Trane TCONT803AS32DA, TCONT802AS32DA User Manual

Page 1
TCONT802AS32DA Touch Screen and TCONT803AS32DA Touch Screen with Dehumidification Control Comfort Controls
18-HD25D19-3
INSTALLATION INSTRUCTIONS
APPLICATION
Table 1. TCONT802AS32DA and TCONT803AS32DA Comfort Control Description.
Power Method Changeover System Selection Fan Selection Comments
24 Vac common wire
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
Automatic or manual selectable
Heat-Off-Cool­Auto (Em. Heat for heat pumps)
On-Auto-Circ System and Fan selection
vary based on system type
System and Fan selection vary based on System type. Humidity sensor to control dehumidification.
Selecting Location
Install the comfort control about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Installer must be a trained, experienced service technician.
3. After completing installation, use these instructions to check out the product operation.
U.S. Pat. No. 6595430, D509151, and Other Patents Pending
NO
YES
NO
NO
Fig. 1. Selecting comfort control location.
5 FEET
[1.5 METERS]
M19925
69-1790-3
Page 2
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
/COOL
SC
S
P
S1
S2
C
G
Do not install the comfort control where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall
behind the comfort control.
Installing Wallplate
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The comfort control can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Position and level the wallplate (for appearance only).
2. Use a pencil to mark the mounting holes.
WALL
WIRES THROUGH WALL AND WIRE SLOT
WALL ANCHORS (2)
MOUNTING HOLES
MOUNTING SCREWS (2)
Fig. 2. Mounting wallplate.
3. Remove the wallplate from the wall and, if drywall,
drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.
5. Insert mounting screws into the holes and tighten.
M19916
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the comfort control.
HEAT PUM
HEAT
Y2
F
X2
W1
S1
S2
Fig. 3. Selecting terminal identifications for
Table 2. Selecting Terminal Identifications for
W2
system type.
System Type.
System Type
R
W1
REW TERMINAL
Wallplate
Ter mi nal
Identifications
Standard Heat/Cool Heat/Cool Fig. 5,
Standard Multistage up to 2 Heat/2 Cool
Heat Pump with Electric Auxiliary (Backup) Heat
Heat Pump with Fossil Fuel Auxiliary (Dual Fuel) Heat
NOTE: The factory default setting is configured for a
1 Heat/1 Cool System with a gas furnace.
Heat/Cool Fig. 7,
Heat Pump Fig. 9,
Heat Pump Fig. 12,
RC
R
O
Y
Y
G
B
M22636
Wiring
Diagram
Reference
Fig. 6
Fig. 8
Fig. 10, Fig. 11
Fig. 13, Fig. 14, Fig. 15
WIRING (FIG. 5-15)
All wiring must comply with local electrical codes and ordinances.
1. Select set of terminal identifications (Table 2) that corresponds with system type (heat/cool or heat pump in Fig. 3).
2. Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.
Pub. No. 18-HD25D19-3 69-1790—3 2
Fig. 4. Inserting wires in terminal block.
IMPORTANT
Use 18 gauge comfort control wire.
M19917
Page 3
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT/COOL
Y2
W2
S1
S2
T
2
GYR
W1
INDOOR
OUTDOOR
ODT
Y
TO POWER SUPPLY PER LOCAL CODES
FACTORY INSTALLED JUMPER.
1
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
2
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 5. Typical hookup of single-stage heat and cool
system with single transformer (1H/1C).
Y2
W2
S1
S2
T
1
GYR
T
OIL BURNER PRIMARY
INDOOR
OUTDOOR
Y
TO POWER SUPPLY PER LOCAL CODES
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
1
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 6. Typical hookup of single-stage heat and cool
system with two transformers (1H/1C).
1
W2
T
W3
B/C
B
(3 PH ONLY)
HEAT/COOL
W
B/C
B
(3 PH ONLY)
RC
R
W1
Y G B
RC
R
W1
Y G B
AIR HANDLER
COOLING UNIT O.D. SECTION (SINGLE STAGE)
OIL FURNACE
COOLING UNIT O.D. SECTION (SINGLE STAGE)
M22637
M22638
HEAT/COOL
Y2
W2 S1
S2
T
2
O
LO
BKR
Y
Y
Y2
Y1
TO POWER SUPPLY PER LOCAL CODES
FACTORY INSTALLED JUMPER.
