Trane TD-5 Display Installation and Maintenance Manual

Page 1
Installation, Operation, and Maintenance
TracerTD-5 Display
for ReliaTel™ Controller
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air­conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
November 2013
RT-SVX49A-EN
Page 2

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal ProtectiveEquipment (PPE) recommended for the work being undertaken.
ALWAYSreferto appropriate MSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or
© 2013Trane All rights reserved RT-SVX49A-EN
Page 3
Table of Contents
Warnings, Cautions and Notices .......... 2
Introduction ............................. 4
Hardware ............................. 4
Power ............................. 4
Communication ..................... 4
Screen characteristics ................ 4
Touchscreen Guidelines ................ 4
Dimensions ........................... 5
Specifications and Agency Compliance ... 6
Supported Languages .................. 6
Screen Overview ...................... 7
Top Display Area .................... 7
Main Display Area ................... 7
Bottom Display Area ................. 7
Installing the Tracer™ TD-5 Display ....... 8
Packaged Contents .................... 8
Additional Mounting Parts ............. 8
Installing the TD-5 Display onto a VESA Mounting Bracket
...................... 8
Powering up the TD-5 Display for the First Time
................................. 9
Alarms ................................. 10
Active Alarms ........................ 10
Historic Alarms ....................... 11
Viewing Active and Historic Alarms ..... 11
Alarm Icons .......................... 12
Sorting Alarms ....................... 12
Sensor Report ........................20
Binary Input Report ...................20
Binary Output Report ..................21
Graphs .................................22
Creating a Custom Graph ..............22
Standard Graphs ......................25
Space Temperature: .................25
Compressor Graph: ..................25
VAV System: .......................26
Economizer Graph: ..................26
Outside Air Ventilation: ..............26
CO2Graph: ......................... 26
Humidity Graph: ....................26
Heat Pump Graph: ...................26
Settings ................................27
Setpoints ............................ 27
Setup ................................28
Display Settings Screen ................ 29
Display Preferences .................29
Language .......................... 31
Date and Time ......................31
Clean Touchscreen ..................32
Troubleshooting ........................33
Identifying and Diagnosing Issues .......33
Reports ................................ 13
Custom Reports ...................... 13
Creating a Custom Report ............ 13
Editing a Custom Report ............. 15
About ............................... 16
System Report ....................... 17
Economizer/Ventilation Report ......... 18
Compressor Report ................... 18
Heating Report ....................... 19
Configuration Report .................. 19
RT-SVX49A-EN 3
Page 4

Introduction

The purpose of this guide is to assist you in installing,
programming, and operating the Tracer™TD-5 display, which operates with the ReliaTel™ Controller.This guide describes how to access the screens and the types of information that appear on the screens.
TheTracer™TD-5 display allows you to view data and
make operational changes on the following types of applications:
Voyager™
Precedent™

Hardware

TheTracer™TD-5 is a durable touch screen display that is
designed to operate in both indoor or outdoor environments.The TD-5 display utilizes a standard 75mm
VESA mounting pattern for installation. Alternatively, it
can be installed with a user-supplied VESA mount.

Power

TheTracer™TD-5 display is powered by 24 VAC or 24 VDC
and requires 21 VA power, which it receives through a power cable.The display is typically connected to J10 of the RTRM Module, but it can also be powered from an alternate power source.

Communication

Communication is provided to theTD-5 through the RTRM J10 connector.

Screen characteristics

The 5-inch WVGA 800 x 480 resolution touch-sensitive
color screen is LED backlit, which enables viewing in poor light conditions including outdoor usage (with the exception of direct sunlight).

Touchscreen Guidelines

The touch screen registers the downward pressure of a
touch. Light, quick, yet deliberate touches are most effective.Touching with more pressure has no effect.
Recommended tools to use:
finger
thumb
pencil eraser
Do not use:
a screwdriver
a pen
a pencil point
any other sharp or pointed object that might scratch the screen surface
4 RT-SVX49A-EN
Page 5

Dimensions

32,0
42,1
Introduction
147,0
][8.5
][7.1
154,0
][3.1
][1.6
Note: The power cable is permanently attached
to theTD-5 display.The power connector provides strain relief and protection from the
115,3
][5.4
106,4
][2.4
RT-SVX49A-EN 5
Page 6
Introduction

Specifications and Agency Compliance

Specification
Input power:
Storage temperature:
Operating temperature:
Mounting weight:
Environmental rating (enclosure):
Agency Compliance
• UL916 PAZX, Open Energy Management Equipment
• UL94-5V, Flammability
• FCC CFR Title 47, Part 15.109: Class A Limit, (30 MHz – 4 GHz)
• CE EMC Directive 2004/108/EC
• CE EMC Directive 2004/108/EC
24 Vac ± 15%, or 24 Vdc ± 10% 21 VA, 50 or 60 Hz
–67°F to 203°F (–55°C to 95°C) Humidity: Between 5% to 100% (non-
condensing) Temperature: –40°F to 158°F (–40°C to 70°C)
Humidity: Between 5% to 100% (non­condensing)
Mounting surface must support 0.93 lb (422 grams) Mounting Type: VESA (75 mm x 75 mm)
IP55 (dust and strong water protected) (PN: X19070632020)

Supported Languages

TheTD-5 display supports 26 built-in languages. For help
on how to select a specific language for the display, see
“Language,” p. 31.
Arabic Hungarian Romanian Chinese (Simplified) Indonesian Russian Chinese (Traditional) Italian Spanish (Mexico) Czech Japanese Spanish (Spain) Dutch Korean Swedish English Norwegian Thai French Polish Indonesian German Portuguese (Brazil) French Canadian Hebrew Portuguese (Portugal)
6 RT-SVX49A-EN
Page 7
Introduction

