Trane TCD330B, TCD480B, TCD360B, TCD420B, TCD600B Installation & Operation Manual

...
Installation, Operation, Maintenance
Voyager™ Commercial
27.5 to 50 Ton 60 Hz
Model Numbers
“B” and later design sequence TC*, TE*, YC*330B, 360B, 420B, 480B, 600B (60 Hz/3 phase) TC*, TE*, YC*275B, 305B, 350B, 400B, 500B (50 Hz/3 phase)
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
November 2010 RT-SVX34C-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Literature Change History
RT-SVN34B-EN (April 2010)
Updated issue of manual: provides specific installation, operation and maintenance instructions for B and later design sequence on units with R-410A refrigerant.
RT-SVN34B-EN (January 2010)
Updated issue of manual: provides specific installation, operation and maintenance instructions for B and later design sequence on units with R-410A refrigerant.
RT-SVN34A-EN (March 2009)
Original issue of manual: provides specific installation, operation and maintenance instructions for A and later design sequence on units with R-410A refrigerant.
© 2010 Trane All rights reserved RT-SVX34C-EN
Overview of Manual
One copy of the appropriate service literature ships inside the control panel of each unit. The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians.
Note: Do not release refrigerant to the atmosphere! If adding or removing refrigerant is required,
the service technician must comply with all federal, state, and local laws.
This booklet describes the proper installation, startup, operation, and maintenance procedures for TC_, TE_, and YC_22.9 to 50 Ton CV (Constant Volume) and VAV (Variable Air Volume) applications. Refer to the table of contents for a listing specific topics. Refer to the "System Troubleshooting" section at the end of this manual for troubleshooting information.
By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Warnings, Cautions and Notices
60 Hz units with standard options are certified by Underwriters Laboratory.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNIN G
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow codes could result in death or serious injury.
RT-SVX34C-EN 3
Table of Contents
Literature Change History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
60 Hz Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
50 Hz Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Commonly Used Acronyms/Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Gas Heat Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
About the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Precautionary Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
First Aid Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Downflow Models Only: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
All Units: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Field Installed Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Unit Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Roof Curb and Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Horizontal Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Rigging and Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installation General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
O/A Sensor & Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Units with Statitrac™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Disconnect Switch External Handle (Factory Mounted Option) . . . . . . . . . . 29
Main Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Thru-the-Base Electrical (Optional Accessory) . . . . . . . . . . . . . . . . . . . . . 30
Electrical Wire Sizing and Protection Device Equations . . . . . . . . . . . . . . . . 35
Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Control Power Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Field Installed AC Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Field Installed DC Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Remote Panels and Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 RT-SVX34C-EN
Constant Volume Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Variable Air Volume Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Installation Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Connecting the Gas Supply Line to the Furnace Gas Train . . . . . . . . . . . 51
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Unit Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Microelectronic Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Variable Air Volume Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Constant Volume or Variable Air Volume Applications . . . . . . . . . . . . . . 63
Preparing the Unit for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Electrical Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Voltage Supply and Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Test Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Verifying Proper Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Verifying Proper Air Flow (CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Exhaust Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Economizer Damper Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Economizer (O/A) Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Manual Fresh Air Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Starting the Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Starting 27.5 to 35 Ton Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Starting 40 to 50 Ton Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Scroll Compressor Operational Noises . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Compressor Crankcase Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Charging by Subcooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Measuring Subcooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Gas Heat Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Electric Heat Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Final Unit Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
For Constant Volume Units; . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
For Variable Air Volume Units; . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Mechanical Cooling Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 112
Dehumidification (Modulating Hot Gas Reheat) Sequence of Operation . 112
RT-SVX34C-EN 5
