Trane SCWG-020, SCWG-025, SCWG-030, SCWG-032, SCWG-035 Installation and Maintenance Manual

...
Installation, Operation, and Maintenance
Intellipak™ Commercial Self-Contained
Models
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
June 2014
SCWG -020, -025, -030, -032, -035 SIWG -020, -025, -030, -032, -035 SCRG -020, -025, -032 SIRG -020, -025, -032
SAFETY WARNING
SCXG-SVX01H-EN

Introduction

Read this manual thoroughlybefore operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only accidents.
WARNING
Refrigerant under High Pressure!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to recover refrigerant to relieve pressure or the use of non­approved refrigerants, refrigerant substitutes, or refrigerant additives could result in an explosion which could result in death or serious injury or equipment damage.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved SCXG-SVX01H-EN
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.

Copyright

This document andthe information in it arethe property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Introduction
Trademarks
Trane, Intellipak,Tracer and theTrane logo are trademarks
ofTrane in the United States and other countries.All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
SCXG-SVX01H-EN (24 Jun 2014)
Updated to correct input line current for 575V, 15HP, with bypass.
SCXG-SVX01G-EN (23 Oct 2012)
Updated fan motor FLA data.
SCXG-SVX01H-EN 3

Table of Contents

Model Number Descriptions .............. 6
Modular Series Self-Contained .......... 6
Self-Contained Ship-With Accessory Model Number
.............................. 8
Remote Air-Cooled Condenser .......... 8
General Data ............................ 9
Modular Series Self-Contained Unit Components
.......................... 9
General Data ......................... 11
Pre-Installation Considerations ........... 13
Receiving ............................ 13
Contractor Installation Responsibilities .. 13
Unpackaging ......................... 13
Dimensions & Weights .................. 16
Service Clearances .................... 24
Installation - Mechanical ................ 25
Unit Handling Procedures ............. 25
Skid Removal ...................... 27
Installation Preparation ................ 27
Split-Apart Unit Assembly ............ 28
Unit Vibration Isolator Option .......... 29
Duct Connections ..................... 30
Plenum .............................. 30
Airside Economizer Installation ......... 31
Water Piping ......................... 32
Condenser Connections .............. 32
Condensate Drain Connections ........ 32
General Waterside Recommendations:
Cooling Towers .................... 32
Waterside Piping Arrangements ....... 33
Water Temperature Requirements ..... 33
Waterside Economizer Installation Procedure
Waterside Economizer with right-hand
factory piping components ........... 35
........................... 34
Hydronic Coil Installation .............. 36
Refrigerant System ................... 36
Interconnecting Piping ............... 37
Preliminary Refrigerant Charging ....... 37
Installation - Electrical ....................39
Unit Wiring Diagrams ..................39
Supply Power Wiring ..................39
Selection Procedures ..................40
Variable Frequency Drive Option (VFD) ...41
Variable Frequency Drive Without ByPass 41
Variable Frequency Drive With ByPass . .45
Static Pressure Transducer Installation (VAV units only)
.......................49
Electric Heat Installation ................49
Standard with All IntelliPak Units .......51
Zone Sensor Options for IntelliPak Control Units
CV and VAV Unit Zone Sensor Options . .52
.........................51
Integrated Comfort™ Systems Sensors for CV and VAV Applications
............52
Zone Sensor Installation ................53
Programmable Zone Sensors ...........54
Time Clock Option .....................56
Remote Human Interface Panel Installation 56
Mounting the Remote Human Interface (RHI) Panel
...........................57
Wiring the Remote Human Interface .....59
Connecting to Tracer Summit ...........61
Programming the Time Clock Option .....61
Operating Principals .....................63
Control Sequences of Operation .........63
Unoccupied Sequence of Operation ......63
Occupied Sequence ....................64
Thermostatic Expansion Valve ..........66
Compressors .........................66
Unit Airside Components ...............71
Controls ................................74
Points List ............................74
RTM Module ........................74
GBAS Module .......................74
ECEM Module .......................74
Tracer™ LCI-I Module ..................74
Constant Volume (CV) Points ..........74
4 SCXG-SVX01H-EN
Table of Contents
Variable Air Volume (VAV) Points ...... 75
BCI-Points List ........................ 76
Phase Monitor ....................... 76
Unit Control Components .............. 76
RTM Module Board -
Standard on all Units ................ 76
Compressor Module (MCM) -
Standard on all Units ................ 78
Human Interface Module -
Standard on all Units ................ 78
Remote Human Interface Module Option 78
Waterside Module -
Standard on all water-cooled units ..... 78
Heat Module ....................... 78
Ventilation Override Module
(VOM) Option ...................... 78
Trane IntelliPak Communications
Modules .......................... 79
Exhaust/Comparative Enthalpy (ECEM)
Module ........................... 80
Ventilation Control Module (VCM) ..... 80
Generic Building Automation System
Module Option ..................... 80
Input Devices and System Functions . . . 82
Adjusting Belt Tension ...............94
Refrigerant System ....................95
Refrigerant Leak Test Procedure ........95
Brazing Procedures ..................96
System Evacuation Procedures ........97
Compressors .........................98
Scroll Compressor Failure Diagnosis
and Replacement ....................98
Components ..........................99
Coil Fin Cleaning .....................100
Piping Components ...................102
Maintenance Periodic Checklists ........102
Diagnostics ............................104
Troubleshooting ......................104
System Checks .....................104
Diagnostics ..........................104
Wiring Diagrams .......................113
Pre-Startup ............................. 85
Pre-Startup Checklist .................. 85
Start-up ................................ 86
Final Refrigerant Charge ............... 87
Start-up Procedure .................... 87
Startup Log .......................... 88
Maintenance ........................... 90
Service Access ....................... 90
Variable Frequency Drive (VFD) ....... 90
Variable Frequency Drive (VFD) -
Remote Mounted ................... 90
Air Filters ............................ 90
Inspecting and Cleaning Drain Pan ...... 90
Inspecting and Cleaning the Fan ........ 91
Supply Fan .......................... 91
Fan Drive .......................... 91
Fan Bearings ....................... 92
Fan Belt Tension .................... 93
SCXG-SVX01H-EN 5

