Trane TCONT803AS32DA, tcont802as32daa Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
69-1790-3
U.S. Pat. No. 6595430, D509151, and Other Patents Pending
TCONT802AS32DA Touch Screen and TCONT803AS32DA Touch Screen with Dehumidification Control Comfort Controls
18-HD25D19-3
The TCONT802AS32DA and TCONT803AS32DA Touch Screen Comfort Controls provide electronic control of 24 Vac heating and cooling systems. See Table 1 for a general description.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Installer must be a trained, experienced service technician.
3. After completing installation, use these instructions to check out the product operation.
Selecting Location
Install the comfort control about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Fig. 1. Selecting comfort control location.
Table 1. TCONT802AS32DA and TCONT803AS32DA Comfort Control Description.
Power Method Changeover System Selection Fan Selection Comments
24 Vac common wire
Automatic or manual selectable
Heat-Off-Cool­Auto (Em. Heat for heat pumps)
On-Auto-Circ System and Fan selection
vary based on system type
System and Fan selection vary based on System type. Humidity sensor to control dehumidification.
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M19925
Page 2
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 2
Do not install the comfort control where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall
behind the comfort control.
Installing Wallplate
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The comfort control can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Position and level the wallplate (for appearance only).
2. Use a pencil to mark the mounting holes.
Fig. 2. Mounting wallplate.
3. Remove the wallplate from the wall and, if drywall,
drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.
5. Insert mounting screws into the holes and tighten.
WIRING (FIG. 5-15)
All wiring must comply with local electrical codes and ordinances.
1. Select set of terminal identifications (Table 2) that corresponds with system type (heat/cool or heat pump in Fig. 3).
2. Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the comfort control.
Fig. 3. Selecting terminal identifications for
system type.
NOTE: The factory default setting is configured for a
1 Heat/1 Cool System with a gas furnace.
Fig. 4. Inserting wires in terminal block.
IMPORTANT
Use 18 gauge comfort control wire.
WALL
MOUNTING HOLES
M19916
MOUNTING SCREWS (2)
WALL ANCHORS (2)
WIRES THROUGH WALL AND WIRE SLOT
Table 2. Selecting Terminal Identifications for
System Type.
System Type
Wallplate
Termi nal
Identifications
Wiring
Diagram
Reference
Standard Heat/Cool Heat/Cool Fig. 5,
Fig. 6
Standard Multistage up to 2 Heat/2 Cool
Heat/Cool Fig. 7,
Fig. 8
Heat Pump with Electric Auxiliary (Backup) Heat
Heat Pump Fig. 9,
Fig. 10, Fig. 11
Heat Pump with Fossil Fuel Auxiliary (Dual Fuel) Heat
Heat Pump Fig. 12,
Fig. 13, Fig. 14, Fig. 15
HEAT
/COOL
SC
REW TERMINAL
S
HEAT PUM
P
M22636
Y2
F
X2
W1
S1
S2
W2
S1
S2
RC
R
O
Y
G
B
R
C
W1
Y
G
M19917
Page 3
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
3 69-1790—3
Fig. 5. Typical hookup of single-stage heat and cool
system with single transformer (1H/1C).
Fig. 6. Typical hookup of single-stage heat and cool
system with two transformers (1H/1C).
Fig. 7. Typical hookup of two-stage indoor and
two-stage cooling unit in a single transformer system
(2H/2C or 2H/1C or 1H/2C).
Fig. 8. Typical hookup of two-stage indoor and
two-step scroll cooling unit in a single transformer
system (2H/2C or 2H/1C or 1H/2C).