Units without an Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Economizer operation based on Dry Bulb . . . . . . . . . . . . . . . . . . . . . . . . 113
Economizer operation based on Reference Enthalpy . . . . . . . . . . . . . . 114
Economizer Operation based on Comparative Enthalpy . . . . . . . . . . . . 114
Gas Heat Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Electric Heat Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Low Pressure Control (LPC) Sequence of Operation (ReliaTel Control) . . 117
High Pressure Control and Temperature Discharge Limit (ReliaTel Control)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Fan Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Cooling Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Heating Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Fall Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Refrigerant Evacuation and Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Compressor Replacements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Electrical Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Precision Suction Restrictor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
System Status/Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Terminal locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Diagnostics (CV units only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Diagnostics (VAV only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Resetting Cooling and Ignition Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . 131
Zone Temperature Sensor (ZSM) Service Indicator . . . . . . . . . . . . . . . . 132
RTRM Zone Sensor Module (ZSM) Test . . . . . . . . . . . . . . . . . . . . . . . . . 132
Test 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Test 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Test 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Test 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Programmable & Digital Zone Sensor Test . . . . . . . . . . . . . . . . . . . . . . 134
ReliaTel Refrigeration Module (RTRM) . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Test 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Test 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
ReliaTel Air Module (RTAM) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Test 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Test 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Test 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Test 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Test 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Compressor—Blink Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
6 RT-SVX34C-EN
TR-1 and TR-200 VFD Programming Parameters . . . . . . . . . . . . . . . . . . 146
Unit Wiring Diagram Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Warranty and Liability Clause . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
COMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATED ACCESSORIES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
RT-SVX34C-EN 7
Model Number Descriptions
60 Hz Description
Digit 1, 2 — Unit Function
TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat
Digit 3 — Unit Airflow Design
D = Downflow Configuration H = Horizontal Configuration
Digit 4, 5, 6 — Nominal Cooling Capacity
330 = 27½ Tons 360 = 30 Tons 420 = 35 Tons 480 = 40 Tons 600 = 50 Tons
Digit 7 — Major Development Sequence
B = R-410A Refrigerant
Digit 8 — Power Supply1
E = 208/60/3 F = 230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 9 — Heating Capacity4
0 = No Heat (TC only) L = Low Heat (YC only) H = High Heat (YC only) J = Low Heat-Stainless Steel Gas
Heat Exchanger (YC only)
K = High Heat-Stainless Steel Gas
Heat Exchangers (YC only)
M = Low Heat-Stainless Steel Gas
Heat Exchanger w/ Modulating control (27.5-35 ton YC only)
P = High Heat-Stainless Steel Gas
Heat Exchangers w/ Modulating control (27.5-35 ton YC only)
R = Low Heat-Stainless Steel Gas
Heat Exchanger w/ Modulating control (40-50 ton YC only)
T = High Heat-Stainless Steel Gas
Heat Exchangers w/ Modulating control (40-50 ton YC only)
Note: When second digit is “E” for
Electric Heat, the following values apply in the ninth digit.
A = 36 kW (27 kW for 208v) B = 54 kW (41 kW for 208v) C = 72 kW D = 90 kW E = 108 kW
Digit 10 — Design Sequence
A = First
Digit 11 — Exhaust
0= None 1 = Barometric Relief (Available
w/ Economizer only)
2 = 100% Power Exhaust Fan
(Available w/ Economizer only)
3 = 50% Power Exhaust Fan
(Available w/ Economizer only)
4 = 100% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
5 = 50% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
6 = 100% Power Exhaust w/
Statitrac™
6
Digit 12 — Filter
A = 2” Std Eff, Throwaway Filters B = 2” MERV 8, High Eff, Throwaway
C = 4” MERV 8, High Eff, Throwaway
D = 4” MERV 14, High Eff, Throwaway
Filters
Filters
Filters
Digit 13 — Supply Fan Motor, HP
1= 7.5 Hp 2=10 Hp 3= 15 Hp 4 = 20 Hp
Digit 14 — Supply Air Fan Drive
3
Selections
A = 550 RPM H = 500 RPM B = 600 RPM J = 525 RPM C = 650 RPM K = 575 RPM D = 700 RPM L = 625 RPM E = 750 RPM M = 675 RPM F = 790 RPM N = 725 RPM G = 800 RPM
Digit 15 — Fresh Air Selection
A= No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb
D = 0-100% Economizer,
E = 0-100% Economizer,
F = “C” Option and Low Leak
G = “D” Option and Low Leak
H = “E” Option and Low Leak
Control
Reference Enthalpy Control
Differential Enthalpy Control
FreshAir Damper
Fresh Air Damper
Fresh Air Damper
Digit 16 — System Control
1 = Constant Volume 2 = VAV Supply Air Temperature
3 = VAV Supply Air Temperature
4 = VAV Supply Air Temperature
Control w/o Inlet Guide Vanes
Control w/Inlet Guide Vanes
Control w/Variable Frequency
5 = VAV Supply Air Temperature
Note: Zone sensors are not included
Drive w/o Bypass
Control w/Variable Frequency Drive and Bypass
with option and must be ordered as a separate accessory.
Miscellaneous Options
Digit 17
A = Service Valves
2
Digit 18
B = Through the Base Electrical
Provision
Digit 19
C = Non-Fused Disconnect Switch
with External Handle
Digit 20
D= Factory-Powered 15A GFI
Convenience Outlet and Non-Fused Disconnect Switch with External Handle
Digit 21
E = Field-Powered 15A GFI
Convenience Outlet
Digit 22
F = Trane Communication
Interface (TCI)
Digit 23
G = Ventilation Override
Digit 24
H = Hinged Service Access
Digit 25
H = Tool-less Condenser Hail Guards J = Condenser Coil Guards
Digit 26
K = LCI (LonTalk) B = BACnet Communications
Interface (BCI)
