Trane TR1 6006, TR1 6011, TR1 6004, TR1 6003, TR1 6016 Installation And Operation Manual

...
Page 1
TR1 Series VFD Variable Frequency Drive
Installation and Operation Manual
August, 2004 TR1-SVX10A-EN
175R5559
Page 2
!
Equipment Hazard!
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by qualified personnel. Failure to follow the NEC or local regulations could result in death or serious injury.
Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit.
Although shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the motor is stopped, it should be consid­ered alive as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the controller.
Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking compo­nents. Always work with another person in case of an emergency. Disconnect power whenever possible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1. The drive must be disconnected from the AC line before any service work is done.
2. The STOP/OFF key on the local control panel of the drive does not disconnect the equipment from the AC line and is not to be used as a safety switch.
3. Correct protective grounding of the equipment must be estab­lished. The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.
4. Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the LOCAL/HAND key is activated, the motor can only be brought to a stop by means of the STOP/OFF key or an external safety interlock.
Motor Overload Protection
NOTE Person installing drive is responsible to provide proper grounding and branch circuit protection for incoming power and motor overload according to National Electrical Code (NEC) and local codes.
WARNING
!
Hazardous Voltage!
Touching electrical parts may be fatal, even after equipment has been disconnected from the AC input line. To be sure that capacitors have fully discharged, wait 14 minutes for 208 V and 480 V units and 30 minutes for 600 V units over 25 hp after power has been removed before touching any internal component. Failure to wait for capacitors to fully discharge before touching internal components could result in death or serious injury.
Copyright © 2004 American Standard, Inc. All rights reserved.
The electronic thermal relay (ETR) in UL listed TR1s provides Class 20 motor overload protection in accordance with the NEC in single motor applications when parameter 117 is set for ETR TRIP and parameter 105 is set for the rated motor current.
Page 3
Never ignore warnings, cautions and notes in this manual. They are provided to alert anyone installing, operating, or maintaining this equipment to potential hazards or ineffective practices. Notes are used to call special attention to information which, if ignored or not clearly understood, in most cases will result in degraded or less then optimum equipment operation.
Become familiar with all warnings, cautions, and notes in this manual. These are important guidelines intended for your safety and for full utilization of the operational features of the equipment.
WARNING
!
CAUTION
!
CAUTION
NOTE
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation which, if not avoided, may result in injury. It may
also be used to alert against unsafe practices.
In dic ates a situa tio n wh ich , if ignored, could result in substantial equipment or property
damage.
Contains important information that, if not clearly understood or ignored, could result in
degraded or less than optimum equipment operation.
3
Page 4
Page 5
Table of Contents
General ................................................................................................................................................................................................................... 7
Clearances ............................................................................................................................................................................................................. 7
Backplate Requirements .......................................................................................................................................................................................... 7
Plenum Mounting..................................................................................................................................................................................................... 8
Grounding Plate ...................................................................................................................................................................................................... 8
Shielded Wires ........................................................................................................................................................................................................ 8
Standard Service Conditions ................................................................................................................................................................................... 8
UL, C-UL, and CE Conformity ................................................................................................................................................................................. 8
Drive Output Ratings ............................................................................................................................................................................................... 9
Input Fuses ........................................................................................................................................................................................................... 10
Internal Drive Fuses .............................................................................................................................................................................................. 11
Terminal Identification ............................................................................................................................................................................................. 11
Input Power Delay ................................................................................................................................................................................................ 11
Power Connections ............................................................................................................................................................................................... 12
Input Power Connection ........................................................................................................................................................................................ 13
Motor Wiring Connection ........................................................................................................................................................................................ 13
Grounding ............................................................................................................................................................................................................. 13
Electronic Thermal Protection ................................................................................................................................................................................. 13
Terminal Tightening Torque ................................................................................................................................................................................... 14
Terminal Tightening Torque for Optional Auxiliary Control Panels ........................................................................................................................... 14
External DC Bus Connection ................................................................................................................................................................................. 17
High Voltage Form C Relay ................................................................................................................................................................................... 17
Control Connections .............................................................................................................................................................................................. 18
Electrical Installation, Control Terminals .................................................................................................................................................................. 18
Drive Inputs and Outputs ....................................................................................................................................................................................... 18
Input Signals ......................................................................................................................................................................................................... 18
Output Signals ....................................................................................................................................................................................................... 19
Programming Control Terminals............................................................................................................................................................................. 19
Control Terminal Functions .................................................................................................................................................................................... 19
Typical Control Connections .................................................................................................................................................................................. 21
Electrical Installation, Control Wiring ....................................................................................................................................................................... 22
DIP Switches 1 through 4 ...................................................................................................................................................................................... 22
Ground Leakage Current .........................................................................................................
Galvanic Isolation .................................................................................................................................................................................................. 23
Extra Safety Protection .......................................................................................................................................................................................... 23
Electrical Noise ...................................................................................................................................................................................................... 23
Application Control Connection Examples .............................................................................................................................................................. 24
Control Panel ........................................................................................................................................................................................................ 25
Keys for Parameter Changes ................................................................................................................................................................................ 25
Indicator Lamps ..................................................................................................................................................................................................... 26
Local Control......................................................................................................................................................................................................... 26
Display Modes ...................................................................................................................................................................................................... 26
Changing Data...................................................................................................................................................................................................... 28
Changing Numeric Values ..................................................................................................................................................................................... 28
Changing Functional Values .................................................................................................................................................................................. 28
Changing Numeric Values in a List......................................................................................................................................................................... 28
Quick Menu ........................................................................................................................................................................................................... 29
To Enter or Change Quick Menu Parameter Data .................................................................................................................................................. 29
Example of Changing Parameter Data ................................................................................................................................................................... 29
Extended Menu..................................................................................................................................................................................................... 30
Manual Initialization of Parameters.......................................................................................................................................................................... 30
Uploading Parameters........................................................................................................................................................................................... 30
TR1 Series VFD Start-Up...................................................................................................................................................................................... 31
Pre-installation Checks .......................................................................................................................................................................................... 31
Installation Checks ................................................................................................................................................................................................. 31
............................................................................. 22
5
Page 6
Setting Up Drive for Motor Start ............................................................................................................................................................................. 31
HAND Operational Tests........................................................................................................................................................................................ 31
AUTO Operational Tests ........................................................................................................................................................................................ 31
Final Adjustments ................................................................................................................................................................................................... 31
Programming......................................................................................................................................................................................................... 32
Description of Parameters ...................................................................................................................................................................................... 32
Operation and Display
Parameters 000 through 017 ......................................................................................................................................................................... 32
Setup Configuration and Copying Parameters ........................................................................................................................................................ 32
Setup of User-defined Readout.............................................................................................................................................................................. 33
Load and Motor
Parameters 100 through 118.......................................................................................................................................................................... 38
Procedure for Automatic Motor Adaptation: ............................................................................................................................................................. 40
DC Braking ........................................................................................................................................................................................................... 42
Motor Thermal Protection....................................................................................................................................................................................... 43
References and Limits
Parameters 200 through 228 ......................................................................................................................................................................... 44
Reference Handling .............................................................................................................................................................................................. 45
Reference Type .................................................................................................................................................................................................... 48
Warning Functions................................................................................................................................................................................................. 50
Inputs and Outputs
Parameters 300 through 328 ......................................................................................................................................................................... 52
Analog Inputs ........................................................................................................................................................................................................ 55
Analog/Digital Outputs............................................................................................................................................................................................ 58
Relay Outputs........................................................................................................................................................................................................ 61
Application Functions
Parameters 400 through 427 ......................................................................................................................................................................... 63
Sleep Mode .......................................................................................................................................................................................................... 64
Feedback Signals in Open Loop ............................................................................................................................................................................ 68
PID for Process Regulation.................................................................................................................................................................................... 69
Feedback .............................................................................................................................................................................................................. 69
Reference (Setpoint) ............................................................................................................................................................................................. 69
Inverse Regulation ................................................................................................................................................................................................ 69
Anti-windup ........................................................................................................................................................................................................... 69
Start-up Conditions ................................................................................................................................................................................................ 69
Differentiator Gain Limit .......................................................................................................................................................................................... 70
Lowpass Filter....................................................................................................................................................................................................... 70
Optimization of the Process Regulator ..................................................................................................................................................................... 70
PID Overview ....................................................................................................................................................................................................... 70
Feedback Handling ............................................................................................................................................................................................... 70
Serial Communication
Parameters 500 through 571 ......................................................................................................................................................................... 75
Programming Custom Display Text ........................................................................................................................................................................ 80
Warning Words, Extended Status Word and Alarm Word ........................................................................................................................................ 82
Serial Communication for FC Protocol .................................................................................................................................................................... 83
Protocols ............................................................................................................................................................................................................... 83
Packet Communication ........................................................................................................................................................................................... 83
Service Functions
Parameters 600 through 631 ......................................................................................................................................................................... 88
Relay Card Functions
Parameters 700 through 711.......................................................................................................................................................................... 93
Electrical Installation of the Relay Card ................................................................................................................................................................... 93
Status Messages ................................................................................................................................................................................................... 94
Warnings and Alarms............................................................................................................................................................................................. 96
Warnings............................................................................................................................................................................................................... 97
Alarms................................................................................................................................................................................................................... 97
Factory Settings................................................................................................................................................................................................... 102
SOFTWARE VERSION NOTICE: The software version number can be read in parameter
6
624, Software Version.
Page 7
General
The specific installation instructions may vary depending upon the model of TR1 Series VFD being installed. When this occurs, the model can be identified by a TR1 Type 6XXX number. This number can be found on the red nameplate on the outside left side of the drive enclosure, or the outside right side of a drive with an auxiliary enclosure.
The drive must always be installed vertically. To ensure that no injury or damage occurs, the drive must always be firmly attached to the wall or the floor before further installation work is carried out.
Clearances
The drive is cooled by air circulation. For proper cooling, the minimum distances above and below the unit must be maintained as shown in the table below. For units in an auxiliary enclosure with the drive mounted on a backpanel, the required clearances are measured from the top and bottom of the drive, not the backpanel.
Backplate Requirements
Mount directly to the wall all drives without a backplate. This ensures that air flow is in contact with the heatsink all the way from the bottom of the drive. If this is not possible, a metal plate at least as large as the back of the drive may need to be firmly mounted to the back of the drive (see tables below). A backplate assembly is available from Trane.
X
X
Drive Size Top Cleara nce Bottom Clearance
1 to 3 hp, 200-240 V 1 to 10 hp, 380-460, 550-600 V 5 to 30 hp, 200-240 V 15 to 75 hp, 380-460, 550-600 V 40 to 60 hp, 200-240 V 100 to 125 hp, 380-460, 550-600 V
150 to 300 hp, 380-460, 550-600 V 12" (300mm) 12" (300mm)
350 to 600 hp, 380-460 V 16" (400mm) Floor mou nt
4" (100mm) 4" (100mm)
8" (200mm) 8" (200mm)
9" (225mm) 9" (225mm)
All drives can be mounted with no side clearance. Sufficient space must be provided in front of the drive for door swing on units with a hinged door. TR1 drives 350 hp and above require 25 inches (605 mm) front space for access. In addition, sufficient room must be available for installation and service access. On units with an auxiliary enclosure, the auxiliary enclosure door will have a greater door swing than the drive. See the dimensional drawings of the auxiliary enclosure which are included with the drive.
Drives without a backplate must be mounted directly to a solid wall with no spacers between the drive and the wall. Free-standing drives without a backplate require a backplate to be mounted.
NEMA 1
Backplate Required
Drive Size Power
5 to 30 hp 200-240 V
15 to 75 hp 380-460 V
150 to 300 hp 380-460 V
15 to 75 hp 550-600 V
200 to 300 hp 550-600 V
NEMA 12
Backplate Required
Drive Size Power
1 to 30 hp 200-240 V
1 to 75 hp 380-460 V
7
Page 8
Plenum Mounting
The drive is UL rated for plenum mounting as well as auxiliary panels that may be supplied with the drive. If the equipment is to be mounted in the plenum, allow sufficient access for servicing. All normal clearance, temperature, humidity limitations and local codes apply.
Standard Service Conditions
The mechanical and electrical components of the TR1 Series VFDs can be adversely affected by the environment. High temperatures and harsh environments may reduce life of drive if proper precautions are not taken.
Grounding Plate
Drives up to 3 hp, 200 to 240 V, and up to 10 hp, 380 to 460 V and 550 to 600 V with a NEMA 1 enclosure have a plastic bottom cover with provision for conduit entry. To meet UL requirements, the metal grounding plate must be in place above the plastic bottom cover. The plate must be grounded to the chassis and the conduit grounded to the plate. If the grounding plate is not factory installed, it must be installed in the drives that have a plastic bottom panel to ensure proper grounding of the conduit to the enclosure. Connect the ground wire from the grounding plate to the ground tab marked with the ground symbol.
This tab is located near the AC line terminal strip. Mount the bottom cover on the control unit.
Shielded Wires
Wires to control signals should be shielded to reduce radiofrequency noise interference. When RFI is a concern, shielded cable should be used between the drive and the motor.
If unshielded control wires are used, control inputs are subject to signal disturbances. Such disturbances may affect drive operation. Extreme noise levels may disturb the microprocessor of the control card.
The shield of the control wires must be grounded at the cable clamp at the bottom of the drive, but the shield must continue with the cable all the way up to the control card. The shield is not to be connected to any of the terminals on the control card. For safety reasons, the insulation around the shield should only be removed where it is connected to the cable clamp. The insulation should be left on the shield between the clamp and the terminals.
Airborne Liquids
Rain, steam, oil, water vapor, high humidity, and such may cause corrosion of drive components. In such environments, use NEMA 12 enclosures. NEMA 12 enclosures limit the exchange of outside air into the drive enclosure. Extremely harsh environments may require a higher levels of protection.
Solids
Dust, dirt, metal drill shavings, foreign objects and the like may cause mechanical, electrical or thermal failure in the drive. A NEMA 1 enclosure provides a reasonable degree of protection against falling particles but will not prevent the drive fan from pulling dirty air into the drive. A typical indicator of excessive levels of airborne particles is dust around the fan. In dusty environments, use NEMA 12 enclosures.
Corrosive Chemicals
In environments with high temperatures and humidity, corrosive gases such as sulfur, nitrogen and chlorine compounds cause corrosion to occur in the drive. Such chemical reactions rapidly affect and damage electronic components. An indication of corrosion is blackened copper or oxygenation of steel or aluminum. In such environments, it is recommended that the equipment be mounted in a cabinet with fresh air ventilation and that corrosive compounds be kept away from the drive. A non-ventilated cabinet fitted with an air conditioner as a heat exchanger may be used. Conformal coated circuit boards may be specified to reduce the corrosive effects of a harsh environment.
Maximum Relative Humidity
Generally speaking, all conductors coming from a shieldedcontrol cable must be as short as possible. Long conductor ends attract noise. The shield must be connected to the chassis by means of the cable clamp. Long pigtails on the shield reduce the effectiveness of the shield.
8
95% non-condensing
Ambient Temperature
14°F to 104°F (-10°C to 40°C)
14°F to 122°F (-10°C to 50°C) for 200-240 V units of 40 hp or less and 380-600 V units of 125 hp or less when used with motor leads of 50 ft (15m) or less
UL, C-UL, and CE Conformity
All 200-240 V and 380-460 V TR1 Series VFDs are CE marked. All drives and option packages are UL and C-UL listed.
Page 9
Drive Output Ratings
208 V Input
TR1 Type Max. Nominal
Output HP
6002 1 / 1½ 6.9 6003 2 7.8 6004 3 11 6006 5 17.5 6008 26 6011 10 33 6016 15 48.3 6022 20 62.1 6027 25 78.2 6032 30 92 6042 40 120 6052 50 143 6062 60 170
460 V Input
TR1 Type Max. Nominal
Output HP
6002 1 / 1½ 3.0 6003 2 3.4
6004 3 4.8 6006 5 8.2 6008 11.0 6011 10 14.2 6016 15 21 6022 20 27 6027 25 34 6032 30 40 6042 40 52 6052 50 65 6062 60 77 6072 75 106 6102 100 130 6122 125 160 6150 150 190 6152 150 190 6172 200 240 6175 200 240 6222 250 302 6225 250 302 6272 300 361 6275 300 361 6350 350 443 6352 450 443 6400 450 540 6500 500 590 6550 600 678
Max. Drive
Output Current
Max. Drive
Output Current
230 V Input
TR1 Type Max. Nominal
6002 1 / 1½ 6.9 6003 2 7.8 6004 6006 5 17.5 6008 26 6011 10 33 6016 15 48.3 6022 20 62.1 6027 25 78.2 6032 30 92 6042 40 104 6052 50 130 6062 60 154
380 V Input
TR1 Type Max. Nominal
6002 1 / 1½ 3.0 6003 2 4.1
6004 3 5.6 6006 5 10 6008 13 6011 10 16 6016 15 24 6022 20 32 6027 25 37.5 6032 30 44 6042 40 61 6052 50 73 6062 60 90 6072 75 106 6102 100 147 6122 125 177 6150 150 212 6152 150 212 6172 200 260 6175 200 260 6222 250 315 6225 250 315 6272 300 368 6275 300 368 6350 350 480 6352 350 480 6400 450 600 6500 500 658 6550
600 V Input
TR1 Type Max. Nominal
6002 2.4 6003 2 2.7 6004 3 3.9 6006 5 6.1 6008 9 6011 10 11.4 6016 15 17 6022 20 22 6027 25 27 6032 30 32 6042 40 41 6052 50 52 6062 60 62 6072 75 77 6100 100 99 6125 125 1 25 6150 150 1 44 6175 200 1 92 6225 250 2 42 6275 300 2 89
Output HP
311
Output HP
600 745
Output HP
Max. Drive
Output Current
Max. Drive
Output Current
Max. Drive
Output Current
9
Page 10
Input Fuses
208/230 Volt Input
CAUTION
Branch Circuit Fuses Required!
All drives must be protected with branch circuit
fuses in accordance with the National Electrical
Code. Failure to provide branch circuit fuses in
accordance with the NEC may result in
equipment or property damage.
To comply with UL508C, input fuses shown in the tables below must be installed in the power supply to drives which are 208 V above 30 hp, and 380/460 V and 600 V drives above 75 hp. The fuse ratings in the tables below are the recommended maximum ratings.
NOTE Any UL listed Class T fuse with equivalent voltage and current rating may be used in place of JJS and JJN fuse types.
Trane recommends input fuses on all drives. If specified as a drive option, input fuses will be installed by The Trane Company in an enclosure external to the drive, which may include other optional features. If not supplied, they must be provided by the drive installer as part of installation.
380/460 Volt Input
Maximum Fuse
TR1 Type
6002 10 JJS 6003 15 JJS 6004 15 JJS 6006 25 JJS 6008 35 JJS 6011 45 JJS 6016 70 JJS 6022 90 JJS 6027 110 JJS 6032 125 JJS 6042 175 JJS 6052 200 JJS 6062 200 JJS 6072 250 JJS 6102 300 JJS 6122 350 JJS 6150 300 FWH 6152 300 FWH 6172 300 FWH 6175 350 FWH 6222 350 FWH 6225 400 FWH 6272 400 FWH 6275 500 FWH 6350 600 FWH 6352 600 FWH 6400 700 FWH 6500 800 FWH 6550 800 FWH
Rating (Amps)
Bussmann Type
Maximum Fuse
TR1 Type
6002 20 JJN or JJS 6003 20 JJN or JJS 6004 40 JJN or JJS 6006 50 JJN or JJS 6008 80 JJN or JJS 6011 100 JJN or JJS 6016 150 JJN or JJS 6022 200 JJN or JJS 6027 225 JJN or JJS 6032 300 JJN or JJS 6042 400 JJN or JJS 6052 200 FW X or FWH 6062 250 FW X or FWH
Rating (Am ps) Bussmann Type
600 Volt Input
Maximum Fuse
TR1 Type
6002 10 JJS 6003 10 JJS 6004 15 JJS 6006 20 JJS 6008 25 JJS 6011 35 JJS 6016 50 JJS 6022 60 JJS 6027 80 JJS 6032 90 JJS 6042 110 JJS 6052 150 JJS 6062 175 JJS 6072 100 JJS 6100 125 FW P 6125 175 FW P 6150 200 FW P 6175 250 FW P 6225 350 FW P 6275 400 FW P
200-240 V drives are suitable for use on a circuit capable of supplying a maximum of 100,000 A RMS (symmetrical), 250 V maximum.
380-460 V drives are suitable for use on a circuit capable of supplying a maximum of 100,000 A RMS (symmetrical), 500 V maximum.
550-600 V drives are suitable for use on a circuit capable of supplying a maximum of 100,000 A RMS (symmetrical), 600 V maximum.
Rating (Amps) Bussmann Type
10
Page 11
Internal Drive Fuses
The table below specifies fuses used internally in the TR1 series drives. Use the specified fuse or an exact replacement only.
Terminal Identification
The connectors for input and output power, auxiliary relay connections, and external DC bus are identified in the tables below.
Internal Fuses Provided with TR1 Series VFDs
TR1 Type Soft Charge Fuse
6042 Littelfuse KLK-15 Littelfuse KL K-D-12 Bussmann KTK-5 6052 Littelfuse KLK-15 Littelfuse KL K-D-12 Bussmann KTK-5 6062 Littelfuse KLK-15 Littelfuse KL K-D-12 Bussmann KTK-5
TR1 Type Soft Charge
6072 Littelfuse KLK-15 Littelfuse KL K-D-12 (1X) Bussmann KT K-5 6102 Littelfuse KLK-15 Littelfuse KL K-D-12 (1X) Bussmann KT K-5 6122 Littelfuse KLK-15 Littelfuse KL K-D-12 (1X) Bussmann KT K-5 6150 Littelfuse KLK-30 Littelfuse KL K-D-12 (1X) Bussmann KT K-5 6175 Littelfuse KLK-30 Littelfuse KL K-D-12 (2X) Bussmann KT K-5 6225 Littelfuse KLK-30 Littelfuse KL K-D-12 (2X) Bussmann KT K-5 6275 Littelfuse KLK-30 Littelfuse KL K-D-12 (2X) Bussmann KT K-5
TR1 Type Soft Charge
6350 Littelfuse KLK-9 Littelfuse KLK-15 Bussmann KTK-5 6400 Littelfuse KLK-9 Littelfuse KLK-15 Bussmann KTK-5 6500 Littelfuse KLK-9 Littelfuse KLK-15 Bussmann KTK-5 6550 Littelfuse KLK-9 Littelfuse KLK-15 Bussmann KTK-5
TR1 Type
6152 Bussmann
6172 Bussmann
6222 Bussmann
6272 Bussmann
6352 Bussmann
(3X)
Fuse (3X)
Fuse (3X)
Soft Charge
Fuse (3 phase)
FWH20A6F
FWH20A6F
FWH20A6F
FWH20A6F
FWH20A6F
200 – 240 VAC
Soft Charge Resistor
Fuse (1X)
380 – 460 VAC
Soft Charge Resistor
Fuse (1X or 2X)
Line Snubber
Fuse (3X)
Fan Fuse (1 phase)
Bussmann KTK-4 Bussmann KTK-4
Bussmann KTK-4 Bussmann KTK-4
Bussmann KTK-4 Bussmann KTK-4
Bussmann KTK-4 Bussmann KTK-4
Bussmann KTK-4 Bussmann KTK-4
Power Car d
Fuse (1X)
Power Car d
Fuse (1X)
Interface Board
Fuse (1X)
Power Card/SM PS Fuse (1 phase)
AC Line
Motor
L1 L2 L3 91 92 93
U V W PE (ground)
96 97 98 99
AUX RELAY 01 02 03
DC Bus
(-) DC (+) DC
88 89
CAUTION
Drive Failure!
Do not connect input power to drive output motor terminals. Connecting input power to motor terminals will result in drive failure when power is applied.
On drives with an auxiliary enclosure, some or all of the power connections at the drive will be factory made. Custom input and output terminals may be inside the auxiliary enclosure. See the drawings supplied with the drive for details on custom terminal blocks and conduit entry locations for the auxiliary enclosure.
Input Power Delay
To ensure that the input surge suppression circuitry performs correctly, a time delay between successive applications of input power must be observed.
The table below shows the minimum time that must be allowed between applications of input power.
Input voltage 380 V 415 V 460 V 600 V W aiting time 48 sec 65 s ec 89 sec 133 sec
11
Page 12
Power Connections
A
A
1. Make all power connections with 75o C rated copper wiring.
2. Conduit entry must be from the bottom on all drives. Conduit entries are provided on smaller drives. For drives with auxiliary enclosures, refer to the dimensional drawings provided for conduit entry locations.
3. To meet UL requirements, install the metalgrounding plate in all drives that have a plastic bottom. Install the grounding plate just above the plastic bottom. Ground the metal plate to the chassis and ground the conduit to the metal plate.
4. The conduit entries provide strain relief for the wires in drives mounted in NEMA 1 or NEMA 12 enclosures. With chassis mounted drives, the power and control wires must have strain relief supplied by the installer. D provide strain relief.
Model
6002 6.3 10 6003 7.3 10 6004 10.4 10 6006 16.8 10 6008 23.8 6 6011 32.2 6 6016 48.3 6 6022 61.9 2 6027 78.2 2 6032 92.0 0 6042 117.0 1/0 6052 139.2 3/0 6062 165.5 4/0
200 - 208 VAC Input Current/Wire Gage
Model
6002 2.8 10 6003 3.8 10 6004 5.3 10 6006 9.1 10 6008 12.2 10 6011 15 10 6016 24 6 6022 32.0 6 6027 37.5 6 6032 44 6 6042 60 2 6052 72 2 6062 89 2 6072 104 1/0 6102 145 2/0 6122 174 3/0 6150 206 2x1/0 6152 206 2x1/0 6172 256 2x1/0 6175 256 2x1/0 6222 317 2x3/0 6225 317 2x3/0 6272 366 2x4/0 6275 366 2x4/0 6350 467 3x1/0 6352 467 3x1/0 6400 584 3x3/0 6500 648 3x3/0 6550 734 3x4/0
380 VAC Input Current/Wire Gage
O NOT rely on the terminal blocks to
Drive Input
Current
Drive Input
Current
Maximum
AWG
Maximum
WG
Current ratings are in Amps
!
Induced Voltage!
Run output motor cables from multiple drives separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately could result in death or serious injury.
Drive Input
Model
6002 2.5 10 6003 3.4 10 6004 4.8 10 6006 8.3 10 6008 10.6 10 6011 14 10 6016 21 6 6022 27.6 6 6027 34 6 6032 41 6 6042 53 2 6052 64 2 6062 77 2 6072 104 1/0 6102 128 2/0 6122 157 3/0 6150 185 2x1/0 6152 185 2x1/0 6172 236 2x1/0 6175 236 2x1/0 6222 304 2x3/0 6225 304 2x3/0 6272 356 2x4/0 6275 356 2x4/0 6350 431 3x1/0 6352 431 3x1/0 6400 526 3x3/0 6500 581 3x3/0 6550 668 3x4/0
Current
460 VAC Input Current/Wire Gage
Model
Drive Input
Current
6002 2.3 10 6003 2.6 10 6004 3.8 10 6006 5.9 10 6008 8.8 10 6011 11.1 10 6016 16.6 6 6022 21.4 6 6027 26.3 6 6032 31.2 2 6042 39.9 2 6052 50.6 1/0 6062 60.4 1/0 6072 75 1/0 6100 92.4 3/0 6125 117 3/0 6150 134 4/0 6175 179 2 x 4/0 6225 226 2 x 4/0 6275 270 2 x 4/0
550 - 600 VAC Input Current/Wire Gage
Maximum
WG
Maximum
AWG
12
All current ratings are in amps.
Page 13
NOTE
Run input power, motor wiring and control wiring in three separate metallic conduits or raceways for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum drive and associated equipment performance.
!
Grounding Hazard! For operator safety, it is important to ground drive properly. Follow the grounding guidelines provided. Failure to follow grounding guidlines could result in death or serious injury.
Input Power Connection
For drives with no auxiliary enclosure, connect input power to drive terminals L1, L2, and L3, (terminal numbers 91, 92, and 93). If an auxiliary enclosure is provided, input power connections are made in the auxiliary enclosure. Refer to the connection diagrams shipped with the drive.
Size wiring to the input current of the drive as shown in the tables below. Maximum AWG wire size is also provided. Local codes must be complied with for cable sizes.
Motor Wiring Connection
For drives with no auxiliary enclosure, connect the motor to drive terminals U, V, and W (terminal numbers 96, 97, and 98). Terminal 99 is earth ground. If an auxiliary enclosure is provided, refer to the connection diagrams shipped with the drive. Ground the shield on the motor wire, if used, at both the drive and the motor.
Grounding
Ground the drive properly. Use a ground wire at least 7 AWG (10mm2). Connect the ground wire directly to a reliable earth ground. Do not use the conduit connecting to the drive as a replacement for a ground wire. Do not ground one drive to another in a daisy chain fashion.
Electronic Thermal Protection
The electronicthermal relay is UL approved for single motor thermal protection as long as the following is complied with:
1. Parameter 117, Thermal Protection, is set to ETR TRIP.
2. Parameter 105, Motor Current, is set for the full-load nameplate motor current.
13
Page 14
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the motor(s) and ground to the values shown in the tables below. Drives with 200 to 240 volts of 88 amps and less, and drives with 380 to 600 volts of 90 amps and less, have removable terminal blocks with screws. Larger drives have fixed bolts. (See the drive nameplate for maximum drive output current.)
Max. Drive
Output Current
6.9 5 (0.6)
7.8 5 (0.6) 11 5 (0.6)
17.5 5 (0.6) 26 17 (1.8) 33 17 (1.8)
48.3 28 (3.0)
62.1 28 (3.0)
78.2 28 (3.0) 92 35 (4.0)
115 100 (11.3) 143 100 (11.3) 170 100 (11.3)
Tor que
in-lbs (Nm)
200 to 240 VAC Terminal Tightening Torque
Max. Drive
Output Current
Torque
in-lbs (Nm)
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 10 5 (0.6) 147 100 (11.3)
16 5 (0.6) 177 100 (11.3) 24 17 (1.8) 212 100 (11.3) 32 17 (1.8) 260 100 (11.3)
37.5 17 (1.8) 315 100 (11.3) 44 28 (3.0) 368 100 (11.3) 61 28 (3.0) 487 372 (42.0) 73 28 (3.0) 594 372 (42.0) 90 28 (3.0) 649 372 (42.0)
106 100 (11.3) 746 372 (42.0)
380 to 460 VAC Terminal Tightening Torque
Max. Drive
Output Current
to 11 5 (0.6)
27 17 (1.8) 41 28 (3.0)
77 35 (4.0) 144 100 (11.3) 289 100 (11.3)
Torque
in-lbs (Nm )
All current ratings are in amps.
