Trane SCXG-SVX01B-EN User Manual

Installation, Operation, & Maintenance
TM
IntelliPak Commercial Self-Contained
Modular Series, 20-35 tons
“JO” and later design sequence
Models:
SCRG -020, -025, -030, -032 SIRG -020, -025, -030, -032
March 2008
SCXG-SVX01B-EN
Introduction
About This Manual Literature Change History
Use this manual for commercial self­contained models SCWG, SIWG, SCRG, and SIRG. This is the second or “B” revision of this manual. It provides specific installation, operation, and maintenance, instructions for “JO” and later design sequences. The “JO” design sequence includes the addition of 407c refrigerant option and VFD change from Square D 58 to the Trane TR-1. Also, this literature contains changes in the filter sizes and quantities for some unit sizes. For previous design sequences, contact your local Trane representative.
Hazard Identification
Warnings and cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING
Indicates a potentially hazardous situation, which could result in death or serious injury if not avoided.
CAUTION
Indicates a potentially hazardous situation, which may result in minor or moderate injury if not avoided. Also, it may alert against unsafe practices.
NOTICE
Indicates a situation that may result in equipment or property-damage-only accidents.
WARNING
Grounding Required!
Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.
Sample Warnings and Cautions
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regard­ing the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may result in equipment damage.
Common HVAC Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.
BAS = Building automation systems CFM = Cubic-feet-per-minute CKT. = Circuit CV = Constant volume CW = Clockwise CCW = Counterclockwise E/A = Exhaust air ECEM = Exhaust/comparative enthalpy module F/A = Fresh air GBAS = Generic building automation system HGBP = Hot gas bypass HI = Human Interface
HVAC = Heating, ventilation and air conditioning IGV = Inlet guide vanes I/O = Inputs/outputs IOD= Installation/owner/ diagnosticmanual IPC = Interprocessor communications IPCB = Interprocessor communications bridge LH = Left-hand MCM = Multiple compressor module MWU = Morning warmup NSB = Night setback O/A = Outside air psig = Pounds-per-square-inch, gauge pressure R/A = Return air RH = Right-hand RPM = Revolutions-per-minute RTM = Rooftop module S/A = Supply air SCM = Single circuit module SZ = Single-zone (unit airflow) LCI-I communications module UCM = Unit control modules VAV = Variable air volume VCM = Ventilation control module VOM = Ventilation override module w.c. = Water column WSM = Waterside module ZSM = Zone sensor module
Special Note on Refrigeration Emissions
World environmental scientists have concluded that ozone in our upper atmosphere is being reduced due to the release of CFC fully halogenated compounds.
Trane urges all HVAC service personnel to make every effort to prevent any refrigerant emissions while installing, operating, or servicing equipment. Always conserve refrigerants for continued use.
© 2008 Trane All rights reserved SCXG-SVX01B-EN
Contents
Cross reference to related publications/information:
• Product Catalog, PKG-PRC003-EN, Modular Series Commercial Self-Contained
• IntelliPak• Self-Contained Programming Guide, PKG-SVP01B-EN
• Remote Air-Cool-Condenser Installation, Owner, and Diagnostic Manual, CXRC­SVX01B-EN
Installation …………………………........…....…6
general information …………………………………………6 pre-installation considerations… …………………………11 dimensions & weights ………………………………...…19 mechanical specifications …………………………………30 electrical requirements ……………………………………33 pre-startup requirements …………………………………35
programming ………………………………….……………57
startup …………………………………………………….…67
Operation ………………………………………70
general information ………………………………………70 sequence of operation ………………………………….…84
Maintenance ……………………………………91
maintenance procedures ………………………………92 troubleshooting ………………………………………..…105 diagnostics ………………………………………………..106
SCXG-SVX01B-EN 3
Features and Benefits
Refrigerant Handling Procedures
Environmental Accountability Policy
Trane urges that all HVAC servicers to make every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC, and HFC refrigerants to the atmosphere. Always act in a responsible manner to conserve refrigerants for continued usage even when acceptable alternatives are available.
Recover and Recycle Refrigerants
Never release refrigerant to the atmosphere! Always recover and/or recycle refrigerant for reuse, reprocessing (reclaimed), or properly dispose if removing from equipment. Always determine the recycle or reclaim requirements of the refrigerant before beginning the recovery procedure. Obtain a chemical analysis of the refrigerant if necessary. Questions about recovered refrigerant and acceptable refrigerant quality standards are addressed in ARI Standard 700.
Refrigerant Handling and Safety
Consult the manufacturer’s material safety data sheet (MSDS) for information on refrigerant handling to fully understand health, safety, storage, handling, and disposal requirements. Use the approved containment vessels and refer to appropriate safety standards. Comply with all applicable transportation standards when shipping refrigerant containers.
Service Equipment and Procedures
To minimize refrigerant emissions while recovering refrigerant, use the manufacturer’s recommended recycling equipment per the MSDS. Use equipment and methods which will pull the lowest possible system vacuum while recovering and condensing refrigerant. Equipment capable of pulling a vacuum of less than 1,000 microns of mercury is recommended.
Do not open the unit to the atmosphere for service work until refrigerant is fully removed/recovered. When leak-testing with trace refrigerant and nitrogen, use HCFC-22 (R-22) rather than CFC-12 (R-
12) or any other fully-halogenated refrigerant . Be aware of any new leak test methods which may eliminate refrigerants as a trace gas. Perform evacuation prior to charging with a vacuum pump capable of pulling a vacuum of 1,000 microns of mercury or less. Let the unit stand for 12 hours and with the vacuum not rising above 2,500 microns of mercury.
A rise above 2,500 microns of mercury indicates a leak test is required to locate and repair any leaks. A leak test is required on any repaired area.
Charge refrigerant into the equipment only after equipment does not leak or
contain moisture. Reference proper refrigerant charge requirements in the maintenance section of this manual to ensure efficient machine operation. When charging is complete, purge or drain charging lines into an approved refrigerant container. Seal all used refrigerant containers with approved closure devices to prevent unused refrigerant from escaping to the atmo­sphere. Take extra care to properly maintain all service equipment directly supporting refrigerant service work such as gauges, hoses, vacuum pumps, and recycling equipment .