Digit 27
* = Unused Digit
Digit 28
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency
N = Standard Efficiency
Condenser Coil
Condenser Coil with Black Epoxy Pre-Coating
Digit 30-31 — Miscellaneous Options
8 RT-SVX34C-EN
Model Number Descriptions
P = Discharge Temperature
Sensor
R = Clogged Filter Switch
Digit 32 — Dehumidification Option
T = Modulating Hot Gas Reheat
Model Number Notes
1. All voltages are across the line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50 ton units only.
4. Electric Heat KW ratings are based upon voltage ratings of 208/240/480/ 600 V. For a 240 V heater derated to 208 V, the resulting kW rating decreases from 36 kW to 27 kW, and from 54 kW to 41 kW. Voltage offerings are as follows: (see Tabl e 19,
p. 47 for additional information):
Electric
Heater
Rated
Tons
VoltageKW27/36 41/54 72 90 108
208 x x
27½
to 35
240 x x
480 x x x x
600 x x x
208 x
40
240 x
and
480 x x x x
50
600 x x x x
5. The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6. Ventilation override exhaust mode is not available for the exhaust fan with fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
RT-SVX34C-EN 9
Model Number Descriptions
50 Hz Description
Digits 1, 2 – Unit Function
TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat
Digit 3 – Unit Airflow Design
D = Downflow Configuration H = Horizontal Configuration
Digits 4, 5, 6 – Nominal Cooling
D = 4” (102 MM) MERV 14, High Eff,
Digit 13 – Supply Fan Motor, HP
1 = 7.5 Hp (5.6 kW) 2 = 10 Hp (7.5 kW) 3=15 Hp (10 kW) 4 = 20 Hp (15 kW)
Digit 14 – Supply Air Fan Drive Selections
Capacity
275 = 22.9 Tons (82 kW) 305 = 25.4 Tons (89 kW) 350 = 29.2 Tons (105 kW) 400 = 33.3 Tons (120 kW) 500 = 41.7 Tons (148 kW)
Digit 7 – Major Development Sequence
B = R-410A Refrigerant
Digit 8 – Power Supply1
C = 380/50/3 D = 415/50/3
Digit 9 – Heating Capacity4
0 = No Heat (TC only) L = Low Heat (YC only) H = High Heat (YC only)
Note: When second digit is “E” for
Electric Heat, the following values apply in the ninth digit.
380V / 415V
A = 23 kW / 27 kW B = 34 kW / 40 kW C = 45 kW / 54 kW D = 56 kW / 67 kW E = 68 kW / 81 kW
Digit 10 – Design Sequence
A= First
Digit 11 – Exhaust6
0= None 1 = Barometric Relief (Available
w/ Economizer only)
2 = 100% Power Exhaust Fan
(Available w/ Economizer only)
3 = 50% Power Exhaust Fan
(Available w/ Economizer only)
4 = 100% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
5 = 50% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
6 = 100% Power Exhaust w/
Statitrac™
Digit 12 – Filter
A = 2” (51 MM) Std Eff, Throwaway
Filters
B = 2” (51 MM) MERV 8, High Eff,
Throwaway Filters
C = 4” (102 MM) MERV 8, High Eff,
10 RT-SVX34C-EN
Digit 15 – Fresh Air Selection
A= No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb
D = 0-100% Economizer,
E = 0-100% Economizer,
F = “C” Option and Low Leak
G = “D” Option and Low Leak
H = “E” Option and Low Leak
Digit 16 – System Control
1 = Constant Volume 2 = VAV Supply Air Temperature
3 = VAV Supply Air Temperature
Note: Zone sensors are not included
Miscellaneous Options
Digit 17
A = Service Valves
Digit 18
B = Through the Base Electrical
Digit 19
C = Non-Fused Disconnect Switch
Digit 20
D = Factory-Powered 15A GFI
Digit 21
E=Field-Powered 15A GFI
Digit 22
Throwaway Filters
Throwaway Filters
3
A = 458 RPM H = 417 RPM B = 500 RPM J = 437 RPM C = 541 RPM K = 479 RPM D = 583 RPM L = 521 RPM E = 625 RPM M = 562 RPM F = 658 RPM N = 604 RPM G = 664 RPM
Control
Reference Enthalpy Control
Differential Enthalpy Control
Fresh Air Damper
Fresh Air Damper
Fresh Air Damper
Control w/o Inlet Guide Vanes
Control w/Inlet Guide Vanes
with option and must be ordered as a separate accessory.
2
Provision
with External Handle
Convenience Outlet and Non-Fused Disconnect Switch with External Handle
Convenience Outlet
F = Trane Communication
Interface (TCI)
Digit 23
G = Ventilation Override
Digit 24
H = Hinged Service Access
Digit 25
H = Tool-less Condenser Hail Guards J = Condenser Coil Guards
Digit 26
K = LCI (LonTalk) B = BACnet Communications
Interface (BCI)
Digit 27
* = Unused Digit
Digit 28
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency
Condenser Coil
N = Standard Efficiency
Condenser Coil with Black Epoxy Pre-Coating
Digit 30-31 — Miscellaneous Options
P = Discharge Temperature
Sensor
R = Clogged Filter Switch
Digit 32 — Dehumidification Option
T = Modulating Hot Gas Reheat
Model Number Notes
1. All voltages are across-the-line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 22.9-29.2 ton (82-105 kW) units only and drives H thru N are used with 33.3 and 41.7 ton (120-148 kW) units only.