Screen Overview

There are three distinct areas on the TD-5 screens:
Top display area
Figure 1. Tracer™TD-5 display screen

Top display area

Main display area

Bottom display area

Main display area
Bottom display area
Top Display Area
The Back button, when touched, returns to the previous screen visited.
The Home button, when touched, navigates to the Home Page. Home can be configured. See “Display Preferences,”
p. 29.
The Header Data Point is a user-defined data point that will appear at the top portion of each display screen. This value can be the present value of any point in the TD-5. See “Header Data Point, ” p. 29.
Main Display Area
This area serves as the main task area in which you can
view custom graphics, create reports, view and take action on alarms, and view or change display settings.
Bottom Display Area
The bottom display area contains functional buttons that
provide a link to the appropriate screen.
Screen brightness settings: Touch this icon to change the display’s brightness.
Touch this button to open the Alarms screen. When an alarm is present, this button will flash red.
Touch this button to navigate to the Reports screen.
T ouch this button to open the Data Graphs screen to view Graphs.
Touch this button to open the Settings screen, which contains options for controls, security (if enabled), and display settings.
Language selection: Touch this icon to select a language that will be displayed on all screens.
RT-SVX49A-EN 7
Page 8

Installing the Tracer™TD-5 Display

This section describes installation procedures when
mounting theTracer™ TD-5 display near the RTRM module or remotely mounted up to 328 ft (100 m) by using a field-suppled 75 mm VESA mounting bracket. Read and observe all warning and caution statements before you begin the installation procedure.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Packaged Contents

One (1)Tracer™ TD-5 display with permanently attached 2.6 ft (0.8 m) power cable with male connector
Four (4) M-4 screws
Four (4) spacer washers

Additional Mounting Parts

TD-5 Display Low Profile Mounting Bracket (VESA 75mm) (PN: X05010511010)
4. Securely tighten the M-4 screws using a Phillips screwdriver.
Installing the TD-5 Display onto a
VESA Mounting Bracket
TheTracer™TD-5 can be mounted near the RTRM module
in the control panel, or remotely mounted up to 328 ft (100 m) by using a field-suppled 75 mm VESA mount.
Remote mounting requires the following additional field­supplied components:
A power source that will supply 24 VAC to the display
Power cables
Many commercial 75mm VESA mounting brackets are available, which range from a simple wall mount to tilt­and-swivel mounts such as the one shown in Figure 2, p. 9, or theTD-5 Display Low Profile Mounting Bracket (VESA 75mm) (PN: X05010511010) .
To install onto a VESA mounting bracket:
1. Disconnect power at the circuit breaker and perform lockout/tagout procedures.
2. Mount the VESA mounting bracket according to manufacturer’s instructions.
3. Position the TD-5 display bracket bracket while inserting and hand-tightening the four M-4 screws. (Some brands ofVESA mounting brackets may require the use of the four spacer washers to allow the M-4 screws to tighten properly.)
2 and align the four mounting holes with the
1onto the VESA mounting
8 RT-SVX49A-EN
Page 9
Figure 2. Example VESA mounting
Installing theTracer™TD-5 Display
1
Powering up the TD-5 Display for
2
the First Time
After completing the installation instructions in “Installing
theTracer™TD-5 Display,” p. 8,TheTD-5 display can be
powered up.
Before applying power to theTD-5 Display, verify that the RTRM Module is powered up.
Upon successful power up, theTD-5 Display will default to the configured home screen. The System Report is the factory default.
Important: Do not attempt to update theTD-5 Display
from a connection type other than a USB.
RT-SVX49A-EN 9
Page 10

Alarms

Alarms appear on the Tracer™TD-5 display immediately upon detection.Touch the Alarms button in the bottom display area to view the Alarms screen.

Active Alarms

Figure 3, p. 10 shows the Active Alarms screen and
commonly used functions. Configuration is not required in order for points in alarm to appear in the Active Alarms
Figure 3. Active alarms screen
Sortable columns
Alarm severity
screen. When the alarm clears and the point returns to normal, the alarm will automatically be removed from the list.The number of active alarms is displayed in the top right portion of the screen. When an active alarm is present, the alarm button at the bottom of the screen will flash.
The Alarms screen defaults to Active Alarms. The Active
Alarms button has a shaded appearance which indicates
that you are viewing active alarms.
Number of active alarms
Active Alarms button
10 RT-SVX49A-EN
Page 11

Historic Alarms

On the Alarms screen, touch the Historic Alarms button to view all alarms, commonly referred to as the event log (see
Figure 4, p. 11).
Figure 4. Historic alarms screen
Sortable columns
Alarm severity
Alarms
Number of historic alarms
Historic Alarms button
Viewing Active and Historic
Alarms
Active alarms:These are alarms that require attention. All alarms that are currently active appear when you view this category. Active alarms are not reset by way of the display. Active alarms will clear automatically when the condition causing the alarm is removed.
Historicalarms: Historic alarms appear when you view this category.The alarms are listed in chronological order.
Alarm Severity
A color-code icon representing the severity of each alarm is shown under the severity (!) column. For a description of the five alarm icons, see Table 1, p. 12.
Sortable Alarms
You can sort active alarms by touching one of the column
headers. Choose to sort by severity (!), date and time, point name, or description.
RT-SVX49A-EN 11
Page 12
Alarms

Alarm Icons

Alarms icons appear in the left-most column of the alarms screen.They are identifiable by their shape and color.
Table 1. Alarm icons
Active Alarm Icons
Note: Notifications classes are configured in point alarm settings section
in Tracer TU.
Notification Class
Critical
Service Required
Information

