Note: One copy of the appropriate service
literature (Installation, Owner, and Diagnostic Manual) ships inside the control panel
of each unit.
About This Manual
Literature Change History
Use this manual for IntelliPak® commercial self-contained models SCWF/SIWF,
SCRF/SIRF, SCWG/SIWG, and SIWG/
SIRG. This is the second issue of this
manual. This revision includes an index,
which was not in the original issue.
It provides specific programming
instructions for “AO” and later design
sequences. For previous design
sequences, contact your local Trane
representative.
Overview
This manual is divided into multiple
sections based on the unit’s human
interface (HI) panel format. Each section
provides step by step instructions for
programming the unit using the HI. In
addition, each section provides specific
information about the system operating
parameters and their related HI screens,
in the order they appear when scrolling
through the HI.
By carefully following the screen layout
in this manual while referencing the HI
panel, the user can monitor operating
status, set specific operating parameters,
and diagnose system problems.
Some screens shown in this manual are
dependent on unit options and/or model
configuration. Therefore, some screens in
this manual may not appear on a
particular unit’s human interface panel.
Screens that are configuration-dependent are labeled as such. Follow the
appropriate steps for each screen as it
appears and proceed through each
section.
Refer to the table of contents and index
for specific topics contained in this
manual and supporting manuals.
Complete the “Start-Up” procedures in
the applicable Installation, Owner, and
Diagnostic (IOD) manual before attempting to operate or service this equipment
to minimize the risk of improper operation.
Note: The procedures discussed in this
manual should only be performed by
qualified, experienced HVAC technicians.
General Information
STATUS Menu
SETUP Menu
SETPOINT Menu
CONFIGURATION Menu
SERVICE MODE Menu
DIAGNOSTICS Menu
Index
• IntelliPak® Self-Contained Installation,
Owner, and Diagnostic Manual SCXFSVX01A-EN
SCWG, SCRG, SIWG, and SIRG
for Modular Series models
2
17
32
57
63
68
72
76
PKG-SVP01B-EN3
General
InformationProgramming
Commonly Used Acronyms
and Abbreviations
For convenience, a number of acronyms
and abbreviations are used throughout
this manual. These acronyms are
alphabetically listed and defined below.
Act = active
AH = Air Handler
Annunc = Annunciater
AS = Airside
Aux = auxiliary
BAS = building automation systems
ccfm = (100 cfm) cubic-feet-per-minute
Cfg = Configured, configuration
cfm = cubic-feet-per-minute
ckt = circuit
Cmd = command
Comp (s) = compressor, compressors
Cond = condenser, condensers
Config = configured, configuration
Ctrl = control
CV = constant volume
Cy = cycle
CW = clockwise
CCW = counterclockwise
Dflt = default
Diag = diagnostic
Dmpr = damper
DWU = Daytime Warmup
E/A = exhaust air
ECEM = exhaust control/enthalpy module
Econ = economizer, economizing
Ent = entering
Evap = evaporator
F/A = fresh air
Funct = function
GBAS = generic building automation
system (module)
Heat = Heat, heating
HEAT = where all caps HEAT (module)
HGBP = hot gas bypass
Hi = high
HI = where all caps Human Interface
HVAC = heating, ventilation and air
conditioning
ICS = Integrated Comfort System
IGV = inlet guide vanes
I/O = input/output
Indep = Independent
IOD = installation/owner/ diagnostic
manual
IPC = interprocessor communications
IPCB = interprocessor communications
bridge (module)
IWC = inches water column
LCD = liquid crystal display
LH = left-hand
Lo = low
Manif = manifolded
Max = maximum
Min = minimum
Misc = miscellaneous
MCM = multiple compressor module
Mod = modulating
MWU = morning warmup
NSB = night setback panel
Num = number
O/A = outside air
Occ = occupied
Pos = position
Pot = potentiometer
PPM = parts per million
Press = pressure
Propor = proportional
psig = pounds-per-square-inch gauge
pressure
PWS = part-winding start
R/A = return air
Refrig = refrigerant
RHI = Remote Human Interface
RH = right-hand
rpm = revolutions-per-minute
RTM = RTM module
SA = supply air
SAP = supply air pressure
Sat = saturated
SCM = single compressor module
Setpt = setpoint
SF = supply fan
SRC = source
Stg = stage
Stnd = standard
STP = setpoint
Sw = switch
SZ = single-zone (unit airflow)
TCI = Tracer communications interface
module
Temp = temperature
UCM = unit control module
Unocc = unoccupied
VAV = variable air volume
VCM = ventilation control module
VDC = volts DC
Ventil = ventilation
VFD = variable frequency drive
VOM = ventilation override module
W/ = with
w.c. = water column
WU = warmup
4PKG-SVP01B-EN
General
InformationProgramming
Glossary
These terms are used throughout this
manual. Knowledge of these terms is
essential in gaining an understanding of
how these units operate.
Active Setpoint
The setpoint which is currently being
used for control by the setpoint source
selection.
Compressor Lockout
All affected compressors stop and
remain off until the condition resets or is
manually reset.
Compressor Protection Switch
A pressure switch installed on the
suction line that prevents compressor
operation below the switch’s setpoint.
The purpose is to prevent no-flow scroll
compressor operation.
Control Band
The range of temperatures or pressures
which would normally be maintained by
the various control functions.
Control Point
The value of a setpoint that an algorithm
is using at any given time.
Deadband
As applied to SA temperature control,
this refers to a range of temperatures
equally spaced above and below the SA
temperature control point in which the
control algorithm is satisfied.
Economizer Zone Temp Setpoint
Suppression
A parameter used for setting the Zone
Temp setpoint at a lower value than the
mechanical cooling zone temperature
setpoint.
External Heat
A heat source external to the selfcontained unit that is field installed. i.e.
duct heat or VAV reheat boxes.
External Stop
A binary input on the RTM that allows
unit shutdown when connected to a fieldsupplied switch.
Hydronic Heat
Optional steam or hot water heat coil.
Independent Refrigerant Circuit
All model SCWG/SIWG, SCRG/SIRG and
SCWF/SIWF units have independent
refrigerant circuits.
Low Ambient Compressor Lockout
A function which prevents compressor
operation at low outdoor ambient
temperatures.
Low Entering Condenser Water Temperature
When the entering water temperature
sensor reads a water temperature below
the minimum water temperature input
into the controller. 54 F is the factory
preset temperature.
Low Entering Water Temperature
Compressor Lockout
On units with head pressure control
disabled and an entering water temperature below 54 F, compressor operation
disables. Economizer operation is still
functional.
Manifolded Refrigerant Circuit
Only model SCRF/SIRF units, 30-60 tons,
have manifolded refrigerant circuits.
Night Setback (NSB)
Applies to unit control during unoccupied
periods.
Night Setback (NSB) Panel
The HI panel display uses this term for
NSB zone sensor.
OA Reset
Outdoor Air Reset - Supply Air Temperature Reset based on Outdoor Air Temperature.
Occupied Zone Low Temperature Limit
Setpoint
The temperature that initiates daytime
warmup.
Purge
A function which causes zone air to purge
and be replaced by outside air.
Reference Enthalpy
An outdoor enthalpy value above which
economizing disables.
Remote Human Interface
A human interface module designed to
be mounted remotely from the unit.
There are some functional differences
between a unit mounted and a remote
mounted human interface module.
Reset Amount Maximum
The maximum amount of reset allowed.
Reset End Temperature
The temperature at which the maximum
reset amount will occur.
Reset Start Temperature
The temperature at which reset will
begin.
Space Pressure
The pressure in the building as measured
by the space pressure transducer,
referenced to outside (atmospheric)
pressure.
Supply Air Pressure High Limit
A pressure limit to prevent unit casing
and/or ductwork overpressurization.
Supply Air Pressure
The pressure in inches water column
(IWC) of the supply duct plenum or outlet
as measured by the supply air pressure
transducer, referenced to local outside
(atmospheric) pressure.
Supply Air Tempering
Turning on heat when the supply air
temperature drops below a preset value
usually due to cold outside air being
brought in to provide building ventilation.
Supply Air Temperature Control Point
The revised value of supply air temperature setpoint after supply air temperature
reset has been applied.
Supply Air Temperature Reset
A function that shifts the SA Temp
Setpoint an amount based on the value of
another parameter—typically Zone Temp
or Outdoor Air Temp. The purpose of this
function is to lower unit capacity to better
meet load requirements.
Water Purge
When the waterside economizer valve
opens to flush out the economizer tubes
to prevent failure due to stagnant water
and sedimentation.
PKG-SVP01B-EN5
General
InformationProgramming
Table P-GI-1. IntelliPak® Points List.
Unit ModuleAnalog InputsAnalog OutputsBinary InputsBinary Outputs
RTMASE damper min posO/A damper actuatorEmergency stopVAV box drive max
SCMEvap temp sensorCond fan speedLow pressure controlCompressor relay
MCMEvap temp sensorCond fan speedLow pressure control - ckt 1 & 2Compressor relay
The IntelliPak® self-contained unit is
controlled by a microelectronic control
system that consists of a network of
modules. These modules are referred to
as unit control modules (UCM). In this
manual, the acronym UCM refers to the
entire control system network.
The unit size, type, heating functions,
peripheral devices, options, exhaust
capabilities, etc. determine the number
and type of modules that a particular unit
may have.
These modules perform specific unit
functions using proportional/integral
control algorithms. They are mounted in
the unit control panel and are factory
wired to their respective internal components. By processing analog and binary
inputs, each module supplies outputs in
the form of modulating voltages (from
other unit modules, sensors, remote
panels, and customer binary contacts) to
perform the applicable request; such as
economizing, mechanical cooling,
heating, ventilation.
The UCM provides some equipment
protection functions both directly and
indirectly, such as duct pressure limits
and compressor lockouts.
Following is a description of each
module’s function within the UCM
system.
RTM Module Board - Standard on all
Units
The RTM is the central processor of the
system. It continuously receives information from the other unit modules, sensors,
the remote control panel, and customer
supplied relays. It interprets this information and responds to cooling, heating, and
ventilation requests by directing the other
modules in the system to energize the
proper unit components. It also directly
initiates supply fan operations, and
economizer operation.
Compressor Modules (SCM and MCM )
The compressor modules (single circuit
and multiple circuit) energize the appropriate compressors and condenser fans
upon receiving a request for mechanical
cooling. The modules monitor the
compressor operation through feedback
from various protection devices.
Heat Module - Standard on all Heating
Units
The heat module directs the unit’s heater
to stage up and down to bring the zone
temperature within the applicable
heating setpoint.
Exhaust/Comparative Enthalpy Module
(ECEM) Option
The ECEM is on units with the comparative enthalpy option. It receives data from
the return air humidity sensor, the return
air temperature sensor, and the return air
space pressure transducer and controls
dampers to maintain space pressure and
humidity levels.
Generic Building Automation System
(GBAS) Module Option
The GBAS module links the RTM with
non-Trane building control systems to
enable communication (input/output
interface) between the systems. It can
accept external setpoints for cooling,
heating, demand limiting, and S/A
pressure.
Ventilation Override Module (VOM)
Option
The VOM can control the unit’s air
handling functions to perform customerspecified functions, such as space
pressurization, exhaust, purge, unit off,
etc.
Interprocessor Communications Board
(IPCB) Option
The IPCB is used to expand communication from the unit’s UCM network to a
remote human interface panel. DIP
switch settings on the IPCB module for
this application should be; switches 1 and
2 “off,” switch 3 “on.”
The TCI module allows external setpoints
for most of the unit functions to be
communicated to the unit’s UCM network
via a Trane ICS
settings on the TCI module for these
applications should be; switches 1, 2, and
3 are “off.”
Human Interface Module (HI)
The HI module illustrated in Figure P-GI-1,
on page 9, enables the user to communicate unit operating parameters; such as
cooling and heating setpoints, demand
limiting, ventilation override modes, etc.
TM
system. DIP switch
The HI module is in the unit’s main control
panel. A small door located in the unit’s
control panel door allows access to the HI
module keypad and display window.
The HI has a 2 line by 40 character LCD
screen to provide status information for
various unit functions and menus to set or
modify operating parameters. There is a
16-key keypad adjacent to the LCD
screen to allow the user to scroll through
the various menus and make adjustments to setpoints, etc.
The information displayed in the LCD
window is top-level status information
unless the operator initiates other
displays.
At power-up, the human interface LCD
displays one of four initial screens as
illustrated in the “General Status
Display”section on page 11 and described below:
1. Unit Off (unit off or stopped)
The unit is configured and operational,
but is not running. This screen shows
state, mode, and function information
when the unit is off or stopped.