Model Number Descriptions

Modular Series Self­Contained
Digit 1 - Unit Model
S = self contained
Digit 2 - Unit Type
C = commercial I = industrial
Digit 3 - Condenser Medium
W = water-cooled
R = remote air-cooled
Digit4-Development Sequence
G = modular series
Digit 5 - Refrigerant Circuit Configuration
U = independent, R-410A refrigerant
Digits 6, 7 - Unit Nominal Capacity
20 = 20Tons (water or air cooled) 25 = 25Tons (water or air cooled) 30 = 30Tons (water cooled only) 32 = 32Tons (air cooled only) 35 = 35Tons (water cooled only)
Digit 8 - Unit Voltage
6 = 200 volt/60 hz/3 ph 4 = 460 volt/60 hz/3 ph 5 = 575 volt/60 hz/3 ph
Digit 9 - Air Volume/Temp Control
2 = I-Pak & VFD & supply air temp ctrl 3 = I-Pak & VFD w/ bypass & supply
air temp ctrl
4 = I-Pak w/o vol. ctrl, w/ zone temp
cool
5 = I-Pak w/o vol. ctrl, w/ zone temp
heat/cool
6 = I-Pak w/o vol. ctrl, w/ supply air
temp ctrl
8 = thermostat interface
Digits 10, 11 - Design Sequence
** = Factory Assigned
Digit 12 - Unit Construction
A = vertical discharge
B = vertical discharge with double
wall C = horizontal discharge D = horizontal discharge w/ double
wall E = vertical discharge, ship separate F = vert. dis. w/ double wall,
ship sep. G = horizontal discharge, ship
separate H = horiz. dis. w/ double wall,
ship sep.
Digit 13 - PlenumType
B = std plenum w/ factory cut holes C = low plenum w/ factory cut holes E = std plenum w/ field cut holes F = low plenum w/ field cut holes H = std plenum double wall (perf)
w/ field cut holes
J = low plenum double wall (perf)
w/ field cut holes
L = std. plenum w/factory cut holes,
ship separate
M = low plenum w/ factory cut holes,
ship separate P = std plenum w/ field cut holes, ship
separate R = low plenum w/ field cut holes,
ship separate U = std plenum double wall (perf) w/
field cut holes, ship separate
V = low plenum double wall (perf) w/
field cut holes, ship separate 0 = without plenum
Digit 14 - MotorType
2 = ODP motor 3 = TEFC motor
Digits 15, 16 - Motor HP
05 = 5 hp 07 = 7.5 hp 10 = 10 hp 15 = 15 hp 20 = 20 hp 25 = 25 hp
Digits 17, 18, 19 - Fan RPM
085 = 850 rpm 090 = 900 rpm 095 = 950 rpm 100 = 1000 rp m 105 = 1050 rpm 110 = 110 0 r p m 115 = 1150 rpm 120 = 1200 rpm 125 = 1250 rpm 130 = 1300 rpm 135 = 1350 rpm 140 = 1400 rpm 145 = 1450 rpm 150 = 1500 rpm 155 = 1550 rpm 160 = 1600 rpm 165 = 1650 rpm 170 = 1700 rpm 175 = 1750 rpm 180 = 1800 rpm 185 = 1850 rpm
Digit 20 - Heating Type
A = steam coil, LH B = hot water coil, LH C = electric heat, 1 stage F = hydronic heat ctrl interface G = elec. heat ctrl interface,1 stage K = steam coil ship separate, LH L = hot water coil ship separate, LH M = steam coil, RH N = hot water coil, RH P = steam coil ship separate, RH R = hot water coil ship separate, RH
T = hi-cap. hot water coil, LH
U = hi-cap hot water coil, LH, ship
sep V = hi-cap hot water coil, RH W = hi-cap hot water coil, RH, ship
sep
0 = none
Digit 21 - Unit Isolators
A = isopads
B = spring isolators
0 = none
Digit 22 - Unit Finish
1 = paint - slate gray
2 = protective coating
3 = protective coating w/ finish coat
Digit 23
0 = none
Digit 24 - Unit Connection
1 = disconnect switch
2 = terminal block
3 = dual point power
Digit 25 - Industrial Options
A = protective coated evaporator coil
B = silver solder
C = stainless steel screws
D = A and B
E = A and C
F = B and C
G = A, B and C
0 = none
Digit 26 - Drain PanType
A = galvanized sloped
B = stainless steel sloped
Digit 27 - Waterside Economizer
A = mechanical clean full capacity
(4-row)
B = mechanical clean low capacity
(2-row)
C = chemical clean full capacity
(4-row)
D = chemical clean low capacity
(2-row)
E = mechanical clean full capacity
(4-row) ship separate
F = mechanical clean low capacity
(2-row) ship separate
G = chemical clean full capacity
(4-row) ship separate
H = chemical clean low capacity
(2-row) ship separate
0 = none
6 SCXG-SVX01H-EN
Model Number Descriptions
Digit 28 - Ventilation Control
B = airside econ w/Traq™ damper
(top O/A inlet)
C = airside econ w/ standard
dampers (top O/A inlet)
E = airside econ w/ Traq™ damper
and comparative enthalpy (top O/A)
F = airside econ w/ std dampers and
comparative enthalpy (top O/A)
H = none/ventilation for 2-position
control interface J = airside economizer interface K = airside economizer interface w/
comparative enthalpy 0 = None
Digit 29 - Water Piping
A = RH condenser connection
B = LH condenser connection C = RH basic piping D = LH basic piping E = RH intermediate piping F = LH intermediate piping J = RH basic w/ flow switch K = LH basic w/ flow switch L = RH intermediate w/ flow switch M = LH intermediate w/ flow switch 0 = none
Digit 30 - Condenser Tube Type
A = standard condenser tubes
B = 90/10 CuNi condenser tubes 0 = none
Digit 31 - Compressor Service
Valves
1 = with service valves 0 = none
Digit 32 - Miscellaneous System Control
1 = timeclock 2 = interface for remote HI (IPCB) 3 = dirty filter switch 4 = 1 and 2 5 = 1 and 3 6 = 2 and 3 7 = 1, 2, and 3 0 = none
Digit 33 - Control Interface Options
A = Generic BAS Module; 0-5 VDC
(GBAS)
B = Ventilation Override Module
(VOM) D = Remote Human Interface (RHI) G = GBAS & VOM H = GBAS & RHI J = VOM & RHI M = GBAS & VOM & RHI N = BACnet Communications
Interface (BCI) P = BCI and GBAS Q = BCI and VOM R = BCI and RHI
T = BCI and GBAS and VOM
U = BCI and GBAS and RHI
V = BCI and VOM and RHI W = BCI and GBAS and VOM and RHI
0 = None 1 = LonTalk Comm5 Interface (LCI) 2 = LCI and GBAS 3 = LCI and VOM 4 = LCI and RHI 5 = LCI and GBAS and VOM 6 = LCI and GBAS and RHI 7 = LCI and VOM and RHI 8 = LCI and GBAS and VOM and RHI
Digit 34 - Agency
T = UL agency listing
0 = none
Digit 35 - Filter Type
1 = 2-inch construction throwaway 2 = 2-inch med eff. throwaway
Digit 36 - Miscellaneous Control Option
A = low entering air temp. protect
device (LEATPD) B = high duct temp t-stat C = plenum high static switch D = kit for heat mode output (w/t’stat) E = A and B F = A and C G = B and C H = A, B, and C 0 = None
SCXG-SVX01H-EN 7
Model Number Descriptions
Self-Contained Ship-
With Accessory
Model Number
Digit1-Parts/Accessories
P = parts/accessories
Digit 2 - Unit Model
S = self-contained
Digit 3 - Shipment
W = with unit
Digit4-Development Sequence
F = signature series G = modular series
Digit5-Sensors and Other
Accessories
S = sensors
Digit6-Sensors and
Thermostats (Field Installed)
A = BAYSENS077 - zone temp only
(CV and VAV)
B = BAYSENS073- zone temp with
timed override button (CV and
VAV)
C = BAYSENS074 - zone temp with
timed override button, setpoint dial (CV and VAV)
E = BAYSENS108 - CV zone sensor
-dual setpoint, man/auto changeover
F = BAYSENS110 - CV zone sensor-
dual setpoint, man/auto changeover w, indicastor lights
G = BAYSENS119 - CV/VAV program-
mable night setback Sensor
H = BAYSENS021 - VAV zone sensor
with indicator lights
K = BAYSTAT150 2H/2C ProgTstat w/
BAYSTAT077 Remote Sensor L = outside air temperature sensor kit M = outside air humidity sensor kit N = BAYSTAT155 3H/2CTstat P = BAYSTAT150 2H/2C
ProgrammableTstat 0 = none
Digit 7 - Mixed Air Temperature Protection Kit (Field Installed)
1 = mixed air temperature protection
kit 0 = none
Digit 8 - Carbon Dioxide Sensor (Field Installed)
1 = carbon dioxide sensor kit 0 = none
Digit9-Future Option
0 = none
Digits 10, 11 - Design Sequence
** = Factory Assigned