Sorting Alarms

To sort alarms by a category other than date and time,
touch one of the other column headings in the table. The column heading responds by changing to blue, and the alarms table re-sorts according to the blue column heading. By touching the blue column heading again, the column will change the sort direction.
Severity (!): Active alarms are at the top, followed by the most severe, followed by the most recent.
Date andTime (the default sort): Most recent alarms are at the top.
Description: Alarms are sorted alphabetically by description.
Table 2. List of alarms
Space Temp Sensor Failure Outdoor Temp Sensor Fail Compressor 1 HPC Lockout Compressor 1 LPC Lockout Comp 1 Disable Input/LPC Compressor 2 HPC Lockout Compressor 2 LPC Lockout Comp 2 Disable Input/LPC Smoke Detector Heat Failure Dirty Filter Supply Fan Failure Emergency Stop Frostat™ Trip Mixed Air Temp Sensor Fail OA Humidity Sensor Failure Return Air Temp Sensor Fail Return Air RH Sensor Failure Coil Temp Sensor #1 Fail Demand Defrost Fault A Demand Defrost Fault B Demand Defrost Fault C Demand Defrost Fault D Defrost Default Mode Local Cool Setpoint Fail Local Heat Setpoint Fail Vent Override – Purge Vent Override – Exhaust Vent Override – Pressurize Drain Pan Overflow Freezestat Tripped Supply Air Temp Sensor Fail CO
Sensor Failure CO2 Setpoint Failure
2
Space Humidity Sensor Fail Dehumid Setpoint Failure
Table 2. List of alarms (continued)
Air Flow Sensor Fail Min OA Flow Setpoint Fail Space Pressure Setpoint Fail Space Pressure Sensor Fail Heating High Temp Limit Open Flame Rollout Switch Open Inducer Proving Switch Fail No Flame Sensed on heat call Flame Sensed w/Gas Valve Off Gas Heat Module Failure Economizer Actuator Fault Morning Warmup Setpoint Fail SA Reset Amount Failure SA Temp Cool Setpoint Fail SA Temp Heat Setpoint Fail SA Reset Setpoint Failure SA Press Setpoint Fail SA Pressure Deadband Fail Supply Air Press Sensor Fail SA High Press Limit SA Pressure PWM Fault Comp 1 Disable Input/HPC Comp 2 Disable Input/HPC CO2 Low Limit Setpoint Fault Exh/Ret Fan Proving Failure RTOM Comm Fail RTEM Comm Fail RTAM Comm Fail RTVM Comm Fail RTCM Comm Fail SA Reheat Setpoint Failure RTDM Comm Fail Space Press Deadband Fail Mod Dehumid Config Ent Evap Temp Sensor Fail Coil Temp Sensor #2 Fail SA Temp Heat Setpoint Fail Demand Defrost Fault A Ckt 2 Demand Defrost Fault B Ckt 2 Demand Defrost Fault C Ckt 2 Defrost Default Mode Ckt 2 Demand Defrost Fault A Ckt 1 Demand Defrost Fault B Ckt 1 Demand Defrost Fault C Ckt 1 Defrost Default Mode Ckt 1 Exhaust Fan Setpoint Fail IGN1 Communications Timed out IGN2 Communications Timed out DCV Min Position Setpoint Fail (@
Full Fan Speed) Enthalpy Setpoint Fail DCV Min Position at Minimum Fan
Speed Fail DA Cool Setpoint Fail PWM Max Fan Spd Setpt Fail Compressor 3 HPC Lockout Compressor 3 LPC Lockout Comp 3 Disable Input/LPC Comp 3 Disable Input/HPC Power on Reset TD-5 Loss of Comm with RTRM
Design Min Position Setpoint Fail (@ Full Fan Speed)
Design Min Position at Minimum Fan Speed Fail
Design Min Position at Midpoint Fan Speed Fail
12 RT-SVX49A-EN
Page 13

Reports

You can use theTracer™ TD-5 Display to view a variety of
reports and create and edit custom reports.
Touch the Reports button in the bottom display area to
view the Reports screen. The Reports screen contains the following buttons:
Table 3. Representation of screen below
Custom Report 1 System Report About Custom Report 2 Compressor Report Sensor Report Custom Report 3 Operating Modes Configuration Report
Economizer/ Ventilation Report
Binary Input Report Binary Output Report
Figure 5. Reports screen
Heating Report

Custom Reports

You can create up to three custom reports using the Tracer™TD-5 Display

Creating a Custom Report

1. Navigate to the Reports screen, then touch one of the three custom report buttons.
The Custom Report (1, 2, or 3) screen appears.
2. Touch the Edit button.
The Edit Custom Report screen appear s (Figure 6,
p. 14).
RT-SVX49A-EN 13
Page 14
Reports
Figure 6. Creating a custom report
3. Use the up and down arrow buttons to select a point. Add items by touching the item that is highlighted blue, then touch the Add button.
4. Continue adding values to your report. When you are finished, touch the Save button.
The Custom Report screen, populated with your
selected values, appears (Figure 7, p. 14).
Figure 7. New custom report screen
To view the items in the selected list, touch a value in
this list and use the up and down arrows to the right of the list.To change the location of an item in the list, select the item and then use the up and down arrows above the table to move the items.
14 RT-SVX49A-EN
Page 15
Reports