2. Unit On (unit on)
The unit is configured and operational,
and is running. This screen shows state,
mode, and function information when
the unit is on.
3. VOM Active (a ventilation override
command was received)
This screen shows that the unit is in a
ventilation override mode.
4. No Configuration (the unit needs to be
configured)
This screen shows that required
configuration data is missing.
The LCD screen display will go out if no
keys are pressed for 30 minutes. If it goes
out, simply press the STATUS key.
PKG-SVP01B-EN7
General
InformationProgramming
Ventilation Override Module (VOM)
Definitions
The ventilation override module can be
field-configured with up to five different
override sequences for ventilation
override control purpose. When any one
of the module’s five binary inputs are
activated, it will initiate specified functions such as; space pressurization,
exhaust, purge, purge with duct pressure
control, and unit off.
Once the ventilation sequences are
configured, they can be changed unless
they are locked using the HI. Once
locked, the ventilation sequences cannot
be unlocked.
The compressors and condenser fans
disable during the ventilation operation. If
more than one ventilation sequence
activates, the one with the highest
priority (VOM “A”) begins first, with
VOM “E” having lowest priority and
beginning last.
A description of the VOM binary inputs
follows below.
UNIT OFF sequence “A”
When complete system shut down is
required, the following sequence can be
used.
• Supply fan – Off
• Supply fan VFD – Off (0 Hz)
(if equipped)
• Inlet guide vanes – closed
(if equipped)
• Outside air dampers – Closed
• Heat – all stages – Off, Modulating heat
output at 0 vdc
• Occupied/Unoccupied output – Deenergized
• VO relay – Energized
• Exhaust fan (field-installed) - Off
• Exhaust damper (field-installed) -
Closed
PRESSURIZE sequence “B”
This override sequence can be used if a
positively pressured space is desired
instead of a negatively pressurized
space.
• Supply fan – on
• Supply fan VFD – on (60 Hz)
(if equipped)
• Inlet guide vanes/VAV boxes – open
(if equipped)
• Outside air dampers – open
• Heat – all stages – off, hydronic heat
output at 0 vdc
• Occupied/ unoccupied output - energized
• VO relay - energized
• Exhaust fan (field-installed) - off
• Exhaust damper (field-installed) - closed
EXHAUST sequence “C”
With the building’s exhaust fans running
and the unit’s supply fan off, the condi-
tioned space becomes negatively
pressurized. This is desirable for clearing
the area of smoke when necessary; i.e.
from an extinguished fire, to keep smoke
out of areas that were not damaged.
• Supply fan – off
• Supply fan VFD – off (0 Hz)
(if equipped)
• Inlet guide vanes – closed
(if equipped)
• Outside air dampers – closed
• Heat – all stages – Off, hydronic heat
output at 0 vdc
• Occupied/Unoccupied output – deenergized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
PURGE sequence “D”
This sequence could be used for purging
the air out of a building before coming out
of unoccupied mode of operation on VAV
units. Also, it can be used to purge smoke
or stale air.
• Supply fan – on
• Supply fan VFD – on (60 Hz)
(if equipped)
• Inlet guide vanes/VAV boxes – Open
(if equipped)
• Outside air damper – Open
• Heat – all stages – Off, Modulating heat
output at 0 vdc
• Occupied/Unoccupied output – Energized
• VO relay – Energized
• Exhaust fan (field-installed) - On
• Exhaust damper (field-installed) - Open
PURGE with duct pressure control “E”
This sequence can be used when supply
air control is required for smoke control.
• Supply fan – on
• Supply fan VFD – on (if equipped)
• Inlet guide vanes – controlled by supply
air pressure control function with
supply air pressure high limit disabled
• Outside air dampers – open
• Heat – all stages – off, hydronic heat
output at 0 vdc
• Occupied/unoccupied output – energized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
Note: Each system (cooling, exhaust,
supply air, etc.) within the unit can be
redefined in the field for each of the five
sequences, if required. Also the definitions
of any or all of the five sequences may be
locked into the software by using the
human interface panel keypad. Once
locked into the software, the sequences
cannot be changed.
8PKG-SVP01B-EN
Programming the Unit
The UCM must be programmed with
“job-specific”setup information for the
unit to operate and function properly. The
data necessary for unit operation will
vary depending on factors such as unit
size, type, and options.
This manual provides step by step
instructions for programming setup
information using the HI or RHI. It also
includes instructions for checking unit
operating status, accessing and clearing
diagnostics, and performing service tests.
Some of the displays in this manual may
not appear on the HI or RHI screen during
programming. Only applicable screens
for specific unit options and operating
parameters will display.
Any steps that do not apply to all unit
types are marked accordingly. Ignore any
steps that do not apply to your unit and/or
application. Continue this process until all
applicable screens are programmed with
the required information.
Menu Keys
Any references in this section to the HI
applies to both the HI and RHI, with the
exception of the SERVICE MODE key.
Reference Figure P-GI-2 for an illustration
of the six menu keys. The menu keys are:
STATUS, SETPOINTS, SETUP, CONFIGURATION, DIAGNOSTICS, and SERVICE
MODE. These keys allow access to
various interactive menus so the user
can input and access unit operating data.
Pressing these keys will display the initial
menu screen designated by the key’s
name. The following information describes each key and its function.
If no key is pressed for 30 minutes while
the HI is displaying a menu screen, it will
revert back to the unit operating status
screen.
STATUS Key
Pressing the status key displays the
operating status screen: On, Unit Stop,
External Stop, Emergency Stop, or
Service Mode. Pressing the NEXT key
allows the operator to scroll to screens
that provide information such as air and
refrigerant temperatures, humidity
levels, fan operation, compressor
operation, heater operation, economizer
positioning, exhaust operation, and
Figure P-GI-1. Human interface module.
heating, cooling, and compressor lockout
setpoints. Pressing the STATUS key while
viewing any of the data screens will
cause the HI to go back to the operating
status screen.
SETPOINTS Key
Pressing the SETPOINTS key displays the
first of the setpoint screens, allowing the
user to designate default temperatures
and pressure setpoints. While scrolling
through the setpoint screens, pressing
this key again will cause the LCD to
display the first setpoint screen.
DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any
time will allow the user to view any unit
function failures. The LCD screen will
display one of the diagnostic screens
(depending on which diagnostic, if any, is
present). If no key is pressed for 30
minutes while the screen is displaying
diagnostic information, it will revert back
to the operating status display.
CONFIGURATION Key
Pressing the CONFIGURATION key
displays the first of the configuration
screens. This allows the user to view or
designate unit configuration data such as
unit type, capacity, system control, etc
General
InformationProgramming
Pressing the configuration key at any
level in the configuration menu will
display the first configuration screen.
Note: Unit configuration information is
factory-programmed. Use this key only to
view current configuration data, or to
designate new data if the unit’s configuration data is lost or if new options are added
in the field.
SETUP Key
Pressing the SETUP key displays screens
that designate various operating parameters such as temperature and pressure
ranges, limits, percentages, setpoint
source selections, and sensor input
definitions for the control of the unit’s
various operating modes. Pressing the
SETUP key at any level in the SETUP
menu will display the first SETUP screen.
SERVICE MODE Key
Pressing the SERVICE MODE key displays
the first of the service test mode screens
that allow the user to turn on or off
various unit components for a particular
test being performed. After designating
on/off status, a screen will display
requesting the user to designate the
TEST START time delay for each test.
PKG-SVP01B-EN9
General
InformationProgramming
Data Manipulation Keys
The data manipulation keys allow theuser
to modify data within the screens: ENTER,
CANCEL, + (Plus), - (Minus), PREVIOUS,
and NEXT. See Figure P--GI-2.
ENTER Key
This key will confirm new values designated by pressing the + (Plus) or - (Minus)
keys at all edit points. When viewing
status and diagnostics screens, it has no
function.
CANCEL Key
After changing data, at an editable
screen, but before confirming it with the
ENTER key, pressing the CANCEL key will
return the data to its previous value. This
key shall also function to clear active
diagnostics.
+ (Plus) Key
When viewing a setpoint screen, this key
will increase the temperature or pressure
value of the setpoint. When working with
a status menu, it will add the current
status display to the custom menu. When
viewing the setup or service test screens,
it will increase setpoints or toggle choices
on or off at each edit point.
- (Minus) Key
When viewing the setpoint screen, the
minus key will decrease the temperature
or pressure value of the setpoint. When
viewing the setup or service test screens,
it will decrease setpoints or toggle
choices on or off at each edit point. When
viewing the custom menu, pressing the (Minus) key will remove the status screen
from the custom menu. When viewing
diagnostics screens it has no function.
PREVIOUS Key
Pressing the PREVIOUS key causes the
LCD to scroll backwards through the
various displays for each menu. At
displays with multiple edit points, it
moves the cursor from one edit point to
another.
NEXT Key
Pressing the NEXT key causes the LCD to
scroll forward through the various
displays for each menu. At displays with
multiple edit points it moves the cursor
from one edit point to another.
cause the display to go to the top level
status display and, if the unit is shutdown,
will cause the unit to begin operation in
the appropriate mode no matter what
menu level is currently displayed. If the
current display is an editable display, the
AUTO key will confirm the desired edit.
STOP Key
Pressing the STOP key will cause the unit
to transition to the stop state. If the
current display is editable, pressing the
STOP key will cancel the desired edit.
TEST START Key (SERVICE)
Pressing this key while viewing any
screen in the SERVICE Mode menu will
start the service test. When viewing
status, setup, setpoint, and diagnostics
screens, it has no function.
CUSTOM Key
The Custom menu is a status menu that
can be customized to contain frequently
used screens. The Custom menu can only
contain five status screens. To create the
Custom menu, press the STATUS key,
followed by the NEXT key (this brings up
the initial status screen). Press the NEXT
key until a screen appears that you would
like to add to the CUSTOM menu. To add
a screen to the Custom menu, press the +
(Plus) key. Once the Custom menu is
programmed, access it by pressing the
CUSTOM key. To remove a status screen
from the Custom menu, press the
CUSTOM key. Press the NEXT key until
the screen you want to remove appears.
Press the - (Minus) key to remove the
screen.
Unit Operation Keys
AUTO Key
Pressing the AUTO key at any time will
10PKG-SVP01B-EN
Figure P-GI-2. Human interface keypad.
General
InformationProgramming
General Status Display
Anytime the self-contained unit is
powered up or when the STATUS, AUTO,
or STOP keys are pressed, the unit
mounted HI will display one of four
general status display screens. This will
allow the user to navigate through a set
of menus and submenus to provide or
access various monitoring, setup, and
configuration information. The HI will not
display screens that the unit is not
configured for.
1. Unit “Off” or “Stopped”
If at power up the unit is not running, the following display will appear. When this
screen displays, the only functional keys are the menu keys (STATUS, SETPOINTS,
DIAGNOSTICS, SETUP, CONFIGURATION, and SERVICE MODE), the AUTO key, the
CUSTOM key, and the STOP key.
If the unit has entered an operating state (running), the following display will appear.
When this screen displays, the only functional keys are the menu keys (STATUS,
SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, AND SERVICE MODE), the
AUTO key, the CUSTOM key, and the STOP key.
Function in Operation
O/A Flow (CCFM)
Unoccupied
(Blank if supply fan off or no VCM)
If at power up the unit is running
following display will appear on the human interface LCD screen.
and has entered a ventilation override mode, the
VO Mode in Operation
(A, B, C, D, E)
Ventilation Override Mode
4. No Configuration
If at power-up the unit has not been programmed with the necessary configuration
data for normal unit operation, the following display will appear at the human interface
LCD screen. When this screen displays, the only functional key is the CONFIGURATION key.
Note: This screen will only appear when the RTM has been field replaced. Refer to the
Configuration Menu section on page 63.
______
Trouble Indicator
(Blank)
(Diagnostics)
12PKG-SVP01B-EN
General
InformationProgramming
Factory Presets
The UCM controlled unit has many
operating functions that are preset at the
factory, but may be modified to meet the
specific job requirements. Tables P-GI-2,
P-GI-3, P-GI-4, and P-GI-5 identify each
adjustable unit function and the value
assigned to it. The tables also provide a
Table P-GI-2. Control Parameters Setup.