When cleaning system components or parts, avoid using CFC-11 (R-11) or CFC­113 (R-113). Use only cleaning-solvents that do not have ozone depletion factors. Properly dispose of used materials. Refrigeration system cleanup methods using filters and driers are preferred.
Keep abreast of unit enhancements, conversion refrigerants, compatible parts, and manufacturer’s recommenda­tions that will reduce refrigerant emis­sions and increase equipment operating efficiencies.
4 SCXG-SVX01B-EN
Features and Benefits
Modular Series Self-Contained Unit Components
Commercial self contained units are complete HVAC systems used in floor-by­floor applications. Units are easy to install because they feature a single point power connection, factory installed and tested controls, single water point connection, factory installed options, and an internally trapped drain connection. Modular self-contained units can ship as split-apart units for installation ease. Split­apart units ship with a dry nitrogen charge and require field refrigerant charging.
Units consist of multiple compressors, water-cooled condensers (water-cooled units only), an evaporator coil, dual forward curved fans, and control panel. Air-cooled units require a remote air­cooled condenser, model CXRC. The hermetically sealed 3-D scroll compressor motors utilize internal motor protection and time delays to prevent excessive cycling. Unit controls are either an electromechanical thermostat or microprocessor controls on the IntelliPak unit. See Figure I-GI-1 for a typical unit.
The hermetically sealed 3-D scroll compressor motors utilize internal motor protection and time delays to prevent excessive cycling.
The water-cooled condensers are shell and tube type with an internal subcooler. Condensers are available as mechani­cally or chemically cleanable. The evaporator fan is double width, double inlet and forward curved with a fixed pitch belt drive assembly. Frequency drives or inlet guide vanes are optional. Motor options include open drip proof, high efficiency, TEFC, or mill and chem spec.
All water-cooled units ship with a full refrigerant and oil charge. Air-cooled units ship with oil and a dry nitrogen holding charge and require field-piping
refrigerant connections to the air cooled condensing unit. Also, air-cooled units have two refrigerant circuits. Water­cooled units have four refrigerant circuits; which include a filter drier, pressure relief valve, liquid line service valve, sight glass/ moisture indicator, thermal expansion valve with a sensing bulb and external equalizing line, discharge line shrader valve, a suction line shrader valve, and high and low pressure cutout switches. Water-cooled units also include a liquid line service valve for each circuit.
For more detailed information, see the Owner’s section of this manual.
Figure I-GI-1. IntelliPak® commercial self-contained Modular Series unit.
SCXG-SVX01B-EN 5
general
Installation
Control Options
Units may be ordered with either conventional thermostat interface or IntelliPak IntelliPak Interface (HI) panel with two line by forty (40) character clear English display for easy operator interface to unit setup and control parameters. All basic setup parameters are preset from the factory.
Human Interface Panel
The HI is unit mounted and accessible without opening the unit’s front panel. It allows easy setpoint adjustment using the HI keypad. In addition, the HI displays all unit operating parameters and conditions in a clear language display, which can be configured for either English, French, or Spanish.
The optional remote human interface (RHI) will control up to four self-contained units, each containing an interprocessor communications bridge (IPCB). It has all the same features as the unit-mounted HI except for the service mode.
For more information on setpoint defaults and ranges and unit programming, see the
ming Guide, PKG-SVP01B-EN
ships with each unit.
IntelliPak
IntelliPakTM DDC Control provides “smart” unit control with safety features and control relays for pumps, dampers, etc. The Modular Series IntelliPak self­contained unit is controlled by a microelectronic control system that consists of a network of modules. These modules are referred to as unit control modules (UCM). In this manual, the acronym UCM refers to the entire control
TM
Direct Digital Control (DDC).
TM
controls include a Human
IntelliPak Self-Contained Program-
TM
DDC Control
. A copy
information
system network.
These modules perform specific unit functions using proportional/integral control algorithms. They are mounted in the unit control panel and are factory wired to their respective internal compo­nents. Each module receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request; i.e., economizing, mechanical cooling, heating, ventilation. See the Operation section of this manual for a detailed description of each module’s function.
Optional Controls
Optional controls include a disconnect switch, dirty filter switch, water flow switch (water-cooled only), supply air temperature reset, or external setpoint inputs. Daytime heating is available on units with electric, steam, or hot water heat control options. Morning warmup operation is available on all units.
The static pressure probe, zone night heat/morning warmup, supply air temperature reset sensor options ship separate inside the unit control panel for field installation. For more detailed information on the unit control options, see the Owner’s section of this manual.
Unit Nameplate
The unit nameplate identifies the unit model number, appropriate service literature, and wiring diagram numbers. It is mounted on the left end of the unit control panel.
6 SCXG-SVX01B-EN
Model Number Description
SCWG
Model Number Description
Each IntelliPak self-contained unit has a multiple character model number unique to that unit. To determine a unit’s specific options, reference the model number on the unit nameplate using the model number explanation below.