1
2
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 7. Typical hookup of two-stage indoor and
two-stage cooling unit in a single transformer system
Y2
W2 S1
S2
1
2
3
Fig. 8. Typical hookup of two-stage indoor and
two-step scroll cooling unit in a single transformer
(2H/2C or 2H/1C or 1H/2C).
T
2
3
O
BK R
Y2
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.
LO
Y
Y1
Y
TO POWER SUPPLY PER LOCAL CODES
system (2H/2C or 2H/1C or 1H/2C).
1
G
W1
INDOOR
OUTDOOR
HEAT/COOL
1
W1
G
W2
RC
R
W1
Y G B
B/C
W2
B
(3 PH ONLY)
RC
R
W1
Y
G
B
B/C
B
(3 PH ONLY)
VARIABLE SPEED
TWO-STAGE
FURNACE/VARIABLE
SPEED AIR HANDLER
COOLING UNIT
O.D. SECTION (TWO STAGE)
M22640
VARIABLE SPEED
TWO STAGE
FURNACE
INDOOR
OUTDOOR
16 SEER
COOLING UNIT
O.D. SECTION
(TWO STEP)
M24231
3 69-1790—3
Pub. No. 18-HD25D19-3
Page 4
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT PUMP
Y2
F
X2
W1 S1
S2
T
2
O
GYR
W1
ODT-1
ODT-2
INDOOR
OUTDOOR
O
Y
R
FACTORY INSTALLED JUMPER.
1
2
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
W2
RC
R
O
Y G B
I-PF
SUPPL. HTR.
CONTROL BOX
W3
TO POWER
SUPPLY PER
LOCAL CODES AND AS DEFINED
IN FIELD
WIRING TABLE
BR(T)X2/BK
TO POWER SUPPLY PER LOCAL CODES
PM-A
REQ.
FOR
3 PH
AIR
B/C
T
HANDLER
HEAT PUMP O.D. SECTION
B
(SINGLE STAGE)
(3 PH ONLY)
M22641
Fig. 9. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
HEAT PUMP
Y2
F
X2
W1 S1
S2
T
2
BK
YLO
OYR
G
INDOOR
OUTDOOR
Y2
O
R
1
2
Y1
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
W1
ODT-1
ODT-2
X2/BK
RC
R
O
Y G B
I-PF
PM-A
SUPPL. HTR.
CONTROL BOX
W3
W2
WIRING TABLE
BR(T)
REQ. FOR 3 PH
TO POWER
SUPPLY PER
LOCAL
CODES AND
AS DEFINED
IN FIELD
TO POWER SUPPLY PER LOCAL CODES
F
VARIABLE
B/C
T
SPEED AIR HANDLER
HEAT PUMP
O.D. SECTION
B
(TWO STAGE)
(3 PH ONLY)
M22642
Fig. 10. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).
Pub. No. 18-HD25D19-3 69-1790—3 4
Page 5
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT PUMP
Y2
F X2 W1
S1
S2
T
2
3
O
BK R
G
LO
Y
Y2
Y1
O
R
FACTORY INSTALLED JUMPER.
1
2
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.
3
X2/BK
TO POWER SUPPLY PER LOCAL CODES
1
Y
BR(T)
W1
W2
RC
R
O
Y
G
B
VARIABLE SPEED
B/C
AIR HANDLER
INDOOR
OUTDOOR
B
(3 PH
ONLY)
16 SEER
HEAT PUMP
O.D. SECTION
(TWO STEP)
M24230
Fig. 11. Typical hookup of multistage two-step scroll heat pump with auxiliary/backup heat (3H/2C heat pump).
HEAT PUMP
Y2
F
X2
W1
S1
2
S2
T
1
RC
R
O
Y
G
B
NON-V.S. ONE OR TWO
R
R O BR(T)X2/BK
1
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A
2
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
G
Y
Y
W1
INDOOR
OUTDOOR
TO POWER SUPPLY PER LOCAL CODES
W2
(3 PH ONLY)
M24200
B/C
B
STAGE GAS FURNACE
HEAT PUMP
O.D. SECTION
(SINGLE STAGE)
Fig. 12. Typical hookup of singe-stage heat pump with non-variable speed gas furnace.