1
M22637
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
2
2
RC
S1
R
S2
W1
Y G B
HEAT/COOL
T
B/C
W3
W2
W1
GYR
AIR HANDLER
Y
B
COOLING UNIT O.D. SECTION (SINGLE STAGE)
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
INDOOR
OUTDOOR
ODT
Y2
W2
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
1
RC
S1
R
S2
W1
Y G B
HEAT/COOL
T
B/C
W
T
T
GYR
OIL FURNACE
Y
B
COOLING UNIT O.D. SECTION (SINGLE STAGE)
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
M22638
OIL BURNER PRIMARY
INDOOR
OUTDOOR
Y2
W2
1
M22640
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
2
2
RC
S1
R
S2
W1
Y G B
HEAT/COOL
T
B/C
G
Y
Y
LO
BKR
VARIABLE SPEED
TWO-STAGE
FURNACE/VARIABLE
SPEED AIR HANDLER
B
COOLING UNIT
O.D. SECTION (TWO STAGE)
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
INDOOR
OUTDOOR
W2
Y2
O
Y2
W1
Y1
W2
1
M24231
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.
1
2
2
RC
S1
R
S2
W1
Y G B
HEAT/COOL
T
B/C
G
Y
Y
LO
BK R
VARIABLE SPEED
TWO STAGE
FURNACE
B
16 SEER
COOLING UNIT
O.D. SECTION
(TWO STEP)
TO POWER SUPPLY PER LOCAL CODES
(3 PH
ONLY)
INDOOR
OUTDOOR
W2
Y2
O
Y2
W1
Y1
W2
3
3
Page 4
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 4
Fig. 9. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
Fig. 10. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).
PM-A
1
M22641
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
2
2
RC
S1
R
S2
O
Y G B
HEAT PUMP
T
T
B/C
W2
W1
GYR
AIR HANDLER
Y
B
HEAT PUMP O.D. SECTION (SINGLE STAGE)
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
INDOOR
OUTDOOR
W1
Y2
F
X2
O
R
O
W3
TO POWER
SUPPLY PER
LOCAL CODES AND AS DEFINED
IN FIELD
WIRING TABLE
SUPPL. HTR.
CONTROL BOX
I-PF
REQ.
FOR
3 PH
ODT-1
ODT-2
BR(T)X2/BK
PM-A
1
M22642
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
1
2
2
RC
S1
R
S2
O
Y G B
HEAT PUMP
T
T
B/C
W1
G
OYR
VARIABLE SPEED AIR HANDLER
B
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
INDOOR
OUTDOOR
W1
Y2
F
X2
YLO
R
X2/BK
ODT-1
ODT-2
F
BR(T)
W2
TO POWER
SUPPLY PER
LOCAL CODES AND AS DEFINED
IN FIELD
WIRING TABLE
SUPPL. HTR.
CONTROL BOX
I-PF
REQ.
FOR
3 PH
W3
Y2
O
HEAT PUMP
O.D. SECTION
(TWO STAGE)
BK
Y1
Page 5
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
5 69-1790—3
Fig. 11. Typical hookup of multistage two-step scroll heat pump with auxiliary/backup heat (3H/2C heat pump).
Fig. 12. Typical hookup of singe-stage heat pump with non-variable speed gas furnace.
1
M24230
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.
1
2
2
RC
S1
R
S2
O
Y G B
HEAT PUMP
T
B/C
G
Y
Y
LO
BK R
VARIABLE SPEED
AIR HANDLER
B
16 SEER
HEAT PUMP
O.D. SECTION
(TWO STEP)
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
INDOOR
OUTDOOR
W1
Y2
F
X2
O
Y2
W1
Y1
W2
R
O
BR(T)
X2/BK
3
3
W1
W2
G
Y
B/C
R
T
1
1
2
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Y
R O BR(T)X2/BK
B
HEAT PUMP
O.D. SECTION
(SINGLE STAGE)
2
NON-V.S. ONE OR TWO STAGE GAS FURNACE
INDOOR
OUTDOOR
HEAT PUMP
RC
R
O
Y
G
B
Y2
F
X2
W1
S1
S2
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
M24200
Page 6
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 6
Fig. 13. Typical hookup of single-stage heat pump with two stage variable speed gas furnace
(2H/1C heat pump).
