Trane SCWG-020, SCWG-025, SCWG-030, SCWG-035, SIWG-020 Programming Manual

...
Programming Guide
IntelliPak
®
Commercial Self-Contained
Signature Series, 20-80 Ton Modular Series, 20-35 Ton
SCWG -020, -025, -030, -035 SIWG -020, -025, -030, -035
SCRG -020, -025, -032 SIRG -020, -025, -032
SCWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080 SIWF -020, -022, -025, -029, -032, -035, -038, -042, -046, -052, -058, -065, -072, -080
SCRF -020, -025, -029, -030, -035, -040, -050, -060 SIRF -020, -025, -029, -030, -035, -040, -050, -060
April 2000
PKG-SVP01B-EN
General Information
Note: One copy of the appropriate service literature (Installation, Owner, and Diagnos­tic Manual) ships inside the control panel of each unit.
About This Manual Literature Change History
Use this manual for IntelliPak® commer­cial self-contained models SCWF/SIWF, SCRF/SIRF, SCWG/SIWG, and SIWG/ SIRG. This is the second issue of this manual. This revision includes an index, which was not in the original issue. It provides specific programming instructions for “AO” and later design sequences. For previous design sequences, contact your local Trane representative.
Overview
This manual is divided into multiple sections based on the unit’s human interface (HI) panel format. Each section provides step by step instructions for programming the unit using the HI. In addition, each section provides specific information about the system operating parameters and their related HI screens, in the order they appear when scrolling through the HI.
By carefully following the screen layout in this manual while referencing the HI panel, the user can monitor operating
status, set specific operating parameters, and diagnose system problems.
Some screens shown in this manual are dependent on unit options and/or model configuration. Therefore, some screens in this manual may not appear on a particular unit’s human interface panel. Screens that are configuration-depen­dent are labeled as such. Follow the appropriate steps for each screen as it appears and proceed through each section.
Refer to the table of contents and index for specific topics contained in this manual and supporting manuals.
Complete the “Start-Up” procedures in the applicable Installation, Owner, and Diagnostic (IOD) manual before attempt­ing to operate or service this equipment to minimize the risk of improper opera­tion.
Note: The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians.
©American Standard Inc. 2000 PKG-SVP01B-EN
Contents
Cross reference to related publications:
IntelliPak® Self-Contained Installation,
Owner, and Diagnostic Manual SCXF­SVX01A-EN
models SCWF, SCRF, SIWF, and SIRF
for Signature Series
Programming
General Information STATUS Menu SETUP Menu SETPOINT Menu CONFIGURATION Menu SERVICE MODE Menu DIAGNOSTICS Menu Index
IntelliPak® Self-Contained Installation, Owner, and Diagnostic Manual SCXF­SVX01A-EN
SCWG, SCRG, SIWG, and SIRG
for Modular Series models
2
17 32
57
63
68
72
76
PKG-SVP01B-EN 3
General InformationProgramming
Commonly Used Acronyms and Abbreviations
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.
Act = active AH = Air Handler Annunc = Annunciater AS = Airside Aux = auxiliary BAS = building automation systems ccfm = (100 cfm) cubic-feet-per-minute Cfg = Configured, configuration cfm = cubic-feet-per-minute ckt = circuit Cmd = command Comp (s) = compressor, compressors Cond = condenser, condensers Config = configured, configuration Ctrl = control CV = constant volume Cy = cycle CW = clockwise CCW = counterclockwise Dflt = default Diag = diagnostic Dmpr = damper DWU = Daytime Warmup E/A = exhaust air ECEM = exhaust control/enthalpy module Econ = economizer, economizing Ent = entering Evap = evaporator F/A = fresh air Funct = function GBAS = generic building automation system (module) Heat = Heat, heating HEAT = where all caps HEAT (module) HGBP = hot gas bypass Hi = high HI = where all caps Human Interface HVAC = heating, ventilation and air conditioning ICS = Integrated Comfort System IGV = inlet guide vanes I/O = input/output Indep = Independent IOD = installation/owner/ diagnostic manual IPC = interprocessor communications IPCB = interprocessor communications bridge (module) IWC = inches water column LCD = liquid crystal display
LH = left-hand Lo = low Manif = manifolded Max = maximum Min = minimum Misc = miscellaneous MCM = multiple compressor module Mod = modulating MWU = morning warmup NSB = night setback panel Num = number O/A = outside air Occ = occupied Pos = position Pot = potentiometer PPM = parts per million Press = pressure Propor = proportional psig = pounds-per-square-inch gauge pressure PWS = part-winding start R/A = return air Refrig = refrigerant RHI = Remote Human Interface RH = right-hand rpm = revolutions-per-minute RTM = RTM module SA = supply air SAP = supply air pressure Sat = saturated SCM = single compressor module Setpt = setpoint SF = supply fan SRC = source Stg = stage Stnd = standard STP = setpoint Sw = switch SZ = single-zone (unit airflow) TCI = Tracer communications interface module Temp = temperature UCM = unit control module Unocc = unoccupied VAV = variable air volume VCM = ventilation control module VDC = volts DC Ventil = ventilation VFD = variable frequency drive VOM = ventilation override module W/ = with w.c. = water column WU = warmup
4 PKG-SVP01B-EN
General InformationProgramming
Glossary
These terms are used throughout this manual. Knowledge of these terms is essential in gaining an understanding of how these units operate.
Active Setpoint
The setpoint which is currently being used for control by the setpoint source selection.
Compressor Lockout
All affected compressors stop and remain off until the condition resets or is manually reset.
Compressor Protection Switch
A pressure switch installed on the suction line that prevents compressor operation below the switch’s setpoint. The purpose is to prevent no-flow scroll compressor operation.
Control Band
The range of temperatures or pressures which would normally be maintained by the various control functions.
Control Point
The value of a setpoint that an algorithm is using at any given time.
Deadband
As applied to SA temperature control, this refers to a range of temperatures equally spaced above and below the SA temperature control point in which the control algorithm is satisfied.
Economizer Zone Temp Setpoint Suppression
A parameter used for setting the Zone Temp setpoint at a lower value than the mechanical cooling zone temperature setpoint.
External Heat
A heat source external to the self­contained unit that is field installed. i.e. duct heat or VAV reheat boxes.
External Stop
A binary input on the RTM that allows unit shutdown when connected to a field­supplied switch.
Hydronic Heat
Optional steam or hot water heat coil.
Independent Refrigerant Circuit
All model SCWG/SIWG, SCRG/SIRG and SCWF/SIWF units have independent refrigerant circuits.
Low Ambient Compressor Lockout
A function which prevents compressor operation at low outdoor ambient temperatures.
Low Entering Condenser Water Tem­perature
When the entering water temperature sensor reads a water temperature below the minimum water temperature input into the controller. 54 F is the factory preset temperature.
Low Entering Water Temperature Compressor Lockout
On units with head pressure control disabled and an entering water tempera­ture below 54 F, compressor operation disables. Economizer operation is still functional.
Manifolded Refrigerant Circuit
Only model SCRF/SIRF units, 30-60 tons, have manifolded refrigerant circuits.
Night Setback (NSB)
Applies to unit control during unoccupied periods.
Night Setback (NSB) Panel
The HI panel display uses this term for NSB zone sensor.
OA Reset
Outdoor Air Reset - Supply Air Tempera­ture Reset based on Outdoor Air Tem­perature.
Occupied Zone Low Temperature Limit Setpoint
The temperature that initiates daytime warmup.
Purge
A function which causes zone air to purge and be replaced by outside air.
Reference Enthalpy
An outdoor enthalpy value above which economizing disables.
Remote Human Interface
A human interface module designed to be mounted remotely from the unit. There are some functional differences between a unit mounted and a remote mounted human interface module.
Reset Amount Maximum
The maximum amount of reset allowed.
Reset End Temperature
The temperature at which the maximum reset amount will occur.
Reset Start Temperature
The temperature at which reset will begin.
Space Pressure
The pressure in the building as measured by the space pressure transducer, referenced to outside (atmospheric) pressure.
Supply Air Pressure High Limit
A pressure limit to prevent unit casing and/or ductwork overpressurization.
Supply Air Pressure
The pressure in inches water column (IWC) of the supply duct plenum or outlet as measured by the supply air pressure transducer, referenced to local outside (atmospheric) pressure.
Supply Air Tempering
Turning on heat when the supply air temperature drops below a preset value usually due to cold outside air being brought in to provide building ventilation.
Supply Air Temperature Control Point
The revised value of supply air tempera­ture setpoint after supply air temperature reset has been applied.
Supply Air Temperature Reset
A function that shifts the SA Temp Setpoint an amount based on the value of another parametertypically Zone Temp or Outdoor Air Temp. The purpose of this function is to lower unit capacity to better meet load requirements.
Water Purge
When the waterside economizer valve opens to flush out the economizer tubes to prevent failure due to stagnant water and sedimentation.
PKG-SVP01B-EN 5
General InformationProgramming
Table P-GI-1. IntelliPak® Points List.
Unit Module Analog Inputs Analog Outputs Binary Inputs Binary Outputs RTM ASE damper min pos O/A damper actuator Emergency stop VAV box drive max
SCM Evap temp sensor Cond fan speed Low pressure control Compressor relay
MCM Evap temp sensor Cond fan speed Low pressure control - ckt 1 & 2 Compressor relay
Heat Module MWU temp sensor Modulating heat actuator Low entering air Heat 1 relay
ECEM Return air temp sensor
VOM N/A N/A VOM mode A, B, C, D, E contacts VOM relay GBAS 4 inputs from these choices: N/A Demand limit contacts Dirty filter
Sat cond temp sensor (Low ambient) Compressor proving Condenser fan A, B
Sat cond temp sensor (Low ambient - ckt 1 & 2) Compressor proving - ckt 1 & 2 Condenser fan 1A, 1B, 2A, 2B
Return air humidity sensor
Occ zone cool setpt Refrigeration fail relay Occ zone heat setpt Heat fail relay
Unocc zone cooling setpt Fan fail relay
Unocc zone heat set TBD relay
Min O/A flow setpt Sup air cooling setpt Sup air heating setpt
Sup air static pres setpt
External auto/stop CV unoccupied mode indicator Unoccupied/occupied Alarm
Dirty filter Fan run request VAV changeover Water pump request Supply airflow proof
Heat 2 relay Heat 3 relay
6 PKG-SVP01B-EN
General InformationProgramming
UCM Control System
The IntelliPak® self-contained unit is controlled by a microelectronic control system that consists of a network of modules. These modules are referred to as unit control modules (UCM). In this manual, the acronym UCM refers to the entire control system network.
The unit size, type, heating functions, peripheral devices, options, exhaust capabilities, etc. determine the number and type of modules that a particular unit may have.
These modules perform specific unit functions using proportional/integral control algorithms. They are mounted in the unit control panel and are factory wired to their respective internal compo­nents. By processing analog and binary inputs, each module supplies outputs in the form of modulating voltages (from other unit modules, sensors, remote panels, and customer binary contacts) to perform the applicable request; such as economizing, mechanical cooling, heating, ventilation.
The UCM provides some equipment protection functions both directly and indirectly, such as duct pressure limits and compressor lockouts.
Following is a description of each module’s function within the UCM system.
RTM Module Board - Standard on all Units
The RTM is the central processor of the system. It continuously receives informa­tion from the other unit modules, sensors, the remote control panel, and customer supplied relays. It interprets this informa­tion and responds to cooling, heating, and ventilation requests by directing the other modules in the system to energize the proper unit components. It also directly initiates supply fan operations, and economizer operation.
Compressor Modules (SCM and MCM )
The compressor modules (single circuit and multiple circuit) energize the appro­priate compressors and condenser fans upon receiving a request for mechanical cooling. The modules monitor the compressor operation through feedback from various protection devices.
Heat Module - Standard on all Heating Units
The heat module directs the unit’s heater to stage up and down to bring the zone temperature within the applicable heating setpoint.
Exhaust/Comparative Enthalpy Module (ECEM) Option
The ECEM is on units with the compara­tive enthalpy option. It receives data from the return air humidity sensor, the return air temperature sensor, and the return air space pressure transducer and controls dampers to maintain space pressure and humidity levels.