5 69-1790—3
Pub. No. 18-HD25D19-3
Page 6
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT PUMP
(3 PH
ONLY)
M24201
RC
R
O
Y
G
B
B
VARIABLE SPEED TWO STAGE FURNACE
HEAT PUMP
O.D. SECTION
(SINGLE STAGE)
Y2
F
X2
W1
S1
2
S2
T
1
O
R
BK
R O BR(T)BR/X2
1
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A
2
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 13. Typical hookup of single-stage heat pump with two stage variable speed gas furnace
G
Y
LO
Y
OR BK
(2H/1C heat pump).
1
W1 W2
YB/C
INDOOR
OUTDOOR
TO POWER SUPPLY PER LOCAL CODES
Pub. No. 18-HD25D19-3 69-1790—3 6
Page 7
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT PUMP
Y2
F
X2
W1
S1
2
S2
T
1
Y
1/
O
R
BK
Y2
R O BR(T)X2/BK
1
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A
2
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
G
Y1
Y/Y2 B/C
Y
LO
1
W1 W2
INDOOR
OUTDOOR
TO POWER SUPPLY PER LOCAL CODES
RC
R
O
Y
G
B
VARIABLE SPEED TWO STAGE FURNACE
F
(3 PH
ONLY)
M24202
HEAT PUMP
B
O.D. SECTION (TWO STAGE)
Fig. 14. Typical hookup of multistage heat pump with two stage variable speed gas furnace (3H/2C heat pump).
7 69-1790—3
Pub. No. 18-HD25D19-3
Page 8
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
HEAT PUMP
(3 PH
ONLY)
M24203
RC
R
O
Y
G
B
VARIABLE SPEED TWO STAGE FURNACE
B
16 SEER
HEAT PUMP
O.D. SECTION
(TWO STEP)
Y2
F
X2
W1
S1
2
S2
T
1
O
R
BK
3
Y2
R O BR(T)X2/BK
1
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A
2
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
3
REMOVE / CUT JUMPER FROM R TO BK.
Fig. 15. Typical hookup of multistage two-step scroll heat pump with two stage variable speed gas furnace
G
Y
LO
Y1
(3H/2C heat pump).
1
W1 W2
YB/C
INDOOR
OUTDOOR
TO POWER SUPPLY PER LOCAL CODES
Powering the Comfort Control
The Comfort Control can be powered with 24 Vac.
24 Vac Common Power (Recommended)
Wire the common side of the transformer to the B screw of the comfort control wallplate. When installing in a single transformer system, keep the jumper wire between the R and Rc screws. When installing in a two-transformer system, use the common from the cooling transformer to connect to the B screw and remove the jumper wire between the R and Rc screws.
Battery Power (Optional)
CAUTION
Equipment or Property Damage Hazard. Using battery power only may not provide adequate power to comfort control and can cause damage during freezing conditions.
Connect the 24 Vac Common (B) wire from the system transformer to the comfort control for proper operation when the battery power is drained.
Pub. No. 18-HD25D19-3 69-1790—3 8
Three AAA alkaline batteries can be used to power the comfort control for armchair programming only. To prevent the comfort control and heating/cooling system from shutting down due to lack of battery power, it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation. When using batteries, make sure positive and negative terminals are oriented correctly, as marked on the device. See Fig. 16.
BATTERIES (3)
M19918
Fig. 16. Installing batteries on comfort control back.
Page 9
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
E
MON
UE
THUSASUN
E
MON
THUSASUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
US
E
R
U
Mounting the Comfort Control
1. Align the terminal screw blocks with the pins on the back of the comfort control.
2. Push the comfort control straight onto the wallplate. See Fig. 17.
WALL
INSTALLATION
REMOVE DURING
M22643
Fig. 17. Mounting comfort control on wallplate.
