Trane AUD1A040A9241A, AUD1A040A9301A, AUD1A060A9241A, AUD1A060A9361A, AUD1B060A9361A Installer's Manual

...
Page 1
18- CD19D7- 22
Installer’s Guide
Upflow / Horizontal — Downflow / Horizontal, Gas-Fired Furnaces, “Fan Assisted Combustion System”
*UD1A040A9241A *UD1A040A9301A *UD1A060A9241A *UD1A060A9361A *UD1B060A9361A
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
*UD1B080A9241A *UD1B080A9361A *UD1B080A9481A *UD1C080A9601A *UD1B100A9361A
*First letter may be “A” or “T”
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
USA —
National Fuel Gas Code .......ANSI Z223.1/NFPA 54 (latest version)
Natural Gas Installation Code ..... CAN/CGA-B149.1 (latest version)
Propane Installation Code ............ CAN/CGA-B149.2 (latest version)
USA/CANADA ALTERNATE —
Category I Venting Guide ............................... Pub. No. 18-CH23D1-2
*UD1B100A9451A *UD1C100A9481A *UD1C100A9601A *UD1D100A9721A *UD1C120A9541A
For VENT SIZING INFORMATION see:
*UD1D120A9601A *UD1D140A9601A *DD1A040A9241A *DD1A060A9241A *DD1A060A9361A
*DD1B060A9361A *DD1B080A9361A *DD1B080A9451A *DD1B100A9451A *DD1C100A9481A
*DD1C100A9541A *DD1C120A9541A *DD1D120A9601A *DD1D140A9601A
Upflow / Horizontal* Downflow / Horizontal*
*Horizontal Conversion for these furnaces may be left or right side rotation.
A341789P01
Page 2
Installer’s Guide
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location and Clearances section (page
3), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in the Air for Combustion and Ventilation section (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Venting section (pages 13-14), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the Gas Piping section (page 17), of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the Location and Clearances section (page 3), of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer’s instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperature range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
10.This product must be piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING and CAUTION.
a. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
© 2011 Trane All Rights Reserved 18-CD19D7-22
Page 3
Installer’s Guide
GENERAL
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at Altitudes above 2000 ft., remember the gas input must be reduced (See High Altitude Derate, page 19).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the installa­tion of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org
These furnaces have been classified as Fan Assisted Combustion system CATEGORY I furnaces as required by ANSI Z21.47 “latest edition” and CAN/CGA 2.3. Therefore they do not require any special provisions for venting other than what is indicated in these instructions. (Category I defined on page 13).
These furnaces may be twinned. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams for Twinning on page 16 for proper hookup.
!
CAUTION
To prevent shortening its service life, the furnace should not be used as a “Construction Heater” during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluo­rides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
!
WARNING
These furnaces are not approved or intended for installa­tion in manufactured (mobile) housing, trailers, or recre­ational vehicles. Failure to follow this warning could result in property damage, personal injury, or death.
!
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the follow­ing requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
Contents
Installation Instructions 3
General 3 Location and Clearances 3 Outline Drawings 4-5 Upflow Installation 6 Downflow Installation 6 Horizontal Installation 6 Air for Combustion and Ventilation 7 Duct Connections 8 Return Air Filters 9-13 General Venting Instructions 13 Venting into a Masonry Chimney 13 Electrical Connections 14 Field Wiring Diagrams 15 Twinning Connection Diagrams 16 Gas Piping 17 Sequence of Operation 17
Start-up and Adjustment 18
Preliminary Inspections 18 Combustion and Input Check 18 High Altitude Derate 19 Lighting Instructions 20 Control and Safety Switch Adjustment 20
Abnormal Conditions 21
IFC Error Flash Codes 21
2. Do all clearances between the furnace and enclosure equal or exceed the minimums stated in the Clearance Table on the Outline Drawings (see pages 4&5).
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessi­bility to the furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section on pages 7&8.)
6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
18-CD19D7-22 3
Page 4
Installer’s Guide
From Dwg. 21C341699 Rev. 7
(ALL DIMENSIONS ARE IN INCHES)
*UD-A-1A OUTLINE DRAWING
4 18-CD19D7-22
Page 5
Installer’s Guide
From Dwg. 21C341700 Sh. 1 Rev. 3
(ALL DIMENSIONS ARE IN INCHES)
*DD-A-1A OUTLINE DRAWING
18-CD19D7-22 5
Page 6
Installer’s Guide
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clear­ance alignment holes near the bottom of the coil wrapper and drill screws are used to engage the furnace top flange. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace airflow. These instructions apply only if the coil is on top of an upflow furnace.
