[17]HP
[18]
[19]
[20]
1
1
1
1
2
[34]
[35]
[36]
[37]
[38]
Function:
The value and the unit are shown in display mode whenever Custom
Readout has been selected in one of parameters 007 through 010,
Display Readout. If flow or speed units are selected, the relationship
between readout and output frequency will be a linear one. If pressure
units are selected, the ratio will be square. If power units are selected,
the ratio will be cubed.
Motor current [A] (MOTOR CURRENT [A])[5]
Power [kW] (POWER [KW])[6]
Power [HP] (POWER [HP])[7]
Output energy [kWh] (ENERGY [KWH])[8]
Hours run [Hours] (HOURS RUN [h])[9]
Custom readout [unit] (CUSTOM READ [UNITS])[10]
Setpoint 1 [unit] (SETPOINT 1 [UNITS])[11]
Setpoint 2 [unit] (SETPOINT 2 [UNITS])[12]
Feedback 1 (FEEDBACK 1 [UNITS])[13]
Feedback 2 (FEEDBACK 2 [UNITS])[14]
Feedback [unit] (FEEDBACK [UNITS])[15]
Motor voltage [V] (MOTOR VOLTAGE [V])[16]
DC link voltage [V] (DC VOLTAGE [V])[17]
Thermal motor load [%]
(THERM.MOTOR LOAD [%])[18]
Thermal drive load [%] (THERM.DRIVE LOAD [%]) [19]
Digital input [Binary code] (DIGITAL INPUT [BIN])[20]
Analog input 53 [V] (ANALOG INPUT 53 [V])[21]
Analog input 54 [V] (ANALOG INPUT 54 [V])[22]
Analog input 60 [mA] (ANALOG 60 [mA])[23]
Relay status [Binary code] (RELAY STATUS [BIN])[24]
Pulse reference [Hz] (PULSE REFERENCE [Hz])[25]
External reference [%] (EXT. REFERENCE [%])[26]
Heat sink temp. [oC] (HEATSINK TEMP [oC])[27]
Profibus fault [HEX] (COMM.OPTION WARN [HEX]) [28]
Free program array [text] (FREE PROG. ARRAY)[29]
Status word (STATUS WORD [HEX])[30]
Control word (CONTROL WORD [HEX])[31]
Alarm word (ALARM WORD [HEX])[32]
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
34
Page 35
Function:
This parameter allows a choice of the data value to be shown in the
large display when power is applied to the drive. In Display Mode, the
+ and - keys change this display when the drive is in operation.
Description of choice:
None can only be selected in parameters 008 through 010, Small
Readout, but not in parameter 007, Large Readout.
Reference [%] gives the total of all references as a percentage of
parameter 205, Maximum Reference.
Reference [unit] gives the total of all references. This is displayed in
Hz in open loop. In closed loop, the reference unit is selected in
parameter 415, Process Units.
Frequency [Hz] gives the output frequency of the drive.
Frequency [%] is the output frequency as a percentage of maximum
output frequency in parameter 202, Output Frequency High Limit.
Motor current [A] is the average phase current of the motor.
Power [kW] is the actual power, in kW, delivered to the motor.
Motor voltage [V] is the voltage supplied to the motor.
DC link voltage [V] is the drive DC bus voltage.
Thermal load, motor [%] is the calculated thermal load of the motor.
100% is the cutout limit. See also parameter 117, Motor Thermal
Protection.
Thermal drive load [%] is the calculated thermal load of the drive.
100% is the trip point.
Digital input [binary code] is the signal status from the 8 digital
inputs (16, 17, 18, 19, 27, 29, 32 and 33). Terminal 16 corresponds to
the bit at the far left. (0 = no signal, 1 = connected signal.)
Analog input 53 [V] is the voltage applied to terminal 53.
Analog input 54 [V] is the voltage applied to terminal 54.
Analog input 60 [mA] is the current applied to terminal 60.
Relay status [binary code] displays the open or closed position of
relays 1 through 6 in binary code. Open is 0 and closed 1, read left to
right (positions 7 and 8, displayed in parameter 007, are not used.)
Power [HP] is the actual power, in HP, delivered to the motor.
Output energy [kWh] is the energy delivered by the motor since the
latest reset was made using parameter 618, Reset of kWh Counter.
Hours run [hours] is the number of hours that the motor has run
since the latest reset was made using parameter 619, Reset of Hours
Run Counter.
Custom readout [-] is a user defined value, calculated on the basis of
the present output frequency, as well as the scaling in parameter 005,
Maximum Value of User-Defined Readout, and the unit in parameter
006, Custom Readout.
Setpoint 1 [unit] is the setpoint value programmed in parameter 418,
Setpoint 1. The unit is selected in parameter 415, Process Units.
Setpoint 2 [unit] is the setpoint value programmed in parameter 419,
Setpoint 2. The unit is selected in parameter 415, Process Units.
Feedback 1 [unit] is the value of the feedback signal applied to
Terminal 53. The unit is selected in parameter 415, Process Units.
Feedback 2 [unit] is the value of the feedback signal applied to
Terminal 54. The unit is selected in parameter 415, Process Units.
Pulse reference [Hz] is the pulse frequency applied to terminal 17 or
terminal 29.
External reference [%] is the sum of the external references as a
percentage of parameter 205, Maximum Reference.
Heat sink temp. [°C] is the present heat sink temperature of the drive.
The trip point is 90 ± 5°C for NEMA 1 units, 80 ± 5°C for NEMA 12.
Profibus fault [HEX] is enabled when the Profibus communication
option is installed and the warnings in Profibus parameter 953 is active.
Free program array [text] displays the array of characters programmed in parameters 533, Display Text Line 1 and 534, DisplayText Line 2 on lines 1 and 2 of the LCP.
Status word [HEX] displays the drive status word (see parameter
608, Data Log).
Control word [HEX] displays the drive control word (see parameter
609, Data Log).
Alarm word [HEX] displays the drive alarm word.
Feedback [unit] is the total feedback signal using the unit scaling
selected in parameter 413, Minimum Feedback; parameter 414
Maximum Feedback; parameter 415, Process Units; and parameter
417, 2 Feedback Calc.
35
Page 36
008Small Readout 1
(SMALL READOUT 1)
Value:
✭ Reference, %[1]
011Unit of Local Reference (UNIT OF LOC REF)
Value:
Hz (HZ)[0]
★ % of output frequency range (%) (% OF FMAX)[1]
Function:
This parameter selects the meter shown on the left display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID. This allows tracking how the process reacts to a change of
reference.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
009Small Readout 2
(SMALL READOUT 2)
Value:
★ Motor current [A][5]
Function:
This parameter selects the meter shown on the center display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
010Small Readout 3
(SMALL READOUT 3)
Value:
★ Power [HP][7]
Function:
This parameter selects the meter shown on the right display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
Function:
This parameter sets the unit that will be displayed in Display Mode IV
when the drives speed is being controlled locally.
Description of choice:
Choose the desired unit for local reference.
012Hand Start on LCP (HAND START BUTTON)
Value:
Disable (DISABLE)[0]
★ Enable (ENABLE)[1]
Function:
This parameter allows disabling the Hand/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Hand/Start key will be
disabled.
013OFF/STOP on LCP (STOP BUTTON)
Value:
Disable (DISABLE)[0]
★ Enable (ENABLE)[1]
Function:
This parameter allows disabling the Off/Stop key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Off/Stop key will be disabled.
CAUTION
!
OFF/STOP Key Disabled!
If Disable is selected in parameter 013, the motor
cannot be stopped by pressing the OFF/STOP
key on the keypad. Use of the Disable option
could result in injury or equiment or property
damage.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
36
Page 37
014Auto Start on LCP(AUTO START BTTN)
Value
Disable (DISABLE)[0]
★ Enable (ENABLE)[1]
Function:
This parameter allows disabling the Auto/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Auto/Start key will be
disabled.
P015
015Reset on LCP(RESET BUTTON)
Value:
Disable (DISABLE)[0]
★ Enable (ENABLE)[1]
Function:
This parameter allows disabling the Reset key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Reset key will be inactive.
NOTE
Do not disable Reset on LCP in parameter 015
unless a remote reset is available through
digital inputs and parameters 300 through 307.
017Operating State at Power Up
(POWER UP ACTION)
Value:
★ Auto restart (AUTO RESTART)[0]
OFF/STOP (OFF/STOP)[1]
Function:
Selects auto or manual restart when power is reapplied after an outage
occurs to a running drive.
Description of choice:
Auto restart is selected if the drive is to resume operation after a power
outage.
OFF/STOP is selected if the drive is to remain stopped after a power
outage. To restart, press the Hand/Start or Auto/Start key at the
keypad. If HAND START or AUTO START are disabled by
parameters 012 and 014, the motor will not be able to restart if OFFSTOP is selected in parameter 017.
016Lock for Data Change (DATA CHANGE LOCK)
Value:
★ Not Locked (NOT LOCKED)[0]
Locked (LOCKED)[1]
Function:
This parameter allows locking out parameter changes at the local
control panel.
Description of choice:
If Locked is selected, data modifications in the parameters cannot be
made. Parameter changes will be possible through serial communication.
Parameters 007 through 010, Display Readout can be changed at the
local control panel.
The local control panel can also be locked or unlocked by a digital
input controlled by parameters 300 through 307.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
37
Page 38
Load and Motor
Parameters 100 through 118
This parameter group controls output power and other output
characteristics of the drive.
For correct operation, motor nameplate data must be entered into
parameters 102 through 106 either through the Quick Menu or the
Extended Menu. In addition, automatic motor adaptation, DC braking
and motor thermal protection can be set by this parameter group.
This parameter configures the drive for single or multiple motor
operation.
100Configuration(CONFIG. MODE)
Value:
★ Open loop (OPEN LOOP)[0]
Closed loop (CLOSED LOOP)[1]
Function:
This parameter is used for selecting closed loop or open loop
operation.
Description of choice:
If Open loop is selected, speed control is changed directly by the
speed reference signal. Any feedback signal applied to the drive will
have no effect on the drives speed.
If Closed loop is selected, the internal process regulator is available to
accept feedback signal(s) to provide the desired speed regulation.
NOTE
It is important to set parameter 100,
Configuration, properly when closed loop
operation is required. When open loop is
selected, parameters associated with setting up
PID controller are not accessible.
The AEO function will automatically and continuously monitor the load
and adjust the output voltage to maximize motor and drive efficiency
and performance. After the motor reaches the set speed, the AEO
function reduces the output voltage to the motor, if the load will allow.
When the load is light, the voltage is reduced, as shown in the graph
below. This lower voltage reduces motor heating and motor noise, and
increases efficiency.
Description of choice:
Select Automatic Energy Optimization (AEO) for all single motor
applications. When AEO has been selected, only one motor may be
connected to the drive at a time.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
38
Select Parallel motors when more than one motor is connected in
parallel to the output. In this case, it is necessary to set a start voltage in
parameter 108, Start Voltage of Parallel Motors.
NOTE
To optimize AEO for use with motors having
more than 4 poles, see parameter 118, Motor
Power Factor.
Page 39
NOTE
It is very important that values set in parameters
102, Motor Power, through 106, Rated MotorSpeed, correspond accurately to nameplate data
of motor. Failure to enter motor nameplate data
accurately could result in erratic or less than
optimum equipment operation.
Select a value that equals the nameplate data on the motor. This may
be less than the input voltage. It is also possible to set any voltage
within the range of the drive.
104Motor Frequency(MOTOR FREQUENCY)
Value:
50 Hz (50 Hz)[50]
★ 60 Hz (60 Hz)[60]
Function:
This is where the rated motor frequency is selected. This is usually the
frequency of the power line.
Description of choice:
Select the desired value. It is also possible to set any frequency within
the range of the drive.
NOTE
Failure to enter motor nameplate data
accurately could result in erratic or less than
optimum equipment operation. Also, changing
values in parameter 102, Motor Power, or
parameter 103, Motor Voltage, after motor
current has been entered in parameter 105, may
automatically change the value in parameter 105.
105Motor Current(MOTOR CURRENT)
Value:
0.01 to drive rating
★ Set based on motor nameplate.
Function:
The rated motor current in amps is used for setting output current and
providing motor thermal protection. It is important to set the motor
current to the fullloadcurrent rating (FLA) of the motor.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
Description of choice:
Set a value that equals the nameplate data on the motor.
39
Page 40
NOTE
Failure to enter motor nameplate data
accurately could result in erratic or less than
optimum equipment operation. Changing
values in parameter 104, Motor Frequency, after
rated motor speed has been entered in
parameter 106, may automatically change the
value in parameter 106.
NOTE
Some motors (such as motors with 6 or more
poles) may be unable to run AutomaticAdaptation. Limited AMA is a procedure which
can be effective in such cases since results
measure motors stator and effects of cable
length. Multiple motor applications cannot use
AMA.
106Rated Motor Speed(MOTOR NOM. SPEED)
Value:
100 through 60000
✭ Depends on parameter 102, Motor Power
Function:
This is where the value is set that corresponds to the rated motor
speed shown on the motor nameplate.
Description of choice:
Choose a value that corresponds to the motor nameplate data.
107Automatic Motor Adaptation, AMA
(AUTO MOTOR ADAPT)
Value:
★ Optimization disable (NO AMA)[0]
Automatic adaptation (RUN AMA)[1]
Limited AMA (RUN LIMITED AMA)[2]
Function:
Automatic Motor Adaptation (AMA) is an advanced procedure that
measures electrical characteristics of the motor. This procedure does
not cause the motor to run.
AMA optimizes the adjustment of the drive to the motor. This feature is
particularly useful when the drive-to-motor cable length is long, and
with nonstandard motors or high hp motors. Although it is not necessary
to run AMA, it is highly recommended for optimum operation and
increases the capability of the Automatic Energy Optimization function
selectable in parameter 101, Torque Characteristics.
For the best adjustment of the drive, it is recommended to carry out
AMA on a cold motor.
The following must be noted when either AMA function is used:
-Before running AMA, the correct nameplate data for the motor
must be entered in parameters 102 through 106.
-Total automatic motor adaptation may take up to 10 minutes.
-Alarms and warnings will be shown in the display if faults occur
during motor adaptation.
-AMA can only be carried out if the rated motor current of the motor
is at least 35% of the rated output current of the drive.
Description of choice:
Select Automatic Adaptation if the drive is to carry out a complete
automatic motor adaptation procedure.
Select Limited AMA if an LC-filter has been placed between the drive
and the motor, for a motor with 6 or more poles, or if Automatic
Adaptation was unsuccessful. Some drives may display Automatic
Adaptation with LC-filter rather than Limited AMA. The functions are
the same.
Procedure for Automatic Motor Adaptation:
1.Set motor parameters 102 through 106 according to motor
nameplate data.
2.Connect 24 VDC from terminal 12, or from external source, to
terminal 27.
3.Select either Automatic Adaptation or Limited AMA in parameter
107, Automatic Motor Adaptation.
4.Start drive by pressing Hand Start or connect terminal 18 (start) to
terminal 12 and press Auto Start.
To stop automatic adaptation or limited AMA prior to completion:
Press OFF/STOP key.
After a normal sequence is complete, the display reads: AMA STOP
Press RESET key. Drive is now ready for operation.
NOTE
Repeated AMA operation may lead to motor
heating that could result in an increase of stator
resistance. This can reduce test accuracy. Run
AMA only on a cool motor.
If an output LC-filter has been connected between the drive and the
motor, select Limited AMA. If the complete AMA procedure is desired,
remove the LC-filter, run Automatic Adaptation (RUN AMA), and
reinstall the filter.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
40
NOTE
RESET key must be pressed after AMA
is completed to save results to drive.
If there is a fault, the display reads: ALARM 22
1.Check alarms section in this manual for possible causes of alarm.
2.Press RESET key to clear fault.
If there is a warning, the display reads: WARNING (39 through 42)
1.Check warnings section in this manual for possible causes of
warning.
2.Press CHANGE DATA key and select Continue if AMA is to
continue despite warning, or press OFF/STOP key to stop AMA.
Page 41
108Start Voltage of Parallel Motors
(MULTIM.START VOLT)
Value:
0.0 through parameter 103 Motor Voltage✭ depends on par. 103 Motor Voltage
Function:
This parameter sets the voltage at 0 Hz for all drives with two or more
motors connected in parallel.
The start voltage represents a supplementary voltage input to the
motor. Increasing the start voltage will increase the starting torque. A
start voltage is especially useful for small motors (<5 hp) as they have a
higher stator resistance than larger motors.
This function is only active if Parallel Motors has been selected in
parameter 101, Torque Characteristics.
Description of choice:
To set the start voltage, monitor the motor current while starting the load
and choose the starting voltage that gives the lowest starting current.
Start with a small value and increase only as required for reliable
starting.
109Resonance Dampening (RESONANCE DAMP.)
Value:
0 to 500 %★100 %
111Start Delay(START DELAY)
Value:
0.0 to 120.0 sec.★ 0.0 sec.
Function:
This parameter allows a delayed start of the drive after the conditions
for start have been fulfilled. After the start delay time has elapsed, the
drive will start and ramp up to the commanded speed.
Description of choice:
Set the desired time before the drive will start.
112Motor Preheat(MOTOR PREHEAT)
Value:
✭ Disable (DISABLE)[0]
Enable (ENABLE)[1]
Function:
The motor preheat function protects the motor from condensation by
running a small DC current through the motor. Motor preheat is only
active during stop when control voltage is applied to terminal 27.
Description of choice:
Select Disable if this function is not required. Select Enable to activate motor
preheating. The amount of motor preheating is set in parameter 113.
CAUTION
Function:
High-frequency resonances in the motor can be eliminated by adjusting
this parameter.
Description of choice:
Adjust the dampening percentage for smoothest high speed operation.
The drive is able to breakaway high friction loads. This high starting
torque, approximately 1.6 x rated torque is available for up to 0.5
seconds. The current level is limited by the protective circuits of the
drive. OFF corresponds to 0.0 sec.
Description of choice:
Set the time for which high starting torque is desired.
Motor Damage!
Be sure to check settings in parameter 113 if
parameter 112, Motor Preheat, is enabled. Do
not apply any more current than required.
Excessive current or preheating time may
damage the motor.
113Motor Preheat DC Current
(PREHEAT DC-CURR.)
Value:
0 to 100 %★ 50 %
The maximum value depends on the rated motor current.
Function:
The motor can be preheated when stopped by applying DC current to
it. A holding torque can also be provided.
Description of choice:
The motor can be preheated by means of a DC current. At 0%, the
function is inactive; at a value higher than 0%, a DC current will be
supplied to the motor whenever it is stopped. A windmilling fan can be
held by providing a holding toque by using this parameter.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
41
Page 42
DC Braking
Applying DC current to the motor will brake the motor. Parameter 114,
DC Braking Current, sets the DC braking current as a percentage of
the rated motor current. Parameter 115, DC Braking Time, sets the
amount of time that the DC current will be applied. Parameter 116, DCBrake Cut-in Frequency, sets the frequency at which DC braking
begins when the motor decelerates during a stop.
If terminal 19 or 27 (parameters 303 or 304 Digital Input) has been
programmed to DC Braking Inverse and shifts from logic 1 to logic 0,
the DC braking will be activated immediately.
When the start signal on terminal 18 changes from logic 1 to logic 0,
the DC braking will be activated when the output frequency becomes
lower than the brake cut-in frequency.
If a DC brake current is set in parameter 114, the drives switching
frequency will be limited to 4 kHz during the braking.
CAUTION
Motor Damage!
A high braking current supplied for a long time
will overheat the motor. Use only the DC braking
current and time required. Excessive braking
current may damage the motor.
Also, do not use DC braking function if inertia
of driven load is more than 20 times inertia of
motor. Excessive load inertia may damage the
motor.
NOTE
Most HVAC applications do not required braking
or holding. It is suggested that parameter 114
remain set at 0 unless braking or holding torque
is required.