Generic Building Automation System (GBAS) Module Option
The GBAS module links the RTM with non-Trane building control systems to enable communication (input/output interface) between the systems. It can accept external setpoints for cooling, heating, demand limiting, and S/A pressure.
Ventilation Override Module (VOM) Option
The VOM can control the unit’s air handling functions to perform customer­specified functions, such as space pressurization, exhaust, purge, unit off, etc.
Interprocessor Communications Board (IPCB) Option
The IPCB is used to expand communica­tion from the unit’s UCM network to a remote human interface panel. DIP switch settings on the IPCB module for this application should be; switches 1 and 2 off,” switch 3 on.
Trane Communications Interface Module (TCI) Option
The TCI module allows external setpoints for most of the unit functions to be communicated to the unit’s UCM network via a Trane ICS settings on the TCI module for these applications should be; switches 1, 2, and 3 are “off.”
Human Interface Module (HI)
The HI module illustrated in Figure P-GI-1, on page 9, enables the user to communi­cate unit operating parameters; such as cooling and heating setpoints, demand limiting, ventilation override modes, etc.
TM
system. DIP switch
The HI module is in the unit’s main control panel. A small door located in the unit’s control panel door allows access to the HI module keypad and display window.
The HI has a 2 line by 40 character LCD screen to provide status information for various unit functions and menus to set or modify operating parameters. There is a 16-key keypad adjacent to the LCD screen to allow the user to scroll through the various menus and make adjust­ments to setpoints, etc.
The information displayed in the LCD window is top-level status information unless the operator initiates other displays.
At power-up, the human interface LCD displays one of four initial screens as illustrated in the General Status Displaysection on page 11 and de­scribed below:
1. Unit Off (unit off or stopped) The unit is configured and operational, but is not running. This screen shows state, mode, and function information when the unit is off or stopped.
2. Unit On (unit on) The unit is configured and operational, and is running. This screen shows state, mode, and function information when the unit is on.
3. VOM Active (a ventilation override command was received) This screen shows that the unit is in a ventilation override mode.
4. No Configuration (the unit needs to be configured) This screen shows that required configuration data is missing.
The LCD screen display will go out if no keys are pressed for 30 minutes. If it goes out, simply press the STATUS key.
PKG-SVP01B-EN 7
General InformationProgramming
Ventilation Override Module (VOM) Definitions
The ventilation override module can be field-configured with up to five different override sequences for ventilation override control purpose. When any one of the module’s five binary inputs are activated, it will initiate specified func­tions such as; space pressurization, exhaust, purge, purge with duct pressure control, and unit off.
Once the ventilation sequences are configured, they can be changed unless they are locked using the HI. Once locked, the ventilation sequences cannot be unlocked.
The compressors and condenser fans disable during the ventilation operation. If more than one ventilation sequence activates, the one with the highest priority (VOM “A”) begins first, with VOM “E” having lowest priority and beginning last.
A description of the VOM binary inputs follows below.
UNIT OFF sequence “A
When complete system shut down is required, the following sequence can be used.
Supply fan Off
Supply fan VFD Off (0 Hz)
(if equipped)
Inlet guide vanes – closed (if equipped)
Outside air dampers Closed
Heat all stages – Off, Modulating heat
output at 0 vdc
Occupied/Unoccupied output – De­energized
VO relay Energized
Exhaust fan (field-installed) - Off
Exhaust damper (field-installed) -
Closed
PRESSURIZE sequence “B
This override sequence can be used if a positively pressured space is desired instead of a negatively pressurized space.
Supply fan on
Supply fan VFD on (60 Hz)
(if equipped)
Inlet guide vanes/VAV boxes – open (if equipped)
Outside air dampers open
Heat all stages – off, hydronic heat
output at 0 vdc
Occupied/ unoccupied output - ener­gized
VO relay - energized
Exhaust fan (field-installed) - off
Exhaust damper (field-installed) - closed
EXHAUST sequence “C
With the building’s exhaust fans running and the unit’s supply fan off, the condi- tioned space becomes negatively pressurized. This is desirable for clearing the area of smoke when necessary; i.e. from an extinguished fire, to keep smoke out of areas that were not damaged.
Supply fan off
Supply fan VFD off (0 Hz)
(if equipped)
Inlet guide vanes – closed (if equipped)
Outside air dampers closed
Heat all stages – Off, hydronic heat
output at 0 vdc
Occupied/Unoccupied output – de­energized
VO relay energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
PURGE sequence “D
This sequence could be used for purging the air out of a building before coming out of unoccupied mode of operation on VAV units. Also, it can be used to purge smoke or stale air.
Supply fan on
Supply fan VFD on (60 Hz)
(if equipped)
Inlet guide vanes/VAV boxes – Open (if equipped)
Outside air damper Open
Heat all stages – Off, Modulating heat
output at 0 vdc
Occupied/Unoccupied output – Ener­gized
VO relay Energized
Exhaust fan (field-installed) - On
Exhaust damper (field-installed) - Open
PURGE with duct pressure control “E
This sequence can be used when supply air control is required for smoke control.
Supply fan on
Supply fan VFD on (if equipped)
Inlet guide vanes controlled by supply
air pressure control function with supply air pressure high limit disabled
Outside air dampers open
Heat all stages – off, hydronic heat
output at 0 vdc
Occupied/unoccupied output energized
VO relay energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
Note: Each system (cooling, exhaust, supply air, etc.) within the unit can be redefined in the field for each of the five sequences, if required. Also the definitions of any or all of the five sequences may be locked into the software by using the human interface panel keypad. Once locked into the software, the sequences cannot be changed.
8 PKG-SVP01B-EN
Programming the Unit
The UCM must be programmed with job-specificsetup information for the unit to operate and function properly. The data necessary for unit operation will vary depending on factors such as unit size, type, and options.
This manual provides step by step instructions for programming setup information using the HI or RHI. It also includes instructions for checking unit operating status, accessing and clearing diagnostics, and performing service tests.
Some of the displays in this manual may not appear on the HI or RHI screen during programming. Only applicable screens for specific unit options and operating parameters will display.
Any steps that do not apply to all unit types are marked accordingly. Ignore any steps that do not apply to your unit and/or application. Continue this process until all applicable screens are programmed with the required information.
Menu Keys
Any references in this section to the HI applies to both the HI and RHI, with the exception of the SERVICE MODE key.
Reference Figure P-GI-2 for an illustration of the six menu keys. The menu keys are: STATUS, SETPOINTS, SETUP, CONFIGU­RATION, DIAGNOSTICS, and SERVICE MODE. These keys allow access to various interactive menus so the user can input and access unit operating data. Pressing these keys will display the initial menu screen designated by the key’s name. The following information de­scribes each key and its function.
If no key is pressed for 30 minutes while the HI is displaying a menu screen, it will revert back to the unit operating status screen.
STATUS Key
Pressing the status key displays the operating status screen: On, Unit Stop, External Stop, Emergency Stop, or Service Mode. Pressing the NEXT key allows the operator to scroll to screens that provide information such as air and refrigerant temperatures, humidity levels, fan operation, compressor operation, heater operation, economizer positioning, exhaust operation, and
Figure P-GI-1. Human interface module.
heating, cooling, and compressor lockout setpoints. Pressing the STATUS key while viewing any of the data screens will cause the HI to go back to the operating status screen.
SETPOINTS Key
Pressing the SETPOINTS key displays the first of the setpoint screens, allowing the user to designate default temperatures and pressure setpoints. While scrolling through the setpoint screens, pressing this key again will cause the LCD to display the first setpoint screen.
DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any time will allow the user to view any unit function failures. The LCD screen will display one of the diagnostic screens (depending on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the screen is displaying diagnostic information, it will revert back to the operating status display.
CONFIGURATION Key
Pressing the CONFIGURATION key displays the first of the configuration screens. This allows the user to view or designate unit configuration data such as unit type, capacity, system control, etc
General InformationProgramming
Pressing the configuration key at any level in the configuration menu will display the first configuration screen.
Note: Unit configuration information is factory-programmed. Use this key only to view current configuration data, or to designate new data if the unit’s configura­tion data is lost or if new options are added in the field.
SETUP Key
Pressing the SETUP key displays screens that designate various operating param­eters such as temperature and pressure ranges, limits, percentages, setpoint source selections, and sensor input definitions for the control of the unit’s various operating modes. Pressing the SETUP key at any level in the SETUP menu will display the first SETUP screen.
SERVICE MODE Key
Pressing the SERVICE MODE key displays the first of the service test mode screens that allow the user to turn on or off various unit components for a particular test being performed. After designating on/off status, a screen will display requesting the user to designate the TEST START time delay for each test.
PKG-SVP01B-EN 9
General InformationProgramming
Data Manipulation Keys
The data manipulation keys allow theuser to modify data within the screens: ENTER, CANCEL, + (Plus), - (Minus), PREVIOUS, and NEXT. See Figure P--GI-2.
ENTER Key
This key will confirm new values desig­nated by pressing the + (Plus) or - (Minus) keys at all edit points. When viewing status and diagnostics screens, it has no function.
CANCEL Key
After changing data, at an editable screen, but before confirming it with the ENTER key, pressing the CANCEL key will return the data to its previous value. This key shall also function to clear active diagnostics.
+ (Plus) Key
When viewing a setpoint screen, this key will increase the temperature or pressure value of the setpoint. When working with a status menu, it will add the current status display to the custom menu. When viewing the setup or service test screens, it will increase setpoints or toggle choices on or off at each edit point.
- (Minus) Key
When viewing the setpoint screen, the minus key will decrease the temperature or pressure value of the setpoint. When viewing the setup or service test screens, it will decrease setpoints or toggle choices on or off at each edit point. When viewing the custom menu, pressing the ­(Minus) key will remove the status screen from the custom menu. When viewing diagnostics screens it has no function.
PREVIOUS Key
Pressing the PREVIOUS key causes the LCD to scroll backwards through the various displays for each menu. At displays with multiple edit points, it moves the cursor from one edit point to another.
NEXT Key
Pressing the NEXT key causes the LCD to scroll forward through the various displays for each menu. At displays with multiple edit points it moves the cursor from one edit point to another.
cause the display to go to the top level status display and, if the unit is shutdown, will cause the unit to begin operation in the appropriate mode no matter what menu level is currently displayed. If the current display is an editable display, the AUTO key will confirm the desired edit.
STOP Key
Pressing the STOP key will cause the unit to transition to the stop state. If the current display is editable, pressing the STOP key will cancel the desired edit.
TEST START Key (SERVICE)
Pressing this key while viewing any screen in the SERVICE Mode menu will start the service test. When viewing status, setup, setpoint, and diagnostics screens, it has no function.
CUSTOM Key
The Custom menu is a status menu that can be customized to contain frequently used screens. The Custom menu can only contain five status screens. To create the Custom menu, press the STATUS key, followed by the NEXT key (this brings up the initial status screen). Press the NEXT key until a screen appears that you would like to add to the CUSTOM menu. To add a screen to the Custom menu, press the + (Plus) key. Once the Custom menu is programmed, access it by pressing the CUSTOM key. To remove a status screen from the Custom menu, press the CUSTOM key. Press the NEXT key until the screen you want to remove appears. Press the - (Minus) key to remove the screen.
Unit Operation Keys
AUTO Key
Pressing the AUTO key at any time will
10 PKG-SVP01B-EN
Figure P-GI-2. Human interface keypad.
General InformationProgramming
General Status Display
Anytime the self-contained unit is powered up or when the STATUS, AUTO, or STOP keys are pressed, the unit mounted HI will display one of four general status display screens. This will allow the user to navigate through a set of menus and submenus to provide or access various monitoring, setup, and configuration information. The HI will not display screens that the unit is not configured for.