Terminal Tightening Torque for Optional Auxiliary Control Panels
For drives with an optional auxiliary control panel enclosure, tighten terminal connections in accordance with the tables provided.
200-208 V Hp
Rat ing
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
Overload
Rel ay
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
17 (1.9) 15 (1.7) 2 2 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
17 (1.9) 35 (4.0) 2 2 (2.5) 7 (.8) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
40 (4.5) 175 (19. 8) 44 (5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
40 (4.5) 175 (19. 8) 44 (5) 18 (2) 18 (2) 120 (13 .6) 120 (13.6) 50 (5.6)
40 (4.5) 175 (19.8) 44 (5) 55 (6 .2) 55 (6.2) 120 (13.6) 275 (30.1) 50 (5.6)
40 (4.5) 175 (19.8) 44 (5) 70 (7 .9) 70 (7.9) 120 (13.6) 275 (30.1) 50 (5.6)
200 (22.6) 275 (30. 1) 27 5 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
200 (22.6) 275 (30. 1) 27 5 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
200 (22.6) 275 (30. 1) 27 5 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30. 1)
In/Out Power
Termina l
CTK Breaker
Ma in Disco
Switch
550 to 600 VAC Terminal Tightening Torque
Drive Di sco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Terminal
200 to 208 VAC Auxiliary Control Panel Tightening Torques
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
14
Page 15
Terminal Tightening Torque for Optional Auxiliary Control Panels (continued)
230-240 V Hp
Rati ng
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
380-460 V Hp
Rating
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
Overload
Rel ay
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 35 (4.0) 45 (5.1)
17 (1.9) 15 (1.7) 22 (2.5) 7 (.8) 7 (.8) 25 (2.8) 45 (5.1) 45 (5.1)
17 (1.9) 35 (4.0) 22 (2.5) 7 (.8) 7 (.8) 45 (5.1) 45 (5.1) 45 (5.1)
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 18 (2) 120 (13.6) 275 (30.1) 50 (5.6)
40 (4.5) 175 (19.8) 275 (30. 1) 70 (7.9 ) 55 (6.2) 275 (31.1 ) 275 (30.1) 50 (5.6)
40 (4.5) 175 (19.8) 275 (30. 1) 375 (42. 4) 70 (7.9) 275 (31.1 ) N/A 50 (5.6)
200 (22.6) 275 (30 .1) 275 ( 30.1) 375 (42. 4) 375 (42. 4) 275 (31.1 ) N/ A 50 (5. 6)
200 (22.6) 275 (30 .1) 275 ( 30.1) 375 (42. 4) 375 (42. 4) 450 (50.8 ) N/ A 275 (30.1)
In/Out Powe r
Termina l
CTK Bre aker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Terminal
230 to 240 VAC Auxiliary Control Panel Tightening Torques
Overload
Rel ay
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 25 ( 2.8) 45 (5.1)
17 (1.9 ) 15 (1 .7) 22 (2.5) 7 (.8) 7 (.8) 25 (2. 8) 45 ( 5.1) 45 (5.1)
17 (1.9 ) 35 (4 .0) 22 (2.5) 7 (.8) 7 (.8) 45 (5. 1) 45 ( 5.1) 45 (5.1)
17 (1.9) 35 (4. 0) 22 (2. 5) 18 ( 2) 7 (.8) 45 (5.1) 45 (5. 1) 45 (5. 1)
40 (4.5) 35 (4. 0) 22 (2. 5) 18 ( 2) 1 8 (2) 45 (5.1) 45 (5. 1) 50 (5. 6)
40 (4.5) 17 5 (19.8) 44 (5) 18 (2) 18 (2) 45 (5. 1) 120 (13. 6) 50 (5.6)
40 (4.5) 17 5 (19.8) 44 (5) 55 (6. 2) 18 (2) 120 (13. 6) 120 (13. 6) 50 (5.6)
40 (4.5 ) 175 (1 9.8) 44 (5) 70 (7. 9) 55 (6.2) 120 (13 .6) 275 (30.1) 50 (5.6)
40 (4.5) 17 5 (19.8) 275 (30 .1) 375 (42. 4) 70 (7. 9) 275 (31.1 ) N/ A 50 (5. 6)
200 (22.6) 27 5 (3 0.1) 27 5 (30 .1) 37 5 (42.4) 375 (42 .4) 275 (31 .1) N/A 50 (5. 6)
200 (22.6) 27 5 (3 0.1) 27 5 (30 .1) 37 5 (42.4) 375 (42 .4) 275 (31 .1) N/A 275 (30.1)
200 (22. 6) 275 (3 0.1) 275 (30.1) 37 5 (42.4) 375 (42.4) 450 (50.8 ) 500 (56. 5) 275 (30. 1)
200 (22. 6) 375 (4 2.4) 275 (30.1) 50 0 (56.8) 500 (56.8) 450 (50.8 ) 500 (56. 5) 275 (30. 1)
375 (42. 4) 375 (4 2.4) 275 (30.1) 50 0 (56.8) 500 (56.8) 450 (50.8 ) 275 (30. 1) 275 (30. 1)
375 (42. 4) 375 (4 2.4) 275 (30.1) 50 0 (56.8) 500 (56.8) 375 (42.4 ) 375 (42. 4) 275 (30. 1)
In/Out Po wer
Termin al
CTK Breaker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Terminal
Ground
Ground
380 to 460 VAC Auxiliary Control Panel Tightening Torques
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
15
Page 16
Terminal Tightening Torque for Optional Auxiliary Control Panels (continued)
550-600 V Hp
Rating
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
Overload
Relay
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 25 (2.8 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 2 5 (2.8) 45 (5.1 ) 45 (5. 1)
17 (1.9) 15 (1.7) 50 (5.6) 7 (.8) 7 (. 8) 4 5 (5.1) 45 (5.1 ) 45 (5. 1)
17 (1.9) 35 (4.0) 50 (5.6) 7 (.8) 7 (. 8) 4 5 (5.1) 45 (5.1 ) 45 (5. 1)
17 (1.9) 35 (4. 0) 50 (5. 6) 18 (2) 18 (2) 45 (5. 1) 120 (13. 6) 45 (5. 1)
40 (4.5) 35 (4. 0) 50 (5. 6) 18 (2) 18 (2) 45 (5. 1) 120 (13. 6) 50 (5. 6)
40 (4.5) 175 (19.8) 50 (5. 6) 70 (7. 9) 55 (6. 2) 120 (13. 6) 120 (13. 6) 50 (5.6)
40 (4.5) 175 (19.8) 50 (5. 6) 70 (7. 9) 55 (6. 2) 120 (13. 6) 120 (13. 6) 50 (5.6)
40 (4.5) 175 (19.8) 275 (30. 1) 70 (7. 9) 55 (6. 2) 120 (13. 6) 120 (1 3.6) 50 (5. 6)
40 (4.5) 175 (19.8) 275 (30. 1) 375 (42 .4) 70 (7. 9) 275 (31. 1) 275 (3 0.1) 50 (5.6)
200 (22.6) 275 (30.1) 275 (30.1) 375 (42. 4) 375 (42. 4) 275 (31. 1) N /A 50 (5. 6)
200 (22.6) 275 (30.1) 275 (30.1) 375 (42. 4) 375 (42. 4) 275 (31. 1) N /A 275 (30. 1)
200 (22.6) 275 (30.1) 275 (30.1) 375 (42. 4) 375 (42. 4) 450 (50. 8) N /A 275 (30. 1)
375 (42.4) 375 (42.4) 275 (30.1) 500 (56. 8) 500 (56. 8) 450 (50. 8) 500 (56. 5) 275 (30. 1)
375 (42.4) 375 (42.4) 275 (30.1) 500 (56. 8) 500 (56. 8) 375 (42. 4) 275 (30. 1) 275 (30. 1)
In/Ou t P ower
Terminal
CTK Bre aker
Main Disco
Switch
Drive Disco
Switch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Term inal
550 to 600 VAC Auxiliary Control Panel Tightening Torques
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
16
Page 17
Multiple Motors
The TR1 can control several motors at once, all changing speed together. The sum of the nameplate currents of all the motors must not exceed the current rating of the drive.
External DC Bus Connection
Terminals 88 and 89 access the DC bus of the drive. They can provide DC backup power for the drive or to connect to a 12-pulse input rectifier.
CAUTION
Motor Damage!
When multiple motors are used, the drive electronic thermal relay cannot be used to provide individual motor protection. A separate motor overload must be supplied for each motor. Failure to provide individual motor protection when multiple motors are used could result in motor or equipment damage.
If the multiple motors are of significantly different sizes, starting problems may occur. This is because the higher electrical resistance of smaller motors will require more start voltage than larger motors.
NOTE Automatic†Motor Adaptation and Automatic Energy Optimization cannot be used for multiple motor installations.
WARNING
!
Hazardous Voltage!
Terminals 88 and 89 will be at approximately 150% of line voltage and remain at high voltage for up to 30 minutes after power has been removed from the drive. To be sure that capacitors have fully discharged, wait 14 minutes for 208 V and 480 V units and 30 minutes for 600 V units after power has been removed before touching terminals 88 and 89. Failure to wait for capacitors to fully discharge before touching DC bus terminals could result in death or serious injury.
CAUTION
Equipment Damage!
Do not connect anything to terminals 88 and 89 without first consulting with Trane. Failure consult with Trane could result in motor or equipment damage.
High Voltage Form C Relay
The connections for the high-voltage relay are terminals 01, 02, 03. The high-voltage relay is programmed in parameter 323, Relay
Output 1.
1+3 normally closed, 1+2 normally open
Max. 240 VAC, 2 Amp Min. 24 VDC, 10 mA or
24 VAC, 100 mA Max. wire gage: 10 AWG (4 mm Terminal Torque: 5 in-lbs ( 0.5 - 0.6 Nm)
2
)
17
Page 18
Control Connections
All terminals for the low voltage control wires are located under the protective cover below the keypad. Remove the cover with a screwdriver or other pointed object as shown bellow.
Drive Inputs and Outputs
The drive operates by receiving control signals. Control input gets to the drive in three possible ways. One way is from input signals through the wiring connected to the drive control terminals. The drive control terminals are located below the LCP keypad.
Another control source is through serial communication from a serial bus. A serial communication protocol supplies commands and references to the drive and reads status and data from the drive. The serial bus connects to the drive through the RS-485 serial port. Use of serial communication may require installation of a corresponding option card.
A building management system, remote sensors, a speed command from associated equipment, or a PLC (programmable logic controller) are examples of possible remote drive controllers.
The third way for drive control input is through the keypad on the front of the drive when operating in local (hand) mode. These inputs include start, stop, reset, and speed reference.
Electrical Installation, Control Terminals
Torque control terminals to 5 in-lbs (0.5-0.6 N-m) Max. wire size: 16 AWG (1.5mm
The diagram below shows the location of the control terminals. The programming section of the manual covers the programmable terminals in greater depth.
2
)
Input Signals
The drive can receive two types of remote input signals: digital or analog. Digital inputs are wired to terminals 16, 17, 18, 19, 20 (common), 27, 29, 32, and 33. Analog inputs are wired to terminals 53, 54, and 55 (common), or terminal 60.
Analog signals can be either voltage (0 to +10 VDC) connected to terminals 53 and 54, or current (0 to 20 mA or 4 to 20 mA) connected to terminal 60. Analog signals can be varied like dialing a rheostat up and down. The drive can be programmed to increase or decrease output in relation to the amount of current or voltage. For example, a sensor may supply a variable current. The drive output, in turn, regulates the speed of the motor connected to the drive in response to that analog signal.
Digital signals are a simple binary 0 or 1 which, in effect, act as a switch. Digital signals are controlled by a 0 to 24 VDC signal. A voltage signal lower than 5 VDC is a logic 0. A voltage higher than 10 VDC is a logic 1. Zero is open, one is close. Digital inputs to the drive are switched commands such as start, stop, reverse, coast, reset, and so on. (Do not confuse these digital inputs with serial communication formats where digital bytes are grouped into communication words and protocols.)
18
The RS-485 serial communication connector is wired to terminals (+) 68 and (-) 69. Terminal 61 is common and may be used for terminating shields only when the control cable is run between VLT drives, not between drives and other devices.
Page 19
Output Signals
The drive also produces output signals that are carried through either the RS-485 serial bus or terminals 42 and 45. Output terminals 42 and 45 operate in the same manner as the inputs. These terminals can be programmed for either a variable analog signal in mA or a digital signal (0 or 1) in 24 VDC. In addition, the terminals can provide a pulse reference of 0 to 32,000 pulses. Output analog signals generally report the drive frequency, current, torque and so on to an external controller or system. Digital outputs can be control signals used to open or close a damper, for example, or send a start or stop command to auxiliary equipment.
Additional terminals are 01, 02, and 03, which are a Form C relay output. Terminals 04 and 05 are a 1 A low voltage relay output.
Terminals 12 and 13 provide 24 VDC low voltage power, often used to supply power to the digital input terminals (16-33). Those terminals must be supplied with power from either terminal 12 or 13, or from a customer supplied external 24 VDC power source. Improperly connected control wiring can be the cause of a motor not operating or the drive not responding to a remote input.
Programming Control Terminals
Control terminals must be programmed. Each terminal has specific functions it is capable of performing and a numbered parameter associated with it. See the table below for associated parameter numbers. The setting selected in the parameter enables the function of the terminal.
It is important to confirm that the control terminal is programmed for the correct function. See Control Panel for details on operator interface and changing parameters.
In addition, the input terminal must be receiving a signal. Confirm that the control and power sources are wired to the terminal. Then check the signal.
Control Terminal Functions
The following is a description of the functions of the control terminals. Many of these terminals have multiple functions determined by parameter settings.
Terminal No. Function
01, 02, 03 FormC relay output. Maximum 240 VAC, 2 A.
Minimum 24 VDC, 10 mA or 24 VAC, 100 mA.
(Location of Form C relay output varies with unit
type. See connection diagram with unit for
location.)
04, 05 30 VAC, 42.5 VDC, 1 A relay output can be used
for indicating status and warnings.
12, 13 Voltage supply to digital inputs and external
transducers. For the 24VDC to be used for digital
inputs, switch 4 on the control card must be closed,
position on. The maximum output current is 200 mA.
16 - 33 Digital inputs. R
>10V = logical 1. See parameters 300 through
307, Digital Inputs.
20 Common for digital inputs.
39 Common for analog and digital outputs.
42, 45 Analog and digital outputs for indicating frequency,
reference, current and torque. The analog signal
is 0 to 20 mA, or 4 to 20 mA at a maximum of
500Ω. The digital signal is 24VDC at a minimum
of 600. See parameters 319-322, Analog/digital
Outputs.
50 10 VDC, 17mA maximum analog supply voltage to
potentiometer and thermistor.
=2kohm. <5V = logical 0,
Signals can be checked in two ways. Relay status can be selected in the display using the [DISPLAY MODE] key (see Display Modes), or a voltmeter may be used to check for voltage at the control terminal.
In summary, for proper drive functioning, the drive control terminals must be:
1. wired properly
2. programmed correctly for the intended function
3. powered
4. receiving a signal
Term 16 17 18 19 27 29 32 33 53 54 60 42 45 1-3 4-5 Para 300 301 302 303 304 305 306 307 308 311 314 319 321 323 326
Control terminals must be programmed. Each terminal has specific functions it is capable of performing and a numbered parameter associated with it. The setting selected in the parameter enables the function of the terminal.
53, 54 0 to 10 VDC voltage input, R = 10 kΩ.
55 Common for analog inputs. This common is
isolated from the common of all other power
supplies. If, for example, the drives 24 VDC
power supply is used to power an external
transducer which provides an analog input signal,
terminal 55 must be wired to terminal 39.
Control Terminals and Associated Parameter
19
Page 20
Control Terminal Functions (continued)
Terminal No. Function
60 0 to 20 mA or 4 to 20 mA, analog current input,
R=188 . See parameters 314 through 316.
61 Shield for serial communication.
68, 69 RS-485 interface and serial communication. When
the drive is connected to an RS-485 serial communication bus, DIP switch settings on the control card may have to be reset. See Dip Switches 1 through 4 in this manual.
20
Electronic Control Terminals
Page 21
Typical Control Connections
Shown below are typical interfaces between the TR1 and other components in an HVAC system. The terminal numbers and the functions of the terminals are identical on all TR1s. An optional relay card, not shown, can provide four additional Form C output relays. The RS-485 connections allow direct communication through the drives built-in serial communication protocols.
Typical TR1 Wiring
3 Phase
Power
Input
External
DC Bus
Connection
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
Preset Speed*
91 (L1)
92 (L2)
93 (L3)
99 (PE)
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
60 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN)
29 (D IN)
SW4
Switch Mode
Power Supply
10 V DC
17 mA
+ -
EIA-485
Interface
24 V DC
200 mA
+ -
5 V
SW2 SW3
(COM EIA-485) 61
(U) 96
(V) 97
(W) 98
(PE) 95
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
(RELAY) 04
(RELAY) 05
(COM A OUT) 39
(A OUT) 42
0 V
(A OUT) 45
(P EIA-485) 68
(N EIA-485) 69
Motor
Fault Indication* 240 V AC, 2 A
Run Indication* 30 V AC, 1 A
Output Current Indication* 4 - 20 mA
Output Speed Indication* 4 - 20 mA
+
EIA-485
-
Setup Select*
Setup Select*
32 (D IN)
33 (D IN)
* The operation of all control inputs and outputs is programmable.
* Typical terminal functions are shown.
21
Page 22
NOTE
Run input power, motor wiring and control wiring in three separate metallic conduits or raceways for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum drive and associated equipment performance.
Electrical Installation, Control Wiring
Torque: 5 - 6 in-lbs Screw size: M3
Shielded control wires are recommended. To reduce interference from electrical noise, ground the cable shield at a cable clamp, as shown below, at both ends. Connect the shield to the grounded clamp. Very long control wires may create 60 Hz interference. To resolve this, connect one end of the shield to earth with a 0.1µF capacitor, keeping the leads as short as possible. If interference persists, disconnect the grounded shield connection at the end opposite to the drive.
DIP Switches 1 through 4
DIP switches are located on the control card.
They are used for serial communication and the common of digital inputs 16 through 33. The switch positions shown are the factory settings.
Sw itc h 1 i s no t used .
Switches 2 and 3 are used for terminating serial communication. On the first and last drive in a multiple device network, or on the only drive of a single drive network, switches 2 and 3 must be ON (the default setting). On all other drives in a multiple device network, set switches 2 and 3 to OFF.
Switch 4 separates the common for the internal 24 VDC supply from the common of the external 24 VDC supply. Normally this switch is ON and the power supply is present at terminals 12 and 13. Set Switch 4 to the OFF position when an external 24 VDC supply is used.
Ground Leakage Current
It is normal for there to be some leakage current from the drive to earth ground. Paths of current leakage are shown on the drawing below. The leakage current will exceed 3.5 mA.
22
Paths of Normal Current Leakage to Ground
Page 23
Galvanic Isolation
Galvanic isolation offers protection from electric shock. All control terminals of all TR1 drives, and terminals 1 through 3 of the relay output, offer galvanic isolation. The galvanic isolation in the TR1 conforms to the European standard EN 50178. (See figure below.)
The components that make up the galvanic isolation are:
1. Power supply, including signal isolation.
2. Gate drive for the IGBTs, the trigger transformers and opto­couplers.
3. The output current Hall effect transducers.
Galvanic Isolation
Extra Safety Protection
Residual Current Device (RCD) relays for ground fault protection, or multiple protective grounding, can be used as extra safety protection, provided that local safety regulations are complied with. In case of a grounding fault, the fault current may contain a DC component. If RCD relays, also known as Earth Leakage Circuit Breakers (ELCB), are used, they may be suitable for protection of 3-phase equipment with a bridge rectifier and for a brief current surge at power-up.
Electrical Noise
In general, electrical noise can be divided into two forms: wire-borne electromagnetic interference (EMI), and radiating radio frequency interference (RFI).
Using shielded motor cables reduces RFI but increases EMI. This is because shielded wires have a greater capacitance than unshielded wires. Unshielded input power connections to the drive generate more noise in the radio frequency range on the AC line. The shield reduces the radiated noise, but increases the low-frequency electromagnetic noise on the AC line. But, since the noise current is taken back to the unit through the shield, only a small electromagnetic field is generated from shielded motor wires.
With an EMI filter, the noise level on the AC line will be reduced to about the same level for shielded and unshielded wires alike.
Connect the motor wiring shield, if used, in the enclosure of the drive as well as at the motor. Use shield brackets to avoid pigtail shield ends. Even short pigtails increase the shields impedance at higher frequencies, which reduces the shields effect and increases the noise produced.
It is generally easier and less complicated to use unshielded motor wires than shielded cables. If unshielded wires are used, the RFI will be greater. But, since the strength of the radiated signal decreases with distance from the signal source, radiated noise is generally not a problem.
To reduce the noise level from the total system (drive + installation) make the motor wiring as short as possible.
Provide separate conduits, or raceways, for power, motor and control wiring to provide the greatest immunity from distortion.
Since leakage current is greater than 3.5 mA, reinforced grounding must be provided if compliance with EN 50178 is required. The relays must be suitable to meet the following requirements:
1) protecting equipment with a DC content (Din VDE 0664) in the fault current (3-phase rectifier)
2) power-up with short pulse-shaped charging current to ground
3) high leakage currents
RCD fault relays type B comply with these requirements according to the norm IEC 755-2.
23
Page 24
Application Control Connection Examples Two-wire Start/Stop
In Auto mode, closing the contact to terminal 18 will make the drive run. In any mode, opening the safety interlock contact to terminal 27 will stop the drive.
Set Parameter 302 to Start. Set Parameter 304 to Safety Interlock.
Digital Speed Up/down
Closing the switch to terminal 32 will make the drive accelerate. Closing the switch to terminal 33 will make the drive decelerate.
Run Permissive
After receiving a run command, the drive will apply power to the damper motor and wait until it receives permission via the switch that is connected to terminal 16.
Set Parameter 300 to Run Permissive. Set Parameter 302 to Start. Set Parameter 304 to External Fault. Set Parameter 323 to Start Signal Applied.
Two Feedback Signals
The drive processes two independent feedback signals during closed loop operation. It can respond to the sum, difference, average, minimum or maximum of these signals.
Set Parameter 306 to Speed up. Set Parameter 307 to Speed down. Set Parameter 305 to Freeze reference.
Potentiometer Reference
A manual potentiometer is used as a input reference for the drive.
Set Parameter 308, Terminal 53, Analog Input Voltage, to Reference. Set Parameter 309, Terminal 53, Min. Scaling, to 0 V. Set Parameter 310, Terminal 53, Max. Scaling, to 10 V.
Set Parameter 308 to Feedback. Set Parameter 311 to Feedback Set Parameter 417 for the desired operation.
Transmitter Connection
The drives internal 24 VDC power supply is used to power an external 4 to 20 mA transducer.
Set Parameter 314, Terminal 60, Analog Input Current, to correspond to the purpose of the 4 to 20mA signal. Set Parameter 315, Terminal 60, Min. Scaling, to 4 mA Set Parameter 316, Terminal 60, Max. Scaling, to 20mA.
Because the commons of the +24 VDC power supply and the input reference follower have separate circuit commons, it is necessary to connect a jumper between terminals 39 and 55.
24
Page 25
Control Panel
The Local Control Panel (LCP), normally mounted on the front of the drive, is a complete interface for programming and operating the drive. The control panel can be removed from the drive and installed up to 10 feet (3 meters) from the drive by using a remote mounting kit.
The control panel has five functions:
1. Display
2. Keys for changing the display
3. Keys for changing programming parameters
4. Indicator lamps
5. Keys for controlling drive operation
The LCP uses a four-line, alpha-numeric, back-lit, LCD display. The display can show four operating data values and three operating condition values continuously. During programming, all the information required for quick, effective parameter setup of the drive will be displayed. As a supplement to the display, there are three indicator lamps for power on (ON), warning (WARNING) and alarm (ALARM).
All drive parameters can be changed from the control panel, unless this ability has been locked out by setting parameter 016, Lock for Data Change, to Locked, or by a digital input to terminals 16 through 33. See the related parameters for more information.
Keys for Parameter Changes
The keys are divided into groups by function. The keys between the display and indicator lamps are used for parameter setup, selecting the display indication during normal operation and controlling the drive speed during local speed control operation. The keys below the indicator lamps are used for Start/Stop control and selection of the operating site.
The DISPLAY MODE key is used to change the mode of the display or to return to the Display Mode from either the Quick Menu or the Extend Menu mode.
The QUICK MENU key gives access to the parameters available for the Quick Menu setup. Parameters in this menu are the 12 most important setup parameters for the drive.
The EXTEND MENU key gives access to all parameters.
The CHANGE DATA key is used for changing the value of a parameter selected either in the Extend Menu or the Quick Menu mode. The desired parameter is first selected. Then the CHANGE DATA key is pressed to enable the editing of the parameter. The underline in the display will move under the parameters value to show that it is being edited.
The CANCEL key is used if a change of the selected parameter is not to be carried out.
The OK key is used for confirming a change of the parameter selected.
25
Page 26
The + and - keys are used to scroll through parameters and to change the value of a chosen parameter. These keys are also used to change the local reference. In Display Mode, these keys are used to switch between readouts.
The v and w keys are used to select a parameter group and also to move the cursor to the desired digit when changing numerical values.
Indicator Lamps
At the bottom of the control panel is a red alarm LED, a yellow warning LED, and a green poweron LED.
AUTO START is used if the drive is to be started via the control terminals and/or serial communication. When a remote start signal is active, the drive will start if the AUTO START key has been pressed.
WARNING
!
Unintended Start!
In Auto Mode, a start signal via digital inputs may cause drive to start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness in Auto Mode could result in death, serious injury, or equipment or property damage.
red yellow green
If certain threshold values are exceeded, the alarm and/or warning lamps will flash and text describing the alarm or warning condition will be displayed.
Local Control
Below the indicator lamps are keys which are used to determine the point of control. Each of these keys can be individually enabled or disabled using parameter 012 through 015. The Hand Start and Auto Start keys will also be disabled if any of the control terminals are programmed for either Remote Hand or Remote Auto.
The HAND START key is used if the drive is to be started from the control panel. Pressing HAND START will give a start command to the drive.
NOTE If a minimum speed is set in parameter 201, Output Frequency, Low Limit, the motor will start and ramp up to this frequency when HAND START is pressed. If drive is running in Auto Mode when the HAND START key is pressed, drive control will switch to Hand Mode.
The OFF/STOP key is used for stopping the connected motor in either the Hand or Auto mode. Enable or disable via parameter 013. If this stop function is activated, the second line in the LCD display will flash.
The RESET key is used for manually resetting the drive after a fault trip (alarm). In this case, the top line of the display will show TRIP (RESET). If the top line of the display shows TRIP (AUTO START), the drive will automatically restart. If the top line of the display shows TRIPLOCK (DISC. MAINS), input power to the drive must be removed before the trip can be reset.
Display Modes
In Auto operational mode, information is displayed in any of three programmable displays. Pressing the DISPLAY MODE key enters display mode and toggles between modes I and II. While in Display mode, the [+] and [-] keys scroll through all data display options. When in Mode II, holding down the DISPLAY MODE key enters Mode III which identifies the units on the top line that the display is showing. Mode IV is available only in local Hand operation and displays the local speed reference.
In normal operation, three data readouts can be shown on the first (top) line of the display. Parameters 008, 009 and 010 select the data displayed on the top line. One readout is available for the large display (line 2). Parameter 007, Large Display Readout, selects the data displayed on line 2. The list on the next page defines the operating data that can be selected for the display readouts.
During an alarm (fault trip), ALARM and the alarm number are shown on the large display. An explanation is given in line 3 or in lines 3 and
4. For a warning, WARN. and the warning number are shown with an explanation in line 3 and/or 4. Both alarms and warnings cause the display to flash.
Line 4 (bottom line), in normal operation, automatically displays the operating status of the drive.
The active setup number and an arrow indicating the direction of motor rotation is shown on the right side of the large display. Clockwise indicates forward and counterclockwise indicates reverse. The arrow body is removed if a stop command is given or if the output frequency falls below 0.01 Hz.
26
Page 27
The table below gives the operating data options for the first and second lines of the display.
Data Item: Unit:
Resulting reference, % % Resulting reference unit chosen in par. 415 Frequency Hz % of maximum output frequency % Motor current A Power kW Power HP Output energy kWh Hours run hours User defined readout unit chosen in par. 006 Setpoint 1 unit chosen in par. 415 Setpoint 2 unit chosen in par. 415 Feedback 1 unit chosen in par. 415 Feedback 2 unit chosen in par. 415 Feedback unit chosen in par. 415 Motor voltage V DC link voltage V Thermal load on motor % Thermal load on TR1 % Input status, digital input binary code Input status, analog terminal 53 V Input status, analog terminal 54 V Input status, analog terminal 60 mA Pulse reference Hz External reference % Heat sink temperature
Display Mode I:
In Display mode I, the drive is in Auto mode with reference and control determined via the control terminals. Following is an example in which the drive is running in setup 1, in Auto mode, with a remote reference, and at an output frequency of 40 Hz.
o
C
Status line (Line 4): Additional automatic displays for the drive status line are shown below. See Status Messages section in this manual for additional information.
80.0% 5.08A 2.15HP
SETUP
40.0Hz
1
AUTO REM. RUNNING
HAND
OFF
LOCAL
STOP
RAMPING JOGGING
. . . .
STAND BY
The left indicator on the status line displays the active control mode of the TR1 drive. AUTO is displayed when control is via the control terminals. HAND indicates that control is local via the keys on the LCP. OFF indicates that the drive ignores all control commands and will not run.
The center part of the status line indicates the reference element that is active. REM. (Remote) means that reference from the control terminals is active, while LOCAL indicates that the reference is determined via the [+] and [-] keys on the control panel.
The last part of line 4 indicates the drive's operational status, for example: RUNNING, STOP, or RUN REQUEST, and so on.
Display Mode II:
This display mode shows three operating data values in the top line programmed via parameters 008, 009, and 010. Pressing the DISPLAY MODE key toggles between Display modes I and II.
The text in line 1, FREQUENCY, describes the meter shown in the large display. Line 2 (large display) shows the current output frequency (40.0 Hz), direction of rotation (reverse arrow), and active setup (1). Line 3 is blank. Line 4 is the status line and the information is automatically generated for display by the drive in response to its operation. It shows that the drive is in auto mode, with a remote reference, and that the motor is running.