4. Electric Heat kW ratings are based upon voltage ratings of 380/415 V. Heaters A, B, C, D are used with 22.9-
29.2 ton (82-105 kW) units only and heaters B, C, D, E are used with 33.3-
41.7 ton (120-148 kW) units only.
5. The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6. Ventilation override exhaust mode is not available for the exhaust fan with fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
General Information
Commonly Used Acronyms/Abbreviations
BAS = Building Automation System
CFM = Cubic Feet per Minute
CLV = Cooling Valve (Reheat only)
COMM = Module Designation for TCI/LCI
CV = Constant Volume
CW = Clockwise
CCW = Counterclockwise
DSP = Direct Space Pressure control
DTS = Discharge Air Sensor
DWU = Daytime Warm-up
E/A = Exhaust Air
ECA = Economizer Actuator
EET = Entering Evaporator Temperature Sensor
F/A = Fresh Air
FFS = Fan Failure Swi tc h
ICS = Integrated Comfort System (See BAS)
IDM = Indoor Fan Motor
IGV = Inlet Guide Vanes
I/O = Input/Output
IOM = Installation, Operation and Maintenance manual (Ships with each unit)
LCI = LonTalk® Communication Interface
LCI-R = LonTalk Communication Interface with ReliaTel
LH = Left Hand
MAS = Mixed Air Sensor
MAT = Mixed Air Temperature
MWU = Morning Warm Up
NSB = Night Setback (programmable ZSM BAYSENS119*)
O/A = Outside Air
OAH = Outside Air Humidity
OAT = Outside Air Temperature
PGA = Power Exhaust Actuator
PSIG = Pounds Per Square Inch Gauge pressure
PHM = Phase monitor
R/A = Return Air
RAH = Return Air Humidity
RAT = Return Air Temperature sensor
RH = Right Hand
RHP = Reheat Pumpout Solenoid
RHV = Reheat Valve
RLP = Reheat Low Pressure Cutout
RPM = Revolutions Per Minute
RTAM = ReliaTel Airhandler Mo dule
RTDM = ReliaTel Dehumidification Module
RTVM = ReliaTel Ventilation Module
RT-SVX34C-EN 11
General Information
RTOM = ReliaTel Options Module
RTRM = ReliaTel Refrigeration Module
S/A = Supply Air
SPC = Space Pressure Calibration Solenoid
SPP = Space Pressure Transducer
SPT = Static Pressure Transducer
TCI = Trane Communication Interface
TCO = Temperature Cutout
TDL = Temperature Discharge Limit
VAV = Variable Air Volume
VFD = Variable Frequency Drive
VHR = Ventilation Heat Relay (VAV box relay)
W.C. = Wa t e r Colu m n
XFSP = Exhaust Fan Setpoint
ZSM = Sensor, Zone Sensor, Zone Sensor Module, Zone Panel
About the Unit
Overall unit dimensional data is illustrated in Figure 1, p. 17 to Figure 9, p. 22. Each package rooftop unit ships fully assembled and charged with the proper refrigerant quantity from the factory. They are controlled by a microelectronic unit control processor. Several solid state modules are grouped to form the "Control System". The number of modules within any given control system will be dependent upon the options and accessories ordered with the unit. Acronyms are used extensively throughout this manual when referring to the "Control System" (see acronyms/abbreviations previous page).
Basic unit components include:
Scroll compressors
One (1) Intertwined Evaporator Coil
One (1) Intertwined Condenser Coil
One (1) Supply Fan
Three (3) to Four (4) Condenser Fans
Filters (type is dependent on option selection)
Precautionary Measures
WARNIN G
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
- Avoid breathing fiberglass dust.
- Use a NIOSH approved dust/mist respirator.
- Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
- Wash clothes separately from other clothing: rinse washer thoroughly.
- Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
12 RT-SVX34C-EN
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact - Wash affected areas gently with soap and warm water after handling.
An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Unit Inspection
As soon as the unit arrives at the job site:
Verify that the nameplate data corresponds to the sales order and bill of lading (including
Visually inspect the exterior of the unit, including the roof, for physical signs of shipping
Check for material shortages. Figure 11 on page 23 illustrates where "ship with" items are
If the job site inspection reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the "bill of lading" before signing. Do not install a damaged unit without the Appropriate Trane sales representative's approval!
Visually check the internal components for shipping damage as soon as possible after delivery
General Information
electrical data).
damage.
placed inside the unit.
and before it is stored. Do not walk on the sheet metal base pans.
Storage
WARNIN G
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse. Failure of the drain pan could result in death or serious injury.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.