Remote Air-Cooled Condenser

Digit 1 - Unit Model
C = Condenser
Digit 2 - Unit Type
C = Commercial I = Industrial
Digit 3 - Condenser Medium
R = Remote
Digit4-Development Sequence
C=C
Digits 5, 6, 7 - Nominal Capacity
020 = 20 Tons 029 = 29 Tons 032 = 32 Tons
Digit 8 - Unit Voltage
4 = 460 Volt/60 Hz/3 ph 5 = 575 Volt/60 Hz/3 ph 6 = 200 Volt/60 Hz/3 ph
Digit 9 - Control Option
0 = No Low Ambient, I-Pak
A = No Low Ambient,T-stat
B = Low Ambient, I-Pak C = Low Ambient,T-stat
Digits 10, 11 - Design Sequence
** = Factory Assigned
Digit 12 - Unit Finish
1 = Paint (Slate Gray) 2 = Protective Coating 3 = Protective Coating with
Finish Coat
4 = Unpainted Unit
Digit 13 - Coil Options
A = Non-Coated Aluminum
C = Protective Coated Aluminum
Digit 14 - Unit Isolators
0 = None
A = Spring Isolators
B = Isopads
Digit 15 - Panels
0 = None 1 = Louvered Panels
Digit 16 - Agency
0 = None
T = UL Listing
8 SCXG-SVX01H-EN