Adjusting Real-Time Clock
Setting Calendar and Time
Locate and remove the tab labeled Remove in the lower left corner on the comfort control back. The tab must be removed to activate the real-time clock. See Fig. 18.
REMOVE TAB TO ACTIVATE REAL TIME CLOCK
INSTALLATION
REMOVE DURING
INSTALLATION
REMOVE DURING
M22644
Fig. 18. Removing tab to activate real-time clock.
This comfort control is designed to automatically keep the current time and day in memory for up to ten years under normal use once the calendar is set. When the comfort control is first powered, the display is ready for the calendar date to be entered. See Fig. 19.
SET CURRENT DAY SET MONTH
T
DON
E ARROWS TO SET YEAR AND TIM
DON
M22645
Fig. 19. Setting calendar and time after initial
IMPORTANT
The tab on the back of the comfort control in the lower left corner must be removed for this feature to be active.
powerup.
Using the Comfort Control
The comfort control has a touch screen interface. Words or symbols appear, highlighting the keys, as necessary, to complete tasks. Always press the keys with your fingertips. Sharp instruments like a pen or pencil point can damage the comfort control.
1. Use the arrow keys to set the Year, Month and Day, as shown in Fig. 19.
2. Press the Done key.
3. Use the arrow keys to set the current time. See
Fig. 19.
4. Press the Done key.
9 69-1790—3
Pub. No. 18-HD25D19-3
Page 10
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
OPERATION
78°F (25.5°C)
85°F (29.5°C)
78°F (25.5°C)
82°F (28°C)
TO C
M22646
SettingHeat Cool
Auto
Auto
Auto
Auto
System and Fan Settings
The System default setting is Heat and the Fan default setting is Auto.
SYSTEM SETTINGS
Heat: controls heating system. Off: heating and cooling are off. Cool: controls cooling system. Auto: automatically changes between heating and cooling systems, depending on indoor temperature. (See Installer Setup section.) Em Heat: emergency heat cycles to maintain temperature. Compressor is locked out. (Used only for heat pump systems with backup heat.)
FAN SETTINGS
The Fan setting can be programmed into the comfort control schedule for each period (Wake, Leave, Return, Sleep). See the Owners’ Guide for additional information.
LED Indication (Requires 24 Vac Common Connection)
An LED indicator is located in the upper right corner of the comfort control. It is only visible when lighted:
• It indicates when the comfort control is in the Emergency Heat mode. When in Em. Ht. mode, the F terminal is continuously energized and the LED is on.
• When the F terminal is wired to an equipment monitor, the LED signals when a check or fail signal is sent to the comfort control from the system. See Fig. 20. (This can occur only when the comfort control is not in Em. Ht. mode.)
C
EQUIPMENT
MONITOR
FTO R
Fig. 20. F terminal switch to R (power) side of system
Preprogrammed Settings
Table 3 shows the default program settings. See Owners’ Guide for complete instructions on changing the program.
transformer.
Table 3. Default Program Settings.
Schedule
Period Time
Wake 6:00AM 70°F
Leave 8:00AM 62°F
Return 6:00PM 70°F
Sleep 10:00PM 62°F
Setpoints
(21°C)
(16.5°C)
(21°C)
(16.5°C)
Fan
Pub. No. 18-HD25D19-3 69-1790—3 10
Page 11
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
E
MO
USASU
SYSTE
M
OFF
g
Schedule
de
Se
o
E
DONE
MON
THUSASUN
A
INSTALLER SETUP
The comfort control works with many different system types. To operate correctly, the comfort control must be set up to operate the installed heating and/or cooling system.
Follow these steps to enter the Installer Setup:
1. Be sure the comfort control is powered.
2. Press and release the System Key.
FAN
ON
AUTO
SYSTEM
EM HEAT
OFF
COOL
3. Press and hold the two blank keys on either side of the center blank key for approximately five seconds until screen changes.
THU
Inside
SCHED HOLD CLOCK SCREE
Insi
Set To
A M
T
t T
Following Schedule
Followin
M22647
4. Release the two blank keys when the screen on the comfort control matches the screen below.
DON
M22649
5. See screen below to review how the comfort control keys are used during Installer Setup. See Table 4 for the Installer Setup Numbers and Settings.