If concealed damage is discovered, notify the carrier's terminal office immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove the damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Take precautions to prevent condensate formation inside the unit electrical components and motors when:
a. The unit is stored before it is installed; or,
b. The unit is set on the roof curb and temporary auxiliary heat is provided in the building.
Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for startup.
Do not use the unit heater as temporary heat without completing the startup procedures detailed under "Unit startup".
Trane will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.
RT-SVX34C-EN 13
Pre-Installation
The checklist listed below is a summary of the steps required to successfully install a Voyager Commercial rooftop unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual.
General Unit Requirements
Downflow Models Only:
An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Assemble and install the roof curb, including necessary gaskets. Make sure the curb is level.
Install and secure the ductwork to the curb.
All Units:
Check unit for shipping damage and material shortage. (Refer to "Unit inspection" section).
Rigging the unit. Refer to Figure 12, p. 24.
Placing the unit on curb; check for levelness. See “Roof Curb and Ductwork” on page 16.
Ensure that the unit-to-curb seal is tight and without buckles or cracks.
Install an appropriate drain line to the evaporator condensate drain connections, as required. Refer to Figure 14, p. 29.
Service Valve Option; See “Starting the Compressor” on page 98.
Return/Fresh-air damper adjustment. Refer to “Economizer Damper Adjustment” on page 94.
Exhaust Fan Damper Stop Adjustment. Refer to Exhaust Damper Adjustment figures, beginning with Figure 46, p. 103.
Electrical Requirements
(See Figure 18, “Typical Field Power Wiring,” on page 34.)
Verify that the electrical power supply characteristics comply with the unit nameplate specifications.
Inspect all control panel components; tighten any loose connections.
Connect properly sized and protected power supply wiring to a field supplied/installed disconnect and unit power terminal block HTB1, or to the optional unit-mounted disconnect switch.
WARNIN G
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow codes could result in death or serious injury.
Properly ground the unit.
14 RT-SVX34C-EN
Field Installed Control Wiring
(Figure 19, p. 41 and Figure 20, p. 42.)
Important: All field-installed wiring must comply with NEC and applicable local codes.
Complete the field wiring connections for the constant volume controls as applicable. Refer to
“Low Voltage Wiring” on page 39 for guidelines.
the
Complete the field wiring connections for the variable air volume controls as applicable. Refer to the “Low Voltage Wiring” on page 39 for guidelines.
Gas Heat Requirements
(See “Installation Piping” on page 53.)
Gas supply line properly sized and connected to the unit gas train.
All gas piping joints properly sealed.
Drip leg Installed in the gas piping near the unit.
Gas piping leak checked with a soap solution. If piping connections to the unit are complete, do not pressurize piping in excess of 0.50 psig or 14 inches w.c. to prevent component failure.
Main supply gas pressure adequate.
Flue Tubes clear of any obstructions.
Pre-Installation
RT-SVX34C-EN 15
Unit Dimensions and Weights
Recommended Clearances
Adequate clearance around and above each Voyager Commercial unit is required to ensure proper operation and to allow sufficient access for servicing.
If the unit installation is higher than the typical curb elevation, a field constructed catwalk around the unit is recommended to provide safe, easy access for maintenance and servicing. Table 1, p. 23 lists the recommended clearances for single and multiple unit installation. These clearances are necessary to assure adequate serviceability, cataloged capacities, and peak operating efficiency.
If the clearances available on the job site appear to be inadequate, review them with your Trane sales representative.
Roof Curb and Ductwork
The curbs for the 27.5 to 50 Ton commercial rooftop units enclose the entire unit base area. They are referred to as "full perimeter" type curbs.
Step-by-step instructions for the curb assembly and installation with curb dimensions and curb configuration for "A", "B", and "C" cabinets ship with each Trane accessory roof curb kit. (See the latest edition of the curb installation guide) Follow the instructions carefully to assure proper fit when the unit is set into place.
The S/A and R/A ductwork adjoining the roof curb must be fabricated and installed by the installing contractor before the unit is set into place. Trane curbs include flanges around the openings to accommodate duct attachment.
Ductwork installation recommendations are included in the instruction booklet that ships with each Trane accessory roof curb kit.
Note: For sound consideration, cut only the holes in the roof deck for the supply and return duct
penetration. Do Not remove the roof decking from the inside perimeter of the curb.
If a Trane curb accessory kit is not used:
Horizontal Ductwork
When attaching the ductwork to a horizontal unit, provide a water tight flexible connector at the unit to prevent noise transmission from the unit into the ductwork. Refer to figures beginning on page
17 for the S/A and R/A opening dimensions.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
If optional power exhaust is selected, an access door must be field-installed on the horizontal return ductwork to provide access to exhaust fan motors.
a. The ductwork can be attached directly to the S/A and R/A openings. Be sure to use a flexible
duct connector at the unit.
b. For "built-up" curbs supplied by others, gaskets must be installed around the curb perimeter
flange, S/A opening, and R/A openings.
c. Insulation must be installed on the bottom of the condenser section of the unit.