General Data

Modular Series Self-Contained Unit Components

Commercial self contained units are complete HVAC systems used infloor-by-floor applications. Units are easy to install because they feature a single point power connection, factory installed and tested controls, single water point connection, factory installed options, and an internally trapped drain connection. Modular self­contained units can ship assplit-apart units forinstallation ease. Split-apart units ship with a dry nitrogen charge and require field refrigerant charging.
Units consist of multiple hermetically sealed 3-D scroll compressors, water-cooled condensers (water-cooled units only), an evaporator coil, dual forward curved fans, and control panel. Air-cooled units require a remote air­cooled condenser, model CXRC. Unit controls are either electromechanical thermostat or microprocessor controls on IntelliPak unit.
Hermetically sealed 3-D scroll compressor motors utilize internal motor protection and time delays to prevent excessive cycling.
Water-cooled condensers are shell and tube type with
internal subcooler. Condensers are available as mechanically or chemically cleanable. Evaporator fan is double width, double inlet andforward curved witha fixed pitch belt drive assembly. Variable frequency drives are optional. EISA efficiency open drip proof (ODP) and totally enclosed fan cooled (TEFC) motor options are available.
Package water-cooled units ship with full refrigerant and compressor oil charge. Split apart water cooled, and air cooled, units ship with dry nitrogen charge and complete compressor oil charge.
Split apart water cooled units require field connection of suction and liquid lines. Air-cooled units require field­piping discharge and liquid lines to remote air cooled condenser.
All units have two refrigerant circuits that include filter
drier (field installed in air cooled), liquid line service valve, sight glass/moisture indicator, thermal expansion valve with a sensing bulb and external equalizing line, suction and discharge line accessports,and high andlow pressure cutout switches. Water-cooled units also include pressure relief valve. Air cooled units include liquid line solenoid valve and discharge line check valve.
Control Options
Units may be ordered with conventional thermostat interface or IntelliPak™ Direct Digital Control (DDC). IntelliPak controls include a Human Interface (HI) panel with two line by forty (40) character clear English display for easy operator interface to unit setup and control parameters. All basic setup parameters are preset from factory.
Human Interface Panel
HI is unit mounted and accessible without opening unit’s front panel. It allows easy setpoint adjustment using HI keypad. HI displays all unit operating parameters and conditions in a clear language display, which can be configured for either English, French, or Spanish.
Optional remote human interface (RHI) will control up to four self-contained units, each containing an interprocessor communications bridge (IPCB). It has the same features as unit-mounted HI except for service mode.
For more information on setpointdefaults, ranges and unit programming, see IntelliPakSelf-Contained Programming Guide, PKG-SVP01*-EN that ships with each unit.
IntelliPak™ DDC Control
IntelliPak™ DDC Control provides “smart” unit control with safety features and control relays for pumps, dampers, etc. Modular Series IntelliPak self-contained unit is controlled by microelectronic controlsystem consisting of a network of modules.These modules are referred to as unit control modules (UCM). Inthis manual, acronym UCM refers to the entire control system network.
These modules perform specific unit functions using
proportional/integral control algorithms.They are mounted in the unit control panel and are factory wired to their respective internal components. Each module receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request; i.e., economizing, mechanical cooling, heating, ventilation. See the Operation section of this manual for a detailed description of each module’s function.
Optional Controls
Optional controls include a disconnect switch, dirty filter switch, water flow switch (water-cooled only), supply air temperature reset, or external setpoint inputs. Daytime heating is available on units with electric, steam, or hot water heat control options. Morning warmup operation is available on all units.
The static pressure probe, zone night heat/morning
warmup, supply air temperature resetsensor options ship separate inside the unit control panel for field installation. For more detailed information on the unit control options, see the Owner’s section of this manual.
SCXG-SVX01H-EN 9
General Data
Unit Nameplate
Unit nameplate, mounted on left end of unitcontrol panel, identifies unit model number, service literature, and wiring diagram numbers.
Figure 1. IntelliPak™ commercial self-contained
modular series unit
10 SCXG-SVX01H-EN

General Data

General Data
Table 1. SCWG/SIWG/SCRG/SIRG general data
Water-Cooled Units Air-Cooled Units
Unit Size 20 25 30 35 20 25 32
Compressor Data
Quantity 2 2 1/1 2 2 1/1 2
Nominal Ton/Comp 10 10 10/15 15 10 10/15 15
Circuits 2 2 2 2 2 2 2
Evaporator Coil Data
Rows 2 4 4 4 3 4 4
Sq. Ft. 22.5 25.0 25.0 25.0 25.0 25.0 25.0
FPF 144 144 144 144 144 144 144
Condenser Data
Minimum GPM w/o Econ 36 36 46 54 - - -
Minimum GPM w/ Econ 41 41 60 65 - - -
Maximum GPM 80 80 102 119 - - -
Evaporator Fan Data
Quantity 2 2 2 2 2 2 2
Size (Dia. x width - inches) 12 5/8"x8" 12 5/8"x9" 12 5/8"x11" 12 5/8 x11" 12 5/8"x8" 12 5/8"x9" 12 5/8"x11"
Minimum HP 5 5 5 5 5 5 5 Maximum HP 20 25 25 25 20 25 25
Minimum Design CFM 6350 7250 7250 7250 7250 7250 7250
Maximum Design CFM 8500 10,625 12,750 14,875 8500 10,625 13600
R-410A Refrigerant Data
EER 14.0 14.3 14.1 14.0 10.0 10.1 10.4
IEER (CV) 14.1 14.8 15.4 15.6 10.8 11.8 11.9
IEER (VFD) 17.1 18.1 18.2 17.7 13.4 13.3 13.8
Refrigerant Charge - lb (kg)
Circuit A 19.0 (8.6) 24.0 (10.9) 24.5 (11.1) 23.0 (10.4) See Note 3 See Note 3 See Note 3 Circuit B 19.0 (8.6) 24.0 (10.4) 23.0 (10.4) 23.0 (10.4) See Note 3 See Note 3 See Note 3
Capacity Steps - % 100/53/0 100/53/0 100/65/42/6 100/53/0
Filter Data
Quantity 4 4 4 4 4 4 4
Size (inches) 16x25x2 16x25x2 16x25x2 16x25x2 16x25x2 16x25x2 16x25x2
Quantity 4 4 4 4 4 4 4
Size (inches) 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2 20x25x2
CCRC/CIRC Condenser Match
Notes:
1. Compressors are Trane 3-D™scroll.
2. EER and IEER are rated in accordance to the AHRI Standard 340/360-2010. Based on 80/67°F (26.7/19.4°C) to the evaporator coil, nominal airflow
and 85-95°F (29.4-35°C) condenser water or 95° F (35° C) ambient.
3. All units operate with R-410A. Water Cooled units ship with full operating charge. Air-cooled units ship with dry nitrogen charge. Field refrigerant system charge required. Refer to Table 2, p. 12 for amounts required.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Filter sizes are for units without hot water or steam heating coils
- - - - 20 29 32
SCXG-SVX01H-EN 11
General Data
Table 2. SCRG/SIRG self-contained and CCRC/CIRC
remote air-cooled condenser
SCRG/SIRG & CCRC/CIRC Unit Size 20/20 25/29 32/32
No. of Refrigerant Circuits 2 2 2 Operating Charge - lbs R-410A 36.5/36.5 48.5/36 46/46 Operating Charge - kg R-410A 16.6/16.6 22/16.3 20.9/20.9 Cond. Storage Cap. - lbs R-410A 37/37 51/37 51/51 Cond. Storage Cap. - kg R-410A 16.8/16.8 23.1/16.8 23.1/23.1
Notes:
1. Refrigerant charges are listed as circuit 1/circuit 2 and provide only an estimate. Final charge requires sound field charging practice.
2. Operating charge estimate includes the air-cooled self-contained, remote air-cooled condenser, and 25 feet of interconnecting refrigerant piping.
3. At conditions of 95°F (35°C), condenser storage capacity is 95% full.
4. To determine the correct amount of refrigerant needed for a particular
application, reference the Trane Reciprocating Refrigeration Manual.
5. Field piping over 25 feet requires additional refrigerant. See Table 25,
p. 37 and Table 26, p. 38 to determine amounts.
Table 3. CCRC/CIRC remote air-cooled condenser
general data
Unit Size 20 29 32
Condenser Fan Data
Number/Type/Drive 4/Prop/Direct 4/Prop/Direct 4/Prop/Direct
Size (inches) 26 26 26
HP ea. 1 1 1
Nominal Cfm 18,800 21,200 32,000
Condenser Coil Data
Circuit 1 Size (in.) 1/46x71 1/46x71 1/64x71
Circuit 2 No./Size (in.) 1/46x71 1/64x71 1/64x71
Face Area (sq. ft.) 45.4 54.2 63.1
Rows/fpf 4/144 4/144 4/144
Ambient Temperature Operating Range
Standard Ambient (°F) 50-115 50-115 50-115
Low Ambient Option
(°F)
0-115 0-115 0-115
Table 4. SCWG/SIWG/SCRG/SIRG self-contained
heating coil
Filter Data for Heating Coil
Quantity 4
Size (inches) 20x18x2
Size (mm) (508x457x51)
Quantity 8
Size (inches) 20x20x2
Size (mm) (508x508x51)
Coil Data Type
Steam Coil NS 1
Hot Water Coil,
std. cap
Hot Water Coil,
hi-cap.
Notes:
1. Hot water and steam heating coils have Prima-Flo® fins and do not have turbulators.
2. For coil capacities, use TOPSS™ (Trane Official Product Selection Program).
5W 1
5W 2
Size (in)
2
24 x 58
1
48 x 6211219 x 1575
1
48 x 6211219 x 1575
RowsNo.
No.
Size (mm) fpf
2
609.6x1473.242
Table 5. Waterside economizer coil physical data -
SCXG 20, 25, 30, 35
Type Rows FPF
Chemically Cleanable 2 108 50 72
Mechanically Cleanable 2 108 50 72
Chemically Cleanable 4 108 50 72
Mechanically Cleanable 4 108 50 72
(in)
Height
Length
(in)
80
108
12 SCXG-SVX01H-EN