S C W G N 20 4 2 JO A B 2 10 085 B A 1 0 1 0 A A C F A 1 1 0 T 2 0
1 2 3 4 5 67 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Digit 1 - Unit Model
S = Self Contained
Digit 2 - Unit Type
C = Commercial I = Industrial
Digit 3 - Condenser Medium
W = Water-Cooled R = Remote Air-Cooled
Digit 4 - Development Sequence
G = Modular Series
Digit 5 - Refrigerant Circuit Configuration
N = Independent, R-22 Refrigerant R = Independent, 407C Refigerant
Digit 6, 7 - Unit Nominal Capacity
2 0 = 20 Tons (Water or Air Cooled) 2 5 = 25 Tons (Water or Air Cooled) 30 = 30 Tons (Water Cooled Only) 32 = 32 Tons (Air Cooled Only) 35 = 35 Tons (Water Cooled Only)
Digit 8 - Unit Voltage
6 = 200 Volt/60 Hz/3 ph 4 = 460 Volt/60 Hz/3 ph 5 = 575 Volt/60 Hz/3 ph
Digit 9 - Air Volume/Temp Control
1 = I-Pak & IGV and Supply Air Temp
Ctrl
2 = I-Pak & VFD and Supply Air
Temp Ctrl
3 = I-Pak & VFD w/ Bypass and
Supply Air Temp Ctrl
4 = I-Pak w/o Vol. CTRL, w/ Zone Temp
Cool
5 = I-Pak w/o Vol. CTRL, w/ Zone Temp
Heat/Cool
6 = I-Pak w/o Vol. CTRL, w/ Supply Air
Temp Ctrl
8 = Thermostat Interface
Digit 10, 11 - Design Sequence
JO= “J” Design
Digit 12 - Unit Construction
A = Vertical Discharge B = Vertical Discharge with Double Wall C = Horizontal Discharge D = Horizontal Discharge w/ Double
Wall
E = Vertical Discharge, Ship Separate F = Vertical Discharge w/ Double Wall,
Ship Separate G = Horizontal Discharge, Ship Separate H = Horizontal Discharge w/ Double
Wall, Ship Separate
Digit 13 - Plenum Type
B = Std Plenum w/ Factory Cut Holes C = Low Plenum w/ Factory Cut Holes E = Std Plenum w/ Field Cut Holes F = Low Plenum w/ Field Cut Holes H = Std Plenum Double Wall (Perf)
w/ Field Cut Holes J = Low Plenum Double Wall (Perf)
w/ Field Cut Holes L = Std. Plenum w/Factory Cut Holes,
Ship Separate M = Low Plenum with Factory Cut
Holes, Ship Separate P = Std Plenum w/ Field Cut Holes, Ship
Separate R = Low Plenum w/ Field Cut Holes,
Ship Separate U = Std Plenum Double Wall (Perf) w/
Field Cut Holes, Ship Separate V = Low Plenum Double Wall (Perf) w/
Field Cut Holes, Ship Separate 0 = Without Plenum
Digit 14 - Motor Type
1 = Std. Efficiency ODP 2 = Premium Eff. ODP 3 = Std. Efficiency Totally Enclosed
Digit 15, 16 - Motor HP
05 = 5 HP Motor 07 = 7.5 HP Motor 10 = 10 HP Motor 15 = 15 HP Motor 20 = 20 HP Motor 25 = 25 HP Motor
Digit 17, 18, 19 - Fan RPM
085 = 850 rpm 090 = 900 rpm 095 = 950 rpm 100 = 1000 rpm 105 = 1050 rpm
110 = 1100 rpm 115 = 1150 rpm 120 = 1200 rpm 125 = 1250 rpm 130 = 1300 rpm 135 = 1350 rpm 140 = 1400 rpm 145 = 1450 rpm 150 = 1500 rpm 155 = 1550 rpm 160 = 1600 rpm 165 = 1650 rpm 170 = 1700 rpm 175 = 1750 rpm 180 = 1800 rpm 185 = 1850 rpm
Digit 20 - Heating Type
A = Steam Coil, LH B = Hot Water Coil, LH C = Electric Heat, 1 Stage F = Hydronic Heat Ctrl Interface G = Elec. Heat Ctrl Interface, 1 stage K = Steam Coil Ship Separate, LH L = Hot Water Coil Ship Separate, LH M = Steam Coil, RH N = Hot Water Coil, RH P = Steam Coil Ship Separate, RH R = Hot Water Coil Ship Separate, RH T = Hi-cap. hot water coil, LH U = Hi-cap, hot water coil LH,
Ship Seperate V = Hi-cap. hot water coil, RH W = Hi-cap. hot water coil, RH,
Ship Seperate 0 = None
Digit 21 - Unit Isolators
A = Isopads B = Spring Isolators 0 = None
SCXG-SVX01B-EN 7
Model Number
Digit 22 - Unit Finish
1 = Paint - Executive Beige 2 = Protective Coating 3 = Protective Coating w/ Finish Coat
Digit 23
0 = None
Digit 24 - Unit Connection
1 = Disconnect Switch 2 = Terminal Block 3 = Dual Point Power
Digit 25 - Industrial Options
A = Protective Coated Evaporator Coil B = Silver Solder C = Stainless Steel Screws D = A and B E = A and C F = B and C G = A, B and C 0 = None
Digit 26 - Drain Pan Type
A = Galvanized Sloped B = Stainless Steel Sloped
Digit 27 - Waterside Economizer
A = Mechanical Clean Full Cap. (4-row) B = Mechanical Clean Low Cap. (2-row) C = Chemical Clean Full Cap. (4-row) D = Chemical Clean Low Cap. (2-row) E = Mechanical Clean Full Capacity
(4-row) Ship Separate
F = Mechanical Clean Low Capacity
(2-row) Ship Separate
G = Chemical Clean Full Capacity
(4-row) Ship Separate
H = Chemical Clean Low Capacity
(2-row) Ship Separate
0 = None
Description
Digit 28 - Ventilation Control
B = Airside Econ w/ Traq
(Top O/A Inlet)
C = Airside Econ w/ Standard
Dampers (Top O/A Inlet)
E = Airside Econ w/ Traq
Comparative Enthalpy (Top O/A Inlet)
F = Airside Econ w/ Std Dampers and
Comparative Enthalpy (Top O/A
Inlet) G = Traq Damper Ventilation Interface H = Ventilation For 2 Pos. Cntrl Interface 0 = None
Digit 29 - Water Piping
A = Right Hand Condenser Connection B = Left Hand Condenser Connection C = Right Hand Basic Piping D = Left Hand Basic Piping E = Right Hand Intermediate Piping F = Left Hand Intermediate Piping J = Right Hand Basic w/ Flow Switch K = Left Hand Basic w/ Flow Switch L = Right Hand Intermediate
w/ Flow Switch M = Left Hand Intermediate
w/ Flow Switch 0 = None
Digit 30 - Condenser Tube Type
A = Standard Condenser Tubes B = 90/10 CuNi Condenser Tubes 0 = None
Digit 31 - Compressor Service Valves
1 = With Service Valves 0 = None
Damper
Damper and
SCWG
Digit 32 - Miscellaneous System Control
1 = Timeclock 2 = Interface for Remote HI 3 = Dirty Filter Switch 4 = 1 and 2 5 = 1 and 3 6 = 2 and 3 7 = 1, 2, and 3 0 = None
Digit 33 - Control Interface Options
A = Generic BAS Module (GBAS) B = Ventilation Override Module (VOM) D = Remote Human Interface (RHI) G = GBAS and VOM H = GBAS and RHI J = VOM and RHI M = GBAS, VOM, and RHI 0 = None 1 = Tracer/LCI-I (COMM5) interface module 2 = Tracer/LCI-I and GBAS 3 = Tracer/LCI-I and VOM 4 = Tracer/LCI-I and RHI 5 = Tracer/LCI-I, GBAS and VOM 6 = Tracer/LCI-I, GBAS and RHI 7 = Tracer/LCI-I, VOM and RHI 8 = Tracer/LCI-I, GBAS, VOM and RHI