W1 W2
G
YB/C
R
T
1
1
2
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Y
R O BR(T)BR/X2
OR BK
B
HEAT PUMP
O.D. SECTION
(SINGLE STAGE)
2
VARIABLE SPEED TWO STAGE FURNACE
INDOOR
OUTDOOR
HEAT PUMP
RC
R
O
Y
G
B
Y2
F
X2
W1
S1
S2
TO POWER SUPPLY PER LOCAL CODES
(3 PH ONLY)
M24201
1
BK
O
Y
LO
Page 7
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
7 69-1790—3
Fig. 14. Typical hookup of multistage heat pump with two stage variable speed gas furnace (3H/2C heat pump).
W1 W2
G
Y/Y2 B/C
R
T
1
1
2
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Y2
R O BR(T)X2/BK
B
F
HEAT PUMP O.D. SECTION (TWO STAGE)
Y1
2
VARIABLE SPEED TWO STAGE FURNACE
INDOOR
OUTDOOR
HEAT PUMP
RC
R
O
Y
G
B
Y2
F
X2
W1
S1
S2
TO POWER SUPPLY PER LOCAL CODES
(3 PH
ONLY)
M24202
1
BK
O
Y
LO
Y
1/
Page 8
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 8
Fig. 15. Typical hookup of multistage two-step scroll heat pump with two stage variable speed gas furnace
(3H/2C heat pump).
Powering the Comfort Control
The Comfort Control can be powered with 24 Vac.
24 Vac Common Power (Recommended)
Wire the common side of the transformer to the B screw of the comfort control wallplate. When installing in a single transformer system, keep the jumper wire between the R and Rc screws. When installing in a two-transformer system, use the common from the cooling transformer to connect to the B screw and remove the jumper wire between the R and Rc screws.
Battery Power (Optional)
CAUTION
Equipment or Property Damage Hazard. Using battery power only may not provide adequate power to comfort control and can cause damage during freezing conditions.
Connect the 24 Vac Common (B) wire from the system transformer to the comfort control for proper operation when the battery power is drained.
Three AAA alkaline batteries can be used to power the comfort control for armchair programming only. To prevent the comfort control and heating/cooling system from shutting down due to lack of battery power, it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation. When using batteries, make sure positive and negative terminals are oriented correctly, as marked on the device. See Fig. 16.
Fig. 16. Installing batteries on comfort control back.
W1 W2
G
YB/C
R
T
1
1
2
3
FACTORY INSTALLED JUMPER.
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Y2
R O BR(T)X2/BK
B
16 SEER
HEAT PUMP O.D. SECTION
(TWO STEP)
Y1
2
VARIABLE SPEED TWO STAGE FURNACE
INDOOR
OUTDOOR
HEAT PUMP
RC
R
O
Y
G
B
Y2
F
X2
W1
S1
S2
TO POWER SUPPLY PER LOCAL CODES
(3 PH
ONLY)
M24203
1
3
BK
O
Y
LO
REMOVE / CUT JUMPER FROM R TO BK.
M19918
BATTERIES (3)
Page 9
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
9 69-1790—3
Mounting the Comfort Control
1. Align the terminal screw blocks with the pins on the back of the comfort control.
2. Push the comfort control straight onto the wallplate. See Fig. 17.
Fig. 17. Mounting comfort control on wallplate.
Adjusting Real-Time Clock
Setting Calendar and Time
Locate and remove the tab labeled Remove in the lower left corner on the comfort control back. The tab must be removed to activate the real-time clock. See Fig. 18.
Fig. 18. Removing tab to activate real-time clock.
This comfort control is designed to automatically keep the current time and day in memory for up to ten years under normal use once the calendar is set. When the comfort control is first powered, the display is ready for the calendar date to be entered. See Fig. 19.