ADVANCE TO NEXT
INSTALLER SETUP NUMBER
INSTALLER SETUP
CURRENT SETTING
DON
CANC
M22648
PRESS TO EXIT INSTALLER SETUP
6. Press the Done key to exit the Installer Setup screen.
11 69-1790—3
CHANGE THE CURRENT SETTING
M22650
Pub. No. 18-HD25D19-3
Page 12
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
IMPORTANT
The Installer Setup Menu (Table 4) shows all the available options. These options customize themselves as you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are avail­able to change.
Table 4. Installer Setup Menu.
Factory Setting Other Choices
Installer
Select
Not used. 1 thru
Date (Year Upper)
Date (Year Lower)
Date (Month) 0140 6 Digit(s) represents
Date (Day)
Schedule Options
System Type Selection
Fan Operation 0180 0 Heat/Cool
Backup Heat Source (Auxiliary Heat)
External Fossil Fuel Kit
Cycles per hour (cph) for 1st Stage Compressor
Cycles per hour (cph) for 2nd Stage Compressor
Setup
Number
0099 0120 20 Set first two digits of
0130 05 Represents last two
0150 15 Digit(s) represents
—— —
current calendar year (20 for year 2005, etc)
digits of current calendar year (2005).
current calendar month.
current calendar date.
21 21 —first two digits of current
calendar year (21xx)
00 -99 Select last two digits of current
calendar year.
1-12 Select number that represents
current calendar month.
1-31 Select number that represents
current calendar date.
CommentsOption Description Options Description
2000 - 2178 available
2000 - 2178 available
0160 4 7-day programming 0 0—nonprogrammable
0170 1 1 Heat/1Cool 1-12 1—1heat/1cool
applications where equipment controls fan operation in heat
0200 0 Heat pump backup
0210 1 External fossil fuel kit
0220 3 Compressor Stage 1
0230 3 Compressor Stage 2
mode.
heat source is electric.
is controlling heat pump backup heat (recommended)
cycles per hour (cph)
cycles per hour (cph)
2—single-stage heat pump (no aux. heat)
3—heat only (no fan) 4—heat only (with fan) 5—hot water Series 20 (3-wire
or normally open zone valves)
6—cool only 7—2 heat/1cool heat pump 8—2 heat/2 cool 9—2 heat/1cool 10—1 heat/2 cool oil furnace
or 0H/2C 11—2 heat/2 cool heat pump (with no auxiliary heat) 12—3 heat/2 cool heat pump (with auxiliary heat)
1 Heat pump or electric heat
applications where comfort control controls fan operation in heat mode.
1 Heat pump backup heat
source is fossil fuel.
0 No external fossil fuel kit is
controlling heat pump backup heat. This comfort control controls the backup fossil fuel heat with outdoor sensor.
1-6 1-6 available;
3 is recommended.
1-6 1-6 available;
3 is recommended.
Available options and defaults vary by comfort control. System selection automatically modifies some default settings and/ or hides other Installer Setup options.
Only shown if heat/ cool system is selected. If heat pump is chosen, fan defaults to electric.
Only shown if 2 heat/ 1 cool or 3 heat/2 cool heat pump is chosen.
Only shown if fossil fuel is chosen as backup heat source.
Only shown if two stages of cool are selected.
Pub. No. 18-HD25D19-3 69-1790—3 12
Page 13
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Table 4. Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
Cycles per hour (cph) for 1st Stage Heat
Cycles per hour (cph) for 2nd Stage Heat
Cycles per hour (cph) for 3rd Stage Heat
Cycles per hour (cph) for Em Heat
Continuous Backlight
Setup
Number
0240 5 Heat Stage 1 cycles
0250 5 Cycles per hour (cph)
0260 9 Cycles per hour (cph)
0270 9 Cycles per hour (cph)
0280 0 Backlight not on
per hour (cph)
for 2nd Stage Heat or Auxiliary Heat for 2 H/1C Heat Pump Systems
for Auxiliary Heat in 3H/2C Heat Pump Systems
for Emergency Heat
continuously. Comfort control backlight comes on with each key press.