Digit 34 - Agency
T = UL Agency Listing 0 = None
Digit 35 - Filter Type
1 = 2-inch Construction Throwaway 2 = 2-inch Med Eff. Throwaway
Digit 36 - Miscellaneous Control Option
A = Low Entering Air Temp. Protect
Device (LEATPD) B = High Duct Temp T-Stat C = Plenum High Static Switch D = Kit for Heat Mode Output (w/t’stat) E = A and B F = A and C G = B and C H = A, B, and C 0 = None
8 SCXG-SVX01B-EN
Model Number Description PSWG
Self-Contained Ship-With Accessory Model Number Description
P S W G S A 1 1 0 JO 1 2 3 4 5 6 7 8 9 10 11
Digit 1 - Parts/Accessories
P = Parts/Accessories
Digit 2 - Unit Model
S= Self-Contained
Digit 3 - Shipment
W = With Unit
Digit 4 - Development Sequence
F = Signature Series G = Modular Series
Digit 5 - Sensors and Other Accessories
S = Sensors
Digit 6 - Sensors and Thermostats (field installed)
A = BAYSENS077 - Zone Temp Only (C V and VAV) B = BAYSENS073 - Zone Temp with Timed Override Button (CV and VAV) C = BAYSENS074 - Zone Temp with Timed Override Button, Setpoint Dial (CV and VAV) D = BAYSENS023 - Remote Min. Position Potentiometer Control (OA Damper) E = BAYSENS108 - CV Zone Sensor-dual setpoint, man/auto changeover F = BAYSENS110 - CV Zone Sensor-dual setpoint, man/auto changeover w, indicator lights G = BAYSENS019 - CV Programmable Night Setback Sensor H = BAYSENS021 - VAV Zone Sensor with Indicator Lights J = BAYSENS020 - VAV Programmable Night Setback Sensor K = Remote Sensor Kit L = Outside Air Temperature Sensor Kit M = Outside Air Humidity Sensor Kit N = BAYSTAT010 - 2 Heat/2 Cool Thermostat P = BAYSTAT037A - 2 Heat/2 Cool Programmable Thermostat 0 = None
Digit 7 - Mixed Air Temperature Protec­tion Kit (field installed)
1 = Mixed Air Temperature Protection Kit 0 = None
Digit 8 - Carbon Dioxide Sensor (field installed)
1 = Carbon Dioxide Sensor Kit 0 = None
Digit 9 - Future Option
0 = None
Digit 10, 11 - Design Sequence
J0 = J Design
SCXG-SVX01B-EN 9
Model Number Description
PSWG
“After-Shipment” Accessory Model Number
P S A G W N 20 4 ** 1 10 0 0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 0 0 L 1 0 0 7 0 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
0 0 0 0 0
41 42 43 44 45
Digit 1 - Parts/Accessories
P = Parts/Accessories
Digit 2 - Unit Model
S= Self-Contained
Digit 3 - Shipment
A = After Unit
Digit 4 - Development Sequence
F = Signature Series G = Modular Series
Digit 5 - Condenser Medium
W = Water Cooled R = remote Air Cooled
Digit 6 - Refrigerant Circuit Configuration
N = Independent (Water-Cooled) M = Manifolded (Air-Cooled)
Digits 7, 8 - Unit Nominal Capacity
20 = 20 Tons (Water or Air) 22 = 22 Tons (Water Only) 25 = 25 Tons (Water or Air) 29 = 29 Tons (Water or Air) 30 = 30 Tons (Air Only) 32 = 32 Tons (Water Only) 35 = 35 Tons (Water or Air) 38 = 38 Tons (Water Only) 40 = 40 Tons (Air Only) 42 = 42 Tons (Water Only) 46 = 46 Tons (Water Only) 50 = 50 Tons (Air Only) 52 = 52 Tons (Water Only) 58 = 58 Tons (Water Only) 60 = 60 Tons (Air Only) 65 = 65 Tons (Water Only) 72 = 72 Tons (Water Only) 80 = 80 Tons (Water Only)
Digit 9 - Unit Voltage
6 = 200 Volt/60 Hz/3 ph 4 = 460 Volt/60 Hz/3 ph 5 = 575 Volt/60 Hz/3 ph 0 = Not Defined
Digits 10, 11 - Design Sequence
** = Factory Assigned
Digit 12 - Unit Power Connection
1 = Single Point Power 2 = Dual Point Power 0 = Not Defined
Digit 13, 14 - Motor HP
05 = 5 HP Motor 07 = 7.5 HP Motor 10 = 10 HP Motor 15 = 15 HP Motor 20 = 20 HP Motor 25 = 25 HP Motor 30 = 30 HP Motor 40 = 40 HP Motor 50 = 50 HP Motor (460V & 575V Only) 0 = Not Defined
Digit 15 - Exhaust/Comparative Enthalpy Module (Field Installed)
1 = ECEM Kit 0 = None
Digit 16 - Generic BAS Module
1 = GBAS 0-5 VDC Kit 0 = None
Digit 17 - Heat Module
1 = Electric Heat Module Kit 2 = Hydronic Heat Module Kit 0 = None
Digit 18 - Remote Human Interface and IPCB
1 = Remote Human Interface Panel Kit (RHI Only) 2 = Interprocessor Communications Module Kit (IPCB Only) 3 = RHI and IPCB Kit 0 = None
Digit 19 - LonTalk Communications Interface Kit (LCI)
2 = Tracer/LCI-I Comm Interface Kit 0 = None
Digit 20 - Ventilation Override Module Kit (VOM)
1 = VOM Kit 0 = None
Digit 21 - Sensors and Thermostats
A = BAYSENS077 - Zone Temp Only (CV and VAV) B = BAYSENS073 - Zone Temp with Timed Override Button (CV and VAV) C = BAYSENS074 - Zone Temp with Timed Override Button, Setpoint Dial (CV and VAV) E = BAYSENS108 - CV Zone Sensor-dual setpoint, man/auto changeover F = BAYSENS110 - CV Zone Sensor-dual setpoint, man/auto changeover w, indicator lights G = BAYSENS019 - CV Programmable Night Setback Sensor H = BAYSENS021 - VAV Zone Sensor with Indicator Lights J = BAYSENS020 - VAV Programmable Night Setback Sensor K = Remote Sensor Kit L = Outside Air Temperature Sensor Kit M = Outside Air Humidity Sensor Kit 0 = None
Digit 22 - Low Entering Air Temperature Protection Device
1 = Low Entering Air Temperature Protection Device Kit 0 = None
Digit 23 - High Duct Temperature Thermostat
1 = High Duct Temp. Thermostat Kit 0 = None
Digit 24 - Plenum High Static Switch
1 = Plenum High Static Switch Kit 0 = None
Digits 25 — 45 - Future Use
0 = None
10 SCXG-SVX01B-EN
pre-installation
Receiving and Handling
Shipping Package
Commercial self-contained units ship assembled with protective coverings over the coil and discharge openings. Figure I-PC-1 illustrates a typical shipping package.