Editing a Custom Report

1. Touch Reports to view the Reports screen.
Figure 8. Editing a custom report
Category Selector
Scroll buttons to navigate through the data list
Changing the Order of Items in a Custom Report
Items in a custom report can be rearranged according to personal preference by using the editing tools as described in Editing a Custom Report.
For example, you created the custom report shown in
Figure 7, p. 14, but would prefer to move item “Diagnostic:
Space Static Pressure Failure” to the top left portion of the report.
To change the order for the example described above:
1. Touch the Edit button on the Custom Report screen.
2. Use the arrow buttons to locate the item to be reordered. When located, touch the item which will then be highlighted blue (see Figure 8, p. 15).
3. Use the arrow buttons to move the highlighted item to the top of the list (number 1 position).
4. Touch Save.You will be returned to the Custom Report screen, where the reordering changes now appear.
Note: On theTD-5 display, report items are ordered from
left to right with the first item appearing at the top left portion of the screen. Up to nine items can appear on each Custom Report screen.
The model in Figure 9, p. 15 depicts a custom report
screen with the first nine items displayed on the screen. Use this model to accurately reorder items in your custom reports.
2. Touch the report that you want to edit.
Follow steps 2 through 4 in “Creating a Custom
Report,” p. 13. to complete your edits.
Buttons that re-order your custom report list
Scroll buttons to navigate through the data list
Figure 9. Custom report (order of items)
Custom Report
1
4
7
23
5
8
6
9
RT-SVX49A-EN 15
Page 16
Reports

About

Touch the About button to view the About screen. View
information about the unit controller and theTD-5 display
Figure 10. About screen
to which it is connected.Touch the arrow button to scroll to the next screen.
Data Area
The following data are displayed on the About screen.
Unit Name ABCDEFGHIJKLMNOPQRSTUVWXYZ12456789
RTRM Software Version 6200-XXXX-YY.ZZ
RTOM Software Version 6200-XXXX-YY.ZZ
RTDM Software Version 6200-XXXX-YY.ZZ
Display User Interface Software Version 6200-XXXX-YY.zz
RTVM Software Version 6200-XXXX-YY.ZZ
RTAM Software Version 6200-XXXX-YY.ZZ
BAS Interface Software Version 6200-XXXX-YY.ZZ
Display Firmware Version 6200-XXXX-YY.zz
Unit Name. This is the name that was entered.
VSM Software Version 6200-XXXX-YY.ZZ
RTEM Software Version 6200-XXXX-YY.ZZ
Display Boot Code Version 6200-XXXX-YY.zz
16 RT-SVX49A-EN
Page 17

System Report

Touch the System Report button to view the System
Report screen.Touch the arrow buttons to move between screens.
Figure 11. System report screen
Reports
Data Area
The following data can be configured to appear on the
System Report screen. Only configured items will appear.
Unit Application VAV,CV,SZVAV
Supply Fan Output Energized, De-energized
Occupancy Occupied, Unoccupied
Active Space Temp XXX.X F/C
Supply Air Temp XXX.X F/C
Economizing Enabled, Disabled
Fresh Air Measurement Installed, Not Installed
Exhaust Fan Status Supply Fan Starts
XXXXX Supply Air Pressure
X.XX in(H RTOM Low Fan Speed Output Alarm Indicator Output VAV Box Output Thermostat Y1 Input Thermostat W1/O Input Thermostat G Input Thermostat W2 Input Thermostat Y2 Input Thermostat X2 Input Supply Fan Proving Input Condensate Drain Overflow Input Frostat™ Input Clogged Filter Input Smoke Detector Input Reheat Humidistat Input Changeover Switch Input
O)/ mm(H20)
2
Unit Mode Heat, Cool, Off, Emergency Heat
Supply Fan Speed % XXX %
Active Cooling Stages X
Active Space Temp Setpoint XXX.X F/C
Active Supply Air Temp Setpoint XXX.X F/C
Ventilation Type Fixed/DCV (*DCV = Demand Control Ventilation)
Demand Limit Active/Not Active
Available Cooling Stages X
Supply Fan Running Time HHHHH:MM
Local Space Temp X XX.X OF/C
Setpoint Source Remote, Local
Supply Fan Mode On, Auto
Active Heating Stages X
Outdoor Air Damper % XXX % Open
System Control Mode Manual, Auto
Variable Compressor Speed % XXX %
Heating Type None, Electric, Gas, Hydronic
Available Heating Stages X
Space Pressure X.XX in(H
Emergency Stop Input
O)/ mm(H20)
2
RT-SVX49A-EN 17
Page 18
Reports

Economizer/Ventilation Report

Touch the Economizer/Ventilation Report button to view
the Economizer/Ventilation Report screen.Touch the arrow buttons to move between screens.
Outdoor Air Damper % XXX % Open
Ventilation Type
Active Min OA Damper Position Target XXX %
Active Upper CO2 Limit Setpoint XXXX PPM
Active Enthalpy Setpoint XXXXX BTU / LBM
Outdoor Air Flow XXXXX CFM / LPM
Design Min Position High Speed Setpoint XXX %
DCV Min Position High Speed Setpoint XXX %
DCV Min OA Flow Setpoint XXXXX CFM / LPM
Exhaust Fan Running Time HHHHH:MM
Active Space Pressure Setpoint XX.XX IWC /cmWC
Outdoor Fan B Output Variable Speed Outdoor Fan % Ventilation Override Pressurize Input Ventilation Override Purge Input Ventilation Override Exhaust Input Power Exhaust Fan Output Supply Fan Proving Input
Economizing Enabled, Disabled
Economizing Enable Type Dry Bulb, Reference Enthalpy, Comparative
Enthalpy Manual Enthalpy Override
Enabled, Disabled Active Lower CO
XXXX PPM Return Air Humidity
XXX % Min Outdoor Air Flow Target
XXXXX CFM / LPM Design Min Position Mid Speed Setpoint
XXX % DCV Min Position Low Speed Setpoint
XXX %
Outdoor Air Flow Adjustment Setpoint
Exhaust Damper Position % Open XXX %
Space Pressure Deadband XX.XX IWC /cmWC
Limit Setpoint
2
Data Area
The following data can be configured to appear on the
Economizer/Ventilation Report screen. Only configured items will appear.
Mixed Air Temp XXX.X F/C
Outdoor Air Temp XXX.X F/C
Return Air Temp XXX.X F/C
Space CO XXXX PPM
Outdoor Air Humidity XXX %
Min Outdoor Air Flow Deadband XXXXX CFM / LPM
Design Min Position Low Speed Setpoint XXX %
Power Exhaust Fan Output Off, On, Auto
Exhaust Fan Starts XXXXX
Space Pressure XX.XX IWC /cmWC
Outdoor Fan A Output
2