115DC Braking Time(DC BRAKE TIME)
Value:
0.0 to 60.0 sec.✭ 10.0 sec.
Function:
This parameter sets the time that the DC braking is active.
Description of choice:
Set the desired time.
116DC Brake Cut-in Frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) to setting of parameter 202✭ OFF
Function:
This parameter is used for setting the frequency at which DC braking
begins after a stop command is issued.
Description of choice:
Set the desired frequency for braking to begin upon deceleration.
114DC Braking Current(DC BRAKE CURRENT)
Value:
0 to 100%★ 50 %
The maximum value depends on the rated motor current.
Function:
This parameter is used for setting the DC braking current that is
applied:
1.When the DC brake frequency set in parameter 116 DC BrakeCut-in Frequency has been reached during a stop.
2.When DC brake inverse is active via terminal 19 or 27, or via the
serial bus.
The DC braking current will be active for the duration of the DC
braking time set in parameter 115 DC Braking Time.
Description of choice:
To be set as a percentage value of the rated motor current set in
parameter 105 Motor Current.
100% DC braking current corresponds to the value set in parameter
105.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
42
Page 43
117Motor Thermal Protection
(MOT. THERM PROTEC)
Value:
No protection (NO PROTECTION)[0]
Thermistor warning (THERMISTOR WARNING)[1]
Thermistor trip (THERMISTOR FAULT)[2]
ETR Warning 1 (ETR WARNING 1)[3]
The drive is able to monitor the motor temperature in two different
ways:
By a thermistor installed in the motor. The thermistor is connected
to one of the analog input terminals (53 or 54).
Calculation of the thermal load by the Electronic Thermal Relay
(ETR) is based on current, frequency and time. This is compared
with the rated motor current and the rated motor frequency. The
calculations take into account the reduced cooling of the motor at
low speeds.
ETR Tip 1 through 4 and ETR Warning 1 through 4 correspond to the
four drive setups. This enables the use of the ETR function to protect
up to four different motors if a different setup is used for each different
motor.
NOTE
If multiple setups are used, be sure to program
complete motor data (parameters 102 through
106) and parameter 117 in each setup.
Description of choice:
Select No protection if no warning or trip is desired when the motor is
overheated.
Motor Thermal Protection
The motor temperature is calculated on the basis of motor current,
output frequency and time. The graph shows the amount of time that the
drive can provide a current level to the motor at the rated motor
frequency, 20% of rated motor frequency and 200% of rated motor
frequency.
118Motor Power Factor (Cos Æ)
(MOTOR PWR FACT)
Value:
0.50 - 0.99✭ 0. 75
Function:
Automatic Energy Optimization (AEO) (see parameter 101, Torque
Characteristics) can be calibrated to work with motors with greater than
4 poles. Motors with 6, 8, and 12 poles have a lower power factor
which restricts the energy saving capability of AEO. Calibrating AEO
can optimize this function. The full load power factor will either be on the
motor nameplate or available from the motor manufacturer.
Description of choice:
Enter the full load power factor value.
Select Thermistor warning if a warning is desired when the motor
thermistor reaches its trip point.
Select Thermistor trip if a fault is desired when the motor thermistor
reaches its trip point.
Select ETR Warning 1 through 4, if a warning is desired when the
motor is overheated according to the ETR calculations.
The drive can also be programmed to give off a warning signal through
one of the digital outputs.
Select ETR Trip 1 through 4 if a fault is desired when the motor is
overheated according to the ETR calculations.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
43
Page 44
References and Limits
Parameters 200 through 228
In this parameter group, the frequencies and references of the drive
are set.
202Output Frequency High Limit
(MAX. FREQUENCY)
Value:
Parameter 201 to parameter 200★ 60 Hz
This parameter group includes:
Setting of ramp times
Choice of four preset references
Setting four bypass frequencies
Setting maximum current to motor
Setting warning limits for current, frequency, reference and
feedback
200Output Frequency Range
(FREQUENCY RANGE)
Value:
★ 0 to 120 Hz (0 - 120 HZ)[0]
0 to 1000 Hz (0 - 1000 HZ)[1]
Function:
Choose one of two maximum output frequency ranges.
Description of choice:
Select the output frequency range that includes the highest output
frequency required for normal operation.
NOTE
HVAC applications seldom require output
frequency greater than 120 Hz. Check with Trane,
motor manufacturer, or manufacturer of driven
equipment before selecting 0 - 1000 Hz range.
Function:
Set the highest speed at which the motor is to run.
NOTE
Output frequency of drive can never assume
value higher than 1/10th of switching frequency.
See parameter 407, Switching Frequency.
Description of choice:
Set a value between the low frequency limit, set in parameter 201, and
the frequency range limit, set in parameter 200. The drive will not be
able to run continuously at an output frequency above this value in any
mode.
NOTE
HVAC applications seldom require output
frequency greater than 60 Hz. Check with Trane,
motor manufacturer, or manufacturer of driven
equipment before selecting a maximum
frequency greater than 60 Hz.
201Output Frequency Low Limit
(MIN. FREQUENCY)
Value:
0.0 to parameter 202★ 0.0 HZ
Function:
Set the minimum speed at which the motor is to run.
Description of choice:
A value from 0.0 Hz to the Output Frequency High Limit frequency set
in parameter 202 can be selected. The drive will not be able to run
continuously at an output frequency below this value in any mode.
NOTE
For fan applications, factory setting of
parameter 201 is 6 Hz. For pump applications,
factory setting for parameter 201 is 18 Hz.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
44
Page 45
Reference Handling
Reference handling is shown in the block diagram at the bottom of this
page. The block diagram shows how a change in a parameter can
effect the resulting reference.
It is possible to have both internal preset references and external
references at the same time. In parameter 210, Reference Type, a
choice is made of how the preset references are to be combined with
the external references.
Parameters 203 to 205, Reference Handling, Minimum and MaximumReference, and parameter 210, Reference Type, define the way
reference handling is carried out. These parameters are active both in
closed loop and open loop operation.
In closed loop operation, the resulting reference is affected by parameters 418 and 419, Setpoint 1 and 2, as well as by remote references.
Remote references can be:
1) external references, including analog inputs 53, 54 and 60; pulse
references through terminals 17 or 29 and references from serial
communication
2) preset references
The resulting reference can be shown in the display as a percentage
or as a selected unit of measure. The sum of the external references
can be displayed in a percentage of the range between MinimumReference to Maximum Reference. Select External Reference, [%] or
the desired unit in parameters 007 through 010, Display Readout, to
display the reference value.
An independent local reference exists, where the resulting reference is
set by means of the [+] and [-] keys. In all cases, the output frequency
range is limited by parameter 201, Output Frequency Low Limit, and
parameter 202, Output Frequency High Limit.
NOTE
If local reference is active, drive is always in
Open Loop, regardless of choice made in
parameter 100, Configuration.
The unit of the local reference can be set either as Hz or as a
percentage of the output frequency range. The unit is selected in
parameter 011, Unit of Local Reference.
203Reference Handling(REFERENCE SITE)
Value:
★ Hand/Auto linked reference
(LINKED TO HAND/AUTO)[0]
Local reference (LOCAL)[1]
Remote controlled reference (REMOTE)[2]
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
45
Page 46
Function:
This parameter chooses the active resulting reference. If Hand/Auto
linked reference is selected, the resulting reference will depend on
whether the drive is in Hand or Auto mode.
The table below shows which reference is active when Hand/Autolinked reference, Remote reference or Local reference has been
selected. The Hand mode or Auto mode can be selected via the
keypad or by a digital input set in parameters 300 through 307 Digital
Inputs.
Reference HandlingHand ModeAuto Mode
Hand/AutoLocal ref. activeRemote ref. active
RemoteRemote ref. activeRemote ref. active
LocalLocal ref. activeLocal ref. active
The unit for the reference can be seen from the following table:
Minimum Reference is the lowest reference value that can be set for
the drive.
205Maximum Reference(MAX. REFERENCE)
Value:
If parameter 100, Configuration = Open loop,
parameter 204, Minimum Reference,
to 1000.000 Hz✭60.000 Hz
Description of choice:
If Hand/Auto linked reference is chosen, the motor speed in Hand
mode will be set by the local reference, while in Auto mode it is set by
the remote references and any setpoints selected.
If Remote reference is selected, the motor speed will depend on
remote references and any setpoints selected, regardless of whether
Hand mode or Auto mode has been chosen.
If Local reference is selected, the motor speed will only depend on the
local reference set via the control panel, regardless of whether Hand
mode or Auto mode has been selected.
204Minimum Reference(MIN. REFERENCE)
Value:
If parameter 100, Configuration = Open loop,
0.000Hz to parameter 205, Maximum Reference. ✭ 0.000 Hz
If parameter 100 Configuration = Closed loop,
parameter 413, Minimum Feedback, t o
parameter 205, Maximum Reference.✭ 0.000 Hz
Function:
The Minimum Reference sets the minimum value of the sum of all
references. If Closed loop has been selected in parameter 100,
Configuration, the minimum reference is limited by parameter 413,
Minimum Feedback.
If parameter 100, Configuration = Closed loop,
parameter 204, Minimum Reference, to
parameter 414, Maximum Feedback. ✭60.000 Hz
Function:
The Maximum Reference sets the maximum value of the sum of all
references. If Closed loop has been selected in parameter 100,Configuration, the maximum reference cannot be set above parameter
414, Maximum Feedback. The Maximum Reference is ignored when
the local reference is active.
The reference unit can be determined from the following table:
Unit
Parameter 100 Configuration = Open loopHz
Parameter 100 Configuration = Closed loopPar. 415
Description of choice:
Maximum reference is the highest reference value that can be set for
the drive.
Minimum reference is ignored when the local reference is active. In this
case, minimum reference is determined by parameter 201, MinimumFrequency.
NOTE
For fan applications, factory setting of
parameter 204 is 6 Hz. For pump applications,
factory setting for parameter 204 is 18 Hz.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
46
Page 47
206Ramp Up Time(RAMP UP TIME)
Value:
1 to 3600 seconds ★ Depends on the unit
Function:
The ramp up time is the acceleration time from 0 Hz to the rated motor
frequency set in parameter 104. It is assumed that the output current
does not reach the current limit set in parameter 215. This determines
the maximum acceleration rate for all modes of operation.
Description of choice:
Program the desired accel time. Too long of a ramp up time can cause
sluggish drive operation. Too short of a ramp up time can cause the
drive to go into current limit during acceleration or cause unacceptable
torque pulses in the controlled system.
NOTE
For fan applications, factory setting of
parameter 206 is 60 seconds. For pump
applications, factory setting for parameter 206
is 10 seconds.
Description of choice:
Program the desired decel time. Too long of a ramp down time can
cause sluggish operation. Too short of a ramp down time can cause the
drive to trip off due to high DC bus voltage or cause unacceptable
torque pulses in the controlled system.
NOTE
Factory setting of parameter 207 for fan
applications, is 60 seconds. For pump
applications, factory setting for parameter 207
is 10 seconds.
208Automatic Ramp Down(AUTO RAMPING)
Value:
Disable (DISABLE)[0]
★ Enable (ENABLE)[1]
Function:
This function ensures that the drive does not trip during deceleration if
the decel time set is too short. If, during deceleration, the DC bus
voltage increases to the maximum value permitted, the drive automatically extends the ramp-down time.
NOTE
If auto ramp down is enabled, ramp time could
be considerably longer than that set in
parameter 207, Ramp Down Time.
207Ramp Down Time(RAMP DOWN TIME)
Value:
1 to 3600 seconds ★ Depends on the unit
Function:
The ramp-down time is the deceleration time from the rated motor
frequency set in parameter 104, Motor Frequency, to 0 Hz. This
ramp-down time may be automatically extended to prevent an
overvoltage trip if the load regenerates to the drive. This determines
the maximum deceleration rate for all modes of operation.
Description of choice:
Program this function as Enable to avoid trips caused by too rapid a
deceleration.
209Jog Frequency(JOG FREQUENCY)
Value:
Parameter 201, Output Frequency Low Limit, to parameter 202
Output Frequency High Limit★ 10.0 HZ
Function:
The jog frequency is the fixed output frequency at which the drive is
running when the jog function is activated.
Jog can be activated via the digital inputs.
Description of choice:
Set the desired frequency.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
47
Page 48
Reference Type
The example below shows how the resulting reference is calculated
when Preset references are used together with Sum and Relative
references set in parameter 210, Reference Type. A formula for
calculating the resulting reference is given under Calculation of
Resulting Reference. See the drawing under Reference Handling.
Example:
The following parameters have been set:
Parameter 204 Minimum Reference:10 Hz
Parameter 205 Maximum Reference:60 Hz
Parameter 211 Preset Reference:15%
Parameter 308 Terminal 53, Analog Input:Reference
Parameter 309 Terminal 53, Min. Scaling:0 V
Parameter 310 Terminal 53, Max. Scaling:10 V
When parameter 210 Reference Type is set to Sum, one of the
adjusted Preset References, parameters 211 through 214, will be
added to the external references as a percentage of the reference
range. If terminal 53 has an analog input voltage of 4 V, the resulting
reference will be:
If parameter 210 Reference Type is set to Relative, one of the adjustedPreset References parameters 211 through 214 will be totaled as a
percentage of the sum of the present external references. If terminal 53
has an analog input voltage of 4 V, the resulting reference will be:
The graph in the next column shows the resulting reference while the
external reference changes from 0 to 10 V. Parameter 210, Reference
Type has been programmed for Sum and Relative. Parameter 211,
Preset Reference 1, is programmed for 0%.
= 6.0 Hz
210Reference Type(REF. FUNCTION)
Value:
Sum (SUM)[0]
Relative (RELATIVE)[1]
★ External/preset (EXTERNAL/PRESET)[2]
Function:
It is possible to define how the preset references are added to the other
references. For this purpose, Sum or Relative is used. It is also
possible, by using the External/Preset function, to select between the
external references and a preset reference.
Description of choice:
If Sum is selected, one of the preset references (parameters 211
through 214, Preset Reference) is added to the other external
references as a percentage of the reference range (minimum reference
through maximum reference).
If Relative is selected, one of the adjusted preset references (parameters 211 through 214, Preset Reference) is added as a percentage of
the total external reference.
If External/Preset is selected, it is possible to shift between the external
references and the preset references using terminals 16, 17, 29, 32 or
33 (parameters 300, 301, 305, 306 or 307, Digital Inputs). Preset
references are a percentage value of the reference range. External
reference is the sum of the analog references, pulse references and
any references from serial communication.
NOTE
If Sum or Relative is selected, one of preset
references is always active. If preset references
are not used, set value to 0%.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
48
NOTE
See Calculation of Resulting Reference section
in this manual for mathematic formula to
calculate references.
-100.00 % to +100.00 %★ 0.00%
of the reference range or external reference
Function:
Four different preset references can be programmed in parameters 211
to 214, Preset Reference. The preset reference is stated as a
percentage of the reference range or as a percentage of the other
external references, depending upon the choice made in parameter
210, Reference Type.
The choice of preset references is made by activating terminals 16, 17,
29, 32 or 33, as shown in the table below.
Description of choice:
Set the required maximum output current.
NOTE
When drive is in current limit and a stop
command is issued by pressing the STOP key
on LCP keypad, drive output is immediately cut
off and motor will coast-to-stop.
216Frequency Bypass, Bandwidth
(FREQUENCY BYPASS B.W.)
Value:
0 (OFF) to 100 Hz ★ DISABLED
Function:
Mechanical resonance in the driven system sometimes makes it
desirable to avoid operation at critical speeds.
Set the required preset reference(s) that is/are to be used.
215Current Limit(CURRENT LIMIT)
Value:
0.1 to 1.1 x rated current ★ rated current
Function:
This is where the maximum output current is set. If the motor attempts to
draw more than this amount of current, the drive will reduce its output
frequency until the current is less than or equal to the current limit
value.
The factory setting corresponds to the rated output current. If the
current limit is to be used as motor protection, the rated motor current
must be set. If the current limit is set within the range of 1.0 to 1.1 times
the rated output current of the drive, the drive can only handle current
greater than its rated output intermittently. After the load has been higher
than rated output current limit, it must be reduced to a level that is lower
than the rated current of the drive for a period of time.
These output frequencies can be programmed in parameters 217
through 220.
In this parameter, Frequency Bypass, Bandwidth, the width of the
frequency to be bypassed is defined.
Description of choice:
The bypass bandwidth is equal to the programmed bandwidth
frequency. This bandwidth will be centered around each bypass
frequency.
0 to 120 or 1000 HZ★ 120.0 Hz
The frequency range depends on the selection made in parameter
200, Output Frequency Range.
Function:
Some systems require that some output frequencies be avoided
because of mechanical resonance problems in the system.
Description of choice:
Enter the frequencies to be avoided.
See also parameter 216, Frequency Bypass, Bandwidth.
Note that if the current limit is set to less than the maximum value of the
drive, acceleration torque is reduced correspondingly.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
49
Page 50
Warning Functions
The warning functions in parameters 221 through 228 are not active
during ramp-up after a Start command, ramp down after a Stop
command, or while stopped. The warning functions are activated when
the output frequency has reached the resulting reference.
The signal outputs can be programmed to generate a warning signal
via terminal 42 or 45 and via the relay outputs.
The reference limits in parameter 226, Warning: High Reference and
parameter 227, Warning: Low Reference are only active when remote
reference has been selected.
222Warning: High Current(WARN. HIGH CURR)
Value:
Parameter 221 to 1.1 x rated current
★ 1.1 x rated current
Function:
If the motor current is above the limit programmed in this parameter, the
display shows a flashing CURRENT HIGH.
Description of choice:
The upper signal limit of the motor frequency must be programmed
within the normal working range of the drive. See the drawing at
parameter 221, Warning: Low Current.
221Warning: Low Current(WARN. LOW CURR)
Value:
0.0 to parameter 222 Warning: High current✭ 0.0 A
Function:
When the motor current is below the limit programmed in this parameter,
the display shows a flashing CURRENT LOW, provided Warning has
been selected in parameter 409, Function in Case of No Load. The
drive will trip if parameter 409 has been selected as Trip. This can be
used to indicate when a belt between the motor and the driven load is
broken.
Description of choice:
The lower signal limit must be programmed within the normal working
range of the drive.
223Warning: Low Frequency
(WARN. LOW FREQ)
Value:
0.0 to parameter 224★ 0.0 Hz
Function:
If the output frequency is below the limit programmed in this parameter,
the display will show a flashing F OUT < FLOW.
Description of choice:
The lower signal limit of the motor frequency must be programmed
within the normal working range of the drive. See drawing at parameter
221 Warning: Low current.
224Warning: High Frequency
(WARN. HIGH FREQ.)
Value:
Par. 200 Output frequency range = 0 to 120 Hz
parameter 223 - 120 Hz✭ 120.0 Hz
Par. 200 Output frequency range = 0 to 1000 Hz
parameter 223 - 1000 Hz✭ 120.0 Hz
Function:
If the output frequency is above the limit programmed in this parameter,
the display will show a flashing F OUT > F HIGH
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
50
Description of choice:
The higher signal limit of the motor frequency must be programmed
within the normal working range of the drive. See the drawing at
parameter 221, Warning: Low Current.
Page 51
225Warning: Low Reference
(WARN. LOW REF)
Value:
-999,999.999 - High Reference (par. 226) ★ -999,999.999 Hz
Function:
When the total remote reference is less than the limit programmed in this
parameter, the display shows a flashing REF.<REF. LOW
The reference limits in parameter 226, Warning: High Reference and
parameter 225, Warning: Low Reference are only active when remote
reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop
the unit is programmed in parameter 415, Process Units.
227Warning: Low Feedback
(WARN .LOW FDBK)
Value:
-999,999.999 to High Feedback (parameter 228)
★ -999,999.999
Function:
If the feedback signal is below the limit of Low Feedback programmed
in this parameter, the display will flash FEEDBACK<FOB LOW.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the desired value within the feedback range, parameter 413,
Minimum Feedback, and parameter 414, Maximum Feedback.