1
STANDOFFS (4)
CASED
COIL
DRILL SCREWS (4)
FOR VERTICAL
INSTALLATIONS
TABLE 1
CABINET
WIDTH
RETURN
DUCT WIDTH
14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position.
Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position. See Figure 4.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The
SCREWS
UPFLOW
FURNACE
STANDOFFS
(BOTH SIDES)
(BOTH SIDES)
DOWNFLOW INSTALLATION
!
WARNING
Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
2
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/horizontal furnace). Use four of the screws provided to secure the bracket.
This furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left or right side (as viewed from the front in the upright position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Clearance Table on Outline Drawings, pages 4&5, and Figure 5 below).
If the furnace is suspended using perforated steel strap (plumber’s strap), it must be supported at all four corners and in the middle at the front of the furnace. The forward most screw on the side of the furnace may be used to connect the strapping (See Figure 6 on page 7).
5
REQUIRED FLOOR OPENING: (DOWNFLOW)
See Figure 2 and Table 1
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
3
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FRONT
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
A (width)
B (depth)
6 18-CD19D7-22
D
C
TYPICAL ATTIC PLATFORM INSTALLATION
(UPFLOW/HORIZONTAL FURNACE SHOWN)
Page 7
Installer’s Guide
Line contact is only permissible between lines formed by the intersection of the top and two sides of the furnace casing and the building joists, studs, or framing.
A cutout is provided on both sides of the downflow furnace cabinet to allow a 90° elbow to be attached inside the cabinet and the vent piping to connect there. In horizontal, the downflow furnace may be vented through the top of the cabinet if needed. In vertical configuration, the downflow furnace may be vented using the side cabinet cutouts. This venting configuration could be used if an electronic air cleaner is installed.
When the downflow furnace is vented through the left side of the furnace cabinet in horizontal or vertical configuration, Type B vent pipe must be used within the cabinet.
6
TYPICAL SUSPENDED INSTALLATION
(UPFLOW/HORIZONTAL FURNACE SHOWN)
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided in the furnace casing must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the effi­ciency and safe operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made in accordance with “latest edition” of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 Installation Codes, and applicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
Furnace locations may be in “confined space” or “unconfined space”. Unconfined space is defined in Table 2 and Figure 7. These spaces may have adequate air by infiltration to provide air for combustion, ventilation, and dilution of flue gases. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for confined space.
7
UNCONFINED
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
8
LESS THAN 50 CU. FT. PER 1000 BTU/HR. INPUT ALL EQUIP INSTALLED
Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure 9 (page 8), or from the outdoors, as in Figure 10 (page 8).
1.
2.
3. The following types of installations will require use of
FURNACE MAXIMUM
BTUH / INPUT RATING
CONFINED
All air from inside the building as in Figure 9 (page 8): The confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 3 (page 8), for minimum open areas required.
All air from outdoors as in Figure 10 (page 8): The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3 (page 8), for minimum open areas required.
OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in commercial laundry rooms * Furnaces installed in hobby or craft rooms * Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
TABLE 2
MINIMUM AREA IN SQUARE FEET FOR
UNCONFINED SPACE INSTALLATIONS
WITH 8 FOOT CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
40,000 60,000
80,000 100,000 120,000 140,000
250 375 500 625 750 875
18-CD19D7-22 7
Page 8
Installer’s Guide
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000
80,000 100,000 120,000 140,000
Air From
Inside
100 100 100 100 120 140
Vertical
Duct
20 25 30 35
9
0
Air From Outside
Horizontal
10 15
Duct
20 30 40 50 60 70
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. Check controls to make certain they are correct for the electrical supply.
Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling units to avoid condensation in the heating element, unless the furnace has been specifically approved for down­stream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns which minimize noise transmission through the return air grille. Although these winter air conditioners are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
Minimum return air “entering temperature” for the furnace is 55° F.
Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space.
DO NOT install return air through the back of the furnace cabinet.
8 18-CD19D7-22
RETURN AIR DUCT CONNECTION
NOTE: On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the furnace in order to connect to the existing supply and return ductwork.