Default system modeAuto 32
Demand limit definition for coolingNone 33
Demand limit definition for heatingNone 34
Economizer minimum position (without IGV or VFD)*15% 59
Economizer minimum position with IGV @ 0%*15% 59
Economizer minimum position with IGV @ 100%*10% 59
Morning warmup typeFull 33
Power-up start time delay0 seconds 34
Supply air low limit*50 F 59
Supply air temperature deadband for cooling*8 F 59
Supply air temperature deadband for heating*4 F 57
Supply air temperature O/A reset start temp cooling90 F 35
Supply air temperature O/A reset end temp cooling70 F 35
Supply air temperature O/A reset start temp heating10 F 36
Supply air temperature O/A reset end temp heating60 F 36
Supply air temperature reset type coolingnone 34
Supply air temperature reset type heatingnone 35
Supply air temperature zone reset start temp cooling72 F 35
Supply air temperature zone reset end temp cooling69 F 35
Supply air temperature zone reset start temp heating65 F 36
Supply air temperature zone reset end temp heating68 F 36
Supply air temperature reset maximum amount cooling5 F 35
Supply air temperature reset maximum amount heating10 F 36
Unit Address1 32
Unit ControlLocal 32
Note: Press the SETUP or SETPOINTS* key to adjust.
space for recording field modifications. If
these factory presets match your
application requirements, simply press
the AUTO key on the HI to begin unit
operation (after completing the Pre-Start
and Start-Up procedures in the appropriate Installation, Owner, and Diagnostic
manual). If your application requires
page beside the function, press the
designated function menu key, then press
and hold the NEXT or PREVIOUS key until
its screen appears. Once the proper
screen appears, simply follow the
programming instructions given below
the applicable screen in this manual.
different settings, turn to the referenced
Factory PresetChanged to:Reference Page #
PKG-SVP01B-EN13
General
InformationProgramming
Use Table P-GI-3 to reference factory default setpoints and keep track of setpoint adjustments at start-up. Make necessary adjustments using the setpoint key on the HI.
Table P-GI-3. Default Setpoint Setups.
Factory PresetChanged to:Reference Page #
Daytime warmup - initiate67 F 57
Daytime warmup - terminate71 F 57
Low ambient compressor lockout (std. units)50 F 60
Supply air temp - cooling55 F 57
Supply air temp - heating100 F 57
Unoccupied zone temp - cool85 F 58
Unoccupied zone temp - heat60 F 58
Unoccupied zone temp - MWU72 F 58
Use Table P-GI-4 to reference function setups and keep track of start-up adjustments. Make necessary adjustments using the setup
key on the HI.
Table P-GI-4. Function (Enable/Disable) Setups.
Factory PresetChanged to:Reference Page #
Compressor lead/lagDisable 34
Daytime warmupDisable 32
Morning warmupEnable 33
Supply air temperingDisable 33
Unoccupied economizerEnable 37
Unoccupied heatingEnable 33
Unoccupied mechanical coolingEnable 33
14PKG-SVP01B-EN
General
InformationProgramming
Use Table P-GI-5 to reference module factory setups and keep track of setpoint adjustments. Make necessary adjustments using the
setup key on the HI.
Table P-GI-5. Module Defaults.
Factory PresetChanged to:Reference Page #
GBAS input/output assignments
GBAS input/outputnot assigned 46
Information format
Text displaysEnglish 32
Unit displaysEnglish 32
Reference Enthalpy25 btu/lb. 59
RTM alarm output assignmentsany active diagnostic 47
Sensor source selection for:
Daytime warmupRTM zone temp 40
Monitor Specified Temp. InputRTM zone temp 42
Morning warmupRTM zone temp 41
Unoccupied zone controlRTM zone temp 41
Zone resetRTM aux temp 41
Setpoint source selection for:
Cooling supply air tempdefault 60
Heating supply air tempdefault 61
Morning warmupdefault 62
Unoccupied zone coolingdefault 61
Unoccupied zone heatingdefault 61
Actuator setup:
Direct/reverse actiondirect acting 51-55
Max stroke time150 seconds 51-55
Max voltage10 VDC 51-55
Min voltage2 VDC 51-55
Coil frost cutout temperature30 F 34
Condenser temperature control band:
Temporary low limit suppression10 F 39-40
Upper limit120 F 39-40
Low limit80 F 39-40
Condenser temperature:
Efficiency check point105 F 40
Low ambient control point90 F 40
Control algorithm tuning parametersN/A 56
Max IGV position occupied100% 37
Temperature input offset for:
Heat morning warmup0 F 48
Return air0 F 48
RTM zone temperature0 F 48
RTM aux. temperature0 F 48
Outdoor air0 F 48
Ventilation override definitionN/A 43-45
PKG-SVP01B-EN15
General
InformationProgramming
Password Protected Screens
Some of the operating displays on the
human interface LCD screen are intended for access by qualified users only,
and require a password to change. The
following screens display the various
programming sections that require a
password to view or modify preset
operating parameters. The password for
each screen is a different series of +
(Plus) or - (Minus) key strokes in a
predefined sequence. Following are the
password protected screens and passwords to access them.
The following screen will appear if the PASSWORD is not entered within approximately 15 seconds.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen displays.
Configuration is Password Protected
Please Enter Password: ___________
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen displays.
Ventilation Override Mode _________
Enter Pass word To Lock D e finition:
1. Press the + or - keys in this sequence ( + - - + ) to lock each VO mode.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
Diagnos tic R e s e t is Pas s word Protected
Please Enter Password: ___________
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
16PKG-SVP01B-EN
Diagnostic Log is Password Protected
Please Enter Password: ___________
1. Press the + or - keys in this sequence ( - + + -) to access this restricted screen.
2. Press the ENTER key to confirm the password and lock the definitions.
3. Press the NEXT key until the following screen displays.
Programming
OCCUPIED OA DMPR 0% DIAGNOSTICS
RTM Supply Airflow Proving: FLOW
Active Supply Air Pressure 2.0 IWC
Active Supply Air Pressure 2.0 IWC
WSM Water Pump Re la y Status: OFF
Active Wa ter Flow Indication Flow
STATUS
STATUS Menu
The STATUS menu allows the user to
view various setpoints, operating
conditions (such as temperature and
humidity levels), and unit component
status (such as fan, compressor, heater,
and economizer operation).
STATUS screens in this section are
examples only. Pressing the + (Plus) key
while viewing any of the status display
screens will add that screen to the
CUSTOM menu. When a status screen
displays for 30 minutes without a key
being pressed, the LCD screen will revert
to the general operating status display. If
this happens, press the STATUS key
again to return to the status menu.
Following are sample status screens that
can be viewed by pressing the STATUS
key.
Note: Some of the screens in this section
may not be visible on your HI since they
are applicable only for particular unit
options.
Press the STATUS key to enter into the
status menu. The “STATUS MODE”will
automatically return to the power-up
screen after 30 minutes, if no keys are
pressed.
Note: The range for all temperature inputs
is –40 to 200 F. “ERR” will appear if the
temperature is out of range.
STATUS Menu Screens
VAV OA FLOW 350 .0 C C FM SUPPLY FAN ON
1. Pressing the NEXT key will display the following screen.
General System Status Submenu
Pres s ENTER to View Da ta in This Subme nu
1. Pressing the NEXT key will bypass this section.
RTM Supply Fan Re la y : OFF
Possible values: Fan = On, Off
Airflow = Flow, No Flow
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed
screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom
menu. Refer to the custom menu for the creation and maintenance of customized
menus.
4. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD only)
IGV/VFD Cmd 30 %
Possible values: Increasing to 0-100%
(On units without IGV or VFD only)
Decreasing 100 to 0%
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Possible values: Pump Status = Off, On
Waterflow = Flow, No flow
1. Pressing the NEXT key will display the following screen.
17
Programming
Stage 1 OFF Stage 2 OFF Stage 3 OFF
OA Flow 35 0 .0 C C FM OA D a m pe r Pos 0 %
C02 Level 1512 PPM OA Damper Pos 0 %
Pres s ENTER to View Da ta in This Subme nu
(On units with electric heat only)
Electric Heat ENABLED
Possible values: Off, On
Note: Two or three-stage electric heat is a field-provided option.
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
Hydronic Heat ENABLED 0 %
Low Air Temp Limit OK
Possible values: Hydronic Heat = Enabled, Disabled
Valve position = 0-100% open
Low temp air = OK , tripped
1. Pressing the NEXT key will display the following screen.
(On units with VCM module or Traq™ damper option only)
Active Min OA Flow Setpoint 342.0 CC FM
STATUS
Possible values: Unit Airflow = 0 to maximum unit airflow
1. Pressing the NEXT key will display the following screen.
(On units with VCM module and CO2 reset enabled)
Active Min OA Flow Setpoint 342.0 C C FM
Possible values: Unit Airflow = 0 to maximum unit airflow
1. Pressing the NEXT key will display the following screen.
(On units with VCM module and preheat enabled)
OA Preheat Output Control: ON
Possible values: On, Off
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Co mpre ss o r Sta tu s Sub me n u
18
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Compress or Rela y K 1 1 OFF
Enabled
Possible values: K11 = Off, On, Locked, Disabled, Enabled
Disabled by:Compressor ProtectionFrost Protection
Contactor FailureTracer Summit® Lockout
Low Pressure CutoutMinimum Off Time
Bad Cond Temp SensorLow Ambient Lockout
Demand LimitVentilation Override
Low Ent Cond water Temp
1. Pressing the NEXT key will display the following screen.
(On units with manifolded refrigerant circuits)
Compress or Rela y K 1 2 OFF
Enabled
Possible values: K11 = Off, On, Locked, Disabled, Enabled
Note: On models SCWF/SIWF and SCRF/SIRF units, K12 is the “B” compressor on units
with manifolded refrigerant circuits and “C” compressor on all units with independent
refrigerant circuits. Check unit model number, digit 5 to determine which type circuit the
unit has.
STATUS
1. Pressing the NEXT key will display the following screen.
(On units with independent refrigerant circuits)
Compress or Rela y K 3 OFF
Enabled
Possible values: K3 = Off, On, Locked, Disabled, Enabled
Note: On models SCWF/SIWF, 35-80 tons, K3 is the “B” compressor.
1. Pressing the NEXT key will display the following screen.
(On model SCWF/SIWF, 60-80 ton units)
Compress or Rela y K 4 OFF
Enabled
Possible values: K4 = Off, On, Locked, Disabled, Enabled
Disabled by:Compressor ProtectionFrost Protection
Contactor FailureTracer Summit® Lockout
Low Pressure CutoutMinimum Off Time
Bad Cond Temp SensorLow Ambient Lockout
Demand LimitVentilation Override
Low Ent Cond Water Temp
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
19
Programming
Low Ambie nt Com p Loc k out Tem p: 32 F
Low Water Temp Com press or Lockout 34 F
Evap Tem p 7 5 .0 F Sat Cond Te m p 8 1 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Evap Tem p 7 2 .0 F Sat Cond Te m p 9 7 .0 F
Pres s ENTER to View Da ta in This Subme nu
Active Outside A ir Tempe rature 86.0 F
Possible values: Lockout Temperature = -20-80 F
1. Pressing the NEXT key will display the following screen.
On units all water-cooled units only)
(
WSM Ent Cond Wa ter Temp Input 65 .2 F
Possible values: Lockout Temperature = 0-99 F
1. Pressing the NEXT key will display the following screen.
Compressor Module Ckt 1
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 2
STATUS
1. Pressing the NEXT key will display the following screen.
(
On all SCWF/SIWF 35-80 ton units only)
Compress or Module Ckt 3
1.Pressing the NEXT key will display the following screen.