Description of choice:
When parameter 100, Configuration, has been programmed for Open
Loop, the lower signal limit of the reference must be programmed within
the normal working range of the drive. If parameter 100 is programmed as Closed Loop, Low Reference must be within the
reference range programmed in parameters 204 and 205.
226Warning: High Reference
(WARN. HIGH REF)
Value:
Reference Low (par. 225) to 999,999.999 ★ 999,999.999 Hz
Function:
If the resulting reference is below the limit programmed in this parameter, the display flashes REF. > REF. HIGH.,
The reference limits in parameter 226 Warning: High Reference and
parameter 225 Warning: Low Reference are only active when remote
reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop
the unit is programmed in parameter 415, Process Units.
Description of choice:
The high reference warning must be programmed within the normal
working range of the drive, provided parameter 100 Configuration has
been programmed for Open Loop. If parameter 100 has been
programmed for Closed Loop, Reference High must be within the
reference range programmed in parameters 204 and 205.
228Warning: High Feedback
(WARN. HIGH FDBK)
Value:
Low Feedback (parameter 227) to 999,999.999
★999,999.999
Function:
If the feedback signal is above the limit programmed in this parameter,
the display will show a flashing FEEDBACK>FOBHIGH.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the required value within the feedback range, parameter 413,
Minimum Feedback, and parameter 414, Maximum Feedback.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
51
Page 52
Inputs and Outputs
Parameters 300 through 328
In this parameter group, the functions of the drive input and output
terminals are defined. The digital inputs are through terminals 16, 17,
18, 19, 27, 32 and 33. Inputs are programmed by parameters 300
through 307. The table below shows the functions available for input.
Digital inputs require a signal of 0 or 24VDC. A signal lower than
5VDC is a logic 0, while a signal higher than 10 VDC is a logic 1.
The terminals for the digital inputs can be connected to the internal 24
VDC supply through terminals 12 and 13, or an external 24VDC
supply can be connected.
The drawings at the right show one setup using the internal 24VDC
supply and one setup using an external 24VDC supply.
Switch 4 is used for separating the common potential of the internal
24VDC supply from the common potential of an external 24VDC
supply. Switch 4 is the DIP switch on the far right of the group of DIP
switches located on the lower right of the control card, just above the
control terminals.
When Switch 4 is in the OFF position, the
external 24VDC supply is galvanically isolated
from the drive.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
52
Page 53
Function:
In parameters 300 through 307, Digital Inputs, the functions of
terminals 16 through 33 are selected.
These options are shown in the table on the previous page.
Description of choice:
No Function is selected if the drive is not to react to signals transmitted
to the terminal.
Reset allows reset of the drive after a resettable fault. Not all faults can
be reset without removing and reapplying the input power. Faults that
require the removal of input power are called trip lock faults. See
Warnings and Alarms.
Coasting Stop, Inverse is used to release the motor immediately by
turning off the output transistors. The motor will coast freely to a stop.
Inverse indicates a closed terminal sends the stop signal. Logic 0
implements coasting to a stop.
Reset and Coasting Stop, Inverse is used for activating coasting
stop at the same time as reset. Inverse indicates a closed terminal
sends the stop signal. Logic 0 implements coasting stop and reset.
DC Braking, Inverse is used for stopping the motor by energizing it
with a DC voltage for a given time, as set by parameters 114 and 115.
Inverse indicates a closed terminal sends the braking signal. Logic 0
implements DC braking. See the DC braking parameters.
Safety Interlock is the s ame as Coasting Stop, Inverse, except Safety
Interlock generates an alarm message on the display when terminal 27
is logic 0. The alarm message will also be active through digital outputs
42 and 45 and relay outputs 1 and 2, if programmed for SafetyInterlock.
Start is selected for a remote Start/Stop command.
Logic 1 = Start.Logic 0 = Stop.
Reversing is used for changing the direction of rotation of the motor.
Logic 0 is for forward. Logic 1 is for reverse. The drive can be safely
reversed while it is driving the motor. The reversing signal only
changes the direction of rotation, it does not activate the start function. It
is not active in Closed Loop mode.
Freeze Reference freezes the present reference. The frozen
reference can only be changed by means of Speed Up or SpeedDown. The frozen reference is saved after a stop command and when
power is removed.
Freeze Output freezes the present output frequency. The frozen
output frequency can now only be changed by means of Speed Up orSpeed Down.
NOTE
If Freeze Output is active, the drive cannot be
stopped via terminal 18.
To stop the drive when Freeze Output is active, one of the four
methods listed below must be used.
Turn off the Freeze Output function and perform a normal stop.
Press the keypad Off/Stop key.
Remove the control voltage to terminal 27.
If terminal 19 is programmed in parameter 303 for DC BrakeInverse, remove the control voltage to it.
Selection of Setup, Lsb* and Selection of Setup, Msb** enables
digital selection of the four possible setups. To enable this, parameter
002 Active Setup must be set to Multi Setup.
*Lsb - Least significant bit. **Msb - Most significant bit.
Preset Reference, on is used for switching between remote controlled
reference and preset reference. This assumes that Remote/preset has
been selected in parameter 210, Reference Type. Logic 0 = remote
controlled references active; logic 1 = one of the four preset references is active in accordance with the table below.
Preset Reference, Lsb and
Preset reference, Msb enables a
choice of one of the four preset references, in accordance with the table
below.
Reversing and Start is used for Start/Stop and reversing using the
same signal. A start signal through terminal 18 starts the drive in the
forward direction. If both terminal 18 and a reversing and start terminal
are given a logic 1 at the same time, the drive will not start. It is not
active in Closed Loop.
Speed Up and Speed Down are selected if digital control of the up/
down speed is desired. This function is only active if Freeze Reference
or Freeze Output has been selected.
53
Page 54
As long as there is a logic 1 on the terminal selected for Speed Up, the
reference or the output frequency will increase by the Ramp-up Time
set in parameter 206.
As long as there is a logic 1 on the terminal selected for Speed Down,
the reference or the output frequency will decrease by the Ramp-downTime set in parameter 207.
Pulses (logic 1 minimum high for 3ms and a minimum pause of 3ms)
will lead to a change of speed of 0.1% (reference) or 0.1 Hz (output
frequency).
The speed reference frozen through the control panel can be changed
even if the drive has stopped. In addition, the frozen reference will be
retained in memory after power interruption.
Run Permissive.Run Permissive is used to require a second run
permission signal in addition to the normal run command, either in
Hand or Auto mode. When a run command alone is given, the display
will show RUN REQ., but the drive will not start. The drive can also
indicate that a run has been requested through one of the transistorized
or relay outputs. When, in addition to the run command, a logic 1 is
applied to the Run Permissive terminal, the drive will run. If more than
one terminal is programmed for Run Permissive, a logic 1 at any of
these terminals will allow the drive to run.
Jog is used to start the drive and run it at the frequency set in
parameter 209, Jog Frequency. Jog is active in both Hand and Auto
mode.
Jog is not active if a stop command has been given through the keypad
or terminal 27.
Pulse reference is selected if the frequency of a pulse train is to be
used as a reference signal. 0 Hz corresponds to parameter 204,
Minimum Reference. The frequency set in parameter 327, Pulse
Reference, Maximum Frequency corresponds to parameter 205
Maximum Reference.
Pulse feedback is selected if the frequency of a pulse train is to be
used as a feedback signal. Parameter 328, Pulse Feedback, MaximumFrequency is the pulse frequency that corresponds to maximum
feedback.
Hand start is selected if an external signal is used to switch the drive
to Hand mode. A logic 1 (Hand Start active) will start the motor. A logic
0 will stop the motor. The drive will then be in OFF/STOP mode,
unless there is an active Auto Start signal from an external source.
Programming one of the digital inputs for Hand Start will disable the
LCP Hand Start and Auto Start keys.
WARNING
!
Unintended Start!
With Hand Start active, digital inputs may cause
drive to start at any time. The drive, motor, and
any driven equipment must be in operational
readiness. Failure to be in operational readiness
with Hand Start active could result in death,
serious injury, or equipment or property
damage.
Auto start is selected if an external signal is sent to switch the drive to
Auto mode. When a start signal is active on the control terminals or the
serial communication port, the drive will start the motor. If Auto Start and
Hand Start are active at the same time on the control terminals, Auto
Start will have the higher priority. If Auto Start and Hand Start are not
active, the motor will stop and the drive will then be in the OFF/STOP
mode. Programming one of the digital inputs for Auto Start will disable
the LCP Hand Start and Auto Start keys.
Data change lock is selected if changes to parameters are not to be
made via the control panel. It is be possible to change parameters
through the serial bus.
54
Page 55
Analog Inputs
Two analog inputs for voltage signals, terminals 53 and 54, and an
analog input for current, terminal 60, are provided for reference and
feedback signals. A thermistor can be connected to the voltage inputs,
terminals 53 or 54.
Feedback. If a feedback signal is connected, a voltage input may be
connected to either terminal 53 or 54, or a current input conected to
terminal 60. If a two zone PID control is used, the feedback signals must
be voltage inputs and applied to terminals 53 and 54. See FeedbackHandling.
The two analog voltage inputs can be scaled over the range of
0to10VDC. The current input can be scaled over the range of 0
to20mA.
The table below shows the possible analog input programming.
Parameter 317, Time Out, and Parameter 318, Function After TimeOut, allow activation of a time-out function on all analog inputs. If the
signal value of the reference or feedback signal connected to one of the
analog input terminals drops below 50% of the minimum scaling, the
function set in parameter 318, Function After Time Out, will be
activated after the time-out set in parameter 317.
Analog InputsTerminal Number
53 (Voltage)54 (Voltage)
308Terminal 53, Analog Input Voltage
60 (Current)
(AI [V] 53 FUNCT.)
Function:
This parameter is used to select the required function to be linked to
terminal 53.
Description of choice:
No operation. Selected if the drive is not to react to signals connected
to the terminal.
Reference. Selected to enable change of reference by means of an
analog reference signal. If reference signals are connected to several
inputs, these reference signals will be summed.
Thermistor. Selected if a thermistor in the motor stops the drive in case
of motor overtemperature. The cutout value is 3kohm. A Klixonthermal
switch may also be connected to this input. If parallel sensors are used,
the thermistors/thermal switches can be connected in series. The drive
will shut down when the total resistance exceeds 3 kohms.
NOTE
When a thermistor is mounted in motor wiring,
a breakdown of insulation between thermistor
and motor can feed high voltage back to drive
control terminals. To comply with protective
extra-low voltage (PELV) grounding
requirements, if applicable, thermistor must be
mounted externally.
Parameter 117, Motor Thermal Protection, must be programmed for
Thermal Warning or Thermistor Trip, and the thermistor must be
inserted between terminal 53 or 54, analog voltage input, and terminal
50, 10V supply.
Analog InputsTerminal Number535460
Param eter308311314
Value:
No operation(NO OPERATION)★[0]★[0][0]
Reference(REFERENCE[1][1]★[1]
Feedback(FEEDBACK)[2][2][2]
Thermistor(THERMISTOR)[3][3]
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
55
Page 56
309Terminal 53, Minimum Scaling
(AI 53 SCALE LOW)
Value:
0.0 to 10.0 V★ 0.0 V
312Terminal 54, Minimum Scaling
(AI 54 SCALE LOW)
Value:
0.0 to 10.0 V★ 0.0 V
Function:
This parameter is used for setting the signal value that corresponds to
the minimum reference or the minimum feedback, parameter 204,
Minimum Reference, or parameter 413, Minimum Feedback. See
Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage
losses in long signal lines should be compensated for. If the time out
functions in parameter 317, Time Out, and parameter 318, FunctionAfter Time Out, are to be used, the value must be set to >1 V.
310Terminal 53, Maximum Scaling
(AI 53 SCALE HIGH)
Value:
0.0 to 10.0 V★ 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the
maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See
Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal lines should be
compensated for.
311Terminal 54, Analog Input Voltage
(AI [V] 54 FUNCT.)
Value:
See the description of parameter 308. ★ No operation
Function:
This parameter selects the function of terminal 54.
The input signal is scaled by parameter 312, Terminal 54, MinimumScaling, and by parameter 313, Terminal 54, Maximum Scaling.
Description of choice:
See description of parameter 308.
Function:
This parameter is used to set the signal value that corresponds to the
minimum reference value or the minimum feedback, parameter 204,
Minimum Reference, and parameter 413, Minimum Feedback. See
Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage
losses in long signal lines should be compensated for.
If the time out function is to be applied, parameter 317, Time Out, an d
parameter 318, Function After Time Out, the value must be set to >1 V.
313Terminal 54, Maximum Scaling
(AI 54 SCALE HIGH)
Value:
0.0 to 10.0 V★ 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the
maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See
Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage
losses in long signal lines should be compensated for.
314Terminal 60, Analog Input Current
(AI [mA] 60 FUNCT.)
Value:
See description of parameter 308. ★ Reference
Function:
This parameter selects the function of terminal 60.
Scaling of the input signal is set by parameter 315, Terminal 60,
Minimum Scaling, and by parameter 316, Terminal 60, Maximum
Scaling.
Description of choice:
See description of parameter 308, Terminal 53, Analog Input Voltage.
For reasons of accuracy, voltage losses in long signal lines should be
compensated for.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
56
Page 57
315Terminal 60, Minimum Scaling
(AI 60 SCALE LOW)
Value:
0.0 to 20.0 mA★ 4 .0 mA
317Time Out
(LIVE ZERO TIME)
Value:
1 to 99 sec.★ 10 sec.
Function:
This parameter determines the signal value that corresponds to the
minimum reference or the minimum feedback, parameter 204 Minimum
Reference, parameter 413, Minimum Feedback. See Reference
Handling or Feedback Handling.
Description of choice:
Set the required current value.
If the time-out function is to be used, parameter 317, Time Out, and
parameter 318, Function After Time Out, the value must be set to
>2mA.
316Terminal 60, Maximum Scaling
(AI 60 SCALE HIGH)
Value:
0.0 to 20.0 mA★ 20.0 mA
Function:
This parameter determines the signal value that corresponds to the
maximum reference or maximum feedback, parameter 205, Maximum
Reference Value, or parameter 414, Maximum Feedback. See
Reference Handling or Feedback Handling.
Description of choice:
Set the desired current value.
Function:
If the signal value of the reference or feedback signal connected to one
of the input terminals 53, 54 or 60 drops to below 50% of the minimum
scaling for a longer period than the Live Zero time, the function selected
in parameter 318, Function After Time Out, will be activated.
This function will only be active if, in parameter 309 or 312, a value has
been selected for Terminals 53 and 54, Minimum Scaling, that exceeds
1 V, or if, in parameter 315, Terminal 60, Minimum Scaling, a value
has been selected that exceeds 2 mA.
Description of choice:
Set the desired time.
318Function After Time Out
(LIVE ZERO FUNCT.)
Value:
★ Off (NO FUNCTION)[0]
Freeze output frequency
(FREEZE OUTPUT FREQ.)[1]
Stop (STOP)[2]
Jog (JOG FREQUENCY)[3]
Max. output frequency (MAX FREQUENCY)[4]
Stop and trip (STOP AND TRIP)[5]
Function:
This is where to select the function to be activated after the end of the
time-out period, parameter 317, Time Out.
If a time-out function occurs at the same time as a bus time-out function,
parameter 510, Bus Time Interval Function, the time-out function in
parameter 318 will be activated.
Description of choice:
The output frequency of the drive can:
-go to minimum (NO FUNCTION)
-be frozen at the present value (FREEZE OUTPUT
FREQUENCY)
-stop (STOP)
-run at the jog frequency set in parameter 209
(JOGFREQUENCY)
-run at the maximum frequency set in parameter 202
(MAX.FREQUENCY)
-stop and send an alarm (STOP AND TRIP)
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
57
Page 58
Analog/Digital Outputs
The two analog/digital outputs available through terminals 42 and 45
can be programmed to show a status or an analog value such as
For the analog output, there is a choice of three types of output signal:
0 to 20 mA, 4 to 20 mA or 0to32000 pulses. The pulse rate is set by
parameter 322, Terminal 45, Output, Pulse Scaling.
frequency. The status signal is a 24 VDC output.
See the Electrical Installation, Control Terminals section of this manual
for the ratings of these outputs.
Value:
No function (NO FUNCTION)[0][0]
Drive ready (READY)[1][1]
Standby (ENABLED & NO WARNING)[2][2]
Running (RUNNING)[3][3]
Running at ref. value (RUNNING AT REFERENCE)[4][4]
Running, no warning (RUNNING NO WARNING)[5][5]
Local reference active (DRIVE IN LOCAL REF.)[6][6]
Remote controlled references active (DRIVE IN REMOTE REF.)[7][7]
Alarm (ALARM)[8][8]
Alarm or warning (ALARM OR WARNING)[9][9]
No alarm (NO ALARM)[10][10]
Current limit (CURRENT LIMIT)[11][11]
Safety interlock (SAFETY INTERLOCK)[12][12]
Start command active (START SIGNAL APPLIED)[13][13]
Reversing (RUNNING IN REVERSE)[14][14]
Thermal warning (THERMAL WARNING)[15][15]
Hand mode active (DRIVE IN HAND MODE)[16][16]
Auto mode active (DRIVE IN AUTO MODE)[17][17]
Sleep mode (SLEEP MODE)[18][18]
Output frequency lower than parameter 223 (F OUT < F LOW)[19][19]
Output frequency higher than parameter 223 (F OUT > F HIGH)[20][20]
Out of frequency range (FREQ. RANGE WARN.)[21][21]
Output current lower than low current, parameter 221 (I OUT < I LOW)[22][22]
Output current higher than high current, parameter 222 (I OUT > I HIGH)[23][23]
Out of current range (CURRENT RANGE WARN)[24][24]
Out of feedback range (FEEDBACK RANGE WARN.)[25][25]
Out of reference range (REFERENCE RANGE WARN)[26][26]
Relay 123 (RELAY 123)[27][27]
Input phase loss (MAINS PHASE LOSS)[28][28]
Output frequency, (OUT. FREQ. 0-20 mA)[29][29]
Output frequency, (OUT. FREQ. 4-20 mA)[30] ★ [30]
Output frequency (pulse sequence), (OUT. FREQ. PULSE)[31][31]
External reference, (EXT. REF. 0-20 mA)[32][32]
External reference, (EXTERNAL REF. 4-20 mA)[33][33]
External reference (pulse sequence), (EXTERNAL REF. PULSE)[34][34]
Feedback, (FEEDBACK 0-20 mA)[35][35]
Feedback, (FEEDBACK 4-20 mA)[36][36]
Feedback (pulse sequence), (FEEDBACK PULSE)[37][37]
Output current, 0-20 mA (MOTOR CUR. 0-20mA)[38][38]
Output current, 4-20 mA (MOTOR CUR. 4-20mA)★ [39][39]
Output current (pulse sequence), (MOTOR CUR PULSE)[40][40]
Output power, 0-20 mA (MOTOR POWER 0-20mA)[41][41]
Output power, 4-20 mA (MOTOR POWER 4-20mA)[42][42]
Output power (pulse sequence), 0- 32000 pulses (MOTOR POWER PULSE)[43][43]
Controlled by serial bus: 0-20 mA (BUS CONTROL 0-20MA)[44][44]
Controlled by serial bus: 4-20 mA (BUS CONTROL 4-20MA)[45][45]
Controlled by serial bus: pulses (BUS CONTROL PULSE)[46][46]
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
58
Page 59
Function:
These outputs can act both as digital and analog outputs. If used as a
digital output, a 0 or 24 VDC signal is transmitted. If used as an analog
output, either a 0 to 20 mA signal, a 4 to 20 mA signal, or a pulse
sequence with a frequency of 0 to up to 32,000 Hz is transmitted.
Description of choice:
No function. Selected if this output is always to remain off.