2. For side return installations on upflow models, remove the insulation around the opening in the blower compartment.
Page 9
Installer’s Guide
3. The side panels on upflow furnaces include locating notches which may be used as guides for cutting an opening for return air. Refer to Figure 12 and the outline drawing on page 4 for duct connection dimen­sions for various furnaces.
4. If a 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dashed lines in Figure 12. Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is in­stalled, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either side or on the bottom if the filter is to be used within the furnace cabinet.
When the upflow furnace is installed in the horizontal right or left application and a return duct is attached to the top side as shown in Figure 11, install the filter in a remote location.
!
WARNING
Do not install the filter in the return duct directly above the furnace in horizontal applications. Install the filter remotely. Installing the filter directly above the furnace in horizontal applications may cause property damage, serious injury or death.
Close coupled (less than 36") return (filter directly beneath bottom side return) is not recommended due to noise considerations.
Downflow Furnaces: Brackets are factory supplied to mount filters in the return air duct work.
7. Connect the duct work to the furnace. See Outline Drawing (pages 4&5) for supply and return duct size and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air ple­nums are removable.
8. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 min­utes. Don’t forget to remove the cloths before you start the furnace.
RETURN AIR FILTERS (FILTER AND FILTER RACK ARE NOT
SUPPLIED WITH UNIT)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The optional filters may be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. Some optional filters may need to be trimmed for side or bottom filter use.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE SERVICING FILTERS.
Do not install the filter in the return duct directly above the furnace in horizontal applications.
When the upflow furnace is installed in the horizontal right or left application and a close coupled (less than 36") return duct is attached to the bottom side of the furnace as shown in Figure 11, securely attach a 1/2" mesh metal hardware cloth protective screen to the inside bottom of the filter grill to prevent personal
injury from contacting moving parts when reach­ing into the return opening to replace the filter.
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL LEFT OR RIGHT APPLICATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely attach 1/2" mesh metal hardware cloth protective screen to the inside bottom of filter grill.
FILTER
q
NOTE:
On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
w
LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT
*
*
*
*
SEE OUTLINE DRAWING
*
The furnace and the blower filter rack installation can be seen in Figure 13.
The optional furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return.
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
18-CD19D7-22 9
Page 10
Installer’s Guide
TABLE 4
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"
17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"
21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"
24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use of the filter rack for right side return. Pre-drill clearance holes and then attach filter clips with the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM RETURN
With the filter removed, the filter rack is compressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. See Figures 13, 14 & 16.
NOTE: Remove the bottom front channel to install the filter rack in the 14-1/2" width cabinet furnaces.
t
Blower Deck Engagement
Hole
r
e
Airflow
BOTTOM FILTER RACK INSTALLATION
ENGAGEMENT
HOLE DETAIL
(Typical both sides and blower deck)
y
Furnace
Cabinet
Side
Engagement Hole For
Filter Rack Installation With Bottom Return
VIEW
Filter Rack
Filter Rack Retaining Screw/Pin
Optional Filter Rack Accessory Kit
BAYRACK960A
10 18-CD19D7-22
Page 11
Installer’s Guide
Airflow
Airflow
TABLE 5
Cabinet Width Left Side Bottom Right Side
14.5 X
17.5 X X X
21 X X X
24.5 X X X
1. UC1B060C has 10x7 blower which requires use of alternate filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, the following instructions should be used:
a. Open or remove the blower door.
b. Leave the bottom panel in place. (Some models
require field supplied bottom panels.)
c. After the side cutout is made following the directions
in the “Return Air Duct Connections” section on pages 8 and 9; compress the filter rack and reinstall in the side of the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 14, 15, & 17-20.
d. Install the furnace filter on the side. See Figures 14,
15, & 17-20.
u
Furnace
Cabinet
Side
1
BOTTOM ENGAGEMENT
X2Use Alternate Filter Clips Only
Filter Rack Retaining Screw/Pin
Filter Rack
o
Typical Upflow Left Side Return Filter Rack Installation
p
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Airflow
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Engagement Hole
For
Installation With
Bottom Return
i
BLOWER DECK
Furnace
Cabinet
Side
Filter Rack
Engagement Hole For
Filter Rack Installation With Side
Return
Filter Rack Retaining Screw/Pin
Bottom Panel
Furnace Blower Deck
Filter Rack Assembly
BOTTOM
PANEL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK
RAILS
a
Airflow
Optional door kit BAYFLTR206
Typical Horizontal Filter Installation
18-CD19D7-22 11
Page 12
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal configu­ration, the filter must never be installed inside or outside the cabinet directly above the blower assembly. See Figure 11 (page 9). Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the furnace. See Figures 11 (page 9) and 21 (page
11).