Pre-Installation Considerations

Receiving

Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage.
Inspect individual cartons before accepting. Check for rattles, bent carton corners, orother visible indications of shipping damage.
If a unit appears damaged, inspect it immediately before accepting the shipment. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery. Report concealed damage tothe freight line within theallotted time after delivery. Check with the carrier for their allotted time to submit a claim.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing, cartons, and crate.Take photos of damaged material if possible.
Notify the carrier’s terminal of the damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.
Notify yourTrane representative of the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.
Ship-Separate Accessories
Field-installed sensors ship separately inside unit’s main control panel. Extra filters, sheaves,and belts ship in unit’s fan motor section. Condenser plugs, spring isolators, and isopads ship in unit’s bottom left side.

Contractor Installation Responsibilities

Complete the following checklist before beginning final unit installation.
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and sufficient to support the unit and accessory weights. Level or repair the floor before positioning the unit if necessary.
Allow minimum recommended clearances for routine maintenance and service. Allow space at end of the
unit for shaft removal and servicing. Refer to unit submittals for dimensions. See also
Clearances,” p. 24.
Allow three fan diameters above the unit for the discharge ductwork. Return air enters the rear of the unit and conditionedsupply air discharges through the top.
Electrical connection knockouts are on the top, leftside of the unit.
Allow adequate space for piping access and panel removal. Condenser water piping, refrigerant piping, and condensate drainconnections are on the lowerleft end panel.
Note: Unit height and connection locations will change if
using vibration isolators. The unit height may increase up to 5 7/8” with spring type isolators.
Electrical supply power must meet specific balance and voltage requirements as described in section
“Installation - Electrical,” p. 39.
Water-cooled units only:The installeris responsible for providing a condenser main, standby water pump, cooling tower, pressure gauges, strainers, and all components for waterside piping. See
p. 32 for general waterside recommendations.
Air-cooled units only: The installer is responsible for providing and installing the remote air-cooled condenser and refrigerant piping.
“Service
“Water Piping,”

Unpackaging

Commercial self-contained units ship assembled with protective coverings over the coil and discharge openings.
Figure 2, p. 14 illustrates a typical shipping package.
Unit Protective Covers
Remove the shipping protection coverings from the human interface panel (HI) at the control panel, the filter box (or air inlet opening), the discharge air opening, and optional variable frequency drive (VFD).
Supply Fan Isolators
Remove the shipping channels and mounting bolts from beneath the fan. See Figure 4, p. 15. Open both fan compartment access doors to access the channels.There are four mounting points for 20-38 ton units.
Note: For 20-38 ton units, do not remove the fan
assembly shipping blocks and tie down bolts if the fan speed is 750 rpm or less.
While keeping the fan mounting frame level, turn the fan
isolator height adjusting bolts until the fan housing P­gasket compresses 1/4” against the roof transition piece. See Figure 4, p. 15.
SCXG-SVX01H-EN 13
Pre-Installation Considerations
Figure 2. Typical unit mounting on shipping skid
Figure 3. Fan isolator locations
14 SCXG-SVX01H-EN
Figure 4. Supply fan horizontal isolation shipping
bracket
Pre-Installation Considerations
SCXG-SVX01H-EN 15