1. Unit “Off” or “Stopped”
If at power up the unit is not running, the following display will appear. When this screen displays, the only functional keys are the menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, and SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Top Level State
(Unit Off) (Unit Stopped) (External Stop) (Emergency Stop) (Unit Starting) (Service Mode On)
___________________ ____________ _____________
Function in Operation
(Blank) (Shutdown) (Check Config) (Invalid Cfg)
Trouble Indicator
(Blank) (Diagnostics)
2. Unit On
If the unit has entered an operating state (running), the following display will appear. When this screen displays, the only functional keys are the menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, AND SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Function in Operation
O/A Flow (CCFM) Unoccupied (Blank if supply fan off or no VCM)
Unit Type
(CV) (VAV)
VAV OA Flow
___________ _______ ____________
Mode of Operation
(Occupied) (Daytime WU) (Morning WU) (Standby) (Unoccupied) (Shutdown) (Initializing) (Blank)
PKG-SVP01B-EN 11
___
Function Stage
(Heat) (Cool) (O/A Dmpr) (Blank)
CFM
Range
0-600
Supply Fan
Trouble Indicator
(Blank) (Diagnostics Present)
____
Fan Mode
(On) (Off)
General
_____________
InformationProgramming
3. VOM Active
If at power up the unit is running following display will appear on the human interface LCD screen.
and has entered a ventilation override mode, the
VO Mode in Operation
(A, B, C, D, E)
Ventilation Override Mode
4. No Configuration
If at power-up the unit has not been programmed with the necessary configuration data for normal unit operation, the following display will appear at the human interface LCD screen. When this screen displays, the only functional key is the CONFIGURA­TION key.
Note: This screen will only appear when the RTM has been field replaced. Refer to the Configuration Menu section on page 63.
______
Trouble Indicator
(Blank) (Diagnostics)
12 PKG-SVP01B-EN
General InformationProgramming
Factory Presets
The UCM controlled unit has many operating functions that are preset at the factory, but may be modified to meet the specific job requirements. Tables P-GI-2, P-GI-3, P-GI-4, and P-GI-5 identify each adjustable unit function and the value assigned to it. The tables also provide a
Table P-GI-2. Control Parameters Setup.
Default system mode Auto 32
Demand limit definition for cooling None 33
Demand limit definition for heating None 34
Economizer minimum position (without IGV or VFD)* 15% 59
Economizer minimum position with IGV @ 0%* 15% 59
Economizer minimum position with IGV @ 100%* 10% 59
Morning warmup type Full 33
Power-up start time delay 0 seconds 34
Supply air low limit* 50 F 59
Supply air temperature deadband for cooling* 8 F 59
Supply air temperature deadband for heating* 4 F 57
Supply air temperature O/A reset start temp cooling 90 F 35
Supply air temperature O/A reset end temp cooling 70 F 35
Supply air temperature O/A reset start temp heating 10 F 36
Supply air temperature O/A reset end temp heating 60 F 36
Supply air temperature reset type cooling none 34
Supply air temperature reset type heating none 35
Supply air temperature zone reset start temp cooling 72 F 35
Supply air temperature zone reset end temp cooling 69 F 35
Supply air temperature zone reset start temp heating 65 F 36
Supply air temperature zone reset end temp heating 68 F 36
Supply air temperature reset maximum amount cooling 5 F 35
Supply air temperature reset maximum amount heating 10 F 36
Unit Address 1 32
Unit Control Local 32
Note: Press the SETUP or SETPOINTS* key to adjust.
space for recording field modifications. If these factory presets match your application requirements, simply press the AUTO key on the HI to begin unit operation (after completing the Pre-Start and Start-Up procedures in the appropri­ate Installation, Owner, and Diagnostic manual). If your application requires
page beside the function, press the designated function menu key, then press and hold the NEXT or PREVIOUS key until its screen appears. Once the proper screen appears, simply follow the programming instructions given below the applicable screen in this manual.
different settings, turn to the referenced
Factory Preset Changed to: Reference Page #
PKG-SVP01B-EN 13
General InformationProgramming
Use Table P-GI-3 to reference factory default setpoints and keep track of setpoint adjustments at start-up. Make necessary adjust­ments using the setpoint key on the HI.
Table P-GI-3. Default Setpoint Setups.
Factory Preset Changed to: Reference Page #
Daytime warmup - initiate 67 F 57
Daytime warmup - terminate 71 F 57
Low ambient compressor lockout (std. units) 50 F 60
Supply air temp - cooling 55 F 57
Supply air temp - heating 100 F 57
Unoccupied zone temp - cool 85 F 58
Unoccupied zone temp - heat 60 F 58
Unoccupied zone temp - MWU 72 F 58
Use Table P-GI-4 to reference function setups and keep track of start-up adjustments. Make necessary adjustments using the setup key on the HI.
Table P-GI-4. Function (Enable/Disable) Setups.
Factory Preset Changed to: Reference Page #
Compressor lead/lag Disable 34
Daytime warmup Disable 32
Morning warmup Enable 33
Supply air tempering Disable 33
Unoccupied economizer Enable 37
Unoccupied heating Enable 33
Unoccupied mechanical cooling Enable 33
14 PKG-SVP01B-EN
General InformationProgramming
Use Table P-GI-5 to reference module factory setups and keep track of setpoint adjustments. Make necessary adjustments using the setup key on the HI.
Table P-GI-5. Module Defaults.
Factory Preset Changed to: Reference Page #
GBAS input/output assignments
GBAS input/output not assigned 46
Information format
Text displays English 32
Unit displays English 32
Reference Enthalpy 25 btu/lb. 59
RTM alarm output assignments any active diagnostic 47
Sensor source selection for:
Daytime warmup RTM zone temp 40
Monitor Specified Temp. Input RTM zone temp 42
Morning warmup RTM zone temp 41
Unoccupied zone control RTM zone temp 41
Zone reset RTM aux temp 41
Setpoint source selection for:
Cooling supply air temp default 60
Heating supply air temp default 61
Morning warmup default 62
Unoccupied zone cooling default 61
Unoccupied zone heating default 61
Actuator setup:
Direct/reverse action direct acting 51-55
Max stroke time 150 seconds 51-55
Max voltage 10 VDC 51-55
Min voltage 2 VDC 51-55
Coil frost cutout temperature 30 F 34
Condenser temperature control band:
Temporary low limit suppression 10 F 39-40
Upper limit 120 F 39-40
Low limit 80 F 39-40
Condenser temperature:
Efficiency check point 105 F 40
Low ambient control point 90 F 40
Control algorithm tuning parameters N/A 56
Max IGV position occupied 100% 37
Temperature input offset for:
Heat morning warmup 0 F 48
Return air 0 F 48
RTM zone temperature 0 F 48
RTM aux. temperature 0 F 48
Outdoor air 0 F 48
Ventilation override definition N/A 43-45
PKG-SVP01B-EN 15
General InformationProgramming
Password Protected Screens
Some of the operating displays on the human interface LCD screen are in­tended for access by qualified users only, and require a password to change. The following screens display the various programming sections that require a password to view or modify preset operating parameters. The password for each screen is a different series of + (Plus) or - (Minus) key strokes in a predefined sequence. Following are the password protected screens and pass­words to access them.
The following screen will appear if the PASSWORD is not entered within approxi­mately 15 seconds.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen displays.
Configuration is Password Protected Please Enter Password: ___________
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen displays.
Ventilation Override Mode _________ Enter Pass word To Lock D e finition:
1. Press the + or - keys in this sequence ( + - - + ) to lock each VO mode.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
Diagnos tic R e s e t is Pas s word Protected Please Enter Password: ___________
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
16 PKG-SVP01B-EN
Diagnostic Log is Password Protected Please Enter Password: ___________
1. Press the + or - keys in this sequence ( - + + -) to access this restricted screen.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
Programming
OCCUPIED OA DMPR 0% DIAGNOSTICS
RTM Supply Airflow Proving: FLOW
Active Supply Air Pressure 2.0 IWC
Active Supply Air Pressure 2.0 IWC
WSM Water Pump Re la y Status: OFF
Active Wa ter Flow Indication Flow
STATUS
STATUS Menu
The STATUS menu allows the user to view various setpoints, operating conditions (such as temperature and humidity levels), and unit component status (such as fan, compressor, heater, and economizer operation).
STATUS screens in this section are examples only. Pressing the + (Plus) key while viewing any of the status display screens will add that screen to the CUSTOM menu. When a status screen displays for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the STATUS key again to return to the status menu. Following are sample status screens that can be viewed by pressing the STATUS key.
Note: Some of the screens in this section may not be visible on your HI since they are applicable only for particular unit options.
Press the STATUS key to enter into the status menu. The STATUS MODE”will automatically return to the power-up screen after 30 minutes, if no keys are pressed.
Note: The range for all temperature inputs is –40 to 200 F. “ERR” will appear if the temperature is out of range.
STATUS Menu Screens
VAV OA FLOW 350 .0 C C FM SUPPLY FAN ON
1. Pressing the NEXT key will display the following screen.
General System Status Submenu
Pres s ENTER to View Da ta in This Subme nu
1. Pressing the NEXT key will bypass this section.
RTM Supply Fan Re la y : OFF
Possible values: Fan = On, Off
Airflow = Flow, No Flow
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus.
4. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD only)
IGV/VFD Cmd 30 %
Possible values: Increasing to 0-100%
(On units without IGV or VFD only)
Decreasing 100 to 0%
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Possible values: Pump Status = Off, On
Waterflow = Flow, No flow
1. Pressing the NEXT key will display the following screen.
17
Programming
Stage 1 OFF Stage 2 OFF Stage 3 OFF
OA Flow 35 0 .0 C C FM OA D a m pe r Pos 0 %
C02 Level 1512 PPM OA Damper Pos 0 %
Pres s ENTER to View Da ta in This Subme nu
(On units with electric heat only)
Electric Heat ENABLED
Possible values: Off, On
Note: Two or three-stage electric heat is a field-provided option.
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
Hydronic Heat ENABLED 0 %
Low Air Temp Limit OK
Possible values: Hydronic Heat = Enabled, Disabled
Valve position = 0-100% open Low temp air = OK , tripped
1. Pressing the NEXT key will display the following screen.
(On units with VCM module or Traq™ damper option only)
Active Min OA Flow Setpoint 342.0 CC FM
STATUS
Possible values: Unit Airflow = 0 to maximum unit airflow
1. Pressing the NEXT key will display the following screen.
(On units with VCM module and CO2 reset enabled)
Active Min OA Flow Setpoint 342.0 C C FM
Possible values: Unit Airflow = 0 to maximum unit airflow
1. Pressing the NEXT key will display the following screen.
(On units with VCM module and preheat enabled)
OA Preheat Output Control: ON
Possible values: On, Off
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Co mpre ss o r Sta tu s Sub me n u
18
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Compress or Rela y K 1 1 OFF
Enabled
Possible values: K11 = Off, On, Locked, Disabled, Enabled Disabled by: Compressor Protection Frost Protection
Contactor Failure Tracer Summit® Lockout Low Pressure Cutout Minimum Off Time Bad Cond Temp Sensor Low Ambient Lockout Demand Limit Ventilation Override Low Ent Cond water Temp
1. Pressing the NEXT key will display the following screen.
(On units with manifolded refrigerant circuits)
Compress or Rela y K 1 2 OFF
Enabled
Possible values: K11 = Off, On, Locked, Disabled, Enabled
Note: On models SCWF/SIWF and SCRF/SIRF units, K12 is the “B” compressor on units with manifolded refrigerant circuits and “C” compressor on all units with independent refrigerant circuits. Check unit model number, digit 5 to determine which type circuit the unit has.
STATUS
1. Pressing the NEXT key will display the following screen.
(On units with independent refrigerant circuits)
Compress or Rela y K 3 OFF
Enabled
Possible values: K3 = Off, On, Locked, Disabled, Enabled
Note: On models SCWF/SIWF, 35-80 tons, K3 is the “B” compressor.
1. Pressing the NEXT key will display the following screen.
(On model SCWF/SIWF, 60-80 ton units)
Compress or Rela y K 4 OFF
Enabled
Possible values: K4 = Off, On, Locked, Disabled, Enabled Disabled by: Compressor Protection Frost Protection
Contactor Failure Tracer Summit® Lockout Low Pressure Cutout Minimum Off Time Bad Cond Temp Sensor Low Ambient Lockout Demand Limit Ventilation Override Low Ent Cond Water Temp
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
19
Programming
Low Ambie nt Com p Loc k out Tem p: 32 F
Low Water Temp Com press or Lockout 34 F
Evap Tem p 7 5 .0 F Sat Cond Te m p 8 1 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Pres s ENTER to View Da ta in This Subme nu
Active Outside A ir Tempe rature 86.0 F
Possible values: Lockout Temperature = -20-80 F
1. Pressing the NEXT key will display the following screen.
On units all water-cooled units only)
(
WSM Ent Cond Wa ter Temp Input 65 .2 F
Possible values: Lockout Temperature = 0-99 F
1. Pressing the NEXT key will display the following screen.
Compressor Module Ckt 1
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 2
STATUS
1. Pressing the NEXT key will display the following screen.
(
On all SCWF/SIWF 35-80 ton units only)
Compress or Module Ckt 3
1.Pressing the NEXT key will display the following screen.