Drive ready. The drives control card receives a supply voltage and
the drive is ready for operation.
Output frequency lower than low frequency warning level. The
output frequency is lower than the value set in parameter 223,
Warning: Low Frequency.
Output frequency higher than high frequency warning level.
The output frequency is higher than the value set in parameter 224,
Warning: High Frequency.
Out of frequency range. The output frequency is outside the
frequency range programmed in parameter 223, Warning: LowFrequency, and 224, Warning: High Frequency.
Stand by. The drive is ready for operation, but no start command has
been given. No warning.
Running. The drive is running or the drive is in the sleep mode.
Running at ref. value. The drive is at the speed commanded by the
reference.
Running, no warning. The drive is running and there are no
warnings.
Local reference active. The motors speed is being controlled by the
local reference through the keypad. This output will also be on if the
drive is set up for local speed control but the jog function has been
activated.
Remote references active. The motors speed is being controlled by
a remote reference or a preset speed.
Alarm. The drive has been stopped by an alarm.
Alarm or warning. An alarm or a warning exists in the drive.
No alarm. The drive has no alarm.
Current limit. The output current is greater than or equal to the value
programmed in parameter 215, Current Limit. The speed of the drive
is being limited to keep the current from increasing.
Output current lower than low current warning level. The output
current is lower than the value set in parameter 221, Warning: LowCurrent. This can be used to indicate a broken belt.
Output current higher than high current warning level. The
output current is higher than the value set in parameter 222, Warning:
High Current.
Out of current range. The output current is outside the range
programmed in parameter 221, Warning: Low Current, and parameter
Warning: High Current.
222,
Out of feedback range. The feedback signal is outside the range
programmed in parameter 227 Warning: Low Feedback, and 228
Warning: High feedback.
Out of reference range. The reference is outside the range
programmed in parameter 225, Warning: Low Reference, and
parameter 226, Warning: High Reference.
Relay 123. This function is only used when a Profibus option card is installed.
Input phase loss. An incoming power phase is missing.
Safety interlock. Terminal 27 has been programmed for Safety
Interlock in parameter 304, and no control voltage has been applied to it.
Start command active. The drive is either running or it has received
a run command. This is commonly used in conjunction with the drives
run permissive control.
Reversing. The drive is running in the reverse direction.
Thermal warning. The temperature limit of either the motor, the drive,
or a thermistor connected to an analog input has been exceeded.
Hand mode active. The drive is operating in the Hand run/stop mode.
Auto mode active. The drive is operating in the Auto run/stop mode.
Sleep mode. The drive is stopped because of Sleep Mode.
59
Page 60
Output frequency: 0 to 20 mA, 4 to 20 mA, and pulses. An output
signal proportional to the output frequency in the range from 0 to
Output Frequency, High Limit, set by parameter 202. Maximum pulse
frequency is determined in parameters 320, Terminal 42, Output PulseScaling, and 322, Terminal 45, Output Pulse Scaling.
External reference: 0 to 20 mA, 4 to 20 mA, and pulses. An output
signal proportional to the resulting reference value in the range from
Minimum Reference to Maximum Reference, set by parameters 204
and 205. Maximum pulse frequency is determined in parameters 320,
Feedback Minimum to Feedback Maximum: 0 to 20 mA, 4 to 20
mA, and pulses. An output signal proportional to the reference value
in the range from Minimum Feedback to Maximum Feedback, set by
parameters 413 and 414. Maximum pulse frequency is determined in
parameters 320, Terminal 42, Output Pulse Scaling, and 322,Terminal 45, Output Pulse Scaling.
Output Current: to 20 mA, 4 to 20 mA, and pulses. An output
signal proportional to the output current in the range from 0 to the
maximum drive output current. Maximum pulse frequency is determined
in parameters 320, Terminal 42, Output Pulse Scaling, and 322,Terminal 45, Output Pulse Scaling.
Output power: 0 to 20 mA, 4 to 20 mA, and pulses. Generates an
output signal proportional to the present output power. 20 mA
corresponds to the value set by parameter 102, Motor Power.
Maximum pulse frequency is determined in parameters 320, Terminal
Bus Control: 0 to 20 mA, 4 to 20 mA, and pulses. Generates a
proportional output signal provided over a serial communication bus.
The serial bus value for output terminal 42 is written to parameter 364
and the serial bus value for output terminal 45 is written to parameter
365. Maximum pulse frequency is determined in parameters 320,
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
321Terminal 45, Output
(AO 45 FUNCTION)
Value:
★ OUT. FREQ. 4 - 20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When
used as a digital output, it generates a 24 V (max. 40 mA) signal. For
the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a
pulse sequence.
Description of choice:
See the description of analog/digital outputs.
322Terminal 45, Output Pulse Scaling
(AO 45 PULS SCALE)
Value:
1 to 32000 Hz★ 5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
319Terminal 42, Output
(AO 42 FUNCTION)
Value:
★ MOTOR CUR. 4-20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When
used as a digital output, it generates a 24 V (max. 40 mA) signal. For
the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a
pulse sequence.
Description of choice:
See the description of analog/digital outputs.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
24 VDC, 10 mA
The high voltage relay connections are located
near the input power and motor terminals.
The low voltage relay terminals are
located on the control wiring terminal
strips.
Relay outputsRelay Number:12
Parameter:323326
Value:
No function (NO FUNCTION)[0][0]
Drive ready (READY)[1][1]
Waiting for start (ENABLED & NO WARNING)[2][2]
Running (RUNNING)[3] ★ [3]
Running at reference value (RUNNING AT REFERENCE)[4][4]
Running, no warning (RUNNING NO WARNING)[5][5]
Local reference active (DRIVE IN LOCAL REF)[6][6]
Remote controlled references active (DRIVE IN REMOTE REF.)[7][7]
Alarm (ALARM)[8][8]
Alarm or warning (ALARM OR WARNING)[9][9]
No alarm (NO ALARM) ★ [10][10]
Current limit (CURRENT LIMIT)[11][11]
Safety interlock (SAFETY INTERLOCK)[12][12]
Start command active (START SIGNAL APPLIED)[13][13]
Running in reverse (RUNNING IN REVERSE)[14][14]
Thermal warning (THERMAL WARNING)[15][15]
Hand mode active (DRIVE IN HAND MODE)[16][16]
Auto mode active (DRIVE IN AUTO MODE)[17][17]
Sleep mode active (SLEEP MODE)[18][18]
Output frequency lower than low frequency, parameter 223 (F OUT < F LOW)[19][19]
Output frequency higher than high frequency, parameter 224 (F OUT > F HIGH)[20][20]
Out of frequency range (FREQ RANGE WARN.)[21][21]
Output current lower than low current, parameter 221 (I OUT < I LOW)[22][22]
Output current higher than high current, parameter 222 (I OUT > I HIGH)[23][23]
Out of current range (CURRENT RANGE WARN.)[24][24]
Out of feedback range (FEEDBACK RANGE WARN.)[25][25]
Out of reference range (REFERENCE RANGE WARN.)[26][26]
Relay 123 (RELAY 123)[27][27]
Input phase loss (MAINS PHASE LOSS)[28][28]
Control word bit 11/12 (CONTROL WORD 11/12)[29][29]
42.5 VDC, 1 A
Function:
Relay outputs 1 and 2 can be used to give the present status or a
warning. See the description of options in Analog/Digital Outputs.
Control word bit 11/12 [29]. Relay 1 and relay 2 can be activated
through serial communication. Bit 11 activates relay 1 and bit 12
activates relay 2.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
If parameter 556, Bus Time Interval Function, becomes active, relay 1
and relay 2 will cut out if they are activated through serial
communication.
Description of choice:
Select the output relay function.
61
Page 62
323Relay 1, Output Function
(RELAY1 FUNCTION)
Function:
★ NO ALARM
Relay 1 is a form C relay that can be used for status indications and
warnings. The relay is activated when the programmed condition
occurs.
Time delays for relay 1 are programmed in parameter 324, Relay 1,ON Delay, and parameter 325, Relay 1, OFF Delay.
Description of choice:
See data choice and connections under Relay Outputs.
324Relay 1, ON Delay
(RELAY1 ON DELAY)
Value:
0 to 600 sec.★ 0 sec.
Function:
This parameter determines the time delay before the relay activates.
Description of choice:
Enter the desired value.
327Pulse Reference, Maximum Frequency
(PULSE REF. MAX)
Value:
100 to 65,000 Hz at terminal 29★ 5,000 Hz
100 to 5,000 Hz at terminal 17
Function:
This parameter is used to set the pulse value that corresponds to the
maximum reference, parameter 205, Maximum Reference.
The pulse reference signal can be connected to terminal 17 or 29.
Description of choice:
Set the required maximum pulse reference.
328Pulse Feedback, Maximum Frequency
(PULSE FDBK MAX.)
Value:
100 to 65,000 Hz at terminal 33 ★ 25,000 Hz
Function:
This parameter is used to set the pulse value that corresponds to the
maximum feedback value. The pulse feedback signal is connected to
terminal 33.
325Relay 1, OFF Delay
(RELAY1 OFF DELAY)
Value:
0 to 600 sec.★ 2 sec.
Function:
This parameter determines the time delay before the relay deactivates.
Description of choice:
Enter the desired value.
326Relay 2, Output Function
(RELAY2 FUNCTION)
Value:
See the functions of relay 1. ★ RUNNING
Function:
Relay 2 is a form A relay that can be used for status indications and
warnings. The relay is activated when the programmed condition
occurs.
Description of choice:
See data choice and connections under Relay Outputs.
Description of choice:
Set the desired feedback value.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
62
Page 63
Application Functions
Parameters 400 through 427
Special functions of the drive are set up in this parameter group. This
includes the proportional, integral, derivative controller (PID) and
setting the sleep mode function.
Additionally, this parameter group includes:
Reset function
Flying start
Interference reduction
Lossof load
Carrier frequency
Selectionofprocess units
WARNING
!
Unintended Start!
With any automatic reset active, digital inputs
may cause drive to start at any time. The drive,
motor, and any driven equipment must be in
operational readiness. Failure to be in
operational readiness with automatic reset
active could result in death, serious injury, or
equipment or property damage.
400Reset Function(RESET FUNCTION)
Value:
Manual reset (MANUAL RESET)[0]
Automatic reset x 1 (AUTOMATIC X 1)[1]
Automatic reset x 2 (AUTOMATIC X 2)[2]
Automatic reset x 3 (AUTOMATIC X 3)[3]
Automatic reset x 4 (AUTOMATIC X 4)[4]
Automatic reset x 5 (AUTOMATIC X 5)[5]
Automatic reset x 10 (AUTOMATIC X 10)[6]
Automatic reset x 15 (AUTOMATIC X 15)[7]
Automatic reset x 20 (AUTOMATIC X 20)[8]
This parameter sets the automatic reset time delay until each reset is
attempted. One of the automatic resets must be selected in parameter
400, Reset Function.
Description of choice:
Set the desired time before each restart attempt.
CAUTION
!
Motor Rotation!
When parameter 402, Flying Start, is enabled,
motor may turn forward and reverse a few
revolutions even with motor stopped. In highly
dynamic pumping processes, it is recommended
to disable Flying Start function. Using Flying Start
in highly dynamic pumping processes could
result in injury or equiment or property damage.
402Flying Start(FLYING START)
Value:
★ Disable (DISABLE)[0]
Enable (ENABLE)[1]
DC brake and start (DC BRAKE AND START)[3]
Function:
This function makes it possible for the drive to catch a rotating motor
when the drive is started. The drive will sense the speed of rotation and
direction of rotation of the motor and synchronize with it.
This function is active whenever a start command is present.
For the drive to catch the spinning motor, the motor speed must be
lower than the maximum frequency set in parameter 202.
Function:
This parameter allows a choice of manual or automatic reset after a fault
trip. There is also a choice of the number of times the unit will attempt to
restart. The time between each attempt is set in parameter 401,
Automatic Restart Time.
Description of choice:
If Manual Reset is selected, the Reset key must be pressed or a digital
input given to reset the drive.
If auto reset after a fault trip is desired, select one of the Automatic reset
choices.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
Description of choice:
Select Disable if this function is not required.
Select Enable if the drive is to catch and control a rotating motor.
Select DC brake and start if the drive is to brake the motor by means of
the DC brake first, and then start. Ensure that parameters 114 through
116, DC Braking, are set appropriately. Select DC brake and start if the
motor may be externally driven at a significant speed in the reverse
direction.
NOTE
For fan applications, factory setting for FlyingStart is Enable. For pump applications, factory
setting for Flying Start is Disable.
63
Page 64
Sleep Mode
Sleep mode makes it possible to stop the drive when the system
demand drops below a preset level. When the demand increases to a
higher preset level, the drive will restart. A significant amount of energy
can be saved using sleep mode. Unlike a set-back time clock, the drive
is always available to run when the demand reaches the preset wake
up level. Sleep mode is not active if Local Reference is selected in
parameter 203, Reference Handling, or if the Jog function activates via
digital inputs. Sleep mode operates in both Open Loop and ClosedLoop.
Activate sleep mode in parameter 403, Sleep Mode Timer. In this
parameter, set how long the output frequency must be lower than the
sleep frequency set in parameter 404, Sleep Frequency, before sleep
mode activates. After the set time, the drive will ramp down the motor to
a stop, as controlled by parameter 207, Ramp Down Time. If the output
frequency needed to meet the system demand rises above the sleep
frequency during the timed period, the drive will simply ramp up to the
demanded frequency.
When the sleep mode timer expires and the drive is stopped in sleep
mode, a theoretical output frequency is calculated based upon the
reference signal. When the theoretical output frequency rises above the
frequency set in parameter 405, Wake-up Frequency, the drive will
restart the motor and ramp up to the commanded reference.
For closed loop operation, it may be useful to over satisfy the system
before putting the drive into sleep mode. The boost setpoint parameter
provides for this. After the sleep mode timer expires, the drive will reset
the set point based on the value in parameter 406, Boost Setpoint.
Once this new setpoint is satisfied, the drive enters sleep mode. A
setting of 100% in parameter 406, Boost Setpoint, indicates no setpoint
boost. Boost setpoint is only active in Closed Loop, selected in
parameter 100, Configuration.
64
Sleep Mode Frequency Response
Page 65
WARNING
!
Unintended Start!
In Sleep Mode, a start signal via digital inputs
may cause drive to start at any time. The drive,
motor, and any driven equipment must be in
operational readiness. Failure to be in
operational readiness in Sleep Mode could
result in death, serious injury, or equipment or
property damage.
405Wake-up Frequency (WAKEUP FREQUENCY)
Value:
Parameter 404 to parameter 202, Maximum Frequency
★ 60 Hz
Function:
When the theoretical output frequency exceeds the preset value, the
drive restarts the motor.
Description of choice:
Set the required frequency.
403Sleep Mode Timer(SLEEP MODE TIMER)
Value:
0 to 300 seconds (OFF)★ OFF
Function:
This parameter enables the drive to stop the motor if the load on the
system is minimal. The timer starts when the output frequency drops
below the frequency set in parameter 404, Sleep Frequency. When the
time set has passed, the drive will stop. The drive will restart when the
theoretical output frequency exceeds the frequency set in parameter
405, Wake-up Frequency.
Description of choice:
Select OFF if this function is not wanted.
Set the amount of time that the drive must run at or below the sleep
frequency before it stops and goes to sleep.
404Sleep Frequency (SLEEP FREQUENCY)
Value:
0.0 to parameter 405, Wake-up Frequency★ 0.0 Hz
Function:
When the output frequency falls below this set value, the timer set in
parameter 403, Sleep Mode Timer, will start. The drives speed will
follow the reference signal until the timer times out.
406Boost Setpoint(BOOST SETPOINT)
Value:
0 to 200 % ★ 100 % of setpoint
Function:
This function can only be used if Closed Loop has been selected in
parameter 100, Configuration.
In some systems, it may advantageous to increase the set point of the
system before the drive stops the motor. This extends the time that the
drive will be stopped and reduces cycling of the motor.
Description of choice:
Set the required Boost Setpoint as a percentage of the resulting
reference under normal operation. 100% corresponds to the boost.
Description of choice:
Choose the output frequency at which the drive will activate the sleep
mode timer. It is generally best to set SLEEP FREQUENCY equal to the
minimum frequency set in parameter 201, Output Frequency Low Limit
and parameter 204, Minimum Reference. This is because the sleep
mode isnt active until after the drive output frequency equals the sleep
frequency. If the sleep frequency is less than the minimums, the sleep
mode cannot activate.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
65
Page 66
407Switching Frequency(SWITCHING FREQ.)
Value:
Depends on the current rating of the unit.
Function:
The value of this parameter determines the maximum switching
frequency of the inverter. If Fixed Switching Frequency has been
selected in parameter 408, Interference Reduction Method, this will be
the fixed inverter switching frequency. Changing the switching
frequency may reduce audible noise from the motor. The output
frequency of the drive can never be a greater than 1/10 of the
switching frequency.
Description of choice:
When the motor is running, the switching frequency may be adjusted
by parameter 407, Switching Frequency, until the sound level is as low
as possible.
Used to select different methods for reducing the amount of audible
noise from the motor.
Description of choice:
ASFM (Automatic Switching Frequency Modulation) uses the
maximum switching frequency possible while providing the output
required by the load. The load is automatically monitored and the
switching frequency set accordingly. The maximum switching frequency
is set in parameter 407, Switching Frequency.
Switching frequencies higher than 4.5 kHz will result in automatic
derating of the maximum continuous output current of the drive. The
derate is linear from 4.5 kHz to the maximum switching frequency of the
drive. At maximum switching frequency, the continuous output current
from the drive will be limited to 60% of the rated current. To avoid
possible problems at high load when using a high switching frequency,
it may be desirable to select Automatic Switching Frequency Modulation
in parameter 408, below.
NOTE
Switching frequencies higher than 4.5 kHz
automatically derate maximum continuous
output of drive.
FixedSwitching Frequency makes it possible to set a fixed switching
frequency. The switching frequency is set in parameter 407, Switching
Frequency.
LC-filter fitted is to be used if an LC filter is installed between the drive
and the motor. This prevents excessive heating of the LC filter.
409Function in Case of No Load
(FUNCT. LOW CURR.)
Value:
Trip (TRIP)[0]
★ Warning (WARNING)[1]
Function:
This parameter can be used for monitoring the V-belt of a fan or other
power transmission component to make sure it has not broken. This
function is activated when the output current goes below the current level
set in parameter 221, Warning: Low Current. This function is not active
during a start until the drive has reached the speed reference. It is also
not active while the drive is stopped or while it is decelerating to a stop.
Description of choice:
In the case of a Trip, the drive will stop the motor if the output current
drops below the value set in parameter 221.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
66
If Warning is selected, the drive will give a warning if the output current
drops below the value set in parameter 221.
This determines the action of the drive when one of the incoming power
phases is lost. Some action is required to control the level of ripple
voltage on the DC bus to avoid damage to the DC bus capacitors.
Drive display will show MAINS PHASE LOSS.
Select the function to be activated when the drive is exposed to an
overtemperature condition.
Description of choice:
At Trip, the drive stops the motor and exports an alarm.
Description of choice:
At Trip, the drive stops the motor within a few seconds (depending on
drive size).
If Autoderate & Warning is selected, the drive will export a warning and
reduce the output current to 30% of maximum current to maintain
operation.
CAUTION
Input Phase Loss!
If Warning is selected, life expectancy of the
drive could be reduced if input phase loss
persists. Select Warning only when input phase
loss is known to be temporary.
At Warning, only a warning will be exported when an input phase loss
occurs, but in severe cases, other extreme conditions might result in a
trip.
For drives with software version 2.0 or later, select Autoderate &Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
CAUTION
At Autoderate & Warning, the drive first reduces the switching
frequency to minimize internal loss. If the overtemperature condition
persists, the drive reduces the output current until the heat sink
temperature stabilizes. A warning is issued when the function is active.