Fig. 19. Setting calendar and time after initial
powerup.
IMPORTANT
The tab on the back of the comfort control in the lower left corner must be removed for this feature to be active.
Using the Comfort Control
The comfort control has a touch screen interface. Words or symbols appear, highlighting the keys, as necessary, to complete tasks. Always press the keys with your fingertips. Sharp instruments like a pen or pencil point can damage the comfort control.
1. Use the arrow keys to set the Year, Month and Day, as shown in Fig. 19.
2. Press the Done key.
3. Use the arrow keys to set the current time. See
Fig. 19.
4. Press the Done key.
WALL
M22643
REMOVE DURING
INSTALLATION
REMOVE DURING
INSTALLATION
M22644
REMOVE TAB TO ACTIVATE REAL TIME CLOCK
REMOVE DURING
INSTALLATION
DON
E
MON
T
UE
THUSASUN
DON
E
MON
THUSASUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
SET CURRENT DAY SET MONTH
US
E ARROWS TO SET YEAR AND TIM
E
M22645
R
U
Page 10
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 10
OPERATION
System and Fan Settings
The System default setting is Heat and the Fan default setting is Auto.
SYSTEM SETTINGS
Heat: controls heating system. Off: heating and cooling are off. Cool: controls cooling system. Auto: automatically changes between heating and cooling systems, depending on indoor temperature. (See Installer Setup section.) Em Heat: emergency heat cycles to maintain temperature. Compressor is locked out. (Used only for heat pump systems with backup heat.)
FAN SETTINGS
The Fan setting can be programmed into the comfort control schedule for each period (Wake, Leave, Return, Sleep). See the Owners’ Guide for additional information.
LED Indication (Requires 24 Vac Common Connection)
An LED indicator is located in the upper right corner of the comfort control. It is only visible when lighted:
• It indicates when the comfort control is in the Emergency Heat mode. When in Em. Ht. mode, the F terminal is continuously energized and the LED is on.
• When the F terminal is wired to an equipment monitor, the LED signals when a check or fail signal is sent to the comfort control from the system. See Fig. 20. (This can occur only when the comfort control is not in Em. Ht. mode.)
Fig. 20. F terminal switch to R (power) side of system
transformer.
Preprogrammed Settings
Table 3 shows the default program settings. See Owners’ Guide for complete instructions on changing the program.
Table 3. Default Program Settings.
Schedule
Period Time
Setpoints
Fan
SettingHeat Cool
Wake 6:00AM 70°F
(21°C)
78°F (25.5°C)
Auto
Leave 8:00AM 62°F
(16.5°C)
85°F (29.5°C)
Auto
Return 6:00PM 70°F
(21°C)
78°F (25.5°C)
Auto
Sleep 10:00PM 62°F
(16.5°C)
82°F (28°C)
Auto
M22646
EQUIPMENT
MONITOR
FTO R
TO C
C
Page 11
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
11 69-1790—3
INSTALLER SETUP
The comfort control works with many different system types. To operate correctly, the comfort control must be set up to operate the installed heating and/or cooling system.
Follow these steps to enter the Installer Setup:
1. Be sure the comfort control is powered.
2. Press and release the System Key.
3. Press and hold the two blank keys on either side of
the center blank key for approximately five seconds until screen changes.
4. Release the two blank keys when the screen on the comfort control matches the screen below.
5. See screen below to review how the comfort control keys are used during Installer Setup. See Table 4 for the Installer Setup Numbers and Settings.
6. Press the Done key to exit the Installer Setup screen.
SCHED HOLD CLOCK SCREE
FAN
ON
AUTO
A M
THU
SYSTEM
EM HEAT
OFF
COOL
Following Schedule
Inside
Set To
M22647
DON
E
CANC
MO
T
USASU
SYSTE
M
OFF
Followin
g
Schedule
Insi
de
Se
t T
o
M22648
DON
E
M22649
DONE
MON
THUSASUN
INSTALLER SETUP NUMBER
CURRENT SETTING
ADVANCE TO NEXT INSTALLER SETUP
PRESS TO EXIT INSTALLER SETUP
CHANGE THE CURRENT SETTING
M22650
A
Page 12
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 12
IMPORTANT
The Installer Setup Menu (Table 4) shows all the available options. These options customize themselves as you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are avail­able to change.