Ship-Separate Accessories
Field-installed sensors ship separately inside the unit’s main control panel. Extra filters, sheaves, and belts ship in the unit’s fan motor section. Condenser plugs, spring isolators, and isopads ship in the unit’s bottom left side.
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage.
Inspect individual cartons before

accepting. Check for rattles, bent carton corners, or other visible indications of shipping damage.
If a unit appears damaged, inspect it
immediately before accepting the shipment. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage
before it is stored and as soon as possible after delivery. Report concealed damage to the freight line within the allotted time after delivery. Check with the carrier for their allotted time to submit a claim.
Do not move damaged material from
the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the
shipment if it appears damaged. Retain all internal packing, cartons, and crate. Take photos of damaged material if possible.
Notify the carrier’s terminal of the
damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.
Notify your Trane representative of
the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.
Installation
Figure I-PC-1. Typical unit mounted on shipping skid.
considerations
SCXG-SVX01B-EN 11
pre-installation
Installation
Installation Preparation
Before installing the unit, perform the following procedures to ensure proper unit operation.
1. Verify the floor or foundation is level. Shim or repair as necessary. To ensure proper unit operation, install the unit level (zero tolerance) in both horizontal axis. Failure to level the unit properly can result in condensate management problems, such as standing water inside the unit. Standing water and wet surfaces inside units can result in microbial growth (mold) in the drain pan that may cause unpleasant odors and serious health-related indoor air quality problem.
2. Allow minimum recommended clearances for maintenance and routine service. See “Service Access” section on page 13.
3. Position the unit and skid assembly in its final location. If unit shipped split­apart, follow the procedure in the “Split-Apart Unit Assembly” section on page 16 before completing this step. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location. See Figure I-PC-7 and I-PC-8 on page 15 for typical rigging procedures, including cautions and proper uses of such equipment as fork lifts, spreader bars, and hooks.
considerations
5. Remove the protective shipping covers from the unit. Refer to the “Unit Protective Covers” section on page 35.
Note: Unit height and connection locations will change if external vibration isolators are used. The unit may be raised an additional 5-7/8 inches with spring-type isolators.
Note: Unit height and connection locations will change if the unit is constructed to be split-a-part in the field. See unit submittal drawings for connection locations.
6. Electrical supply power must meet specific balance and voltage requirements, as described in the “Electrical Requirements” section on page 33.
7. Water-cooled units only (model SCWG): The installer must furnish and install a condenser main and standby water pump, cooling tower, pressure gauges and all components for the waterside piping. See the “Water Piping” section on page 30 for general waterside recommendations.
8. Air-cooled units only (model SCRG): These units require field-installation of a remote air-cooled condenser and refrigerant piping. See the “Refrigerant Piping” section on page 32 for general piping recommendations.
4. Remove the skids from under the unit. See the “Rigging and Handling” section on page 14. Refer to the “Skid Removal” section on page 18. If you find internal damage, file a claim immediately to the delivering carrier.
12 SCXG-SVX01B-EN
pre-installation
Service Access
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regard­ing the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR.
See Figure I-PC-2 and Table I-PC-1 for recommended service and code clearances. Access to thermostat unit controls is through a hinged access panel door on the front, lower left of the unit’s compressor section.
IntelliPak unit controls access is through a panel on the middle right of the fan section. The panel is secured with an automatic latch and quick-acting fasten­ers, which require a screwdriver to open.
Removable front unit panels provide access to compressors, fan, motor, inlet guide-vane actuator, and belts.
Removable left side panels give access to drive side, fan bearing, inlet guide-vanes, condensers, and waterside economizer control valve. The compressor, con­denser and fan motor access panels are secured with quick-acting fasteners. Access panels for evaporator coils, expansion and water valves, and left fan bearing are sheet metal screws. Access to other components for service requires removal of panels secured with sheet metal screws. During operation, sight glasses are viewable through portholes on the upper right side panel of the fan section.
Installation
Variable Frequency Drives are shipped separately and field installed. See page 29 for VFD related dimensions and weights.
Top View CCRC/CIRC 20, 29, 32
48” (1066 mm)
Table I-PC-1. Service and code clearance requirements
Side Distance Purpose front 42 in. (20-38 tons) NEC code requirement left 18 in. air-cooled units only
36 in. refrigeration & waterside component service
77 in. fan shaft removal right 36 in. provides uniform airflow inlet 18 in. provides uniform airflow
See table
Figure I-PC-2. Top view of self-contained unit showing recommended service and code clear­ances
considerations
96” (2132 mm)
96” (2132 mm)
air inlet
42” minimum
18” minimum
48” (1066 mm)
Control Panel
Control Panel
36”minimum
SCXG-SVX01B-EN 13
pre-installation
Rigging and Unit Handling
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
WARNING
Lifting Equipment Capacity!
Ensure lifting equipment capacity exceeds unit weight by an adequate safety factor to prevent injury, death, or unit damage.
Installation
Figure I-PC-5. Assembled unit gravity block location.
considerations
Before lifting the unit or modular component, determine the approximate center of gravity for lifting safety. See Figure I-PC-5 for assembled modular units and Figure I -PC-6 for split-apart units. The center of gravity may vary slightly within the gravity block depending on unit options.