FREQUENCY
40.0 Hz
AUTO REMOTE RUN
SETUP
1
100% 7.8A 5.9HP
SETUP
50.0 Hz
1
AUTO REMOTE RUN
27
Page 28
Display Mode III:
Press and hold the [DISPLAY MODE] key while in ModeII. Mode III is visible as long as the key is depressed. The top line changes to identify the data names and units displayed. Lines 2 and 4 are unchanged. When the key is released, the display returns to Mode II.
Changing Numeric Values
If the chosen parameter represents a number value, the flashing digit can be changed by means of the [+]and [-] keys. Position the cursor by using the [<]and [>] keys, then change the data value using the [+] and [-] keys.
REF% CURR.A POW.HP
SETUP
50.0 Hz
1
AUTO REMOTE RUN
Display Mode IV:
This display mode is available when local reference is selected. In this display mode, the speed reference is increased or decreased via +/- keys.
The first line shows the present speed reference. The second line shows the present drive output frequency. The third line show a bar graph of the relative value of the present drive output frequency in relation to the maximum frequency.
USE +/- 56Hz
SETUP
40.0Hz
1
0 ••-----60
FREQUENCY
SETUP
24.2 Hz
1
205 MAX. REFERENCE
000060.000 Hz
The selected digit is indicated by a flashing cursor. The bottom display line gives the data value that will be entered (saved) by pressing the OK button. Use CANCEL to ignore the change.
Changing Functional Values
If the selected parameter is a functional value, the selected text value can be changed by means of the [+] and [-] keys.
MOTOR CURRENT
SETUP
3.90 A
1
210 REFERENCE TYPE SUM
HAND LOCAL RAMPING
Changing Data
Regardless of whether a parameter has been selected under the Quick Menu or the Extend Menu, the procedure for changing data is the same. Pressing the CHANGE DATA key gives access to changing the selected parameter. Line 3 displays the parameter number and title. The underlined function or number flashing in line 4 on the display is subject to change.
The procedure for changing data depends on whether the selected parameter represents a numerical data value or a function.
The functional value flashes until signing off by pressing the OK button. The functional value has then been selected. Use CANCEL to ignore the change.
Changing Numeric Values in a List
A few parameters offer numeric lists of values that can be selected from or changed. This means that if the numeric value is not listed, a value may be entered using the procedure for changing numeric values. This applies to parameter 102, Motor power, parameter 103, Motor voltage, and parameter 104, Motor frequency.
28
Page 29
Quick Menu
The Quick Menu gives access to the 12 most important setup parameters of the drive. After programming the Quick Menu items, the drive will, in many cases, be ready for operation. The Quick Menu
parameters are described in the table below. A detailed description of the functions are given in the Programming section of this manual. The Quick Menu is activated by pressing the QUICK MENU key on the control panel.
Quick Menu Parameter Item Number Name
1 001 Language Selects language used for all displays. 2 102 Motor Power Sets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102, Motor Power, to convert HP to kW. 3 103 Motor Voltage Sets output characteristics of drive based on voltage of motor. 4 104 Motor Frequency Sets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency. 5 105 Motor Current Sets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor. 6 106 Motor Nominal Speed Sets output characteristics of drive based on nominal full load speed of
motor. 7 201 Minimum Frequency Sets minimum controlled frequency at which motor will run. 8 202 Maximum Frequency Sets maximum controlled frequency at which motor will run. 9 206 Ramp Up Time Sets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
10 207 Ramp Down Time Sets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
11 323 Relay 1 Function Sets function of high voltage Form C relay.
12 326 Relay 2 Function Sets function of low voltage Form A relay.
Description
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the following procedure.
1. Press Quick Menu key.
2. Use t and u keys to find parameter group to edit.
3. Use + and - keys to find parameter you chose to edit.
4. Press Change Data key.
5. Use + and - keys to select correct parameter setting. Or, to move to digits within a number, use t and u arrows. Flashing cursor
indicates digit selected to change.
6. Press Cancel key to disregard change, or press OK key to accept change and enter new setting.
Example of Changing Parameter Data
Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change the ramp up time to 100 seconds in accordance with the following procedure.
1. Press Quick Menu key.
2. Press + key until you reach Parameter 206, Ramp Up Time.
3. Press Change Data key.
4. Press t key twice  hundreds digit will flash.
5. Press + key once to change hundreds digit from 0 to 1.
6. Press u ke y to move cur sor to t ens digit.
7. Press - key until 6 counts down to 0 and setting for Ramp Up Time reads 100 s.
8. Press OK key to enter new value into drive controller.
NOTE Programming additional parameter functions available through Extended Menu key is done in accordance with same procedure as described for Quick Menu functions.
29
Page 30
Extended Menu
In some applications, the Quick Menu will not access all additional parameters necessary to set up the drive. To access all parameters, including Quick Menu items, use the Extended Menu. The Extended Menu is enabled by pressing the EXTEND. MENU key. The Programming section of this manual describes in detail all the parameters available through the Extended Menu.
Manual Initialization of Parameters
NOTE Manual initialization using either procedure described below, or in parameter 620, will reset the drive to standard default parameters. Any special application programming performed at the factory, during start-up or thereafter, will be lost. As a backup, upload drive settings into the driveís local control panel (LCP) keypad as described in parameter 004, LCP Copy.
It is possible to reset parameters back to their original default values at once. To reset the drive parameters to their read only default values, first remove power from the drive. Then press and hold the DISPLAY MODE, the CHANGE DATA and the OK keys down simultaneously while reapplying power. Continue to hold down the three keys. Shortly after power is reapplied, the bottom line of the display will read Initialized. After the display stops changing, release the keys. If Initialized did not appear, repeat the procedure.
Uploading Parameters
At any time the present parameters may be copied to the local control panel (LCP). This may be useful when setting up multiple drives. It is also useful when it is desired to return to a previous set of parameters. See parameter 004, LCP Copy, for more information.
Manually initializing the drive using either the procedure described above or parameter 620, Operating Mode, does not change the values uploaded to the local control panel.
These parameters are not reset by manual initialization:
Parameter 600 Operating hours Parameter 601 Hours run Parameter 602 kWh counter Parameter 603 Number of power-ups Parameter 604 Number of overtemperatures Parameter 605 Number of overvoltages
Initialization can also be done using Parameter 620.
30
Page 31
TR1 Series VFD Start-Up
Pre-installation Checks
1. Compare drive model number to what was ordered.
2. Ensure each of following are rated for same voltage:
DrivePower lineMotor
3. Record following motor data:
VoltageFrequencyFull load currentFull load speedPower  convert HP to kW (See conversion table in parameter
102, Motor Power, in this manual.)
4. Ensure that rated drive current is equal to or greater than total full load current.
For multiple motor operations, add up full load current ratings of
all motors.
Drive can be at most one size smaller than motor.If drive rating is less than motor, full motor output cannot be achieved.
5. Check motor wiring:
Any disconnect between drive and motor should be interlocked
to drive safety interlock circuit to avoid unwanted drive trips.
No power factor correction capacitors can be connected between
drive and motor.
Two speed motors must be wired permanently for full speed.Y-start, r-run motors must be wired permanently for run.
Installation Checks
1. Input fusing in power supply for all drives must be provided (see Input Fuses section in this manual).
2. Environmental concerns  for standard NEMA 1 drive:
Clean air supplyDry air (max 95% relative humidity, non-condensing)
o
14
F to 104oF ambient temperature operating range, or as rated
3,300 foot maximum elevation with no derating
3. Mounting
VerticalDrives with heat sink fins exposed in back of unit must be
mounted against a solid surface (see Clearances section in this manual).
Keep any construction dirt out of drive.
4. Wiring
Wire drive in accordance with instructions and diagrams received
with drive.
Separate conduits must be provided to drive for input power,
output power, and control wiring.
Note that safety interlock and remote run/stop circuitry is 115 VAC
for drives with bypasses.
Use knockouts or conduit entry plates. Avoid metal shavings in cabinet.
Protect signal wires from noise.Ground each drive individually.Double check input and output power wiring for correct location.
Setting Up Drive for Motor Start
Enter motor nameplate data into drive through Quick Menu.
1. Parameter 101:
If one motor is connected to drive, set to AEO FUNCTION.If more than one motor connected to drive, set to MULTIPLE
MOTORS. (Parameter 108, MULTIPLE MOTOR STARTING VOLTAGE should be adjusted later to provide reliable starts and minimum starting current.)
2. Parameter 102, MOTOR POWER (in kW) (See conversion table in parameter 102, Motor Power, in this manual.)
3. Parameter 103, MOTOR VOLTAGE
4. Parameter 104, MOTOR FREQUENCY
5. Parameter 105, MOTOR CURRENT
6. Parameter 106, MOTOR SPEED
7. Parameter 107, (optional) select AUTOMATIC MOTOR ADAPTA­TION and run AMA in accordance with procedure in parameter 107, Automatic Motor Adaptation, in this manual.
8. Press HAND START key to initiate operation in local control.
HAND Operational Tests
1. Check motor rotation from drive. If incorrect, disconnect input power from drive and reverse two leads between drive and motor.
2. If a bypass is provided, check motor rotation in bypass mode. If incorrect, disconnect input power from drive and reverse two input power leads.
3. Accelerate motor quickly to full speed and verify operation.
4. Decelerate motor quickly to stop and verify operation.
5. Operate motor over entire speed range while closely checking for resonance.
AUTO Operational Tests
1. Ensure that drive follows run/stop and safety interlock commands from system.
2. Ensure drive follows speed reference, or feedback, from system.
Final Adjustments
1. Use parameters 216 through 220 to reject any resonant points.
2. Lock out keypad functions, as required.
General Troubleshooting
1. Display Messages:
AUTO STARTDrive has tripped off and is in process of
automatically restarting.
TRIPDrive has tripped off. Press RESET to start.TRIP LOCKEDDrive has tripped off. Remove and apply
power before restarting with RESET.
2. Refer to Warnings and Alarms section in this manual.
3. Check tightness of all connections and wires for proper location.
4. Measure input signals.
5. Check drive input and output for balanced voltage and current.
31
Page 32
Programming
Using the ExtendMenu key, it is possible to access to all the parameters for the drive.
Description of Parameters
Parameters are grouped by function. The groups are:
Operation and Display Parameters 001 through 017 Load and Motor Parameters 100 through 117 References and Limits Parameters 200 through 228 Input and Outputs Parameters 300 through 328 Application Functions Parameters 400 through 427 Serial Communication Parameters 500 through 566 Service Functions Parameters 600 through 631 Relay Card Functions Parameters 700 through 711
The numbers shown in the square brackets ([ ]) after the parameter values are used in serial communications to choose the parameter value from a numerical list. They are not shown on the display panel when programming the drive locally. The symbol indicates read­only default factory settings. Special default parameter settings for various Trane TR1 Series VFD applications are noted under Factory Settngs in this manual.
Operation and Display Parameters 000 through 017
This parameter group deals with the display, control keys and other general functions.
001 Language (Language) Value:
English (ENGLISH) [0]
German (DEUTSCH) [1] French (FRANCAIS) [2] Danish (DANSK) [3] Spanish (ESPAÑOL) [4] Italian (ITALIANO) [5] Swedish (SVENSKA) [6] Dutch (NEDERLANDS) [7] Portuguese (PORTUGUESA) [8] Finnish (SUOMI) [9]
Function:
This parameter determines the language used on the display.
Description of choice:
Select the display language.
Setup Configuration and Copying Parameters
The TR1 has four independent parameter setups that can be pro­grammed. Each setup acts independently in controlling the drive. Example applications would be programming different setups for day/night or summer/winter operation. Any of the four setups can be used.
The setup is selected in parameter 002, Active Setup, for programming and operation. Setups are changed manually by switching between active setups in parameter 002. It is also possible to change setups through digital inputs or serial communication by selecting Multi-setup in parameter 002 and providing an external signal.
The number of the active setup selected is shown on the keypad display under Setup in the second line of the display.
A short cut to programming more than one setup is possible by using parameter 003, Setup Copy. This enables copying one setup to another setup. After copying parameter settings from one setup, just those parameters unique to the other setups need be changed.
All setups can be transferred from one TR1 drive to another by using the removable keypad. Parameter 004, LCP Copy, allows this function. First, upload all parameter values to the keypad. The keypad can then be removed and plugged into another TR1 drive where all parameter values can be downloaded. If motor or drive sizes differ, Download Power-independent Parameters can be selected in parameter 004 to omit downloading motor and current dependent data.
002 Active Setup (ACTIVE SETUP) Value:
Factory Setup (FACTORY SETUP) [0]
Setup 1 (SETUP 1) [1]
Setup 2 (SETUP 2) [2] Setup 3 (SETUP 3) [3] Setup 4 (SETUP 4) [4] Multi-setup (MULTI SETUP) [5]
Function:
This parameter defines the setup number that controls the drive.
All parameters can be programmed in four individual parameter setups, Setup 1, Setup 2, Setup 3 and Setup 4.
There is also a pre-programmed, read-only setup, called Factory
Setup.
Description of choice:
The Factory Setup contains the parameter values preset at the factory. This data can be used as a default setup to reset parameters to a known state.
Setups 1 through 4 are four individual setups that can be selected as required.
Multi-setup is used if remote switching between different setups is required. Terminals 16, 17, 29, 32, 33 and the serial communication port can be used for switching between setups.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
32
Page 33
Setup Change Connection Example
004 LCP Copy (LCP COPY) Value:
No copying (NO COPY) [0]
Upload all parameters (UPLOAD ALL PARAMET.) [1] Download all parameters (DOWNLOAD ALL PARAM.) [2] Download power-independent parameters (DOWNLOAD SIZE INDEP.) [3]
Function:
Parameter 004, LCP Copy, is used to copy all parameter setups to or from the Local Control Panel (LCP). This can be used to store a backup copy of all parameters in the LCP or to copy all setups from one drive to another.
Selection of setup using terminals 32 and 33. See the descriptions of parameters 300 through 307. Parameter 306 = Selection of Setup, lsb Parameter 307 = Selection of Setup, msb Parameter 002 = Multi Setup
003 Copying of Setups (Setup Copy) Value:
No copying (NO COPY) [0]
Copy active Setup to Setup 1 (COPY TO SETUP 1) [1] Copy active Setup to Setup 2 (COPY TO SETUP 2) [2] Copy active Setup to Setup 3 (COPY TO SETUP 3) [3] Copy active Setup to Setup 4 (COPY TO SETUP 4) [4] Copy active Setup to all (COPY TO ALL) [5]
Function:
A copy is made from the active setup selected in parameter 002, Active Setup, to the setup or setups selected in parameter 003, Copying of Setups.
NOTE
Copying is only possible when drive is stopped.
Description of choice:
The copying starts when the required copying function has been selected and the OK key has been pressed.
Description of choice:
Select Upload All Parameters if all parameter values are to be copied from the drive to the LCP.
Select Download All Parameters if all parameter values are to be copied from the LCP to the drive on which the control panel has been mounted.
Select Download Power-independent Parameters if only the power- independent parameters are to be downloaded. This allows the parameters from one drive to be easily copied to another drive of a different size. Settings in parameters 102, 103, 104, 105, 106, 215, 221, and 222 are not downloaded using this function.
NOTE
Copying is only possible when drive is stopped.
Setup of User-defined Readout
Parameter 005, Maximum Value of User-defined Readout, and Parameter 006, Unit for User-defined Readout, allow users to design their own readout which can be seen if the User-defined Readout has been selected as one of the displayed meters. The range is set in parameter 005, Maximum Value of User-defined Readout and the unit is determined in parameter 006, Unit for User-defined Readout. The choice of unit determines whether the relationship between the output frequency and the readout is a linear, square or cubed. Units representing rates (RPM, CFM, GPM, etc.) are linear. Units represent­ing pressure (PSI, in. wg., etc.) are square. Units representing power (HP, kW, etc.) are cubed.
The display indicates when copying is in progress.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
33
Page 34
005 Maximum Value of Custom Readout
(CUSTOM READOUT )
Value:
0.01 to 999,999.99 100.000
Function:
This parameter determines the value that the user defined meter will display when the drives output frequency is the value set in parameter 202, Output Frequency High.
Description of choice:
Set the required value for maximum output frequency.
006 Custom Readout
(CUST. READ. UNIT)
Value:
No unit [0] GPM [21]
% [1] gal/s [22]
rpm [2] gal/min [23] ppm [3] gal/h [24] pulse/s [4] lb/s [25] l/s [5] lb/min [26] l/min [6] lb/h [27] l/h [7] CFM [28] kg/s [8] ft3/s [29] kg/min [9] ft3/min [30] kg/h [10] ft3/h [31] m3/s [11] ft3/min [32] m3/min [12] ft/s [3 3] m3/h [13] in wg m/s [14] ft wg
1
mbar
1
bar
1
Pa
1
MPa
1
MWG
2
kW
1
Squared units (pressure)
2
Cubed units (power)
[15] PSI [16] lb/in [17] HP [18] [19] [20]
1
1
1
1
2
[34] [35] [36] [37] [38]
Function:
The value and the unit are shown in display mode whenever Custom Readout has been selected in one of parameters 007 through 010, Display Readout. If flow or speed units are selected, the relationship
between readout and output frequency will be a linear one. If pressure units are selected, the ratio will be square. If power units are selected, the ratio will be cubed.
Description of choice:
Select the required unit for Custom Readout.
007 Large Readout (LARGE READOUT) Value:
None [0] Reference [%] (REFERENCE [%]) [1] Reference [unit] (REFERENCE [UNIT]) [2] Frequency [Hz] (FREQUENCY [HZ]) [3]
Frequency [%] (FREQUENCY [%]) [4]
Motor current [A] (MOTOR CURRENT [A]) [5] Power [kW] (POWER [KW]) [6] Power [HP] (POWER [HP]) [7] Output energy [kWh] (ENERGY [KWH]) [8] Hours run [Hours] (HOURS RUN [h]) [9] Custom readout [unit] (CUSTOM READ [UNITS]) [10] Setpoint 1 [unit] (SETPOINT 1 [UNITS]) [11] Setpoint 2 [unit] (SETPOINT 2 [UNITS]) [12] Feedback 1 (FEEDBACK 1 [UNITS]) [13] Feedback 2 (FEEDBACK 2 [UNITS]) [14] Feedback [unit] (FEEDBACK [UNITS]) [15] Motor voltage [V] (MOTOR VOLTAGE [V]) [16] DC link voltage [V] (DC VOLTAGE [V]) [17] Thermal motor load [%] (THERM.MOTOR LOAD [%]) [18] Thermal drive load [%] (THERM.DRIVE LOAD [%]) [19] Digital input [Binary code] (DIGITAL INPUT [BIN]) [20] Analog input 53 [V] (ANALOG INPUT 53 [V]) [21] Analog input 54 [V] (ANALOG INPUT 54 [V]) [22] Analog input 60 [mA] (ANALOG 60 [mA]) [23] Relay status [Binary code] (RELAY STATUS [BIN]) [24] Pulse reference [Hz] (PULSE REFERENCE [Hz]) [25] External reference [%] (EXT. REFERENCE [%]) [26] Heat sink temp. [oC] (HEATSINK TEMP [oC]) [27] Profibus fault [HEX] (COMM.OPTION WARN [HEX]) [28] Free program array [text] (FREE PROG. ARRAY) [29] Status word (STATUS WORD [HEX]) [30] Control word (CONTROL WORD [HEX]) [31] Alarm word (ALARM WORD [HEX]) [32]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
34
Page 35
Function:
This parameter allows a choice of the data value to be shown in the large display when power is applied to the drive. In Display Mode, the + and - keys change this display when the drive is in operation.
Description of choice:
None can only be selected in parameters 008 through 010, Small Readout, but not in parameter 007, Large Readout.
Reference [%] gives the total of all references as a percentage of parameter 205, Maximum Reference.
Reference [unit] gives the total of all references. This is displayed in Hz in open loop. In closed loop, the reference unit is selected in parameter 415, Process Units.
Frequency [Hz] gives the output frequency of the drive.
Frequency [%] is the output frequency as a percentage of maximum
output frequency in parameter 202, Output Frequency High Limit.
Motor current [A] is the average phase current of the motor.
Power [kW] is the actual power, in kW, delivered to the motor.
Motor voltage [V] is the voltage supplied to the motor.
DC link voltage [V] is the drive DC bus voltage.
Thermal load, motor [%] is the calculated thermal load of the motor.
100% is the cutout limit. See also parameter 117, Motor Thermal Protection.
Thermal drive load [%] is the calculated thermal load of the drive. 100% is the trip point.
Digital input [binary code] is the signal status from the 8 digital inputs (16, 17, 18, 19, 27, 29, 32 and 33). Terminal 16 corresponds to the bit at the far left. (0 = no signal, 1 = connected signal.)
Analog input 53 [V] is the voltage applied to terminal 53.
Analog input 54 [V] is the voltage applied to terminal 54.
Analog input 60 [mA] is the current applied to terminal 60.
Relay status [binary code] displays the open or closed position of
relays 1 through 6 in binary code. Open is 0 and closed 1, read left to right (positions 7 and 8, displayed in parameter 007, are not used.)
Power [HP] is the actual power, in HP, delivered to the motor.
Output energy [kWh] is the energy delivered by the motor since the
latest reset was made using parameter 618, Reset of kWh Counter.
Hours run [hours] is the number of hours that the motor has run since the latest reset was made using parameter 619, Reset of Hours
Run Counter.
Custom readout [-] is a user defined value, calculated on the basis of the present output frequency, as well as the scaling in parameter 005, Maximum Value of User-Defined Readout, and the unit in parameter 006, Custom Readout.
Setpoint 1 [unit] is the setpoint value programmed in parameter 418, Setpoint 1. The unit is selected in parameter 415, Process Units.
Setpoint 2 [unit] is the setpoint value programmed in parameter 419, Setpoint 2. The unit is selected in parameter 415, Process Units.
Feedback 1 [unit] is the value of the feedback signal applied to Terminal 53. The unit is selected in parameter 415, Process Units.
Feedback 2 [unit] is the value of the feedback signal applied to Terminal 54. The unit is selected in parameter 415, Process Units.
Pulse reference [Hz] is the pulse frequency applied to terminal 17 or terminal 29.
External reference [%] is the sum of the external references as a percentage of parameter 205, Maximum Reference.
Heat sink temp. [°C] is the present heat sink temperature of the drive. The trip point is 90 ± 5°C for NEMA 1 units, 80 ± 5°C for NEMA 12.
Profibus fault [HEX] is enabled when the Profibus communication option is installed and the warnings in Profibus parameter 953 is active.
Free program array [text] displays the array of characters pro­grammed in parameters 533, Display Text Line 1 and 534, Display Text Line 2 on lines 1 and 2 of the LCP.
Status word [HEX] displays the drive status word (see parameter 608, Data Log).
Control word [HEX] displays the drive control word (see parameter 609, Data Log).
Alarm word [HEX] displays the drive alarm word.
Feedback [unit] is the total feedback signal using the unit scaling
selected in parameter 413, Minimum Feedback; parameter 414 Maximum Feedback; parameter 415, Process Units; and parameter 417, 2 Feedback Calc.
35
Page 36
008 Small Readout 1
(SMALL READOUT 1)
Value:
Reference, % [1]
011 Unit of Local Reference (UNIT OF LOC REF) Value:
Hz (HZ) [0]
% of output frequency range (%) (% OF FMAX) [1]
Function:
This parameter selects the meter shown on the left display on line 1. Showing three different meters on line 1 is recommended when setting up the PID. This allows tracking how the process reacts to a change of reference.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
009 Small Readout 2
(SMALL READOUT 2)
Value:
Motor current [A] [5]
Function:
This parameter selects the meter shown on the center display on line 1. Showing three different meters on line 1 is recommended when setting up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
010 Small Readout 3
(SMALL READOUT 3)
Value:
Power [HP] [7]
Function:
This parameter selects the meter shown on the right display on line 1. Showing three different meters on line 1 is recommended when setting up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
Function:
This parameter sets the unit that will be displayed in Display Mode IV when the drives speed is being controlled locally.
Description of choice:
Choose the desired unit for local reference.
012 Hand Start on LCP (HAND START BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Hand/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Hand/Start key will be disabled.
013 OFF/STOP on LCP (STOP BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Off/Stop key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Off/Stop key will be disabled.
CAUTION
!
OFF/STOP Key Disabled!
If Disable is selected in parameter 013, the motor cannot be stopped by pressing the OFF/STOP key on the keypad. Use of the Disable option could result in injury or equiment or property damage.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
36
Page 37
014 Auto Start on LCP (AUTO START BTTN) Value
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Auto/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Auto/Start key will be disabled.
P 015 015 Reset on LCP (RESET BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Reset key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Reset key will be inactive.
NOTE Do not disable Reset on LCP in parameter 015 unless a remote reset is available through digital inputs and parameters 300 through 307.
017 Operating State at Power Up
(POWER UP ACTION)
Value:
Auto restart (AUTO RESTART) [0]
OFF/STOP (OFF/STOP) [1]
Function:
Selects auto or manual restart when power is reapplied after an outage occurs to a running drive.
Description of choice:
Auto restart is selected if the drive is to resume operation after a power outage.
OFF/STOP is selected if the drive is to remain stopped after a power outage. To restart, press the Hand/Start or Auto/Start key at the keypad. If HAND START or AUTO START are disabled by parameters 012 and 014, the motor will not be able to restart if OFF STOP is selected in parameter 017.
016 Lock for Data Change (DATA CHANGE LOCK) Value:
Not Locked (NOT LOCKED) [0]
Locked (LOCKED) [1]
Function:
This parameter allows locking out parameter changes at the local control panel.
Description of choice:
If Locked is selected, data modifications in the parameters cannot be made. Parameter changes will be possible through serial communica­tion.
Parameters 007 through 010, Display Readout can be changed at the local control panel.
The local control panel can also be locked or unlocked by a digital input controlled by parameters 300 through 307.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
37
Page 38
Load and Motor Parameters 100 through 118
This parameter group controls output power and other output characteristics of the drive.
For correct operation, motor nameplate data must be entered into parameters 102 through 106 either through the Quick Menu or the Extended Menu. In addition, automatic motor adaptation, DC braking and motor thermal protection can be set by this parameter group.
101 101 Torque Characteristics ( VT CHARACT) Value:
Automatic Energy Optimization
(AEO FUNCTION) [0] Parallelmotors (MULTIPLE MOTORS) [1]
Function:
This parameter configures the drive for single or multiple motor operation.
100 Configuration (CONFIG. MODE) Value:
Open loop (OPEN LOOP) [0]
Closed loop (CLOSED LOOP) [1]
Function:
This parameter is used for selecting closed loop or open loop operation.
Description of choice:
If Open loop is selected, speed control is changed directly by the speed reference signal. Any feedback signal applied to the drive will have no effect on the drives speed.
If Closed loop is selected, the internal process regulator is available to accept feedback signal(s) to provide the desired speed regulation.
NOTE It is important to set parameter 100, Configuration, properly when closed loop operation is required. When open loop is selected, parameters associated with setting up PID controller are not accessible.
The AEO function will automatically and continuously monitor the load and adjust the output voltage to maximize motor and drive efficiency and performance. After the motor reaches the set speed, the AEO function reduces the output voltage to the motor, if the load will allow. When the load is light, the voltage is reduced, as shown in the graph below. This lower voltage reduces motor heating and motor noise, and increases efficiency.
Description of choice:
Select Automatic Energy Optimization (AEO) for all single motor applications. When AEO has been selected, only one motor may be connected to the drive at a time.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
38
Select Parallel motors when more than one motor is connected in parallel to the output. In this case, it is necessary to set a start voltage in parameter 108, Start Voltage of Parallel Motors.
NOTE To optimize AEO for use with motors having more than 4 poles, see parameter 118, Motor
Power Factor.
Page 39
NOTE It is very important that values set in parameters 102, Motor Power, through 106, Rated Motor Speed, correspond accurately to nameplate data of motor. Failure to enter motor nameplate data accurately could result in erratic or less than optimum equipment operation.
102 Motor Power (MOTOR POWER) Value:
0.25 kW (0.33 HP) [25]
0.37 kW (0.5 HP) [37]
0.55 kW (0.75 HP) [55]
0.75 kW (1 HP) [75]
1.1 kW (1.5 HP) [110]
1.5 kW (2 HP) [150]
2.2 kW (3 HP) [220] 3 kW -- [300] 4 kW (5 HP) [400]
5.5 kW (7.5 HP) [550]
7.5 kW (10 HP) [750] 11 kW (15 HP) [1100] 15 kW (20 HP) [1500]
18.5 kW (25 HP) [1850] 22 kW (30 HP) [2200] 30 kW (40 HP) [3000] 37 kW (50 HP) [3700] 45 kW (60 HP) [4500] 55 kW (75 HP) [5500] 75 kW (100 HP) [7500] 90 kW (125 HP) [9000] 110 kW (150 HP) [11000] 132 kW (175 HP) [13200] 160 kW (200 HP) [16000] 200 kW (300 HP) [20000] 250 kW -- [25000] 300 kW -- [30000] 315 kW (350 HP) [31500] 355 kW (450 HP) [35500] 400 kW (500 HP) [40000] 450 kW (600 HP) [50000] Depends on the unit
Function:
Set the power value that corresponds to the nameplate power of the motor. The default setting is the full rating of the drive.
Description of choice:
Select a value that equals the nameplate data on the motor. It is also possible to set any power within the range of the drive.
103 Motor Voltage (MOTOR VOLTAGE) Value:
200 V [200] 208 V [208] 220 V [220] 230 V [230] 240 V [240] 380 V [380] 400 V [400] 415 V [415] 440 V [440] 460 V [460] 480 V [480] 500 V [500] 575 V [575]
Depends on the unit
Function:
Set the rated motor voltage.
Description of choice:
Select a value that equals the nameplate data on the motor. This may be less than the input voltage. It is also possible to set any voltage within the range of the drive.
104 Motor Frequency (MOTOR FREQUENCY) Value:
50 Hz (50 Hz) [50]
60 Hz (60 Hz) [60]
Function:
This is where the rated motor frequency is selected. This is usually the frequency of the power line.
Description of choice:
Select the desired value. It is also possible to set any frequency within the range of the drive.
NOTE Failure to enter motor nameplate data accurately could result in erratic or less than optimum equipment operation. Also, changing values in parameter 102, Motor Power, or parameter 103, Motor Voltage, after motor current has been entered in parameter 105, may automatically change the value in parameter 105.
105 Motor Current (MOTOR CURRENT) Value:
0.01 to drive rating
Set based on motor nameplate.
Function:
The rated motor current in amps is used for setting output current and providing motor thermal protection. It is important to set the motor current to the fullloadcurrent rating (FLA) of the motor.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
Description of choice:
Set a value that equals the nameplate data on the motor.
39
Page 40
NOTE Failure to enter motor nameplate data accurately could result in erratic or less than optimum equipment operation. Changing values in parameter 104, Motor Frequency, after rated motor speed has been entered in parameter 106, may automatically change the value in parameter 106.