Table 4. Installer Setup Menu.
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Not used. 1 thru
0099
—— —
Date (Year Upper)
0120 20 Set first two digits of
current calendar year (20 for year 2005, etc)
21 21 —first two digits of current
calendar year (21xx)
2000 - 2178 available
Date (Year Lower)
0130 05 Represents last two
digits of current calendar year (2005).
00 -99 Select last two digits of current
calendar year.
2000 - 2178 available
Date (Month) 0140 6 Digit(s) represents
current calendar month.
1-12 Select number that represents
current calendar month.
Date (Day)
0150 15 Digit(s) represents
current calendar date.
1-31 Select number that represents
current calendar date.
Schedule Options
0160 4 7-day programming 0 0—nonprogrammable
System Type Selection
0170 1 1 Heat/1Cool 1-12 1—1heat/1cool
2—single-stage heat pump (no aux. heat)
3—heat only (no fan) 4—heat only (with fan) 5—hot water Series 20 (3-wire
or normally open zone valves)
6—cool only 7—2 heat/1cool heat pump 8—2 heat/2 cool 9—2 heat/1cool 10—1 heat/2 cool oil furnace
or 0H/2C 11—2 heat/2 cool heat pump (with no auxiliary heat) 12—3 heat/2 cool heat pump (with auxiliary heat)
Available options and defaults vary by comfort control. System selection automatically modifies some default settings and/ or hides other Installer Setup options.
Fan Operation 0180 0 Heat/Cool
applications where equipment controls fan operation in heat mode.
1 Heat pump or electric heat
applications where comfort control controls fan operation in heat mode.
Only shown if heat/ cool system is selected. If heat pump is chosen, fan defaults to electric.
Backup Heat Source (Auxiliary Heat)
0200 0 Heat pump backup
heat source is electric.
1 Heat pump backup heat
source is fossil fuel.
Only shown if 2 heat/ 1 cool or 3 heat/2 cool heat pump is chosen.
External Fossil Fuel Kit
0210 1 External fossil fuel kit
is controlling heat pump backup heat (recommended)
0 No external fossil fuel kit is
controlling heat pump backup heat. This comfort control controls the backup fossil fuel heat with outdoor sensor.
Only shown if fossil fuel is chosen as backup heat source.
Cycles per hour (cph) for 1st Stage Compressor
0220 3 Compressor Stage 1
cycles per hour (cph)
1-6 1-6 available;
3 is recommended.
Cycles per hour (cph) for 2nd Stage Compressor
0230 3 Compressor Stage 2
cycles per hour (cph)
1-6 1-6 available;
3 is recommended.
Only shown if two stages of cool are selected.
Page 13
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
13 69-1790—3
Cycles per hour (cph) for 1st Stage Heat
0240 5 Heat Stage 1 cycles
per hour (cph)
1-12 1-12 available; typical settings:
1—1 cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
Not shown if system selection is heat pump. Selection in this stage changes default cph for 2nd stage heat.
Cycles per hour (cph) for 2nd Stage Heat
0250 5 Cycles per hour (cph)
for 2nd Stage Heat or Auxiliary Heat for 2 H/1C Heat Pump Systems
1-12 1-12 available; typical settings:
1—1 cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
Only shown if two stages of heat are selected.
Cycles per hour (cph) for 3rd Stage Heat
0260 9 Cycles per hour (cph)
for Auxiliary Heat in 3H/2C Heat Pump Systems
1-12 1-12 available; typical settings:
1—1cph used for steam or gravity system. 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
Only shown if 3H/2C heat pump system is selected.