16 RT-SVX34C-EN
Unit Dimensions and Weights
1 1/4 (32)
3 1/4 (81)
Figure 1. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat)
Figure 2. Rear view showing duct openings for horizontal units
RT-SVX34C-EN 17
Unit Dimensions and Weights
NOTES:
1. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
179 3/4"
4565.65mm
42"
1066.8mm
83 13/16"
2128.8mm
90 1/16"
2287.5mm
180 5/16"
4579.9mm
90 3/8"
2295.5mm
5 3/8"
136.5mm
7 9/16"
192.1mm
3.25 [82.55mm] TO TOP OF FAN GRILLE
70 7/16"
1789.1mm
40 3/16"
1020.7mm
6 7/8"
174.6mm
1 1/4" [31.7mm] FEMALE
PVC PIPE
3/4" [19.0mm] NPT GAS INLET
SEE NOTE 2
CUSTOMER CONNECTION POINT
191
Figure 3. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat)
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
Figure 4. 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat)
18 RT-SVX34C-EN
Unit Dimensions and Weights
Figure 5. Duct openings, 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat)
3 1/4 (81)
1 1/4 (32)
Figure 6. 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat)
90 5/8"
2301.8mm
208 1/16"
5284.7mm
SEE NOTE 2
NOTES:
1. SEE ROOFCURB DRAWING FOR DETAILS ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
3.25 [82.55mm] TO TOP OF FAN GRILLE
1 1/4" [31.7mm]
PVC PIPE FEMALE
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
RT-SVX34C-EN 19
42"
1066.8mm
2128.8mm
1" [25.4MM] NPT GAS INLET
83 13/16"
5 3/8"
136.5m
7 9/16"
192.1m
207 1/2"
5270.5mm
CUSTOMER CONNECTION POINT
40 3/16"
1020.7mm
6 15/16"
174.6mm
90 1/16"
2287.5mm
70 7/16"
1789.1mm
Unit Dimensions and Weights
1 1/4 (32)
3 1/4 (81)
Figure 7. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat)
Figure 8. Duct openings, 60 Hz 40-50, 50 Hz 33-42 Tons
(TC, TE, YC Low and High Heat)
20 RT-SVX34C-EN
Unit Dimensions and Weights
7 9/16"
232 3/8"
5902.3mm
232 3/4"
5911.8mm
90 5/8"
49 9/16"
1258.8mm
93 3/8"
2371.7mm
5 5/16"
90 1/16"
77"
1955.8mm
46 15/16"
1192.2mm
4 3/4"
120.6mm
NOTES:
1. SEE ROOFCURB DRAWING FOR DETAILS ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
SEE NOTE 2
CUSTOMER CONNECTION POINT
2301.8mm
PVC PIPE FEMALE
1" [25.4MM] NPT HIGH HEAT GAS INLET
2287.5mm
136.5m
192.1m
3.25 [82.55mm] TO TOP OF FAN GRILLE
1 1/4" [31.7mm]
3/4" [19MM] NPT LOW HEAT GAS INLET
Figure 9. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low and High Heat)
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
Figure 10. Fresh Air and Power Exhaust Dimensions for TC*, TE*, and YC* Units
RT-SVX34C-EN 21
Unit Dimensions and Weights
Figure 11. Location of "Ship With" Items for TC*, TE*, and YC* Units
Unit Rigging and Placement
WARNIN G
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit may result in death or serious injury.
Use spreader bars as shown in the diagram. Refer to the Installation manual or nameplate for unit weight. Refer to the Installation instructions located inside the control panel for further rigging information.
1. Verify that the roof curb has the proper gaskets installed and is level and square to assure an adequate curb-to-unit seal.
The units must be as level as possible in order to assure proper condensate flow out of the unit. The maximum side-to-side and end-to-end slope allowable in any application is listed in
Table 2, p. 23.
22 RT-SVX34C-EN
Unit Dimensions and Weights
Figure 12. Unit Rigging
Table 1. Minimum Operating Clearances Installation (Horizontal and Downflow Configurations)
Recommended Clearances
Single Unit
TC*, TE*, YC*
27.5 to 50 Tons
Exhaust End
6 Feet 8 Feet 4 Feet
Distance Between Units
Economizer/
Economizer/
Multiple Unit
TC*, TE*, YC*
27.5 to 50 Tons
(a) Condenser coil is located at the end and side of the unit.