1-12 1-12 available; typical settings:
1—1 cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
1-12 1-12 available; typical settings:
1—1 cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
1-12 1-12 available; typical settings:
1—1cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
1-12 1-12 is available; typical
settings: 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
1 Backlight is on continuously
(comfort control must have a common wire attached for this function).
CommentsOption Description Options Description
Not shown if system selection is heat pump. Selection in this stage changes default cph for 2nd stage heat.
Only shown if two stages of heat are selected.
Only shown if 3H/2C heat pump system is selected.
Only shown if 2 heat/ 1 cool or 3 heat/2 cool heat pump is selected.
Option is always shown; however, continuously on backlight works only if comfort control is wired with 24 Vac Common.
Changeover 0300 0 Manual changeover 1 1—auto changeover
13 69-1790—3
Pub. No. 18-HD25D19-3
Page 14
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Table 4. Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
Deadband 0310 2 thru 9 Heating and cooling
Temperature Indication Scale
Daylight Savings
Remote Temperature Sensor (Outdoor or Indoor)
Heat Pump Compressor Lockout
Setup
Number
setpoints can be set no closer than chosen value:
2—2°F (1°C) 3—3°F (2°C) 4—4°F (2.5°C) 5—5°F (3°C) 6—6°F (3.5°C) 7—7°F (4°C) 8—8°F (4.5°C) 9—9°F (5°C)
0320 0 Temperature is
0330 1 Daylight savings
0340 0 No remote
0350 0 No compressor
displayed in °F.
enabled (use through 2006 and for areas that do not new 2007 DST calendar).
use the
temperature sensor
lockout.
3 Heating and cooling setpoints
can be set no closer than 3°F (1.5°C).
Shown only if automatic changeover is selected. The deadband is restricted to the range of 5 to 9 if ISU 0380 is set to dehumidification droop control.
1 Temperature is displayed in °C.
CommentsOption Description Options Description
0, 2 0—daylight savings is
disabled. 2—daylight savings is enabled (start using in 2007, for areas that use the new 2007 DST calendar).
1-3 1—outdoor temperature
sensor for display only. 2—outdoor temperature sensor for system control, used for select heat pump systems. (See Special Heat Pump Features section for more details.) 3—indoor temperature sensor
15, 20,
15°F (-9.5°C)
25, 30,
20°F (-6.5°C)
35, 40,
25°F (-4°C)
45
30°F (-1°C) 35°F (1.5°C) 40°F (4.5°C) 45°F (7°C)
Set to 0 in areas that do not follow daylight savings.
Defaults and Options depend on System Type selection. Indoor Temperature Sensor uses an averaging network and does not include on-board sensor.
Default depends on other selections. Shown if Outdoor Temperature for control is selected.
Heat Pump Auxiliary Lockout
Indoor Dehumidifica­tion Control
Furnace Filter Change Reminder
Humidifier Pad Replacement Reminder
Pub. No. 18-HD25D19-3 69-1790—3 14
0360 0 No heat pump
0380 0 No indoor
0500 0 Furnace filter change
0510 0 Humidifier pad
auxiliary lockout.
dehumidification control.
reminder off.
replacement reminder off.
40, 45, 50, 55, 60
1 1—dehumidification droop
1-6 1—10 run time days
1-3 1—90 calendar days
40°F (4.5°C) 45°F (7°C) 50°F (10°C) 55°F (13°C) 60°F (15.5°C
control.
2—30 run time days 3—60 run time days 4—90 run time days 5—120 run time days 6—365 run time days
2—180 calendar days 3—365 calendar days
Shown if electric is chosen for backup heat source and outdoor temperature sensor for control is selected.
Available on models with humidity sensor.
Run time based on call for fan.
Page 15
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Table 4. Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
Adaptive Intelligent Recovery™
Number of Periods
Minimum Compressor Off Time
Heat Temperature Range Stop
Cool Temperature Range Stop
Setup
Number
0530 1 Adaptive Intelligent
0540 4 Four periods available
0580 5 Five minute minimum
0600 90 Highest heating
0610 50 Lowest cooling
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
(Wake, Leave, Return, Sleep)
off time for compressor.
setpoint.
setpoint.