ALTERNATE UPFLOW FILTER CLIP / BRACKET INSTALLATION - KIT09224
1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. See Figure 22.
s
REAR
SIDE
CUT-OUT
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS
d
Airflow
f
ALTERNATE FILTER CLIPS LOCATION
Optional horizontal filter conversion kits are BAYFLTR203 for 17 1/2" width cabinets, BAYFLTR204 for 21" width cabinets, and BAYFLTR205 for 24" width cabinets. These include filters and brackets necessary for horizontal filters. In addition, optional door kit BAYFLTR206 is also available. See Figures 21 and 24.
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on the location of the return air filter.
A score line and the words “CUT HERE” are located on the end of the filter. If your application requires cutting the filter, do so as indicted by the score mark.
TABLE 6
UNIT
SIZE
RETURN AIR
BOTTOM SIDE
14-1/2" CUT ON LINE DO NOT CUT
17-1/2" DO NOT CUT DO NOT CUT
Airflow
Optional door kit BAYFLTR206
Two high velocity type air filters are required for each down­flow furnace. Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figures 23 and 24. Tables 7 and 8 (page 13) provide information for installation of the filter retaining brackets shipped with downflow furnaces.
TABLE 7
CABINET
WIDTH
14-1/2" 2 - 14X20X1 12-7/8" 17-1/2" 2 - 16X20X1 14-3/8"
21" 2 - 16X20X1 13-1/8"
24-1/2" 2 - 16X20X1 11-5/8"
* Location dimension is from end of duct to the screw holes for the bracket.
FILTER
SIZE
FILTER BRACKET
LOCATION *
21" DO NOT CUT CUT ON LINE
24-1/2" DO NOT CUT CUT ON LINE
12 18-CD19D7-22
Page 13
Installer’s Guide
TABLE 8
CABINET
WIDTH
14-1/2" 13-1/4" 12" 14" 17-1/2" 16-1/4" 15" 14"
21" 19-3/4" 19-1/2" 14"
24-1/2" 23-1/4" 22" 14"
RETURN
DUCT
WIDTH
FILTER ACCESS
OPENING -
DIMENSION "A"
FILTER ACCESS
OPENING -
DIMENSION "B"
GENERAL VENTING INSTRUCTIONS
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
VENT PIPING
These furnaces have been classified as Fan-Assisted Com­bustion System, Category I furnaces under the “latest edition” provisions of ANSI Z21.47 and CAN/CGA 2.3 standards. Category I furnaces operate with a non-positive vent static pressure and with a flue loss of not less than 17 percent.
18-CD19D7-22 13
NOTE: If desired, a side wall termination can be accom­plished through the use of an “add-on” draft inducer. The inducer must be installed according to the inducer manufacturer’s instructions. Set the barometric pressure relief to achieve -0.02 inch water column.
NOTE: When the downflow furnace is vented through the left side of the furnace cabinet using the provided cutout, Type B vent piping must be used.
The furnace shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
!
WARNING
Furnace venting into an unlined masonry chimney or concrete chimney is prohibited. Failure to follow this warning could result in property damage, personal injury, or death.
VENTING INTO A MASONRY CHIMNEY
If the chimney is oversized, the liner is inadequate, or flue­gas condensation is a problem in your area, consider using the chimney as a pathway or chase for type “B” vent or flex­ible vent liner. If flexible liner material is used, size the vent using the “B” vent tables, then reduce the maximum capacity by 20% (multiply 0.80 times the maximum capacity).
Internal Masonry Chimneys
Venting of fan assisted appliances into a lined, internal masonry chimney is allowed only if it is common vented with at least one natural draft appliance; OR, if the chimney is lined with type “B”, double wall vent or suitable flexible liner material (See Table 9, page14).
!
WARNING
The chimney liner must be thoroughly inspected to insure no cracks or other potential areas for flue gas leaks are present in the liner. Liner leaks will result in early deteriora­tion of the chimney.
Failure to follow this warning could result in carbon monox­ide poisoning or death.
NOTE: The following section does not apply if BAYVENT800B (Masonry Chimney Vent Kit) is used. All instructions with the kit must be followed. Masonry Chim­ney Kit BAYVENT800B may be used with these furnaces (UPFLOW model furnaces ONLY) to allow venting into an external masonry chimney. Refer to the BAYVENT800B Installer’s Guide for application requirements.