(
On all SCWF/SIWF 60-80 ton units only)
Compress or Module Ckt 4
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside or airside economizer only)
Eco n o mizer Statu s Subme n u
20
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Outside Air Dam pe r Pos: 10 %
WSM Entering Water Temperature: 60 F
Water Econ Bypas s Pos: 10 %
Outside Air Dam pe r Pos: 0 %
ECEM Return Air Enthalpy 34.0 B TU /LB
ECEM Return Air Tempe rature 78.0 F
(
On units with a waterside economizer only)
Water Economizing: DISABLED
Possible values:Economizer = Disable, Enable
Water econ position = opening to/closing to 0-100%
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside economizer or condenser only)
WSM Mixe d A i r Tempe rature: 68 F
1. Pressing the NEXT key will display the following screen.
(
On units with a waterside economizer and condenser only)
Possible values:Water econ position = opening to/closing to 0-100%
1. Pressing the NEXT key will display the following screen.
STATUS
On units with an airside economizer only)
(
Air Economizing: DISABLED
Possible values:Economizer = Disable, Enable
Outside air = opening to/closing to 0-100%
1. Press the NEXT key until the following screen is displayed.
On units with an airside economizer and comparative enthalpy only)
(
Active Outside A ir Enthalpy 12.0 B TU/LB
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible values:
On units with an airside economizer only)
(
Active Outside A ir Tempe rature 86.0 F
10-99 BTU/LB
PKG-SVP01B-EN
21
Programming
ECEM Return Air Humidity 6 2 %
Controlling Setpoint Status Submenu
Pres s ENTER to View Da ta in This Subme nu
HI (KEYPAD) SETPOINT MENU Is 5 5 F
HI (KEYPAD) SETPOINT MENU Is 1 0 0 F
Initiate: 67 F is Te rminate: 71 F
(
On units with an airside economizer only)
Active Outside A ir Humidity 3 0 %
STATUS
Possible values:
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
(On all VAV units only)
Active Supply Air Cooling STP From
Possible Values:HI (Keypad) Setpoint Menu
1. Pressing the NEXT key will display the following screen.
0-100%
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
22
(On all VAV units with hydronic heat only)
Active Su p p l y A i r H ea ti n g ST P F rom
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit
(On all VAV units with hydronic, electric, or external heat only)
Active Daytime Warmup Setpoints
Possible Values:HI (Keypad) Setpoint Menu
®
)
PKG-SVP01B-EN
Programming
RTM ZONE TEMP INPUT is 7 4 F
RTM ZONE TEMP INPUT is 1 0 0 F
RTM ZONE TEMP INPUT is 8 5 F
RTM ZONE TEMP INPUT is 6 0 F
Active Oc c upied Zone C ooling STP From
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat with daytime warmup
enabled only)
Active Oc c upied Zone H e a ting STP From
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
STATUS
Active U noc c upied Zone C o oling STP From
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Active U nocc upie d Zone H e a ting STP From
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
Setpoint Range:50-90 F
PKG-SVP01B-EN
23
Programming
HI (KEYPAD) SETPOINT MENU is 7 2 F
REMOTE MIN POS POT INPUT 342 .0 C FM
HI (KEYPAD SETPOINT MENU is 2 .0 IWC
High Limit: 40 IWC D e a dba nd: 0.5 IWC
Controlling Sens or Status Submenu
Pres s ENTER to View Da ta in This Subme nu
(On units with hydronic, electric, or external heat only)
Active Morning Warmup Setpoint From
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Input
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
ICS (Tracer Summit®)
Setpoint Range:50-90 F
1. Pressing the NEXT key will display the following screen.
(On units with VCM module only)
Active Min OA Flow Setpoint From
Possible Values:HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
Setpoint Range:0 to max unit airflow
1. Pressing the NEXT key will display the following screen.
STATUS
(On units with IGV or VFD only)
Active Supply Air Pressure STP From
Possible Values:HI (Keypad) Setpoint Menu
GBAS Module
1. Pressing the NEXT key will display the following screen.
On units with IGV or VFD only)
Active Supply Air Pressure Setpoints
Possible Values:High Limit = 1.6-4.7 IWC
Deadband = 0.1-2.0 IWC
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
24
PKG-SVP01B-EN
Programming
RTM ZONE TEMP INPUT is 5 0 .0 F
RTM ZONE TEMP INPUT is 8 2 .0 F
HI (KEYPAD) SETPOINT MENU Is 9 0 F
RTM ZONE TEMP INPUT is 7 5 .0 F
Active Supply A ir Temp Sens or Input From
Possible Values:RTM Supply Air Temp Input
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Active D a y time WU Te m p Sens or Input From
Possible Values:RTM Zone Temp Input
Sensor Range:-40 to 200 F
1. Pressing the NEXT key will display the following screen.
ICS (Tracer Summit®)
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM return Air Temp Input
ICS (Tracer Summit®)
STATUS
(On units with hydronic, electric, or external heat with DWU installed only)
Active Oc c upied Zone Te m p Sens or Input From
Possible Values:RTM Zone Temp Input
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM return Air Temp Input
ICS (Tracer Summit®)
Sensor Range:-40 to 200 F
1. Pressing the NEXT key will display the following screen.
Active U noc c Zone Te m p Sens or Input From
Possible Values:RTM Zone Temp Input
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM return Air Temp Input
ICS (Tracer Summit®)
Sensor Range:-40 to 200 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat with MWU enabled only)
PKG-SVP01B-EN
25
Programming
Active Morning WU Temp Sens or Input From
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values:RTM Zone Temp Input
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM return Air Temp Input
ICS (Tracer Summit®)
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Sensor Range:-40 to 200 F
Active Zone R e s e t Sensor Input From
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values:RTM Zone Temp Input
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
ICS (Tracer Summit
Sensor Range:-40 to 200 F
STATUS
®
)
Active OA Te m pe rature Sensor Input From
RTM OUTSIDE AIR TEMP INPUT is 86 .0 F
Possible Values:RTM Outside Air Temp Input
ICS (Tracer Summit
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Active Outside A ir Humidity Input From
OA HU MIDITY SENSOR INPUT is 3 0 %
Possible Values:O/A Humidity Sensor Input
ICS (Tracer Summit®)
Sensor Range:0-100%
1. Pressing the NEXT key will display the following screen.
(On units with IGV, VFD, or with the SAP sensor enabled)
Active Supply A ir Pres s Sens or Input From
RTM SA PRESSUR E INPUT is 2 .1 IWC
Possible Values:RTM SA Pressure Input
1. Pressing the NEXT key will display the following screen.
ICS (Tracer Summit®)
®
)
26
PKG-SVP01B-EN
Programming
Temp Sens or Input Being Monitored:
RTM ZONE TEMP INPUT is 8 2 .0 F
Possible Values:RTM Zone Temp Input
NSB Zone Sensor Setpoint Input
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
ICS (Tracer Summit®)
No sensor selected
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Sensor Range:-40 to 200 F
End o f Su b me n u (N EXT ) to En ter SETU P
Tempe rature Input Status Subme nu
Pres s ENTER to View Da ta in This Subme nu
STATUS
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM ZONE TEMP INPUT 8 2 .0 F
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM SUPPLY AIR TEMP INPUT 50.0 F
1. Pressing the NEXT key will display the following screen.
(On units with a NSB zone sensor installed)
Temp Measured By Sensor Connected To
NSB Panel Te m p Sens or Input 79.5 F
1. Pressing the NEXT key will display the following screen.
Temp Measured By Sensor Connected To
RTM AUX TEMP INPUT 62.0 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Temp Measured By Sensor Connected To
RTM OUTSIDE AIR TEMP INPUT 86.0 F
1. Pressing the NEXT key will display the following screen.
27
Programming
(On units with hydronic, electric, or external heat only)
Temp Mea s ured By Sens or Connec ted To
HEAT MODULE AU X TEMP INPUT 82.0 F
1. Pressing the NEXT key will display the following screen.
(On units with a VCM and OA preheater enabled)
Temp Mea s ured By Sens or Connec ted To
ECEM RETURN AIR TEMP INPUT 78.0 F
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM ENT WA TER TEMP INPUT 60.1 F
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM MIXED AIR TEMP INPUT 51 .7 F
STATUS
1. Pressing the NEXT key will display the following screen.
(On water-cooled units only)
Temp Mea s ured By Sens or Connec ted To
WSM ENT C ON D WA TER TEMP INPUT 64.9 F
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and O/A preheater enabled)
Temp Mea s ured By Sens or Connec ted To
VCM MODULE AUX TEMP INPUT 5 0 .0 F
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 1
Evap Tem p 7 5 .0 Sat Cond Te m p 8 1 .0 F
1. Pressing the NEXT key will display the following screen.
Compress or Module Ckt 2
Evap Tem p 7 2 .0 Sat Cond Te m p 8 7 .0 F
1. Pressing the NEXT key will display the following screen.
28
PKG-SVP01B-EN
Programming
(On models SCWF/SIWF 42-80 tons or SCRF/SIRF 50-60 tons only)
Compressor Module Ckt 3
Evap Tem p 7 2 .0 Sat Cond Tem p 87.0 F
1. Pressing the NEXT key will display the following screen.
(On models SCWF/SIWF 65-80 tons only)
Compressor Module Ckt 4
Evap Tem p 7 2 .0 Sat Cond Tem p 87.0 F
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Misc Input Status Submenu
Pres s ENTER to View Da ta in This Subme nu
STATUS
1. Pressing the NEXT key will display the following screen.
RTM Supply Airflow Proving Input: FLOW
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values:Flow, No Flow
(On units when minimum position pot is assigned to function)
RTM Rem ote Min Position Pot Input 0 %
Possible Values:0-100%
(On units with IGV or VFD, or units without IGV or VFD and supply air
pressure is present)
RTM Supply Air Press ure Input 2.1 IWC
(On units with an airside economizer only)
Active Outside A ir Humidity 3 0 %
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
Possible Values:0-100%
29
Programming
(On units with an airside economizer and comparative enthalpy only)
Active Outside A ir Humidity 3 0 %
ECEM Return Air Humidity 6 2 %
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
VCM Outside Air Flow Input 350.0 C C FM
Possible Values:0 to max unit airflow.
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
VCM CO2 Lev e l Input 1512 PPM
STATUS
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values:0-2000 PPM
(On water-cooled units with a water flow switch installed)
WSM Water Flow Switch Input Flow
Possible Values:Flow, No Flow
End of Subm en u (NEXT) to Enter SETUP
(On units with GBAS module)
GBAS 0 - 5VDC Module Status Submenu
Pres s ENTER to View Da ta in This Subme nu
30
PKG-SVP01B-EN
Programming
(On units with GBAS module)
GBAS 0 - 5VDC Module Input 1 0 .0 0 VDC
Ass ignm e nt: Not Ass igne d
Possible Values:The inputs 1, 2, 3, and 4 may be assigned to:
Occ Zone Cooling Setpoint
Occ Zone Heating Setpoint
Unocc Zone Cooling Setpoint
Unocc Zone Heating Setpoint
Space Static Pressure Setpoint
Supply Air Static Pressure Setpoint
Min O/A Flow Setpoint
1. Press the NEXT key to display GBAS 0-5 VDC inputs 2, 3, and 4.
2. Pressing the NEXT key will display the following screen.
(On units with GBAS module)
GBAS (0 - 5VDC) Demand Limit Input Status
OPEN
Possible Values:Open, Closed
1. Pressing the NEXT key will display the following screen.
Not Assigned
STATUS
(On units with GBAS module)
GBAS (0 - 5VDC) Module Re la y Output Status
Output 1 OFF
Possible Values:Open, Closed
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
31
SETUP Menu
The setup menu allows the user to input
unit control parameters; i.e., setpoint
source selection, sensor source selections, ventilation override definitions,
functions enable/disable, status, text
display (language), temperature display
(C or F), and system tuning parameters.
When a setup screen displays for 30
minutes without a key being pressed, the
LCD screen will revert to the appropriate
power-up display. If this happens, press
the SETUP key again to return to the
setup menu.
Note: Some of the screens in this section
may not be visible on your HI since they
are applicable only for specific unit options.
Press the SETUP key to begin viewing or
modifying the SETUP screens. Follow this
procedure when viewing a screen that
requires modification:
1. Press the + or - key until the proper
value displays.
2. Press the ENTER key to confirm your
choice.
3. Press the NEXT key to advance the
cursor.
4. Repeat steps 1 and 2 if there are
additional values on the same screen
that require changing.
Programming
SETUP
SETUP Menu Screens
Press the SETUP key to display the following screen(s).
Displa y Te x t in: ENGLISH LANGUA GE
Displa y U nits U s ing: ENGLISH NOTA TION
Factory Presets: Text and Units = English
Possible Values:Text = English, French, Spanish
Units = English, SI
1. Pressing the NEXT key will display the following screen.
(On units with a TCI module)
Unit Control: LOCA L
Unit Address: 31
Factory Presets:Control = Local
Address = 1
Possible Values:Unit Control = Local, ICS (Tracer Summit®)
Unit Address = 0-31
1. Pressing the NEXT key will display the following screen.
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with VFD and bypass)
Supply Fan VFD Mode: BYPASS
Factory Presets:Mode = Normal
Address = 1
Possible Values:Mode = Normal, Bypass
1. Pressing the NEXT key will display the following screen.
If Remote Pane l Mode Input Not Present:
System Mode: AUTO
1. Pressing the NEXT key will display the following screen.
1.Pressing the NEXT key will display the following screen.