Dimensions & Weights

Table 6. SCWG/SIWG weight, lbs.
Unit Tons Base Weight - lb (kg)
20 2227 (1010) 25 2697 (1223) 30 2765 (1254) 35 2834 (1286)
Notes:
1. All unit weights include refrigerant, water and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
3. Split-apart unit weights are approximately: 60% total unit weight =
compressor section, 40% total unit weight = fan section.
Table 7. SCRG/SIRG weight, lbs (kg)
unit tons base weight
20 2311 (1048) 25 2380 (1079) 32 2448 (1110)
Notes:
1. All unit weights include refrigerant, water and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
3. Split-apart unit weights are approximately: 60% total unit weight =
compressor section, 40% total unit weight = fan section.
16 SCXG-SVX01H-EN
Figure 5. SCWG/SIWG, in.
Dimensions & Weights
6.75”
SCXG-SVX01H-EN 17
Dimensions & Weights
Figure 6. SCRG/SIRG, in.
6.75”
18 SCXG-SVX01H-EN
Table 8. Detail dimensions, in.
Model A B C D E F
SCWG/SCRG 20 20 10 3/4 58 1/2 5 1/8 13 1/4 11 1/2 SCWG/SCRG 25 19 1/4 12 1/4 57 5/8 5 1/8 13 1/4 11 1/2
SCWG 30 - 35
SCRG 32
18 14 5/8 56 1/2 5 1/8 13 1/4 11 1/2
Figure 7. SCRG/SIRG/SCWG/SIWG detail “A”
electrical connections, in.
Dimensions & Weights
Note: When unit is ordered with horizontal supply,
ensure that all applicable codes are considered when installing equipment. Special attention should be made to over head clearances of unit/ ducting to meet code requirements.
Figure 8. Detail “B” discharge options, in.
SCXG-SVX01H-EN 19
Dimensions & Weights
Figure 9. CCRC/CIRC air-cooled condenser
AA
AB
AC
OPTIONAL LOW AMBIENT DAMPER (ONE DAMPER PER CIRCUIT)
REFRIGERANT LINE CONNECTIONS
FRONTAL VIEW
REFRIGERANT CIRCUIT 2
REFRIGERANT CIRCUIT 1
OPTIONAL LOW AMBIENT DAMPER
24 VOLT WIRE ENTRY HOLE SIZED
3
FOR
/4” CONDUIT
115 VOLT WIRE ENTRY HOLE SIZED FOR
3
/4” CONDUIT
SUPPLY VOLTAGE WIRE ENTRY HOLE SIZED FOR 1” CONDUIT
B
C
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 1)
(HOT GAS CONNECTION REFRIG. CIRCUIT 1)
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 2)
(HOT GAS CONNECTION REFRIG. CIRCUIT 2)
Table 9. CCRC/CIRC air-cooled condenser dimensions & weight, in-lbs.
Model AA AB AC shipping weight operating weight
CCRC/CIRC 20 70 1/8 88 88 2030 1906 CCRC/CIRC 29 70 1/8 88 88 2084 1960 CCRC/CIRC 32 70 1/8 88 88 2138 2014
Table 10. CCRC/CIRC refrigerant connections, in.
Model E F G H J K L M N
CCRC/CIRC 20-32 66 7/8 14 3/8 18 1/2 24 3/4 29 5/8 7/8 5/8 7/8
Table 11. CCRC/CIRC electrical connections, in.
Model A B C
CCRC/CIRC 20-32 4 1/2 10 1/2 17 1/2
20 SCXG-SVX01H-EN
Figure 10. Hot water coil: left-hand connections
Dimensions & Weights
Table 12. Hot water coil dimensions & weight, in-lbs
A B C D E F G H J K Weight
one-row coil 53 3/4 4 7/8 73 1/2 16 5/8 6 3/4 7 1/2 23 1/8 37 1/4 1 3/4 2 1/2 415 two-row coil 53 3/4 5 1/8 73 1/2 16 5/8 6 3/4 7 1/2 22 3/8 37 1/4 2 3/4 3 5/8 510
Figure 11. Hot water coil: right-hand connections
SCXG-SVX01H-EN 21
Dimensions & Weights
40 15/16"
53 13/16"
22 1/2"
3 5/16"
15 7/8"
1"
36 15/16"
3 7/8"
9 3/8"
6 3/4"
16 15/16"
35"
PIPING CONNECTIONS 2 1/2" NPTE
STEAM INLET 1" FEMALE CONN
CONDENSATE RETURN TRAP 1 1/2" FEMALE CONN
CONDENSATE RETURN TRAP 1" FEMALE CONN
VACUUM BREAKER 1" FEMALE CONN
VACUUM BREAKER 1" FEMALE CONN
30 7/8"
2 1/8"
92 3/4"
73 1/2"
10 15/16"
64 1/2"
11"
3/4" (4X) ISOLATOR MOUNTING LOCATION ON BOTTOM OF UNIT
VERTICAL DISCHARGE
RIGHT VIEW
TOP VIEW
Figure 12. Steam coil: left connections
92 3/4"
73 1/2"
VERTICAL DISCHARGE
30 7/8"
2 1/8"
14 9/16"
64 1/2"
TOP VIEW
3/4" (4X) ISOLATOR MOUNTING LOCATION ON BOTTOM OF UNIT
11"
Note: Steam Coil Weight 460 Lbs.
Figure 13. Steam coil: right connections
53 13/16"
36 15/16"
22 1/2"
3 5/16"
15 7/8"
40 15/16"
1"
9 3/8"
3 7/8"
6 3/4"
16 15/16"
LEFT VIEW
35"
CONDENSER FITTINGS 1 1/2" NPTI
ELECTRICAL CONNECTIONS
Note: Steam Coil Weight 460 Lbs.
22 SCXG-SVX01H-EN
Dimensions & Weights
Figure 14. Electric Heat Coil
Table 13. Electric heat coil dimensions & weight, in-lbs.
Unit Size A B C D Weight
20 tons 70 1/4 4 7/8 11 1/2 19 460 25 tons 70 1/4 4 1/8 11 1/2 19 460 30 - 35
tons
Note: Coil box height is 8 in.
70 1/4 2 7/8 11 1/2 19 460
Figure 16. Waterside Economizer
Table 15. Waterside economizer weight, in-lbs.
Weight
Unit size 2-row 4-row
20 - 35 tons 488 584
Figure 15. Flexible horizontal discharge plenum
Figure 17. Airside Economizer
Table 14. Flexible horizontal discharge plenum
dimensions & weights, in-lbs.
20-35 tons A B C Weight
Low height 35 17 1/4 86 1/2 262
Standard height 35 25 1/4 86 1/2 352
Table 16. Airside economizer dimensions & weight, in-lbs.
Unit Size A B C D E F (1) F (2) G (1) G (2) H (1) H (2) J K L M Weight
SCWG/SIWG 20, 25 SCRG/SIRG 20
SCWG/SIWG 30, 35 SCRG/SIRG 25, 32
36 65 5/8 37 74 1/4 6 1/8 56 1/2 49 3/4 23 1/4 20 1/2 5 5/8 7 20 1/2 17 1/8 12 49 3/4 273
36 65 5/8 37 74 1/4 6 1/8 61 3/8 62 3/4 28 1/8 20 1/2 3 1/4 7 20 1/2 17 1/8 5 1/2 62 3/4 273
SCXG-SVX01H-EN 23
Dimensions & Weights
Figure 18. Detail “B” (top) and Detail “A” (bottom)
Table 17. Service and code clearance requirements
Side Distance Purpose
42 in.
front
(20-38 tons) 18 in.
left
36 in.
77 in. right 36 in. provides uniform airflow inlet 18 in. provides uniform airflow
NEC code requirement air-cooled units only
refrigeration & waterside component service fan shaft removal