TABLE 9
MASONRY CHIMNEY VENTING
Tile Lined Chimney Chimney Lining
Type Furnace Internal External “B” Vent
Single Fan
Assist
Fan Assist
+
Fan Assist
Fan Assist
+
Natural
* Flexible chimney liner size is determined by using the type “B” vent size for the available BTUH input, then reducing the maximum capacity by 20% (multiply maximum capacity times 0.80). The minimum capacity is the same as shown in the “B” vent tables.
No No Yes Yes*
No No Yes Yes*
Ye s N o Ye s Ye s *
Flexible
Metal Liner
Page 14
Installer’s Guide
External Masonry Chimney
Venting of fan assisted appliances into external chimneys (one or more walls exposed to outdoor temperatures), requires the chimney be lined with type “B”, double wall vent or suitable flexible chimney liner material. This applies in all combina­tions of common venting as well as for fan assisted appliances vented alone.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following installation practices are recommended to minimize corrosion caused by condensation of flue products in the furnace and flue gas system.
1. Avoid an excessive number of bends.
2. Horizontal runs should pitch upward at least 1/4" per foot.
3. Horizontal runs should be as short as possible.
4. All vent pipe or connectors should be securely supported and must be inserted into, but not beyond the inside wall at the chimney vent.
5. When vent connections must pass through walls or parti­tions of combustible material, a thimble must be used and installed according to local codes.
6. Vent pipe through the roof should be extended to a height determined by National Fuel Gas Code or local codes. It should be capped properly to prevent rain water from entering the vent. Roof exit should be waterproofed.
7. Use type “B” double wall vent when vent pipe is routed through cool spaces (below 60° F.).
8. Where long periods of airflow are desired for comfort, use long fan cycles instead of continuous airflow.
9. Apply other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223.1 “latest edition”.
10. Vent connectors serving appliance vented by
natural draft or non-positive pressure shall not be connected into any portion of a mechanized draft system operating under positive pressure.
11. Horizontal pipe runs must be supported by hangers, straps or other suitable material in intervals at a minimum of every 3 feet of pipe.
12. A furnace shall not be connected to a chimney or flue serving a separate appliance designed to burn solid fuel.
13. The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods.
Maximum Vent or Tile
Lined Chimney Flow Area
*Drafthood outlet diameter, flue collar diameter, or listed appliance categorized vent diameter.
ELECTRICAL CONNECTIONS
!
WARNING
The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/ NFPA 70 – “latest edition” and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. A failure to follow this warn­ing could result in an electrical shock, fire, injury, or death.
= X 7
ππ
π(D*)
ππ
4
2
g
TABLE 10
GAS VENT TERMINATION
ROOF PITCH MINIMUM HEIGHT
FLAT TO 7/12 OVER 7/12 TO 8/12 OVER 8/12 TO 9/12 OVER 9/12 TO 10/12 OVER 10/12 TO 11/12 OVER 11/12 TO 12/12 OVER 12/12 TO 14/12 OVER 14/12 TO 16/12 OVER 16/12 TO 18/12 OVER 18/12 TO 20/12 OVER 20/12 TO 22/12
* THIS REQUIREMENT COVERS MOST INSTALLATIONS
1.0 FEET *
1.5 FEET
2.0 FEET
2.5 FEET
3.25 FEET
4.0 FEET
5.0 FEET
6.0 FEET
7.0 FEET
7.5 FEET
8.0 FEET
!
CAUTION
The integrated furnace control is polarity sensitive. The hot leg of the 115 VAC power must be connected to the BLACK field lead.
!
WARNING
To prevent injury or death due to electrical shock or contact with moving parts, lock unit disconnect switch in the open position before servicing the unit. Failure to follow this warning could result in electrical shock, personal injury, or death.
14 18-CD19D7-22
Page 15
Installer’s Guide
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recommended that it be provided with a separate “circuit protection device” electric circuit. The furnace must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 “latest edition” or Canadian Electrical Code, CSA C22.1, if an external electri­cal source is utilized.
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
B/C
SEE
NOTE 7
SEE
NOTE 6
FURNACE
TWIN
B/C
All field supplied wiring must conform with the tempera­ture limitation for Type T wire [63° F. (35° C)], when in­stalled in accordance with these instructions and wiring diagrams supplied with the furnace. A disconnecting means must be located within sight from, and readily accessible to, the furnace.