(
On all SCWF/SIWF 60-80 ton units only)
Compress or Module Ckt 4
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside or airside economizer only)
Eco n o mizer Statu s Subme n u
20
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Outside Air Dam pe r Pos: 10 %
WSM Entering Water Temperature: 60 F
Water Econ Bypas s Pos: 10 %
Outside Air Dam pe r Pos: 0 %
ECEM Return Air Enthalpy 34.0 B TU /LB
ECEM Return Air Tempe rature 78.0 F
(
On units with a waterside economizer only)
Water Economizing: DISABLED
Possible values: Economizer = Disable, Enable
Water econ position = opening to/closing to 0-100%
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside economizer or condenser only)
WSM Mixe d A i r Tempe rature: 68 F
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside economizer and condenser only)
Possible values: Water econ position = opening to/closing to 0-100%
1. Pressing the NEXT key will display the following screen.
STATUS
On units with an airside economizer only)
(
Air Economizing: DISABLED
Possible values: Economizer = Disable, Enable
Outside air = opening to/closing to 0-100%
1. Press the NEXT key until the following screen is displayed.
On units with an airside economizer and comparative enthalpy only)
(
Active Outside A ir Enthalpy 12.0 B TU/LB
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible values:
On units with an airside economizer only)
(
Active Outside A ir Tempe rature 86.0 F
10-99 BTU/LB
PKG-SVP01B-EN
21
Programming
ECEM Return Air Humidity 6 2 %
Controlling Setpoint Status Submenu
Pres s ENTER to View Da ta in This Subme nu
HI (KEYPAD) SETPOINT MENU Is 5 5 F
HI (KEYPAD) SETPOINT MENU Is 1 0 0 F
Initiate: 67 F is Te rminate: 71 F
(
On units with an airside economizer only)
Active Outside A ir Humidity 3 0 %
STATUS
Possible values:
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
(On all VAV units only)
Active Supply Air Cooling STP From
Possible Values: HI (Keypad) Setpoint Menu
1. Pressing the NEXT key will display the following screen.
0-100%
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
22
(On all VAV units with hydronic heat only)
Active Su p p l y A i r H ea ti n g ST P F rom
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit
(On all VAV units with hydronic, electric, or external heat only)
Active Daytime Warmup Setpoints
Possible Values: HI (Keypad) Setpoint Menu
®
)
PKG-SVP01B-EN
Programming
RTM ZONE TEMP INPUT is 7 4 F
RTM ZONE TEMP INPUT is 1 0 0 F
RTM ZONE TEMP INPUT is 8 5 F
RTM ZONE TEMP INPUT is 6 0 F
Active Oc c upied Zone C ooling STP From
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat with daytime warmup enabled only)
Active Oc c upied Zone H e a ting STP From
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
STATUS
Active U noc c upied Zone C o oling STP From
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Active U nocc upie d Zone H e a ting STP From
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
Setpoint Range: 50-90 F
PKG-SVP01B-EN
23
Programming
HI (KEYPAD) SETPOINT MENU is 7 2 F
REMOTE MIN POS POT INPUT 342 .0 C FM
HI (KEYPAD SETPOINT MENU is 2 .0 IWC
High Limit: 40 IWC D e a dba nd: 0.5 IWC
Controlling Sens or Status Submenu
Pres s ENTER to View Da ta in This Subme nu
(On units with hydronic, electric, or external heat only)
Active Morning Warmup Setpoint From
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module ICS (Tracer Summit®)
Setpoint Range: 50-90 F
1. Pressing the NEXT key will display the following screen.
(On units with VCM module only)
Active Min OA Flow Setpoint From
Possible Values: HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
Setpoint Range: 0 to max unit airflow
1. Pressing the NEXT key will display the following screen.
STATUS
(On units with IGV or VFD only)
Active Supply Air Pressure STP From
Possible Values: HI (Keypad) Setpoint Menu
GBAS Module
1. Pressing the NEXT key will display the following screen.
On units with IGV or VFD only)
Active Supply Air Pressure Setpoints
Possible Values: High Limit = 1.6-4.7 IWC
Deadband = 0.1-2.0 IWC
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
24
PKG-SVP01B-EN
Programming
RTM ZONE TEMP INPUT is 5 0 .0 F
RTM ZONE TEMP INPUT is 8 2 .0 F
HI (KEYPAD) SETPOINT MENU Is 9 0 F
RTM ZONE TEMP INPUT is 7 5 .0 F
Active Supply A ir Temp Sens or Input From
Possible Values: RTM Supply Air Temp Input
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Active D a y time WU Te m p Sens or Input From
Possible Values: RTM Zone Temp Input
Sensor Range: -40 to 200 F
1. Pressing the NEXT key will display the following screen.
ICS (Tracer Summit®)
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM return Air Temp Input ICS (Tracer Summit®)
STATUS
(On units with hydronic, electric, or external heat with DWU installed only)
Active Oc c upied Zone Te m p Sens or Input From
Possible Values: RTM Zone Temp Input
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM return Air Temp Input ICS (Tracer Summit®)
Sensor Range: -40 to 200 F
1. Pressing the NEXT key will display the following screen.
Active U noc c Zone Te m p Sens or Input From
Possible Values: RTM Zone Temp Input
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM return Air Temp Input ICS (Tracer Summit®)
Sensor Range: -40 to 200 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat with MWU enabled only)
PKG-SVP01B-EN
25
Programming
Active Morning WU Temp Sens or Input From
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values: RTM Zone Temp Input
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM return Air Temp Input ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Sensor Range: -40 to 200 F
Active Zone R e s e t Sensor Input From
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values: RTM Zone Temp Input
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input ICS (Tracer Summit
Sensor Range: -40 to 200 F
STATUS
®
)
Active OA Te m pe rature Sensor Input From RTM OUTSIDE AIR TEMP INPUT is 86 .0 F
Possible Values: RTM Outside Air Temp Input
ICS (Tracer Summit
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Active Outside A ir Humidity Input From
OA HU MIDITY SENSOR INPUT is 3 0 %
Possible Values: O/A Humidity Sensor Input
ICS (Tracer Summit®)
Sensor Range: 0-100%
1. Pressing the NEXT key will display the following screen.
(On units with IGV, VFD, or with the SAP sensor enabled)
Active Supply A ir Pres s Sens or Input From
RTM SA PRESSUR E INPUT is 2 .1 IWC
Possible Values: RTM SA Pressure Input
1. Pressing the NEXT key will display the following screen.
ICS (Tracer Summit®)
®
)
26
PKG-SVP01B-EN
Programming
Temp Sens or Input Being Monitored:
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values: RTM Zone Temp Input
NSB Zone Sensor Setpoint Input RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input ICS (Tracer Summit®) No sensor selected
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Sensor Range: -40 to 200 F
End o f Su b me n u (N EXT ) to En ter SETU P
Tempe rature Input Status Subme nu
Pres s ENTER to View Da ta in This Subme nu
STATUS
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM ZONE TEMP INPUT 8 2 .0 F
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM SUPPLY AIR TEMP INPUT 50.0 F
1. Pressing the NEXT key will display the following screen.
(On units with a NSB zone sensor installed)
Temp Measured By Sensor Connected To
NSB Panel Te m p Sens or Input 79.5 F
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM AUX TEMP INPUT 62.0 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Temp Measured By Sensor Connected To
RTM OUTSIDE AIR TEMP INPUT 86.0 F
1. Pressing the NEXT key will display the following screen.
27
Programming
(On units with hydronic, electric, or external heat only)
Temp Mea s ured By Sens or Connec ted To
HEAT MODULE AU X TEMP INPUT 82.0 F
1. Pressing the NEXT key will display the following screen.
(On units with a VCM and OA preheater enabled)
Temp Mea s ured By Sens or Connec ted To
ECEM RETURN AIR TEMP INPUT 78.0 F
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM ENT WA TER TEMP INPUT 60.1 F
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM MIXED AIR TEMP INPUT 51 .7 F
STATUS
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM ENT C ON D WA TER TEMP INPUT 64.9 F
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and O/A preheater enabled)
Temp Mea s ured By Sens or Connec ted To
VCM MODULE AUX TEMP INPUT 5 0 .0 F
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 1
Evap Tem p 7 5 .0 Sat Cond Te m p 8 1 .0 F
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 2
Evap Tem p 7 2 .0 Sat Cond Te m p 8 7 .0 F
1. Pressing the NEXT key will display the following screen.
28
PKG-SVP01B-EN
Programming
(On models SCWF/SIWF 42-80 tons or SCRF/SIRF 50-60 tons only)
Compressor Module Ckt 3
Evap Tem p 7 2 .0 Sat Cond Tem p 87.0 F
1. Pressing the NEXT key will display the following screen.
(On models SCWF/SIWF 65-80 tons only)
Compressor Module Ckt 4
Evap Tem p 7 2 .0 Sat Cond Tem p 87.0 F
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Misc Input Status Submenu
Pres s ENTER to View Da ta in This Subme nu
STATUS
1. Pressing the NEXT key will display the following screen.
RTM Supply Airflow Proving Input: FLOW
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values: Flow, No Flow
(On units when minimum position pot is assigned to function)
RTM Rem ote Min Position Pot Input 0 %
Possible Values: 0-100%
(On units with IGV or VFD, or units without IGV or VFD and supply air pressure is present)
RTM Supply Air Press ure Input 2.1 IWC
(On units with an airside economizer only)
Active Outside A ir Humidity 3 0 %
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
Possible Values: 0-100%
29
Programming
(On units with an airside economizer and comparative enthalpy only)
Active Outside A ir Humidity 3 0 %
ECEM Return Air Humidity 6 2 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
VCM Outside Air Flow Input 350.0 C C FM
Possible Values: 0 to max unit airflow.
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
VCM CO2 Lev e l Input 1512 PPM
STATUS
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values: 0-2000 PPM
(On water-cooled units with a water flow switch installed)
WSM Water Flow Switch Input Flow
Possible Values: Flow, No Flow
End of Subm en u (NEXT) to Enter SETUP
(On units with GBAS module)
GBAS 0 - 5VDC Module Status Submenu
Pres s ENTER to View Da ta in This Subme nu
30
PKG-SVP01B-EN
Programming
(On units with GBAS module)
GBAS 0 - 5VDC Module Input 1 0 .0 0 VDC
Ass ignm e nt: Not Ass igne d
Possible Values: The inputs 1, 2, 3, and 4 may be assigned to:
Occ Zone Cooling Setpoint Occ Zone Heating Setpoint Unocc Zone Cooling Setpoint Unocc Zone Heating Setpoint Space Static Pressure Setpoint Supply Air Static Pressure Setpoint Min O/A Flow Setpoint
1. Press the NEXT key to display GBAS 0-5 VDC inputs 2, 3, and 4.
2. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Demand Limit Input Status
OPEN
Possible Values: Open, Closed
1. Pressing the NEXT key will display the following screen.
Not Assigned
STATUS
(On units with GBAS module)
GBAS (0 - 5VDC) Module Re la y Output Status
Output 1 OFF
Possible Values: Open, Closed
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
31
SETUP Menu
The setup menu allows the user to input unit control parameters; i.e., setpoint source selection, sensor source selec­tions, ventilation override definitions, functions enable/disable, status, text display (language), temperature display (C or F), and system tuning parameters. When a setup screen displays for 30 minutes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press the SETUP key again to return to the setup menu.
Note: Some of the screens in this section may not be visible on your HI since they are applicable only for specific unit options.
Press the SETUP key to begin viewing or modifying the SETUP screens. Follow this procedure when viewing a screen that requires modification:
1. Press the + or - key until the proper value displays.
2. Press the ENTER key to confirm your choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 if there are additional values on the same screen that require changing.
Programming
SETUP
SETUP Menu Screens
Press the SETUP key to display the following screen(s).