NOTE Some motors (such as motors with 6 or more poles) may be unable to run Automatic Adaptation. Limited AMA is a procedure which can be effective in such cases since results measure motors stator and effects of cable length. Multiple motor applications cannot use AMA.
106 Rated Motor Speed (MOTOR NOM. SPEED) Value:
100 through 60000
Depends on parameter 102, Motor Power
Function:
This is where the value is set that corresponds to the rated motor speed shown on the motor nameplate.
Description of choice:
Choose a value that corresponds to the motor nameplate data.
107 Automatic Motor Adaptation, AMA
(AUTO MOTOR ADAPT)
Value:
Optimization disable (NO AMA) [0]
Automatic adaptation (RUN AMA) [1] Limited AMA (RUN LIMITED AMA) [2]
Function:
Automatic Motor Adaptation (AMA) is an advanced procedure that measures electrical characteristics of the motor. This procedure does not cause the motor to run.
AMA optimizes the adjustment of the drive to the motor. This feature is particularly useful when the drive-to-motor cable length is long, and with nonstandard motors or high hp motors. Although it is not necessary to run AMA, it is highly recommended for optimum operation and increases the capability of the Automatic Energy Optimization function selectable in parameter 101, Torque Characteristics.
For the best adjustment of the drive, it is recommended to carry out AMA on a cold motor.
The following must be noted when either AMA function is used:
- Before running AMA, the correct nameplate data for the motor must be entered in parameters 102 through 106.
- Total automatic motor adaptation may take up to 10 minutes.
- Alarms and warnings will be shown in the display if faults occur during motor adaptation.
- AMA can only be carried out if the rated motor current of the motor is at least 35% of the rated output current of the drive.
Description of choice:
Select Automatic Adaptation if the drive is to carry out a complete automatic motor adaptation procedure.
Select Limited AMA if an LC-filter has been placed between the drive and the motor, for a motor with 6 or more poles, or if Automatic
Adaptation was unsuccessful. Some drives may display Automatic Adaptation with LC-filter rather than Limited AMA. The functions are
the same.
Procedure for Automatic Motor Adaptation:
1. Set motor parameters 102 through 106 according to motor nameplate data.
2. Connect 24 VDC from terminal 12, or from external source, to terminal 27.
3. Select either Automatic Adaptation or Limited AMA in parameter 107, Automatic Motor Adaptation.
4. Start drive by pressing Hand Start or connect terminal 18 (start) to terminal 12 and press Auto Start.
To stop automatic adaptation or limited AMA prior to completion:
Press OFF/STOP key.
After a normal sequence is complete, the display reads: AMA STOP
Press RESET key. Drive is now ready for operation.
NOTE Repeated AMA operation may lead to motor heating that could result in an increase of stator resistance. This can reduce test accuracy. Run AMA only on a cool motor.
If an output LC-filter has been connected between the drive and the motor, select Limited AMA. If the complete AMA procedure is desired, remove the LC-filter, run Automatic Adaptation (RUN AMA), and reinstall the filter.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
40
NOTE RESET key must be pressed after AMA is completed to save results to drive.
If there is a fault, the display reads: ALARM 22
1. Check alarms section in this manual for possible causes of alarm.
2. Press RESET key to clear fault.
If there is a warning, the display reads: WARNING (39 through 42)
1. Check warnings section in this manual for possible causes of warning.
2. Press CHANGE DATA key and select Continue if AMA is to continue despite warning, or press OFF/STOP key to stop AMA.
Page 41
108 Start Voltage of Parallel Motors
(MULTIM.START VOLT)
Value:
0.0 through parameter 103 Motor Voltage depends on par. 103 Motor Voltage
Function:
This parameter sets the voltage at 0 Hz for all drives with two or more motors connected in parallel.
The start voltage represents a supplementary voltage input to the motor. Increasing the start voltage will increase the starting torque. A start voltage is especially useful for small motors (<5 hp) as they have a higher stator resistance than larger motors.
This function is only active if Parallel Motors has been selected in parameter 101, Torque Characteristics.
Description of choice:
To set the start voltage, monitor the motor current while starting the load and choose the starting voltage that gives the lowest starting current. Start with a small value and increase only as required for reliable starting.
109 Resonance Dampening (RESONANCE DAMP.) Value:
0 to 500 % 100 %
111 Start Delay (START DELAY) Value:
0.0 to 120.0 sec. 0.0 sec.
Function:
This parameter allows a delayed start of the drive after the conditions for start have been fulfilled. After the start delay time has elapsed, the drive will start and ramp up to the commanded speed.
Description of choice:
Set the desired time before the drive will start.
112 Motor Preheat (MOTOR PREHEAT) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
The motor preheat function protects the motor from condensation by running a small DC current through the motor. Motor preheat is only active during stop when control voltage is applied to terminal 27.
Description of choice:
Select Disable if this function is not required. Select Enable to activate motor preheating. The amount of motor preheating is set in parameter 113.
CAUTION
Function:
High-frequency resonances in the motor can be eliminated by adjusting this parameter.
Description of choice:
Adjust the dampening percentage for smoothest high speed operation.
110 High Breakaway Torque (HIGH START TORQ.) Value:
0.0 to 0.5 sec. OFF
Function:
The drive is able to breakaway high friction loads. This high starting torque, approximately 1.6 x rated torque is available for up to 0.5 seconds. The current level is limited by the protective circuits of the drive. OFF corresponds to 0.0 sec.
Description of choice:
Set the time for which high starting torque is desired.
Motor Damage!
Be sure to check settings in parameter 113 if parameter 112, Motor Preheat, is enabled. Do not apply any more current than required. Excessive current or preheating time may damage the motor.
113 Motor Preheat DC Current
(PREHEAT DC-CURR.)
Value:
0 to 100 % 50 %
The maximum value depends on the rated motor current.
Function:
The motor can be preheated when stopped by applying DC current to it. A holding torque can also be provided.
Description of choice:
The motor can be preheated by means of a DC current. At 0%, the function is inactive; at a value higher than 0%, a DC current will be supplied to the motor whenever it is stopped. A windmilling fan can be held by providing a holding toque by using this parameter.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
41
Page 42
DC Braking
Applying DC current to the motor will brake the motor. Parameter 114, DC Braking Current, sets the DC braking current as a percentage of the rated motor current. Parameter 115, DC Braking Time, sets the amount of time that the DC current will be applied. Parameter 116, DC Brake Cut-in Frequency, sets the frequency at which DC braking begins when the motor decelerates during a stop.
If terminal 19 or 27 (parameters 303 or 304 Digital Input) has been programmed to DC Braking Inverse and shifts from logic 1 to logic 0, the DC braking will be activated immediately.
When the start signal on terminal 18 changes from logic 1 to logic 0, the DC braking will be activated when the output frequency becomes lower than the brake cut-in frequency.
If a DC brake current is set in parameter 114, the drives switching frequency will be limited to 4 kHz during the braking.
CAUTION
Motor Damage!
A high braking current supplied for a long time will overheat the motor. Use only the DC braking current and time required. Excessive braking current may damage the motor.
Also, do not use DC braking function if inertia of driven load is more than 20 times inertia of motor. Excessive load inertia may damage the motor.
NOTE Most HVAC applications do not required braking or holding. It is suggested that parameter 114 remain set at 0 unless braking or holding torque is required.
115 DC Braking Time (DC BRAKE TIME) Value:
0.0 to 60.0 sec. 10.0 sec.
Function:
This parameter sets the time that the DC braking is active.
Description of choice:
Set the desired time.
116 DC Brake Cut-in Frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) to setting of parameter 202 OFF
Function:
This parameter is used for setting the frequency at which DC braking begins after a stop command is issued.
Description of choice:
Set the desired frequency for braking to begin upon deceleration.
114 DC Braking Current (DC BRAKE CURRENT) Value:
0 to 100% 50 %
The maximum value depends on the rated motor current.
Function:
This parameter is used for setting the DC braking current that is applied:
1. When the DC brake frequency set in parameter 116 DC Brake Cut-in Frequency has been reached during a stop.
2. When DC brake inverse is active via terminal 19 or 27, or via the serial bus.
The DC braking current will be active for the duration of the DC braking time set in parameter 115 DC Braking Time.
Description of choice:
To be set as a percentage value of the rated motor current set in parameter 105 Motor Current.
100% DC braking current corresponds to the value set in parameter
105.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
42
Page 43
117 Motor Thermal Protection
(MOT. THERM PROTEC)
Value:
No protection (NO PROTECTION) [0] Thermistor warning (THERMISTOR WARNING) [1] Thermistor trip (THERMISTOR FAULT) [2] ETR Warning 1 (ETR WARNING 1) [3]
ETR Trip 1 (ETR TRIP 1) [4]
ETR Warning 2 (ETR WARNING 2) [5] ETR Trip 2 (ETR TRIP 2) [6] ETR Warning 3 (ETR WARNING 3) [7] ETR Trip 3 (ETR TRIP 3) [8] ETR Warning 4 (ETR WARNING 4) [9] ETR Trip 4 (ETR TRIP 4) [10]
Function:
The drive is able to monitor the motor temperature in two different ways:
By a thermistor installed in the motor. The thermistor is connected to one of the analog input terminals (53 or 54).
Calculation of the thermal load by the Electronic Thermal Relay (ETR) is based on current, frequency and time. This is compared with the rated motor current and the rated motor frequency. The calculations take into account the reduced cooling of the motor at low speeds.
ETR Tip 1 through 4 and ETR Warning 1 through 4 correspond to the four drive setups. This enables the use of the ETR function to protect up to four different motors if a different setup is used for each different motor.
NOTE If multiple setups are used, be sure to program complete motor data (parameters 102 through
106) and parameter 117 in each setup.
Description of choice:
Select No protection if no warning or trip is desired when the motor is overheated.
Motor Thermal Protection
The motor temperature is calculated on the basis of motor current, output frequency and time. The graph shows the amount of time that the drive can provide a current level to the motor at the rated motor frequency, 20% of rated motor frequency and 200% of rated motor frequency.
118 Motor Power Factor (Cos Æ)
(MOTOR PWR FACT)
Value:
0.50 - 0.99 0. 75
Function:
Automatic Energy Optimization (AEO) (see parameter 101, Torque Characteristics) can be calibrated to work with motors with greater than
4 poles. Motors with 6, 8, and 12 poles have a lower power factor which restricts the energy saving capability of AEO. Calibrating AEO can optimize this function. The full load power factor will either be on the motor nameplate or available from the motor manufacturer.
Description of choice:
Enter the full load power factor value.
Select Thermistor warning if a warning is desired when the motor thermistor reaches its trip point.
Select Thermistor trip if a fault is desired when the motor thermistor reaches its trip point.
Select ETR Warning 1 through 4, if a warning is desired when the motor is overheated according to the ETR calculations.
The drive can also be programmed to give off a warning signal through one of the digital outputs.
Select ETR Trip 1 through 4 if a fault is desired when the motor is overheated according to the ETR calculations.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
43
Page 44
References and Limits Parameters 200 through 228
In this parameter group, the frequencies and references of the drive are set.
202 Output Frequency High Limit
(MAX. FREQUENCY)
Value:
Parameter 201 to parameter 200 60 Hz
This parameter group includes:
Setting of ramp times Choice of four preset references Setting four bypass frequencies Setting maximum current to motor Setting warning limits for current, frequency, reference and feedback
200 Output Frequency Range
(FREQUENCY RANGE)
Value:
0 to 120 Hz (0 - 120 HZ) [0]
0 to 1000 Hz (0 - 1000 HZ) [1]
Function:
Choose one of two maximum output frequency ranges.
Description of choice:
Select the output frequency range that includes the highest output frequency required for normal operation.
NOTE HVAC applications seldom require output frequency greater than 120 Hz. Check with Trane, motor manufacturer, or manufacturer of driven equipment before selecting 0 - 1000 Hz range.
Function:
Set the highest speed at which the motor is to run.
NOTE Output frequency of drive can never assume value higher than 1/10th of switching frequency. See parameter 407, Switching Frequency.
Description of choice:
Set a value between the low frequency limit, set in parameter 201, and the frequency range limit, set in parameter 200. The drive will not be able to run continuously at an output frequency above this value in any mode.
NOTE HVAC applications seldom require output frequency greater than 60 Hz. Check with Trane, motor manufacturer, or manufacturer of driven equipment before selecting a maximum frequency greater than 60 Hz.
201 Output Frequency Low Limit
(MIN. FREQUENCY)
Value:
0.0 to parameter 202 0.0 HZ
Function:
Set the minimum speed at which the motor is to run.
Description of choice:
A value from 0.0 Hz to the Output Frequency High Limit frequency set in parameter 202 can be selected. The drive will not be able to run continuously at an output frequency below this value in any mode.
NOTE For fan applications, factory setting of parameter 201 is 6 Hz. For pump applications, factory setting for parameter 201 is 18 Hz.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
44
Page 45
Reference Handling
Reference handling is shown in the block diagram at the bottom of this page. The block diagram shows how a change in a parameter can effect the resulting reference.
It is possible to have both internal preset references and external references at the same time. In parameter 210, Reference Type, a choice is made of how the preset references are to be combined with the external references.
Parameters 203 to 205, Reference Handling, Minimum and Maximum Reference, and parameter 210, Reference Type, define the way reference handling is carried out. These parameters are active both in closed loop and open loop operation.
In closed loop operation, the resulting reference is affected by param­eters 418 and 419, Setpoint 1 and 2, as well as by remote references.
Remote references can be:
1) external references, including analog inputs 53, 54 and 60; pulse references through terminals 17 or 29 and references from serial communication
2) preset references
The resulting reference can be shown in the display as a percentage or as a selected unit of measure. The sum of the external references can be displayed in a percentage of the range between Minimum Reference to Maximum Reference. Select External Reference, [%] or the desired unit in parameters 007 through 010, Display Readout, to display the reference value.
An independent local reference exists, where the resulting reference is set by means of the [+] and [-] keys. In all cases, the output frequency range is limited by parameter 201, Output Frequency Low Limit, and parameter 202, Output Frequency High Limit.
NOTE If local reference is active, drive is always in Open Loop, regardless of choice made in parameter 100, Configuration.
The unit of the local reference can be set either as Hz or as a percentage of the output frequency range. The unit is selected in parameter 011, Unit of Local Reference.
203 Reference Handling (REFERENCE SITE) Value:
Hand/Auto linked reference
(LINKED TO HAND/AUTO) [0] Local reference (LOCAL) [1] Remote controlled reference (REMOTE) [2]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
45
Page 46
Function:
This parameter chooses the active resulting reference. If Hand/Auto linked reference is selected, the resulting reference will depend on
whether the drive is in Hand or Auto mode.
The table below shows which reference is active when Hand/Auto linked reference, Remote reference or Local reference has been selected. The Hand mode or Auto mode can be selected via the keypad or by a digital input set in parameters 300 through 307 Digital
Inputs.
Reference Handling Hand Mode Auto Mode
Hand/Auto Local ref. active Remote ref. active Remote Remote ref. active Remote ref. active Local Local ref. active Local ref. active
The unit for the reference can be seen from the following table:
Unit
Parameter 100 Configuration = Open loop Hz Parameter 100 Configuration = Closed loop Par. 415
Description of choice:
Minimum Reference is the lowest reference value that can be set for the drive.
205 Maximum Reference (MAX. REFERENCE) Value:
If parameter 100, Configuration = Open loop, parameter 204, Minimum Reference, to 1000.000 Hz 60.000 Hz
Description of choice:
If Hand/Auto linked reference is chosen, the motor speed in Hand mode will be set by the local reference, while in Auto mode it is set by the remote references and any setpoints selected.
If Remote reference is selected, the motor speed will depend on remote references and any setpoints selected, regardless of whether Hand mode or Auto mode has been chosen.
If Local reference is selected, the motor speed will only depend on the local reference set via the control panel, regardless of whether Hand mode or Auto mode has been selected.
204 Minimum Reference (MIN. REFERENCE) Value:
If parameter 100, Configuration = Open loop,
0.000Hz to parameter 205, Maximum Reference. ✭ 0.000 Hz
If parameter 100 Configuration = Closed loop, parameter 413, Minimum Feedback, t o parameter 205, Maximum Reference. ✭ 0.000 Hz
Function:
The Minimum Reference sets the minimum value of the sum of all references. If Closed loop has been selected in parameter 100,
Configuration, the minimum reference is limited by parameter 413, Minimum Feedback.
If parameter 100, Configuration = Closed loop, parameter 204, Minimum Reference, to parameter 414, Maximum Feedback. ✭60.000 Hz
Function:
The Maximum Reference sets the maximum value of the sum of all references. If Closed loop has been selected in parameter 100, Configuration, the maximum reference cannot be set above parameter 414, Maximum Feedback. The Maximum Reference is ignored when the local reference is active.
The reference unit can be determined from the following table:
Unit Parameter 100 Configuration = Open loop Hz Parameter 100 Configuration = Closed loop Par. 415
Description of choice:
Maximum reference is the highest reference value that can be set for the drive.
Minimum reference is ignored when the local reference is active. In this case, minimum reference is determined by parameter 201, Minimum Frequency.
NOTE For fan applications, factory setting of parameter 204 is 6 Hz. For pump applications, factory setting for parameter 204 is 18 Hz.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
46
Page 47
206 Ramp Up Time (RAMP UP TIME) Value:
1 to 3600 seconds Depends on the unit
Function:
The ramp up time is the acceleration time from 0 Hz to the rated motor frequency set in parameter 104. It is assumed that the output current does not reach the current limit set in parameter 215. This determines the maximum acceleration rate for all modes of operation.
Description of choice:
Program the desired accel time. Too long of a ramp up time can cause sluggish drive operation. Too short of a ramp up time can cause the drive to go into current limit during acceleration or cause unacceptable torque pulses in the controlled system.
NOTE For fan applications, factory setting of parameter 206 is 60 seconds. For pump applications, factory setting for parameter 206 is 10 seconds.
Description of choice:
Program the desired decel time. Too long of a ramp down time can cause sluggish operation. Too short of a ramp down time can cause the drive to trip off due to high DC bus voltage or cause unacceptable torque pulses in the controlled system.
NOTE Factory setting of parameter 207 for fan applications, is 60 seconds. For pump applications, factory setting for parameter 207 is 10 seconds.
208 Automatic Ramp Down (AUTO RAMPING) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This function ensures that the drive does not trip during deceleration if the decel time set is too short. If, during deceleration, the DC bus voltage increases to the maximum value permitted, the drive automati­cally extends the ramp-down time.
NOTE If auto ramp down is enabled, ramp time could be considerably longer than that set in parameter 207, Ramp Down Time.
207 Ramp Down Time (RAMP DOWN TIME) Value:
1 to 3600 seconds ★ Depends on the unit
Function:
The ramp-down time is the deceleration time from the rated motor frequency set in parameter 104, Motor Frequency, to 0 Hz. This ramp-down time may be automatically extended to prevent an overvoltage trip if the load regenerates to the drive. This determines the maximum deceleration rate for all modes of operation.
Description of choice:
Program this function as Enable to avoid trips caused by too rapid a deceleration.
209 Jog Frequency (JOG FREQUENCY) Value:
Parameter 201, Output Frequency Low Limit, to parameter 202 Output Frequency High Limit 10.0 HZ
Function:
The jog frequency is the fixed output frequency at which the drive is running when the jog function is activated.
Jog can be activated via the digital inputs.
Description of choice:
Set the desired frequency.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
47
Page 48
Reference Type
The example below shows how the resulting reference is calculated when Preset references are used together with Sum and Relative references set in parameter 210, Reference Type. A formula for calculating the resulting reference is given under Calculation of Resulting Reference. See the drawing under Reference Handling.
Example:
The following parameters have been set:
Parameter 204 Minimum Reference: 10 Hz Parameter 205 Maximum Reference: 60 Hz Parameter 211 Preset Reference: 15% Parameter 308 Terminal 53, Analog Input: Reference Parameter 309 Terminal 53, Min. Scaling: 0 V Parameter 310 Terminal 53, Max. Scaling: 10 V
When parameter 210 Reference Type is set to Sum, one of the adjusted Preset References, parameters 211 through 214, will be added to the external references as a percentage of the reference range. If terminal 53 has an analog input voltage of 4 V, the resulting reference will be:
Parameter 210 Reference type = Sum
Parameter 204 Minimum Reference = 10.0 Hz Reference contribution at 4 V = 16.0 Hz Parameter 211 Preset Reference Resulting reference = 32.0 Hz
If parameter 210 Reference Type is set to Relative, one of the adjusted Preset References parameters 211 through 214 will be totaled as a percentage of the sum of the present external references. If terminal 53 has an analog input voltage of 4 V, the resulting reference will be:
Parameter 210 Reference type = Relative
Parameter 204 Minimum Reference = 10.0 Hz Reference contribution at 4 V = 16.0 Hz Parameter 211 Preset Reference = 2.4 Hz Resulting reference = 28.4 Hz
The graph in the next column shows the resulting reference while the external reference changes from 0 to 10 V. Parameter 210, Reference
Type has been programmed for Sum and Relative. Parameter 211, Preset Reference 1, is programmed for 0%.
= 6.0 Hz
210 Reference Type (REF. FUNCTION) Value:
Sum (SUM) [0] Relative (RELATIVE) [1]
External/preset (EXTERNAL/PRESET) [2]
Function:
It is possible to define how the preset references are added to the other references. For this purpose, Sum or Relative is used. It is also possible, by using the External/Preset function, to select between the external references and a preset reference.
Description of choice:
If Sum is selected, one of the preset references (parameters 211 through 214, Preset Reference) is added to the other external references as a percentage of the reference range (minimum reference through maximum reference).
If Relative is selected, one of the adjusted preset references (param­eters 211 through 214, Preset Reference) is added as a percentage of the total external reference.
If External/Preset is selected, it is possible to shift between the external references and the preset references using terminals 16, 17, 29, 32 or 33 (parameters 300, 301, 305, 306 or 307, Digital Inputs). Preset references are a percentage value of the reference range. External reference is the sum of the analog references, pulse references and any references from serial communication.
NOTE If Sum or Relative is selected, one of preset references is always active. If preset references are not used, set value to 0%.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
48
NOTE See Calculation of Resulting Reference section in this manual for mathematic formula to calculate references.
Page 49
211 Preset Reference 1 (PRESET REF. 1) 212 Preset Reference 2 (PRESET REF. 2) 213 Preset Reference 3 (PRESET REF. 3) 214 Preset Reference 4 (PRESET REF. 4) Value:
-100.00 % to +100.00 % 0.00% of the reference range or external reference
Function:
Four different preset references can be programmed in parameters 211 to 214, Preset Reference. The preset reference is stated as a percentage of the reference range or as a percentage of the other external references, depending upon the choice made in parameter 210, Reference Type.
The choice of preset references is made by activating terminals 16, 17, 29, 32 or 33, as shown in the table below.
Description of choice:
Set the required maximum output current.
NOTE When drive is in current limit and a stop command is issued by pressing the STOP key on LCP keypad, drive output is immediately cut off and motor will coast-to-stop.
216 Frequency Bypass, Bandwidth
(FREQUENCY BYPASS B.W.)
Value:
0 (OFF) to 100 Hz ★ DISABLED
Function:
Mechanical resonance in the driven system sometimes makes it desirable to avoid operation at critical speeds.
Terminal 17/29/33 Terminal 16/29/32
preset reference msb preset reference lsb
0 0 Preset reference 1 0 1 Preset reference 2 1 0 Preset reference 3 1 1 Preset reference 4
Description of choice:
Set the required preset reference(s) that is/are to be used.
215 Current Limit (CURRENT LIMIT) Value:
0.1 to 1.1 x rated current rated current
Function:
This is where the maximum output current is set. If the motor attempts to draw more than this amount of current, the drive will reduce its output frequency until the current is less than or equal to the current limit value.
The factory setting corresponds to the rated output current. If the current limit is to be used as motor protection, the rated motor current must be set. If the current limit is set within the range of 1.0 to 1.1 times the rated output current of the drive, the drive can only handle current greater than its rated output intermittently. After the load has been higher than rated output current limit, it must be reduced to a level that is lower than the rated current of the drive for a period of time.
These output frequencies can be programmed in parameters 217 through 220.
In this parameter, Frequency Bypass, Bandwidth, the width of the frequency to be bypassed is defined.
Description of choice:
The bypass bandwidth is equal to the programmed bandwidth frequency. This bandwidth will be centered around each bypass frequency.
217 Frequency Bypass 1 (BYPASS FREQ. 1) 218 Frequency Bypass 2 (BYPASS FREQ. 2) 219 Frequency Bypass 3 (BYPASS FREQ. 3) 220 Frequency Bypass 4 (BYPASS FREQ. 4) Value:
0 to 120 or 1000 HZ 120.0 Hz The frequency range depends on the selection made in parameter 200, Output Frequency Range.
Function:
Some systems require that some output frequencies be avoided because of mechanical resonance problems in the system.
Description of choice:
Enter the frequencies to be avoided.
See also parameter 216, Frequency Bypass, Bandwidth.
Note that if the current limit is set to less than the maximum value of the drive, acceleration torque is reduced correspondingly.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
49
Page 50
Warning Functions
The warning functions in parameters 221 through 228 are not active during ramp-up after a Start command, ramp down after a Stop command, or while stopped. The warning functions are activated when the output frequency has reached the resulting reference.
The signal outputs can be programmed to generate a warning signal via terminal 42 or 45 and via the relay outputs.
The reference limits in parameter 226, Warning: High Reference and parameter 227, Warning: Low Reference are only active when remote reference has been selected.
222 Warning: High Current (WARN. HIGH CURR) Value:
Parameter 221 to 1.1 x rated current
1.1 x rated current
Function:
If the motor current is above the limit programmed in this parameter, the display shows a flashing CURRENT HIGH.
Description of choice:
The upper signal limit of the motor frequency must be programmed within the normal working range of the drive. See the drawing at parameter 221, Warning: Low Current.
221 Warning: Low Current (WARN. LOW CURR) Value:
0.0 to parameter 222 Warning: High current ✭ 0.0 A
Function:
When the motor current is below the limit programmed in this parameter, the display shows a flashing CURRENT LOW, provided Warning has been selected in parameter 409, Function in Case of No Load. The drive will trip if parameter 409 has been selected as Trip. This can be used to indicate when a belt between the motor and the driven load is broken.
Description of choice:
The lower signal limit must be programmed within the normal working range of the drive.
223 Warning: Low Frequency
(WARN. LOW FREQ)
Value:
0.0 to parameter 224 0.0 Hz
Function:
If the output frequency is below the limit programmed in this parameter, the display will show a flashing F OUT < FLOW.
Description of choice:
The lower signal limit of the motor frequency must be programmed within the normal working range of the drive. See drawing at parameter 221 Warning: Low current.
224 Warning: High Frequency
(WARN. HIGH FREQ.)
Value:
Par. 200 Output frequency range = 0 to 120 Hz parameter 223 - 120 Hz 120.0 Hz Par. 200 Output frequency range = 0 to 1000 Hz parameter 223 - 1000 Hz 120.0 Hz
Function:
If the output frequency is above the limit programmed in this parameter, the display will show a flashing F OUT > F HIGH
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
50
Description of choice:
The higher signal limit of the motor frequency must be programmed within the normal working range of the drive. See the drawing at parameter 221, Warning: Low Current.
Page 51
225 Warning: Low Reference
(WARN. LOW REF)
Value:
-999,999.999 - High Reference (par. 226) -999,999.999 Hz
Function:
When the total remote reference is less than the limit programmed in this parameter, the display shows a flashing REF.<REF. LOW
The reference limits in parameter 226, Warning: High Reference and parameter 225, Warning: Low Reference are only active when remote reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop the unit is programmed in parameter 415, Process Units.
227 Warning: Low Feedback
(WARN .LOW FDBK)
Value:
-999,999.999 to High Feedback (parameter 228) -999,999.999
Function:
If the feedback signal is below the limit of Low Feedback programmed in this parameter, the display will flash FEEDBACK<FOB LOW.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the desired value within the feedback range, parameter 413, Minimum Feedback, and parameter 414, Maximum Feedback.
Description of choice:
When parameter 100, Configuration, has been programmed for Open Loop, the lower signal limit of the reference must be programmed within
the normal working range of the drive. If parameter 100 is pro­grammed as Closed Loop, Low Reference must be within the reference range programmed in parameters 204 and 205.
226 Warning: High Reference
(WARN. HIGH REF)
Value:
Reference Low (par. 225) to 999,999.999 999,999.999 Hz
Function:
If the resulting reference is below the limit programmed in this param­eter, the display flashes REF. > REF. HIGH.,
The reference limits in parameter 226 Warning: High Reference and parameter 225 Warning: Low Reference are only active when remote reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop the unit is programmed in parameter 415, Process Units.
Description of choice:
The high reference warning must be programmed within the normal working range of the drive, provided parameter 100 Configuration has been programmed for Open Loop. If parameter 100 has been programmed for Closed Loop, Reference High must be within the reference range programmed in parameters 204 and 205.
228 Warning: High Feedback
(WARN. HIGH FDBK)
Value:
Low Feedback (parameter 227) to 999,999.999
999,999.999
Function:
If the feedback signal is above the limit programmed in this parameter, the display will show a flashing FEEDBACK>FOBHIGH.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the required value within the feedback range, parameter 413, Minimum Feedback, and parameter 414, Maximum Feedback.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
51
Page 52
Inputs and Outputs Parameters 300 through 328
In this parameter group, the functions of the drive input and output terminals are defined. The digital inputs are through terminals 16, 17, 18, 19, 27, 32 and 33. Inputs are programmed by parameters 300 through 307. The table below shows the functions available for input.
Digital inputs require a signal of 0 or 24VDC. A signal lower than 5VDC is a logic 0, while a signal higher than 10 VDC is a logic 1.
The terminals for the digital inputs can be connected to the internal 24 VDC supply through terminals 12 and 13, or an external 24VDC supply can be connected.
The drawings at the right show one setup using the internal 24VDC supply and one setup using an external 24VDC supply.
Switch 4 is used for separating the common potential of the internal 24VDC supply from the common potential of an external 24VDC supply. Switch 4 is the DIP switch on the far right of the group of DIP switches located on the lower right of the control card, just above the control terminals.
When Switch 4 is in the OFF position, the external 24VDC supply is galvanically isolated from the drive.