Refer to the SERVICE FACTS literature for unit wiring diagrams in addition to the diagram inside the blower door.
OUTDOOR UNIT
(NO TRANSFORMER)
HUM SEE NOTE 5
EAC SEE NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
FURNACE
SEE
B/C
NOTE 7
SEE
NOTE 8
SEE
NOTE 6
TWIN
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
From Dwg. B341437 Rev. 1
18-CD19D7-22 15
FIELD WIRING DIAGRAMS
HUM SEE NOTE 5
EAC SEE NOTE 5
From Dwg. B341436 Rev. 1
Page 16
TWINNING CONNECTION DIAGRAMS
Installer’s Guide
TWINNING
These furnaces may be twinned. Twinning requires that two furnaces with the same configuration, capacity, and airflow
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
1 STAGE HEAT
ONLY
THERMOSTAT
(WITH FAN SWITCH) FURNACE NO. 1
TWIN
SINGLE WIRE TWINNING FEATURE
1 STAGE HEATING ONLY THERMOSTAT
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 4
R1
must be used. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams below for proper hookup.
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
SEE NOTE 4
R1
ISOLATION RELAY
SEE NOTE 4
B/C
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 3
OUTDOOR UNIT
(NO TRANSFORMER)
SEE NOTE 3
B/C
1 STAGE
HEATING / COOLING
THERMOSTAT FURNACE NO. 1
B/C
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
TWIN
SEE NOTE 4
From Dwg. 21B341422 Rev. 3
R1
ISOLATION RELAY
SEE NOTE 4
B/C
16 18-CD19D7-22
SEE NOTE 5
B/C
R1
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 4
B/C
From Dwg. 21B341423 Rev. 2
Page 17
Installer’s Guide
GAS PIPING
!
WARNING
FIRE - EXPLOSION HAZARD DO NOT RUN FLEXIBLE GAS LINE THROUGH THE FUR­NACE CABINET WALL. FAILURE TO FOLLOW THIS WARN­ING COULD RESULT IN PROPERTY DAMAGE, SERIOUS PERSONAL INJURY, OR DEATH.
This unit is shipped standard for left side installation of gas piping. A piping knockout is also provided in the right side for an alternate piping arrangement. The installation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe joint compound must be resis­tant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 11 for delivery sizes.
NOTE: Refer to local codes and the National Fuel Gas Code, current edition, for gas pipe requirements.
The furnace and its individual shut-off valve must be discon­nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig.
The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
!
CAUTION
Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly.
NOTE: Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Mini­mum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WITH AN
OPEN FLAME!
The following warning complies with State of California law, Proposition 65.
When the thermostat is satisfied, R and W thermostat contacts open, the gas valve will close, the flames will extin­guish, and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan off period (fixed at 100 seconds), then will be de-energized by the control module.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life.
IMPORTANT:
A sediment trap must be installed in the gas line before the furnace gas valve. The sediment trap must be located as close to the furnace cabinet as practical.
LEFT SIDE PIPING (STANDARD)
h
DRIP LEG
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
SEQUENCE OF OPERATION
Thermostat call for heat
R and W thermostat contacts close signaling the control module to run its self-check routine. After the control module has verified that the pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized.
As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 6 second ignition trial period.
After the flame sensor confirms that ignition has been achieved, the delay fan ON period (fixed at 45 seconds) begins timing. After the delay of 45 seconds, the indoor blower motor will be energized and will continue to run during the heating cycle.
18-CD19D7-22 17
RIGHT SIDE PIPING (OPTIONAL)
DRIP LEG
TOP VIEW OF RIGHT SIDE PIPING
AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF
TOP VIEW
Page 18
Installer’s Guide
!
WARNING
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY COL­LECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any
detectors and makes no representations regarding any brand or type of detector.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn knob on main gas valve within the unit to the “OFF” position. Turn the external gas valve to “ON”. Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution – DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dissipate. LP Gas, being heavier than air, may require forced ventilation. Turn the knob on the gas valve in the unit to the “ON” position.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (deter­mine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 14 (page 19) with the time clocked.