Compressor Report

Touch the Compressor Report button to view the
Compressor Report screen.Touch the arrow buttons to move between screens.
Table 4. Compressor report - data area
Active Cooling Stages X
Outdoor Fan A Output Energized, De-energized
Dehumidification Status Inactive, Active Reheat, Active Enhanced
Compressor 1 Disable Input Enabled, Disabled
Compressor 1 Proving Input Open, Closed
Heatsink Refrigerant Temperature XXX.X F/C
Active Space Cooling Setpoint XXX.X F/C
Active Supply Air Temp Cooling Setpoint XXX.X F/C
Outdoor Coil Temp Ckt 1 XXX.X F/C
Available Cooling Stages X
Outdoor Fan B Output Energized, De-energized
Reheat Entering Evap Temp XXX.X F/C
Compressor 2 Disable Input Enabled, Disabled
Compressor 2 Proving Input Open, Closed
Supply Air Temp XXX.X F/C
Defrost Status Ckt 1 Inactive, Defrosting
Switchover Valve (SOV) 1 Output Heating, Cooling
Outdoor Coil Temp Ckt 2 XXX.X F/C
Data Area
The following data can be configured to appear on the
Compressor Report screen. Only configured items will appear.
Number of Compressors Installed X
Variable Speed Outdoor Fan % XXX.X %
Variable Compressor Speed % XXX.X %
Compressor 3 Disable Input Enabled, Disabled
Compressor 3 Proving Input Open, Closed
Space Temp XXX.X F/C
Defrost Status Ckt 2 Inactive, Defrosting
Switchover Valve (SOV) 2 Output Heating, Cooling
Compressor 1 Starts XXXXX
18 RT-SVX49A-EN
Page 19
Table 4. Compressor report - data area (continued)
Reports
Compressor 2 Starts XXXXX
Compressor 2 Running Time HHHHH:MM
Variable Speed Compressor Reheat Pumpout Relay

Heating Report

Touch the Heating Report button to view the Heating
Report screen.Touch the arrow buttons to move between
Compressor 3 Starts XXXXX
Compressor 3 Running Time HHHHH:MM
The following data can be configured to appear on the
Compressor 1 Running Time HHHHH:MM
Number of Compressors Installed
Defrost Starts Ckt 1 XXXXX *Phase 2
Data Area
Heating Report screen. Only configured items will appear.
screens.
Table 5. Heating report - data area
Heating Type None, Electric, Gas, Hydronic
Active Heating Stages X
Gas Heating Status
Defrost Status Ckt 2 Inactive, Defrosting
Outdoor Coil Temp Ckt 2 XXX.X F/C
Heating Stage 2 Output Active, Inactive
Gas Heating Type IGN Pressure Switch Input IGN Temp Limit Input IGN Flame Rollout Input IGN Inducer High Output IGN Inducer Low Output
Heating Configuration Staged /Modulating
Space Temp XXX.X F/C
Supply Air Temp XXX.X F/C
Active Space Heating Setpoint XXX.X F/C
Active Supply Air Temp Heating Setpoint XXX.X F/C
Freezestat Input Open, Closed
Available Heating Stages X
Modulating Heat Output % XXX %
Defrost Status Ckt 1 Inactive, Defrosting
Outdoor Coil Temp Ckt 1 XXX.X F/C
Heating Stage 1 Output Active, Inactive
Outdoor Air Temp XXX.X F/C

Configuration Report

Touch the Configuration Report button to view the
Configuration Report screen.Touch the arrow buttons to move between screens.
Table 6. Configuration report - data area
Unit Application CV, VAV, SZVAV
Dehumidification None, Hot Gas Reheat, Enhanced
Dehumidification Type Staged, Modulating
Cooling Stages Configured X
Economizer Enable Type Drybulb, Reference Enthalpy, Comparative
Enthalpy Heat Pump Type
Single, Independent True Supply Air Reporting
Enable, Disable
Refrigeration Type Cooling Only, Heat Pump
Supply Fan Control Type Fixed, Variable, IGV
Heating Type None, Electric, Gas, Hydronic
Cooling Steps Input 3 Step, 2 Step
Heating Stages Configured X
Supply Fan Motor Type Fixed, VFD, ECM, ERM
Windmill Prevention Enable, Disable
Supply Air Tempering Input Enable, Disable
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will appear.
Product Type Voyager™ Commercial, Precedent™/
Precedent™ 17 Plus/Voyager™ Light Commercial/Odyssey™
Economizer Installed, Not Installed
CV Control Type Zone Sensor, Thermostat
Number of Compressors Installed X
Variable Speed Compressor Installed, Not Installed
Supply Fan Motor Control 0 to 10VDC, PWM
Gas Ignition Module 1 Staged, Modulating
Gas Ignition Module 2 Installed, Not Installed
RT-SVX49A-EN 19
Page 20
Reports
Table 6. Configuration report - data area (continued)
Manual Enthalpy Override Enable, Disable
Outdoor Fan Cycling Input Normal, Lower
Outdoor Air Flow Compensation Enable, Disable
Supply Air Tempering Input Disable, Enable
Lead Lag Configuration Input Enable, Disable
Programmable Zone Sensor Installed, Not Installed
Evaporator Defrost Control Enable, Disable
Outdoor Fan Cycling Input Normal, Lower