Cycles per hour (cph) for Em Heat
0270 9 Cycles per hour (cph)
for Emergency Heat
1-12 1-12 is available; typical
settings: 3—3 cph used for 2-stage fossil fuel forced air systems or hot water systems. 5—5 cph used for single-stage fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
Only shown if 2 heat/ 1 cool or 3 heat/2 cool heat pump is selected.
Continuous Backlight
0280 0 Backlight not on
continuously. Comfort control backlight comes on with each key press.
1 Backlight is on continuously
(comfort control must have a common wire attached for this function).
Option is always shown; however, continuously on backlight works only if comfort control is wired with 24 Vac Common.
Changeover 0300 0 Manual changeover 1 1—auto changeover
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Page 14
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 14
Deadband 0310 2 thru 9 Heating and cooling
setpoints can be set no closer than chosen value:
2—2°F (1°C) 3—3°F (2°C) 4—4°F (2.5°C) 5—5°F (3°C) 6—6°F (3.5°C) 7—7°F (4°C) 8—8°F (4.5°C) 9—9°F (5°C)
3 Heating and cooling setpoints
can be set no closer than 3°F (1.5°C).
Shown only if automatic changeover is selected. The deadband is restricted to the range of 5 to 9 if ISU 0380 is set to dehumidification droop control.
Temperature Indication Scale
0320 0 Temperature is
displayed in °F.
1 Temperature is displayed in °C.
Daylight Savings
0330 1 Daylight savings
enabled (use through 2006 and for areas that do not
use the new 2007 DST calendar).
0, 2 0—daylight savings is
disabled. 2—daylight savings is enabled (start using in 2007, for areas that use the new 2007 DST calendar).
Set to 0 in areas that do not follow daylight savings.
Remote Temperature Sensor (Outdoor or Indoor)
0340 0 No remote
temperature sensor
1-3 1—outdoor temperature
sensor for display only. 2—outdoor temperature sensor for system control, used for select heat pump systems. (See Special Heat Pump Features section for more details.) 3—indoor temperature sensor
Defaults and Options depend on System Type selection. Indoor Temperature Sensor uses an averaging network and does not include on-board sensor.
Heat Pump Compressor Lockout
0350 0 No compressor
lockout.
15, 20, 25, 30, 35, 40, 45
15°F (-9.5°C) 20°F (-6.5°C) 25°F (-4°C) 30°F (-1°C) 35°F (1.5°C) 40°F (4.5°C) 45°F (7°C)
Default depends on other selections. Shown if Outdoor Temperature for control is selected.
Heat Pump Auxiliary Lockout
0360 0 No heat pump
auxiliary lockout.
40, 45, 50, 55, 60
40°F (4.5°C) 45°F (7°C) 50°F (10°C) 55°F (13°C) 60°F (15.5°C
Shown if electric is chosen for backup heat source and outdoor temperature sensor for control is selected.
Indoor Dehumidifica­tion Control
0380 0 No indoor
dehumidification control.
1 1—dehumidification droop
control.
Available on models with humidity sensor.
Furnace Filter Change Reminder
0500 0 Furnace filter change
reminder off.
1-6 1—10 run time days
2—30 run time days 3—60 run time days 4—90 run time days 5—120 run time days 6—365 run time days
Run time based on call for fan.
Humidifier Pad Replacement Reminder
0510 0 Humidifier pad
replacement reminder off.
1-3 1—90 calendar days
2—180 calendar days 3—365 calendar days
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Page 15
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
15 69-1790—3
Adaptive Intelligent Recovery™
0530 1 Adaptive Intelligent
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
0 0—conventional recovery
(system starts recovery at programmed time)
Number of Periods
0540 4 Four periods available
(Wake, Leave, Return, Sleep)
2 Two periods available (Wake
and Sleep)
Not shown if non-programmable is selected. 2 or 4 applies to all days of the week.