Exhaust End End/Side Service Side Access
12 Feet 16 Feet 8 Feet
Condenser Coil
Orientation End/Side
(a)
Service Side Access
Table 2. Maximum Slope
Cabinet End to End (inches) Side to Side (inches)
"A" (27.5 - 35 Ton Low Heat) 3 1/2 1 5/8
"B" (27.5 - 35 Ton High Heat) 4 1 5/8
"C" (All 40 and 50 Ton Units) 4 1/2 1 5/8
Note: Do not exceed these allowances. Correct the improper slope by building up the curb base. The material used to raise
the base must be adequate to support both the curb and the unit weight.
RT-SVX34C-EN 23
Unit Dimensions and Weights
X
Y
Z (see note 2)
Figure 13. Center of Gravity
Table 3. Center of Gravity
1
Center-of-Gravity (inches)
Unit Model
YC Low Heat
Dimension
YC High Heat
Dimension TC/TE Dimension
X Y Z X Y Z X Y Z
***330/275* 41 76 33 41 84 33 42 76 33
***360/305* 43 77 33 43 85 33 44 77 33
***420/350* 42 78 33 42 86 33 43 78 33
***480/400* 42 111 35 42 111 35 42 111 35
***600/500* 43 108 35 43 108 35 43 108 35
Note: Center-of-gravity dimensions are approximate, and are based on the unit equipped with: standard
efficiency coils, standard efficiency motors, economizer, inlet guide vanes, and throwaway filters
Note: Z dimension is upward from the base of the unit.
Example: Locating the center-of-gravity for a YC-360 MBH High Heat unit with 100% exhaust. X = 43 inches inward from the control panel side Y = 85 inches inward from the compressor end Z = 33 inches upward from the base
Table 4. Approximate Units Operating Weights — lbs./kg1
Basic Unit Weights1
Unit
Model
**D330/275 3750 1701 4130 1873 3620 1642 3640 1651
**H330/275 3790 1719 4220 1914 3660 1660 3680 1669
**D360/305 3845 1744 4225 1916 3715 1685 3735 1694
**H360/305 3885 1762 4315 1957 3755 1703 3775 1712
**D420/350 3970 1801 4350 1973 3840 1742 3860 1751
**H420/350 4010 1819 4440 2014 3880 1760 3900 1769
**D480/400 4764 2161 4884 2215 4539 2059 4564 2070
**H480/400 4859 2204 4984 2261 4599 2091 4634 2102
**D600/500 5174 2347 5294 2401 4949 2245 4974 2256
**D600/500 5269 2390 5394 2447 5019 2277 5044 2288
Notes:
1. Basic unit weight includes minimum horsepower supply fan motor.
YC
Low Heat
YC
High Heat TC TE
24 RT-SVX34C-EN
Unit Dimensions and Weights
DE F
TOP VIEW OF UNIT
COMPRS
CBA
Table 5. Point Loading Average Weight1,2 — lbs./kg
Model A B C D E F
**D330/275 846 384 688 313 743 337 745 338 604 275 503 228
**H330/275 867 393 707 321 767 348 753 342 613 279 513 233
**D360/305 836 379 680 309 779 353 741 336 621 285 568 258
**H360/305 897 407 696 316 766 348 729 330 590 268 636 288
**D420/350 892 405 692 314 779 353 765 347 633 288 590 268
**H420/350 867 393 869 395 690 313 758 344 601 273 654 297
**D480/400 820 372 856 388 937 425 742 336 762 346 769 349
**H480/400 841 381 876 397 957 434 754 342 775 352 782 355
**D600/500 894 406 955 428 970 440 756 343 862 391 866 393
**H600/500 915 415 966 438 990 449 768 348 875 397 879 399
Notes:
1. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F.
2. Point load calculations provided are based on the unit weight for YC high heat gas models.
Table 6. Approximate Operating Weights1— Optional Components — lbs./kg
Unit
Model
**D330/275 110/50 165/74 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H330/300 145/65 200/90 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D360/305 110/50 165/74 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H330/305 145/65 200/90 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D420/350 110/50 165/74 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H420/350 145/65 200/90 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D480/400 110/50 165/74 50/23 290/131 70/32 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**H480/400 145/65 200/90 50/23 300/135 70/32 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**D600/500 110/50 165/74 50/23 290/131 70/32 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**H600/500 145/65 200/90 50/23 300/135 70/32 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
Note:
1. Basic unit weight includes minimum horsepower supply fan motor.
Baro.
Relief
Power
Exhaust
0-25%
Man
Damper Econ.
RT-SVX34C-EN 25
Inlet Guide Vanes
Var. Freq.
Drives (VFD’s)
Bypass Lo Hi
Valves
Serv
Thru-
the base Elec.
Non-
Fused
Discon.
Switch
Factory.
GFI with
Discon.
Switch
Roof CurbW/O With
Installation General Requirements
Condensate Drain Connection
Each commercial rooftop unit is equipped with one (1) 1-1/4 inch Female PVC condensate drain connection.
Refer to Figure 11, p. 23 for the location of the connector. A condensate trap must be installed due to the drain connection being on the "negative pressure" side of the fan. Install a P-Trap at the unit using the guidelines in Figure 14, p. 26.