Service Clearances

See Figure 19, p. 24 andFigure 20, p. 24 for recommended service and code clearances.
Figure 19. Top view CCRC/CIRC 20, 29, 32
96” (2132 mm)
48”
(1066 mm)
96” (2132 mm)
Table 18. Service and code clearance requirements
Side Distance Purpose
42 in.
front
(20-38 tons) 18 in.
left
36 in. 77 in.
right 36 in. provides uniform airflow
inlet 18 in. provides uniform airflow
NEC code requirement air-cooled units only
refrigeration & waterside component service fan shaft removal
Note: When unit is ordered with horizontal supply,
ensure that all applicable codes are considered when installing equipment. Special attention should be made to overhead clearances of unit/ ducting to meet code requirements.
Figure 20. Top view of self-contained unit showing
recommended service and code clearances
air inlet
18” minimum
48” (1066 mm)
Control
Panel
See
table
42” minimum
Control Panel
36” minimum
24 SCXG-SVX01H-EN

Installation - Mechanical

Unit Handling Procedures

WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
Figure 21. Assembled unit gravity block location
Before lifting the unit or modular component, determine the approximate center of gravity for lifting safety. See
Figure 21, p. 25 for assembled modular units and Figure 22, p. 26 for split-apart units.The center of gravity
may vary slightly within the gravity block depending on unit options.
Always test-lift the unit todetermine the exactunit balance
and stability before hoisting it to the installation location. See Figure 23, p. 26 and Figure 24, p. 27 for typicalrigging procedures and proper rigging equipment usage.
Table 19. Gravity block dimensions
Model A B C D
SCWG 36 14 38 12
SCRG 36 16 40 12
SCXG-SVX01H-EN 25
Installation - Mechanical
Figure 22. Split-apart unit gravity block location
Fan Section Only
Compressor Section Only
Figure 23. Split-apart modular unit proper rigging (L) and fan section (R)
26 SCXG-SVX01H-EN
Figure 24. Assembled modular unit proper rigging

Skid Removal

The unit ships on skids to provide forklift locations from
the front or rear.The skid allows easy maneuverability of the unit during storage and transportation. Remove the skids before placing the unit in its permanent location.
Remove the skids using a forklift orjack. Lift one end ofthe unit off of the skids. See Figure 21, p. 25 and Figure 22,
p. 26 for unit gravity block location. Slide the skids out and
lower the unit at the installation location.
NOTICE:
Equipment Damage!
Do not use hooks to lift unit or hook into open channels to lift unit.This could cause unit damage
1. Position rigging sling under wood shipping skid.
2. Use spreader bars to avoid unit damage.
3. When using a forklift, exercise caution to prevent unit damage.
4. Use the standard fork length to lift one end and drag or pull unit while skidding the opposite end.
5. The unit center of gravity will fall within center of gravity block at various locations depending on unit options.
Installation - Mechanical
6. Use hooks to lift fan sectiononly.Do not hook into open channels to lift unit.
7. See unit nameplate for unit weight.
8. Do not stack units.

Installation Preparation

Important: Before installing the unit, perform the
following procedures to ensure proper unit operation.
Before installing the unit, perform the following procedures to ensure proper unit operation.
1. Position the unit and skidassembly in its finallocation. If unit shipped split-apart, follow the procedure in the
“Split-Apart Unit Assembly,” p. 28 before completing
this step.Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location. See Figure 23, p. 26 and
Figure 24, p. 27 for typical rigging procedures,
including cautions and proper uses of such equipment as fork lifts, spreader bars, and hooks.
2. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location. See
“Unit Handling Procedures,” p. 25 for proper
rigging procedures and cautions.
3. Remove the skids from under the unit. See “Skid
Removal,” p. 27.
4. Remove the protective shipping covers from the unit.
5. Verify isolators are properly tightened for operation. See
“Unit Vibration Isolator Option,” p. 29.
Note: Unit height and connection locations will change if
external vibration isolators are used.The unit may be raised an additional 5-7/8 inches with spring­type isolators.
Note: Unit height and connection locations will change if
the unit is constructed to be split-a-part in the field. See unit submittal drawings for connection locations.
6. Tighten compressor isolator mounting bolts.Torque to 18 ft. lbs. (± 2 ft. Lbs.)
7. Electrical supply power must meet specific balance and voltage requirements, as described in section
“Installation - Electrical,” p. 39.
8. Water-cooled units only (model SCWG): The installer must furnish andinstall a condenser mainand standby water pump, cooling tower, pressure gauges and all components for the waterside piping. See
Waterside Recommendations: CoolingTowers,” p. 32.
9. Air-cooled units only (model SCRG): These units require field-installation of a remote air-cooled condenser and refrigerant piping. See
System,” p. 36.
“General
“Refrigerant
SCXG-SVX01H-EN 27
Installation - Mechanical