Digital Inputs Terminal Number: 16 17 18 19 27 29 32 33
Parameter: 300 301 302 303 304 305 306 307
Value:
No function (NO OPERATION) [0] ✭[0] [0] [0] [0] ✭[0] ✭[0] Reset (RESET) [1] [1] [1] [1] [1] Coasting stop, inverse (COAST INVERSE) [0] Reset and coasting stop, inverse (RESET & COAST INVERSE) [1] Start (START) ✭[1] Reversing (REVERSE) [1] Reversing and start (START REVERSE) [2] DC-braking, inverse (DC BRAKE INVERSE) [3] [2] Safety interlock (SAFETY INTERLOCK) ✭[3] Freeze reference (FREEZE REFERENCE) [2] [2] [2] [2] [2] Freeze output (FREEZE OUTPUT) [3] [3] [3] [3] [3] Selection of Setup, lsb (SETUP SELECT LSB) [4] [4] [4] Selection of Setup, msb (SETUP SELECT MSB) [4] [5] [4] Preset reference, on (PRESET REF. ON) [5] [5] [6] [5] [5] Preset reference, lsb (PRESET REF. LSB) [6] [7] [6] Preset reference, msb (PRESET REF. MSB) [6] [8] [6] Speed down (SPEED DOWN) [7] [9] [7] Speed up (SPEED UP) [7] [10] [7] Start enabled (RUN PERMISSIVE) [8] [8] [11] [8] [8] Jog (JOG) [9] [9] [12] [9] [9] Data change lock (PROGRAMMING LOCK) [10] [10] [13] [10] [10] Pulse reference (PULSE REFERENCE) [11] [14] Pulse feedback (PULSE FEEDBACK) [11] Hand start (HAND START) [11] [12] [15] [11] [12] Auto start (AUTOSTART) [12] [13] [16] [12] [13]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
52
Page 53
Function:
In parameters 300 through 307, Digital Inputs, the functions of terminals 16 through 33 are selected.
These options are shown in the table on the previous page.
Description of choice:
No Function is selected if the drive is not to react to signals transmitted to the terminal.
Reset allows reset of the drive after a resettable fault. Not all faults can be reset without removing and reapplying the input power. Faults that require the removal of input power are called trip lock faults. See Warnings and Alarms.
Coasting Stop, Inverse is used to release the motor immediately by turning off the output transistors. The motor will coast freely to a stop. Inverse indicates a closed terminal sends the stop signal. Logic 0 implements coasting to a stop.
Reset and Coasting Stop, Inverse is used for activating coasting stop at the same time as reset. Inverse indicates a closed terminal sends the stop signal. Logic 0 implements coasting stop and reset.
DC Braking, Inverse is used for stopping the motor by energizing it with a DC voltage for a given time, as set by parameters 114 and 115. Inverse indicates a closed terminal sends the braking signal. Logic 0 implements DC braking. See the DC braking parameters.
Safety Interlock is the s ame as Coasting Stop, Inverse, except Safety Interlock generates an alarm message on the display when terminal 27
is logic 0. The alarm message will also be active through digital outputs 42 and 45 and relay outputs 1 and 2, if programmed for Safety Interlock.
Start is selected for a remote Start/Stop command. Logic 1 = Start. Logic 0 = Stop.
Reversing is used for changing the direction of rotation of the motor. Logic 0 is for forward. Logic 1 is for reverse. The drive can be safely reversed while it is driving the motor. The reversing signal only changes the direction of rotation, it does not activate the start function. It is not active in Closed Loop mode.
Freeze Reference freezes the present reference. The frozen reference can only be changed by means of Speed Up or Speed Down. The frozen reference is saved after a stop command and when power is removed.
Freeze Output freezes the present output frequency. The frozen output frequency can now only be changed by means of Speed Up or Speed Down.
NOTE If Freeze Output is active, the drive cannot be stopped via terminal 18.
To stop the drive when Freeze Output is active, one of the four methods listed below must be used.
Turn off the Freeze Output function and perform a normal stop. Press the keypad Off/Stop key. Remove the control voltage to terminal 27. If terminal 19 is programmed in parameter 303 for DC Brake Inverse, remove the control voltage to it.
Selection of Setup, Lsb* and Selection of Setup, Msb** enables digital selection of the four possible setups. To enable this, parameter 002 Active Setup must be set to Multi Setup.
Setup, Msb Setup, Lsb Setup 1 0 0 Setup 2 0 1 Setup 3 1 0 Setup 4 1 1
*Lsb - Least significant bit. **Msb - Most significant bit.
Preset Reference, on is used for switching between remote controlled reference and preset reference. This assumes that Remote/preset has been selected in parameter 210, Reference Type. Logic 0 = remote controlled references active; logic 1 = one of the four preset refer­ences is active in accordance with the table below.
Preset Reference, Lsb and
Preset reference, Msb enables a
choice of one of the four preset references, in accordance with the table below.
Reversing and Start is used for Start/Stop and reversing using the same signal. A start signal through terminal 18 starts the drive in the forward direction. If both terminal 18 and a reversing and start terminal are given a logic 1 at the same time, the drive will not start. It is not active in Closed Loop.
Preset ref. msb Preset ref. lsb Preset ref. 1 0 0 Preset ref. 2 0 1 Preset ref. 3 1 0 Preset ref. 4 1 1
Speed Up and Speed Down are selected if digital control of the up/ down speed is desired. This function is only active if Freeze Reference or Freeze Output has been selected.
53
Page 54
As long as there is a logic 1 on the terminal selected for Speed Up, the reference or the output frequency will increase by the Ramp-up Time set in parameter 206.
As long as there is a logic 1 on the terminal selected for Speed Down, the reference or the output frequency will decrease by the Ramp-down Time set in parameter 207.
Pulses (logic 1 minimum high for 3ms and a minimum pause of 3ms) will lead to a change of speed of 0.1% (reference) or 0.1 Hz (output frequency).
Example:
Terminal Terminal Freeze ref./
(16) (17) Freeze output No speed change 0 0 1 Speed down 0 1 1 Speed up 1 0 1 Speed down 1 1 1
The speed reference frozen through the control panel can be changed even if the drive has stopped. In addition, the frozen reference will be retained in memory after power interruption.
Run Permissive. Run Permissive is used to require a second run permission signal in addition to the normal run command, either in Hand or Auto mode. When a run command alone is given, the display will show RUN REQ., but the drive will not start. The drive can also indicate that a run has been requested through one of the transistorized or relay outputs. When, in addition to the run command, a logic 1 is applied to the Run Permissive terminal, the drive will run. If more than one terminal is programmed for Run Permissive, a logic 1 at any of these terminals will allow the drive to run.
Jog is used to start the drive and run it at the frequency set in parameter 209, Jog Frequency. Jog is active in both Hand and Auto mode.
Jog is not active if a stop command has been given through the keypad or terminal 27.
Pulse reference is selected if the frequency of a pulse train is to be used as a reference signal. 0 Hz corresponds to parameter 204,
Minimum Reference. The frequency set in parameter 327, Pulse Reference, Maximum Frequency corresponds to parameter 205 Maximum Reference.
Pulse feedback is selected if the frequency of a pulse train is to be used as a feedback signal. Parameter 328, Pulse Feedback, Maximum Frequency is the pulse frequency that corresponds to maximum feedback.
Hand start is selected if an external signal is used to switch the drive to Hand mode. A logic 1 (Hand Start active) will start the motor. A logic 0 will stop the motor. The drive will then be in OFF/STOP mode, unless there is an active Auto Start signal from an external source. Programming one of the digital inputs for Hand Start will disable the LCP Hand Start and Auto Start keys.
WARNING
!
Unintended Start!
With Hand Start active, digital inputs may cause drive to start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness with Hand Start active could result in death, serious injury, or equipment or property damage.
Auto start is selected if an external signal is sent to switch the drive to Auto mode. When a start signal is active on the control terminals or the serial communication port, the drive will start the motor. If Auto Start and
Hand Start are active at the same time on the control terminals, Auto Start will have the higher priority. If Auto Start and Hand Start are not
active, the motor will stop and the drive will then be in the OFF/STOP mode. Programming one of the digital inputs for Auto Start will disable the LCP Hand Start and Auto Start keys.
Data change lock is selected if changes to parameters are not to be made via the control panel. It is be possible to change parameters through the serial bus.
54
Page 55
Analog Inputs
Two analog inputs for voltage signals, terminals 53 and 54, and an analog input for current, terminal 60, are provided for reference and feedback signals. A thermistor can be connected to the voltage inputs, terminals 53 or 54.
Feedback. If a feedback signal is connected, a voltage input may be connected to either terminal 53 or 54, or a current input conected to terminal 60. If a two zone PID control is used, the feedback signals must be voltage inputs and applied to terminals 53 and 54. See Feedback Handling.
The two analog voltage inputs can be scaled over the range of 0to10VDC. The current input can be scaled over the range of 0 to20mA.
The table below shows the possible analog input programming.
Parameter 317, Time Out, and Parameter 318, Function After Time Out, allow activation of a time-out function on all analog inputs. If the signal value of the reference or feedback signal connected to one of the analog input terminals drops below 50% of the minimum scaling, the function set in parameter 318, Function After Time Out, will be activated after the time-out set in parameter 317.
Analog Inputs Terminal Number 53 (Voltage) 54 (Voltage)
308 Terminal 53, Analog Input Voltage
60 (Current)
(AI [V] 53 FUNCT.)
Function:
This parameter is used to select the required function to be linked to terminal 53.
Description of choice:
No operation. Selected if the drive is not to react to signals connected to the terminal.
Reference. Selected to enable change of reference by means of an analog reference signal. If reference signals are connected to several inputs, these reference signals will be summed.
Thermistor. Selected if a thermistor in the motor stops the drive in case of motor overtemperature. The cutout value is 3kohm. A Klixonthermal switch may also be connected to this input. If parallel sensors are used, the thermistors/thermal switches can be connected in series. The drive will shut down when the total resistance exceeds 3 kohms.
NOTE When a thermistor is mounted in motor wiring, a breakdown of insulation between thermistor and motor can feed high voltage back to drive control terminals. To comply with protective extra-low voltage (PELV) grounding requirements, if applicable, thermistor must be mounted externally.
Parameter 117, Motor Thermal Protection, must be programmed for Thermal Warning or Thermistor Trip, and the thermistor must be
inserted between terminal 53 or 54, analog voltage input, and terminal 50, 10V supply.
Analog Inputs Terminal Number 53 54 60
Param eter 308 311 314
Value:
No operation (NO OPERATION) ★[0] ★[0] [0] Reference (REFERENCE [1] [1] [1] Feedback (FEEDBACK) [2] [2] [2] Thermistor (THERMISTOR) [3] [3]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
55
Page 56
309 Terminal 53, Minimum Scaling
(AI 53 SCALE LOW)
Value:
0.0 to 10.0 V 0.0 V
312 Terminal 54, Minimum Scaling
(AI 54 SCALE LOW)
Value:
0.0 to 10.0 V 0.0 V
Function:
This parameter is used for setting the signal value that corresponds to the minimum reference or the minimum feedback, parameter 204,
Minimum Reference, or parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for. If the time out functions in parameter 317, Time Out, and parameter 318, Function After Time Out, are to be used, the value must be set to >1 V.
310 Terminal 53, Maximum Scaling
(AI 53 SCALE HIGH)
Value:
0.0 to 10.0 V ★ 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal lines should be compensated for.
311 Terminal 54, Analog Input Voltage
(AI [V] 54 FUNCT.)
Value:
See the description of parameter 308. No operation
Function:
This parameter selects the function of terminal 54.
The input signal is scaled by parameter 312, Terminal 54, Minimum Scaling, and by parameter 313, Terminal 54, Maximum Scaling.
Description of choice:
See description of parameter 308.
Function:
This parameter is used to set the signal value that corresponds to the minimum reference value or the minimum feedback, parameter 204,
Minimum Reference, and parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for.
If the time out function is to be applied, parameter 317, Time Out, an d parameter 318, Function After Time Out, the value must be set to >1 V.
313 Terminal 54, Maximum Scaling
(AI 54 SCALE HIGH)
Value:
0.0 to 10.0 V 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for.
314 Terminal 60, Analog Input Current
(AI [mA] 60 FUNCT.)
Value:
See description of parameter 308. Reference
Function:
This parameter selects the function of terminal 60.
Scaling of the input signal is set by parameter 315, Terminal 60,
Minimum Scaling, and by parameter 316, Terminal 60, Maximum Scaling.
Description of choice:
See description of parameter 308, Terminal 53, Analog Input Voltage.
For reasons of accuracy, voltage losses in long signal lines should be compensated for.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
56
Page 57
315 Terminal 60, Minimum Scaling
(AI 60 SCALE LOW)
Value:
0.0 to 20.0 mA 4 .0 mA
317 Time Out
(LIVE ZERO TIME)
Value:
1 to 99 sec. 10 sec.
Function:
This parameter determines the signal value that corresponds to the minimum reference or the minimum feedback, parameter 204 Minimum
Reference, parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required current value.
If the time-out function is to be used, parameter 317, Time Out, and parameter 318, Function After Time Out, the value must be set to >2mA.
316 Terminal 60, Maximum Scaling
(AI 60 SCALE HIGH)
Value:
0.0 to 20.0 mA 20.0 mA
Function:
This parameter determines the signal value that corresponds to the maximum reference or maximum feedback, parameter 205, Maximum
Reference Value, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the desired current value.
Function:
If the signal value of the reference or feedback signal connected to one of the input terminals 53, 54 or 60 drops to below 50% of the minimum scaling for a longer period than the Live Zero time, the function selected in parameter 318, Function After Time Out, will be activated.
This function will only be active if, in parameter 309 or 312, a value has been selected for Terminals 53 and 54, Minimum Scaling, that exceeds 1 V, or if, in parameter 315, Terminal 60, Minimum Scaling, a value has been selected that exceeds 2 mA.
Description of choice:
Set the desired time.
318 Function After Time Out
(LIVE ZERO FUNCT.)
Value:
Off (NO FUNCTION) [0]
Freeze output frequency (FREEZE OUTPUT FREQ.) [1] Stop (STOP) [2] Jog (JOG FREQUENCY) [3] Max. output frequency (MAX FREQUENCY) [4] Stop and trip (STOP AND TRIP) [5]
Function:
This is where to select the function to be activated after the end of the time-out period, parameter 317, Time Out.
If a time-out function occurs at the same time as a bus time-out function, parameter 510, Bus Time Interval Function, the time-out function in parameter 318 will be activated.
Description of choice:
The output frequency of the drive can:
- go to minimum (NO FUNCTION)
- be frozen at the present value (FREEZE OUTPUT FREQUENCY)
- stop (STOP)
- run at the jog frequency set in parameter 209 (JOGFREQUENCY)
- run at the maximum frequency set in parameter 202 (MAX.FREQUENCY)
- stop and send an alarm (STOP AND TRIP)
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
57
Page 58
Analog/Digital Outputs
The two analog/digital outputs available through terminals 42 and 45 can be programmed to show a status or an analog value such as
For the analog output, there is a choice of three types of output signal: 0 to 20 mA, 4 to 20 mA or 0to32000 pulses. The pulse rate is set by parameter 322, Terminal 45, Output, Pulse Scaling.
frequency. The status signal is a 24 VDC output.
See the Electrical Installation, Control Terminals section of this manual for the ratings of these outputs.
Analog/Digital Outputs terminal no. Analog/Digital Outputs Terminal Number: 42 45
Parameter: 319 321
Value: No function (NO FUNCTION) [0] [0] Drive ready (READY) [1] [1] Standby (ENABLED & NO WARNING) [2] [2] Running (RUNNING) [3] [3] Running at ref. value (RUNNING AT REFERENCE) [4] [4] Running, no warning (RUNNING NO WARNING) [5] [5] Local reference active (DRIVE IN LOCAL REF.) [6] [6] Remote controlled references active (DRIVE IN REMOTE REF.) [7] [7] Alarm (ALARM) [8] [8] Alarm or warning (ALARM OR WARNING) [9] [9] No alarm (NO ALARM) [10] [10] Current limit (CURRENT LIMIT) [11] [11] Safety interlock (SAFETY INTERLOCK) [12] [12] Start command active (START SIGNAL APPLIED) [13] [13] Reversing (RUNNING IN REVERSE) [14] [14] Thermal warning (THERMAL WARNING) [15] [15] Hand mode active (DRIVE IN HAND MODE) [16] [16] Auto mode active (DRIVE IN AUTO MODE) [17] [17] Sleep mode (SLEEP MODE) [18] [18] Output frequency lower than parameter 223 (F OUT < F LOW) [19] [19] Output frequency higher than parameter 223 (F OUT > F HIGH) [20] [20] Out of frequency range (FREQ. RANGE WARN.) [21] [21] Output current lower than low current, parameter 221 (I OUT < I LOW) [22] [22] Output current higher than high current, parameter 222 (I OUT > I HIGH) [23] [23] Out of current range (CURRENT RANGE WARN) [24] [24] Out of feedback range (FEEDBACK RANGE WARN.) [25] [25] Out of reference range (REFERENCE RANGE WARN) [26] [26] Relay 123 (RELAY 123) [27] [27] Input phase loss (MAINS PHASE LOSS) [28] [28] Output frequency, (OUT. FREQ. 0-20 mA) [29] [29] Output frequency, (OUT. FREQ. 4-20 mA) [30] ★ [30] Output frequency (pulse sequence), (OUT. FREQ. PULSE) [31] [31] External reference, (EXT. REF. 0-20 mA) [32] [32] External reference, (EXTERNAL REF. 4-20 mA) [33] [33] External reference (pulse sequence), (EXTERNAL REF. PULSE) [34] [34] Feedback, (FEEDBACK 0-20 mA) [35] [35] Feedback, (FEEDBACK 4-20 mA) [36] [36] Feedback (pulse sequence), (FEEDBACK PULSE) [37] [37] Output current, 0-20 mA (MOTOR CUR. 0-20mA) [38] [38] Output current, 4-20 mA (MOTOR CUR. 4-20mA) ★ [39] [39] Output current (pulse sequence), (MOTOR CUR PULSE) [40] [40] Output power, 0-20 mA (MOTOR POWER 0-20mA) [41] [41] Output power, 4-20 mA (MOTOR POWER 4-20mA) [42] [42] Output power (pulse sequence), 0- 32000 pulses (MOTOR POWER PULSE) [43] [43] Controlled by serial bus: 0-20 mA (BUS CONTROL 0-20MA) [44] [44] Controlled by serial bus: 4-20 mA (BUS CONTROL 4-20MA) [45] [45] Controlled by serial bus: pulses (BUS CONTROL PULSE) [46] [46]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
58
Page 59
Function:
These outputs can act both as digital and analog outputs. If used as a digital output, a 0 or 24 VDC signal is transmitted. If used as an analog output, either a 0 to 20 mA signal, a 4 to 20 mA signal, or a pulse sequence with a frequency of 0 to up to 32,000 Hz is transmitted.
Description of choice:
No function. Selected if this output is always to remain off.
Drive ready. The drives control card receives a supply voltage and
the drive is ready for operation.
Output frequency lower than low frequency warning level. The output frequency is lower than the value set in parameter 223,
Warning: Low Frequency.
Output frequency higher than high frequency warning level.
The output frequency is higher than the value set in parameter 224,
Warning: High Frequency.
Out of frequency range. The output frequency is outside the frequency range programmed in parameter 223, Warning: Low Frequency, and 224, Warning: High Frequency.
Stand by. The drive is ready for operation, but no start command has been given. No warning.
Running. The drive is running or the drive is in the sleep mode.
Running at ref. value. The drive is at the speed commanded by the
reference.
Running, no warning. The drive is running and there are no warnings.
Local reference active. The motors speed is being controlled by the local reference through the keypad. This output will also be on if the drive is set up for local speed control but the jog function has been activated.
Remote references active. The motors speed is being controlled by a remote reference or a preset speed.
Alarm. The drive has been stopped by an alarm.
Alarm or warning. An alarm or a warning exists in the drive.
No alarm. The drive has no alarm.
Current limit. The output current is greater than or equal to the value
programmed in parameter 215, Current Limit. The speed of the drive is being limited to keep the current from increasing.
Output current lower than low current warning level. The output current is lower than the value set in parameter 221, Warning: Low Current. This can be used to indicate a broken belt.
Output current higher than high current warning level. The output current is higher than the value set in parameter 222, Warning:
High Current.
Out of current range. The output current is outside the range programmed in parameter 221, Warning: Low Current, and parameter
Warning: High Current.
222,
Out of feedback range. The feedback signal is outside the range programmed in parameter 227 Warning: Low Feedback, and 228
Warning: High feedback.
Out of reference range. The reference is outside the range programmed in parameter 225, Warning: Low Reference, and parameter 226, Warning: High Reference.
Relay 123. This function is only used when a Profibus option card is installed.
Input phase loss. An incoming power phase is missing.
Safety interlock. Terminal 27 has been programmed for Safety
Interlock in parameter 304, and no control voltage has been applied to it.
Start command active. The drive is either running or it has received a run command. This is commonly used in conjunction with the drives run permissive control.
Reversing. The drive is running in the reverse direction.
Thermal warning. The temperature limit of either the motor, the drive,
or a thermistor connected to an analog input has been exceeded.
Hand mode active. The drive is operating in the Hand run/stop mode.
Auto mode active. The drive is operating in the Auto run/stop mode.
Sleep mode. The drive is stopped because of Sleep Mode.
59
Page 60
Output frequency: 0 to 20 mA, 4 to 20 mA, and pulses. An output signal proportional to the output frequency in the range from 0 to Output Frequency, High Limit, set by parameter 202. Maximum pulse frequency is determined in parameters 320, Terminal 42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
External reference: 0 to 20 mA, 4 to 20 mA, and pulses. An output signal proportional to the resulting reference value in the range from Minimum Reference to Maximum Reference, set by parameters 204 and 205. Maximum pulse frequency is determined in parameters 320,
Terminal 42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
Feedback Minimum to Feedback Maximum: 0 to 20 mA, 4 to 20 mA, and pulses. An output signal proportional to the reference value
in the range from Minimum Feedback to Maximum Feedback, set by parameters 413 and 414. Maximum pulse frequency is determined in parameters 320, Terminal 42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
Output Current: to 20 mA, 4 to 20 mA, and pulses. An output signal proportional to the output current in the range from 0 to the maximum drive output current. Maximum pulse frequency is determined in parameters 320, Terminal 42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
Output power: 0 to 20 mA, 4 to 20 mA, and pulses. Generates an output signal proportional to the present output power. 20 mA corresponds to the value set by parameter 102, Motor Power. Maximum pulse frequency is determined in parameters 320, Terminal
42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
Bus Control: 0 to 20 mA, 4 to 20 mA, and pulses. Generates a proportional output signal provided over a serial communication bus. The serial bus value for output terminal 42 is written to parameter 364 and the serial bus value for output terminal 45 is written to parameter
365. Maximum pulse frequency is determined in parameters 320,
Terminal 42, Output Pulse Scaling, and 322, Terminal 45, Output Pulse Scaling.
320 Terminal 42, Output Pulse Scaling
(AO 42 PULS SCALE)
Value:
1 to 32000 Hz 5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
321 Terminal 45, Output
(AO 45 FUNCTION)
Value:
OUT. FREQ. 4 - 20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When used as a digital output, it generates a 24 V (max. 40 mA) signal. For the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a pulse sequence.
Description of choice:
See the description of analog/digital outputs.
322 Terminal 45, Output Pulse Scaling
(AO 45 PULS SCALE)
Value:
1 to 32000 Hz 5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
319 Terminal 42, Output
(AO 42 FUNCTION)
Value:
★ MOTOR CUR. 4-20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When used as a digital output, it generates a 24 V (max. 40 mA) signal. For the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a pulse sequence.
Description of choice:
See the description of analog/digital outputs.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
60
Pulse Scaling
Page 61
Relay Outputs
Relay 1: 1 - 3 normally closed, 1 - 2 normally open
Maximum: 240 VAC/DC, 2 A Minimum: 24 VAC, 100 mA;
Relay 02
Relay 2: 4 - 5 normally open Maximum: 30 VAC, 1 A,
24 VDC, 10 mA The high voltage relay connections are located near the input power and motor terminals.
The low voltage relay terminals are located on the control wiring terminal strips.
Relay outputs Relay Number: 1 2
Parameter: 323 326
Value: No function (NO FUNCTION) [0] [0] Drive ready (READY) [1] [1] Waiting for start (ENABLED & NO WARNING) [2] [2] Running (RUNNING) [3] ★ [3] Running at reference value (RUNNING AT REFERENCE) [4] [4] Running, no warning (RUNNING NO WARNING) [5] [5] Local reference active (DRIVE IN LOCAL REF) [6] [6] Remote controlled references active (DRIVE IN REMOTE REF.) [7] [7] Alarm (ALARM) [8] [8] Alarm or warning (ALARM OR WARNING) [9] [9] No alarm (NO ALARM) ★ [10] [10] Current limit (CURRENT LIMIT) [11] [11] Safety interlock (SAFETY INTERLOCK) [12] [12] Start command active (START SIGNAL APPLIED) [13] [13] Running in reverse (RUNNING IN REVERSE) [14] [14] Thermal warning (THERMAL WARNING) [15] [15] Hand mode active (DRIVE IN HAND MODE) [16] [16] Auto mode active (DRIVE IN AUTO MODE) [17] [17] Sleep mode active (SLEEP MODE) [18] [18] Output frequency lower than low frequency, parameter 223 (F OUT < F LOW) [19] [19] Output frequency higher than high frequency, parameter 224 (F OUT > F HIGH) [20] [20] Out of frequency range (FREQ RANGE WARN.) [21] [21] Output current lower than low current, parameter 221 (I OUT < I LOW) [22] [22] Output current higher than high current, parameter 222 (I OUT > I HIGH) [23] [23] Out of current range (CURRENT RANGE WARN.) [24] [24] Out of feedback range (FEEDBACK RANGE WARN.) [25] [25] Out of reference range (REFERENCE RANGE WARN.) [26] [26] Relay 123 (RELAY 123) [27] [27] Input phase loss (MAINS PHASE LOSS) [28] [28] Control word bit 11/12 (CONTROL WORD 11/12) [29] [29]
42.5 VDC, 1 A
Function:
Relay outputs 1 and 2 can be used to give the present status or a warning. See the description of options in Analog/Digital Outputs.
Control word bit 11/12 [29]. Relay 1 and relay 2 can be activated through serial communication. Bit 11 activates relay 1 and bit 12 activates relay 2.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
If parameter 556, Bus Time Interval Function, becomes active, relay 1 and relay 2 will cut out if they are activated through serial communication.
Description of choice:
Select the output relay function.
61
Page 62
323 Relay 1, Output Function
(RELAY1 FUNCTION)
Function:
NO ALARM Relay 1 is a form C relay that can be used for status indications and warnings. The relay is activated when the programmed condition occurs.
Time delays for relay 1 are programmed in parameter 324, Relay 1, ON Delay, and parameter 325, Relay 1, OFF Delay.
Description of choice:
See data choice and connections under Relay Outputs.
324 Relay 1, ON Delay
(RELAY1 ON DELAY)
Value:
0 to 600 sec. 0 sec.
Function:
This parameter determines the time delay before the relay activates.
Description of choice:
Enter the desired value.
327 Pulse Reference, Maximum Frequency
(PULSE REF. MAX)
Value:
100 to 65,000 Hz at terminal 29 ★ 5,000 Hz 100 to 5,000 Hz at terminal 17
Function:
This parameter is used to set the pulse value that corresponds to the maximum reference, parameter 205, Maximum Reference.
The pulse reference signal can be connected to terminal 17 or 29.
Description of choice:
Set the required maximum pulse reference.
328 Pulse Feedback, Maximum Frequency
(PULSE FDBK MAX.)
Value:
100 to 65,000 Hz at terminal 33 25,000 Hz
Function:
This parameter is used to set the pulse value that corresponds to the maximum feedback value. The pulse feedback signal is connected to terminal 33.
325 Relay 1, OFF Delay
(RELAY1 OFF DELAY)
Value:
0 to 600 sec. 2 sec.
Function:
This parameter determines the time delay before the relay deactivates.
Description of choice:
Enter the desired value.
326 Relay 2, Output Function
(RELAY2 FUNCTION)
Value:
See the functions of relay 1. RUNNING
Function:
Relay 2 is a form A relay that can be used for status indications and warnings. The relay is activated when the programmed condition occurs.
Description of choice:
See data choice and connections under Relay Outputs.
Description of choice:
Set the desired feedback value.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
62
Page 63
Application Functions Parameters 400 through 427
Special functions of the drive are set up in this parameter group. This includes the proportional, integral, derivative controller (PID) and setting the sleep mode function.
Additionally, this parameter group includes:
Reset function Flying start Interference reduction Lossof load Carrier frequency Selectionofprocess units
!
Unintended Start!
With any automatic reset active, digital inputs may cause drive to start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness with automatic reset active could result in death, serious injury, or equipment or property damage.
400 Reset Function (RESET FUNCTION) Value:
Manual reset (MANUAL RESET) [0] Automatic reset x 1 (AUTOMATIC X 1) [1] Automatic reset x 2 (AUTOMATIC X 2) [2] Automatic reset x 3 (AUTOMATIC X 3) [3] Automatic reset x 4 (AUTOMATIC X 4) [4] Automatic reset x 5 (AUTOMATIC X 5) [5] Automatic reset x 10 (AUTOMATIC X 10) [6] Automatic reset x 15 (AUTOMATIC X 15) [7] Automatic reset x 20 (AUTOMATIC X 20) [8]
Infinite automatic reset (INFINITE AUTOMATIC) [9]
401 Automatic Restart Time
(AUTORESTART TIME)
Value:
0 to 600 seconds 10 sec.
Function:
This parameter sets the automatic reset time delay until each reset is attempted. One of the automatic resets must be selected in parameter 400, Reset Function.
Description of choice:
Set the desired time before each restart attempt.
CAUTION
!
Motor Rotation!
When parameter 402, Flying Start, is enabled, motor may turn forward and reverse a few revolutions even with motor stopped. In highly dynamic pumping processes, it is recommended to disable Flying Start function. Using Flying Start in highly dynamic pumping processes could result in injury or equiment or property damage.
402 Flying Start (FLYING START) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1] DC brake and start (DC BRAKE AND START) [3]
Function:
This function makes it possible for the drive to catch a rotating motor when the drive is started. The drive will sense the speed of rotation and direction of rotation of the motor and synchronize with it.
This function is active whenever a start command is present.
For the drive to catch the spinning motor, the motor speed must be lower than the maximum frequency set in parameter 202.
Function:
This parameter allows a choice of manual or automatic reset after a fault trip. There is also a choice of the number of times the unit will attempt to restart. The time between each attempt is set in parameter 401, Automatic Restart Time.
Description of choice:
If Manual Reset is selected, the Reset key must be pressed or a digital input given to reset the drive.
If auto reset after a fault trip is desired, select one of the Automatic reset choices.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
Description of choice:
Select Disable if this function is not required.