Pitch the drain line at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow.
Ensure that all condensate drain line installations comply with applicable building and waste disposal codes.
Figure 14. Condensate Trap Installation
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume applications and units with Statitrac™.
A duct pressure transducer and the outside air sensor is used to control the discharge duct static pressure to within a customer-specified controlband. Refer to the illustration in Figure 15, p. 27 and the following steps to install the sensor and the pneumatic tubing.
1. Remove the O/A pressure sensor kit located inside the fan section. The kit contains the following items;
an O/A static pressure sensor
a sensor mounting bracket
50’ of 3/16" O.D. pneumatic tubing
mounting hardware
2. Using two #10-32 x 1-3/4" screws provided, install the sensor's mounting bracket to the factory provided bracket (near the fan section).
3. Using the #10-32 x 1/2" screws provided, install the O/A static pressure sensor vertically to the sensor bracket .
4. Remove the dust cap from the tubing connector located below the sensor in the vertical support.
26 RT-SVX34C-EN
5. Attach one end of the 50' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing.
Units with Statitrac™
1. Open the filter access door, and locate the Statitrac Transducer Assembly illustrated in
Figure 16, p. 28. There are two tube connectors mounted on the left of the solenoid and
transducers. Connect one end of the field provided 1/4" (length 50-100 ft.) or 3/8" (length greater than 100 ft.) O.D. pneumatic tubing for the space pressurization control to the fitting indicated in the illustration.
2. Route the opposite end of the tubing to a suitable location inside the building. This location should be the largest open area that will not be affected by sudden static pressure changes.
Figure 15. Pressure Tubing
Installation General Requirements
RT-SVX34C-EN 27
Installation General Requirements
T
Figure 16. Statitrac Transducer Assembly
Static Reference
ubing Connects
Here (O/A Sensor)
Space Pressure Sensing Tube Connects Here
Space Pressure Transducer
Space Pressure Calibration Solenoid
Space Pressure Transducer
Sensing Tube
LO
HI
to Space Pressure
CNO
NC
Sensing Tube to Outside Air Reference
28 RT-SVX34C-EN
Installation Electrical
Disconnect Switch External Handle (Factory Mounted Option)
Units ordered with the factory mounted disconnect switch come equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle location and its three positions are shown below;
ON - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit.
OFF - Indicates that the disconnect switch is open, interrupting the main power supply at the unit.
OPEN COVER/RESET - Turning the handle to this position releases the handle from the disconnect switch, allowing the control panel door to be opened.
WARNIN G
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Once the door has been opened, it can be closed with the handle in any one of the three positions outlined above, provided it matches the disconnect switch position. The handle can be locked in the "OFF" position. While holding the handle in the "OFF" position, push the spring loaded thumb key, attached to the handle, into the base slot. Place the lock shackle between the handle and the thumb key. This will prevent it from springing out of position.
Figure 17. Disconnect Switch
An overall layout of the field required power wiring is illustrated in Figure 18. To insure that the unit supply power wiring is properly sized and installed, follow the guidelines outlined below.
Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit's name plate ratings for all components. The available power supply must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the 3-phase power supply to the unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
RT-SVX34C-EN 29
Installation Electrical
Main Power Wiring
WARNIN G
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow codes could result in death or serious injury.
1. Table 7, p. 32 and Table 9, p. 34 list the electrical data. The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to “Electrical
Wire Sizing and Protection Device Equations” on page 35 for determining:
a. The appropriate electrical service wire size based on "Minimum Circuit Ampacity" (MCA),
b. The "Maximum Over current Protection" (MOP) device.
c. The "Recommended Dual Element fuse size" (RDE).
2. If the unit is not equipped with an optional factory installed Nonfused disconnect switch, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Refer to DSS calculations “Electrical Wire Sizing and
Protection Device Equations” on page 35 for determining correct size.
Location for the electrical service entrance is shown in the unit dimensional drawings beginning with Figure 1, p. 17. Complete the unit's power wiring connections onto either the main terminal block HTB1, or the factory mounted nonfused disconnect switch inside the unit control panel.
Note: When the factory installed through-the-base option is not used, the installing contractor is
required to seal any holes made in the base of the unit to prevent water from leaking into the building.
3. Provide proper grounding for the unit in accordance with local and national codes.
Thru-the-Base Electrical (Optional Accessory)
Liquid-tite conduit couplings are secured to the base of the unit for both power and control wiring. Liquid-tite conduit must be field installed between the couplings and the unit control box to prevent water leaks into the building.
Note: If the unit is set on the roof curb and temporary auxiliary heat is provided in the building,
it is recommended that the electrical and control wiring conduit opening in the control box be temporarily sealed to provide a vapor barrier.
30 RT-SVX34C-EN
Loading...
+ 122 hidden pages