Always test-lift the unit to determine the exact unit balance and stability before hoisting it to the installation location. See Figures I-PC-7 and I-PC-8 for typical rigging procedures and proper rigging equipment usage.
Table I-PC-2. Gravity Block Dimensions
Model A B C D SCWG 36 14 38 12
SCRG 36 16 40 1 2
Fan Section Only
Compressor Section Only
Figure I-PC-6. Split-apart unit gravity block location.
14 SCXG-SVX01B-EN
pre-installation
Unit Handling Procedure
NOTICE
Do not use hooks to lift unit or hook into open channels to lift unit. This could cause unit damage.
1. Position rigging sling under wood shipping skid.
2. Use spreader bars to avoid unit damage.
3. When using a forklift, exercise caution to prevent unit damage.
4. Use the standard fork length to lift one end and drag or pull unit while skidding the opposite end.
5. The unit center of gravity will fall within center of gravity block at various locations depending on unit options.
6. Use hooks to lift fan section only. Do not hook into open channels to lift unit.
7. See unit nameplate for unit weight.
8. Do not stack units.
Installation
Figure I-PC-7. Assembled modular unit proper rigging.
considerations
Figure I-PC-8. Split-apart modular unit proper rigging.
SCXG-SVX01B-EN 15
pre-installation
Installation
Split-Apart Unit Assembly
1. Ensure the tagging information on the fan section nameplate matches that on the compressor nameplate.
2. Remove the connector brackets holding the the sheet metal shipping cover on compressor section. Retain brackets and screws.
3. Remove shipping cover from the compressor section and verify the ship­with packge contains:
• suction and discharge line couplings
• insulation
• sheet metal screws
4. Lift fan section onto the compressor section using the rigging method in Figure I-PC-8 on page 13.
5. Remove skid from the fan section, placing the fan section onto the compressor section. Reference Figure I­PC-9.
6. Install the connection brackets with the sheet metal screws (referenced in step
2) on all sides of the unit. Reference Detail “A” in Figure I-PC-9.
7. Remove the unit panels labeled RU and RL in Figure I-PC-10 on page 17. To remove panels, first remove the four shipping screws located in the corner of each panel. Next, turn the remaining turn fasteners to the unlatch position. The panel is supported by a “lip” channel. So, lift the panel up and off the unit to remove it. See Detail “A”in Figure I-PC-9.
8. Connect the drain hose to the drainpan outlet fitting and secure it with the drain hose clamp provided.
9. Circulate nitrogen thoughout refrigerant circuits.
10. Unbraze and remove the caps on the discharge and suction lines in both the compressor and fan sections.
11. Install and braze discharge and suction line couplings.
1
considerations
12. Insulate discharge and suction lines with the insulation provided.
13. Remove panel FLR and open the bottom control panel door, FLL. Pull the fan motor leads (coiled in the fan section) through the knockout in the bottom of the fan section to the control panel. Ensure that the bushing is installed in the hole to prevent the wires from chafing. Refer to the unit wiring diagrams to connect the fan motor leads properly and ensure correct phase sequencing.
IntelliPak Units(UCM) Only
14. Remove panels FML, FMM, and FMR.
15. Pull the circular plug connector (CPC) from the compressor section through the knockouts into the fan section. Install the bushings (provided on the wiring harnesses) in the knockouts.
16. Using the CPC wiring diagram, connect the male CPC to the female CPC in the top control panel.
17. If the unit has the mixed air temperature option, route the capillary tube on back of the filter rack.
Units with Thermostat Only
/
4
18. Remove panel FMR. See Note 1 on Figure I-PC-10.
19. Pull frost protection wires from the bottom control panel throughknockouts in bottom of fan section. Route wires to the appropriate frost protection switches on the evaporator coil. Reference the unit wiring diagrams to connect frost protection wiring connectors.
Air-Cooled Units Only:
20. Route the refrigerant circuit wires for circuits 1 and 2 from the bottom control panel through the knockouts to the solenoid valves. The solenoid valves are located in the liquid refrigerant lines on the right-hand side of the unit. Refer to the unit wiring diagrams to make splice connections.
16 SCXG-SVX01B-EN
pre-installation
Installation
considerations
Figure I-PC-9 How to assemble the split apart modular unit
Figure I-PC-10 Modular unit panel description and internal connections
SCXG-SVX01B-EN 17
pre-installation
Skid Removal
The unit ships on skids to provide forklift locations from the front or rear. The skid allows easy maneuverability of the unit during storage and transportation. Remove the skids before placing the unit in its permanent location.
Remove the skids using a forklift or jack. Lift one end of the unit off of the skids. See Figure I-PC-5 and I-PC-6 for unit gravity block location. Slide the skids out and lower the unit at the installation location.
Note: External isolation is not necessary since units are internally isolated. Consult a vibration specialist before “double­isolating” the unit.
External Unit Isolation
If your job requires external vibration isolation, two options are available: isopads or spring-type isolators. Isopads should be placed under the unit at locations indicated on the factory­provided isolator sheet.
Set the spring-type isolators (Figure I-PC-
9) in position after the unit is removed from skids before making electrical, piping, or duct connections. All units require a minimum of four isolators per unit. But some may require six isolators, depending upon unit options.
Installation
view of Figure I-PC-9, must be 1/4 - 1/ inches. To increase the clearance, lift the unit off the isolator and turn the leveling bolt counterclockwise. Recheck the unit level and the housing clearances. Maximum allowable difference between isolator heights is inch. Shim as required under the isolators.
Note: The compressors and fan assembly are internally isolated on most units. Due to this, the addition of external isolation devices (spring mounting isolators) is at the discretion of the building or HVAC system designer.
Pre-Installation Checklist
Complete the following checklist before beginning unit installation.
Verify the unit size and tagging with the
unit nameplate.
Make certain the floor or foundation is
level, solid, and sufficient to support the unit and accessory weights. Level or repair the floor before positioning the unit if neccesary.
Allow minimum recommended
clearances for routine maintenance and service. Refer to unit submittals for dimensions.
2
considerations
Allow three fan diameters above the
unit for the discharge ductwork. Return air enters the rear of the unit and conditioned supply air discharges through the top.
Electrical connection knockouts are on
1
/
the top, left side of the unit.
4
Allow adequate space for piping
access and panel removal. Condenser water piping, refrigerant piping, and condensate drain connections are on the lower left end panel.