32
Possible Values:System Mode = Off, Auto
Day time Wa rmup Function: DISABLED
Factory Preset:Disabled
Possible Values:Daytime Warmup Function = Enabled, Disabled
PKG-SVP01B-EN
Programming
(On units with hydronic or electric heat)
Morning Warmup Function: ENABLED
Morning Warmup Type : FULL C A PA CI TY
Factory Presets: Function = Enabled
MWU Type = Full Capacity
Possible Values:Function = Enabled, Disabled
MWU Type = Full Capacity, Cycling Capacity
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Supply Air Tempering Function: DISABLED
Warm Up Outside A ir Use d for Ventilation
Factory Presets:Function = Disabled
1. Pressing the NEXT key will display the following screen.
Possible Values:Function = Enabled, Disabled
(On cooling-only units)
Unocc Mech Cooling Function: ENABLED
SETUP
Factory Presets: Function = Enabled
Possible Values:Function = Enabled, Disabled
OR
(On units with hydronic, electric, or external heat)
Unocc Mech Cooling Function: ENABLED
Unocc Heating Function: ENABLED
Factory Presets: Cooling and Heating Function = Enabled
Possible Values:Cooling and Heating Function = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Preheater Output Control : ENABLED
Activa te If Preheat Temp B e low Setpoint
Factory Presets: Control = Enabled
Possible Values:Control = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
Dem a nd Lim it De finition:
Cooling: 100 %
Factory Presets: None
1. Pressing the NEXT key will display the following screen.
Possible Values:Cooling = None, 50%, or 100%
PKG-SVP01B-EN
33
Programming
(On units with hydronic or electric heat)
Dem a nd Lim it De finition:
Cooling: 100 % H e a ting: 100 %
Factory Presets: None
Possible Values:Cooling /Heating = None, 50%, or 100%
1. Pressing the NEXT key will display the following screen.
Compress or Lead/La g Func tion: DISABLED
Vary Sta ging Order to Distribute Runtim e
Factory Presets:Function = Disabled
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Coil Frost Cutout Temperature: Shut Off
Compress ors If Evap Tem p Is B e low: 30 F
Factory Presets: Temp = 30 F
Possible Values:Temp = 25-35 F
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
VAV Control Functions Subme nu
Pres s ENTER to Re v ie w or Adjust
1. Pressing the NEXT key will display the following screen.
(On units without heat)
Supply Air Temp Reset Type:
Cooling: ZONE
Factory Presets: None
Possible Values:Cooling = None, Zone, OA
1. Pressing the NEXT key will display the following screen.
34
PKG-SVP01B-EN
Programming
Maximum A m ount of Res e t Applie d: 5 F
Maximum A m ount of Res e t Applie d: 5 F
(On units with hydronic heat)
Supply Air Temp Re s e t Type :
Cooling: ZONE Hea ting: ZONE
Factory Presets: None
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values:Cooling/Heating = None, Zone, OA
(On units when zone cooling reset is selected)
Supply Air Temp Zone
Start Temp: 72 F End Te m p: 69 F
Possible Values:Cooling/Heating = Zone, OA
Res e t For Cooling:
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
SETUP
Supply Air Temp Outside Air
Start Temp: 90 F End Tem p: 70 F
Possible Values:Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Zone
Possible Values:SAT = Zone, OA
Reset (Zone) = 72
Reset (OA) = 72
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Outside Air
Possible Values:SAT = Zone, OA
Reset Zone = 72
Reset OA = 72
1. Pressing the NEXT key will display the following screen.
Reset For Cooling:
Res e t For Cooling:
Res e t For Cooling:
PKG-SVP01B-EN
35
Programming
Start Temp: 10 F End Tem p: 60 F
Start Temp: 65 F End Tem p: 68 F
(On units with outside air heating reset selected)
Supply Air Temp Outside A ir
Factory Presets: Start = 10 F, End = 60 F
Possible Values:Start OA Temp = 73
End OA Temp = 74
1. Pressing the NEXT key will display the following screen.
(On units with zone air heating reset selected)
Supply Air Temp Zone
Factory Presets: Start = 65 F, End = 68 F
Possible Values:Start OA Temp = 211
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp OA R e s e t For Heating:
Maximum A m ount of Res et Applie d: 1 0 F
Reset For Heating:
End OA Temp = 212
SETUP
Res e t For Heating:
Possible Values:SAT Temp = Zone, OA
Zone Reset = 75
OA Reset = 75
1. Pressing the NEXT key will display the following screen.
(On units with outside air heating selected)
Supply Air Temp ZONE Reset For Heating:
Maximum A m ount of Res et Applie d: 1 0 F
Possible Values:SAT Temp = Zone, OA
Zone Reset = 75
OA Reset = 75
1. Pressing the NEXT key will display the following screen.
VAV Box Max Stroke Time: 0 Min
Factory Presets: 6 Min
1. Pressing the NEXT key will display the following screen.
Possible Values:0-10
36
PKG-SVP01B-EN
ProgrammingSETUP
(On units with IGV or VFD)
Max Occ upie d IGV/VFD Com m a nd: 100 %
Factory Presets: 100%
1. Pressing the NEXT key will display the following screen.
1.Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
Possible Values:0-100%
End o f Su b me n u (N EXT ) to En ter SETU P
(On units with an airside or waterside economizer)
Economizer Control Functions Subme nu
Pres s ENTER to Re v ie w or Adjust
(On units with an airside and waterside economizer)
Economizer Priority
Choose Whic h Econom izer Stages Up First
Possible Values:Waterside Econ, Airside Econ
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Unocc Water Economizer Function: ENABLED
Factory Presets: Enabled
Possible Values:Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Unocc Air Economizer Function: ENABLED
Factory Presets: Enabled
Possible Values:Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Disable WS Econ If Difference Between MA
Temp and Ent Water Temp Less Than 4.0 F
PKG-SVP01B-EN
1. Pressing the NEXT key will display the following screen.
37
Programming
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Water Flow Control Setup Submenu
Pres s ENTER to Re v ie w or Adjust
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Periodic Water Purge Function: ENABLED
Interval: 1 Hr Duration: 1 Min
Possible Values:Enabled, Disabled
Interval = 1-999 Hrs
Duration = 1-9 Min
1. Pressing the NEXT key will display the following screen.
SETUP
(On all water-cooled units and all units with a waterside economizer)
Water-Flow Init Time D e la y : 1 Min
Time To Establis h Wa ter Flow Before Diag
Possible Values:0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and all units with a waterside economizer)
Temp Stablization Time D e la y : 1 Min
Water Flow Time For Valid Temp Re a dings
Possible Values:0-20 Min
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Head Pressure Control Inactive Min: 1 0 %
Hea d Pressure Control Active Min: 30 %
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
38
PKG-SVP01B-EN
Programming
(On units with waterside economizer)
Water Economizer Min Position: 10 %
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On water-cooled units with waterside economizer)
Select Water Flow Control Required For
Water Pump System: Variable/Minimize
Possible Values:Constant/Maximize
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Hea d Pre ss u re Ctrl Se tu p Su b me n u
Press ENTER to Review or Adjust
Variable/Minimize
SETUP
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Cond Tem p C ontrol Point: 90 F
Possible Values:80-100 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Pres et Va l u e to Mi n i f Con d W ate r B elo w
Hea d Press Value Preset Tem p Lim it: 90 F
Possible Values:0-99 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Tem p C ontrol Band
Lower Limit: 80 F Upper Limit: 120 F
Factory Presets: Lower = 80 F
Upper = 120 F
Possible Values:Lower = 70-90 F
Upper = 110-130 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
39
Programming
(On all air-cooled units)
Cond Tem p C ontrol Band
Temporary Low Limit Suppression: 10 F
Factory Presets: 10 F
Possible Values:0-20 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp
Efficiency Check Point: 105 F
Factory Presets: 105 F
Possible Values:95-115 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp
Low Ambie nt Control Point: 90 F
SETUP
Factory Presets: 90 F
Possible Values:80-100 F
1. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Sensor Source Selections Submenu
Sensor Source Sele c tions Subme nu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with electric, hydronic, or external heat and supply air temperature
control)
For Daytime Wa rmup Tem p C trl, Use Sens or
Connec ted To: RTM ZONE TEMP INPUT
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
40
PKG-SVP01B-EN
Programming
(On all units except those with supply air temperature control without IGV
or VFD)
For Occupied Zone Te m p C trl, Use Sensor
Connec ted To: RTM ZONE TEMP INPUT
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Unoccupied Zone Tem p C trl, Use Sens or
Connec ted To: RTM ZONE TEMP INPUT
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
SETUP
(
On units with electric, hydronic, or external heat only)
For Morning Warmup Temp Ctrl, Use Sensor
Connec ted To: RTM ZONE TEMP INPUT
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Zone Reset Function, Use Sensor
Connec ted To: RTM ZONE TEMP INPUT
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
41
Programming
(On units with Traq™ dampers only)
For Outside Air Preheat Ctrl, Use Sensor
Connec ted To: VCM MODULE AUX TEMP INPUT
Possible Values:VCM Module Aux Temp Input
WSM Mixed Air Temp Input
1. Pressing the NEXT key will display the following screen.
Monitor Specific Tem p Input, Us e Sensor
Connec ted To: RTM ZONE TEMP INPUT
Factory Presets: RTM Zone Temp Input
Possible Values:RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
No Sensor Selected
1. Pressing the NEXT key will display the following screen.
SETUP
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Outside Air Ventilation Setup
(On units with a VCM or airside economizer)
Outside Air Ventilation Setup Subm e nu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer and IGV or VFD)
OA Flow Com pe ns a tion Function: DISABLED
Use Fix e d OA D a m pe r Minimum Position
Possible Values:Enabled, Disabled
Enabled 2nd line = “OA Damper Min Pos Depends on IGV/VFD Pos”
Disabled 2nd line = “Use Fixed OA Damper Minimum Position”
1. Pressing the NEXT key will display the following screen.
42
PKG-SVP01B-EN
ProgrammingSETUP
(On units with a VCM)
OA Flow CO2 Reset Function: ENABLED
Possible Values:Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
OA Flow CO2 Reset Function: ENABLED
CO2 Start: 800 PPM CO2 Max: 1000 PPM
Possible Values:Enabled, Disabled
CO2 Start = 0-1900 PPM
CO2 Max = 100-2000 PPM
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer with Traq™ damper)
TRAQ D a m pe r Quantity: 1
TRAQ D a m pe r Size: 28 Inches
Possible Values:Quantity = 1-12
Size = 0, 13, 16, 20, 24, or 28
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Flow Ca libration Data:
Gain: 1.0 Offset: 0.0 CC FM
Factory Presets: Gain = 1.0
Offset = 0.0
Possible Values:Gain = 0.0-1.5
Offset = -25.0-25.0
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
Ventilation Override Definitions
(On units with a VOM)
Ventilation Override D e finitions
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
43
Programming
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
Ventilation Override D e finition Mode A
(On units with a VOM and IGV or VFD)
Supply Fan ON
Factory Presets: Refer to definitions on page 5.
Possible Values:On, Off
1. Pressing the NEXT key will display the following screen.
(On units with a VOM and airside or waterside economizer)
Outside Air Dam pe rs OPEN
Factory Presets: Refer to definitions on page 5.
Possible Values:Open, Closed
1. Pressing the NEXT key will display the following screen.
(On units with a VOM and electric or hydronic heat)
Hea t OFF
Factory Presets: Refer to definitions on page 5.
Possible Values:Off, In Control
1. Pressing the NEXT key will display the following screen.
SETUP
(On units with a VOM)
VAV Box Re la y D EENERGIZED
Factory Presets: Refer to definitions on page 5.
Possible Values:Energized, Deenergized
1. Pressing the NEXT key will display the following screen.
(On units with a VOM installed and OA preheater function enabled)
OA Preheater State IN C ON TR OL
Factory Presets: Refer to definitions on page 5.
Possible Values:In Control, Off
1. Pressing the NEXT key will display the following screen.
(On units with a VOM
VO Relay ENERGIZED
Factory Presets: Refer to definitions on page 5.
Possible Values:Energized, Deenergized
1. Pressing the NEXT key will display the following screen.
)
44
PKG-SVP01B-EN
Programming
Ventilation Override D e finition Mode A
Ventilation Override Mode A Is Loc k e d
GBAS 0 - 5VDC Module I/O A s s ignm e nts
SETUP
(On units with a VOM
Enter Pass word to Lock De finition:
Factory Presets: Refer to definitions on page 5.
Possible Values:+ (Plus), - (Minus)
1. Pressing the NEXT key will display the following screen.
Note: After lock a MODE (by entering the password), the display for that MODE becomes
“reporting” only and the definition cannot be changed unless the VOM is replaced. After
entering the password, press the NEXT key to scroll through the previous screens to
confirm selected choices for each mode as follows below.
(On units with a VOM and VO mode locked)
Supply Fan
Factory Presets: Refer to definitions on page 5.
1. Pressing the NEXT key will display the following screen.
(On units with a VOM)
Ventilation Override Mode B
Supply Fan
)
Follow the preceding steps used to program MODE “A” to program MODES “B,” “C,”
“D,” and “E” as needed.