0 0—conventional recovery
(system starts recovery at programmed time)
2 Two periods available (Wake
and Sleep)
0, 2, 3, 4Minimum number of minutes
compressor is off between calls for compressor.
40 to 89 Temperature range (1°F
increments) of heating setpoint.
51 to 99 Temperature range (1°F
increments) of cooling setpoint.
CommentsOption Description Options Description
Not shown if non-programmable is selected. 2 or 4 applies to all days of the week.
Five minutes recommended
Shown in 1/2 °C.
Shown in 1/2 °C.
Clock Format 0640 12 12-hour clock format 24 24-hour clock format — Extended Fan
on time Heat
Extended Fan on time Cool
Keypad Lockout
0650 0 No extended fan
0660 0 No extended fan
operation after call for heat ends.
operation after call for cool ends.
0670 0 Unlocked keypad 1, 2 1—partially locked keypad
90 Fan operation is extended 90
seconds after call for heat ends.
90 Fan operation is extended 90
seconds after call for cool ends.
2—fully locked keypad
Not shown if fan operation is set to fossil fuel or in Cool Only Systems
Not shown in Heat Only Systems.
Unlocked—all functions are available. Partially locked—only temperature up and down keys and ability to enter and modify Installer Setup mode are available. Fully locked—only ability to enter and modify Installer Setup mode are available.
15 69-1790—3
Pub. No. 18-HD25D19-3
Page 16
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Table 4. Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
Temperature Control in Heat
Temperature Control in Cool
Temperature Display Offset
Reset Comfort Control
Setup
Number
0680 2 Standard temperature
0690 2 Standard temperature
0700 0 No difference in
0710 0 No comfort control
control in heating.
control in cooling.
displayed temperature and actual room temperature.
reset.
1, 3 1—less aggressive
temperature control (could cause temperature undershoot) 3—more aggressive temperature control (could cause temperature overshoot)
1, 3 1—less aggressive
temperature control (could cause temperature undershoot) 3—more aggressive temperature control (could cause temperature overshoot)
-3, -2,
-3°F (-1.5°C)
-1, 0, 1,
-2°F (-1°C)
2, 3
-1°F (-0.5°C) 0°F (0°C) 1°F (0.5°C) 2°F (1°C) 3°F (1.5°C)
1 Resets all Installer Setup
Options to default values and resets schedule to default setting.
CommentsOption Description Options Description
Applies to recovery ramp and use of auxiliary heat during recovery. Choose 1 if getting temperature overshoot. Choose 3 if getting temperature undershoot.
Applies to recovery ramp. Choose 1 if getting temperature overshoot. Choose 3 if getting temperature undershoot.
Only calendar settings and time are retained.
Pub. No. 18-HD25D19-3 69-1790—3 16
Page 17
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
SYSTEM CHECKOUT
Installer System Test
The Installer System Test mode is used to test the HVAC system(s). See Table 5. While in System Test mode, minimum off-time for compressors is bypassed.
The Installer Test is part of the Installer Setup options. Enter Installer Setup screen and press the Down arrow key to bring up test selection(s) quickly.
Table 5. System Test(s).
Select
Installer Tes t C o o l
Installer Tes t F a n
Installer Tes t H e a t
Installer Tes t E m Ht
Installer
Setup
Number
Test 1 0 Cool is off 1,2 0—cool off
Test 2 0 Fan is off 1 0—fan off
Test 3 0 Heat is off 1-3 0—heat off
Test 4 0 Emergency
Factory Setting Other Choices
heat is off
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling compressor quickly.
1—cool stage 1 turns on 2—cool stages 1 and 2 on
1—fan turns on
1—stage 1 heat on 2—stages 1 and 2 heat on 3—stages 1, 2 and 3 (Aux
Ht) on
1 0—emergency heat off
1—emergency heat on 2—emergency heat and
auxiliary heat turn on
CommentsOptions Description Options Description
System selection determines which tests are available and the number of stages shown.
Available only if heat pump with auxiliary heat is selected.