Minimum Compressor Off Time
0580 5 Five minute minimum
off time for compressor.
0, 2, 3, 4Minimum number of minutes
compressor is off between calls for compressor.
Five minutes recommended
Heat Temperature Range Stop
0600 90 Highest heating
setpoint.
40 to 89 Temperature range (1°F
increments) of heating setpoint.
Shown in 1/2 °C.
Cool Temperature Range Stop
0610 50 Lowest cooling
setpoint.
51 to 99 Temperature range (1°F
increments) of cooling setpoint.
Shown in 1/2 °C.
Clock Format 0640 12 12-hour clock format 24 24-hour clock format — Extended Fan
on time Heat
0650 0 No extended fan
operation after call for heat ends.
90 Fan operation is extended 90
seconds after call for heat ends.
Not shown if fan operation is set to fossil fuel or in Cool Only Systems
Extended Fan on time Cool
0660 0 No extended fan
operation after call for cool ends.
90 Fan operation is extended 90
seconds after call for cool ends.
Not shown in Heat Only Systems.
Keypad Lockout
0670 0 Unlocked keypad 1, 2 1—partially locked keypad
2—fully locked keypad
Unlocked—all functions are available. Partially locked—only temperature up and down keys and ability to enter and modify Installer Setup mode are available. Fully locked—only ability to enter and modify Installer Setup mode are available.
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Page 16
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 16
Temperature Control in Heat
0680 2 Standard temperature
control in heating.
1, 3 1—less aggressive
temperature control (could cause temperature undershoot) 3—more aggressive temperature control (could cause temperature overshoot)
Applies to recovery ramp and use of auxiliary heat during recovery. Choose 1 if getting temperature overshoot. Choose 3 if getting temperature undershoot.
Temperature Control in Cool
0690 2 Standard temperature
control in cooling.
1, 3 1—less aggressive
temperature control (could cause temperature undershoot) 3—more aggressive temperature control (could cause temperature overshoot)
Applies to recovery ramp. Choose 1 if getting temperature overshoot. Choose 3 if getting temperature undershoot.
Temperature Display Offset
0700 0 No difference in
displayed temperature and actual room temperature.
-3, -2,
-1, 0, 1, 2, 3
-3°F (-1.5°C)
-2°F (-1°C)
-1°F (-0.5°C) 0°F (0°C) 1°F (0.5°C) 2°F (1°C) 3°F (1.5°C)
Reset Comfort Control
0710 0 No comfort control
reset.
1 Resets all Installer Setup
Options to default values and resets schedule to default setting.
Only calendar settings and time are retained.
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Page 17
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
17 69-1790—3
SYSTEM CHECKOUT
Installer System Test
The Installer System Test mode is used to test the HVAC system(s). See Table 5. While in System Test mode, minimum off-time for compressors is bypassed.
The Installer Test is part of the Installer Setup options. Enter Installer Setup screen and press the Down arrow key to bring up test selection(s) quickly.
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling compressor quickly.
Table 5. System Test(s).
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOptions Description Options Description
Installer Tes t Co o l
Test 1 0 Cool is off 1,2 0—cool off
1—cool stage 1 turns on 2—cool stages 1 and 2 on
System selection determines which tests are available and the number of stages shown.
Installer Tes t Fa n
Test 2 0 Fan is off 1 0—fan off
1—fan turns on
Installer Tes t He a t
Test 3 0 Heat is off 1-3 0—heat off
1—stage 1 heat on 2—stages 1 and 2 heat on 3—stages 1, 2 and 3 (Aux
Ht) on
Installer Tes t Em Ht
Test 4 0 Emergency
heat is off
1 0—emergency heat off
1—emergency heat on 2—emergency heat and
auxiliary heat turn on
Available only if heat pump with auxiliary heat is selected.