Select Enable if the drive is to catch and control a rotating motor.
Select DC brake and start if the drive is to brake the motor by means of the DC brake first, and then start. Ensure that parameters 114 through 116, DC Braking, are set appropriately. Select DC brake and start if the motor may be externally driven at a significant speed in the reverse direction.
NOTE For fan applications, factory setting for Flying Start is Enable. For pump applications, factory setting for Flying Start is Disable.
63
Page 64
Sleep Mode
Sleep mode makes it possible to stop the drive when the system demand drops below a preset level. When the demand increases to a higher preset level, the drive will restart. A significant amount of energy can be saved using sleep mode. Unlike a set-back time clock, the drive is always available to run when the demand reaches the preset wake up level. Sleep mode is not active if Local Reference is selected in parameter 203, Reference Handling, or if the Jog function activates via digital inputs. Sleep mode operates in both Open Loop and Closed Loop.
Activate sleep mode in parameter 403, Sleep Mode Timer. In this parameter, set how long the output frequency must be lower than the sleep frequency set in parameter 404, Sleep Frequency, before sleep mode activates. After the set time, the drive will ramp down the motor to a stop, as controlled by parameter 207, Ramp Down Time. If the output frequency needed to meet the system demand rises above the sleep frequency during the timed period, the drive will simply ramp up to the demanded frequency.
When the sleep mode timer expires and the drive is stopped in sleep mode, a theoretical output frequency is calculated based upon the reference signal. When the theoretical output frequency rises above the frequency set in parameter 405, Wake-up Frequency, the drive will restart the motor and ramp up to the commanded reference.
For closed loop operation, it may be useful to over satisfy the system before putting the drive into sleep mode. The boost setpoint parameter provides for this. After the sleep mode timer expires, the drive will reset the set point based on the value in parameter 406, Boost Setpoint. Once this new setpoint is satisfied, the drive enters sleep mode. A setting of 100% in parameter 406, Boost Setpoint, indicates no setpoint boost. Boost setpoint is only active in Closed Loop, selected in parameter 100, Configuration.
64
Sleep Mode Frequency Response
Page 65
!
Unintended Start!
In Sleep Mode, a start signal via digital inputs may cause drive to start at any time. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness in Sleep Mode could result in death, serious injury, or equipment or property damage.
405 Wake-up Frequency (WAKEUP FREQUENCY) Value:
Parameter 404 to parameter 202, Maximum Frequency
60 Hz
Function:
When the theoretical output frequency exceeds the preset value, the drive restarts the motor.
Description of choice:
Set the required frequency.
403 Sleep Mode Timer (SLEEP MODE TIMER) Value:
0 to 300 seconds (OFF) OFF
Function:
This parameter enables the drive to stop the motor if the load on the system is minimal. The timer starts when the output frequency drops below the frequency set in parameter 404, Sleep Frequency. When the time set has passed, the drive will stop. The drive will restart when the theoretical output frequency exceeds the frequency set in parameter 405, Wake-up Frequency.
Description of choice:
Select OFF if this function is not wanted.
Set the amount of time that the drive must run at or below the sleep frequency before it stops and goes to sleep.
404 Sleep Frequency (SLEEP FREQUENCY) Value:
0.0 to parameter 405, Wake-up Frequency 0.0 Hz
Function:
When the output frequency falls below this set value, the timer set in parameter 403, Sleep Mode Timer, will start. The drives speed will follow the reference signal until the timer times out.
406 Boost Setpoint (BOOST SETPOINT) Value:
0 to 200 % 100 % of setpoint
Function:
This function can only be used if Closed Loop has been selected in parameter 100, Configuration.
In some systems, it may advantageous to increase the set point of the system before the drive stops the motor. This extends the time that the drive will be stopped and reduces cycling of the motor.
Description of choice:
Set the required Boost Setpoint as a percentage of the resulting reference under normal operation. 100% corresponds to the boost.
Description of choice:
Choose the output frequency at which the drive will activate the sleep mode timer. It is generally best to set SLEEP FREQUENCY equal to the minimum frequency set in parameter 201, Output Frequency Low Limit and parameter 204, Minimum Reference. This is because the sleep mode isnt active until after the drive output frequency equals the sleep frequency. If the sleep frequency is less than the minimums, the sleep mode cannot activate.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
65
Page 66
407 Switching Frequency (SWITCHING FREQ.) Value:
Depends on the current rating of the unit.
Function:
The value of this parameter determines the maximum switching frequency of the inverter. If Fixed Switching Frequency has been selected in parameter 408, Interference Reduction Method, this will be the fixed inverter switching frequency. Changing the switching frequency may reduce audible noise from the motor. The output frequency of the drive can never be a greater than 1/10 of the switching frequency.
Description of choice:
When the motor is running, the switching frequency may be adjusted by parameter 407, Switching Frequency, until the sound level is as low as possible.
408 Interference Reduction Method
(NOISE REDUCTION)
Value:
ASFM (ASFM) [0]
Fixed switching freq. (FIXED SWITCHING FREQ.) [1] LC filter fitted (LC-FILTER CONNECTED) [2]
Function:
Used to select different methods for reducing the amount of audible noise from the motor.
Description of choice:
ASFM (Automatic Switching Frequency Modulation) uses the maximum switching frequency possible while providing the output required by the load. The load is automatically monitored and the switching frequency set accordingly. The maximum switching frequency is set in parameter 407, Switching Frequency.
Switching frequencies higher than 4.5 kHz will result in automatic derating of the maximum continuous output current of the drive. The derate is linear from 4.5 kHz to the maximum switching frequency of the drive. At maximum switching frequency, the continuous output current from the drive will be limited to 60% of the rated current. To avoid possible problems at high load when using a high switching frequency, it may be desirable to select Automatic Switching Frequency Modulation in parameter 408, below.
NOTE Switching frequencies higher than 4.5 kHz automatically derate maximum continuous output of drive.
FixedSwitching Frequency makes it possible to set a fixed switching frequency. The switching frequency is set in parameter 407, Switching
Frequency.
LC-filter fitted is to be used if an LC filter is installed between the drive
and the motor. This prevents excessive heating of the LC filter.
409 Function in Case of No Load
(FUNCT. LOW CURR.)
Value:
Trip (TRIP) [0]
Warning (WARNING) [1]
Function:
This parameter can be used for monitoring the V-belt of a fan or other power transmission component to make sure it has not broken. This function is activated when the output current goes below the current level set in parameter 221, Warning: Low Current. This function is not active during a start until the drive has reached the speed reference. It is also not active while the drive is stopped or while it is decelerating to a stop.
Description of choice:
In the case of a Trip, the drive will stop the motor if the output current drops below the value set in parameter 221.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
66
If Warning is selected, the drive will give a warning if the output current drops below the value set in parameter 221.
Page 67
410 Function at Input Phase Loss
(MAINS IMBALANCE)
Value:
Trip (TRIP) [0] Autoderate & Warning (AUTODERATE & WARNING) [1] Warning (WARNING) [2]
Function:
This determines the action of the drive when one of the incoming power phases is lost. Some action is required to control the level of ripple voltage on the DC bus to avoid damage to the DC bus capacitors. Drive display will show MAINS PHASE LOSS.
411 Function at Drive Overtemperature
(FUNCT. OVERTEMP)
Value:
Trip (TRIP) [0] Autoderate & Warning (AUTODERATE & WARNING) [1]
Function:
Select the function to be activated when the drive is exposed to an overtemperature condition.
Description of choice:
At Trip, the drive stops the motor and exports an alarm.
Description of choice:
At Trip, the drive stops the motor within a few seconds (depending on drive size).
If Autoderate & Warning is selected, the drive will export a warning and reduce the output current to 30% of maximum current to maintain operation.
CAUTION
Input Phase Loss!
If Warning is selected, life expectancy of the drive could be reduced if input phase loss persists. Select Warning only when input phase loss is known to be temporary.
At Warning, only a warning will be exported when an input phase loss occurs, but in severe cases, other extreme conditions might result in a trip.
For drives with software version 2.0 or later, select Autoderate & Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
CAUTION
At Autoderate & Warning, the drive first reduces the switching frequency to minimize internal loss. If the overtemperature condition persists, the drive reduces the output current until the heat sink temperature stabilizes. A warning is issued when the function is active.
For drives with software version 2.0 or later, select Autoderate & Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
412 Trip Delay Overcurrent
(OVERLOAD DELAY)
Value:
OFF or 0 to 60 sec. OFF
Function:
When the output current has reached the current limit set in parameter 215, Current Limit, and remains there for the time selected in this parameter, the drive will trip.
Description of choice:
Select how long the drive will run in current limit before it trips.
Overheating Hazard!
At phase loss, the cooling fan of NEMA 12 drives cannot be powered. To avoid overheating, an external power supply can be connected. Contact Trane for further information. Failure to provide fan cooling may result in equipment damage.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
67
Page 68
Feedback Signals in Open Loop
In some drives, feedback signals and feedback parameters are only used in closed loop operation. In the TR1, the feedback signals are also active in open loop operation. Although they dont effect the speed of the drive, they can be displayed on the drives meters. Parameters 227 and 228 can set high and low limits for the feedback signals, which can activate warnings.
For open or closed loop operation, the feedback signal is scaled in parameters 413 and 414 Minimum and Maximum Feedback, and the unit displayed is chosen in parameter 415, Process Units.
413 Minimum Feedback
(MIN. FEEDBACK)
Value:
-999,999.999 to Maximum Feedback, Parameter 414 ★ 0.000
Function:
Parameters 413 Minimum Feedback and 414 Maximum Feedback, are used to scale the feedback signal.
Description of choice:
Set the value to be shown on the display when the feedback signal is at its minimum value.
415 Units Relating to Closed Loop
(REF. / FDBK. UNIT)
Value:
No unit [0] °C [21]
% [1] GPM [22]
rpm [2] gal/s [23] ppm [3] gal/min [24] pulse/s [4] gal/h [25] l/s [5] lb/s [26] l/min [6] lb/min [27] l/h [7] lb/h [28] kg/s [8] CFM [29] kg/min [9] ft3/s [30] kg/h [10] ft3/min [31] m3/s [11] ft3/h [32] m3/mi n [1 2] ft/s [ 33] m3/h [13] in wg [34] m/s [14] ft wg [35] mbar [15] PSI [36] bar [16] lb/in
2
Pa [17] HP [38] kPa [18] °F [39] m wg [19] kW [20]
[37]
414 Maximum Feedback
(MAX. FEEDBACK)
Value:
Minimum Feedback to 999,999.999 100.000
Function:
See the description of parameter 413, Minimum Feedback.
Description of choice:
Set the value to be shown on the display when the feedback signal is at its maximum value.
Function:
Selects the unit shown on the feedback display.
The selected unit is used if Reference [unit] or Feedback [unit] has been selected in one of the parameters 007 through 010, as well as in the Display Mode. It will be the unit for Minimum/Maximum Feedback. In Closed Loop, the unit is also used as the unit for Minimum/Maximum Reference and Minimum/Maximum Feedback, as well as Setpoint 1 and Setpoint 2.
Description of choice:
Select the unit for the reference/feedback signal.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
68
Page 69
PID for Process Regulation
The built-in proportional, integral, derivative (PID) controller in the drive maintains a constant condition (pressure, temperature, flow, etc.) in the system. It adjusts motor speed based upon a reference and/or setpoint and the feedback signal. The PID controller is activated by setting parameter 100, Configuration, to Closed loop.
Reference (Setpoint)
In parameter 205, Maximum Reference, the maximum value of the sum of all reference signals is set.
The Minimum Reference, set in parameter 204, indicates the smallest value that the resulting reference can assume.
A transmitter supplies the PID controller with a feedback signal from the process to indicate its current state. The type of feedback signal in use depends upon the type of process.
This means that deviations that occur between the reference/setpoint and the actual process state are sensed. Such deviations are compensated for by the PID regulator by adjusting the output frequency as required by the difference (or error) between the reference/setpoint and the feedback signal.
The PID controller in the drive has been designed for use in HVAC applications and to perform a number of specialized functions. Previously, it was necessary for a building management system to handle these special functions by installing extra modules to program the system.
With the TR1, there is no need for extra modules to be installed. Only the reference and/or setpoint and a selected feedback signal need to be programmed. An advanced feature of the TR1 is the drives ability to accept two feedback signals, making two-zone regulation possible.
Voltage drop in long control cables can be compensated for by using the scaling parameters for the analog inputs.
Feedback
The feedback signal must be connected to the drive according to the table below, depending on the type of feedback signal and the settings of the associated parameters listed.
The reference range cannot exceed the feedback range.
If multiple Preset References are required, use multiple setups or set them in parameters 211 to 214 Preset Reference. See Reference Handling.
If a current signal is used as a feedback signal, voltage can be used as an analog reference. Use the table below to decide which terminal to use and which parameters to program.
Reference type Terminal Parame ters Pulse 17 or 29 301 or 305 Voltage 53 or 54 308, 309, 310 or
311, 312, 313 Current 60 314, 315, 316 Preset reference 211, 212, 213, 214 Setpoints 418, 419 Bus reference * 68 and 69 * The bus reference can only be set by serial communication.
Terminals that are not used should be set to No function.
Inverse Regulation
Normal regulation means that the motor speed increases when the reference/setpoint is higher than the feedback signal. Inverse regula­tion means that the motor speed decreases when the reference/setpoint is higher than the feedback signal. If there is a need for inverse regulation, inverse must be programmed in parameter 420, PID
Normal/Inverse Control.
Feedback type Terminal Parameter s Pulse 33 307 Voltage 53 or 54 308, 309, 310 or
Current 60 314, 315, 316 Bus feedback 1* 68 and 69 537 Bus feedback 2* 68 and 69 538 * The bus feedbacks can only be set by serial communication.
If two analog feedback signals are to be used, they both must be voltage signals.
The Minimum Feedback and Maximum Feedback, parameters 413 and 414, must be set for the feedback signals. The type of process unit for the signals is selected in parameter 415, Process Units.
311, 312, 313
Anti-windup
The process controller is factory set with an active anti-windup function. This function ensures that when either a frequency limit or a current limit is reached, the integrator will be reset to zero. If the frequency limit or current limit is cleared, the integrator will turn on again. This function can be disabled in parameter 421, PID Anti-windup.
Start-up Conditions
In some applications, the optimum setting of the process regulator takes a long time to reach. In such cases, a start-up frequency can be entered in parameter 422, PID Start-up Frequency. The drive will ramp directly to this frequency before PID control begins. This avoids control by deviation between the reference/setpoint and the actual state of the process during acceleration. It also avoids overshoot of the process requirement during acceleration due to lag in the feedback signal.
69
Page 70
Differentiator Gain Limit
The differentiation control reacts to the rate of change of the error between the setpoint and the feedback signal. This is seldom needed for HVAC applications. If the differentiation function becomes too dominant, the differentiation factor can be limited. This is done in parameter 426, PID Differentiator Gain Limit.
Lowpass Filter
Noise on the feedback signal can be reduced by using the built-in lowpass filter. Set a suitable lowpass filter time constant. This time constant determines the cutoff frequency of the filter.
If the lowpass filter has been set to 0.1s, the cut-off frequency will be 10 RAD/sec., corresponding to (10/2 x π) = 1.6 Hz. This means that any noise on the feedback signal whose frequency is greater than 1.6 Hz will be filtered out. Choose a suitable time constant in parameter 427, PID Lowpass Filter Time.
Optimization of the Process Regulator
The basic settings have now been made; all that remains to be done is to optimize the proportional gain, the integration time and, if needed, the differentiation time. These are set by parameters 423, 424 and 425. In most processes, this can be done by following the guidelines below.
PID Overview
The block diagram below shows reference and setpoint in relation to the feedback signal.
As can be seen, the remote reference is added to Setpoint 1 or Setpoint 2. The setpoint that is active depends on the value of parameter 417, Feedback Function.
1. Start the motor.
2. Set parameter 423, PID Proportional Gain, to 0.3 and increase it until the feedback signal becomes unstable. Then reduce the value until the feedback signal has stabilized. Now lower the proportional gain by about half (40% to 60%).
3. Set parameter 424, PID Integration Time, to 20 seconds and reduce the value until the feedback signal becomes unstable. Increase the integration time until the feedback signal stabilizes. Now increase the integration time from 15% to 50%.
4. Parameter 425, PID Differentiation Time, is only used in very fast-acting systems and should be left off for most HVAC applica­tions. When it is used, the typical value is 1/4th the value set in parameter 424, PID Integration Time. The differentiator should only be used when the setting of the proportional gain and the integration time have been fully optimized.
Starting and stopping the drive will produce the necessary error signal in the process to set the PID.
Feedback Handling
Handling of the feedback signal(s) can be seen from the block diagram on the next page. The block diagram shows how and by which parameters the feedback handling is affected.
Feedback signals can be voltage, current, pulse and bus feedback signals. In two zone feedback systems, both feedback signals must be voltage signals (terminals 53 and 54). Please note that Feedback 1 consists of bus feedback 1, (parameter 537) added to the feedback signal value of terminal 53. Feedback 2 consists of bus feedback 2, (parameter 538) added to the feedback signal value of terminal 54.
In addition, the drive has an internal calculator capable of converting a pressure signal into a linear flow feedback signal. This function is activated in parameter 416, Feedback Conversion.
The parameters for feedback handling are active both in closed and open loop modes. In open loop, the feedback signal can be displayed on one of the drives meters and the drive can produce warnings if the feedback signal is beyond the range set in parameters 227, Warning: Low Feedback and 228, Warning: High Feedback.
70
Page 71
Feedback Handling (continued)
During closed loop operation, there are three ways to use the PID controller and setpoint and feedback signals:
1 setpoint and 1 feedback 1 setpoint and 2 feedbacks 2 setpoints and 2 feedbacks
1 Setpoint and 2 Feedbacks
Depending on the feedback function selected in parameter 417, Feedback Function, the two feedback signals will be compared to the setpoint. A description of the individual feedback functions is given in parameter 417. As above, parameter 418, Setpoint 1, will be added to the remote reference, if a remote reference is used.
1 Setpoint and 1 Feedback
In HVAC applications it is often possible to place a pressure or temperature sensor at the farthest significant load and measure actual pressure or temperature in the system. In these cases, the drive's PID controller can respond to system changes, as programmed. When only one setpoint and one feedback signal are used, the drive responds to the feedback signal to match the programmed setpoint in parameter 418, Setpoint 1. (If a remote reference is used, it will be added to the setpoint.)
2 Setpoints and 2 Feedbacks
Whenever two critical zones do not have the same setpoint value, two feedback with two setpoint control is required. Many pumping systems require the monitoring and control of two loads that differ in size and pressure drop. Or this can be effective when controlling different temperature zones in cooling or heating applications. Parameter 418, Setpoint 1, is the setpoint for zone 1. Feedback for zone 1 is the feedback signal at terminal 53. Parameter 419, Setpoint 2, is the setpoint for zone 2 and terminal 54 for feedback 2. Bus Feedback 1 and 2 (parameters 535 and 536) are added to their respective feedback signals, when serial bus data is added to the zone control.
Parameter 417, Feedback Function, selects whether the drive will attempt to have both feedback signals meet the minimum (2 zone min.) or maximum (2 zone max.) to their respective setpoints.
71
Page 72
416 Feedback Conversion
(FEEDBACK CONV.)
Value:
Linear (LINEAR) [0]
Square root (SQUARE ROOT) [1]
Function:
In this parameter, a function is selected which converts a feedback signal from the process to a feedback value that equals the square root of the connected signal.
Function:
This parameter determines the calculation method for two feedback signals. Terminals 53 and 54 are both read in selections [0] through [6]. In each case, if only one feedback signal is received, a zero value will be calculated for the inactive terminal. To read feedback from only one of the two terminals, use Feedback 1 Only (terminal 53) or
Feedback 2 Only (terminal 54) to exclude the inactive terminal.
Feedback 1 = Sum of parameter 535, Bus Feedback 1, (if present) and
the feedback signal value of terminal 53.
This can be used where regulation of a flow is required and the feedback is from a pressure sensor (flow is proportional to the square root of pressure). This conversion makes it possible to set the reference in such a way that there is a linear connection between the reference and the flow required. See diagram below.
Feedback conversion should not be used if two-zone regulation has been selected in parameter 417, Feedback Function.
Description:
If Linear is selected, the feedback signal and the feedback value will be proportional.
If Square root is selected, the drive first takes the square root of the feedback signal.
TR1 drive
Feedback 2 = Sum of parameter 536, Bus Feedback 2, (if present) and the feedback signal value of terminal 54.
Description of choice:
If Minimum is selected, the drive will compare Feedback 1 wi th Feedback 2 and regulate on the basis of the lower feedback value.
If Maximum is selected, the drive will compare Feedback 1 with Feedback 2 and regulate on the basis of the higher feedback value.
If Sum is selected, the drive will total Feedback 1 wit h Feedback 2.
If Difference is selected, the drive will subtract Feedback 1 from Feedback 2.
If Average is selected, the drive will calculate the average of Feedback 1 and Feedback 2.
If 2-zone Minimum is selected, the drive will calculate the difference between Setpoint 1 and Feedback 1 as well as Setpoint 2 and Feedback 2. The drive will regulate its output speed based on the larger difference. A positive difference, (a setpoint higher than the feedback), is always larger than a negative difference.
If 2-zone Maximum is selected, the drive will calculate the difference between Setpoint 1 and Feedback 1 as well as Setpoint 2 and Feedback 2. After the calculation, the drive will use the smaller difference. A negative difference (a setpoint lower than the feedback) is always smaller than a positive difference.
417 Feedback Function
(2 FEEDBACK, CALC.)
Value:
Minimum (MINIMUM) [0]
Maximum (MAXIMUM) [1]
Sum (SUM) [2] Difference (DIFFERENCE) [3] Average (AVERAGE) [4] Two-zone minimum (2 ZONE MIN) [5] Two-zone maximum (2 ZONE MAX) [6] Feedback 1 only (FEEDBACK 1 ONLY) [7] Feedback 2 only (FEEDBACK 2 ONLY) [8]
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
72
If Feedback 1 Only is selected, terminal 53 is read as the feedback signal and terminal 54 ignored. Feedback 1 is compared to Setpoint 1 for drive control.
If Feedback 2 Only is selected, terminal 54 is read as the feedback signal and terminal 53 ignored. Feedback 2 is compared to Setpoint 2 for drive control.
NOTE Value of parameter 418, Setpoint 1, is added to any remote reference when Minimum, Maximum, Sum, Difference or Average is selected.
Page 73
418 Setpoint 1
(SETPOINT 1)
Value:
Feedback Minimum to Feedback Maximum ★ 0.000
Function:
Setpoint 1 is used to provide the setpoint reference for PID control with one feedback signal. It is also used for the setpoint for zone one in two-setpoint PID control. External and preset references may be added to its value.
In open loop, Setpoint 1 should be set to 0 to prevent parameter 417, Feedback Function, from affecting the reference.
See description of parameter 417, Feedback Function.
Description of choice:
Set the desired value within the programmed minimum and maximum. The process unit is selected in parameter 415, Process Units.
419 Setpoint 2
(SETPOINT 2)
Value:
Feedback minimum to Feedback maximum ★ 0.000
421 PID Anti-windup
(PID ANTI WINDUP)
Value:
Off (DISABLE) [0]
On (ENABLE) [1]
Function:
It is possible to choose whether the PID controller integrator is to continue to sum the error signal when it is not possible to increase or decrease the output frequency to correct the error.
Used in Closed Loop, parameter 100.
Description of choice:
The factory setting is On, which means that the error integrator is cleared if either the current limit, the voltage limit or the maximum or minimum frequency has been reached. The integrator will not function again until regulation is possible. Select Off if the integrator is to continue integrating even if it is not possible to correct the error.
422 PID Start-up Frequency
(PID START VALUE)
Value:
Minimum frequency to maximum frequency
(set by parameters 201 and 202) 0 Hz
Function:
Setpoint 2 is used to provide the setpoint reference for zone two in two-zone PID. In open loop, Setpoint 2 should be set to 0, to prevent parameter 417, Feedback Function, from affecting the reference.
See description of parameter 417.
Description of choice:
Set the required value. The process unit is selected in parameter 415, Process Units.
420 PID Normal/Inverse Control
(PID NOR/INV. CTRL)
Value:
Normal (NORMAL) [0]
Inverse (INVERSE) [1]
Function:
This determines how the drives PID controller responds to an error between the setpoint and feedback.
Used in Closed Loop, (parameter 100).
Description of choice:
Select normal when the drive is to reduce the output frequency as the feedback signal increases.
Function:
Each time the drive is given a start command, the start-up frequency is the speed the drive accelerates to before PID control is activated. The drive will follow the acceleration ramp when a start signal is received as if in open loop. When the programmed start-up frequency is reached, it will change to closed loop operation.
Used in Closed Loop, parameter 100.
Description of choice:
Set the required start frequency. For software versions prior to 2.0, do not set this frequency between 0.1 and 7.7 Hz.
NOTE If drive is running in current limit before desired start frequency is obtained, PID control will not be activated. To avoid this, start frequency must be low enough to ensure drive does not go into current limit. This can be done during operation.
Select inverse when the drive is to increase the output frequency as the feedback signal increases.
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
73
Page 74
423 PID Proportional Gain
(PID PROP. GAIN)
Value:
0.00 to 10.00 0.30
426 PID Differentiator Gain Limit
(PID DIFF. GAIN)
Value:
5.0 to 50.0 5.0
Function:
The proportional gain determines how fast the system responds to a change in feedback.
Used in Closed Loop, parameter 100.
Description of choice:
Quick regulation is obtained by a high gain, but, if the gain is too high, the process may become unstable. See Optimization of the Process Regulator for information on proper adjustment.
424 PID Integral Time
(PID INTEGR.TIME)
Value:
0.01 to 9999.00 sec. (OFF) OFF
Function:
The integrator adds the error signal over time and uses this to correct the speed of the drive.
The integral time is the time needed by the integrator to have the same effect as the proportional gain.
Used in Closed Loop parameter 100.
Description of choice:
Fast regulation is obtained by setting a short integration time. However, if this time is too short, the process will overcorrect and become unstable. See Optimization of the Process Regulator for information on proper adjustment.
425 PID Differentiation Time
(PID DIFF. TIME)
Value:
0.00 (OFF) to 10.00 sec. OFF
Function:
When the differentiator is used, fast changes in the error can sometimes cause unstable operation. In these cases it may be useful to limit the contribution of the differentiator.
Used in Closed Loop, parameter 100.
Description of choice:
A lower limit will improve stability, but will reduce the effect of the differential.
427 PID Lowpass Filter Time
(PID FILTER TIME)
Value:
0.01 to 10.00 0.01
Function:
Noise on the feedback signal can be reduced by the lowpass filter.
Used in Closed Loop, parameter 100.
Description of choice:
Select the desired time constant (t).
The cut off frequency equals ½πt. For example, if a time constant of 0.1 s is programmed, the cut off frequency for the lowpass filter will be 1/[2π (.1)] = 1.6 Hz.
The PID controller will then only respond to changes in the feedback signal whose frequency is less than 1.6 Hz.
Function:
The differentiator responds to the rate of change of the error signal.
The quicker the error changes, the greater the response from the differentiator.
Used in Closed Loop, parameter 100.
Description of choice:
Fast regulation can be obtained by means of a long differentiation time. If this time is too long, the process may overshoot. The differentiator is generally set of OFF in HVAC applications. See Optimization of the Process Regulator for information on proper adjustment.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
74
Page 75
Serial Communication Parameters 500 through 571
This parameter group sets up the drive for serial communication.
There is a choice of four protocols: FC (firmware protocol), Johnson Controls Metasys N2, Siemens FLN, and Modbus RTU. In order to use serial communication to control the drive, address and baud rate must always be set. In addition to controlling the drive, operational data from the drive including reference, feedback, motor temperature and others can be read through serial communication.
500 Protocol
(PROTOCOL)
Value:
FC protocol (FC PROTOCOL) [0]
Metasys N2 (METASYS N2) [1] Siemens FLN (FLN) [2] Modbus RTU (MODBUS RTU) [3]
Function:
There is a choice of four different serial communication protocols.
Description of choice:
The transmission speed of the drive must be set at a value that corresponds to the transmission speed of the master. Parameter 502, Baud Rate, cannot be selected through serial communication; it must be set by the keypad. The data transmission time itself, which is determined by the baud rate selected, is only part of the total communication time.
503 Coasting Stop
(COASTING)
Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
In parameters 503 through 508, a choice can be made to control the drive via the digital inputs and/or by serial communication.
If Digital input is selected, the command can only be carried out through digital input.
Description of choice:
Select the required control word protocol.
501 Address
(ADDRESS)
Value:
Parameter 500 Protocol = FC protocol
0 through 126 ★1
Parameter 500 Protocol = Metasys N2
1 through 255 1
Parameter 500 Protocol = FLN
0 through 98 1
Parameter 500 Protocol = Modbus RTU
0 through 247 1
Function:
In this parameter it is possible to allocate an address in a serial communication network to each drive.
Description of choice:
The individual drive must be given a unique address. If the number of drives exceeds 31, a repeater must be used. Parameter 501, Address, cannot be chosen via serial communication but is set via the keypad.
502 Baud Rate
(BAUDRATE)
Value:
300 Baud (300 BAUD) [0] 600 Baud (600 BAUD) [1] 1200 Baud (1200 BAUD) [2] 2400 Baud (2400 BAUD) [3] 4800 Baud (4800 BAUD) [4]
9600 Baud (9600 BAUD) [5]
Function:
In this parameter, the speed at which data is transmitted via serial communication is programmed. Baud rate is defined as the number of bits transmitted per second.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
If Serial communication is selected, the command can only be carried out through serial communication.
If Logic and is selected, the command must be by both serial communi- cation and a digital input.
If Logic or is selected, the command can be made by either digital or serial communication.
Description of choice:
The tables below show whether the motor is running or coasting when Digital Input, Serial Communication, Logic and or Logic or has been selected.
NOTE Terminal 27 and bit 03 of control word are active when logic 0 is selected.
Digital Input Serial Communication
Serial Serial
Term. 27 Comm. F un ct ion Term. 27 Comm. F unction
0 0 Coasting 0 0 Coasting 0 1 Coasting 0 1 Motor run 1 0 Motor run 1 0 Coasting 1 1 Motor run 1 1 Motor run
Logic and Logic or
Serial Serial
Term. 27 Comm. Fu nc tion Term. 27 Comm. F unction
0 0 Coasting 0 0 Coasting 0 1 Motor run 0 1 Coasting 1 0 Motor run 1 0 Coasting 1 1 Motor run 1 1 Motor run
75
Page 76
504 DC Brake
(DC BRAKE)
Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
505 Start
(START)
Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter 503, Coasting Stop.