4. Read the “Flow” column opposite the number of seconds clocked. (Table 14, page 19)
5. Use the following factors
For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu. Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 16), or changing orifices (orifice change may not always be required). To adjust the manifold pres­sure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tubing to the outlet pressure boss marked “OUT P” on White-
if necessary:
Chart Flow Reading ÷ 2
Chart Flow Reading ÷ 4
10X Chart Flow Reading ÷ 4
Rodgers gas valve model 36G or 36J. See Figure 28 for White-Rodgers gas valve model 36J. See Figure 27 for White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set screw one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611)
contains a 3/32" hex wrence, a 5/16" hose and a connector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
5. Adjust gas heat by removing the adjustment regulator cover screw.
a. To increase outlet pressure, turn the regulator adjust
screw clockwise.
b. To decrease outlet pressure, turn the regulator adjust
screw counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in Table 16.
1. The input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude.
d. Replace and tighten the regulator cover screw securely.
6. Cycle the valve several times to verify regulator setting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and tighten
the pressure tap screw.
9. Using a leak detection solution or soap suds, check for
leaks at the pressure outlet boss and pressure tap test screw.
10. Turn on system power and check operation of the unit.
!
CAUTION
Replace and/or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage.
For LP gases, the final manifold pressure setting shall be
10.5" W.C. with an input of no more than the nameplate
rating and no less than 93% of the nameplate rating, unless the unit is derated for altitude.
Table 12 (page 19) lists the main burner orifices shipped with the furnace. If a change of orifices is required to correct the input rate, refer to Table 13 (page 19).
TABLE 11
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10 20 30 40 50 60 70
1 520 350 285 245 215 195 180
LENGTH OF PIPE
18 18-CD19D7-22
Page 19
Installer’s Guide
Outlet Pressure Boss
On/Offff
Switchch
In
let Pressure
Boss (opt.).)
Regulula
tor
Adj
ust
TABLE 12
ORIFICE SIZES
INPUT
RATING
BTUH
40,000
60,000
80,000 100,000 120,000 140,000
NUMBER
OF
BURNERS
2 3 4 5 6 7
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS LP GAS
45 45 45 45 45 45
56 56 56 56 56 56
TABLE 13
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45 46 47 48 49 50
PART
NUMBER
ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493
DRILL
SIZE
54 55 56 57 58 59
PART
NUMBER
ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at elevations up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. The furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max
3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate cannot be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change.
IMPORTANT: Reinstall the propane orifices to the same depth as the orifices supplied with the equipment.
TABLE 14
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88 9 800 30 240 51 141 84 86
10 720 31 232 52 138 86 84
11 655 32 225 53 136 88 82 12 600 33 218 54 133 90 80 13 555 34 212 55 131 92 78 14 514 35 206 56 129 94 76 15 480 36 200 57 126 96 75 16 450 37 195 58 124 98 73 17 424 38 189 59 122 100 72 18 400 39 185 60 120 104 69 19 379 40 180 62 116 108 67 20 360 41 176 64 112 112 64 21 343 42 172 66 109 116 62 22 327 43 167 68 106 120 60 23 313 44 164 70 103 124 58 24 300 45 160 72 100 128 56 25 288 46 157 74 97 132 54 26 277 47 153 76 95 136 53 27 267 48 150 78 92 140 51 28 257 49 147 80 90 144 50
Outlet Pressure Boss
j
tor
Adj
ust
let Pressure
Boss
See Table 15 (page 20) for help in selecting orifices if orifice change is required. Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude.
Installations above 4,000 feet may require a pressure switch change. If required, use the BAYHALT*** Kit (High Altitude Accessory Kit) listed in PRODUCT DATA.
Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with the local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA 149.1. Installation of
this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace.
18-CD19D7-22 19
k
Inlet Pressure Boss (opt.)
Swi
White-Rodgers 36G gas valve
Outlet Pressure Boss
On/Off Switch
White-Rodgers 36J gas valve
Regulator Adjustment
Page 20
Installer’s Guide
TABLE 15
Orifice
Twist Drill
Size If
Installed
At Sea
Level
43
45 46
FINAL MANIFOLD PRESSURE
NATURAL GAS 3.5" W.C.
LIGHTING INSTRUCTIONS
DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death.
Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automati­cally heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied.
TO SHUT OFF
For complete shutdown: Move the control switch on the main gas valve to the “OFF” position (See Figures 27 and 28, page
19). Disconnect the electrical supply to the unit.
If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles. Failure to follow this warning could result in property damage.
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUS­TIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.
20 18-CD19D7-22
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
44
47 54
55 56 57 58
42 44 45 46 47 48
54 55 56 58 59
From National Fuel Gas Code - Table F-4
SETTINGS (inches w.c.)