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
GBAS Module I/O Assignments
(On units with a GBAS)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
45
Programming
GBAS (0 - 5VDC) Ana log Input 1 A s s ignm e nt
GBAS (0 - 5VDC) Output 1 Alarm Ass ignm e nts
(On units with a GBAS)
NOT ASSIGNED
Factory Presets: None
Possible Values:Not Assigned, Occupied Zone
Cooling Setpoint, Unoccupied Zone
Cooling Setpoint, Occupied Zone
Heating Setpoint, Unoccupied Zone
Heating Setpoint
SA Static Pressure Setpoint
SA Heating Setpoint
SA Cooling Setpoint
Min OA Flow Setpoint
1. Press the + or - key until the proper selection displays for the number 1 assignment.
2. Press the ENTER key to confirm this choice. Only one input definition can be assigned
to each input and it cannot be duplicated.
3. Press the NEXT key to advance to the number 2 input assignment screen and repeat
steps 1 and 2 for assignments 3 and 4.
4. Pressing the NEXT key will display the following screen.
(On units with a GBAS)
SETUP
Press ENTER to Review or Adjust
Factory Presets: Output 1 = Dirty Filters
Output 2 = Compressor Trip - Ckt 1, 2, 3, or 4
Low Pressure Control Open
Low Pressure Control Open- Ckt 1, 2, 3, or 4
Contactor Fail
Contactor Fail - Ckt 1, 2, 3, or 4
Output 3 = Heat Fail
Output 4 = Supply Fan Failure
Output 5 = Any Active Diagnostic
Possible Values:Refer to the list of active diagnostics assigned to each of
the five output definitions in the “Diagnositic Menu”
section on page 72. It also can be one of the VOM outputs:
supply fan/VFD bypass enabled or high CO2.
1. Press the NEXT key to bypass this section.
2. Press the + or - key until the proper selection displays for the number 1 assignment.
The plus key will assign all diagnostics and the minus key will allow diagnostic
selection.
3. Press the ENTER key to confirm this choice. If “yes” was assigned to the output
assignment, the output 2 assignment screen will display. Repeat step 1 for each
remaining output. If “no” was assigned, only one output assignment can be assigned
to each output assignment and it cannot be duplicated. Once the output diagnostics
are defined, press the NEXT key to advance to the number 2 output assignment
screen. Repeat steps 1 and 2.
4. Pressing the NEXT key will display the following screen.
Note: Assigning “yes” to a GBAS output definition means that if the assigned diagnostic
is present, the out assigned to it will energize.
46
PKG-SVP01B-EN
Programming
RTM Alarm Output Diagnostic A s s ignm e nts
Ass ign D ia gnos tic to RTM Ala rm Output ?
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
SETUP
RTM Alarm Output Diagnostic Assignment Screens
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
Any A c tive D ia gnos tic (No)
Factory Presets: Any Active Diagnostic
Possible Values:Refer to the list of active diagnostics that can be assigned
to each GBAS output definition in the “Diagnostic Menu”
section on page 72.
1. Press the ENTER key, then the NEXT key to display the possible diagnostics that may
be assigned to the RTM alarm output definition.
2. Press the + (plus) key to assign “yes” to the output definition or - (minus) key to
assign “no” to the output definition.
3. Press the ENTER key to confirm each selection.
Note: Assigning “yes” to an alarm output definition means that if the assigned diagnostic
is present, the RTM alarm output will energize.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
47
Programming
SETUP
Temperature Input Calibration
The following calibration and offset
screens allow sensor calibration, when
necessary.
For example, if using the MWU sensor
and you detect a difference between the
actual measured room temperature and
the corresponding measured sensor
value, the sensor needs calibration. Using
the temperatuare input calibration screen
for MWU heat, program the error
amount into the Temperature Input Offset
field to calibrate the sensor.
To change offset values on a particular
screen:
1. Press the plus or minus key until the
correct value appears in the screen.
2. Press the ENTER key to confirm your
choice. If you’ve made an error, press
the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the
next screen, OR
a. if no further changes are required and
you want to exit back to view the unit
operating status, press the STATUS key
once, OR
b. if you want to remain in the tempera-
ture input calibration submenu, press
the SETUP key once and it will return
you to the beginning of that particular
submenu, OR
c. if you want to exit to another submenu
in the SETUP menu, press the SETUP
key twice. Then press the NEXT key to
scroll through the SETUP submenu
choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that
key once, then press the NEXT key to
scroll through those screens.
Temperature Input Calibration Screens
(Applicable to All Units)
Calibration and Offset Submenu
Pres s ENTER to Re v ie w or Adjust
1. Press the NEXT key to bypass this section or press the ENTER key to view the
following screens.
Tempe rature Calibration Offset For
RTM Zone Tem pe rature Input 0.0 F
Factory Preset:0.0 F
Possible Values:Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
Tempe rature Calibration Offset For
RTM Aux Te m pe rature Input 0.0 F
Factory Preset:0.0 F
Possible Values:Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
Tempe rature Calibration Offset For
RTM Outside Air Tempe rature Input 0.0 F
Factory Preset:0.0 F
Possible Values:Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
(On units with electric or hydronic heat only)
Tempe rature Calibration Offset For
Hea t Module Aux Te m p Input 0.0 F
Factory Preset:0.0 F
Possible Values:Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
48
(On units with comparative enthalpy installed)
Tempe rature Calibration Offset For
ECEM Return Air Tempe rature Input 0.0 F
Factory Preset:0.0 F
Possible Values:Plus or Minus 5.0 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Entering Water Temp Input 0.0 F
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Mixe d A ir Temp Input 0.0 F
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
WSM Ent Cond Water Temp Input 0.0 F
SETUP
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 1 Sat Cond Te m p Input 0.0 F
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 2 Sat Cond Te m p Input 0.0 F
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units and/or units with a waterside economizer)
Temperature Calibration Offset For
Ckt 3 Sat Cond Te m p Input 0.0 F
PKG-SVP01B-EN
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
49
Programming
(On all water-cooled units and/or units with a waterside economizer)
Tempe rature Calibration Offset For
Ckt 4 Sat Cond Te m p Input 0.0 F
Factory Preset:0.0 F
Possible Values:0.0-5.0 F
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (NEXT) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
SETUP
50
PKG-SVP01B-EN
Programming
Max Stroke Tim e 3 0 Sec
Max Voltage 10 .0 VDC
Direct/Rev e rse A c t DIR ECT A C TIN G
SETUP
Device Characteristic Setup
Definitions
To change device characteristic values
on a particular screen:
1. Press the plus or minus key until the
correct value appears in the screen.
2. Press the ENTER key to confirm your
choice. If you’ve made an error, press
the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the
next screen, OR
a. if no further changes are required and
you want to exit back to view the unit
operating status, press the STATUS key
once, OR
b. if you want to remain in the Device
Characteristic Setup Definitions
submenu, press the SETUP key once
and it will return you to the beginning of
that particular submenu, OR
c. if you want to exit to another submenu
in the SETUP menu, press the SETUP
key twice. Then press the NEXT key to
scroll through the SETUP submenu
choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that
key once, then press the NEXT key to
scroll through those screens.
Device Characteristic Setup Screens
(Applicable to units as noted)
Device Characteristics Setup Definitions
Pres s ENTER to Re v ie w or Adjust
1. Press the NEXT key to bypass this section or press the ENTER key to view the
following screens.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Factory Preset:150 Seconds
Possible Values:1-255 Seconds
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Min Voltage 2 .0 VDC
Factory Preset:2.0 VDC
Possible Values:0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
PKG-SVP01B-EN
Factory Preset:10.0 VDC
Possible Values:0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Actuator Setup OA Dampe r
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economize r
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
51
Programming
(On units with a waterside economizer)
Actuator Setup Water Economizer
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Direct/Rev e rse A c ting Direct Ac ting
SETUP
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with water-cooled units)
Actuator Setup Water Econ By pa s s
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Max Voltage 10 .0 VDC
52
Factory Presets: 10.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On units with a waterside economizer)
Actuator Setup Water Econ By pa s s
Direct/Rev e rse A c ting DIR ECT A CT IN G
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Max Stroke Tim e 1 5 0 Sec
Factory Presets: 150 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Min Voltage 2 .0 VDC
SETUP
Factory Presets: 2.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC
Possible Values:0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD)
Actuator Setup IGV/VFD Cm d
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Max Stroke Tim e 1 5 0 Sec
PKG-SVP01B-EN
Factory Presets: 150 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
53
Programming
(On units with hydronic heat)
Actuator Setup Hydronic
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC
Possible Values:0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC
Possible Values:0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Actuator Setup Hydronic
Direct/Rev e rse A c t DIR ECT A C TIN G
SETUP
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Max Stroke Tim e 6 0 Sec
Factory Presets: 60 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Min Voltage 2 .0 VDC
Factory Presets: 2.0 VDC
Possible Values:0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Max Voltage 10 .0 VDC
54
Factory Presets: 10.0 VDC
Possible Values:0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
(On air-cooled units with low ambient damper)
Actuator Setup Num 1 Low Am bie nt
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Max Stroke Tim e 6 0 Sec
Factory Presets: 60 Sec
Possible Values:1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Min Voltage 2 .0 VDC
SETUP
Factory Presets: 2.0 VDC
Possible Values:0.0-9.9 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Max Voltage 10 .0 VDC
Factory Presets: 10.0 VDC
Possible Values:0.1-10.0 VDC
1. Pressing the NEXT key will display the following screen.
(On air-cooled units with low ambient damper)
Actuator Setup Num 2 Low Am bie nt
Direct/Rev e rse A c t DIR ECT AC TIN G
Factory Presets: Direct Acting
Possible Values:Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
End o f Su b me n u (N EXT ) to En ter SETU P
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
55
Programming
SETUP
Control Algorithm Tuning Parameters
(Applicable to all Units)
Control Algorithm Tuning Parameters
Press ENTER to Review or Adjust
1. Do not make any adjustments to these settings before contacting your Trane
Company representative.
2. Pressing the NEXT key will display the following screen.
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
56
PKG-SVP01B-EN
Programming
SETPOINT
SETPOINT Menu
The SETPOINT menu allows you to
designate default zone temperature
setpoints, supply air and space pressure
setpoints, and low ambient compressor
lockout setpoints.
These setpoints are active (in use) for the
“Setpoint Source Selection” designated
as “DEFAULT” for these inputs.
When a setpoint screen displays for 30
minutes without a key being pressed, the
HI display will revert to the general
operating status screen. If this happens,
press the SETPOINT key again to return
to the setpoint menu.
Note: Some of the screens displayed in
this section may not be visible on your HI
since they are applicable only for particular
unit options.
Pressing the SETPOINT key will allow you
to view or modify unit setpoints.
To change setpoint values on a particular
screen:
1. Press the plus or minus key until the
correct value appears in the screen.
2. Press the ENTER key to confirm your
choice. If you’ve made an error, press
the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the
next screen, OR
a. if no further changes are required and
you want to exit back to view the unit
operating status, press the STATUS key
once, OR
b. if you want to remain in the Setpoint
submenu, press the SETPOINT key
once and it will return you to the
beginning of that particular submenu,
OR
c. if you want to exit to another submenu
in the SETPOINT menu, press the
SETPOINT key twice. Then press the
NEXT key to scroll through the SETPOINT submenu choices, OR
d. if you want to exit to another menu,
such as CONFIGURATION, press that
key once, then press the NEXT key to
scroll through those screens.
SETPOINT Menu Screens
(Applicable for all units except as noted)
Default Supply Air Temp Setpoint(s)
Cooling: 55 F
Factory Presets: 55 F
Possible Values:40-90 F
1. Pressing the NEXT key will display the following screen.
Default Supply Air Temp Setpoint(s)
Cooling: 67 F H e a ting: 71 F
Factory Presets: 100 F
Possible Values:Cool = 40-90 F
Heat = 40-180 F
1. Pressing the NEXT key will display the following screen.
Supply Air Temperature Deadband
Cooling: 8.0 F
Factory Presets: 8.0 F
Possible Values:Cool = 4-20 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
Supply Air Temperature Deadband
Cooling: 8.0 F H e a ting: 4.0 F
Factory Presets: Cooling = 8.0 F
Heating = 4.0 F
Possible Values:Cooling= 4-20 F
Heating = 2-10 F
1. Pressing the NEXT key will display the following screen.
Defa u l t Da ytime W arm u p Setpo i n ts
Initiate: 67 F Terminate: 71 F
Factory Presets: Heat = 71 F
Cool = 74 F
Possible Values:Heat = 50-90 F
Cool = 52-92 F
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
57
Programming
Tempe rature Cooling Setpoint By: 1.5 F
Cool: 85 F H e a t: 60 F Morn Warmup: 72 F
(On units with hydronic, electric, or external heat only)
Default Occ upie d Zone Setpoint(s)
Cool: 74 F H e a t: 71 F
Factory Presets: Heat = 71 F
Cool = 74 F
Possible Values:Heat = 50-90 F
Cool = 52-92 F
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints.