For drives with software version 2.0 or later, select Autoderate &Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
412Trip Delay Overcurrent
(OVERLOAD DELAY)
Value:
OFF or 0 to 60 sec.★ OFF
Function:
When the output current has reached the current limit set in parameter
215, Current Limit, and remains there for the time selected in this
parameter, the drive will trip.
Description of choice:
Select how long the drive will run in current limit before it trips.
Overheating Hazard!
At phase loss, the cooling fan of NEMA 12 drives
cannot be powered. To avoid overheating, an
external power supply can be connected.
Contact Trane for further information. Failure
to provide fan cooling may result in equipment
damage.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
67
Page 68
Feedback Signals in Open Loop
In some drives, feedback signals and feedback parameters are only
used in closed loop operation. In the TR1, the feedback signals are
also active in open loop operation. Although they dont effect the speed
of the drive, they can be displayed on the drives meters. Parameters
227 and 228 can set high and low limits for the feedback signals, which
can activate warnings.
For open or closed loop operation, the feedback signal is scaled in
parameters 413 and 414 Minimum and Maximum Feedback, and the
unit displayed is chosen in parameter 415, Process Units.
413Minimum Feedback
(MIN. FEEDBACK)
Value:
-999,999.999 to Maximum Feedback, Parameter 414★ 0.000
Function:
Parameters 413 Minimum Feedback and 414 Maximum Feedback,
are used to scale the feedback signal.
Description of choice:
Set the value to be shown on the display when the feedback signal is at
its minimum value.
See the description of parameter 413, Minimum Feedback.
Description of choice:
Set the value to be shown on the display when the feedback signal is at
its maximum value.
Function:
Selects the unit shown on the feedback display.
The selected unit is used if Reference [unit] or Feedback [unit] has
been selected in one of the parameters 007 through 010, as well as in
the Display Mode. It will be the unit for Minimum/Maximum Feedback.
In Closed Loop, the unit is also used as the unit for Minimum/MaximumReference and Minimum/Maximum Feedback, as well as Setpoint 1
and Setpoint 2.
Description of choice:
Select the unit for the reference/feedback signal.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
68
Page 69
PID for Process Regulation
The built-in proportional, integral, derivative (PID) controller in the
drive maintains a constant condition (pressure, temperature, flow, etc.)
in the system. It adjusts motor speed based upon a reference and/or
setpoint and the feedback signal. The PID controller is activated by
setting parameter 100, Configuration, to Closed loop.
Reference (Setpoint)
In parameter 205, Maximum Reference, the maximum value of the sum
of all reference signals is set.
The Minimum Reference, set in parameter 204, indicates the smallest
value that the resulting reference can assume.
A transmitter supplies the PID controller with a feedback signal from the
process to indicate its current state. The type of feedback signal in use
depends upon the type of process.
This means that deviations that occur between the reference/setpoint
and the actual process state are sensed. Such deviations are
compensated for by the PID regulator by adjusting the output frequency
as required by the difference (or error) between the reference/setpoint
and the feedback signal.
The PID controller in the drive has been designed for use in HVAC
applications and to perform a number of specialized functions.
Previously, it was necessary for a building management system to
handle these special functions by installing extra modules to program
the system.
With the TR1, there is no need for extra modules to be installed. Only
the reference and/or setpoint and a selected feedback signal need to
be programmed. An advanced feature of the TR1 is the drives ability to
accept two feedback signals, making two-zone regulation possible.
Voltage drop in long control cables can be compensated for by using
the scaling parameters for the analog inputs.
Feedback
The feedback signal must be connected to the drive according to the
table below, depending on the type of feedback signal and the settings
of the associated parameters listed.
The reference range cannot exceed the feedback range.
If multiple Preset References are required, use multiple setups or set
them in parameters 211 to 214 Preset Reference. See ReferenceHandling.
If a current signal is used as a feedback signal, voltage can be used as
an analog reference. Use the table below to decide which terminal to
use and which parameters to program.
Reference typeTerminal Parame ters
Pulse17 or 29301 or 305
Voltage53 or 54308, 309, 310 or
311, 312, 313
Current60314, 315, 316
Preset reference211, 212, 213, 214
Setpoints418, 419
Bus reference *68 and 69
* The bus reference can only be set by serial communication.
Terminals that are not used should be set to No function.
Inverse Regulation
Normal regulation means that the motor speed increases when the
reference/setpoint is higher than the feedback signal. Inverse regulation means that the motor speed decreases when the reference/setpoint
is higher than the feedback signal. If there is a need for inverse
regulation, inverse must be programmed in parameter 420, PID
Normal/Inverse Control.
Feedback typeTerminal Parameter s
Pulse33307
Voltage53 or 54308, 309, 310 or
Current60314, 315, 316
Bus feedback 1*68 and 69537
Bus feedback 2*68 and 69538
* The bus feedbacks can only be set by serial communication.
If two analog feedback signals are to be used, they both must be
voltage signals.
The MinimumFeedback and Maximum Feedback, parameters 413
and 414, must be set for the feedback signals. The type of process unit
for the signals is selected in parameter 415, Process Units.
311, 312, 313
Anti-windup
The process controller is factory set with an active anti-windup function.
This function ensures that when either a frequency limit or a current limit
is reached, the integrator will be reset to zero. If the frequency limit or
current limit is cleared, the integrator will turn on again. This function
can be disabled in parameter 421, PID Anti-windup.
Start-up Conditions
In some applications, the optimum setting of the process regulator takes
a long time to reach. In such cases, a start-up frequency can be
entered in parameter 422, PID Start-up Frequency. The drive will
ramp directly to this frequency before PID control begins. This avoids
control by deviation between the reference/setpoint and the actual state
of the process during acceleration. It also avoids overshoot of the
process requirement during acceleration due to lag in the feedback
signal.
69
Page 70
Differentiator Gain Limit
The differentiation control reacts to the rate of change of the error
between the setpoint and the feedback signal. This is seldom needed
for HVAC applications. If the differentiation function becomes too
dominant, the differentiation factor can be limited. This is done in
parameter 426, PID Differentiator Gain Limit.
Lowpass Filter
Noise on the feedback signal can be reduced by using the built-in
lowpass filter. Set a suitable lowpass filter time constant. This time
constant determines the cutoff frequency of the filter.
If the lowpass filter has been set to 0.1s, the cut-off frequency will be 10
RAD/sec., corresponding to (10/2 x π) = 1.6 Hz. This means that any
noise on the feedback signal whose frequency is greater than 1.6 Hz
will be filtered out. Choose a suitable time constant in parameter 427,
PID Lowpass Filter Time.
Optimization of the Process Regulator
The basic settings have now been made; all that remains to be done is
to optimize the proportional gain, the integration time and, if needed, the
differentiation time. These are set by parameters 423, 424 and 425. In
most processes, this can be done by following the guidelines below.
PID Overview
The block diagram below shows reference and setpoint in relation to
the feedback signal.
As can be seen, the remote reference is added to Setpoint 1 or
Setpoint 2. The setpoint that is active depends on the value of
parameter 417, Feedback Function.
1.Start the motor.
2.Set parameter 423, PID Proportional Gain, to 0.3 and increase it
until the feedback signal becomes unstable. Then reduce the
value until the feedback signal has stabilized. Now lower the
proportional gain by about half (40% to 60%).
3.Set parameter 424, PID Integration Time, to 20 seconds and
reduce the value until the feedback signal becomes unstable.
Increase the integration time until the feedback signal stabilizes.
Now increase the integration time from 15% to 50%.
4.Parameter 425, PID Differentiation Time, is only used in very
fast-acting systems and should be left off for most HVAC applications. When it is used, the typical value is 1/4th the value set in
parameter 424, PID Integration Time. The differentiator should
only be used when the setting of the proportional gain and the
integration time have been fully optimized.
Starting and stopping the drive will produce the necessary error signal
in the process to set the PID.
Feedback Handling
Handling of the feedback signal(s) can be seen from the block diagram
on the next page. The block diagram shows how and by which
parameters the feedback handling is affected.
Feedback signals can be voltage, current, pulse and bus feedback
signals. In two zone feedback systems, both feedback signals must be
voltage signals (terminals 53 and 54). Please note that Feedback 1
consists of bus feedback 1, (parameter 537) added to the feedback
signal value of terminal 53. Feedback 2 consists of bus feedback 2,
(parameter 538) added to the feedback signal value of terminal 54.
In addition, the drive has an internal calculator capable of converting a
pressure signal into a linear flow feedback signal. This function is
activated in parameter 416, Feedback Conversion.
The parameters for feedback handling are active both in closed and
open loop modes. In open loop, the feedback signal can be displayed
on one of the drives meters and the drive can produce warnings if the
feedback signal is beyond the range set in parameters 227, Warning:Low Feedback and 228, Warning: High Feedback.
70
Page 71
Feedback Handling (continued)
During closed loop operation, there are three ways to use the PID
controller and setpoint and feedback signals:
1 setpoint and 1 feedback
1 setpoint and 2 feedbacks
2 setpoints and 2 feedbacks
1 Setpoint and 2 Feedbacks
Depending on the feedback function selected in parameter 417,
Feedback Function, the two feedback signals will be compared to the
setpoint. A description of the individual feedback functions is given in
parameter 417. As above, parameter 418, Setpoint 1, will be added to
the remote reference, if a remote reference is used.
1 Setpoint and 1 Feedback
In HVAC applications it is often possible to place a pressure or
temperature sensor at the farthest significant load and measure actual
pressure or temperature in the system. In these cases, the drive's PID
controller can respond to system changes, as programmed. When only
one setpoint and one feedback signal are used, the drive responds to
the feedback signal to match the programmed setpoint in parameter
418, Setpoint 1. (If a remote reference is used, it will be added to the
setpoint.)
2 Setpoints and 2 Feedbacks
Whenever two critical zones do not have the same setpoint value, two
feedback with two setpoint control is required. Many pumping systems
require the monitoring and control of two loads that differ in size and
pressure drop. Or this can be effective when controlling different
temperature zones in cooling or heating applications. Parameter 418,
Setpoint 1, is the setpoint for zone 1. Feedback for zone 1 is the
feedback signal at terminal 53. Parameter 419, Setpoint 2, is the
setpoint for zone 2 and terminal 54 for feedback 2. Bus Feedback 1
and 2 (parameters 535 and 536) are added to their respective
feedback signals, when serial bus data is added to the zone control.
Parameter 417, Feedback Function, selects whether the drive will
attempt to have both feedback signals meet the minimum (2 zone min.)
or maximum (2 zone max.) to their respective setpoints.
71
Page 72
416Feedback Conversion
(FEEDBACK CONV.)
Value:
★ Linear (LINEAR)[0]
Square root (SQUARE ROOT)[1]
Function:
In this parameter, a function is selected which converts a feedback
signal from the process to a feedback value that equals the square root
of the connected signal.
Function:
This parameter determines the calculation method for two feedback
signals. Terminals 53 and 54 are both read in selections [0] through
[6]. In each case, if only one feedback signal is received, a zero value
will be calculated for the inactive terminal. To read feedback from only
one of the two terminals, use Feedback 1 Only (terminal 53) or
Feedback 2 Only (terminal 54) to exclude the inactive terminal.
Feedback 1 = Sum of parameter 535, Bus Feedback 1, (if present) and
the feedback signal value of terminal 53.
This can be used where regulation of a flow is required and the
feedback is from a pressure sensor (flow is proportional to the square
root of pressure). This conversion makes it possible to set the
reference in such a way that there is a linear connection between the
reference and the flow required. See diagram below.
Feedback conversion should not be used if two-zone regulation has
been selected in parameter 417, Feedback Function.
Description:
If Linear is selected, the feedback signal and the feedback value will be
proportional.
If Square root is selected, the drive first takes the square root of the
feedback signal.
TR1 drive
Feedback 2 = Sum of parameter 536, Bus Feedback 2, (if present) and
the feedback signal value of terminal 54.
Description of choice:
If Minimum is selected, the drive will compare Feedback 1 wi th
Feedback 2 and regulate on the basis of the lower feedback value.
If Maximum is selected, the drive will compare Feedback 1 with
Feedback 2 and regulate on the basis of the higher feedback value.
If Sum is selected, the drive will total Feedback 1 wit h Feedback 2.
If Difference is selected, the drive will subtract Feedback 1 from
Feedback 2.
If Average is selected, the drive will calculate the average of Feedback1 and Feedback 2.
If 2-zone Minimum is selected, the drive will calculate the difference
between Setpoint 1 and Feedback 1 as well as Setpoint 2 andFeedback 2. The drive will regulate its output speed based on the
larger difference. A positive difference, (a setpoint higher than the
feedback), is always larger than a negative difference.
If 2-zone Maximum is selected, the drive will calculate the difference
between Setpoint 1 and Feedback 1 as well as Setpoint 2 andFeedback 2. After the calculation, the drive will use the smaller
difference. A negative difference (a setpoint lower than the feedback) is
always smaller than a positive difference.
417Feedback Function
(2 FEEDBACK, CALC.)
Value:
Minimum (MINIMUM)[0]
★ Maximum (MAXIMUM)[1]
Sum (SUM)[2]
Difference (DIFFERENCE)[3]
Average (AVERAGE)[4]
Two-zone minimum (2 ZONE MIN)[5]
Two-zone maximum (2 ZONE MAX)[6]
Feedback 1 only (FEEDBACK 1 ONLY)[7]
Feedback 2 only (FEEDBACK 2 ONLY)[8]
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
72
If Feedback 1 Only is selected, terminal 53 is read as the feedback
signal and terminal 54 ignored. Feedback 1 is compared to Setpoint 1
for drive control.
If Feedback 2 Only is selected, terminal 54 is read as the feedback
signal and terminal 53 ignored. Feedback 2 is compared to Setpoint 2
for drive control.
NOTE
Value of parameter 418, Setpoint 1, is added to
any remote reference when Minimum,Maximum, Sum, Difference or Average is
selected.
Page 73
418Setpoint 1
(SETPOINT 1)
Value:
Feedback Minimum to Feedback Maximum★ 0.000
Function:
Setpoint 1 is used to provide the setpoint reference for PID control with
one feedback signal. It is also used for the setpoint for zone one in
two-setpoint PID control. External and preset references may be added
to its value.
In open loop, Setpoint 1 should be set to 0 to prevent parameter 417,
Feedback Function, from affecting the reference.
See description of parameter 417, Feedback Function.
Description of choice:
Set the desired value within the programmed minimum and maximum.
The process unit is selected in parameter 415, Process Units.
419Setpoint 2
(SETPOINT 2)
Value:
Feedback minimum to Feedback maximum★ 0.000
421PID Anti-windup
(PID ANTI WINDUP)
Value:
Off (DISABLE)[0]
★ On (ENABLE)[1]
Function:
It is possible to choose whether the PID controller integrator is to
continue to sum the error signal when it is not possible to increase or
decrease the output frequency to correct the error.
Used in Closed Loop, parameter 100.
Description of choice:
The factory setting is On, which means that the error integrator is
cleared if either the current limit, the voltage limit or the maximum or
minimum frequency has been reached. The integrator will not function
again until regulation is possible. Select Off if the integrator is to
continue integrating even if it is not possible to correct the error.
422PID Start-up Frequency
(PID START VALUE)
Value:
Minimum frequency to maximum frequency
(set by parameters 201 and 202)★ 0 Hz
Function:
Setpoint 2 is used to provide the setpoint reference for zone two in
two-zone PID. In open loop, Setpoint 2 should be set to 0, to prevent
parameter 417, Feedback Function, from affecting the reference.
See description of parameter 417.
Description of choice:
Set the required value. The process unit is selected in parameter 415,
Process Units.
420PID Normal/Inverse Control
(PID NOR/INV. CTRL)
Value:
★ Normal (NORMAL)[0]
Inverse (INVERSE)[1]
Function:
This determines how the drives PID controller responds to an error
between the setpoint and feedback.
Used in Closed Loop, (parameter 100).
Description of choice:
Select normal when the drive is to reduce the output frequency as the
feedback signal increases.
Function:
Each time the drive is given a start command, the start-up frequency is
the speed the drive accelerates to before PID control is activated. The
drive will follow the acceleration ramp when a start signal is received as
if in open loop. When the programmed start-up frequency is reached, it
will change to closed loop operation.
Used in Closed Loop, parameter 100.
Description of choice:
Set the required start frequency. For software versions prior to 2.0, do
not set this frequency between 0.1 and 7.7 Hz.
NOTE
If drive is running in current limit before desired
start frequency is obtained, PID control will not
be activated. To avoid this, start frequency must
be low enough to ensure drive does not go into
current limit. This can be done during operation.
Select inverse when the drive is to increase the output frequency as the
feedback signal increases.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
73
Page 74
423PID Proportional Gain
(PID PROP. GAIN)
Value:
0.00 to 10.00★ 0.30
426PID Differentiator Gain Limit
(PID DIFF. GAIN)
Value:
5.0 to 50.0★ 5.0
Function:
The proportional gain determines how fast the system responds to a
change in feedback.
Used in Closed Loop, parameter 100.
Description of choice:
Quick regulation is obtained by a high gain, but, if the gain is too high,
the process may become unstable. See Optimization of the Process
Regulator for information on proper adjustment.
424PID Integral Time
(PID INTEGR.TIME)
Value:
0.01 to 9999.00 sec. (OFF)★ OFF
Function:
The integrator adds the error signal over time and uses this to correct
the speed of the drive.
The integral time is the time needed by the integrator to have the same
effect as the proportional gain.
Used in Closed Loop parameter 100.
Description of choice:
Fast regulation is obtained by setting a short integration time. However,
if this time is too short, the process will overcorrect and become
unstable. See Optimization of the Process Regulator for information on
proper adjustment.
425PID Differentiation Time
(PID DIFF. TIME)
Value:
0.00 (OFF) to 10.00 sec.★ OFF
Function:
When the differentiator is used, fast changes in the error can sometimes
cause unstable operation. In these cases it may be useful to limit the
contribution of the differentiator.
Used in Closed Loop, parameter 100.
Description of choice:
A lower limit will improve stability, but will reduce the effect of the
differential.
427PID Lowpass Filter Time
(PID FILTER TIME)
Value:
0.01 to 10.00★ 0.01
Function:
Noise on the feedback signal can be reduced by the lowpass filter.
Used in Closed Loop, parameter 100.
Description of choice:
Select the desired time constant (t).
The cut off frequency equals ½πt. For example, if a time constant of 0.1
s is programmed, the cut off frequency for the lowpass filter will be
1/[2π (.1)] = 1.6 Hz.
The PID controller will then
only respond to changes in
the feedback signal whose
frequency is less than 1.6
Hz.
Function:
The differentiator responds to the rate of change of the error signal.
The quicker the error changes, the greater the response from the
differentiator.
Used in Closed Loop, parameter 100.
Description of choice:
Fast regulation can be obtained by means of a long differentiation time.
If this time is too long, the process may overshoot. The differentiator is
generally set of OFF in HVAC applications. See Optimization of the
Process Regulator for information on proper adjustment.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
74
Page 75
Serial Communication
Parameters 500 through 571
This parameter group sets up the drive for serial communication.
There is a choice of four protocols: FC (firmware protocol), Johnson
Controls Metasys N2, Siemens FLN, and Modbus RTU. In order to
use serial communication to control the drive, address and baud rate
must always be set. In addition to controlling the drive, operational data
from the drive including reference, feedback, motor temperature and
others can be read through serial communication.
There is a choice of four different serial communication protocols.
Description of choice:
The transmission speed of the drive must be set at a value that
corresponds to the transmission speed of the master. Parameter 502,
Baud Rate, cannot be selected through serial communication; it must be
set by the keypad. The data transmission time itself, which is determined
by the baud rate selected, is only part of the total communication time.
503Coasting Stop
(COASTING)
Value:
Digital input (DIGITAL INPUT)[0]
Serial communication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
★ Logic or (LOGIC OR)[3]
Function:
In parameters 503 through 508, a choice can be made to control the
drive via the digital inputs and/or by serial communication.