17 69-1790—3
Pub. No. 18-HD25D19-3
Page 18
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
ADVANCED FEATURES
Outdoor or Indoor Temperature Sensor
For accuracy, the initial reading of the indoor and outdoor temperature sensors require five minutes to stabilize. See the Sensor instructions for installation information.
Special Heat Pump Features
Heat Pump with Fossil Fuel Auxiliary Heat (Dual Fuel) and Outdoor Temperature Sensor
In this operation there is no external fossil fuel kit (dual fuel kit) installed; the comfort control controls this function.
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option as controlling backup heat in installer Setup Number
0210.
4. Outdoor Temperature Sensor for Control Option is automatically chosen in Installer Setup Number
0340.
5. Choose appropriate Balance Point Temperature in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected Balance Point Temperature (ISU 0350), only the compressor operates and the fan (G terminal) energizes when the comfort control calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected Balance Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary heat) operates and the fan (G terminal) does not energize when the comfort control calls for heat.
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the Emergency heat mode. When the comfort control is moved to the Emergency Heat position, the compressor is locked out. The first stage of heat is whatever is connected to the X2 terminal. The second stage of heat is what is connected to the W1 terminal. Often there is only one source of non-compressor heat and the X2 terminal is jumpered to the W1 terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Electric as Auxiliary (Backup) Heat Source in Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor for Control Option in Installer Setup Number 0340.
4. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer Setup Number 0360.
NOTE: There is a 5°F deadband between the Compres-
sor and Auxiliary Heat Lockout Temperatures
OPERATION IN HEAT MODE
When the outdoor temperature is below the Compressor Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout Temperature, only the Compressor operates. See Fig. 21.
COMPRESSOR ONLY
50
BOTH COMPRESSOR AND
AUXILIARY HEAT
35
OUTDOOR TEMPERATURE
When the outdoor temperature is between the two temperatures, both the Compressor and Auxiliary Heat operate.
AUXILIARY ONLY
Fig. 21. Heat Pump Operation with Lockout
Temperatures Set.
AUXILIARY LOCKOUT TEMPERATURE
COMPRESSOR LOCKOUT TEMPERATURE
M19950
OPERATION IN THE EMERGENCY HEAT MODE
Once the comfort control is placed into the Emergency Heat mode, the compressor and auxiliary lockout features are turned off. In the Emergency heat mode, the compressor is locked out. The first stage of heat is whatever is connected to the X2 terminal. The second stage of heat is connected to the W1 terminal. Usually the emergency and auxiliary heat sources are electric strip heat in these cases.
Dehumidification Droop Control
The dehumidification control attempts to control to the user's humidity setpoint by turning on the air conditioner. In extremely high humidity conditions, the comfort control keeps the air conditioner running for up to 3 temperature setpoint. It does this while trying to achieve the desired humidity setpoint and balancing that with the temperature setpoint.
°
F below the
Pub. No. 18-HD25D19-3 69-1790—3 18
Page 19
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
TROUBLESHOOTING (SEE TABLE 6)
Table 6. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Comfort control is not being
Temperature settings do not change.
Heating or cooling does not come on.
Comfort control is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running.
Comfort control does not respond when touch areas are pressed.
powered.
The upper or lower temperature limits were reached.
The keypad is fully locked. Check Installer Setup Number 0670 to
Comfort control minimum off­time is activated.
System selection is not set to Heat or Cool.
System type Selection is incorrect.
Heating or cooling equipment is not operating.
The keypad is locked. Check Installer Setup Number 0670 to
Check for 24 Vac between B and Rc.
Check temperature setpoints. Check Installer Setup Numbers 0600 and 0610; modify as needed.
change keypad locked options.
Wait up to five minutes for the system to respond.
Set system Selection to correct position.
Check Installer Setup Number 0170 and make sure correct System type is chosen.
Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode.
change keypad locked options.
19 69-1790—3
Pub. No. 18-HD25D19-3
Page 20
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
® U.S. Registered Trademark © 2006 American Standard Inc. All Rights Reserved
Pub. No. 18-HD25D19-3 69-1790—3 M.S. Rev. 01-06
American Standard Inc. Troup Highway Tyler, TX 75711-9010
Loading...