Sensor Report

Touch the Sensor Report button to view the Sensor Report
screen.Touch the arrow buttons to move between screens.
Table 7. Sensor report - data area
Active Space Temp XXX.X OF/C
Outdoor Air Temp XXX.X OF/C
Outdoor Air Humidity XXX.X%
Outdoor Air Flow XXXXX CFM/LPM
Outdoor Coil Temp Ckt 2 XXX.X OF/C
Supply Air Pressure X.XX in(H
O)/ mm(H20)
2
Local Space Temp XXX.X OF/C
Mixed Air Temp XXX.X OF/C
Return Air Humidity XXX.X%
Space Humidity XXX%
Space Pressure X.XX in(H
O)/mm(H20)
2
OA Flow Compensation Enable, Disable
Cabinet Type Horizontal, Downflow
RTRM Fan Proving Input Closed, Open
Exhaust Air Control - StatiTrac™ Installed, Not Installed
Data Area
The following data can be configured to appear on the
Sensor Report screen. Only configured items will appear.
Supply Air Temp XXX.X OF/C
Return Air Temp XXX.X OF/C
Space CO XXXX PPM
Outdoor Coil Temp Ckt 1 XXX.X OF/C
Reheat Entering Evap Temp XXX.X OF/C
2

Binary Input Report

The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report button to view the Binary Input Report screen.
Table 8. Binary input report - data area
RTRM
RTOM
VSM
RTVM
Emergency Stop Input Auto, Emergency Stop
Thermostat Y1 Input Open, Closed
Thermostat W2 Input Open, Closed
Compressor 1 Disable Input Closed, Open
Compressor 2 Proving Input Operating, Not Operating
Supply Fan Proving Input Open, Closed
Ventilation Override Purge Input Open, Closed
Clogged Filter Input Open, Closed
Reheat Humidistat Input Open, Closed
Compressor 3 Disable Input Closed, Open
Exhaust Fan Proving Input Open, Closed
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will appear.
Occupancy
Thermostat W1/O Input Open, Closed
Thermostat Y2 Input Open, Closed
Compressor 1 Proving Input Operating, Not Operating
Condensate Drain Overflow Input Open, Closed
Ventilation Override Exhaust Input Open, Closed
Freezestat Input Open, Closed
Changeover Switch Input Cooling, Heating
Compressor 3 Proving Input Operating, Not Operating
RTRM Fan Proving Input Closed, Open
Thermostat G Input Open, Closed
Thermostat X2 Input Open, Closed
Compressor 2 Disable Input Closed, Open
Ventilation Override Pressurize Input Open, Closed
Frostat™ Input Open, Closed
Smoke Detector Input Open, Closed
20 RT-SVX49A-EN
Page 21
Table 8. Binary input report - data area (continued)
Reports
IGN
IGN Pressure Switch Input Open, Closed

Binary Output Report

The Binary Input report provides general Reliatel Unit
operating information.Touch the Binary Input Report button to view the Binary Input Report screen.
Table 9. Binary output report - data area
RTRM
RTOM/RTAM/RTVM/ RTEM/RTDM
IGN
Supply Fan Output Off, On
Heat Stage 1 Output Off, On
Heat Stage 2 Output Off, On
RTOM Low Fan Speed Output Off, On
Power Exhaust Fan Output Off, On
IGN Inducer High Output Off, On
IGN Temp Limit Input Open, Closed
Data Area
The following data can be configured to appear on the
Configuration Report screen. Only configured items will appear.
Compressor 1 Output Off, On
SOV 1 Output Off, On
SOV 2 Output Off, On or Low Fan Speed or Compressor 3 Output Off, On
Alarm Indicator Output Off, On
Reheat Pumpout Relay Off, On
IGN Inducer Low Output Off, On
IGN Flame Rollout Input Open, Closed
Compressor 2 Output Off, On
Outdoor Fan A Output Off, On
Outdoor Fan B Output Off, On
VAV Box Output Off, On
Figure 12. Operating modes report details screen
Note: Operating Modes:The operating Mode page shall
show the user the general operation of the unit, and what modes it is operating in.
RT-SVX49A-EN 21
Page 22

Graphs

Graphs allow users to view data in graphical format on the Display. Four custom graphs and eight standard graphs are available. Graphs can be created with a maximum of four lines per graph. Custom graphs are user-defined and can be edited by changing the scale on the left and rightY­axis and choosing the line color.
Figure 13. Graphs screen
Touchthe Graphs button in the bottom display area to view
the Graphs screen (Figure 13, p. 22).The Graphs screen contains twelve buttons that allow you to view and edit a particular graph.There are four custom graphs and 8 standard graphs.