FUEL PRESSURE
LP GAS 10.5" W.C.
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
45
46
44
44
45
45
46
47
47
45
45
46
47
47
48
48
47
47
47
48
48
49
49
47
47
48
48
49
49
50
48
49
49
49
50
50
51
55
55
55
55
55
55
55
57
56
59
59
60
60
TABLE 16
!
WARNING
!
CAUTION
!
WARNING
56 57 60
61
56 57 60 62
56 58
61
62
56 56 59 62 63
56 56 59 63 63
47 48 50 50 51 52
56 57 60 63 64
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important in below freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes.
CONTROL AND SAFETY SWITCH ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by blocking the return air or by disconnecting the blower. When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit control, be sure to remove the blockage from the return air inlet, or reconnect the blower.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they are within the ranges specified on the furnace rating name­plate. If the airflow needs to be increased or decreased, see the wiring diagram (in Service Facts) for information on changing the speed of the blower motor.
!
WARNING
Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace.
NOTE: Direct drive motors have bearings which are permanently lubricated and under normal use, lubrica­tion is not recommended.
INDOOR BLOWER TIMING
The control module controls the indoor blower. The blower starts approximately 45 seconds after ignition. The FAN­OFF period is approximately 100 seconds from the interrup­tion of gas flow.
ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on the furnace wiring diagram (found inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment (See Figure 26 on page 17). Also turn off electrical power to the furnace and contact the service agency designated by your dealer.
Page 21
Installer’s Guide
!
WARNING
Should overheating occur, or the gas supply fail to shut off, shut off the gas valve to the unit before shutting off the electrical supply. Failure to follow this warning could result in property damage, personal injury or death.
The following warning complies with State of California law, Proposition 65.
!
WARNING
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse
washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact – Flush eyes with water to remove dust.
Skin Contact – Wash affected areas gently with soap
If symptoms persist, seek medical attention.
and warm water after handling.
OPERATING INFORMATION
FLAME ROLL-OUT DEVICE
All models are equipped with a thermal control device on the burner cover. In case of flame roll-out, the device will cause the circuit to open which shuts off all flow of gas.
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow --- Normal - No call for Heat Flashing Fast --- Normal - Call for Heat Continuous ON --- Replace IFC Continuous OFF --- Check Power
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems
3 Flashes ---
4 Flashes --- Open Temperature Limit Circuit 5 Flashes --- Flame sensed when no flame should be present
6 Flashes ---
7 Flashes --- Gas valve circuit error 8 Flashes --- Low flame sense signal
9 Flashes ---
18-CD19D7-22 21
a) Venting problem b) Pressure seitch problem c) Inducer problem
115 Volt AC power reversed or Poor Grounding or system voltage too low
Check Ignitor circuit and Line "N" to 24VAC "Common" voltage (< 2volts) (possible grounding problem)
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION VENT PRESSURE OR FLUE BLOCKAGE If pressure against the induced draft blower outlet becomes excessive, the pressure switch will shut off the gas valve until acceptable combustion pressure is again available.
2. LOSS OF FLAME OR GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle (when flame is not present at the sensor), the control module will retry the ignition sequence up to two times after the sensor cools. If ignition is not achieved, it will lockout the furnace.
3. POWER FAILURE If there is a power failure during a heating cycle, the system will restart the ignition sequence automatically when power is restored, if the thermostat still calls for heat.
4. INDUCED DRAFT BLOWER FAILURE If pressure is not sensed by the pressure switch, it will not allow the gas valve to open, therefore the unit will not start. If failure occurs during a running cycle, the pressure switch will cause the gas valve to close and shut the unit down.
Carbon monoxide, fire or smoke can cause serious bodily injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detec­tors per the manufacturer’s installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide. These devices should be listed by Underwriters Laboratories, Inc. Standards for
Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
TABLE 17
IFC ERROR FLASH CODES
Page 22
Installer’s Guide
NOTES
22 18-CD19D7-22
Page 23
NOTES
Installer’s Guide
18-CD19D7-22 23
Page 24
Trane 6200 Troup Highway Tyler, TX 75707
For more information contact your local dealer (distributor)
Literature Order Number 18-CD19D7-22
File Number 18-CD19D7-22
Supersedes 18-CD19D7-21
Date 02/11
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
P.I. 08/02
Loading...