Displa y Te x t in: ENGLISH LANGUA GE
Displa y U nits U s ing: ENGLISH NOTA TION
Factory Presets: Text and Units = English Possible Values: Text = English, French, Spanish
Units = English, SI
1. Pressing the NEXT key will display the following screen.
(On units with a TCI module)
Unit Control: LOCA L
Unit Address: 31
Factory Presets: Control = Local
Address = 1
Possible Values: Unit Control = Local, ICS (Tracer Summit®)
Unit Address = 0-31
1. Pressing the NEXT key will display the following screen.
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with VFD and bypass)
Supply Fan VFD Mode: BYPASS
Factory Presets: Mode = Normal
Address = 1
Possible Values: Mode = Normal, Bypass
1. Pressing the NEXT key will display the following screen.
If Remote Pane l Mode Input Not Present:
System Mode: AUTO
1. Pressing the NEXT key will display the following screen.
1.Pressing the NEXT key will display the following screen.
32
Possible Values: System Mode = Off, Auto
Day time Wa rmup Function: DISABLED
Factory Preset: Disabled Possible Values: Daytime Warmup Function = Enabled, Disabled
PKG-SVP01B-EN
Programming
(On units with hydronic or electric heat)
Morning Warmup Function: ENABLED
Morning Warmup Type : FULL C A PA CI TY
Factory Presets: Function = Enabled
MWU Type = Full Capacity
Possible Values: Function = Enabled, Disabled
MWU Type = Full Capacity, Cycling Capacity
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Supply Air Tempering Function: DISABLED Warm Up Outside A ir Use d for Ventilation
Factory Presets: Function = Disabled
1. Pressing the NEXT key will display the following screen.
Possible Values: Function = Enabled, Disabled
(On cooling-only units)
Unocc Mech Cooling Function: ENABLED
SETUP
Factory Presets: Function = Enabled Possible Values: Function = Enabled, Disabled
OR
(On units with hydronic, electric, or external heat)
Unocc Mech Cooling Function: ENABLED
Unocc Heating Function: ENABLED
Factory Presets: Cooling and Heating Function = Enabled Possible Values: Cooling and Heating Function = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Preheater Output Control : ENABLED
Activa te If Preheat Temp B e low Setpoint
Factory Presets: Control = Enabled Possible Values: Control = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
Dem a nd Lim it De finition:
Cooling: 100 %
Factory Presets: None
1. Pressing the NEXT key will display the following screen.
Possible Values: Cooling = None, 50%, or 100%
PKG-SVP01B-EN
33
Programming
(On units with hydronic or electric heat)
Dem a nd Lim it De finition:
Cooling: 100 % H e a ting: 100 %
Factory Presets: None Possible Values: Cooling /Heating = None, 50%, or 100%
1. Pressing the NEXT key will display the following screen.
Compress or Lead/La g Func tion: DISABLED Vary Sta ging Order to Distribute Runtim e
Factory Presets: Function = Disabled
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values: Function = Disabled, Enabled
Reduc e Multi-Unit Startup Power D emand
After Power-Up, Dela y U nit Start: 0 Sec
Factory Presets: Start = 0 Seconds Possible Values: Start = 0-255 Seconds
SETUP
Coil Frost Cutout Temperature: Shut Off Compress ors If Evap Tem p Is B e low: 30 F
Factory Presets: Temp = 30 F Possible Values: Temp = 25-35 F
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
VAV Control Functions Subme nu
Pres s ENTER to Re v ie w or Adjust
1. Pressing the NEXT key will display the following screen.
(On units without heat)
Supply Air Temp Reset Type:
Cooling: ZONE
Factory Presets: None Possible Values: Cooling = None, Zone, OA
1. Pressing the NEXT key will display the following screen.
34
PKG-SVP01B-EN
Programming
Maximum A m ount of Res e t Applie d: 5 F
Maximum A m ount of Res e t Applie d: 5 F
(On units with hydronic heat)
Supply Air Temp Re s e t Type :
Cooling: ZONE Hea ting: ZONE
Factory Presets: None
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values: Cooling/Heating = None, Zone, OA
(On units when zone cooling reset is selected)
Supply Air Temp Zone
Start Temp: 72 F End Te m p: 69 F
Possible Values: Cooling/Heating = Zone, OA
Res e t For Cooling:
Start Temp Zone = 209 OA = 70 End Temp Zone = 210 OA = 71
SETUP
Supply Air Temp Outside Air
Start Temp: 90 F End Tem p: 70 F
Possible Values: Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70 End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Zone
Possible Values: SAT = Zone, OA
Reset (Zone) = 72 Reset (OA) = 72
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Outside Air
Possible Values: SAT = Zone, OA
Reset Zone = 72 Reset OA = 72
1. Pressing the NEXT key will display the following screen.
Reset For Cooling:
Res e t For Cooling:
Res e t For Cooling:
PKG-SVP01B-EN
35
Programming
Start Temp: 10 F End Tem p: 60 F
Start Temp: 65 F End Tem p: 68 F
(On units with outside air heating reset selected)
Supply Air Temp Outside A ir
Factory Presets: Start = 10 F, End = 60 F Possible Values: Start OA Temp = 73
End OA Temp = 74
1. Pressing the NEXT key will display the following screen.
(On units with zone air heating reset selected)
Supply Air Temp Zone
Factory Presets: Start = 65 F, End = 68 F Possible Values: Start OA Temp = 211
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp OA R e s e t For Heating:
Maximum A m ount of Res et Applie d: 1 0 F
Reset For Heating:
End OA Temp = 212
SETUP
Res e t For Heating:
Possible Values: SAT Temp = Zone, OA
Zone Reset = 75 OA Reset = 75
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp ZONE Reset For Heating:
Maximum A m ount of Res et Applie d: 1 0 F
Possible Values: SAT Temp = Zone, OA
Zone Reset = 75 OA Reset = 75
1. Pressing the NEXT key will display the following screen.
VAV Box Max Stroke Time: 0 Min
Factory Presets: 6 Min
1. Pressing the NEXT key will display the following screen.
Possible Values: 0-10
36
PKG-SVP01B-EN
Programming SETUP
(On units with IGV or VFD)
Max Occ upie d IGV/VFD Com m a nd: 100 %
Factory Presets: 100%
1. Pressing the NEXT key will display the following screen.
1.Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values: 0-100%
End o f Su b me n u (N EXT ) to En ter SETU P
(On units with an airside or waterside economizer)
Economizer Control Functions Subme nu
Pres s ENTER to Re v ie w or Adjust
(On units with an airside and waterside economizer)
Economizer Priority
Choose Whic h Econom izer Stages Up First
Possible Values: Waterside Econ, Airside Econ
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Unocc Water Economizer Function: ENABLED
Factory Presets: Enabled Possible Values: Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Unocc Air Economizer Function: ENABLED
Factory Presets: Enabled Possible Values: Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Disable WS Econ If Difference Between MA
Temp and Ent Water Temp Less Than 4.0 F
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
37
Programming
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water Flow Control Setup Submenu
Pres s ENTER to Re v ie w or Adjust
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Periodic Water Purge Function: ENABLED
Interval: 1 Hr Duration: 1 Min
Possible Values: Enabled, Disabled
Interval = 1-999 Hrs Duration = 1-9 Min
1. Pressing the NEXT key will display the following screen.
SETUP
(On all water-cooled units and all units with a waterside economizer)
Water-Flow Init Time D e la y : 1 Min
Time To Establis h Wa ter Flow Before Diag
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Temp Stablization Time D e la y : 1 Min
Water Flow Time For Valid Temp Re a dings
Possible Values: 0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Head Pressure Control Inactive Min: 1 0 %
Hea d Pressure Control Active Min: 30 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
38
PKG-SVP01B-EN
Programming
(On units with waterside economizer)
Water Economizer Min Position: 10 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On water-cooled units with waterside economizer)
Select Water Flow Control Required For
Water Pump System: Variable/Minimize
Possible Values: Constant/Maximize
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Hea d Pre ss u re Ctrl Se tu p Su b me n u
Press ENTER to Review or Adjust
Variable/Minimize
SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Cond Tem p C ontrol Point: 90 F
Possible Values: 80-100 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Pres et Va l u e to Mi n i f Con d W ate r B elo w Hea d Press Value Preset Tem p Lim it: 90 F
Possible Values: 0-99 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Tem p C ontrol Band Lower Limit: 80 F Upper Limit: 120 F
Factory Presets: Lower = 80 F
Upper = 120 F
Possible Values: Lower = 70-90 F
Upper = 110-130 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
39
Programming
(On all air-cooled units)
Cond Tem p C ontrol Band Temporary Low Limit Suppression: 10 F
Factory Presets: 10 F Possible Values: 0-20 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp Efficiency Check Point: 105 F
Factory Presets: 105 F Possible Values: 95-115 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp Low Ambie nt Control Point: 90 F
SETUP
Factory Presets: 90 F Possible Values: 80-100 F
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Sensor Source Selections Submenu
Sensor Source Sele c tions Subme nu Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with electric, hydronic, or external heat and supply air temperature control)
For Daytime Wa rmup Tem p C trl, Use Sens or Connec ted To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
40
PKG-SVP01B-EN
Programming
(On all units except those with supply air temperature control without IGV or VFD)
For Occupied Zone Te m p C trl, Use Sensor Connec ted To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Unoccupied Zone Tem p C trl, Use Sens or Connec ted To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
SETUP
(
On units with electric, hydronic, or external heat only)
For Morning Warmup Temp Ctrl, Use Sensor Connec ted To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Zone Reset Function, Use Sensor Connec ted To: RTM ZONE TEMP INPUT
Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
41
Programming
(On units with Traq™ dampers only)
For Outside Air Preheat Ctrl, Use Sensor Connec ted To: VCM MODULE AUX TEMP INPUT
Possible Values: VCM Module Aux Temp Input
WSM Mixed Air Temp Input
1. Pressing the NEXT key will display the following screen.
Monitor Specific Tem p Input, Us e Sensor Connec ted To: RTM ZONE TEMP INPUT
Factory Presets: RTM Zone Temp Input Possible Values: RTM Zone Temp Input
NSB Zone Sensor RTM Aux Temp Input Heat Module Aux Temp Input ECEM Return Air Temp Input No Sensor Selected
1. Pressing the NEXT key will display the following screen.
SETUP
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Outside Air Ventilation Setup
(On units with a VCM or airside economizer)
Outside Air Ventilation Setup Subm e nu Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer and IGV or VFD)
OA Flow Com pe ns a tion Function: DISABLED Use Fix e d OA D a m pe r Minimum Position
Possible Values: Enabled, Disabled Enabled 2nd line = OA Damper Min Pos Depends on IGV/VFD Pos Disabled 2nd line = Use Fixed OA Damper Minimum Position
1. Pressing the NEXT key will display the following screen.
42
PKG-SVP01B-EN
Programming SETUP
(On units with a VCM)
OA Flow CO2 Reset Function: ENABLED
Possible Values: Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
OA Flow CO2 Reset Function: ENABLED CO2 Start: 800 PPM CO2 Max: 1000 PPM
Possible Values: Enabled, Disabled
CO2 Start = 0-1900 PPM CO2 Max = 100-2000 PPM
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer with Traq™ damper)
TRAQ D a m pe r Quantity: 1 TRAQ D a m pe r Size: 28 Inches
Possible Values: Quantity = 1-12
Size = 0, 13, 16, 20, 24, or 28
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Flow Ca libration Data: Gain: 1.0 Offset: 0.0 CC FM
Factory Presets: Gain = 1.0
Offset = 0.0
Possible Values: Gain = 0.0-1.5
Offset = -25.0-25.0
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Ventilation Override Definitions
(On units with a VOM)
Ventilation Override D e finitions Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
43
Programming
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
(On units with a VOM and IGV or VFD)
Supply Fan ON
Factory Presets: Refer to definitions on page 5. Possible Values: On, Off
1. Pressing the NEXT key will display the following screen.
(On units with a VOM and airside or waterside economizer)
Outside Air Dam pe rs OPEN
Factory Presets: Refer to definitions on page 5. Possible Values: Open, Closed
1. Pressing the NEXT key will display the following screen.
(On units with a VOM and electric or hydronic heat)
Hea t OFF
Factory Presets: Refer to definitions on page 5. Possible Values: Off, In Control
1. Pressing the NEXT key will display the following screen.
SETUP
(On units with a VOM)
VAV Box Re la y D EENERGIZED
Factory Presets: Refer to definitions on page 5. Possible Values: Energized, Deenergized
1. Pressing the NEXT key will display the following screen.
(On units with a VOM installed and OA preheater function enabled)
OA Preheater State IN C ON TR OL
Factory Presets: Refer to definitions on page 5. Possible Values: In Control, Off
1. Pressing the NEXT key will display the following screen.
(On units with a VOM
VO Relay ENERGIZED
Factory Presets: Refer to definitions on page 5. Possible Values: Energized, Deenergized
1. Pressing the NEXT key will display the following screen.
)
44
PKG-SVP01B-EN
Programming
Ventilation Override D e finition Mode A
Ventilation Override Mode A Is Loc k e d
GBAS 0 - 5VDC Module I/O A s s ignm e nts
SETUP
(On units with a VOM
Enter Pass word to Lock De finition:
Factory Presets: Refer to definitions on page 5. Possible Values: + (Plus), - (Minus)
1. Pressing the NEXT key will display the following screen.
Note: After lock a MODE (by entering the password), the display for that MODE becomes “reporting” only and the definition cannot be changed unless the VOM is replaced. After entering the password, press the NEXT key to scroll through the previous screens to confirm selected choices for each mode as follows below.