Creating a Custom Graph

5. Navigate to the Graphs screen, then touch an available data graph button.
The Custom Graph screen appears.
Figure 14. Edit graph screen
6. Touch the Edit Graph button.
The Edit Graph screen appears (Figure 14, p. 22).
22 RT-SVX49A-EN
Page 23
Graphs
7. Touch the Add/Remove button to add values to the custom data graph.
The Add/Remove screen appears.
8. Use the arrow buttons to select a value.
Figure 15. Adding data logs to the custom graph
9. Select the values, then touch the Add button (up to four
selections are allowed).
10.Touch the Save button.The Edit Graph screen appears,
which reflects the selected values.
11. Use the Edit Graph screen to modify the graph.Touch the Edit button that corresponds with the value that
Figure 16. Edit graph screen (after values have been added)
you want to change. Only one value can be edited at a time.
12. From the Edit screen you can choose whichY-axis to display the value, a color, and whether or not to show data samples.Touch the Save button when finished. Repeat the process with remaining values.
RT-SVX49A-EN 23
Page 24
Graphs
Figure 17. Customizing the graph
13.Touch the Save button to display the new graph (Figure 18, p. 24).
Note: Depending on the sampling rate, the custom graph
may be empty for several hours.
Figure 18. Viewing the graph
You can make changes to the way data is presented on the
graph at anytime.Touch the zoom-in icon and zoom­out icon to either increase or decrease the viewable time frame.This action also enables back and forward arrows that allow you to view data at various times of the day.
Editing theY-Axis
The default values on the right and left Y-axes can be
changed according to your specifications.
24 RT-SVX49A-EN
14.Touch the EditY-Axis button located on the top portion
of the Custom Data Graph screen.
The EditY-Axis screen appears (Figure 19, p. 25).
Page 25
Graphs
15.Touchthe Manually Select Range box for either the left or rightY-axis.
16.Touch the edit button next to one of the two value ranges.
Figure 19. Editing theY-Axis
The Keypad screen appears.
17. Select a new value and then touch Enter to save.
18. Repeat steps 2 through 4 until all preferred changes have been made.

Standard Graphs

There shall be 8 standard graphs.The standard graphs are
below:
Table 10. Standard graphs
Space Temperature Economizer
Compressor Outside Air Ventilation
VAV Humidity
Heat Pump CO

Space Temperature:

The table below describes the data in the System Status
graph:
Data Point Line Color Axis
Active Space Temp Setpoint Blue Left Active Space Temp Green Left Supply Air Temp Black Left Return Air Temperature Red Left

Compressor Graph:

The table below describes the data in the graph:
Data Point Line Color Axis
Active Supply Air Temp Setpoint Pink Left Variable Compressor Speed % Green Left Supply Air Temp Black Left Active Cooling Stages Blue Right
2
RT-SVX49A-EN 25
Page 26
Graphs

VAV System:

The table below describes the data in the System Status
graph:
Data Point Line Color Axis
Active Supply Air Temp Setpoint Pink Left Active Space Temp Green Left Supply Air Temp Black Left Return Air Temp Red Left

Economizer Graph:

The table below describes the data in the graph:
Data Point Line Color Axis
Outdoor Air Temp Purple Left Mixed Air Temp Grey Left Active Min OA Damper Position Target Pink Right Outdoor Air Damper % Yellow Right

Outside Air Ventilation:

The table below describes the data in the graph:
Data Point Line Color Axis
Min Outdoor Air Flow Target Black Left Outdoor Air Flow Pink Left Outdoor Air Damper % Yellow Right Outdoor Air Temp Purple Right

CO2Graph:

The table below describes the data in the graph:
Data Point Line Color Axis
Active Upper CO2 Limit Setpoint Red Left Active Lower CO Space CO Outdoor Air Damper % Yellow Right
Limit Setpoint Black Left
2
2
Green Left

Humidity Graph:

The table below describes the data in the graph:
Data Point Line Color Axis
Space Dehumidification Setpoint Yellow Left Outdoor Air Humidity Red Left Return Air Humidity Black Left Space Humidity Green Left

Heat Pump Graph:

The table below describes the data in the graph:
Data Point Line Color Axis
Outdoor Coil Temp Ckt 1 Green Left Outdoor Coil Temp Ckt 2 Blue Left Outdoor Air Temp Purple Left Discharge Air Temperature Grey Left
26 RT-SVX49A-EN
Page 27

Settings

The Settings screen provides options for display settings,
language, overrides and security.Touch the Settings button in the bottom display area to view the Settings screen.
Three categories for settings appear on the screen:
Figure 20. Settings screen
Control Settings
Display Settings
Security Settings

Setpoints

Touch the Setpoints button to view the Setpoints screen. Touch the arrow buttons to move between screens.
Figure 21. Setpoints screen
RT-SVX49A-EN 27
Page 28
Settings
Data Area
The following data can be configured to appear on the
Setpoints screen. Only configured items will appear.
Occupied Space Cooling Setpoint Unoccupied Space Cooling Setpoint Space Dehumidification Setpoint Occupied Space Heating Setpoint Unoccupied Space Heating Setpoint Supply Air Reheat Setpoint Discharge Air Heating Setpoint Discharge Air Cooling Setpoint Duct Static Pressure Setpoint Duct Static Pressure Deadband Morning Warm-up Setpoint Supply Air Cooling Setpoint Supply Air Heating Setpoint Daytime Warm-up Initiate Setpoint Space Pressure Setpoint Space Pressure Deadband Daytime Warm-up Terminate Setpoint CO CO
Lower Limit Setpoint Enthalpy Setpoint Supply Air Reset Setpoint
2
Exhaust Fan Enable Setpoint Supply Fan Adjustment Setpoint Outdoor Air Flow Adjustment Setpoint Design Min OA flow Setpoint DCV Min OA Flow Setpoint Min OA Flow Deadband Design Min OA Damper Pos Setpoint 100% FanDesign Min OA Damper Pos Setpoint Mid Fan Design Min OA Damper Pos Setpoint Min Fan DCV Min OA Damper Pos Setpoint 100% Fan DCV Min OA Damper Pos Setpoint Min Fan Outdoor Air Flow Adjustment Setpoint
Upper Limit Setpoint
2