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
When Economizer Cooling, Re duc e Zone
Factory Presets: 1.5 F
Possible Values:0.0-3.0 F
1. Pressing the NEXT key will display the following screen.
SETPOINT
(On cooling-only units)
Default Unoc c upie d Zone Te m p Setpoint(s)
Cool: 85 F
Factory Presets: 85 F
Possible Values:50-90 F
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Default Unoc c upie d Zone Te m p Setpoint(s)
Factory Presets: Cool = 85 F
Heat = 60 F
MWU = 72 F
Possible Values:Cool = 52-90 F
Heat = 50-88 F
MWU = 50-90 F
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints.
Also, the morning warmup cannot be lower than the heating setpoint.
1. Pressing the NEXT key will display the following screen.
58
PKG-SVP01B-EN
ProgrammingSETPOINT
(On units with an airside economizer)
Refe re n ce Entha l py :
When OA Enthalpy is B e low: 25 B TU /LB
Factory Presets: 25 BTU/LB
Possible Values:19-28 BTU/LB
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Supply Air Low Limit - Modulate Econom izer
Toward Min Pos if SA Tem p B e low: 50 F
Factory Presets: 50 F
Possible Values:40-65 F
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer)
Default OA D a m pe r Min Position: 15 %
Ena b l e A i r Ec o n
Factory Presets: 15%
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer, OA cfm compensation, and IGV or VFD
or on units without an economizer, with IGV or VFD, and a VCM)
Default OA D a m pe r Min Position: 15 %
with IGV/VFD C om m a nd a t Minimum (0 % )
Factory Presets: 15%
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer, OA cfm compensation, and IGV or VFD
or on units without an economizer, with IGV or VFD, and a VCM)
Default OA D a m pe r Min Position: 10 %
with IGV/VFD C om m a nd a t Maxim um (10 0 % )
Factory Presets: 10%
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
Default Minimum OA Flow Setpoint: 40 CC FM
Min OA Flow Dea dba nd: 10 .0 C C FM
PKG-SVP01B-EN
Possible Values:Setpoint = 0-max unit airflow
Deadband = 5.0-20 CCFM
1. Pressing the NEXT key will display the following screen.
59
Programming
(On units with a VCM installed and preheat enabled)
Preheat Output ON If Preheat Temp Below
Prehe a t Ac tiva tion Tem pe rature: 35 F
Factory Presets: 35 F
Possible Values:35-75 F
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD. Also, on units with SAT control without air
volume control and supply air pressure sensor installed)
Default Supply Air Pressure: 1.5 IWC
High Limit: 4.0 IWC D e a dba nd: 0.5 IWC
Factory Presets: Setpoint = 1.5 IWC
High Limit = 4.0 IWC
Deadband = 0.5 IWC
Possible Values:Setpoint = 1.0-4.3 IWC
High Limit = 1.2-4.7 IWC
Deadband = 0.1-2.0 IWC
Note: The high limit setpoint cannot be adjusted below the parameters of the following
equation: The high limit = Deadband - 0.1 2
SETPOINT
1. Pressing the NEXT key will display the following screen.
Low Ambie nt Com p Loc k out Tem p: 50 F
Comp (s) OFF If OA Tem p B e low This Value
Factory Presets: 50 F
Possible Values:-20-80 F
1. Pressing the NEXT key will display the following screen.
Setpoint Source Selec tions Subme nu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
For Supply A ir Temp C ooling C ontrol, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
60
PKG-SVP01B-EN
Programming
(On units with hydronic or electric heat)
For Supply A ir Temp H e a ting Control, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
For Occ Zone Tem p C ooling C ontrol, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
For Occ Zone Tem p H e a ting Control, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
SETPOINT
PKG-SVP01B-EN
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
For Unocc Zone Te m p C ooling C ontrol, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
For Unocc ZoneTe m p H e a ting Control, Use
Setp o i n t F rom: H I (KEYPAD) SETPO I NT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
61
Programming
(On units with hydronic, electric, or external heat)
For Unocc ZoneTe m p H e a ting Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat)
For Morn in g W armu p T emp Cont rol , Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
NSB Zone Sensor Setpoint Input
1. Pressing the NEXT key will display the following screen.
SETPOINT
(On units with an airside or waterside economizer or VCM )
For Default OA Min Position, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
Remote Min Pos Pot Input
1. Pressing the NEXT key will display the following screen.
(On units with a VCM and GBAS)
For Min Outside A ir Flow Rate C trl, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD and GBAS)
For Supply A ir Pressure Control, U s e
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:HI (Keypad) Setpoint Menu
GBAS 0-5 VDC Module
1. Pressing the NEXT key will display the following screen.
62
End of Subm en u (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
CONFIGURATION
CONFIGURATION Menu
The self-contained unit has many
operating functions that are factory
preset. The following configuration
programming steps allow the user to
configure a replacement HI module for a
unit that is already in operation.
Refer to the unit model number on the
unit nameplate (on the control panel
door) while scrolling through the configuration screens. Certain digits of this alpha/
numeric model number provide information that must be entered at the HI for the
unit to operate properly.
Note: Some of the screens displayed in
this section are applicable only for particular options and are not visible unless those
options are installed on your unit.
Pressing the CONFIGURATION key will
allow you to view or modify unit setpoints.
To change setpoint values on a particular
screen:
1. Press the plus or minus key until the
correct value appears in the screen.
2. Press the ENTER key to confirm your
choice. If you’ve made an error, press
the CANCEL key to delete your entry.
To navigate to another screen:
1. Press the NEXT key to advance to the
next screen, OR
a. if no further changes are required and
you want to exit back to view the unit
operating status, press the STATUS key
once, OR
b. if you want to remain in the Setpoint
submenu, press the CONFIGURATION
key once and it will return you to the
beginning of that particular submenu,
OR
c. if you want to exit to another submenu
in the CONFIGURATION menu, press
the CONFIGURATION key twice. Then
press the NEXT key to scroll through
the CONFIGURATION submenu
choices, OR
d. if you want to exit to another menu,
such as SETPOINT key, press that key
once, then press the NEXT key to scroll
through those screens.
Configuration - Model Num D igit 1
Unit Type C om m e rcial Self-Contained
Possible Values:Commercial Self-Contained
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 3
Condenser Medium WATER COOLED CONDENSER
Possible Values:Water Cooled Condenser
Air Cooled Condenser
None - No Condenser
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 4
Dev e lopm e nt Type SIGNA TU R E SERIES
Possible Values:Signature Series
Modular Series
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 5
Refrig Ckt Config INDEPENDENT
Possible Values:Independent
Manifolded
Note: Manifolded piping is only available on Signature Series units, 30 tons and larger.
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 27
Water Economizer INSTALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units or units with a waterside economizer)
Configuration - Model Num D igit 29
Water Piping INTERMEDIA TE PIPING
Possible Values:Intermediate Piping
Basic Piping
None - No Piping
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
63
Programming
(On all water-cooled units and water flow switch or units with a waterside
economizer and water flow switch)
Configuration - Model Num D i git 29
Water Flow Switch IN STALLED
CONFIGURATION
Possible Values:Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 20
Hea ting Type H YDR ON IC
Possible Values:Hydronic
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 6, 7
Unit Capa c ity 7 2
Possible Values:20-80
Note: The possible value for unit capacity is dependent upon the unit size (tons).
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 23
Power Exhaust NON E
Not Installed
Electric
None
External
64
Possible Values:None
100% with Statitrac
50%/100% without Statitrac
Note: This option is currently not available on commercial self-contained units, but this
screen still displays.
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28
Air Economizer INSTALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
Programming
Configuration - Model Num D igit 9
Air Temp/Vol Ctrl SA C TR L WITH IGV/VFD
Possible Values:SA Control with IGV/VFD
Zone Control
No IGV/VFD or SA Control
No IGV/VFD
1. Pressing the NEXT key will display the following screen.
(On units with SA Control and IGV/VFD installed)
Configuration - Model Num D igit 9
Supply Fan VFD Bypass INSTALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28
Compa rative Enthalpy IN STALLED
CONFIGURATION
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 33
GBAS 0 - 5 VDC Module IN STALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 33
Ventilation Override (VOM) INSTALLED
Possible Values:Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D igit 28
Ventilation Ctrl TR A Q D A MPERS
Possible Values:Traq™ Dampers
1. Pressing the NEXT key will display the following screen.
Not Installed
Standard Dampers
PKG-SVP01B-EN
65
Programming
Single Compressor Module (SCM) 1.00
Multiple Compressor Module (MCM) 4.0 9
Configuration - Model Num D i git 33
TCI4 C om m unic a tions Module IN STALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
Configuration - Model Num D i git 33
Rem ote H um a n Interface IN STALLED
Possible Values:Installed
Not Installed
1. Pressing the NEXT key will display the following screen.
(On all units unless the RTM has changed)
Unit Model Number
Possible Values:Model Number
1. Pressing the NEXT key will display the following screen.
CONFIGURATION
Software Revision Number Report:
RTM 9.13
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report:
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report:
1. Pressing the NEXT key will display the following screen.
1. Pressing the NEXT key will display the following screen.
(On units with a VOM)
Software Revision Number Report:
Ventilation Override (VOM) 1.00
1. Pressing the NEXT key will display the following screen.
66
PKG-SVP01B-EN
Programming
(On units with comparative enthalpy)
Software Revision Number Report:
Exhaust/Com p Enthalpy Module 8 .0 4
1. Pressing the NEXT key will display the following screen.
(On units with hydronic or electric heat)
Software Revision Number Report:
Hea t Module 1.0 0
1. Pressing the NEXT key will display the following screen.
Software Revision Number Report:
Unit Human Interface 14.07
1. Pressing the NEXT key will display the following screen.
(On units with a RHI)
Software Revision Number Report:
Rem ote H um a n Interface 1 1 .0 4
CONFIGURATION
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
Software Revision Number Report:
Ventilation Control (VCM) 1.12
1. Pressing the NEXT key will display the following screen.
(On units with a TCI)
Software Revision Number Report:
TCI4 C om m unic a tions Module 1 .0 0
1. Pressing the NEXT key will display the following screen.
PKG-SVP01B-EN
67
Programming
SERVICE MODE
SERVICE MODE Menu
The SERVICE MODE key allows the user
to input operating parameters for unit
operation during a service test. Depending on the particular test being conducted,
the user will cycle through all unit outputs
(i.e.; compressors, fans, dampers,
heaters) and selectively turn them on or
off. After designating the operating status
for each unit component, the user will
designate the “TEST START” delay time.
When a service mode screen displays for
30 minutes without a key being pressed,
the HI screen will revert to the general
operating status display. If this happens,
press the SERVICE MODE key to return to
the service menu.
Note: Some of the screens displayed in
this section are applicable only for particular options and may not be visible on your
unit.
To operate the unit in test mode, press
the SERVICE MODE key to enter the
service mode menu. Scroll through
system outputs to selectively turn them
“on” or “off.”
To change service mode values on a
particular screen:
1. Press the plus or minus key until the
correct value appears in the screen.
2. Press the ENTER key to confirm your
choice. If you’ve made an error, press
the CANCEL key to delete your entry.
3. Press the NEXT key to advance the
cursor to another field within a screen.
To navigate to another screen:
1. Press the NEXT key to advance to the
next screen, OR
a. if no further changes are required and
you want to exit back to view the unit
operating status, press the STATUS key
once, OR
b. if you want to remain in the Setpoint
submenu, press the SERVICE MODE
key once and it will return you to the
beginning of that submenu, OR
c. if you want to exit to another submenu
in the SERVICE MODE menu, press the
CONFIGURATION key twice. Then press
the NEXT key to scroll through the
CONFIGURATION submenu choices, OR
d. if you want to exit to another menu,
such as SETPOINT key, press that key
once, then press the NEXT key to scroll
through those screens.