(On units with a VOM and VO mode locked)
Supply Fan
Factory Presets: Refer to definitions on page 5.
1. Pressing the NEXT key will display the following screen.
(On units with a VOM)
Ventilation Override Mode B Supply Fan
)
Follow the preceding steps used to program MODE A” to program MODES B,”C,”D, and “E” as needed.
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
GBAS Module I/O Assignments
(On units with a GBAS)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
45
Programming
GBAS (0 - 5VDC) Ana log Input 1 A s s ignm e nt
GBAS (0 - 5VDC) Output 1 Alarm Ass ignm e nts
(On units with a GBAS)
NOT ASSIGNED
Factory Presets: None Possible Values: Not Assigned, Occupied Zone
Cooling Setpoint, Unoccupied Zone Cooling Setpoint, Occupied Zone Heating Setpoint, Unoccupied Zone Heating Setpoint SA Static Pressure Setpoint SA Heating Setpoint SA Cooling Setpoint Min OA Flow Setpoint
1. Press the + or - key until the proper selection displays for the number 1 assignment.
2. Press the ENTER key to confirm this choice. Only one input definition can be assigned to each input and it cannot be duplicated.
3. Press the NEXT key to advance to the number 2 input assignment screen and repeat steps 1 and 2 for assignments 3 and 4.
4. Pressing the NEXT key will display the following screen.
(On units with a GBAS)
SETUP
Press ENTER to Review or Adjust
Factory Presets: Output 1 = Dirty Filters
Output 2 = Compressor Trip - Ckt 1, 2, 3, or 4
Low Pressure Control Open Low Pressure Control Open- Ckt 1, 2, 3, or 4 Contactor Fail
Contactor Fail - Ckt 1, 2, 3, or 4 Output 3 = Heat Fail Output 4 = Supply Fan Failure Output 5 = Any Active Diagnostic
Possible Values: Refer to the list of active diagnostics assigned to each of
the five output definitions in the Diagnositic Menu section on page 72. It also can be one of the VOM outputs: supply fan/VFD bypass enabled or high CO2.
1. Press the NEXT key to bypass this section.
2. Press the + or - key until the proper selection displays for the number 1 assignment. The plus key will assign all diagnostics and the minus key will allow diagnostic selection.
3. Press the ENTER key to confirm this choice. If yes” was assigned to the output assignment, the output 2 assignment screen will display. Repeat step 1 for each remaining output. If no” was assigned, only one output assignment can be assigned to each output assignment and it cannot be duplicated. Once the output diagnostics are defined, press the NEXT key to advance to the number 2 output assignment screen. Repeat steps 1 and 2.
4. Pressing the NEXT key will display the following screen.
Note: Assigning “yes” to a GBAS output definition means that if the assigned diagnostic is present, the out assigned to it will energize.
46
PKG-SVP01B-EN
Programming
RTM Alarm Output Diagnostic A s s ignm e nts
Ass ign D ia gnos tic to RTM Ala rm Output ?
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
SETUP
RTM Alarm Output Diagnostic Assignment Screens
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
Any A c tive D ia gnos tic (No)
Factory Presets: Any Active Diagnostic Possible Values: Refer to the list of active diagnostics that can be assigned
to each GBAS output definition in the Diagnostic Menu section on page 72.
1. Press the ENTER key, then the NEXT key to display the possible diagnostics that may be assigned to the RTM alarm output definition.
2. Press the + (plus) key to assign yes” to the output definition or - (minus) key to assign no” to the output definition.
3. Press the ENTER key to confirm each selection.
Note: Assigning “yes” to an alarm output definition means that if the assigned diagnostic is present, the RTM alarm output will energize.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
47
Programming
SETUP
Temperature Input Calibration
The following calibration and offset screens allow sensor calibration, when necessary.
For example, if using the MWU sensor and you detect a difference between the actual measured room temperature and the corresponding measured sensor value, the sensor needs calibration. Using the temperatuare input calibration screen for MWU heat, program the error amount into the Temperature Input Offset field to calibrate the sensor.
To change offset values on a particular screen:
1. Press the plus or minus key until the correct value appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve made an error, press the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, OR
a. if no further changes are required and
you want to exit back to view the unit operating status, press the STATUS key once, OR
b. if you want to remain in the tempera-
ture input calibration submenu, press the SETUP key once and it will return you to the beginning of that particular submenu, OR
c. if you want to exit to another submenu
in the SETUP menu, press the SETUP key twice. Then press the NEXT key to scroll through the SETUP submenu choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that key once, then press the NEXT key to scroll through those screens.
Temperature Input Calibration Screens
(Applicable to All Units)
Calibration and Offset Submenu
Pres s ENTER to Re v ie w or Adjust
1. Press the NEXT key to bypass this section or press the ENTER key to view the following screens.
Tempe rature Calibration Offset For
RTM Zone Tem pe rature Input 0.0 F
Factory Preset: 0.0 F Possible Values: Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
Tempe rature Calibration Offset For
RTM Aux Te m pe rature Input 0.0 F
Factory Preset: 0.0 F Possible Values: Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
Tempe rature Calibration Offset For
RTM Outside Air Tempe rature Input 0.0 F
Factory Preset: 0.0 F Possible Values: Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
(On units with electric or hydronic heat only)
Tempe rature Calibration Offset For
Hea t Module Aux Te m p Input 0.0 F
Factory Preset: 0.0 F Possible Values: Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
48
(On units with comparative enthalpy installed)
Tempe rature Calibration Offset For
ECEM Return Air Tempe rature Input 0.0 F
Factory Preset: 0.0 F Possible Values: Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Entering Water Temp Input 0.0 F
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Mixe d A ir Temp Input 0.0 F
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Ent Cond Water Temp Input 0.0 F
SETUP
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 1 Sat Cond Te m p Input 0.0 F
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 2 Sat Cond Te m p Input 0.0 F
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 3 Sat Cond Te m p Input 0.0 F
PKG-SVP01B-EN
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
49
Programming
(On all water-cooled units and/or units with a waterside economizer)
Tempe rature Calibration Offset For
Ckt 4 Sat Cond Te m p Input 0.0 F
Factory Preset: 0.0 F Possible Values: 0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (NEXT) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
SETUP
50
PKG-SVP01B-EN
Programming
Max Stroke Tim e 3 0 Sec
Max Voltage 10 .0 VDC
Direct/Rev e rse A c t DIR ECT A C TIN G
SETUP
Device Characteristic Setup Definitions
To change device characteristic values on a particular screen:
1. Press the plus or minus key until the correct value appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve made an error, press the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, OR
a. if no further changes are required and
you want to exit back to view the unit operating status, press the STATUS key once, OR
b. if you want to remain in the Device
Characteristic Setup Definitions submenu, press the SETUP key once and it will return you to the beginning of that particular submenu, OR
c. if you want to exit to another submenu
in the SETUP menu, press the SETUP key twice. Then press the NEXT key to scroll through the SETUP submenu choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that key once, then press the NEXT key to scroll through those screens.
Device Characteristic Setup Screens
(Applicable to units as noted)
Device Characteristics Setup Definitions
Pres s ENTER to Re v ie w or Adjust
1. Press the NEXT key to bypass this section or press the ENTER key to view the following screens.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Factory Preset: 150 Seconds Possible Values: 1-255 Seconds
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Min Voltage 2 .0 VDC
Factory Preset: 2.0 VDC Possible Values: 0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
PKG-SVP01B-EN
Factory Preset: 10.0 VDC Possible Values: 0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economize r
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
51
Programming
(On units with a waterside economizer)
Actuator Setup Water Economizer Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Direct/Rev e rse A c ting Direct Ac ting
SETUP
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with water-cooled units)
Actuator Setup Water Econ By pa s s
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Max Voltage 10 .0 VDC
52
Factory Presets: 10.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Direct/Rev e rse A c ting DIR ECT A CT IN G
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Min Voltage 2 .0 VDC
SETUP
Factory Presets: 2.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Max Stroke Tim e 1 5 0 Sec
PKG-SVP01B-EN
Factory Presets: 150 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
53
Programming
(On units with hydronic heat)
Actuator Setup Hydronic
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC Possible Values: 0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC Possible Values: 0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Direct/Rev e rse A c t DIR ECT A C TIN G
SETUP
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Max Stroke Tim e 6 0 Sec
Factory Presets: 60 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC Possible Values: 0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Max Voltage 10 .0 VDC
54
Factory Presets: 10.0 VDC Possible Values: 0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Max Stroke Tim e 6 0 Sec
Factory Presets: 60 Sec Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Min Voltage 2 .0 VDC
SETUP
Factory Presets: 2.0 VDC Possible Values: 0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC Possible Values: 0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
55
Programming
SETUP
Control Algorithm Tuning Parameters
(Applicable to all Units)
Control Algorithm Tuning Parameters
Press ENTER to Review or Adjust
1. Do not make any adjustments to these settings before contacting your Trane Company representative.
2. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
56
PKG-SVP01B-EN
Programming
SETPOINT
SETPOINT Menu
The SETPOINT menu allows you to designate default zone temperature setpoints, supply air and space pressure setpoints, and low ambient compressor lockout setpoints.
These setpoints are active (in use) for the Setpoint Source Selection designated as DEFAULT for these inputs.
When a setpoint screen displays for 30 minutes without a key being pressed, the HI display will revert to the general operating status screen. If this happens, press the SETPOINT key again to return to the setpoint menu.
Note: Some of the screens displayed in this section may not be visible on your HI since they are applicable only for particular unit options.
Pressing the SETPOINT key will allow you to view or modify unit setpoints.
To change setpoint values on a particular screen:
1. Press the plus or minus key until the correct value appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve made an error, press the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, OR
a. if no further changes are required and
you want to exit back to view the unit operating status, press the STATUS key once, OR
b. if you want to remain in the Setpoint
submenu, press the SETPOINT key once and it will return you to the beginning of that particular submenu, OR
c. if you want to exit to another submenu
in the SETPOINT menu, press the SETPOINT key twice. Then press the NEXT key to scroll through the SET­POINT submenu choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that key once, then press the NEXT key to scroll through those screens.
SETPOINT Menu Screens
(Applicable for all units except as noted)
Default Supply Air Temp Setpoint(s)
Cooling: 55 F
Factory Presets: 55 F Possible Values: 40-90 F
1. Pressing the NEXT key will display the following screen.
Default Supply Air Temp Setpoint(s)
Cooling: 67 F H e a ting: 71 F
Factory Presets: 100 F Possible Values: Cool = 40-90 F
Heat = 40-180 F
1. Pressing the NEXT key will display the following screen.
Supply Air Temperature Deadband
Cooling: 8.0 F
Factory Presets: 8.0 F Possible Values: Cool = 4-20 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
Supply Air Temperature Deadband
Cooling: 8.0 F H e a ting: 4.0 F
Factory Presets: Cooling = 8.0 F
Heating = 4.0 F
Possible Values: Cooling= 4-20 F
Heating = 2-10 F
1. Pressing the NEXT key will display the following screen.
Defa u l t Da ytime W arm u p Setpo i n ts
Initiate: 67 F Terminate: 71 F
Factory Presets: Heat = 71 F
Cool = 74 F
Possible Values: Heat = 50-90 F
Cool = 52-92 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
57
Programming
Tempe rature Cooling Setpoint By: 1.5 F
Cool: 85 F H e a t: 60 F Morn Warmup: 72 F
(On units with hydronic, electric, or external heat only)
Default Occ upie d Zone Setpoint(s)
Cool: 74 F H e a t: 71 F
Factory Presets: Heat = 71 F
Cool = 74 F
Possible Values: Heat = 50-90 F
Cool = 52-92 F
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints.