Description of choice:
The table below shows when the motor is running and is DC-braking when Digital input, Serial communication, Logic and or Logic or has been selected.
NOTE DC braking inverse, through terminals 19 and 27, and bit 03 of the control word, is active when logic 0 is selected.
Digital Input Serial Communication
Term. Serial Term. Serial 19/27 Comm. Function 19/27 Comm. Function
0 0 DC brake 0 0 DC brake 0 1 DC brake 0 1 Motor run 1 0 Motor run 1 0 DC brake 1 1 Motor run 1 1 Motor run
Logic and Logic or
Term. Serial Term. Serial 19/27 Comm. Function 19/27 Comm. Function
0 0 DC brake 0 0 DC brake 0 1 Motor run 0 1 DC brake 1 0 Motor run 1 0 DC brake 1 1 Motor run 1 1 Motor run
Function:
See the functional description under parameter 503, Coasting Stop.
Description of choice:
The table below shows when the motor has stopped and gives the situations in which the drive has a start command when Digital input, Serial communication, Logic and or Logic or has been selected.
Digital Input Serial Communication
Serial Serial
Term. 18 Comm. F unction Term. 18 Comm. Functio n
00Stop00Stop 01Stop01Start 10Start10Stop 11Start11Stop
Logic and Logic or
Serial Serial
Term. 18 Comm. Fu nction Term. 18 Comm. Function
00Stop00Stop 01Stop01Start 10Stop10Start 1 1 Start 1 1 Start
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
76
Page 77
506 Reversing
(REVERSING)
Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2] Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter, 503 Coasting Stop.
Description of choice:
The table below shows when the motor is running forward and reverse when Digital input, Serial communication, Logic and o r Logic or has been selected.
Digital Input Serial Communication
Serial Serial
Term. 19 Comm. F unction Term. 19 Comm. Function
0 0 Forward 0 0 Forward 0 1 Forward 0 1 Forward 1 0 Reverse 1 0 Forward 1 1 Reverse 1 1 Reverse
Logic and Logic or
Serial Serial
Term. 19 Comm. Fu nction Term. 19 Comm. Function
0 0 Forward 0 0 Forward 0 1 Forward 0 1 Reverse 1 0 Forward 1 0 Reverse 1 1 Start 1 1 Reverse
507 Selection of Setup
(SELECTING OF SETUP)
508 Selection of Preset Reference
(SELECTING OF SPEED)
Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description for parameters 507 and 508 under parameter 503, Coasting Stop.
Description of choice:
The table below shows the Setup (parameter 002 Active Setup) that has been selected via Digital input, Serial communication, Logic and or Logic or. The table also shows the preset reference (parameters 211 through 214, Preset reference) that has been selected via Digital
input, Serial communication, Logic and or Logic or.
Digital Input
Bus Bus Setup/Preset Setup/Preset Setup No. Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1 00 0 1 2 00 1 0 3 00 1 1 4 01 0 0 1 01 0 1 2 01 1 0 3 01 1 1 4 10 0 0 1 10 0 1 2 10 1 0 3 10 1 1 3 11 0 0 1 11 0 1 2 11 1 0 3 11 1 1 4
Se rial Communic ati on
Bus Bus Setup/Preset Setup/Preset Setup No. Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1 00 0 1 1 00 1 0 1 00 1 1 1 01 0 0 2 01 0 1 2 01 1 0 2 01 1 1 2 10 0 0 3 10 0 1 3 10 1 0 3 10 1 1 3 11 0 0 4 11 0 1 4 11 1 0 4 11 1 1 4
Logic and
Bus Bus Setup/Preset Setup/Preset Setup No. Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1 00 0 1 1 00 1 0 1 00 1 1 1 01 0 0 1 01 0 1 2 01 1 0 1 01 1 1 2 10 0 0 1 10 0 1 1 10 1 0 3 10 1 1 3 11 0 0 1 11 0 1 2 11 1 0 3 11 1 1 4
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
77
Page 78
Logic or
Bus Bus Setup/Preset Setup/Preset Setup No. Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1 00 0 1 2 00 1 0 3 00 1 1 4 01 0 0 2 01 0 1 4 01 1 0 2 01 1 1 3 10 0 0 3 10 0 1 4 10 1 0 3 10 1 1 4 11 0 0 4 11 0 1 4 11 1 0 4 11 1 1 4
509 through 532, 537 Data Read-out
Value:
Parameter Description Display Text Unit
No. Interval
509 Reference % (REFERENCE %) % 80 msec. 510 Reference [unit] (REFERENCE [UNIT]) Hz, rpm 80 msec. 511 Feedback [unit] (FEEDBACK) Par. 415 80 msec. 512 Frequency [Hz] (FREQUENCY) Hz 80 msec. 513 User-defined readout (CUSTOM READOUT) Hz x scaling 80 msec. 514 Motor current [A] (CURRENT) Amp 80 msec. 515 Power [kW] (POWER KW) kW 80 msec. 516 Power [hp] (POWER HP) HP 80 msec. 517 Motor voltage [V] (MOTOR VOLT) VAC 80 msec. 518 DC link voltage [V] (DC LINK VOLTAGE) VDC 80 msec. 519 Thermal load, motor [%] (MOTOR TEMPERATURE) % 80 msec. 520 Thermal load, TR1 [%] (TR1 TEMPERATURE) % 80 msec. 521 Digital input (DIGITAL INPUT) Binary 80 msec. 522 Terminal 53, analog input [V] (TERMINAL 53, ANALOG INPUT) Volt 20 msec. 523 Terminal 54, analog input [V] (TERMINAL 54, ANALOG INPUT) Volt 20 msec. 524 Terminal 60, analog input [mA] (TERMINAL 60, ANALOG INPUT) mA 20 msec. 525 Pulse reference [Hz] (PULSE REFERENCE) Hz 20 msec. 526 External reference [%] (EXTERNAL REFERENCE) % 20 msec. 527 Status word (STATUS WORD HEX) Hex 20 msec. 528 Heat sink temperature [°C] (HEAT SINK TEMP.) °C 1.2 sec. 529 Alarm word (ALARM WORD, HEX) Hex 20 msec. 530 Control word (TR1 CONTROL WORD, HEX) Hex 2 msec. 531 Warning word (WARNING WORD) Hex 20 msec. 532 Extended status word (STATUS WORD) Hex 20 msec.
***** ***** ***** ***** *****
537 Relay status (RELAY STATUS) Binary 20 msec.
Updating
78
Page 79
Function:
These parameters are read-only through the serial communication port. To display drive functions on the drive display, see parameters 007 through 010, Display Readout.
Description of choice:
Reference [%], parameter 509 gives a percentage for the resulting reference in the range from Minimum Reference to Maximum
Reference. See also Reference Handling.
Terminal 60, Analog Input [mA], parameter 524, gives the current
value of the signal on terminal 60.
Pulse Reference [Hz], parameter 525, gives a pulse frequency in Hz connected to one of the terminals 17 and 29.
External Reference [%], parameter 526, gives the sum of external references as a percentage (sum of analog/pulse/serial communication) in the range from minimum reference to maximum reference.
Reference [unit], parameter 510 gives the resulting reference by means of the unit Hz in Open Loop, parameter 100. In Closed Loop, the reference unit is selected in parameter 415, Units with Closed Loop.
Feedback [unit], parameter 511, gives the resulting feedback value by means of the unit/scaling selected in parameters 413, 414 and 415. See also Feedback Handling.
Frequency [Hz], parameter 512, gives the output frequency of the drive.
User Defined Read Out, parameter 513, gives a user defined value calculated on the basis of the present output frequency and unit, as well as the scaling in selected in parameter 005, Maximum Value of User
Defined Read Out. The unit is selected in parameter 006, Unit for User Defined Read Out.
Motor Current [A], parameter 514, gives the motor current in A.
Power [kW], parameter 515, gives the present power provided to the
motor in kW.
Power [HP], parameter 516, gives the present power provided to the motor in HP.
Motor Voltage [V], parameter 517, gives the voltage fed to the motor.
DC Link Voltage [V], parameter 518, gives the intermediate circuit
voltage of the drive.
Thermal Load, Motor [%], parameter 519, gives the calculated/ estimated thermal load on the motor. 100% is the trip point. See also parameter 117, Motor Thermal Protection.
Thermal Protection, TR1 [%], parameter 520, gives the calculated/ estimated thermal load on the drive. 100% is the trip point.
Digital Input, parameter 521, gives the signal status of the 8 inputs (16, 17, 18, 19, 27, 29, 32 and 33). Input 16 corresponds to the bit to the extreme left. 0 = no signal, 1 = signal connected.
Terminal 53, Analog Input [V], parameter 522, gives the voltage value of the signal on terminal 53.
Terminal 54, Analog Input [V], parameter 523, gives the voltage value of the signal on terminal 54.
Status Word, parameter 527, gives the present status word of the drive in hex.
Heat Sink Temperature [°C], parameter 528, gives the present heat sink temperature of the drive.
Alarm Word, parameter 529, gives a hex code for the alarm on the drive.
Control Word, parameter 530, gives the present control word of the drive in hex.
Warning Word, parameter 531, indicates in hex warnings from the drive.
Extended Status Word, parameter 532, indicates in hex code whether there is a warning from the drive.
Relay Status, parameter 537, indicates in binary code the status of relays 1 through 6.
533 Display Text Line 1
(DISPL. TEXT LINE 1)
Value:
Max. 20 characters OFF
Function:
Text up to 20 characters may be displayed on line 1 (top line) of the LCP display. Parameter 007, Large Readout, must be set for Free Program Array. Line 1 custom text is only visible in auto mode.
Description of choice:
See Programming Custom Display Text.
534 Display Text Line 2
(DISPL. TEXT LINE 2)
Value:
Max. 8 characters OFF
Function:
Text up to 8 characters may be displayed on line 2 (large text display) of the LCP display. Parameter 007, Large Readout, must be set for Free Program Array. Line 2 custom text is visible in display modes I and II (see Display Modes).
Description of choice:
See Programming Custom Display Text.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
79
Page 80
Programming Custom Display Text
Enter custom text in lines 1 (top line) or 2 (large display) of the LCP keypad display in accordance with the following procedure.
1. Select parameter 533, Display Text Line 1 or 534, Display Text Line 2.
2. Press CHANGE DATA key on keypad.
3. Use left or right arrows on keypad to position cursor.
4. Use [+] or [-] arrows to scroll through character options.
5. Press [OK] key to accept changes or [CANCEL] key to cancel.
6. Select Free Program Array in parameter 007, Large read-
out, to activate custom text readout.
537 Relay Status
(RELAY STATUS)
Value:
binary (0 = open, 1 = closed) 0
Description of choice:
See Data Read-out for parameters 509 through 532, 537 on previous page for relay status description.
NOTE
Parameters 555, Bus Time Interval, and 556, Bus
Time Interval Function, are only active when FC Protocol has been selected in parameter 500, Protocol.
NORTH OFFICE BLDG
SETUP
Pump 6
1
AUTO REMOTE RUN
The available characters are: A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Æ Ø Å Ä Ö Ü É Ì Ù è . / - ( ) 0 1 2 3 4 5 6 7 8 9 space
To erase a character that has been entered, replace it with space.
535 Bus Feedback 1
(BUS FEEDBACK1)
Value:
0 through 16384 decimal (0 through 4000 Hex) 0
Function:
Via the serial communication port, this parameter allows writing of a bus feedback value which will then form part of the feedback handling. Bus Feedback 1 will be added to any feedback value registered on terminal
53.
Description of choice:
Write the required bus feedback value via serial communication.
555 Bus Time Interval
(BUS TIME INTERVAL)
Value:
1 to 99 sec. 60 sec.
Function:
In this parameter, the maximum time allowed between the receipt of two packets in a row is set. If this time is exceeded, the serial communication is assumed to have stopped and the choice made in parameter 556, Bus Time Interval Function, will be carried out.
Description of choice:
Set the required time.
556 Bus Time Interval Function
(BUS TIME INTERVAL FUNCTION)
Value:
Off (NO FUNCTION) [0]
Freeze output (FREEZE OUTPUT) [1] Stop (STOP) [2] Jogging (JOG FREQUENCY) [3] Max. output frequency (MAX FREQUENCY) [4] Stop and trip (STOP AND TRIP) [5]
Function:
In this parameter, the required reaction from the drive is selected when the time set in parameter 555, Bus Time Interval, has been exceeded.
536 Bus Feedback 2
(BUS FEEDBACK 2)
Value:
0 through 16384 decimal (0 through 4000 Hex) 0
Function:
Via serial communication, a bus feedback value can be written in this parameter that will become part of the feedback handling system. Bus Feedback 2 will be added to any feedback value on terminal 54.
Description of choice:
Write the required bus feedback value via the serial communication.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
80
Description of choice:
The output frequency of the drive can be frozen at the present value, frozen as selected in parameter 211, Preset Reference 1, frozen as selected in parameter 202, Maximum Output Frequency, or stop and show a fault.
Page 81
560 N2 override release time
(N2 OVER.REL.TIME)
Value:
1 - 65533 sec. OFF
Function
The maximum time is set between the receipt of two N2 messages. If the time is exceeded, serial communication is assumed stopped. All N2 points which are overridden will be released in the following order:
1. Analog outputs
2. Binary outputs
3. Internal floating points
4. Internal integer points
5. Internal byte points
N2 point addresses are released in numerical order beginning with 1 (or 0).
Description of choice:
Set the required time.
565 FLN bus time interval
(FLN TIME INTER.)
Value:
1 - 65534 sec. 60 sec.
Function
The maximum time is set between the receipt of two FLN messages. If the time is exceeded, serial communication is assumed stopped and the required reaction is set in parameter 566, FLN Bus Time Interval
Function.
Description of choice:
Set the required time.
566 FLN bus time interval function
(FLN TIME FUNCT.)
Value:
Off (NO FUNCTION) [0]
Freeze output (FREEZE OUTPUT) [1] Stop (STOP) [2] Jogging (JOG FREQUENCY) [3] Max. output frequency (MAX.SPEED) [4] Stop and trip (STOP AND TRIP) [5]
Function
The required reaction from the variable frequency drive is selected when the time set in parameter 565, FLN Bus Time Interval, has been exceeded.
570 Modbus parity and message framing
(M.BUS PAR./FRAME)
Value:
Even parity (EVEN / 1 STOPBIT) [0] Odd parity (ODD / 1 STOPBIT) [1]
No parity (NO PARITY / 1 STOPBIT) [2]
Function
This parameter sets the drive Modbus RTU interface to communicate properly with a master controller. The parity (even, odd, or no parity) must be set to match the setting of the master controller. Even and odd parity is sometimes used to allow error checking of a transmitted word.
Description of choice
Because Modbus RTU uses the more efficient CRC (cyclic redundancy check) method for checking for errors, parity checking is seldom used in Modbus RTU networks. Set the drive parity to match the master controller, if appropriate.
571 Modbus communication timeout
(M.BUS COM.TIME.)
Value:
10 ms to 2000 ms 100 ms
Function
This parameter determines the maximum time that the drive will wait between characters sent by the Modbus RTU master controller. When the time expires, the drive assumes it has received the entire message.
Description of choice
Generally, the value of 100 ms is sufficient for Modbus RTU networks, although some Modbus RTU networks may operate with a timeout value as short as 35 ms. If the value is set too short, the drive may miss part of the message. Since the CRC check will be invalid, the drive will ignore the message. The resulting retransmission of messages will slow network communications. A value set too long will cause the drive to wait longer than necessary to determine that the message is complete. This delays response time and could cause the master controller to timeout or slow the network.
Description of choice:
The output frequency of the variable frequency drive can be frozen at the present value at any given time, frozen at parameter 211, Preset Reference 1, frozen at parameter 202, Max. Output Frequency, or stop output and show a fault.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
81
Page 82
Warning Words, Extended Status Word and Alarm Word
Warning Word, Extended Status Word and Alarm Word are shown in hex format on the display. If there is more than one warning or alarm, the sum of the warnings or alarms will be shown.
The descriptions of the Extended Status Words, Warning Words and Alarm Words can be read out via the serial bus in parameter 531, Warning Word; 532, Extended Status Word; and 529, Alarm Word.
Bit Alarm Word (Parameter 529)
00 Unknown fault 01 Trip locked 02 AMA fault 03 HPFB fault 04 RS-485 timeout 05 Short circuit 06 SMPS fault 07 Ground fault 08 Overcurrent 09 Current limit 10 Motor thermistor 11 Motor thermal 12 Inverter thermal 13 Undervoltage 14 Overvoltage 15 Input phase loss 16 Live zero fault 17 Heat sink overtemperature 18 Motor phase W missing 19 Motor phase V missing 20 Motor phase U missing 21 Profibus communication fault 22 Inverter fault 23 Output current low 24 External fault 25 Reserved 26 Reserved 27 Reserved 28 Reserved
Bit Warning Word (Parameter 531)
00 Reference high 01 Control card fault 02 Power card fault 03 HPFB bus timeout 04 RS-485 timeout 05 Overcurrent 06 Current limit 07 Motor thermistor 08 Motor overtemperature 09 Inverter overtemperature 10 Undervoltage 11 Overvoltage 12 Voltage warning low 13 Voltage warning high 14 Input phase fault 15 Live zero fault 16 Under 10 Volt (terminal 50) 17 Reference low 18 Feedback high 19 Feedback low 20 Output current high 21 Out of frequency range66666 22 Profibus communication fault 23 Output current low 24 Output frequency high 25 Output frequency low 26 AMA - motor too small 27 AMA - motor too big 28 AMA - check par. 102, 103, or 105 29 AMA - check par. 102, 104, or 106 30 Reserved 31 Reserved
Bit Extended Status Word (Paramater 532)
00 Autoramping 01 Start delay 02 Sleep boost active 03 Sleep mode active 04 Automatic motor adaptation completed 05 Automatic motor adaptation running 06 Reverse start (not for TR1) 07 Normal ramping 08 Reversing 09 At reference 10 Running 11 Local reference = 0, Remote = 1 12 OFF = 1 13 Hand = 1, Auto = 0 14 Run request 15 No run permission 16 Freeze output frequency 17 Freeze output blocked 18 Jogging 19 No jog permission 20 Stand by 21 Stopped 22 DC braking stop 23 Drive ready 24 Relay 123 active (Profibus only) 25 Drive ready 26 Control ready 27 Start prevented 28 Profibus OFF3 active 29 Reserved
82
Page 83
Serial Communication for FC Protocol
ADDRESS 1
MASTER
ADDRESS 2
Protocols
All TR1 drives have an RS-485 (EIA-485) port which allows control­ling the drive by one of four different serial communication protocols. The protocols, which can be selected in parameter 500, Protocol, are:
Johnson Controls Metasys N2
Siemens FLN
Modbus RTU
FC protocol
Metasys N2 is a registered trademark of Johnson Controls.
FLN is a registered trademark of Siemens.
®
®
ADDRESS 31
REPEATER
ADDRESS 126
Packet Communication
Control and Reply Packets
The packet communication in a master/slave system is controlled by the master. The drives are the slaves. A maximum of 31 TR1 drives can be connected to one master unless a repeater is used. If a repeater is used, a maximum of 126 drives can be connected to one master.
The master continuously sends packets addressed to the slaves and awaits reply packets from them. The response time of the slaves is a maximum of 50 ms.
If FC protocol is to be selected, set parameter 500, Protocol to FC protocol .
For further information on operating the drive through N2, FLN, or Modbus RTU communication, request the related operators manual from Trane.
Only a slave that has received a faultless packet addressed to that slave will respond by sending a reply packet.
Broadcast
When a master sends a packet to all slaves connected to the bus at the same time, it is called a broadcast. In broadcast communication, if the packet has been correctly received, the slaves do not send reply packets to the master.
83
Page 84
Conversion
The different attributes for each parameter can be seen in the section on factory settings.
Since a parameter value can only be transferred as a whole number, a conversion factor must be used to transfer decimals.
Example:
Parameter 201: Minimum Frequency, conversion factor 0.1. If parameter 201 is to be set to 10 Hz, a value of 100 must be trans­ferred, since a conversion factor of 0.1 means that the transferred value will be multiplied by 0.1. A value of 100 will, therefore, be understood as 10.0.
Index Factor
74 3.6
2 100 110 01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
Conversion Table
Data Type
Data type shows the type and length of the packet.
The data types shown in the table are supported by the drive. Unsigned means there is no sign included in the packet.
Control Word
The control word is used for transmitting commands from a master (PC) to a slave (drive).
MasterSlave
Control
word
1514131211109876543210Bit no.
Bit Bit = 0 Bit =1
00 Preset ref. lsb 01 Preset ref. msb 02 DC braking 03 Coasting stop 04 Quick stop 05 Freeze output frequency 06 Ramp stop Start 07 Reset 08 Jog 09 No function No function 10 Data not valid Data valid 11 Activate relay 1 12 Activate relay 2 13 Choice of setup lsb 14 Choice of setup msb 15 Reversing
Serial com.
ref.
Data type Description
3 Integer 16 4 Integer 32 5 Unsigned 8 6 Unsigned 16 7 Unsigned 32 9 Text string
Data Type Table
Bit 00/01:
Bits 00 and 01 are used for choosing between the four pre-pro­grammed references parameters 211 through 214, Preset Reference, as shown in the table below.
Preset Reference Parameter Bit 01 Bit 00
121100 2 212 0 1 3 213 1 0 4 214 1 1
NOTE Parameter 508, Choice of Preset Reference, is used to choose how bits 00/01 are to be gated with the corresponding functions of the digital inputs.
Bit 02, DC BRAKE:
Bit 02 = 0 enables DC braking. Set braking current and duration in parameter 114, DC Braking Current, and in parameter 115, DC Braking Time.
NOTE Parameter 504, DC Brake, is used for selecting how bit 02 is to be gated with the correspond­ing function of terminal 27.
84
Page 85
Bit 03, Coasting Stop:
Bit 03 = 0 means that the drive will coast to a stop. Bit 03 = 1 means that the drive is able to start the motor, provided the other conditions for starting are fulfilled.
NOTE In parameter 503, Coasting Stop, the choice is made of how bit 03 is to be gated with the cor­responding function of terminal 27.
Bit 04, Quick Stop:
Bit 04 = 0 leads to a stop in which the motor speed is ramped down to a stop as set in parameter 207, Ramp Down Time.
Bit 10, Data Not Valid/Data Valid:
Used for telling the drive whether the control is to be used or ignored. Bit 10 = 0 means that the control word is ignored. Bit 10 = 1 means that the control word is used. This function is relevant because the control word is always contained in the packet, regardless of the type of packet used. Therefore it is possible to disconnect the control word if it is not to be used in connection with updating or reading of parameters.
Bit 11, Relay 1:
Bit 11 = 0 Relay 1 is not activated. Bit 11 = 1 Relay 1 is activated, provided Control Word Bits 11/12 has been selected in parameter 323, Relay Outputs.
Bit 05, Freeze Output Frequency:
Bit 05 = 0 means that the given output frequency is frozen. The frozen output frequency can now only be changed with the digital inputs programmed for Speed Up and Speed Down.
NOTE If Freeze Output is active, drive cannot be stopped via Bit 06, Start, or through terminal
18. Drive can only be stopped in following ways:
Bit 03, Coasting Stop
Terminal 27
Bit 02, DC Braking
Terminal 19 programmed for DC Braking
Bit 06, Ramp Stop/Start:
Bit 06 = 0 leads to a stop in which the motor speed is ramped down to stop through parameter 207, Ramp Down Time. Bit 06 = 1 means that the drive is able to start the motor, provided the other conditions for starting are fulfilled.
NOTE Parameter 505, Start, determines how bit 06, Ramp Stop/Start, is gated and corresponding function of terminal 18.
Bit 07, Reset:
Bit 07 = 0 leads to no reset. Bit 07 = 1 means that a trip is reset. Reset is activated on the leading edge of the signal, at the time the signal changes from logic 0 to logic 1.
Bit 08, Jog:
Bit 08 = 1 means that the output frequency is determined by parameter 209, Jog Frequency.
Bit 09, No function:
Bit 09 has no function.
Bit 12, Relay 2:
Bit 12 = 0 Relay 2 is not activated. Bit 12 = 1 Relay 2 is activated, provided Control Word Bits 11/12 has been selected in parameter 326, Relay Outputs.
NOTE If time-out period set in parameter 556, Bus Time Interval Function, is exceeded, relays 1 and 2 will have voltage removed if activated via serial communication.
Bits 13/14, Choice of Setup:
Bits 13 and 14 are used to choose among the four menu setups in accordance with the following table:
Setup Bit 14 Bit 13
100 201 310
411 This function is only possible if Multi-setup has been selected in parameter 004.
NOTE In parameter 507, Choice of Setup, a choice is made of how bits 13/14 are gated with corre­sponding function of digital inputs.
Bit 15, No function/reversing:
Bit 15 = 0 leads to no reversing Bit 15 = 1 leads to reversing In the factory setting, reversing has been selected as digital in parameter 506, Reversing. Bit 15 will only allow reversing, if bus or logic or has been selected, or logic and has been selected and a signal is present at terminal 19.
85
Page 86
Status Word per FC Protocol
The status word is used to inform the master (e.g., a PC) of the condition of the slave (drive).
SlaveMaster
Status
word
1514131211109876543210Bit no.
Bit Bit = 0 Bit =1
00 Trip Control ready 01 Drive ready 02 Stand by 03 No trip Trip 04 Not in use 05 Not in use 06 Not in use 07 No warning Warning 08 Speed reference Speed = reference 09 Local operation Serial comm. control 10 Out of frequency range 11 Running 12 No function No function 13 Voltage warning
14 Current limit 15 Thermal warning
Bit 00, Control Ready:
Bit 00 = 1 The drive is ready for operation. Bit 00 = 0 The drive has tripped.
Bit 01, Drive Ready:
Bit 01 = 1 The drive is ready for operation, but terminal 27 is a logic 0 and/or a coasting command has been received via serial communication.
Bit 02, Standby:
Bit 02 = 1 The drive is able to start the motor when a start command is given.
Bit 03, No Trip/Trip:
Bit 03 = 0 means that the drive is not in an error state. Bit 03 = 1 means that the drive has tripped and needs a reset signal in order for operation to be resumed.
Bit 04, Not in use:
Bit 04 is not used in the status word.
Bit 05, Not in use:
Bit 05 is not used in the status word.
Output
frequency
high/low
Bit 06, Not in use:
Bit 06 is not used in the status word.
Bit 07, No warning/warning:
Bit 07 = 0 means there is no warning. Bit 07 = 1 means a warning has occurred.
Bit 08, Speed ¹ Reference/Speed = Reference:
Bit 08 = 0 means that the motor is running, but that the present speed is different from the preset speed reference. This may be the case when the speed is being ramped up or down after a start or stop command. Bit 08 = 1 means that the present motor speed equals the preset speed reference.
Bit 09, Local Operation/Serial Communication Control:
Bit 09 = 0 means that OFF/STOP has been activated on the control unit, or that the drive is in Hand mode. It is not possible to control the drive through serial communication. Bit 09 = 1 means that it is possible to control the drive through serial communication.
Bit 10, Out of Frequency Range:
Bit 10 = 0 if the output frequency is outside the range established by the values in parameter 201, Output Frequency Low Limit, and parameter 202, Output Frequency High Limit. Bit 10 = 1 means that the output frequency is within the limits of those parameters.
Bit 11, Not Running/Running:
Bit 11 = 0 means that there is no output from the drive. Bit 11 = 1 means that the drive has a start signal, or that the output frequency is greater than 0 Hz.
Bit 12, No Function:
Bit 12 has no function.
Bit 13, Voltage Warning High/Low:
Bit 13 = 0 means that there is no voltage warning. Bit 13 = 1 means that the DC voltage of the drive intermediate circuit is too low or too high.
Bit 14, Current Limit:
Bit 14 = 0 means that the output current is less than or equal to the value in parameter 215, Current Limit. Bit 14 = 1 means that the output current is higher than the value in parameter 215, Current Limit, and the drive will trip after the time set in parameter 412, Trip Delay Overcurrent, has passed if the output current is not reduced.
Bit 15, Thermal Warning:
Bit 15 = 0 means there is no thermal warning. Bit 15 = 1 means that the temperature limit has been exceeded either in the motor, in the drive or from a thermistor connected to an analog input.
86
Page 87
Serial Communication Reference
Present Output Frequency
MasterSlave
Control
word
Serial com.
ref.
1514131211109876543210Bit no.
The serial communication reference is transmitted to the drive in the form of a 16-bit word. The value is transmitted as whole numbers 0 through ±32767 (±200 %). 16384 (4000 Hex) corresponds to 100 %.
The serial communication reference has the following format:
0 through 16384 (4000 Hex) - 0 through 100% (parameter 204, Minimum Reference - Par. 205, Maximum Reference).
It is possible to change the direction of rotation through the serial reference. This is done by converting the binary reference value to 2's complement. See example in next column.
SlaveMaster
Status
word
Output
frequency
1514131211109876543210Bit no.
The value of the output frequency of the drive at any given time is transmitted as a 16-bit word. The value is transmitted in the form of whole numbers 0 through ±32767 (±200%).
16384 (4000 Hex) corresponds to 100%. The output frequency has the following format:
0 through 16384 (4000 Hex) @ 0 to 100% (Parameter 201,
Output Frequency Low limit - Parameter 202, Output Frequency High Limit).
Example - Status Word and Present Output Frequency:
The master receives a status message from the drive that the presentoutput frequency is 50% of the output frequency range.
Example - Control word and serial communication reference:
The drive must receive a start command, and the reference is to be set to 50% (2000 Hex) of the reference range.
Control word = 047F Hex. Start command Reference = 2000 Hex. 50 % reference
047F H 2000 H
Control word
Reference
The drive is to receive a start command, and the reference is to be set to -50% (-2000 Hex) of the reference range. The reference value is first converted to the first complement; then 1 binary is added to get 2s complement:
2000 Hex= 0010 0000 0000 0000 binary 1´ complement = 1101 1111 1111 1111 binary
+ 1 binary
2´ complement = 1110 0000 0000 0000 binary
Control word = 047F Hex. Start command Reference = E000 Hex. -50 % reference
Parameter 201, Output Frequency Low Limit = 0 Hz
Parameter 202, Output Frequency High Limit = 60 Hz
Status word = 0F03 Hex. Status message
Output frequency = 2000 Hex. 50% of the frequency range, cor­responding to 30 Hz.
0F03 H 2000 H
Status word
Output
frequency
047F H E0000 H
Control word
Reference
87
Page 88
Service Functions Parameters 600 through 631
This parameter group contains functions useful for troubleshooting the drive including operating data, data log and fault log.
Parameter 602, kWh Counter
Shows the output power of the drive. The calculation is based on the mean value in kWh over one hour. This value can be reset using parameter 618, Reset of kWh Counter.