Split-Apart Unit Assembly

1. Ensure the tagging information on the fan section nameplate matches that on the compressor nameplate.
2. Remove the connector brackets holding the sheet metal shipping cover on compressor section. Retain brackets and screws.
3. Remove shipping cover from the compressor section and verify the ship-with package contains:
a. suction and liquid line couplings
b. insulation
c. sheet metal screws
4. Lift fan section onto the compressor section using the rigging method in
5. Remove skid from the fan section, placing the fan section onto the compressor section. Reference
Figure 26, p. 29.
6. Install the connection brackets with the sheet metal screws (referenced in step 2) on all sides of the unit. Reference Detail “A” in
7. Removethe unit panels labeled RU and RL in Figure 25,
p. 28. To remove panels, first remove the four shipping
screws located in the corner of each panel. Next, turn the remaining 1/4 turn fasteners to the unlatch position.The panel is supported by a “lip” channel.So, lift the panel up and off the unit to remove it. See Detail
“A” i n
Figure 26, p. 29.
8. Connect the drain hose to the drainpan outlet fitting and secure it with the drain hose clamp provided.
9. See “Refrigerant System,” p. 36 for piping procedures.
10. Remove panel FLR and open the bottom control panel door, FLL. Pull the fan motor leads (coiled in the fan
Figure 25. Modular unit panel description and internal connections
Figure 23, p. 26.
Figure 26, p. 29.
section) through the knockout in the bottom of the fan section to the control panel. Ensure that the bushing is installed in the hole to prevent the wires from chafing. Refer to the unit wiring diagrams to connect the fan motor leads properly and ensure correct phase sequencing.
IntelliPak Units (UCM) Only
11. Remove panels FML, FMM, and FMR.
12. Pull the circular plug connector (CPC) from the compressor section through the knockouts into the fan section. Install the bushings (provided on the wiring harnesses) in the knockouts.\
13. Using the CPC wiring diagram, connect the male CPC to the female CPC in the top control panel.
14. If the unit has the mixed air temperature option, route the capillary tube on back of the filter rack.
Units with Thermostat Only
15. Remove panel FMR. See Note 1 on Figure 25, p. 28.
16. Pull frost protection wires from the bottom control panel through knockouts in bottom of fan section. Route wires to the appropriate frost protection switches on the evaporator coil. Reference the unit wiring diagrams to connect frost protection wiring connectors.
Air-Cooled Units Only
17. Route the refrigerant circuit wires for circuits 1 and 2 from the bottom control panel through the knockouts to the solenoid valves.The solenoid valves are located in the liquid refrigerant lines on the right-hand side of the unit. Refer to the unit wiring diagrams to make splice connections.
28 SCXG-SVX01H-EN
Figure 26. How to assemble the modular unit
Installation - Mechanical

Unit Vibration Isolator Option

If your job requires external vibration isolation, two options are available: isopads or spring-type isolators. Isopads should be placed under the unit at locations indicated on the factory-provided isolator sheet.
Set the spring-type isolators (Figure 27, p. 29) in position after the unit is removed from skids before making electrical, piping, or duct connections. All units require a minimum of four isolators per unit. But some may require six isolators, depending upon unit options.
Note: Trane strongly recommends you consult a
vibration specialist before double-isolating the unit. Double isolation is not recommended.
If you decide to externally isolate the unit, use spring-flex, type CP isolators.The spring number is marked on the outer housing. See Figure 27, p. 29.
To install external isolators, complete the
following procedure.
1. Locate the isolators under unit base at the locations indicated on the factory-provided isolator placement sheet. Lift one end of the unit at a time to position isolators to the floor, using anchor bolts.
2. Level the unit by adjusting isolator heights. Unit weight may cause the upper housing to rest on the lower housing of the spring isolators.The isolator clearance shown in the side view of must be 1/4 - 1/2 inches.To increase the clearance, lift the unit off the isolator and turn the leveling bolt counterclockwise. Recheck the unit level and the housing clearances. Maximum allowable difference
Figure 27, p. 29,
between isolator heights is 1/4 inch. Shim as required under the isolators.
Note: The compressors and fan assembly are internally
isolated on most units. Due to this, the addition of external isolation devices (spring mounting isolators) is at the discretion of the building or HVAC system designer.
Figure 27. Optional spring isolator dimensional data
SCXG-SVX01H-EN 29
Installation - Mechanical

Duct Connections

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
Return air enters the rear of the unit and conditioned supply air discharges through the top. Attach supply air ductwork directly to the unit’s top panel, around the fan discharge opening. A duct collar is not provided.
Note: Units equipped with the flexible horizontal
discharge plenum option may include a duct collar when holes are factory cut. If discharge openings are field-cut, refer to the “Plenum Installation” section.
Install all air ducts accordingto the National Fire Protection
Association standards for the “Installation of Air
Conditioning and Ventilation Systems other than ResidenceType (NFPA 90A) and ResidenceType Warm Air Heating and Air Conditioning Systems (NFPA 90B).
Make duct connections to the unit with a flexible material such as heavy canvas. If a fire hazard exists,Trane recommends using Flexweave 1000, type FW30 or equivalent canvas. Use three inches for the return duct and three inches for the discharge duct. Keep the material loose to absorb fan vibration.
Note: The compressors and fan assembly are internally
isolated.Therefore, external isolation devices (spring mounting isolators) are at the discretion of a vibration specialist consulted by the building or HVAC system designer.
Figure 28. Duct connection recommendations
Discharge Duct
3-inch Flexible Duct
Run the ductwork straight from the opening for a minimum of three fan diameters. See Figure 28, p. 30. Extend remaining ductwork as far as possible without changing size or direction. Do not make abrupt turns or transitions near the unit due to increased noise and excessive static losses. Use elbows with splitters or turning vanes to minimize static losses.
Poorly constructed turning vanes may cause airflow generated noise. Align the fan outlet properly with the ductwork to decrease noise levels in the duct and to increase fan performance. To complete trunk ductwork to the VAV terminal units, refer to the VAV box manuals for specific requirements. Check total external static pressures against fan characteristics to be sure the required airflow is available throughout the ductwork.
To achieve maximum acoustical performance, minimize
the duct static pressure setpoint
3 Fan Diameters
Return Air

Plenum

Before installing theplenum attach the insulation strip that ships with the plenum. See Figure 29, p. 31 for proper insulation location. Align the plenum front with the control panel side of the unit. Using the strips and screws provided, secure the plenum to the unit.
Treat field-cut holes to prevent fiberglass from entering
the airstream.
Note: Plenum insulation must be applied properly to
prevent air bypass around the plenum. See
Figure 29, p. 31.
30 SCXG-SVX01H-EN
Loading...
+ 84 hidden pages