Page 18
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 18
ADVANCED FEATURES
Outdoor or Indoor Temperature Sensor
For accuracy, the initial reading of the indoor and outdoor temperature sensors require five minutes to stabilize. See the Sensor instructions for installation information.
Special Heat Pump Features
Heat Pump with Fossil Fuel Auxiliary Heat (Dual Fuel) and Outdoor Temperature Sensor
In this operation there is no external fossil fuel kit (dual fuel kit) installed; the comfort control controls this function.
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option as controlling backup heat in installer Setup Number
0210.
4. Outdoor Temperature Sensor for Control Option is automatically chosen in Installer Setup Number
0340.
5. Choose appropriate Balance Point Temperature in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected Balance Point Temperature (ISU 0350), only the compressor operates and the fan (G terminal) energizes when the comfort control calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected Balance Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary heat) operates and the fan (G terminal) does not energize when the comfort control calls for heat.
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the Emergency heat mode. When the comfort control is moved to the Emergency Heat position, the compressor is locked out. The first stage of heat is whatever is connected to the X2 terminal. The second stage of heat is what is connected to the W1 terminal. Often there is only one source of non-compressor heat and the X2 terminal is jumpered to the W1 terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Electric as Auxiliary (Backup) Heat Source in Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor for Control Option in Installer Setup Number 0340.
4. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer Setup Number 0360.
NOTE: There is a 5°F deadband between the Compres-
sor and Auxiliary Heat Lockout Temperatures
OPERATION IN HEAT MODE
When the outdoor temperature is below the Compressor Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout Temperature, only the Compressor operates. See Fig. 21.
Fig. 21. Heat Pump Operation with Lockout
Temperatures Set.
When the outdoor temperature is between the two temperatures, both the Compressor and Auxiliary Heat operate.
OPERATION IN THE EMERGENCY HEAT MODE
Once the comfort control is placed into the Emergency Heat mode, the compressor and auxiliary lockout features are turned off. In the Emergency heat mode, the compressor is locked out. The first stage of heat is whatever is connected to the X2 terminal. The second stage of heat is connected to the W1 terminal. Usually the emergency and auxiliary heat sources are electric strip heat in these cases.
Dehumidification Droop Control
The dehumidification control attempts to control to the user's humidity setpoint by turning on the air conditioner. In extremely high humidity conditions, the comfort control keeps the air conditioner running for up to 3
°
F below the temperature setpoint. It does this while trying to achieve the desired humidity setpoint and balancing that with the temperature setpoint.
35
M19950
COMPRESSOR LOCKOUT TEMPERATURE
AUXILIARY LOCKOUT TEMPERATURE
COMPRESSOR ONLY
BOTH COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
50
OUTDOOR TEMPERATURE
Page 19
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
19 69-1790—3
TROUBLESHOOTING (SEE TABLE 6)
Table 6. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Comfort control is not being
powered.
Check for 24 Vac between B and Rc.
Temperature settings do not change.
The upper or lower temperature limits were reached.
Check temperature setpoints. Check Installer Setup Numbers 0600 and 0610; modify as needed.
The keypad is fully locked. Check Installer Setup Number 0670 to
change keypad locked options.
Heating or cooling does not come on.
Comfort control minimum off­time is activated.
Wait up to five minutes for the system to respond.
System selection is not set to Heat or Cool.
Set system Selection to correct position.
System type Selection is incorrect.
Check Installer Setup Number 0170 and make sure correct System type is chosen.
Comfort control is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running.
Heating or cooling equipment is not operating.
Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode.
Comfort control does not respond when touch areas are pressed.
The keypad is locked. Check Installer Setup Number 0670 to
change keypad locked options.
Page 20
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3 69-1790—3 M.S. Rev. 01-06
® U.S. Registered Trademark © 2006 American Standard Inc. All Rights Reserved
American Standard Inc. Troup Highway Tyler, TX 75711-9010
Loading...