Setup

Touch the Setup button to view the Setpoints screen. Touch the arrow buttons to move between screens.
Figure 22. Setup screen
This Setup screen shows a list of the setup items in button
format.The available setup items are listed below:
Unit Mode Heat, Cool, Auto
System Control Mode Local, Remote
Supply Air Reset Type Heat, Cool, Auto
28 RT-SVX49A-EN
Supply Fan Mode On, Auto
Display Read Only Mode Read, Write
Service Test Disable, IGV Close, IGV Open, Fan Only/Min Vent, Economizer Open, Cool 1, Cool 2, Cool 3, Dehumid/Reheat, Heat 1, Heat 2, Heat 3, Defrost, Emergency Heat
Emergency Heat Mode Request Auto, Emergency Heat
Page 29
Settings

Display Settings Screen

The selections in this category contain settings that affect
the way in which information is displayed on all of theTD­5 display screens. From each screen, the current settings can be viewed. To change a setting, touch the preferred value.
Figure 23. Display preferences screen

Display Preferences

Touch the Display Preferences button to open the
associated screen (Figure 23, p. 29). On this screen, all available options to display information on the TD-5 screens are available. There are two pages on this screen, accessed by using the arrow button at the bottom of the screen.
Date Format
Touch the Date Format button to open the associated
screen.Three options are available to display the current date: MMDDYYYY, DDMMYYYY, andYYYYMMDD.
Date Separator
Touch the Date Separator button to open the associated
screen.Three options are available to display separators in the date format: None, Hyphen (-), or Slash (/).
Time Format
Touch the Time Format button to open the associated
screen.Two options are available: 12-Hour format and 24­Hour format (also referred to as “military time”).
Unit System
Touch the Unit System button to open the associated
screen.Two options are available: SI (system international) or IP (Inch-Pound).
Brightness
Touch the Brightness button, or the brightness icon
( )located at the bottom left of each screen, to open the associated screen. Screen brightness is measured in percentage. Use the keypad to enter a new brightness number.
BacklightTime-out
Touch the Backlight Time-out button to open the
associated screen.This value is measured in minutes, with 30 being the maximum limit. Use the keypad to enter a backlight time-out value.This value is the amount of time that the display will remain lit without activity. When the backlight times out, users will be automatically logged off due to inactivity.
Header Data Point
Use the arrow button on the Display Preferences screen to advance to page 2.Touch the Header Data Point button to open the associated screen. The Header Data Point appears in the top right display area on all screens. Use the arrow buttons to scroll through the points. Click Add to move the highlighted point to the right side of the screen(Figure 24, p. 30). Click Save.
RT-SVX49A-EN 29
Page 30
Settings
Figure 24. Setting the header data point
Header data point
Collection Frequency
Collection frequency sets the time interval that the Graph Data is saved, and displayed on the graph.The faster the
Figure 25. Collection frequency
sample rate, the lower the duration.The default of 30 seconds shall provide 3.5 days of data collection.
30 RT-SVX49A-EN
Page 31
Settings
Home Page
Use the arrow button on the Display Preferences screen to advance to page 2. Touch the Home Page button to open
Figure 26. Home page screen
the associated screen.This function allows you to choose what will display when the home button is touched.

Language

Touch the Language button, or the language icon ( )
located at the bottom right of each screen, to open the
Figure 27. Language screen
open the Language screen. Twenty-six languages are available and represented on the selection buttons. Select a language that you want displayed on eachTD-5 screen and then touch Save.See“Language,” p. 31.

Date and Time

Touch the Date and Time button to open the associated
screen.To enter a new date or time, touch the digit you
RT-SVX49A-EN 31
want to change. When enabled for editing, the digit will appeared with a black border. when finished, touch Apply or Save.Or,
Page 32
Settings
tap the digit twice which opens the keypad screen where you can make date and time entries. When finished, touch
Figure 28. Date and time screen
Enter; you will be returned to the Date and Time screen.
Touch Apply or Save.

Clean Touchscreen

Touch the CleanTouchscreen button to safely clean theTD-
5 touchscreen using any brand of common household glass cleaner. When this button is touched, the screen background color becomes black, allowing dirt and fingerprints to become more visible. It also displays a countdown timer (five to zero seconds).Touch the screen anytime within the 5-second countdown to begin cleaning the screen (each touch resets the 5-second countdown).
32 RT-SVX49A-EN
Page 33

Troubleshooting

This section describes the possible error messages and
other issues that you may encounter while using the
Tracer™TD-5 display.
Important: There are no serviceable parts within the
TD-5 display enclosure. Opening the
enclosure will void the product warranty.

Identifying and Diagnosing Issues

Problem Possible Cause Possible Solution
Blank display (TD-5 does not respond to touch).
After powering up, the TD-5 displays a message that it is not communicating.
No data available in custom report. Data has not yet been defined for the report.
No power.
Controller not powered up.
Verify that the TD-5 is connected to a power source, and that the power source is in working condition.
Replace cable if necessary . Power up the controller if necessary.
Add data to report. See “Creating a custom report, ”
p. 14.
RT-SVX49A-EN 33
Page 34
Page 35
Page 36
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensi ve building services, and parts. For more information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2013Trane All rights reserved
RT-SVX49A-EN 04 Nov 2013
(NEW)
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...