If Digital input is selected, the command can only be carried out
through digital input.
Description of choice:
Select the required control word protocol.
501Address
(ADDRESS)
Value:
Parameter 500 Protocol = FC protocol
0 through 126★1
Parameter 500 Protocol = Metasys N2
1 through 255 1
Parameter 500 Protocol = FLN
0 through 98 1
Parameter 500 Protocol = Modbus RTU
0 through 247 1
Function:
In this parameter it is possible to allocate an address in a serial
communication network to each drive.
Description of choice:
The individual drive must be given a unique address. If the number of
drives exceeds 31, a repeater must be used. Parameter 501, Address,
cannot be chosen via serial communication but is set via the keypad.
In this parameter, the speed at which data is transmitted via serial
communication is programmed. Baud rate is defined as the number of
bits transmitted per second.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
If Serial communication is selected, the command can only be carried
out through serial communication.
If Logic and is selected, the command must be by both serial communi-
cation and a digital input.
If Logic or is selected, the command can be made by either digital or
serial communication.
Description of choice:
The tables below show whether the motor is running or coasting when
Digital Input, Serial Communication, Logic and or Logic or has been
selected.
NOTE
Terminal 27 and bit 03 of control word are active
when logic 0 is selected.
Digital InputSerial Communication
SerialSerial
Term. 27 Comm.F un ct ionTerm. 27 Comm.F unction
00Coasting00Coasting
01Coasting01Motor run
10Motor run10Coasting
11Motor run11Motor run
Logic andLogic or
SerialSerial
Term. 27 Comm.Fu nc tionTerm. 27 Comm.F unction
00Coasting00Coasting
01Motor run01Coasting
10Motor run10Coasting
11Motor run11Motor run
75
Page 76
504DC Brake
(DC BRAKE)
Value:
Digital input (DIGITAL INPUT)[0]
Serial communication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
★ Logic or (LOGIC OR)[3]
505Start
(START)
Value:
Digital input (DIGITAL INPUT)[0]
Serial communication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
★ Logic or (LOGIC OR)[3]
Function:
See the functional description under parameter 503, Coasting Stop.
Description of choice:
The table below shows when the motor is running and is DC-braking
when Digital input, Serial communication, Logic and or Logic or has
been selected.
NOTE
DC braking inverse, through terminals 19 and
27, and bit 03 of the control word, is active when
logic 0 is selected.
See the functional description under parameter 503, Coasting Stop.
Description of choice:
The table below shows when the motor has stopped and gives the
situations in which the drive has a start command when Digital input,
Serial communication, Logic and or Logic or has been selected.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
76
Page 77
506Reversing
(REVERSING)
Value:
★ Digital input (DIGITAL INPUT)[0]
Serial communication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
Logic or (LOGIC OR)[3]
Function:
See the functional description under parameter, 503 Coasting Stop.
Description of choice:
The table below shows when the motor is running forward and reverse
when Digital input, Serial communication, Logic and o r Logic or has
been selected.
Digital input (DIGITAL INPUT)[0]
Serial communication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
★ Logic or (LOGIC OR)[3]
Function:
See the functional description for parameters 507 and 508 under
parameter 503, Coasting Stop.
Description of choice:
The table below shows the Setup (parameter 002 Active Setup) that
has been selected via Digital input, Serial communication, Logic and orLogic or. The table also shows the preset reference (parameters 211
through 214, Preset reference) that has been selected via Digital
input, Serial communication, Logic and or Logic or.
509Reference %(REFERENCE %)%80 msec.
510Reference [unit](REFERENCE [UNIT])Hz, rpm80 msec.
511Feedback [unit](FEEDBACK)Par. 41580 msec.
512Frequency [Hz](FREQUENCY)Hz80 msec.
513User-defined readout(CUSTOM READOUT)Hz x scaling80 msec.
514Motor current [A](CURRENT)Amp80 msec.
515Power [kW](POWER KW)kW80 msec.
516Power [hp](POWER HP)HP80 msec.
517Motor voltage [V](MOTOR VOLT)VAC80 msec.
518DC link voltage [V](DC LINK VOLTAGE)VDC80 msec.
519Thermal load, motor [%](MOTOR TEMPERATURE)%80 msec.
520Thermal load, TR1 [%](TR1 TEMPERATURE)%80 msec.
521Digital input(DIGITAL INPUT)Binary80 msec.
522Terminal 53, analog input [V](TERMINAL 53, ANALOG INPUT)Volt20 msec.
523Terminal 54, analog input [V](TERMINAL 54, ANALOG INPUT)Volt20 msec.
524Terminal 60, analog input [mA](TERMINAL 60, ANALOG INPUT)mA20 msec.
525Pulse reference [Hz](PULSE REFERENCE)Hz20 msec.
526External reference [%](EXTERNAL REFERENCE)%20 msec.
527Status word(STATUS WORD HEX)Hex20 msec.
528Heat sink temperature [°C](HEAT SINK TEMP.)°C1.2 sec.
529Alarm word(ALARM WORD, HEX)Hex20 msec.
530Control word(TR1 CONTROL WORD, HEX)Hex2 msec.
531Warning word(WARNING WORD)Hex20 msec.
532Extended status word(STATUS WORD)Hex20 msec.
*************************
537Relay status(RELAY STATUS)Binary20 msec.
Updating
78
Page 79
Function:
These parameters are read-only through the serial communication
port. To display drive functions on the drive display, see parameters
007 through 010, Display Readout.
Description of choice:
Reference [%], parameter 509 gives a percentage for the resulting
reference in the range from Minimum Reference to Maximum
Reference. See also Reference Handling.
Terminal 60, Analog Input [mA], parameter 524, gives the current
value of the signal on terminal 60.
Pulse Reference [Hz], parameter 525, gives a pulse frequency in Hz
connected to one of the terminals 17 and 29.
External Reference [%], parameter 526, gives the sum of external
references as a percentage (sum of analog/pulse/serial communication)
in the range from minimum reference to maximum reference.
Reference [unit], parameter 510 gives the resulting reference by
means of the unit Hz in Open Loop, parameter 100. In Closed Loop,
the reference unit is selected in parameter 415, Units with Closed Loop.
Feedback [unit], parameter 511, gives the resulting feedback value by
means of the unit/scaling selected in parameters 413, 414 and 415.
See also Feedback Handling.
Frequency [Hz], parameter 512, gives the output frequency of the
drive.
User Defined Read Out, parameter 513, gives a user defined value
calculated on the basis of the present output frequency and unit, as well
as the scaling in selected in parameter 005, Maximum Value of User
Defined Read Out. The unit is selected in parameter 006, Unit for
User Defined Read Out.
Motor Current [A], parameter 514, gives the motor current in A.
Power [kW], parameter 515, gives the present power provided to the
motor in kW.
Power [HP], parameter 516, gives the present power provided to the
motor in HP.
Motor Voltage [V], parameter 517, gives the voltage fed to the motor.
DC Link Voltage [V], parameter 518, gives the intermediate circuit
voltage of the drive.
Thermal Load, Motor [%], parameter 519, gives the calculated/
estimated thermal load on the motor. 100% is the trip point. See also
parameter 117, Motor Thermal Protection.
Thermal Protection, TR1 [%], parameter 520, gives the calculated/
estimated thermal load on the drive. 100% is the trip point.
Digital Input, parameter 521, gives the signal status of the 8 inputs (16,
17, 18, 19, 27, 29, 32 and 33). Input 16 corresponds to the bit to the
extreme left. 0 = no signal, 1 = signal connected.
Terminal 53, Analog Input [V], parameter 522, gives the voltage value
of the signal on terminal 53.
Terminal 54, Analog Input [V], parameter 523, gives the voltage value
of the signal on terminal 54.
Status Word, parameter 527, gives the present status word of the drive
in hex.
Heat Sink Temperature [°C], parameter 528, gives the present heat
sink temperature of the drive.
Alarm Word, parameter 529, gives a hex code for the alarm on the
drive.
Control Word, parameter 530, gives the present control word of the
drive in hex.
Warning Word, parameter 531, indicates in hex warnings from the
drive.
Extended Status Word, parameter 532, indicates in hex code whether
there is a warning from the drive.
Relay Status, parameter 537, indicates in binary code the status of
relays 1 through 6.
533Display Text Line 1
(DISPL. TEXT LINE 1)
Value:
Max. 20 characters★ OFF
Function:
Text up to 20 characters may be displayed on line 1 (top line) of the
LCP display. Parameter 007, Large Readout, must be set for FreeProgram Array. Line 1 custom text is only visible in auto mode.
Description of choice:
See Programming Custom Display Text.
534Display Text Line 2
(DISPL. TEXT LINE 2)
Value:
Max. 8 characters★ OFF
Function:
Text up to 8 characters may be displayed on line 2 (large text display)
of the LCP display. Parameter 007, Large Readout, must be set forFree Program Array. Line 2 custom text is visible in display modes I
and II (see Display Modes).
Description of choice:
See Programming Custom Display Text.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
79
Page 80
Programming Custom Display Text
Enter custom text in lines 1 (top line) or 2 (large display) of the LCP
keypad display in accordance with the following procedure.
1. Select parameter 533, Display Text Line 1 or 534, Display
Text Line 2.
2. Press CHANGE DATA key on keypad.
3. Use left or right arrows on keypad to position cursor.
4. Use [+] or [-] arrows to scroll through character options.
5. Press [OK] key to accept changes or [CANCEL] key to
cancel.
6. Select Free Program Array in parameter 007, Large read-
out, to activate custom text readout.
537Relay Status
(RELAY STATUS)
Value:
binary (0 = open, 1 = closed)★ 0
Description of choice:
See Data Read-out for parameters 509 through 532, 537 on previous
page for relay status description.
NOTE
Parameters 555, Bus Time Interval, and 556, Bus
Time Interval Function, are only active when
FC Protocol has been selected in parameter500, Protocol.
NORTH OFFICE BLDG
SETUP
Pump 6
1
AUTO REMOTE RUN
The available characters are:
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Æ Ø Å Ä Ö Ü
É Ì Ù è . / - ( ) 0 1 2 3 4 5 6 7 8 9 space
To erase a character that has been entered, replace it with space.
535Bus Feedback 1
(BUS FEEDBACK1)
Value:
0 through 16384 decimal (0 through 4000 Hex)★ 0
Function:
Via the serial communication port, this parameter allows writing of a bus
feedback value which will then form part of the feedback handling. BusFeedback 1 will be added to any feedback value registered on terminal
53.
Description of choice:
Write the required bus feedback value via serial communication.
555Bus Time Interval
(BUS TIME INTERVAL)
Value:
1 to 99 sec.★ 60 sec.
Function:
In this parameter, the maximum time allowed between the receipt of two
packets in a row is set. If this time is exceeded, the serial communication
is assumed to have stopped and the choice made in parameter 556,
Bus Time Interval Function, will be carried out.
Description of choice:
Set the required time.
556Bus Time Interval Function
(BUS TIME INTERVAL FUNCTION)
Value:
★ Off (NO FUNCTION)[0]
Freeze output (FREEZE OUTPUT)[1]
Stop (STOP)[2]
Jogging (JOG FREQUENCY)[3]
Max. output frequency (MAX FREQUENCY)[4]
Stop and trip (STOP AND TRIP)[5]
Function:
In this parameter, the required reaction from the drive is selected when
the time set in parameter 555, Bus Time Interval, has been exceeded.
536Bus Feedback 2
(BUS FEEDBACK 2)
Value:
0 through 16384 decimal (0 through 4000 Hex)★ 0
Function:
Via serial communication, a bus feedback value can be written in this
parameter that will become part of the feedback handling system. BusFeedback 2 will be added to any feedback value on terminal 54.
Description of choice:
Write the required bus feedback value via the serial communication.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
80
Description of choice:
The output frequency of the drive can be frozen at the present value,
frozen as selected in parameter 211, Preset Reference 1, frozen as
selected in parameter 202, Maximum Output Frequency, or stop and
show a fault.
Page 81
560N2 override release time
(N2 OVER.REL.TIME)
Value:
1 - 65533 sec.★ OFF
Function
The maximum time is set between the receipt of two N2 messages. If the
time is exceeded, serial communication is assumed stopped. All N2
points which are overridden will be released in the following order:
1. Analog outputs
2. Binary outputs
3. Internal floating points
4. Internal integer points
5. Internal byte points
N2 point addresses are released in numerical order beginning with 1
(or 0).
Description of choice:
Set the required time.
565FLN bus time interval
(FLN TIME INTER.)
Value:
1 - 65534 sec.★ 60 sec.
Function
The maximum time is set between the receipt of two FLN messages. If
the time is exceeded, serial communication is assumed stopped and
the required reaction is set in parameter 566, FLN Bus Time Interval
Function.
Description of choice:
Set the required time.
566FLN bus time interval function
(FLN TIME FUNCT.)
Value:
★ Off (NO FUNCTION)[0]
Freeze output (FREEZE OUTPUT)[1]
Stop (STOP)[2]
Jogging (JOG FREQUENCY)[3]
Max. output frequency (MAX.SPEED)[4]
Stop and trip (STOP AND TRIP)[5]
Function
The required reaction from the variable frequency drive is selected
when the time set in parameter 565, FLN Bus Time Interval, has been
exceeded.
This parameter sets the drive Modbus RTU interface to communicate
properly with a master controller. The parity (even, odd, or no parity)
must be set to match the setting of the master controller. Even and odd
parity is sometimes used to allow error checking of a transmitted word.
Description of choice
Because Modbus RTU uses the more efficient CRC (cyclic redundancy
check) method for checking for errors, parity checking is seldom used
in Modbus RTU networks. Set the drive parity to match the master
controller, if appropriate.
571Modbus communication timeout
(M.BUS COM.TIME.)
Value:
10 ms to 2000 ms★ 100 ms
Function
This parameter determines the maximum time that the drive will wait
between characters sent by the Modbus RTU master controller. When
the time expires, the drive assumes it has received the entire message.
Description of choice
Generally, the value of 100 ms is sufficient for Modbus RTU networks,
although some Modbus RTU networks may operate with a timeout
value as short as 35 ms. If the value is set too short, the drive may miss
part of the message. Since the CRC check will be invalid, the drive will
ignore the message. The resulting retransmission of messages will slow
network communications. A value set too long will cause the drive to
wait longer than necessary to determine that the message is complete.
This delays response time and could cause the master controller to
timeout or slow the network.
Description of choice:
The output frequency of the variable frequency drive can be frozen at
the present value at any given time, frozen at parameter 211, PresetReference 1, frozen at parameter 202, Max. Output Frequency, or
stop output and show a fault.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
81
Page 82
Warning Words, Extended Status Word and
Alarm Word
Warning Word, Extended Status Word and Alarm Word are shown in
hex format on the display. If there is more than one warning or alarm,
the sum of the warnings or alarms will be shown.
The descriptions of the Extended Status Words, Warning Words and
Alarm Words can be read out via the serial bus in parameter 531,
Warning Word; 532, Extended Status Word; and 529, Alarm Word.
BitAlarm Word (Parameter 529)
00Unknown fault
01Trip locked
02AMA fault
03HPFB fault
04RS-485 timeout
05Short circuit
06SMPS fault
07Ground fault
08Overcurrent
09Current limit
10Motor thermistor
11Motor thermal
12Inverter thermal
13Undervoltage
14Overvoltage
15Input phase loss
16Live zero fault
17Heat sink overtemperature
18Motor phase W missing
19Motor phase V missing
20Motor phase U missing
21Profibus communication fault
22Inverter fault
23Output current low
24External fault
25Reserved
26Reserved
27Reserved
28Reserved
BitWarning Word (Parameter 531)
00Reference high
01Control card fault
02Power card fault
03HPFB bus timeout
04RS-485 timeout
05Overcurrent
06Current limit
07Motor thermistor
08Motor overtemperature
09Inverter overtemperature
10Undervoltage
11Overvoltage
12Voltage warning low
13Voltage warning high
14Input phase fault
15Live zero fault
16Under 10 Volt (terminal 50)
17Reference low
18Feedback high
19Feedback low
20Output current high
21Out of frequency range66666
22Profibus communication fault
23Output current low
24Output frequency high
25Output frequency low
26AMA - motor too small
27AMA - motor too big
28AMA - check par. 102, 103, or 105
29AMA - check par. 102, 104, or 106
30Reserved
31Reserved
BitExtended Status Word (Paramater 532)
00Autoramping
01Start delay
02Sleep boost active
03Sleep mode active
04Automatic motor adaptation completed
05Automatic motor adaptation running
06Reverse start (not for TR1)
07Normal ramping
08Reversing
09At reference
10Running
11Local reference = 0, Remote = 1
12OFF = 1
13Hand = 1, Auto = 0
14Run request
15No run permission
16Freeze output frequency
17Freeze output blocked
18Jogging
19No jog permission
20Stand by
21Stopped
22DC braking stop
23Drive ready
24Relay 123 active (Profibus only)
25Drive ready
26Control ready
27Start prevented
28Profibus OFF3 active
29Reserved
82
Page 83
Serial Communication for FC Protocol
ADDRESS 1
MASTER
ADDRESS 2
Protocols
All TR1 drives have an RS-485 (EIA-485) port which allows controlling the drive by one of four different serial communication protocols.
The protocols, which can be selected in parameter 500, Protocol, are:
●Johnson Controls Metasys N2
●Siemens FLN
●Modbus RTU
●FC protocol
Metasys N2 is a registered trademark of Johnson Controls.
FLN is a registered trademark of Siemens.
®
®
ADDRESS 31
REPEATER
ADDRESS 126
Packet Communication
Control and Reply Packets
The packet communication in a master/slave system is controlled by the
master. The drives are the slaves. A maximum of 31 TR1 drives can be
connected to one master unless a repeater is used. If a repeater is
used, a maximum of 126 drives can be connected to one master.
The master continuously sends packets addressed to the slaves and
awaits reply packets from them. The response time of the slaves is a
maximum of 50 ms.
If FC protocol is to be selected, set parameter 500, Protocol to FCprotocol .
For further information on operating the drive through N2, FLN, or
Modbus RTU communication, request the related operators manual
from Trane.
Only a slave that has received a faultless packet addressed to that
slave will respond by sending a reply packet.
Broadcast
When a master sends a packet to all slaves connected to the bus at the
same time, it is called a broadcast. In broadcast communication, if the
packet has been correctly received, the slaves do not send reply
packets to the master.
83
Page 84
Conversion
The different attributes for each parameter can be seen in the section
on factory settings.
Since a parameter value can only be transferred as a whole number,
a conversion factor must be used to transfer decimals.
Example:
Parameter 201: Minimum Frequency, conversion factor 0.1. If
parameter 201 is to be set to 10 Hz, a value of 100 must be transferred, since a conversion factor of 0.1 means that the transferred
value will be multiplied by 0.1. A value of 100 will, therefore, be
understood as 10.0.
IndexFactor
743.6
2100
110
01
-10.1
-20.01
-30.001
-40.0001
Conversion Table
Data Type
Data type shows the type and length of the packet.
The data types shown in the table are supported by the drive.
Unsigned means there is no sign included in the packet.
Control Word
The control word is used for transmitting commands from a master
(PC) to a slave (drive).
Master➝Slave
Control
word
1514131211109876543210Bit no.
BitBit = 0Bit =1
00Preset ref. lsb
01Preset ref. msb
02DC braking
03Coasting stop
04Quick stop
05Freeze output frequency
06Ramp stopStart
07Reset
08Jog
09No functionNo function
10Data not validData valid
11Activate relay 1
12Activate relay 2
13Choice of setup lsb
14Choice of setup msb
15Reversing
Bits 00 and 01 are used for choosing between the four pre-programmed references parameters 211 through 214, Preset Reference,
as shown in the table below.