Note: Unit height and connection locations will change if using vibration isolators. The unit height may increase up to 5 7/8” with spring type isolators.
Electrical supply power must meet
specific balance and voltage requirements as described in the “Electrical Requirements” section.
Water-cooled units only: The installer
is responsible for providing a condenser main, standby water pump, cooling tower, pressure gauges, strainers, and all components for waterside piping. See the “Water Piping” section for general waterside recommendations.
Air-cooled units only: The installer is
responsible for providing and installing the remote air-cooled condenser and refrigerant piping, including filter driers.
Note: Trane strongly recommends you consult a vibration specialist before double-isolating the unit. Double isolation is not recommended.
If you decide to externally isolate the unit, use spring-flex, type CP isolators. The spring number is marked on the outer housing. See Figure I-PC-9.
To install external isolators, complete the following procedure.
1. Locate the isolators under unit base at the locations indicated on the factory­provided isolator placement sheet. Lift one end of the unit at a time to position isolators to the floor, using anchor bolts.
2. Level the unit by adjusting isolator heights. Unit weight may cause the upper housing to rest on the lower housing of the spring isolators. The isolator clearance shown in the side
18 SCXG-SVX01B-EN
Figure I-PC-9. Optional spring isolator dimensional data.
Dimensions &
SCWG
SCWG/SIWG Dimensions, in.
left-side view
factory-piped units
SCWG/SIWG weight, lbs.
unit tons base weight 20 2260 25 2730 30 2864 35 3000
Notes:
1. All unit weights include refrigerant, water, inlet guide vanes and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
3. Split-apart unit weights are approximately: 60% total unit weight = compressor section, 40% total unit weight = fan section.
Weights
front view
top view
SIRG
left-side view
direct condenser connections
back view
right-side view
factory-piped units
SCXG-SVX01B-EN 19
right-side view
direct-condenser connections
Dimensions &
SCRG /
SCRG/SIRG Dimensions, in.
left-side view
Weights
front view
SIRG
top view
right-side view
SCRG/SIRG Weight, lbs.
unit tons base weight 20 2344 25 2479 32 2614
Notes:
1. All unit weights include refrigerant, water, inlet guide vanes and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
3. Split-apart unit weights are approximately: 60% total unit weight = compressor section, 40% total unit weight = fan section.
back view
20 SCXG-SVX01B-EN
Dimensions & Weights
SCRG/SIRG/SCWG/SIWG Detail “A” Electrical Connections, in.
Detail “B” Discharge Options , in.
front view
shown with horizontal discharge option
top view
shown with vertical discharge option
Detail Dimensions, in.
model A B C D E F SCWG/SCRG 20 20 10 3/458 1/25 1/813 1/411 1/ SCWG/SCRG 25 19 1/412 1/457 5/85 1/813 1/411 1/ SCWG 30 - 35/SCRG 32 1 8 14 5/856 1/25 1/813 1/ 11 1/
2
2
2
4
SCXG-SVX01B-EN 21
Dimensions &
CCRC /
Weights
CCRC/CIRC — Air-Cooled Condenser
AA
AB
AC
OPTIONAL LOW AMBIENT DAMPER (ONE DAMPER PER CIRCUIT)
REFRIGERANT LINE CONNECTIONS
FRONTAL VIEW
REFRIGERANT CIRCUIT 2
CIRC
REFRIGERANT CIRCUIT 1
OPTIONAL LOW AMBIENT DAMPER
24 VOLT WIRE ENTRY HOLE SIZED FOR 3/4” CONDUIT
115 VOLT WIRE ENTRY HOLE SIZED FOR
3
/4” CONDUIT
SUPPLY VOLTAGE WIRE ENTRY HOLE SIZED FOR 1” CONDUIT
B
C
CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbs.
model A A AB AC weight weight CCRC/CIRC 20 70 1/8 88 88 2030 1906 CCRC/CIRC 29 70 1/8 88 88 2084 1960 CCRC/CIRC 32 70 1/8 88 88 2138 2014
shipping operating
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 1)
(HOT GAS CONNECTION REFRIG. CIRCUIT 1)
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 2)
(HOT GAS CONNECTION REFRIG. CIRCUIT 2)
CCRC/CIRC Electrical connections, in.
model A B C CCRC/CIRC 20-32 4 1/210 1/217 1/
2
CCRC/CIRC Refrigerant connections, in.
model E F G H J K L M N CCRC/CIRC 20-32 66
7
/814
3
/818
1
3
/224
/4295/81 1/
22 SCXG-SVX01B-EN
8
5
/81 1/
8
Hot Water Coil
Dimensions & Weights
Hot water coil dimensions & weight, in-lbs.
unit size A B C D E F G H J weight 20 - 35 tons 37 1/453 3/416 5/873 1/214 7/816 1/443 1/45 5/87 3/4460
SCXG-SVX01B-EN 23
Steam Coil
Dimensions & Weights
Steam coil dimensions, in-lbs.
unit size A B C D E K L M N P Q R weight 20 - 35 tons 37 1/453 3/416 5/873 1/210 7/822 1/23 3/815 7/81419 3/84
24 SCXG-SVX01B-EN
3
/8460
Dimensions & Weights
Electric Heat Coil
Electric heat coil dimensions & weight, in-lbs.
unit size A B C D weight 20 tons 70 1/44 7/811 1/219 460 25 tons 70 1/44 1/811 1/219 460 30 - 35 tons 70 1/42 7/811 1/219 460
Note: Coil box height is 8 in.
Flexible Horizontal Discharge Plenum
Flexible horizontal discharge plenum dimensions & weights, in-lbs.
20-35 tons A B C weight low height 3 5 17 1/486 1/2262 standard height 35 25 1/486 1/2352
SCXG-SVX01B-EN 25
Waterside Economizer
Dimensions & Weights
Waterside economizer weight, in-lbs.
unit size 2-row 4-row 20 - 35 tons 48 8 58 4
26 SCXG-SVX01B-EN
weight
Dimensions &
Airside
Airside Economizer
Weights
Economizer
Airside economizer dimensions & weight, in-lbs.
unit size A B C D E F (1) F (2) G (1) G (2) H (1) H (2) J K L M weight SCWG/SIWG 20, 25 3 6 65 5/837 74 1/46 1/856 1/249 3/423 1/420 1/25 5/87 20 1/217 1/81 2 49 3/4273 SCRG/SIRG 20 SCWG/SIWG 30, 35 3 6 65 5/837 74 1/46 1/861 3/862 3/428 1/820 1/23 1/47 20 1/217 1/85 1/262 3/4273 SCRG/SIRG 25, 32
Detail “A”
Detail “B”
SCXG-SVX01B-EN 27
A
B
C
D
E
F
G
Dimensions &
VFD
There must be a minimum eight inch clearance above and below the VFD. A minimum two inch clearance is required on each side.