68
(On units without IGV/VFD)
Supply Air Controls
Supply Fan OFF
Possible Values:On, Off, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
Supply Air Controls
Supply Fan OFF IGV/VFD Cond 35 %
Possible Values:On, Off, Auto
IGV/VFD Cond = 0-100%
1. Pressing the NEXT key will display the following screen.
(
On water-cooled units or units with water-cooled condenser)
Water Pump Relay State Off
Possible Values:On, Off
1. Pressing the NEXT key will display the following screen.
VAV Box Re la y
RTM Alarm Output
Possible Values:VAV Box - 0 = Occ
Drive Max, Auto - 1 = Unocc
Alarm Output = Off, On
1. Pressing the NEXT key will display the following screen.
(
On water-cooled units or units with water-cooled condenser)
Water Econ Control Valve C om m a nd 0 %
Water Econ Bypas s Valv e C om m a nd 0 %
Possible Values:0-100%
1. Pressing the NEXT key will display the following screen.
(On air-cooled units, 20 - 35 Tons)
Condenser Fan Outputs
1A OFF 1 B OFF
Factory Presets: Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
Possible Values:On, Off, Auto
PKG-SVP01B-EN
ProgrammingSERVICE MODE
(On air-cooled units, 40-60 Tons)
Condens e r Fan Outputs
1A OFF 1 B OFF 2 A OFF 2 B OFF
Factory Presets: Off
Possible Values:On, Off, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed
Ckt 1 0 %
Factory Presets: 0 %
Possible Values:0-100%, Auto
1. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed
Ckt 1 0 % C k t 2 0 %
Factory Presets: 0 %
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
1. Press the NEXT key again to display the following screen.
Possible Values:0-100%, Auto
Compressor Relays:
K11 OFF K 3 OFF K 1 2 OFF K 4 OFF
Factory Presets: Off
Possible Values:On, Off
(On units with hydronic heat)
Hydronic He a t
Actuator 0 %
Factory Presets: 0 %
Possible Values:0-100%, Auto
PKG-SVP01B-EN
69
Programming
(On units with electric heat)
Heat Stages
Stage Off
Factory Presets: 0 %
Possible Values:0-100%, Auto
Note: Only single stage electric heat is available factory installed.
1. Press the NEXT key again to display the following screen.
(On units with an airside economizer)
OA Damper Pos 0 %
Factory Presets: OA Damper = 0%
Possible Values:OA Damper = 0-100%
1. Press the NEXT key again to display the following screen.
(On units with VFD and bypass)
Supply Fan Bypass Relay: NORMAL
SERVICE MODE
Possible Values:Normal, Bypass
1. Press the NEXT key again to display the following screen.
(On units with VOM)
Ventilation Override Module Output Rela y
OFF
Factory Presets: Off
Possible Values:On, Off
1. Press the NEXT key again to display the following screen.
(On units with VCM)
OA Preheater State OFF
Factory Presets: Off
Possible Values:On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
70
PKG-SVP01B-EN
ProgrammingSERVICE MODE
(On units with GBAS)
GBAS 0-5 VDC Module Relay Outputs
#1 OFF # 2 OFF # 3 OFF # 4 OFF # 5 OFF
Factory Presets: Off
Possible Values:1, 2, 3, 4, 5 = On, Off
1. Press the NEXT key again to display the following screen.
Status/Annunc Tes t Sys On (Blink ing)
Hea t: OFF Cool: OFF Service: OFF
Factory Presets: Off
Possible Values:Heat = On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
Start Test In 5 Sec onds
Pres s TEST START To Be gin, STOP To Halt
Cool = On, Off
Service = On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
PKG-SVP01B-EN
71
Programming
DIAGNOSTICS
DIAGNOSTICS Menu
The DIAGNOSTICS menu allows the user
to view diagnostics that result from
system failures within the unit. There are
two lists where diagnostics reside; the
active list, and the diagnostic event log.
Use the active list for viewing all active
diagnostics and clearing manually
resetable diagnostics. If any active
diagnostics are present, they will display
after pressing the DIAGNOSTICS key.
Active manual diagnostics can be cleared
in batch form at the unit mounted Human
Interface. When an active diagnostic is
manually or automatically cleared, it is
removed from this buffer. Automatically
resetting diagnostics cannot be reset by
the HI. To clear the diagnostic, you must
correct the condition that caused the
diagnostic first.
The word “MORE” will display on all
screens if more than one diagnostic
exists, except for the last diagnostic.
Upon reaching the last diagnostic, the
word “MORE” disappears. Pressing the
NEXT key at this point causes the display
to advance to the first diagnostic in the
diagnostic event log.
The diagnostic event log screens allow
the user to view the past 20 diagnostics.
They will display after scrolling through
the active list or after pressing the
DIAGNOSTICS key when no active
diagnostics are present. Diagnostics in
this log are stacked in inverse chronological order, with the first diagnostic screen
being the most recently reported
diagnostic.
One the following screens will display first when the DIAGNOSTIC key is pressed.
Diagnos tic Menu ---- Info
No Active Diagnostics (NEXT) History Log
OR
Press CANCEL to Clear All Active Manual
Diagnostics, or Press NEXT to View
1. Pressing the CANCEL key to clear the diagnostics will prompt the following screen.
Diagnostic Reset Is Password Protected
Please Enter Password: ________________________
Factory Presets: N/A
Possible Values:+ (Plus), - (Minus)
1. Press the + (Plus) and/or - (Minus) keys to enter the password.
2. Press the ENTER key to confirm. When the correct password is entered, the following screen will display.
The following screens will display sequentially.
Resetting Active Manual Diagnostics
Sending Res e t Re ques t
Res e tting Active Manua l D ia gnos tics
Updating Unit Data, Please Wait
Active D ia gnos tic ---- Info
Please Wait, Unit Is In Reset Mode
OR
Pressing the NEXT key to view the diagnostics will prompt the following screen if a
MANUAL RESET failure has occurred.
Active D ia gnos tic ---- Manua l R e s e t
______________________________ More
72
Possible Values:Emergency Stop
Supply Fan Failure
Low Pressure Control Open - Ckt 1, Ckt 2, Ckt 3, Ckt 4
Compressor Trip - Ckt 1, Ckt 2, Ckt 3, Ckt 4
Low Air Temp Limit Trip
Manual Reset SA Static Pressure Limit
Compressor Contactor Fail - Ckt 1, Ckt 2, Ckt 3, Ckt 4
Note: The word MORE will appear on the screen if more than one failure has occurred.
PKG-SVP01B-EN
Programming
OR
Active Diagnostic ---- Auto Reset
______________________________ More
Possible Values:Failure for the Following
RTM ZoneHeat Aux Temp
Supply Air TempUnocc Zone Cool Setpt
RTM Aux. TempUnocc Zone Heat Setpt
OA TempSupply Air Press Setpt
Mode InputSpace Static Pres Setpt
Occ Zone Cool SetpointSpace Pressure
Occ Zone Heat SetpointReturn Air Temp
Supply air PresRA Humidity
OA HumidityAuto Reset SA Static Pres Limit
SCM CommunicationEvap Temp - Ckt 1, 2, 3, 4
MCM CommunicationHeat Module Commun.
ECEM CommunicationCond Temp - Ckt 1, 2, 3, 4
TCI CommunicationGBAS Module Communication
Tracer
Unit HI CommunicationVOM Communication
Sup Air Temp Cool SetptSup Air Temp Heat Setpt
NSB Panel Zone TempCO2 Sensor
VCM Aux TempVelocity Press
VCM CommunicationWSM Communication
Ent Cond Water TempEnt Water Temp
WSM Mixed Air TempWater Flow
DIAGNOSTICS
®
CommunicationNSB Panel Communication
OR
Pressing the NEXT key to view the diagnostics will prompt the following screen if an
“information only” failure has occurred.
Active D ia gnos tic ---- Info
______________________________ More
Possible Values:Heat Fail
Dirty Filter
Ventilation Override Mode A, B, C, D, or E
RTM Data Storage Error
Note: Activation of any VOM mode can be viewed within the “Active Diagnostic” screen.
Viewed or Not Viewed
Active or History
Manual
Auto
Info
or any diagnostic listed under the previous screens
associated with the diagnostic type, including VOM
activated mode
Press the CANCEL key to clear the diagnostics and prompt the following screen.
Possible Values:+ (Plus) and - (Minus)
1. Press the + (Plus) or - (Minus) keys to enter the password.
2. Press the ENTER key to confirm. After entering the correct password, the following
screen will display.
DIAGNOSTICS
Please Wait, Updating Diagnostic Log
Possible Values:Manual, Auto, or Info
If the DIAGNOSTIC LOG is empty when the CANCEL key is pressed, the following
screen will display.
Active D ia gnos tics ---- Info
Diagnos tic B uffer Is Already Empty!
Press the AUTO or STOP key to return to the top level status screen.
Possible Values:Manual, Auto, or Info
74
PKG-SVP01B-EN
Programming
DIAGNOSTICS
Failure Modes
When any condition results in the unit’s
inability to perform a normal function, it
is said to have entered a failure mode.
There are two types of failure modes.
1. An “Analog input out of range” failure
mode.
This failure mode occurs when a
sensing device such as a zone temperature sensor or a humidity sensor
begins to transmit information that is
outside its allowable range.
2. A “Fault recognition by input logic”
failure mode.
This failure mode occurs when the
UCM receives information that does
not “make sense” or does not conform
to its predefined logic.
Diagnostics
There are three types of diagnostics:
1. Informational
Does not affect machine operation
2. Automatic Reset
Affects machine operation but returns
to normal when diagnostic condition no
longer exists
3. Manual Reset
Affects machine operation and must be
reset at the HI or by cycling power to
unit for normal operation to resume.
To troubleshoot diagnostics, reference
Installation, Owner, and Diagnostic
the
Manual
SVX01A-EN
units and
Modular Series units.
that ships with the unit:
ships with Signature Series
SCXG-SVX01A-EN
ships with
SCXF-
PKG-SVP01B-EN
75
Programming
Index
Index
Symbols
+ (Plus) Key 10
- (Minus) Key 10
A
acronyms 4
active diagnostic 72, 73
active setpoint 5
actuator setup 15
AUTO key 10, 11, 13
C
CANCEL key 10
coil frost cutout 15
comparative enthalpy module 7
compressor lockout 5
compressor modules 7
compressor protection switch 5
condenser temperature control band 15
CONFIGURATION 11, 12
CONFIGURATION key 9
CONFIGURATION menu 63
control algorithm tuning parameters
15, 56
control band 5
control point 5
CUSTOM key 10
CUSTOM menu 10, 17
factory presets 13
failure modes 75
function (enable/disable) setups 14
G
GBAS 6, 7
GBAS input/output 15
GBAS module I/O assignments 45
general status display 11
generic building automation system
module 7
glossary 5
H
heat module 6, 7
HI 2, 7, 9 - 12
human interface 2, 7, 9 - 12
I
information format 15
interprocessor communications board 7
IOD 2
IPCB 4, 7
L
literature change history 2
low ambient compressor lockout 5
low entering condenser water temperature 5
low entering water temperature compressor lockout 5
M
MCM 6, 7
menu keys 9, 11
module defaults 15
modules 7
MORE 72
N
NEXT key 10
no configuration 7, 12
O
outside air ventilation setup 42
P
password 72
password protected screens 16
points list 6
PRESSURIZE sequence 8
PREVIOUS key 10
programming the unit 2, 9
PURGE sequence 8
PURGE with duct pressure control
sequence 8
R
reference enthalpy 5, 15
remote human interface 9
reset amount maximum 5
reset end temperature 5
reset start temperature 5
RHI 9
RTM 6, 7,
RTM alarm output assignments 15
RTM alarm output diagnostic assignment
screens 47
S
SCM 6, 7
sensor source selection 15, 40
SERVICE MODE menu 68
SETPOINT menu 57
setpoint source selection 15
setpoints 14, 57
SETPOINTS key 9
SETUP key 9
SETUP menu 32
STATUS key 9
STATUS menu 17
STOP key 10, 11
supply air pressure 5
supply air tempering 5
T
TCI 7
temperature input calibration 48
temperature input offset 15
TEST START 68
TEST START key 10
Trane communications interface module
7
U
UCM 7, 9, 13
unit off 7
UNIT OFF sequence 8
unit on 7
unit operation keys 10
unit status 7, 9
V
ventilation override 7, 8
ventilation override definition 15
ventilation override definitions 43
VOM 6, 7, 8
VOM active 12
76
PKG-SVP01B-EN
Programming
Index
PKG-SVP01B-EN
77
The Trane Company
A Division of American Standard Inc.
www.trane.com
For more information contact
your local Trane office or
e-mail us at comfort@trane.com
An American Standard Company
Literature Order Number
File Number
Supersedes
Stocking Location
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design
and specifications without notice.
PKG-SVP01B-EN
PL-UN-PKG-SVX01B-EN 4-00
PKG-SVP01A-EN
La Crosse - Inland
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.