Preset ReferenceParameterBit 01Bit 00
121100
221201
321310
421411
NOTE
Parameter 508, Choice of Preset Reference, is
used to choose how bits 00/01 are to be gated
with the corresponding functions of the digital
inputs.
Bit 02, DC BRAKE:
Bit 02 = 0 enables DC braking. Set braking current and duration in
parameter 114, DC Braking Current, and in parameter 115, DCBraking Time.
NOTE
Parameter 504, DC Brake, is used for selecting
how bit 02 is to be gated with the corresponding function of terminal 27.
84
Page 85
Bit 03, Coasting Stop:
Bit 03 = 0 means that the drive will coast to a stop.
Bit 03 = 1 means that the drive is able to start the motor, provided the
other conditions for starting are fulfilled.
NOTE
In parameter 503, Coasting Stop, the choice is
made of how bit 03 is to be gated with the corresponding function of terminal 27.
Bit 04, Quick Stop:
Bit 04 = 0 leads to a stop in which the motor speed is ramped down to a
stop as set in parameter 207, Ramp Down Time.
Bit 10, Data Not Valid/Data Valid:
Used for telling the drive whether the control is to be used or ignored.
Bit 10 = 0 means that the control word is ignored.
Bit 10 = 1 means that the control word is used. This function is relevant
because the control word is always contained in the packet, regardless
of the type of packet used. Therefore it is possible to disconnect the
control word if it is not to be used in connection with updating or reading
of parameters.
Bit 11, Relay 1:
Bit 11 = 0 Relay 1 is not activated.
Bit 11 = 1 Relay 1 is activated, provided Control Word Bits 11/12 has
been selected in parameter 323, Relay Outputs.
Bit 05, Freeze Output Frequency:
Bit 05 = 0 means that the given output frequency is frozen. The frozen
output frequency can now only be changed with the digital inputs
programmed for Speed Up and Speed Down.
NOTE
If Freeze Output is active, drive cannot be
stopped via Bit 06, Start, or through terminal
18. Drive can only be stopped in following ways:
●Bit 03, Coasting Stop
●Terminal 27
●Bit 02, DC Braking
●Terminal 19 programmed for DC Braking
Bit 06, Ramp Stop/Start:
Bit 06 = 0 leads to a stop in which the motor speed is ramped down to
stop through parameter 207, Ramp Down Time.
Bit 06 = 1 means that the drive is able to start the motor, provided the
other conditions for starting are fulfilled.
NOTE
Parameter 505, Start, determines how bit 06,
Ramp Stop/Start, is gated and corresponding
function of terminal 18.
Bit 07, Reset:
Bit 07 = 0 leads to no reset.
Bit 07 = 1 means that a trip is reset.
Reset is activated on the leading edge of the signal, at the time the
signal changes from logic 0 to logic 1.
Bit 08, Jog:
Bit 08 = 1 means that the output frequency is determined by parameter
209, Jog Frequency.
Bit 09, No function:
Bit 09 has no function.
Bit 12, Relay 2:
Bit 12 = 0 Relay 2 is not activated.
Bit 12 = 1 Relay 2 is activated, provided Control Word Bits 11/12 has
been selected in parameter 326, Relay Outputs.
NOTE
If time-out period set in parameter 556, Bus TimeInterval Function, is exceeded, relays 1 and 2
will have voltage removed if activated via serial
communication.
Bits 13/14, Choice of Setup:
Bits 13 and 14 are used to choose among the four menu setups in
accordance with the following table:
Setup Bit 14 Bit 13
100
201
310
411
This function is only possible if Multi-setup has been selected in
parameter 004.
NOTE
In parameter 507, Choice of Setup, a choice is
made of how bits 13/14 are gated with corresponding function of digital inputs.
Bit 15, No function/reversing:
Bit 15 = 0 leads to no reversing
Bit 15 = 1 leads to reversing
In the factory setting, reversing has been selected as digital in
parameter 506, Reversing. Bit 15 will only allow reversing, if bus orlogic or has been selected, or logic and has been selected and a
signal is present at terminal 19.
85
Page 86
Status Word per FC Protocol
The status word is used to inform the master (e.g., a PC) of the
condition of the slave (drive).
Slave➝Master
Status
word
1514131211109876543210Bit no.
BitBit = 0Bit =1
00TripControl ready
01Drive ready
02Stand by
03No tripTrip
04Not in use
05Not in use
06Not in use
07No warningWarning
08Speed referenceSpeed = reference
09Local operationSerial comm. control
10Out of frequency range
11Running
12No functionNo function
13Voltage warning
14Current limit
15Thermal warning
Bit 00, Control Ready:
Bit 00 = 1 The drive is ready for operation.
Bit 00 = 0 The drive has tripped.
Bit 01, Drive Ready:
Bit 01 = 1 The drive is ready for operation, but terminal 27 is a
logic 0 and/or a coasting command has been received via serial
communication.
Bit 02, Standby:
Bit 02 = 1 The drive is able to start the motor when a start
command is given.
Bit 03, No Trip/Trip:
Bit 03 = 0 means that the drive is not in an error state.
Bit 03 = 1 means that the drive has tripped and needs a reset
signal in order for operation to be resumed.
Bit 04, Not in use:
Bit 04 is not used in the status word.
Bit 05, Not in use:
Bit 05 is not used in the status word.
Output
frequency
high/low
Bit 06, Not in use:
Bit 06 is not used in the status word.
Bit 07, No warning/warning:
Bit 07 = 0 means there is no warning.
Bit 07 = 1 means a warning has occurred.
Bit 08, Speed ¹ Reference/Speed = Reference:
Bit 08 = 0 means that the motor is running, but that the present speed is
different from the preset speed reference. This may be the case when
the speed is being ramped up or down after a start or stop command.
Bit 08 = 1 means that the present motor speed equals the preset speed
reference.
Bit 09, Local Operation/Serial Communication Control:
Bit 09 = 0 means that OFF/STOP has been activated on the control
unit, or that the drive is in Hand mode. It is not possible to control the
drive through serial communication.
Bit 09 = 1 means that it is possible to control the drive through serial
communication.
Bit 10, Out of Frequency Range:
Bit 10 = 0 if the output frequency is outside the range established by the
values in parameter 201, Output Frequency Low Limit, and parameter
202, Output Frequency High Limit.
Bit 10 = 1 means that the output frequency is within the limits of those
parameters.
Bit 11, Not Running/Running:
Bit 11 = 0 means that there is no output from the drive.
Bit 11 = 1 means that the drive has a start signal, or that the output
frequency is greater than 0 Hz.
Bit 12, No Function:
Bit 12 has no function.
Bit 13, Voltage Warning High/Low:
Bit 13 = 0 means that there is no voltage warning.
Bit 13 = 1 means that the DC voltage of the drive intermediate circuit is
too low or too high.
Bit 14, Current Limit:
Bit 14 = 0 means that the output current is less than or equal to the
value in parameter 215, Current Limit.
Bit 14 = 1 means that the output current is higher than the value in
parameter 215, Current Limit, and the drive will trip after the time set in
parameter 412, Trip Delay Overcurrent, has passed if the output
current is not reduced.
Bit 15, Thermal Warning:
Bit 15 = 0 means there is no thermal warning.
Bit 15 = 1 means that the temperature limit has been exceeded either in
the motor, in the drive or from a thermistor connected to an analog
input.
86
Page 87
Serial Communication Reference
Present Output Frequency
Master➝Slave
Control
word
Serial com.
ref.
1514131211109876543210Bit no.
The serial communication reference is transmitted to the drive in the
form of a 16-bit word. The value is transmitted as whole numbers
0 through ±32767 (±200 %).
16384 (4000 Hex) corresponds to 100 %.
The serial communication reference has the following format:
0 through 16384 (4000 Hex) - 0 through 100% (parameter 204,
Minimum Reference - Par. 205, Maximum Reference).
It is possible to change the direction of rotation through the serial
reference. This is done by converting the binary reference value to 2's
complement. See example in next column.
Slave➝Master
Status
word
Output
frequency
1514131211109876543210Bit no.
The value of the output frequency of the drive at any given time is
transmitted as a 16-bit word. The value is transmitted in the form of
whole numbers 0 through ±32767 (±200%).
16384 (4000 Hex) corresponds to 100%.
The output frequency has the following format:
0 through 16384 (4000 Hex) @ 0 to 100% (Parameter 201,
Output Frequency Low limit - Parameter 202, Output Frequency
High Limit).
Example - Status Word and Present Output Frequency:
The master receives a status message from the drive that the
presentoutput frequency is 50% of the output frequency range.
Example - Control word and serial communication reference:
The drive must receive a start command, and the reference is to be set
to 50% (2000 Hex) of the reference range.
Control word =047F Hex. Start command
Reference =2000 Hex. 50 % reference
047F H 2000 H
Control word
Reference
The drive is to receive a start command, and the reference is to be set
to -50% (-2000 Hex) of the reference range.
The reference value is first converted to the first complement; then 1
binary is added to get 2s complement:
Control word =047F Hex. Start command
Reference =E000 Hex. -50 % reference
Parameter 201, Output Frequency Low Limit = 0 Hz
Parameter 202, Output Frequency High Limit = 60 Hz
Status word = 0F03 Hex. Status message
Output frequency = 2000 Hex. 50% of the frequency range, corresponding to 30 Hz.
0F03 H 2000 H
Status word
Output
frequency
047F HE0000 H
Control word
Reference
87
Page 88
Service Functions
Parameters 600 through 631
This parameter group contains functions useful for troubleshooting the
drive including operating data, data log and fault log.
Parameter 602, kWh Counter
Shows the output power of the drive. The calculation is based on the
mean value in kWh over one hour. This value can be reset using
parameter 618, Reset of kWh Counter.
It also has information on the nameplate data of the drive.
Function:
These parameters can be read out through the serial communication
port as well as on the control panel display.
Description of choice:
Parameter 600, Operating Hours
Shows the number of hours the drive has had power applied. The
value is saved every hour and when the power is removed. This
value cannot be reset.
Parameter 601, Hours Run
Shows the number of hours the drive has powered the motor. This
parameter can be reset in parameter 619, Reset of Hours RunCounter. The value is saved every hour and when the power is
removed.
Parameter 603 Number of Power Ups.
Shows the number of times power has been applied to the drive.
Parameter 604, Number of Overtemperature Trips
Shows the number of overtemperature trips from the heatsink temperature sensor on the drive.
Parameter 605, Number of Overvoltage Trips
Shows the number of overvoltage trips from the sensor of DC link
voltage of the drive. The count is only taken when Alarm 7 Overvoltage
is activated.
600Operating Hours(OPERATING HOURS)Hours0 through 130,000.0
601Hours Run(RUNNING HOURS)Hours0 through 130,000.0
602kWh Counter(KWH COUNTER)kWh 603Number of Power-ups(POWER UPS)Occurences0 through 9999
604Number of Overtemp Trips(OVER TEMPS)Occurences0 through 9999
605Number of Overvoltage Trips(OVER VOLTS)Occurences0 through 9999
88
Page 89
606 - 614 Data Log
Value:
ParameterDescriptionDisplayUnit Range
no.Data log:Text
606Digital Input(LOG: DIGITAL INP)Decimal0 through 255
607Control Word(LOG: BUS COMMAND)Decimal0 through 65535
608Status Word(LOG: BUS STAT WD)Decimal0 through 65535
609Reference(LOG: REFERENCE)%0 through 100
610Feedback(LOG: FEEDBACK)Par. 414-999,999.999 through 999,999.999
611Output Frequency(LOG: MOTOR FREQ.)Hz0.0 through 999.9
612Output Voltage(LOG: MOTOR VOLT)Volt50 through 1000
613Output Current(LOG: MOTOR CURR.)Amp0.0 through 999.9
614DC Link Voltage(LOG: DC LINK VOLT)Volt0.0 through 999.9
Function:
With these parameters, it is possible to see up to twenty saved values,
or data logs. Data log [1] is the most recent and [20] the oldest log.
When a start command has been given, a new entry to the data log is
made every 160 ms. If there is a trip or if the drive is stopped, the 20
latest data log entries will be saved and the values will be visible in the
display. This is useful to view the operation of the drive just before a
trip. These values will be lost if power is removed from the drive.
The drawing below shows a display. The data log number is shown in
the square brackets at the left of the forth line of the display.
EXT. REFERENCE, %
SETUP
63.0 %
606 DATALOG: DIGITAL INP
1
[1] 40
Data logs [1] through [20] can be read by first pressing CHANGE
DATA, followed by the + and - keys to change data log numbers.
The table can be used for converting a decimal number into a binary
code. For example, digital 40 corresponds to binary 00101000. The
nearest smaller decimal number is 32, corresponding to a signal on
terminal 18. 40-32 = 8, corresponds to the signal on terminal 27.
This is where the latest log data is given in decimal code for the control
word of the drive. The control word can only be changed via serial
communication. The control word is read as a decimal number which is
to be converted into hex. See the control word profile under the section
Serial communications.
Parameter 608, Data Log: Status Word:
This gives the latest log data in decimal code for the status word. The
status word is read as a decimal number which is to be converted into
hex. See the status word profile under the section Serial communica-
tion.
Parameter 609, Data Log: Reference:
This gives the latest log data for the resulting reference.
Parameters 606 through 614, Data Log, can also be read out via the
serial communication port.
Description of choice:
Parameter 606 Data Log: Digital Input:
This is where the latest log data is shown in decimal code, representing
the status of the digital inputs. Translated into binary code, terminal 16
corresponds to the bit to the extreme left and to decimal code 128.
Terminal 33 corresponds to the bit to the extreme right and to decimal
code 1.
Parameter 610, Data Log:Feedback:
This gives the latest log data for the feedback signal.
Parameter 611, Data Log: Output Frequency:
This gives the latest log data for the output frequency.
Parameter 612, Data Log: Output Voltage:
This gives the latest log data for the output voltage.
Parameter 613, Data Log: Output Current:
This gives the latest log data for the output current.
Parameter 614, Data Log: DC Link Voltage:
This gives the latest log data for the intermediate circuit voltage.
89
Page 90
615Fault Log: Error Code
(F. LOG: ERROR CODE)
Value:
[Index 1-10] Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason why a fault trip
occurs. Ten log values, indicated as [1] through [10] are stored.
618Reset of kWh Counter
(RESET KWH COUNT)
Value:
★ No reset (DO NOT RESET)[0]
Reset (RESET COUNTER)[1]
Function:
Reset to zero of parameter 602, kWh Counter.
The lowest log number [1] contains the most recently saved data value;
the highest log number [10] contains the oldest data value.
If there is a fault trip, it is possible to see its cause, the time and possibly
the values or output current or output voltage. See the section on
Warnings and Alarms for a table explaining the error codes.
Description of choice:
The fault log is only reset after manual initialization.
616Fault Log: Time
(F. LOG: TIME)
Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total number of hours run in
connection with the 10 most recent fault trips. Ten log values, indicated
as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value:
the highest log number [10] contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialization.
Description of choice:
If Reset has been selected and the OK key is pressed, the kWh counter
of the drive is reset.
619Reset of Hours Run Counter
(RESET RUN. HOUR)
Value:
★ No reset (DO NOT RESET)[0]
Reset (RESET COUNTER)[1]
Function:
Reset to zero of parameter 601, Hours Run.
Description of choice:
If Reset has been selected and the OK key is pressed, parameter 601
Hours-run is reset to zero.
620Operating Mode
(OPERATION MODE)
Value:
★ Normal function (NORMAL OPERATION)[0]
Function with deactivated inverter
(OPER. W/INVERT.DISAB)[1]
Control card test (CONTROL CARD TEST)[2]
Initialization (INITIALIZE)[3]
617Fault Log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at which a fault trip
occurred. The unit of the value depends on the alarm active in
parameter 615, Fault Log: Error Code.
Description of choice:
The fault log is only reset after manual initialization.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
90
Function:
In addition to its normal function, this parameter can be used for two
different tests.
It is possible to reset to the default factory settings for all Setups, except
parameters 500, Address; 501 Baud Rate; 600-605, Operating Data;
and 615-617, Fault Log.
Description of choice:
Normal function is used for normal operation of the motor.
Function with deactivated inverter is selected to operate the control
card using its control signals without running the motor.
Control card test is used to test the analog and digital inputs, analog
and digital outputs, relay output and the power supplies of the control
card.
Page 91
A test connector with the connections shown below is required for this
test.
Initialization is selected to reset the drive to its factory default settings
without resetting parameters 501 Address, 502 Baud Rate; 600-605,Operating Data; and 615-617, Fault Log.
Set test connector set up as follows:
1. Connect 4, 16, 17, 18, 19, 27, 29, 32 and 33.
2. Connect 5 and 12.
3. Connect 39, 20 and 55.
4. Connect 42 and 60.
5. Connect 45, 53 and 54
NOTE
Choosing Initialization resets drive to standard
default values. Any special application
programming performed at the factory, during
start-up, or thereafter, will be lost. As a backup,
upload drive settings into the driveís local
control panel (LCP) keypad as described in
parameter 004, LCP Copy.
Initialization the drive to factory default settings in accordance with the
following procedures:
1. Select Initialization.
2. Press OK key.
3. Remove input power and wait for light in display to go out.
4. Connect input power.
5. Initialization of all parameters will be carried out in all Setups with
exception of parameters 501, Address; 502, Baud Rate;
600-605, Operating Data; and 615-617, Fault Log.
Test the control card in accordance with the following procedure:
1. Select Control Card Test.
2. Remove input power and wait for light in display to go out.
3. Insert test connector described above.
4. Reconnect input power.
5. Press OK key. (Test cannot run without control panel in place.)
6. Drive automatically tests control card.
7. Remove test connector and press OK key when drive displays
TEST COMPLETED.
8. Parameter 620, Operating Mode, is automatically set to NormalFunction.
If the control card test fails, the drive will display TEST FAILED.
Replace the control card.
91
Page 92
621 - 631 Nameplate
Value:
ParameterDescription Display text
NumberNameplate:
621Unit Type(DRIVE TYPE)
622Power Component(POWER SECTION)
623TR1 Ordering No.(ORDERING NO)
624Software Version No.(SOFTWARE VERSION)
625Control Panel Identification No.(LCP ID NO.)
626Database Identification No.(PARAM DB ID)
627Power Component Identification No.(POWER UNIT DB ID)
628Application Option Type(APPLIC. OPTION)
629Application Option Ordering No.(APPLIC. ORDER NO)
630Communication Option Type(COM. OPTION)
631Communication Option Ordering No.(COM. ORDER NO)
Function:
Identification information for the drive can be read from parameters 621
through 631, Nameplate via the display or the serial communication
port.
Description of choice:
Parameter 621, Nameplate: Unit Type:
TR1 type gives the unit size and input voltage. See Cross Reference Model Number to TR1 Type to convert this do the drives model
number.
Parameter 622, Nameplate: Power Component:
This gives the type of power card installed in the drive.
Parameter 623, Nameplate: TR1 Ordering Number:
This gives the ordering number for the specific drive. Because this
number does not specify any special options or programming that was
provided with the drive, it is better to refer to the serial number printed
on the Trane nameplate when contacting the factory about the drive.
Parameter 624, Nameplate: Software Version Number:
This gives the present software version number of the drive.
This gives the ordering number for the application option of the basic
drive. Because this number does not specify any special options or
programming that was provided with the drive, it is better to refer to the
serial number printed on the Trane nameplate when contacting the
factory about the drive.
Parameter 630, Nameplate: Communication Option Type:
This gives the type of communication option card installed in the drive, if
any.
Parameter 631, Nameplate: Communication Option Ordering
Number:
This gives the ordering number for the communication option.
92
Page 93
Relay Card Functions
Parameters 700 through 711
Parameters 700 through 711 are only activated if a relayoption card is
installed in the drive. A relay card can be field installed in the drive if
desired.
Activation/deactivation can be programmed in parameters 701, 704,
707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702,
705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
Relay outputs 6, 7, 8 and 9 can be used for showing status and
warnings. The relay is activated when the conditions for the relevant
data values have been fulfilled. Because these have the same possible
functions as relay 1, see the description under parameter 323.