It also has information on the nameplate data of the drive.
Function:
These parameters can be read out through the serial communication port as well as on the control panel display.
Description of choice:
Parameter 600, Operating Hours
Shows the number of hours the drive has had power applied. The value is saved every hour and when the power is removed. This value cannot be reset.
Parameter 601, Hours Run
Shows the number of hours the drive has powered the motor. This parameter can be reset in parameter 619, Reset of Hours Run Counter. The value is saved every hour and when the power is removed.
Parameter 603 Number of Power Ups.
Shows the number of times power has been applied to the drive.
Parameter 604, Number of Overtemperature Trips
Shows the number of overtemperature trips from the heatsink tempera­ture sensor on the drive.
Parameter 605, Number of Overvoltage Trips
Shows the number of overvoltage trips from the sensor of DC link voltage of the drive. The count is only taken when Alarm 7 Overvoltage is activated.
600-605 Operating Data Value:
Value:
Parameter Description Display Unit Range Number Operating Data: Text
600 Operating Hours (OPERATING HOURS) Hours 0 through 130,000.0 601 Hours Run (RUNNING HOURS) Hours 0 through 130,000.0 602 kWh Counter (KWH COUNTER) kWh ­603 Number of Power-ups (POWER UPS) Occurences 0 through 9999 604 Number of Overtemp Trips (OVER TEMPS) Occurences 0 through 9999 605 Number of Overvoltage Trips (OVER VOLTS) Occurences 0 through 9999
88
Page 89
606 - 614 Data Log
Value:
Parameter Description Display Unit Range no. Data log: Text
606 Digital Input (LOG: DIGITAL INP) Decimal 0 through 255 607 Control Word (LOG: BUS COMMAND) Decimal 0 through 65535 608 Status Word (LOG: BUS STAT WD) Decimal 0 through 65535 609 Reference (LOG: REFERENCE) % 0 through 100 610 Feedback (LOG: FEEDBACK) Par. 414 -999,999.999 through 999,999.999 611 Output Frequency (LOG: MOTOR FREQ.) Hz 0.0 through 999.9 612 Output Voltage (LOG: MOTOR VOLT) Volt 50 through 1000 613 Output Current (LOG: MOTOR CURR.) Amp 0.0 through 999.9 614 DC Link Voltage (LOG: DC LINK VOLT) Volt 0.0 through 999.9
Function:
With these parameters, it is possible to see up to twenty saved values, or data logs. Data log [1] is the most recent and [20] the oldest log. When a start command has been given, a new entry to the data log is made every 160 ms. If there is a trip or if the drive is stopped, the 20 latest data log entries will be saved and the values will be visible in the display. This is useful to view the operation of the drive just before a trip. These values will be lost if power is removed from the drive.
The drawing below shows a display. The data log number is shown in the square brackets at the left of the forth line of the display.
EXT. REFERENCE, %
SETUP
63.0 %
606 DATALOG: DIGITAL INP
1
[1] 40
Data logs [1] through [20] can be read by first pressing CHANGE DATA, followed by the + and - keys to change data log numbers.
The table can be used for converting a decimal number into a binary code. For example, digital 40 corresponds to binary 00101000. The nearest smaller decimal number is 32, corresponding to a signal on terminal 18. 40-32 = 8, corresponds to the signal on terminal 27.
Terminal 16 17 18 19 27 29 32 33 Decimal number 128 64 32 16 8 4 2 1
Parameter 607 Data Log: Control Word:
This is where the latest log data is given in decimal code for the control word of the drive. The control word can only be changed via serial communication. The control word is read as a decimal number which is to be converted into hex. See the control word profile under the section
Serial communications.
Parameter 608, Data Log: Status Word:
This gives the latest log data in decimal code for the status word. The status word is read as a decimal number which is to be converted into hex. See the status word profile under the section Serial communica-
tion.
Parameter 609, Data Log: Reference:
This gives the latest log data for the resulting reference.
Parameters 606 through 614, Data Log, can also be read out via the serial communication port.
Description of choice:
Parameter 606 Data Log: Digital Input:
This is where the latest log data is shown in decimal code, representing the status of the digital inputs. Translated into binary code, terminal 16 corresponds to the bit to the extreme left and to decimal code 128. Terminal 33 corresponds to the bit to the extreme right and to decimal code 1.
Parameter 610, Data Log: Feedback:
This gives the latest log data for the feedback signal.
Parameter 611, Data Log: Output Frequency:
This gives the latest log data for the output frequency.
Parameter 612, Data Log: Output Voltage:
This gives the latest log data for the output voltage.
Parameter 613, Data Log: Output Current:
This gives the latest log data for the output current.
Parameter 614, Data Log: DC Link Voltage:
This gives the latest log data for the intermediate circuit voltage.
89
Page 90
615 Fault Log: Error Code
(F. LOG: ERROR CODE)
Value:
[Index 1-10] Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason why a fault trip occurs. Ten log values, indicated as [1] through [10] are stored.
618 Reset of kWh Counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 602, kWh Counter.
The lowest log number [1] contains the most recently saved data value; the highest log number [10] contains the oldest data value.
If there is a fault trip, it is possible to see its cause, the time and possibly the values or output current or output voltage. See the section on Warnings and Alarms for a table explaining the error codes.
Description of choice:
The fault log is only reset after manual initialization.
616 Fault Log: Time
(F. LOG: TIME)
Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total number of hours run in connection with the 10 most recent fault trips. Ten log values, indicated as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value: the highest log number [10] contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialization.
Description of choice:
If Reset has been selected and the OK key is pressed, the kWh counter of the drive is reset.
619 Reset of Hours Run Counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 601, Hours Run.
Description of choice:
If Reset has been selected and the OK key is pressed, parameter 601 Hours-run is reset to zero.
620 Operating Mode
(OPERATION MODE)
Value:
Normal function (NORMAL OPERATION) [0]
Function with deactivated inverter (OPER. W/INVERT.DISAB) [1] Control card test (CONTROL CARD TEST) [2] Initialization (INITIALIZE) [3]
617 Fault Log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at which a fault trip occurred. The unit of the value depends on the alarm active in parameter 615, Fault Log: Error Code.
Description of choice:
The fault log is only reset after manual initialization.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
90
Function:
In addition to its normal function, this parameter can be used for two different tests.
It is possible to reset to the default factory settings for all Setups, except parameters 500, Address; 501 Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Description of choice:
Normal function is used for normal operation of the motor.
Function with deactivated inverter is selected to operate the control
card using its control signals without running the motor.
Control card test is used to test the analog and digital inputs, analog and digital outputs, relay output and the power supplies of the control card.
Page 91
A test connector with the connections shown below is required for this test.
Initialization is selected to reset the drive to its factory default settings without resetting parameters 501 Address, 502 Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Set test connector set up as follows:
1. Connect 4, 16, 17, 18, 19, 27, 29, 32 and 33.
2. Connect 5 and 12.
3. Connect 39, 20 and 55.
4. Connect 42 and 60.
5. Connect 45, 53 and 54
NOTE Choosing Initialization resets drive to standard default values. Any special application programming performed at the factory, during start-up, or thereafter, will be lost. As a backup, upload drive settings into the driveís local control panel (LCP) keypad as described in parameter 004, LCP Copy.
Initialization the drive to factory default settings in accordance with the following procedures:
1. Select Initialization.
2. Press OK key.
3. Remove input power and wait for light in display to go out.
4. Connect input power.
5. Initialization of all parameters will be carried out in all Setups with exception of parameters 501, Address; 502, Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Test the control card in accordance with the following procedure:
1. Select Control Card Test.
2. Remove input power and wait for light in display to go out.
3. Insert test connector described above.
4. Reconnect input power.
5. Press OK key. (Test cannot run without control panel in place.)
6. Drive automatically tests control card.
7. Remove test connector and press OK key when drive displays TEST COMPLETED.
8. Parameter 620, Operating Mode, is automatically set to Normal Function.
If the control card test fails, the drive will display TEST FAILED. Replace the control card.
91
Page 92
621 - 631 Nameplate
Value:
Parameter Description Display text Number Nameplate:
621 Unit Type (DRIVE TYPE) 622 Power Component (POWER SECTION) 623 TR1 Ordering No. (ORDERING NO) 624 Software Version No. (SOFTWARE VERSION) 625 Control Panel Identification No. (LCP ID NO.) 626 Database Identification No. (PARAM DB ID) 627 Power Component Identification No. (POWER UNIT DB ID) 628 Application Option Type (APPLIC. OPTION) 629 Application Option Ordering No. (APPLIC. ORDER NO) 630 Communication Option Type (COM. OPTION) 631 Communication Option Ordering No. (COM. ORDER NO)
Function:
Identification information for the drive can be read from parameters 621 through 631, Nameplate via the display or the serial communication port.
Description of choice:
Parameter 621, Nameplate: Unit Type:
TR1 type gives the unit size and input voltage. See Cross Reference ­Model Number to TR1 Type to convert this do the drives model number.
Parameter 622, Nameplate: Power Component:
This gives the type of power card installed in the drive.
Parameter 623, Nameplate: TR1 Ordering Number:
This gives the ordering number for the specific drive. Because this number does not specify any special options or programming that was provided with the drive, it is better to refer to the serial number printed on the Trane nameplate when contacting the factory about the drive.
Parameter 624, Nameplate: Software Version Number:
This gives the present software version number of the drive.
Parameter 625, Nameplate: LCP Identification Number:
This gives the identification number of the keypad (LCP) of the unit.
Parameter 626, Nameplate: Database identification Number:
This gives the identification number of the softwares database.
Parameter 627, Nameplate: Power Component Identification Number:
This gives the identification number of the database of the drive.
Parameter 628, Nameplate: Application Option Type:
This gives the type of application options fitted to the basic drive.
Parameter 629, Nameplate: Application Option Ordering Number:
This gives the ordering number for the application option of the basic drive. Because this number does not specify any special options or programming that was provided with the drive, it is better to refer to the serial number printed on the Trane nameplate when contacting the factory about the drive.
Parameter 630, Nameplate: Communication Option Type:
This gives the type of communication option card installed in the drive, if any.
Parameter 631, Nameplate: Communication Option Ordering Number:
This gives the ordering number for the communication option.
92
Page 93
Relay Card Functions Parameters 700 through 711
Parameters 700 through 711 are only activated if a relayoption card is installed in the drive. A relay card can be field installed in the drive if desired.
Activation/deactivation can be programmed in parameters 701, 704, 707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702, 705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
700 Relay 6, Function (RELAY6 FUNCTION) 703 Relay 7, Function (RELAY7 FUNCTION) 706 Relay 8, Function (RELAY8 FUNCTION) 709 Relay 9, Function (RELAY9 FUNCTION) Function:
This output activates a relay.
Relay outputs 6, 7, 8 and 9 can be used for showing status and warnings. The relay is activated when the conditions for the relevant data values have been fulfilled. Because these have the same possible functions as relay 1, see the description under parameter 323.
701 Relay 6, ON Delay (RELAY6 ON DELAY) 704 Relay 7, ON Delay (RELAY7 ON DELAY) 707 Relay 8, ON Delay (RELAY8 ON DELAY) 710 Relay 9, ON Delay (RELAY9 ON DELAY) Value:
0 to 600 sec. 0 sec.
Electrical Installation of the Relay Card
The relays are connected as shown below.
Relay 6-9 A-B make, A-C break Max. 240 VAC, 2 Amp
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9 (terminals 1, and 2).
Description of choice:
Enter the desired value.
702 Relay 6, OFF Delay (RELAY6 OFF DELAY) 705 Relay 7, OFF Delay (RELAY7 OFF DELAY) 708 Relay 8, OFF Delay (RELAY8 OFF DELAY) 711 Relay 9, OFF Delay (RELAY9 OFF DELAY) Value:
0 to 600 sec. 0 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8 and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value.
This parameter allows a delay of the activation of relays 6, 7, 8 and 9 (terminals 1, and 2).
To achieve double isolation, mount the plastic foil as shown below.
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
93
Page 94
Status Messages
Status messages are generated automatically and appear in the fourth (bottom) line of the display as shown.
A. The first part of the status line indicates the CONTROL POINT of
the drive.
B. The center part of the status line indicates the REFERENCE
LOCATION.
C. The last part of the status line gives the present DRIVE STATUS.
The table below defines the status massage display words.
80.0% 5.08A 2.1HP
SETUP
40.0 Hz
1
AUTO REM. RUNNING
HAND
OFF
A
LOCAL
B
STOP
RAMPING JOGGING
. . . .
STAND BY
C
DISPLAY
WORD
CONTROL POINT
AUTO The drive is in Auto mode, which means that Run/Stop control is carried out
HAND The drive is in Hand mode, which means that Run/Stop control is carried out
OFF OFF/STOP is activated either by means of the keypad, or by the digital
REFERENCE LOCATION
REM. If REMOTE has been selected, the reference is set via the control terminals
LOCAL If LOCAL has been selected, the reference is set via the [+] and [-] keys on
DRIVE STATUS
RUNNING The motor speed now corresponds to the resulting reference. RAMPING The output frequency is changing. AUTO RAMP Parameter 208, Autom atic Ramp, is enabled. The drive is attem pting to
SLEEP.BST
SLEEP
via the control term inals and/or serial communication.
via the keys on the keypad
inputs Hand Start and Auto Start, both being a logic ‘0.’
or via serial communication.
the keypad.
avoid a trip from overvoltage by extending its decel ramp time. The boost function in parameter 406, Boost Setpoint, is enabled. This function can only be enabled in Closed Loop operation.
WARNING
!
DESRIPTION
Unintended Start!
When in Sleep mode, motor may restart at any time without warning. The drive, motor, and any driven equipment m ust be in operational readiness. Failure to be in operational readiness could result in death, serious injury, or equipment and property damage.
The energy saving function in parameter 403, Sleep Mode Timer, is enabled. This status m essage shows that at present the motor has been stopped by sleep mode. It can restart automatically.
START DEL
Unintended Start!
When in Start Delay mode, motor may restart at any time without warning. The drive, motor, and any driven equipment m ust be in operational readiness. Failure to be in operational readiness could result in death, serious injury, or equipment and property damage.
A start delay tim e has been programm ed in parameter 111, Start Delay. When the delay has passed, the drive will start and ramp up to the refe ren ce frequency.
94
WARNING
!
Page 95
DISPLAY
WORD
RUN REQ.
WARNING
!
DESRIPTION
Unintended Start!
When in Run Request mode, motor may restart at any time without warning. The drive, motor, and any driven equipm ent must be in operational readiness. Failure to be in operational readiness could result in death, serious injury, or equipment and property damage.
A start com mand has been given, but the motor will not be starte d until a
Run Permission signal is received via a digital input. JOG Jog has been enabled via a digital input or via serial comm unication. JOG REQ.
WARNING
!
Unintended Start!
When in Jog Request mode, motor may restart at any time without warning. The drive, motor, and any driven equipm ent must be in operational readiness. Failure to be in operational readiness could result in death, serious injury, or equipment and property damage.
A start com mand has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input. FRZ.OUT The output frequency has been frozen. FRZ.REQ
WARNING
!
Unintended Start!
When in Freeze Request mode, motor may restart at any time without warning. The drive, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness could result in death, serious injury, or equipment and property damage.
A start com mand has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input. START F/R Reversing and start on terminal 19, parameter 303, Digital Inputs, and Start
AMA RUN Automatic motor adaptation has been enabled in param eter 107, Autom atic
AMA STOP Automatic motor adaptation has been com pleted. The drive is now ready for
STANDBY The drive is able to start the motor when a start command is received. STOP The motor has been stopped via a stop signal from serial communication. DC STOP The DC brake has been enabled in parameters 114 through 116. UN.READY The drive is ready for operation, but term inal 27 is a logic ‘0’ and/or a
NOT READY The drive is not ready for operation, because of a trip or because OFF1,
ST ART IN. T his status will only be dis played if, in param ete r 599, Profidrive [1] has been
XXXX The microprocessor of the control has stopped and the drive is not
on term inal 18, parameter 302, Digital Inputs, are enabled at the same time.
The m otor will rem ain stopped until one of the signals becom es a logic ‘0.’
Motor Adaptation, AMA.
operation after the Reset signal has been given. Note that the m otor will start
after the drive has received the Reset signal.
Coasting Command has been received via the serial communication.
OFF2 or O FF3 is a logic ‘0.’
selected and OFF2 or OFF3 is a logic ‘0.’
operating. The cause m ay be noise on the power line, motor leads or control
wires.
95
Page 96
Warnings and Alarms
A trip can be reset in any one of the following ways: The table below lists the drive fault messages and indicates whether a warning, alarm, or trip-lock occurs. Wherever an X is placed under both warning and alarm, this means that a warning precedes the alarm. An alarm always precedes, or simultaneously accompanies, a trip-lock.
A trip causes the drive to suspend operation by cutting off power to the motor. A trip-lock requires that input power to the drive be removed, the cause of the fault corrected, and the input power restored in order to reset the drive.
1) Manual reset by pressing the RESET key on the keypad
2) A digital input through a digital input terminal
3) Serial communication command
4) Automatic reset
Automatic or manual reset may be selected in parameter 400, Reset
Function. Auto reset will not restore a trip-lock. The number of reset
attempts may be selected or infinite, which allows continuous attempts. A
timer between attempts can be set in parameter 401.
No. Description Warning Alarm Trip Locked
1 Under 10 Volts (10 VOLT LOW) X 2 Live zero fault (LIVE ZERO ERROR) X X 4 Mains phase imbalance (MAINS IMBALANCE) X X X 5 Voltage warning high (DC LINK VOLTAGE HIGH) X 6 Voltage warning low (DC LINK VOLTAGE LOW) X 7 Overvoltage (DC LINK OVERVOLT) X X 8 Undervoltage (DC LINK UNDERVOLT) X X 9 Inverter overloaded (INVERTER TIME) X X 10 Motor overloaded (MOTOR TIME) X X 11 Motor thermistor (MOTOR THERMISTOR) X X 12 Current limit (CURRENT LIMIT) X X 13 Overcurrent (OVERCURRENT) X X 14 Ground fault (EARTH FAULT) X X 15 Switch mode fault (SWITCH MODE FAULT) X X 16 Short circuit (CURR.SHORT CIRCUIT) X X 17 Serial communication timeout (STD BUSTIMEOUT) X X 18 HP field bus timeout (HPFB TIMEOUT) X X 19 Fault in EEPROM on power card (EE ERROR POWER) X 20 Fault in EEPROM on control card (EE ERROR CONTROL) X 22 Auto motor adaptation fault (AMA FAULT) X 29 Heat-sink temperature too high (HEAT SINK OVERTEMP.) X X 30 Motor phase U missing (MISSING MOT.PHASE U) X 31 Motor phase V missing (MISSING MOT.PHASE V) X 32 Motor phase W missing (MISSING MOT.PHASE W) X 34 HPFB communication fault (HPFB COMM. FAULT) X X 35 Out of frequency range (OUT FREQ RNG/ROT LIM) X 37 Inverter fault (GATE DRIVE FAULT) X X 39 Check parameters 104 and 106 (CHECK P.104 & P.106) X 40 Check parameters 103 and 105 (CHECK P.103 & P.106) X 41 Motor too large (MOTOR TOO BIG) X 42 Motor too small (MOTOR TOO SMALL) X 60 Safety stop (EXTERNAL FAULT) X 61 Output frequency low (FOUT < FLOW) X 62 Output frequency high (FOUT > FHIGH) X 63 Output current low (I MOTOR < I LOW) X X 64 Output current high (I MOTOR > I HIGH) X 65 Feedback low (FEEDBACK < FDB LOW) X 66 Feedback high (FEEDBACK > FDB HIGH) X 67 Reference low (REF. < REF. LOW) X 68 Reference high (REF. > REF. HIGH) X 69 Temperature auto derate (TEMP.AUTO DERATE) X 99 Unknown fault (UNKNOWN ALARM) X X
96
Page 97
Warnings
A warning will flash in line 2, while an explanation is given in line 1.
MAINS PHASE LOSS
SETUP
WARN.4
1
Alarms
If an alarm is given, the present alarm number will be shown in line 2. Lines 3 and 4 of the display will offer an explanation.
TRIP (RESET)
SETUP
ALARM:12
1
TORQUE LIMIT
WARNING 1 10 VOLT LOW
The 10 V voltage from terminal 50 on the control card is below 10V.
Remove some of the load from terminal 50, as the 10 volts supply is overloaded. Maximum load is 17 mA, minimum resistance is 590 Ω.
WARNING/ALARM 2 LIVE ZERO ERROR
The current or voltage signal on terminal 53, 54 or 60 is below 50% of the value preset in parameters 309, 312 and 315 Terminal, Minimum
Scaling.
WARNING/ALARM 4 MAINS IMBALANCE
Phase missing on the input power. Check the supply voltage to the drive.
WARNING 5 DC LINK VOLTAGE HIGH
The intermediate DC circuit voltage is higher than Voltage Warning High, see table below. The drive is still controlling the motor.
WARNING 6 DC LINK VOLTAGE LOW
The intermediate DC circuit voltage is lower than Voltage Warning Low, see table below. The drive is still controlling the motor.
WARNING/ALARM 7 DC LINK OVERVOLT
If the intermediate circuit voltage (DC) is higher than the Overvoltage Limit of the drive (see table below), the drive will trip after a fixed
period. The length of this period depends upon the unit.
WARNING/ALARM 8 Undervoltage (DC LINK UNDERVOLT)
If the intermediate circuit voltage (DC) drops below the Undervoltage Limit of the inverter, the drive will trip after a fixed period. The length of
the period depends upon the unit.
The voltage will be stated in the display. Check whether the supply voltage matches the drive rating.
WARNING/ALARM 9 INVERTER TIME
The electronic thermal inverter protection reports that the drive is about to trip because of an overload. The counter for electronic thermal inverter protection gives a warning at 98% and trips at 100% showing an alarm. The drive cannot be reset until the counter drops below 90%. Activate ASFM (Automatic Switching Frequency Modulation) in parameter 408, Interference Reduction Method, or reduce the carrier frequency in parameter 407, Switching Frequency.
Alarm/Warning Limits: Drive 208 to 230 volt 380 to 460 volt 550 to 600 volt
Undervoltage alarm 211 151 402 289 557 413 Voltage warning, low 222 159 423 304 613 443 Voltage warning, high 384 276 777 530 943 667 Overvoltage alarm 425 305 798 550 975 689
VDC VAC VDC VAC VDC VAC
97
Page 98
WARNING/ALARM 10 MOTOR TIME
According to the electronic thermal protection, the motor is overheated. Parameter 117, Motor Thermal Protection, allows a choice of whether the drive is to give a warning or an alarm when the Motor Thermal Projection reaches 100%. The fault is that the motor is overloaded to more than 100% of the preset rated motor current for too long. Check that the motor parameters 102 through 106 have been set correctly.
ALARM 16
CURR. SHORT CIRCUIT
There is a short circuit in the output from the drive.
Remove power to the drive and correct the short circuit.
WARNING/ALARM 17
STD BUSTIMEOUT
There is no serial communication with the drive.
WARNING/ALARM 11 MOTOR THERMISTOR
The thermistor or the thermistor connection has been disconnected. Parameter 117, Motor Thermal Protection, allows a choice of whether the drive is to give a warning or an alarm. Check that the thermistor has been correctly connected between terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply).
WARNING/ALARM 12 CURRENT LIMIT
The current is higher than the value in parameter 215, Current Limit, and the drive trips after the time set in parameter 412, Trip Delay
Overcurrent, has passed. Run AMA on a cold motor in parameter 107, Automatic Motor Adaptation.
WARNING/ALARM 13 OVER CURRENT
The inverter peak current limit, approximately 200% of the rated current, has been exceeded. The warning will last approximately 1 or 2 seconds, and then the drive will trip and signal an alarm.
Turn off the drive and check for free rotation of the motor shaft and other causes of the overload. Run AMA on a cold motor in parameter 107, Automatic Motor Adaptation.
ALARM 14 EARTH FAULT
There is current leakage from the output phases to ground, either in the leads between the drive and the motor or in the motor itself.
Remove power to the drive and correct the ground fault.
ALARM 15 SWITCH MODE FAULT
Fault in the switch mode power supply (internal ±15 V supply).
This warning will only be enabled if parameter 510, Bus Time Interval
Function, has been set to a value different from OFF.
If parameter 510, Bus Time Interval Function, has been set to Stop
and Trip [5], the drive will first give off an alarm, then ramp down and
finally trip while giving an alarm. It is possible to increase parameter
509, Bus Time Interval.
WARNING/ALARM 18
HPFB TIMEOUT
There is no serial communication with the communication option card in
the drive.
The warning will only be enabled if parameter 804, Bus Time Interval
Function, has been set to anything but OFF. If parameter 804, Bus
Time Interval Function, has been set to Stop and Trip, the drive will
first give an alarm, then ramp down and finally trip while giving an
alarm.
Parameter 803, Bus Time Interval could possibly be increased.
Parameter 803 is only available when a communication option card is
installed in the drive.
WARNING 19
EE ERROR POWER
There is a fault on the power card EEPROM. The drive will continue to
function, but is likely to fail at the next power-up. Contact the Trane
service department.
WARNING 20
EE ERROR CONTROL
There is a fault in the EEPROM on the control card. The drive will
continue to function, but is likely to fail at the next power-up. Contact the
Trane service department.
Contact the Trane service department.
98
Page 99
ALARM 22 AMA FAULT
A fault has been found during automatic motor adaptation (AMA). The text shown in the display indicates a fault message.
AMA can only be carried out if there are no alarms during the AMA process.
CHECK 103, 105
Parameter 103 or 105 has a wrong setting. Correct the setting and repeat AMA.
LOW P 105
The motor is too small for AMA to be carried out. If AMA is to be enabled, the rated motor current, parameter 105, must be higher than 35% of the rated output current of the drive.
ASYMMETRICAL IMPEDANCE
AMA has detected an asymmetrical impedance in the motor connected to the system. The motor could be defective.
ALARM 29 HEAT SINK OVER TEMP.
The heatsink temperature became too high. For NEMA 1 drives, the limit is 90°C. For NEMA 12 drives, the limit is 80°C. The tolerance is ±5°C. The fault cannot be reset until the temperature of the heatsink has fallen below 60°C.
The fault could be due to the following:
- Ambient temperature too high
- Air obstructed
- Cooling fan(s) not operating
- Motor leads too long
- Too high a switching frequency
ALARM 30 MISSING MOT.PHASE U
Motor phase U, as indicated by the letters on the output terminal block, is missing or has a high impedance.
Remove power to the drive and check motor phase U.
MOTOR TOO BIG
The motor connected to the system is too big for AMA to be carried out. The setting in parameter 102 does not match the motor used.
MOTOR TOO SMALL
The motor connected to the system is too small for AMA to be carried out. The setting in parameter 102 does not match the motor used.
TIME OUT
AMA fails because of noisy measuring signals. Retry until AMA is successfully completed. Please note that repeated AMA runs may heat the motor to a level where the stator resistance is increased.
INTERRUPTED BY USER
AMA has been interrupted by the user.
INTERNAL FAULT
An internal fault has occurred in the drive. Contact Trane service department.
LIMIT VALUE FAULT
The parameter values found for the motor are outside the acceptable range within which the drive is able to work.
MOTOR ROTATES
The motor shaft is rotating. Make sure that the load is not able to make the motor shaft rotate while the AMA is being performed. Then start AMA all over.
ALARM 31 MISSING MOT.PHASE V
Motor phase V, as indicated by the letters on the output terminal block is missing or has a high impedance.
Remove power to the drive and check motor phase V.
ALARM 32 MISSING MOT.PHASE W
Motor phase W, as indicated by the letters on the output terminal block is missing or has a high impedance.
Remove power to the drive and check motor phase W.
WARNING/ALARM 34 HPFB COMM. FAULT
The serial communication on the communication option card is not working.
WARNING 35 OUT FREQ RNG/ROT LIM
This warning will occur if the output frequency has reached its Output Frequency Low Limit , parameter 201, or Output Frequency High Limit, parameter 202. If the drive is in Closed Loop, parameter 100, the
warning will show in the display.
99
Page 100
ALARM 37 GATE DRIVE FAULT
An output IGBT or the power card is defective. Contact the Trane service department.
WARNING 62
FOUT > FHIGH
The output frequency is higher than parameter 224, Warning: High
Frequency.
Auto Optimization Warnings 39 through 42
Automatic motor adaptation has stopped, because some parameters have probably been improperly set, or the motor used in too large or small for AMA to be carried out.
A choice must be made by pressing CHANGE DATA and choosing Continue + OK or Stop + OK.
If parameters need to be changed, select Stop, change the parameters and run AMA again.
WARNING 39 CHECK PAR. 104, 106
Parameters 104, Motor Frequency, or 106, Rated Motor Speed, have probably not been set correctly. Correct the setting and run AMA again.
WARNING 40 CHECK PAR. 103, 105
Parameter 103 Motor Voltage, or 105 Motor Current, has not been set correctly. Correct the setting and run AMA again.
WARNING 41 MOTOR TOO BIG
The motor used is probably too large for AMA to be carried out. The setting in parameter 102 Motor Power, may not match the motor. Check the motor and select Continue or [STOP].
WARNING 42 MOTOR TOO SMALL
The motor used is probably too small for AMA to be carried out. The setting in parameter 102 Motor Power, may not match the motor. Check the motor and select Continue or [STOP].
ALARM 60 EXTERNAL FAULT
Terminal 27, parameter 304, Digital Inputs, has been programmed for a Safety Interlock and is a logic 0.
WARNING 61 FOUT < FLOW
The output frequency is lower than parameter 223, Warning: Low Frequency.
WARNING/ALARM 63
I MOTOR < I LOW
The output current is lower than parameter 221, Warning: Low
Current. Select the required function in parameter 409, Function in
Case of No Load.
WARNING 64
I MOTOR > I HIGH
The output current is higher than parameter 222, Warning: High
Current.
WARNING 65
FEEDBACK < FDB LOW
The resulting feedback value is lower than parameter 227, Warning:
Low Feedback.
WARNING 66
FEEDBACK > FDB HIGH
The resulting feedback value is higher than parameter 228, Warning:
High Feedback.
WARNING 67
REF. < REF LOW
The remote controlled reference is lower than parameter 225,
Warning: Low Reference.
WARNING 68
REF. > REF HIGH
The remote controlled reference is higher than parameter 226,
Warning: High Reference.
WARNING 69
TEMP.AUTO DERATE
The heat sink temperature has exceeded the maximum value and the
auto derating function in parameter 411, Function at Over Temp
, is
active.
WARNING 99
UNKNOWN ALARM
An unknown fault has occurred which the software is not able to
handle. Contact Trane service department.
100