Also, allow enough clearance for opening the VFD cabinet door. This will ensure sufficient air space for cooling.
Refer to the “Dimensions and Weights” section beginning on page 19 for VFD dimensions and weights.
Variable Frequency Drive Option (VFD)
WARNING
Control and Line Voltage!
Control and line voltage wiring from the VFD to the unit must be in accordance with all local and National Electric Codes. Do not touch circuit components until main power has been turned off and “charge” lamp is extinguished. The capacitors are still charged and could
result in death or serious injury.
WARNING
Weights
Mounting Requirements
Proper location of the VFD is important to achieve proper performance and normal operating life. Installation must be in an area where it will be protected from:
• Direct sunlight, rain or moisture.
• Corrosive gases or liquids.
• Vibration, airborne dust, or metallic particles.
For effective cooling as well as proper maintenance, install the VFD vertically to the ground using four mounting screws.
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regard­ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
The variable frequency drive (VFD) option can only be used with IntelliPak units. The VFD and VFD w/bypass is available from 5 to 25 hp and is a Trane TR1. All VFD’s are pre-configured and run tested at the factory prior to shipping. The VFD is wall mounted.
28 SCXG-SVX01B-EN
VFD dimensions, in.
voltage hp A B C D E F G
460 7.5 15.55 15.12 7.87 8.66 0.39 0.24 7.87
208 7.5 22.05 21.26 7.87 9.53 0.83 0.30 10.24
460 15
208 15 27.56 26.77 10.63 12.13 0.83 0.30 11.05
460 30
208 30 31.50 30.71 10.63 12.13 0.75 0.30 11.65 460 50
208 40 31.49 30.71 10.63 14.57 1.97 - 13.19
10
10
20 25
20
40
60
Dimensions &
H
G
E
D
F
B
A
C
Electrical Installation Procedure
Refer to the
section 310-16
National Electric Code,
for sizing wires 4B - 9B. All other control wires should be twisted shielded or twisted pair shielded, 20 - 14 AWG, with lead length not to exceed 164 feet. When using shielded wire, the shield sheath must be connected at the VFD only. The connection on units with VFD is J13-S. The connection on unis with VFD/ bypass is ITBI-10.
Weights
VFD
Variable Frequency Drive with Bypass
VFD with bypass dimensions, in.
SCXG-SVX01B-EN 29
voltage hp A B C D E F G H
460 7.5 30.40 28.03 16.14 23.35 24.85 0.75 8.59 10.63
208 7.5 41.28 38.89 16.14 24.00 25.5 0.75 10.95 12.99
460 15
208 25 50.81 48.35 21.36 31.61 33.41 0.90 12.36 14.41
10
10 15 20
20 25

Mechanical Specifications

Duct Connections
WARNING
Hazardous Voltage w/Capaci­tors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regard­ing the safe discharge of capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR.
Return air enters the rear of the unit and conditioned supply air discharges through the top. Attach supply air ductwork directly to the unit’s top panel, around the fan discharge opening. A duct collar is not provided.
Note: Units equipped with the flexible horizontal discharge plenum option may include a duct collar when holes are factory cut. If discharge openings are field-cut, refer to the “Plenum Installation” section.
Install all air ducts according to the National Fire Protection Association standards for the “Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A) and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).
Make duct connections to the unit with a flexible material such as heavy canvas. If a fire hazard exists, Trane recommends using Flexweave 1000, type FW30 or equivalent canvas. Use three inches for the return duct and three inches for the discharge duct. Keep the material loose to absorb fan vibration.
Note: The compressors and fan assembly are internally isolated. Therefore, external isolation devices (spring mounting isolators) are at the discretion of a vibration specialist consulted by the building or HVAC system designer.
Run the ductwork straight from the opening for a minimum of three fan diameters. See Figure I-MR-1. Extend remaining ductwork as far as possible without changing size or direction. Do not make abrupt turns or transitions near the unit due to increased noise and excessive static losses. Use elbows with splitters or turning vanes to minimize static losses.
Poorly constructed turning vanes may cause airflow generated noise. Align the fan outlet properly with the ductwork to decrease noise levels in the duct and to increase fan performance. To complete trunk ductwork to the VAV terminal units, refer to the VAV box manuals for specific requirements. Check total external static pressures against fan characteristics to be sure the required airflow is available throughout the ductwork.
To achieve maximum acoustical perfor­mance, minimize the duct static pressure setpoint.
Discharge Duct
3-inch Flexible Duct
Figure I-MR-1. Duct connection recommenda­tions
3 Fan Diameters
Return Air
Water Piping
WARNING
High Pressure Water!
Provide relief valves on system water piping to prevent instantaneous release of high pressure water. Failure to provide relief valves could result in death or serious injury or water pump damage or unit failure.
Condenser Connections
Condenser water piping knockouts are in the lower left end panel. If necessary, remove insulation to gain access. All field installed piping must conform to applicable local, state, and federal codes. To complete condenser water connections follow the procedure below.
Note: Four condenser waterline drain plugs ship in a bag in the unit’s left end. The installer must field install these four plugs using pipe thread sealer. An additional plug is provided for units with a waterside economizer.
1. Attach the water supply line to the inlet connection, and the return line to the outlet connection. Entering and leaving water connections for all condensers are factory manifolded and require only single connections for entering and leaving water. If the unit has a waterside economizer and/or control valves, the factory pipes between these components.
2. If using a cooling tower, refer to Figure I-MR-2 for a typical piping circuit from the unit.
3. Ensure the water pressure to the unit
does not exceed 400 psig.
Note: To prevent water pump damage, design system piping to provide relief when using energy saving waterside economizer valves.
30 SCXG-SVX01B-EN
Loading...
+ 86 hidden pages