701Relay 6, ON Delay(RELAY6 ON DELAY)
704Relay 7, ON Delay(RELAY7 ON DELAY)
707Relay 8, ON Delay(RELAY8 ON DELAY)
710Relay 9, ON Delay(RELAY9 ON DELAY)
Value:
0 to 600 sec.★ 0 sec.
Electrical Installation of the Relay Card
The relays are connected as shown below.
Relay 6-9
A-B make, A-C break
Max. 240 VAC, 2 Amp
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
Description of choice:
Enter the desired value.
702Relay 6, OFF Delay(RELAY6 OFF DELAY)
705Relay 7, OFF Delay(RELAY7 OFF DELAY)
708Relay 8, OFF Delay(RELAY8 OFF DELAY)
711Relay 9, OFF Delay(RELAY9 OFF DELAY)
Value:
0 to 600 sec.★ 0 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8
and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value.
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
To achieve double isolation, mount the plastic foil as shown below.
✭ Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
93
Page 94
Status Messages
Status messages are generated automatically and appear in the fourth
(bottom) line of the display as shown.
A. The first part of the status line indicates the CONTROL POINT of
the drive.
B. The center part of the status line indicates the REFERENCE
LOCATION.
C. The last part of the status line gives the present DRIVE STATUS.
The table below defines the status massage display words.
80.0% 5.08A 2.1HP
SETUP
40.0 Hz
1
AUTO REM. RUNNING
HAND
OFF
A
LOCAL
B
STOP
RAMPING
JOGGING
.
.
.
.
STAND BY
C
DISPLAY
WORD
CONTROL POINT
AUTO The drive is in Auto mode, which means that Run/Stop control is carried out
HAND The drive is in Hand mode, which means that Run/Stop control is carried out
OFF OFF/STOP is activated either by means of the keypad, or by the digital
REFERENCE LOCATION
REM. If REMOTE has been selected, the reference is set via the control terminals
LOCAL If LOCAL has been selected, the reference is set via the [+] and [-] keys on
DRIVE STATUS
RUNNING The motor speed now corresponds to the resulting reference.
RAMPING The output frequency is changing.
AUTO RAMP Parameter 208, Autom atic Ramp, is enabled. The drive is attem pting to
SLEEP.BST
SLEEP
via the control term inals and/or serial communication.
via the keys on the keypad
inputs Hand Start and Auto Start, both being a logic ‘0.’
or via serial communication.
the keypad.
avoid a trip from overvoltage by extending its decel ramp time.
The boost function in parameter 406, Boost Setpoint, is enabled. This
function can only be enabled in Closed Loop operation.
WARNING
!
DESRIPTION
Unintended Start!
When in Sleep mode, motor may restart at any time without warning. The
drive, motor, and any driven equipment m ust be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
The energy saving function in parameter 403, Sleep Mode Timer, is enabled.
This status m essage shows that at present the motor has been stopped by
sleep mode. It can restart automatically.
START DEL
Unintended Start!
When in Start Delay mode, motor may restart at any time without warning. The
drive, motor, and any driven equipment m ust be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
A start delay tim e has been programm ed in parameter 111, Start Delay.
When the delay has passed, the drive will start and ramp up to the refe ren ce
frequency.
94
WARNING
!
Page 95
DISPLAY
WORD
RUN REQ.
WARNING
!
DESRIPTION
Unintended Start!
When in Run Request mode, motor may restart at any time without warning.
The drive, motor, and any driven equipm ent must be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
A start com mand has been given, but the motor will not be starte d until a
Run Permission signal is received via a digital input.
JOG Jog has been enabled via a digital input or via serial comm unication.
JOG REQ.
WARNING
!
Unintended Start!
When in Jog Request mode, motor may restart at any time without warning.
The drive, motor, and any driven equipm ent must be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
A start com mand has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input.
FRZ.OUT The output frequency has been frozen.
FRZ.REQ
WARNING
!
Unintended Start!
When in Freeze Request mode, motor may restart at any time without
warning. The drive, motor, and any driven equipment must be in operational
readiness. Failure to be in operational readiness could result in death, serious
injury, or equipment and property damage.
A start com mand has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input.
START F/R Reversing and start on terminal 19, parameter 303, Digital Inputs, and Start
AMA RUN Automatic motor adaptation has been enabled in param eter 107, Autom atic
AMA STOP Automatic motor adaptation has been com pleted. The drive is now ready for
STANDBY The drive is able to start the motor when a start command is received.
STOP The motor has been stopped via a stop signal from serial communication.
DC STOP The DC brake has been enabled in parameters 114 through 116.
UN.READY The drive is ready for operation, but term inal 27 is a logic ‘0’ and/or a
NOT READY The drive is not ready for operation, because of a trip or because OFF1,
ST ART IN. T his status will only be dis played if, in param ete r 599, Profidrive [1] has been
XXXX The microprocessor of the control has stopped and the drive is not
on term inal 18, parameter 302, Digital Inputs, are enabled at the same time.
The m otor will rem ain stopped until one of the signals becom es a logic ‘0.’
Motor Adaptation, AMA.
operation after the Reset signal has been given. Note that the m otor will start
after the drive has received the Reset signal.
Coasting Command has been received via the serial communication.
OFF2 or O FF3 is a logic ‘0.’
selected and OFF2 or OFF3 is a logic ‘0.’
operating. The cause m ay be noise on the power line, motor leads or control
wires.
95
Page 96
Warnings and Alarms
A trip can be reset in any one of the following ways:
The table below lists the drive fault messages and indicates whether a
warning, alarm, or trip-lock occurs. Wherever an X is placed under
both warning and alarm, this means that a warning precedes the alarm.
An alarm always precedes, or simultaneously accompanies, a trip-lock.
A trip causes the drive to suspend operation by cutting off power to the
motor. A trip-lock requires that input power to the drive be removed, the
cause of the fault corrected, and the input power restored in order to
reset the drive.
1)Manual reset by pressing the RESET key on the keypad
2)A digital input through a digital input terminal
3)Serial communication command
4)Automatic reset
Automatic or manual reset may be selected in parameter 400, Reset
Function. Auto reset will not restore a trip-lock. The number of reset
attempts may be selected or infinite, which allows continuous attempts. A
timer between attempts can be set in parameter 401.
No.DescriptionWarningAlarmTrip Locked
1Under 10 Volts (10 VOLT LOW)X
2Live zero fault (LIVE ZERO ERROR)XX
4Mains phase imbalance (MAINS IMBALANCE)XXX
5Voltage warning high (DC LINK VOLTAGE HIGH)X
6Voltage warning low (DC LINK VOLTAGE LOW)X
7Overvoltage (DC LINK OVERVOLT)XX
8Undervoltage (DC LINK UNDERVOLT)XX
9Inverter overloaded (INVERTER TIME)XX
10Motor overloaded (MOTOR TIME)XX
11Motor thermistor (MOTOR THERMISTOR)XX
12Current limit (CURRENT LIMIT)XX
13Overcurrent (OVERCURRENT)XX
14Ground fault (EARTH FAULT)XX
15Switch mode fault (SWITCH MODE FAULT)XX
16Short circuit (CURR.SHORT CIRCUIT)XX
17Serial communication timeout (STD BUSTIMEOUT)XX
18HP field bus timeout (HPFB TIMEOUT)XX
19Fault in EEPROM on power card (EE ERROR POWER)X
20Fault in EEPROM on control card (EE ERROR CONTROL)X
22Auto motor adaptation fault (AMA FAULT)X
29Heat-sink temperature too high (HEAT SINK OVERTEMP.)XX
30Motor phase U missing (MISSING MOT.PHASE U)X
31Motor phase V missing (MISSING MOT.PHASE V)X
32Motor phase W missing (MISSING MOT.PHASE W)X
34HPFB communication fault (HPFB COMM. FAULT)XX
35Out of frequency range (OUT FREQ RNG/ROT LIM)X
37Inverter fault (GATE DRIVE FAULT)XX
39Check parameters 104 and 106 (CHECK P.104 & P.106)X
40Check parameters 103 and 105 (CHECK P.103 & P.106)X
41Motor too large (MOTOR TOO BIG)X
42Motor too small (MOTOR TOO SMALL)X
60Safety stop (EXTERNAL FAULT)X
61Output frequency low (FOUT < FLOW)X
62Output frequency high (FOUT > FHIGH)X
63Output current low (I MOTOR < I LOW)XX
64Output current high (I MOTOR > I HIGH)X
65Feedback low (FEEDBACK < FDB LOW)X
66Feedback high (FEEDBACK > FDB HIGH)X
67Reference low (REF. < REF. LOW)X
68Reference high (REF. > REF. HIGH)X
69Temperature auto derate (TEMP.AUTO DERATE)X
99Unknown fault (UNKNOWN ALARM)XX
96
Page 97
Warnings
A warning will flash in line 2, while an explanation is given in line 1.
MAINS PHASE LOSS
SETUP
WARN.4
1
Alarms
If an alarm is given, the present alarm number will be shown in line 2.
Lines 3 and 4 of the display will offer an explanation.
TRIP (RESET)
SETUP
ALARM:12
1
TORQUE LIMIT
WARNING 1
10 VOLT LOW
The 10 V voltage from terminal 50 on the control card is below 10V.
Remove some of the load from terminal 50, as the 10 volts supply is
overloaded. Maximum load is 17 mA, minimum resistance is 590 Ω.
WARNING/ALARM 2
LIVE ZERO ERROR
The current or voltage signal on terminal 53, 54 or 60 is below 50% of
the value preset in parameters 309, 312 and 315 Terminal, Minimum
Scaling.
WARNING/ALARM 4
MAINS IMBALANCE
Phase missing on the input power. Check the supply voltage to the
drive.
WARNING 5
DC LINK VOLTAGE HIGH
The intermediate DC circuit voltage is higher than Voltage Warning
High, see table below. The drive is still controlling the motor.
WARNING 6
DC LINK VOLTAGE LOW
The intermediate DC circuit voltage is lower than Voltage Warning Low,
see table below. The drive is still controlling the motor.
WARNING/ALARM 7
DC LINK OVERVOLT
If the intermediate circuit voltage (DC) is higher than the Overvoltage
Limit of the drive (see table below), the drive will trip after a fixed
period. The length of this period depends upon the unit.
WARNING/ALARM 8
Undervoltage (DC LINK UNDERVOLT)
If the intermediate circuit voltage (DC) drops below the Undervoltage
Limit of the inverter, the drive will trip after a fixed period. The length of
the period depends upon the unit.
The voltage will be stated in the display. Check whether the supply
voltage matches the drive rating.
WARNING/ALARM 9
INVERTER TIME
The electronic thermal inverter protection reports that the drive is about
to trip because of an overload. The counter for electronic thermal
inverter protection gives a warning at 98% and trips at 100% showing
an alarm. The drive cannot be reset until the counter drops below
90%. Activate ASFM (Automatic Switching Frequency Modulation) in
parameter 408, Interference Reduction Method, or reduce the carrier
frequency in parameter 407, Switching Frequency.
Alarm/Warning Limits:
Drive 208 to 230 volt 380 to 460 volt550 to 600 volt
Undervoltage alarm211151402289557413
Voltage warning, low222159423304613443
Voltage warning, high384276777530943667
Overvoltage alarm425305798550975689
VDCVACVDCVACVDCVAC
97
Page 98
WARNING/ALARM 10
MOTOR TIME
According to the electronic thermal protection, the motor is overheated.
Parameter 117, Motor Thermal Protection, allows a choice of whether
the drive is to give a warning or an alarm when the Motor ThermalProjection reaches 100%. The fault is that the motor is overloaded to
more than 100% of the preset rated motor current for too long. Check
that the motor parameters 102 through 106 have been set correctly.
ALARM 16
CURR. SHORT CIRCUIT
There is a short circuit in the output from the drive.
Remove power to the drive and correct the short circuit.
WARNING/ALARM 17
STD BUSTIMEOUT
There is no serial communication with the drive.
WARNING/ALARM 11
MOTOR THERMISTOR
The thermistor or the thermistor connection has been disconnected.
Parameter 117, Motor Thermal Protection, allows a choice of whether
the drive is to give a warning or an alarm. Check that the thermistor
has been correctly connected between terminal 53 or 54 (analog
voltage input) and terminal 50 (+10 V supply).
WARNING/ALARM 12
CURRENT LIMIT
The current is higher than the value in parameter 215, Current Limit,
and the drive trips after the time set in parameter 412, Trip Delay
Overcurrent, has passed. Run AMA on a cold motor in parameter 107,
Automatic Motor Adaptation.
WARNING/ALARM 13
OVER CURRENT
The inverter peak current limit, approximately 200% of the rated
current, has been exceeded. The warning will last approximately 1 or
2 seconds, and then the drive will trip and signal an alarm.
Turn off the drive and check for free rotation of the motor shaft and
other causes of the overload. Run AMA on a cold motor in parameter
107, Automatic Motor Adaptation.
ALARM 14
EARTH FAULT
There is current leakage from the output phases to ground, either in the
leads between the drive and the motor or in the motor itself.
Remove power to the drive and correct the ground fault.
ALARM 15
SWITCH MODE FAULT
Fault in the switch mode power supply (internal ±15 V supply).
This warning will only be enabled if parameter 510, Bus Time Interval
Function, has been set to a value different from OFF.
If parameter 510, Bus Time Interval Function, has been set to Stop
and Trip [5], the drive will first give off an alarm, then ramp down and
finally trip while giving an alarm. It is possible to increase parameter
509, Bus Time Interval.
WARNING/ALARM 18
HPFB TIMEOUT
There is no serial communication with the communication option card in
the drive.
The warning will only be enabled if parameter 804, Bus Time Interval
Function, has been set to anything but OFF. If parameter 804, Bus
Time Interval Function, has been set to Stop and Trip, the drive will
first give an alarm, then ramp down and finally trip while giving an
alarm.
Parameter 803, Bus Time Interval could possibly be increased.
Parameter 803 is only available when a communication option card is
installed in the drive.
WARNING 19
EE ERROR POWER
There is a fault on the power card EEPROM. The drive will continue to
function, but is likely to fail at the next power-up. Contact the Trane
service department.
WARNING 20
EE ERROR CONTROL
There is a fault in the EEPROM on the control card. The drive will
continue to function, but is likely to fail at the next power-up. Contact the
Trane service department.
Contact the Trane service department.
98
Page 99
ALARM 22
AMA FAULT
A fault has been found during automatic motor adaptation (AMA). The
text shown in the display indicates a fault message.
AMA can only be carried out if there are no alarms during the AMA
process.
CHECK 103, 105
Parameter 103 or 105 has a wrong setting. Correct the setting
and repeat AMA.
LOW P 105
The motor is too small for AMA to be carried out. If AMA is to be
enabled, the rated motor current, parameter 105, must be higher
than 35% of the rated output current of the drive.
ASYMMETRICAL IMPEDANCE
AMA has detected an asymmetrical impedance in the motor
connected to the system. The motor could be defective.
ALARM 29
HEAT SINK OVER TEMP.
The heatsink temperature became too high. For NEMA 1 drives, the
limit is 90°C. For NEMA 12 drives, the limit is 80°C. The tolerance is
±5°C. The fault cannot be reset until the temperature of the heatsink
has fallen below 60°C.
The fault could be due to the following:
- Ambient temperature too high
- Air obstructed
- Cooling fan(s) not operating
- Motor leads too long
- Too high a switching frequency
ALARM 30
MISSING MOT.PHASE U
Motor phase U, as indicated by the letters on the output terminal block,
is missing or has a high impedance.
Remove power to the drive and check motor phase U.
MOTOR TOO BIG
The motor connected to the system is too big for AMA to be carried
out. The setting in parameter 102 does not match the motor used.
MOTOR TOO SMALL
The motor connected to the system is too small for AMA to be
carried out. The setting in parameter 102 does not match the
motor used.
TIME OUT
AMA fails because of noisy measuring signals. Retry until AMA is
successfully completed. Please note that repeated AMA runs may
heat the motor to a level where the stator resistance is increased.
INTERRUPTED BY USER
AMA has been interrupted by the user.
INTERNAL FAULT
An internal fault has occurred in the drive. Contact Trane service
department.
LIMIT VALUE FAULT
The parameter values found for the motor are outside the
acceptable range within which the drive is able to work.
MOTOR ROTATES
The motor shaft is rotating. Make sure that the load is not able to
make the motor shaft rotate while the AMA is being performed.
Then start AMA all over.
ALARM 31
MISSING MOT.PHASE V
Motor phase V, as indicated by the letters on the output terminal block is
missing or has a high impedance.
Remove power to the drive and check motor phase V.
ALARM 32
MISSING MOT.PHASE W
Motor phase W, as indicated by the letters on the output terminal block
is missing or has a high impedance.
Remove power to the drive and check motor phase W.
WARNING/ALARM 34
HPFB COMM. FAULT
The serial communication on the communication option card is not
working.
WARNING 35
OUT FREQ RNG/ROT LIM
This warning will occur if the output frequency has reached its Output
Frequency Low Limit , parameter 201, or Output Frequency High
Limit, parameter 202. If the drive is in Closed Loop, parameter 100, the
warning will show in the display.
99
Page 100
ALARM 37
GATE DRIVE FAULT
An output IGBT or the power card is defective. Contact the Trane
service department.
WARNING 62
FOUT > FHIGH
The output frequency is higher than parameter 224, Warning: High
Frequency.
Auto Optimization Warnings 39 through 42
Automatic motor adaptation has stopped, because some parameters
have probably been improperly set, or the motor used in too large or
small for AMA to be carried out.
A choice must be made by pressing CHANGE DATA and choosing
Continue + OK or Stop + OK.
If parameters need to be changed, select Stop, change the parameters
and run AMA again.
WARNING 39
CHECK PAR. 104, 106
Parameters 104, Motor Frequency, or 106, Rated Motor Speed, have
probably not been set correctly. Correct the setting and run AMA again.
WARNING 40
CHECK PAR. 103, 105
Parameter 103 Motor Voltage, or 105 Motor Current, has not been set
correctly. Correct the setting and run AMA again.
WARNING 41
MOTOR TOO BIG
The motor used is probably too large for AMA to be carried out. The
setting in parameter 102 Motor Power, may not match the motor. Check
the motor and select Continue or [STOP].
WARNING 42
MOTOR TOO SMALL
The motor used is probably too small for AMA to be carried out. The
setting in parameter 102 Motor Power, may not match the motor. Check
the motor and select Continue or [STOP].
ALARM 60
EXTERNAL FAULT
Terminal 27, parameter 304, Digital Inputs, has been programmed for
a Safety Interlock and is a logic 0.
WARNING 61
FOUT < FLOW
The output frequency is lower than parameter 223, Warning: Low
Frequency.
WARNING/ALARM 63
I MOTOR < I LOW
The output current is lower than parameter 221, Warning: Low
Current. Select the required function in parameter 409, Function in
Case of No Load.
WARNING 64
I MOTOR > I HIGH
The output current is higher than parameter 222, Warning: High
Current.
WARNING 65
FEEDBACK < FDB LOW
The resulting feedback value is lower than parameter 227, Warning:
Low Feedback.
WARNING 66
FEEDBACK > FDB HIGH
The resulting feedback value is higher than parameter 228, Warning:
High Feedback.
WARNING 67
REF. < REF LOW
The remote controlled reference is lower than parameter 225,
Warning: Low Reference.
WARNING 68
REF. > REF HIGH
The remote controlled reference is higher than parameter 226,
Warning: High Reference.
WARNING 69
TEMP.AUTO DERATE
The heat sink temperature has exceeded the maximum value and the
auto derating function in parameter 411, Function at Over Temp
, is
active.
WARNING 99
UNKNOWN ALARM
An unknown fault has occurred which the software is not able to
handle. Contact Trane service department.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.