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
When Economizer Cooling, Re duc e Zone
Factory Presets: 1.5 F Possible Values: 0.0-3.0 F
1. Pressing the NEXT key will display the following screen.
SETPOINT
(On cooling-only units)
Default Unoc c upie d Zone Te m p Setpoint(s)
Cool: 85 F
Factory Presets: 85 F Possible Values: 50-90 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Default Unoc c upie d Zone Te m p Setpoint(s)
Factory Presets: Cool = 85 F
Heat = 60 F MWU = 72 F
Possible Values: Cool = 52-90 F
Heat = 50-88 F MWU = 50-90 F
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints. Also, the morning warmup cannot be lower than the heating setpoint.
1. Pressing the NEXT key will display the following screen.
58
PKG-SVP01B-EN
Programming SETPOINT
(On units with an airside economizer)
Refe re n ce Entha l py :
When OA Enthalpy is B e low: 25 B TU /LB
Factory Presets: 25 BTU/LB Possible Values: 19-28 BTU/LB
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Supply Air Low Limit - Modulate Econom izer
Toward Min Pos if SA Tem p B e low: 50 F
Factory Presets: 50 F Possible Values: 40-65 F
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Default OA D a m pe r Min Position: 15 %
Ena b l e A i r Ec o n
Factory Presets: 15% Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer, OA cfm compensation, and IGV or VFD or on units without an economizer, with IGV or VFD, and a VCM)
Default OA D a m pe r Min Position: 15 %
with IGV/VFD C om m a nd a t Minimum (0 % )
Factory Presets: 15% Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer, OA cfm compensation, and IGV or VFD or on units without an economizer, with IGV or VFD, and a VCM)
Default OA D a m pe r Min Position: 10 %
with IGV/VFD C om m a nd a t Maxim um (10 0 % )
Factory Presets: 10% Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
Default Minimum OA Flow Setpoint: 40 CC FM
Min OA Flow Dea dba nd: 10 .0 C C FM
PKG-SVP01B-EN
Possible Values: Setpoint = 0-max unit airflow
Deadband = 5.0-20 CCFM
1. Pressing the NEXT key will display the following screen.
59
Programming
(On units with a VCM installed and preheat enabled)
Preheat Output ON If Preheat Temp Below
Prehe a t Ac tiva tion Tem pe rature: 35 F
Factory Presets: 35 F Possible Values: 35-75 F
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD. Also, on units with SAT control without air volume control and supply air pressure sensor installed)
Default Supply Air Pressure: 1.5 IWC High Limit: 4.0 IWC D e a dba nd: 0.5 IWC
Factory Presets: Setpoint = 1.5 IWC
High Limit = 4.0 IWC Deadband = 0.5 IWC
Possible Values: Setpoint = 1.0-4.3 IWC
High Limit = 1.2-4.7 IWC Deadband = 0.1-2.0 IWC
Note: The high limit setpoint cannot be adjusted below the parameters of the following equation: The high limit = Deadband - 0.1 2
SETPOINT
1. Pressing the NEXT key will display the following screen.
Low Ambie nt Com p Loc k out Tem p: 50 F
Comp (s) OFF If OA Tem p B e low This Value
Factory Presets: 50 F Possible Values: -20-80 F
1. Pressing the NEXT key will display the following screen.
Setpoint Source Selec tions Subme nu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
For Supply A ir Temp C ooling C ontrol, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
60
PKG-SVP01B-EN
Programming
(On units with hydronic or electric heat)
For Supply A ir Temp H e a ting Control, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
For Occ Zone Tem p C ooling C ontrol, Use Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
For Occ Zone Tem p H e a ting Control, Use Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
SETPOINT
PKG-SVP01B-EN
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
For Unocc Zone Te m p C ooling C ontrol, Use Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
For Unocc ZoneTe m p H e a ting Control, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
61
Programming
(On units with hydronic, electric, or external heat)
For Unocc ZoneTe m p H e a ting Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu NSB Zone Sensor Setpoint Input GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat)
For Morn in g W armu p T emp Cont rol , Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
NSB Zone Sensor Setpoint Input
1. Pressing the NEXT key will display the following screen.
SETPOINT
(On units with an airside or waterside economizer or VCM )
For Default OA Min Position, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
Remote Min Pos Pot Input
1. Pressing the NEXT key will display the following screen.
(On units with a VCM and GBAS)
For Min Outside A ir Flow Rate C trl, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD and GBAS)
For Supply A ir Pressure Control, U s e
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
62
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
CONFIGURATION
CONFIGURATION Menu
The self-contained unit has many operating functions that are factory preset. The following configuration programming steps allow the user to configure a replacement HI module for a unit that is already in operation.
Refer to the unit model number on the unit nameplate (on the control panel door) while scrolling through the configu­ration screens. Certain digits of this alpha/ numeric model number provide informa­tion that must be entered at the HI for the unit to operate properly.
Note: Some of the screens displayed in this section are applicable only for particu­lar options and are not visible unless those options are installed on your unit.
Pressing the CONFIGURATION key will allow you to view or modify unit set­points.
To change setpoint values on a particular screen:
1. Press the plus or minus key until the correct value appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve made an error, press the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, OR
a. if no further changes are required and
you want to exit back to view the unit operating status, press the STATUS key once, OR
b. if you want to remain in the Setpoint
submenu, press the CONFIGURATION key once and it will return you to the beginning of that particular submenu, OR
c. if you want to exit to another submenu
in the CONFIGURATION menu, press the CONFIGURATION key twice. Then press the NEXT key to scroll through the CONFIGURATION submenu choices, OR
d. if you want to exit to another menu,
such as SETPOINT key, press that key once, then press the NEXT key to scroll through those screens.
Configuration - Model Num D igit 1 Unit Type C om m e rcial Self-Contained
Possible Values: Commercial Self-Contained
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 3 Condenser Medium WATER COOLED CONDENSER
Possible Values: Water Cooled Condenser
Air Cooled Condenser None - No Condenser
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 4 Dev e lopm e nt Type SIGNA TU R E SERIES
Possible Values: Signature Series
Modular Series
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 5 Refrig Ckt Config INDEPENDENT
Possible Values: Independent
Manifolded
Note: Manifolded piping is only available on Signature Series units, 30 tons and larger.
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 27 Water Economizer INSTALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units or units with a waterside economizer)
Configuration - Model Num D igit 29 Water Piping INTERMEDIA TE PIPING
Possible Values: Intermediate Piping
Basic Piping None - No Piping
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
63
Programming
(On all water-cooled units and water flow switch or units with a waterside economizer and water flow switch)
Configuration - Model Num D i git 29 Water Flow Switch IN STALLED
CONFIGURATION
Possible Values: Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 20 Hea ting Type H YDR ON IC
Possible Values: Hydronic
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 6, 7 Unit Capa c ity 7 2
Possible Values: 20-80
Note: The possible value for unit capacity is dependent upon the unit size (tons).
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 23 Power Exhaust NON E
Not Installed
Electric None External
64
Possible Values: None
100% with Statitrac 50%/100% without Statitrac
Note: This option is currently not available on commercial self-contained units, but this screen still displays.
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28 Air Economizer INSTALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Configuration - Model Num D igit 9 Air Temp/Vol Ctrl SA C TR L WITH IGV/VFD
Possible Values: SA Control with IGV/VFD
Zone Control No IGV/VFD or SA Control No IGV/VFD
1. Pressing the NEXT key will display the following screen.
(On units with SA Control and IGV/VFD installed)
Configuration - Model Num D igit 9 Supply Fan VFD Bypass INSTALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28 Compa rative Enthalpy IN STALLED
CONFIGURATION
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 33 GBAS 0 - 5 VDC Module IN STALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 33 Ventilation Override (VOM) INSTALLED
Possible Values: Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28 Ventilation Ctrl TR A Q D A MPERS
Possible Values: Traq Dampers
1. Pressing the NEXT key will display the following screen.
Not Installed
Standard Dampers
PKG-SVP01B-EN
65
Programming
Single Compressor Module (SCM) 1.00
Multiple Compressor Module (MCM) 4.0 9
Configuration - Model Num D i git 33 TCI4 C om m unic a tions Module IN STALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 33 Rem ote H um a n Interface IN STALLED
Possible Values: Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
(On all units unless the RTM has changed)
Unit Model Number
Possible Values: Model Number
1. Pressing the NEXT key will display the following screen.
CONFIGURATION
Software Revision Number Report: RTM 9.13
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report:
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report:
1. Pressing the NEXT key will display the following screen.
(On units with a GBAS)
Software Revision Number Report: GBAS 0-5 VDC Module 1 .0 0
1. Pressing the NEXT key will display the following screen.
(On units with a VOM)
Software Revision Number Report: Ventilation Override (VOM) 1.00
1. Pressing the NEXT key will display the following screen.
66
PKG-SVP01B-EN
Programming
(On units with comparative enthalpy)
Software Revision Number Report: Exhaust/Com p Enthalpy Module 8 .0 4
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
Software Revision Number Report: Hea t Module 1.0 0
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report: Unit Human Interface 14.07
1. Pressing the NEXT key will display the following screen.
(On units with a RHI)
Software Revision Number Report: Rem ote H um a n Interface 1 1 .0 4
CONFIGURATION
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
Software Revision Number Report: Ventilation Control (VCM) 1.12
1. Pressing the NEXT key will display the following screen.
(On units with a TCI)
Software Revision Number Report: TCI4 C om m unic a tions Module 1 .0 0
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
67
Programming
SERVICE MODE
SERVICE MODE Menu
The SERVICE MODE key allows the user to input operating parameters for unit operation during a service test. Depend­ing on the particular test being conducted, the user will cycle through all unit outputs (i.e.; compressors, fans, dampers, heaters) and selectively turn them on or off. After designating the operating status for each unit component, the user will designate the “TEST START” delay time.
When a service mode screen displays for 30 minutes without a key being pressed, the HI screen will revert to the general operating status display. If this happens, press the SERVICE MODE key to return to the service menu.
Note: Some of the screens displayed in this section are applicable only for particu­lar options and may not be visible on your unit.
To operate the unit in test mode, press the SERVICE MODE key to enter the service mode menu. Scroll through system outputs to selectively turn them on or off.
To change service mode values on a particular screen:
1. Press the plus or minus key until the correct value appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve made an error, press the CANCEL key to delete your entry.
3. Press the NEXT key to advance the cursor to another field within a screen.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, OR
a. if no further changes are required and
you want to exit back to view the unit operating status, press the STATUS key once, OR
b. if you want to remain in the Setpoint
submenu, press the SERVICE MODE key once and it will return you to the beginning of that submenu, OR
c. if you want to exit to another submenu
in the SERVICE MODE menu, press the CONFIGURATION key twice. Then press the NEXT key to scroll through the CONFIGURATION submenu choices, OR
d. if you want to exit to another menu,
such as SETPOINT key, press that key once, then press the NEXT key to scroll through those screens.
68
(On units without IGV/VFD)
Supply Air Controls Supply Fan OFF
Possible Values: On, Off, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
Supply Air Controls Supply Fan OFF IGV/VFD Cond 35 %
Possible Values: On, Off, Auto
IGV/VFD Cond = 0-100%
1. Pressing the NEXT key will display the following screen.
(
On water-cooled units or units with water-cooled condenser)
Water Pump Relay State Off
Possible Values: On, Off
1. Pressing the NEXT key will display the following screen.
VAV Box Re la y RTM Alarm Output
Possible Values: VAV Box - 0 = Occ
Drive Max, Auto - 1 = Unocc Alarm Output = Off, On
1. Pressing the NEXT key will display the following screen.
(
On water-cooled units or units with water-cooled condenser)
Water Econ Control Valve C om m a nd 0 % Water Econ Bypas s Valv e C om m a nd 0 %
Possible Values: 0-100%
1. Pressing the NEXT key will display the following screen.
(On air-cooled units, 20 - 35 Tons)
Condenser Fan Outputs 1A OFF 1 B OFF
Factory Presets: Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
Possible Values: On, Off, Auto
PKG-SVP01B-EN
Programming SERVICE MODE
(On air-cooled units, 40-60 Tons)
Condens e r Fan Outputs 1A OFF 1 B OFF 2 A OFF 2 B OFF
Factory Presets: Off Possible Values: On, Off, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed Ckt 1 0 %
Factory Presets: 0 % Possible Values: 0-100%, Auto
1. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed Ckt 1 0 % C k t 2 0 %
Factory Presets: 0 %
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
1. Press the NEXT key again to display the following screen.
Possible Values: 0-100%, Auto
Compressor Relays: K11 OFF K 3 OFF K 1 2 OFF K 4 OFF
Factory Presets: Off Possible Values: On, Off
(On units with hydronic heat)
Hydronic He a t Actuator 0 %
Factory Presets: 0 % Possible Values: 0-100%, Auto
PKG-SVP01B-EN
69
Programming
(On units with electric heat)
Heat Stages Stage Off
Factory Presets: 0 % Possible Values: 0-100%, Auto
Note: Only single stage electric heat is available factory installed.
1. Press the NEXT key again to display the following screen.
(On units with an airside economizer)
OA Damper Pos 0 %
Factory Presets: OA Damper = 0% Possible Values: OA Damper = 0-100%
1. Press the NEXT key again to display the following screen.
(On units with VFD and bypass)
Supply Fan Bypass Relay: NORMAL
SERVICE MODE
Possible Values: Normal, Bypass
1. Press the NEXT key again to display the following screen.
(On units with VOM)
Ventilation Override Module Output Rela y OFF
Factory Presets: Off Possible Values: On, Off
1. Press the NEXT key again to display the following screen.
(On units with VCM)
OA Preheater State OFF
Factory Presets: Off Possible Values: On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
70
PKG-SVP01B-EN
Programming SERVICE MODE
(On units with GBAS)
GBAS 0-5 VDC Module Relay Outputs #1 OFF # 2 OFF # 3 OFF # 4 OFF # 5 OFF
Factory Presets: Off Possible Values: 1, 2, 3, 4, 5 = On, Off
1. Press the NEXT key again to display the following screen.
Status/Annunc Tes t Sys On (Blink ing) Hea t: OFF Cool: OFF Service: OFF
Factory Presets: Off Possible Values: Heat = On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
Start Test In 5 Sec onds Pres s TEST START To Be gin, STOP To Halt
Cool = On, Off Service = On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
PKG-SVP01B-EN
71
Programming
DIAGNOSTICS
DIAGNOSTICS Menu
The DIAGNOSTICS menu allows the user to view diagnostics that result from system failures within the unit. There are two lists where diagnostics reside; the active list, and the diagnostic event log.
Use the active list for viewing all active diagnostics and clearing manually resetable diagnostics. If any active diagnostics are present, they will display after pressing the DIAGNOSTICS key.
Active manual diagnostics can be cleared in batch form at the unit mounted Human Interface. When an active diagnostic is manually or automatically cleared, it is removed from this buffer. Automatically resetting diagnostics cannot be reset by the HI. To clear the diagnostic, you must correct the condition that caused the diagnostic first.
The word MORE” will display on all screens if more than one diagnostic exists, except for the last diagnostic. Upon reaching the last diagnostic, the word MORE” disappears. Pressing the NEXT key at this point causes the display to advance to the first diagnostic in the diagnostic event log.
The diagnostic event log screens allow the user to view the past 20 diagnostics. They will display after scrolling through the active list or after pressing the DIAGNOSTICS key when no active diagnostics are present. Diagnostics in this log are stacked in inverse chronologi­cal order, with the first diagnostic screen being the most recently reported diagnostic.
One the following screens will display first when the DIAGNOSTIC key is pressed.
Diagnos tic Menu ---- Info No Active Diagnostics (NEXT) History Log
OR
Press CANCEL to Clear All Active Manual Diagnostics, or Press NEXT to View
1. Pressing the CANCEL key to clear the diagnostics will prompt the following screen.
Diagnostic Reset Is Password Protected Please Enter Password: ________________________
Factory Presets: N/A Possible Values: + (Plus), - (Minus)
1. Press the + (Plus) and/or - (Minus) keys to enter the password.
2. Press the ENTER key to confirm. When the correct password is entered, the follow­ing screen will display.
The following screens will display sequentially.
Resetting Active Manual Diagnostics Sending Res e t Re ques t
Res e tting Active Manua l D ia gnos tics Updating Unit Data, Please Wait
Active D ia gnos tic ---- Info Please Wait, Unit Is In Reset Mode
OR
Pressing the NEXT key to view the diagnostics will prompt the following screen if a MANUAL RESET failure has occurred.
Active D ia gnos tic ---- Manua l R e s e t ______________________________ More
72
Possible Values: Emergency Stop
Supply Fan Failure Low Pressure Control Open - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Compressor Trip - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Low Air Temp Limit Trip Manual Reset SA Static Pressure Limit Compressor Contactor Fail - Ckt 1, Ckt 2, Ckt 3, Ckt 4
Note: The word MORE will appear on the screen if more than one failure has occurred.
PKG-SVP01B-EN
Programming
OR
Active Diagnostic ---- Auto Reset ______________________________ More
Possible Values: Failure for the Following
RTM Zone Heat Aux Temp Supply Air Temp Unocc Zone Cool Setpt RTM Aux. Temp Unocc Zone Heat Setpt OA Temp Supply Air Press Setpt Mode Input Space Static Pres Setpt Occ Zone Cool Setpoint Space Pressure Occ Zone Heat Setpoint Return Air Temp Supply air Pres RA Humidity OA Humidity Auto Reset SA Static Pres Limit SCM Communication Evap Temp - Ckt 1, 2, 3, 4 MCM Communication Heat Module Commun. ECEM Communication Cond Temp - Ckt 1, 2, 3, 4 TCI Communication GBAS Module Communication Tracer Unit HI Communication VOM Communication Sup Air Temp Cool Setpt Sup Air Temp Heat Setpt NSB Panel Zone Temp CO2 Sensor VCM Aux Temp Velocity Press VCM Communication WSM Communication Ent Cond Water Temp Ent Water Temp WSM Mixed Air Temp Water Flow
DIAGNOSTICS
®
Communication NSB Panel Communication
OR
Pressing the NEXT key to view the diagnostics will prompt the following screen if an information only failure has occurred.
Active D ia gnos tic ---- Info ______________________________ More
Possible Values: Heat Fail
Dirty Filter Ventilation Override Mode A, B, C, D, or E RTM Data Storage Error
Note: Activation of any VOM mode can be viewed within the “Active Diagnostic” screen.
PKG-SVP01B-EN
73
Programming
Diagnos tic Log Is Pas s word Protected
Please Enter Password: _____________________
Active Diagnostics _________________________
The following screen will appear sequentially.
Log 1 _________________ ______________________________
Possible Values: Log Number 1-20
Viewed or Not Viewed Active or History Manual Auto Info or any diagnostic listed under the previous screens associated with the diagnostic type, including VOM activated mode
Press the CANCEL key to clear the diagnostics and prompt the following screen.
Possible Values: + (Plus) and - (Minus)
1. Press the + (Plus) or - (Minus) keys to enter the password.
2. Press the ENTER key to confirm. After entering the correct password, the following screen will display.
DIAGNOSTICS
Please Wait, Updating Diagnostic Log
Possible Values: Manual, Auto, or Info If the DIAGNOSTIC LOG is empty when the CANCEL key is pressed, the following screen will display.
Active D ia gnos tics ---- Info Diagnos tic B uffer Is Already Empty!
Press the AUTO or STOP key to return to the top level status screen.
Possible Values: Manual, Auto, or Info
74
PKG-SVP01B-EN
Programming
DIAGNOSTICS
Failure Modes
When any condition results in the unit’s inability to perform a normal function, it is said to have entered a failure mode. There are two types of failure modes.
1. An Analog input out of range” failure mode.
This failure mode occurs when a
sensing device such as a zone tem­perature sensor or a humidity sensor begins to transmit information that is outside its allowable range.
2. A Fault recognition by input logic failure mode. This failure mode occurs when the UCM receives information that does not make sense” or does not conform to its predefined logic.
Diagnostics
There are three types of diagnostics:
1. Informational
Does not affect machine operation
2. Automatic Reset
Affects machine operation but returns
to normal when diagnostic condition no longer exists
3. Manual Reset
Affects machine operation and must be
reset at the HI or by cycling power to unit for normal operation to resume.
To troubleshoot diagnostics, reference
Installation, Owner, and Diagnostic
the
Manual SVX01A-EN
units and Modular Series units.
that ships with the unit:
ships with Signature Series
SCXG-SVX01A-EN
ships with
SCXF-
PKG-SVP01B-EN
75
Programming
Index
Index Symbols
+ (Plus) Key 10
- (Minus) Key 10
A
acronyms 4 active diagnostic 72, 73 active setpoint 5 actuator setup 15 AUTO key 10, 11, 13
C
CANCEL key 10 coil frost cutout 15 comparative enthalpy module 7 compressor lockout 5 compressor modules 7 compressor protection switch 5 condenser temperature control band 15 CONFIGURATION 11, 12 CONFIGURATION key 9 CONFIGURATION menu 63 control algorithm tuning parameters 15, 56 control band 5 control point 5 CUSTOM key 10 CUSTOM menu 10, 17
D
data manipulation keys 10 daytime warmup 5 deadband 5 default setpoints 14 device characteristic setup definitions 51 diagnostic event log 72 DIAGNOSTICS 9, 11, 72, 73, 74, 75 DIAGNOSTICS key 9 DIAGNOSTICS menu 72
E
ECEM 6, 7, 73 ENTER key 10 EXHAUST sequence 8 exhaust/comparative enthalpy module 7
F
factory presets 13 failure modes 75 function (enable/disable) setups 14
G
GBAS 6, 7 GBAS input/output 15 GBAS module I/O assignments 45 general status display 11 generic building automation system module 7 glossary 5
H
heat module 6, 7 HI 2, 7, 9 - 12 human interface 2, 7, 9 - 12
I
information format 15 interprocessor communications board 7 IOD 2 IPCB 4, 7
L
literature change history 2 low ambient compressor lockout 5 low entering condenser water tempera­ture 5 low entering water temperature com­pressor lockout 5
M
MCM 6, 7 menu keys 9, 11 module defaults 15 modules 7 MORE 72
N
NEXT key 10 no configuration 7, 12
O
outside air ventilation setup 42
P
password 72 password protected screens 16 points list 6 PRESSURIZE sequence 8 PREVIOUS key 10 programming the unit 2, 9 PURGE sequence 8 PURGE with duct pressure control
sequence 8
R
reference enthalpy 5, 15 remote human interface 9 reset amount maximum 5 reset end temperature 5 reset start temperature 5 RHI 9 RTM 6, 7, RTM alarm output assignments 15 RTM alarm output diagnostic assignment screens 47
S
SCM 6, 7 sensor source selection 15, 40 SERVICE MODE menu 68 SETPOINT menu 57 setpoint source selection 15 setpoints 14, 57 SETPOINTS key 9 SETUP key 9 SETUP menu 32 STATUS key 9 STATUS menu 17 STOP key 10, 11 supply air pressure 5 supply air tempering 5
T
TCI 7 temperature input calibration 48 temperature input offset 15 TEST START 68 TEST START key 10 Trane communications interface module 7
U
UCM 7, 9, 13 unit off 7 UNIT OFF sequence 8 unit on 7 unit operation keys 10 unit status 7, 9
V
ventilation override 7, 8 ventilation override definition 15 ventilation override definitions 43 VOM 6, 7, 8 VOM active 12
76
PKG-SVP01B-EN
Programming
Index
PKG-SVP01B-EN
77
The Trane Company A Division of American Standard Inc. www.trane.com
For more information contact your local Trane office or e-mail us at comfort@trane.com
An American Standard Company
Literature Order Number File Number Supersedes Stocking Location
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
PKG-SVP01B-EN PL-UN-PKG-SVX01B-EN 4-00 PKG-SVP01A-EN La Crosse - Inland
Loading...