Trane SCWF 35, SCWF 25, SCWF 42, SCWF 38, SCWF 52 Installation, Operation And Maintenance Manual

...
0 (0)
Installation, Operation, and Maintenance
IntelliPak™ Commercial Self-Contained Signature Series
20 to 110 Tons
SSCCWWFF aanndd SSIIWWFF – 20 to 110 Ton SSCCRRFF aanndd SSIIRRFF – 25 to 60 Ton
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
June 2018
SSCCXXFF--SSVVXX0011QQ--EENN
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee MMaatteerriiaall SSaaffeettyy DDaattaa SShheeeettss ((MMSSDDSS))//SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee MMSSDDSS//SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
©2018 Ingersoll Rand
SCXF-SVX01Q-EN
IInnttrroodduuccttiioonn
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
•• AAllll IInnggeerrssoollll RRaanndd ppeerrssoonnnneell mmuusstt ffoollllooww IInnggeerrssoollll RRaanndd EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy ((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc.. AAllll ppoolliicciieess ccaann bbee ffoouunndd oonn tthhee BBOOSS ssiittee.. WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess..
•• NNoonn--IInnggeerrssoollll RRaanndd ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss..
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Running edits included.
Updated motor electrical data.
SCXF-SVX01Q-EN
3
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . 8
R-410A Compressors . . . . . . . . . . . . . . . . . . . . . 8
Signature Series Self-Contained Unit
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Standard Controls. . . . . . . . . . . . . . . . . . . . . 9
Human Interface Panel . . . . . . . . . . . . . . . . 9
Unit Control Module . . . . . . . . . . . . . . . . . . 9
Optional Controls . . . . . . . . . . . . . . . . . . . . 10
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . 10
Model Number Description. . . . . . . . . . . . . . . . 11
Commercial Self-Contained Signature
Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Commercial Self-Contained Air-Cooled
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Data . . . . . . .. . . . . . . . .. . . . . . . . .. . . . . 14
Pre-Installation . . . . . . . . . .. . . . . . . . . . . . . . . . . . 21
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Receiving Checklist. . . . . . . . . . . . . . . . . . . 21
Contractor Installation
Responsibilities . . . . . . . . . . . . . . . . . . . . . . 21
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . 21
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Unit Protective Covers. . . . . . . . . . . . . . . . 23
Supply Fan Isolators . . . . . . . . . . . . . . . . . 23
Dimensional Data . . . . . . . . . . . . . . . . . .. . . . . . . 24
Steam and Hot Water Coils . . . . . . . . . . . . . . . 28
Steam Coils . . . . . . . . . . . . . . . . . . . . . . . . . 28
Hot Water Coils . . . . . . . . . . . . . . . . . . . . . . 28
Plenum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Airside Economizer . . . . . . . . . . . . . . . . . . . . . . 30
Service Clearances . . . . . . . . . . . . . . . . . . . . . . 31
Weights . . . . . .. . . . . . . .. . . . . . . . . . . . . . . . . . . . . 32
Installation - Mechanical. . . . .. . . . . . . . . . . . . . 34
Unit Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installation Preparation . . . . . . . . . . . . . . . . . . 35
Unit Vibration Isolator Option. . . . . . . . . . . . . 35
Unit Isolator Installation
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Duct Connections. . . . . . . . . . . . . . . . . . . . . . . . 36
Installing the Plenum . . . . . . . . . . . . . . . . . . . . 36
Installing the Airside Economizer . . . . . . . . . 37
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condenser Connections . . . . . . . . . . . . . . 38
Condensate Drain Connections. . . . . . . . 38
General Waterside Recommendations for Cooling
Towers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Waterside Piping Arrangements. . . . . . . 39
Water Temperature
Requirements . . . . . . . . . . . . . . . . . . . . . . . 39
Water Piping Verification . . . . . . . . . . . . . 39
Installating the Hydronic Coil . . . . . . . . . . . . . 39
Steam and Hot Water Coil . . . . . . . . . . . . 39
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . 40
Interconnecting Piping . . . . . . . . . . . . . . . 40
Preliminary Refrigerant
Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Installation - Electrical . . . . . . . . . . . . . . . .. . . . . 43
Unit Wiring Diagrams . . . . . . . . . . . . . . . . . . . . 43
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . 43
Voltage Range . . . . . . . . . . . . . . . . . . . . . . . 43
Voltage Imbalance . . . . . . . . . . . . . . . . . . . 43
Phase Monitor . . . . . . . . . . . . . . . . . . . . . . . 43
Control Power . . . . . . . . . . . . . . . . . . . . . . . 43
Selection Procedures . . . . . . . . . . . . . . . . . . . . 44
Static Pressure Transducer Installation
(VAV units only) . . . . . . . . . . . . . . . . . . . . . . . . . 45
Transducer Location . . . . . . . . . . . . . . . . . 45
Installing the Transducer . . . . . . . . . . . . . 46
Zone Sensor Options for Control
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Standard with All Units:
BAYSENS077 . . . . . . . . . . . . . . . . . . . . . . . . 46
CV Unit Zone Sensor Options . . . . . . . . . 47
Integrated Comfort Systems Sensors for
CV and VAV Applications. . . . . . . . . . . . . . . . . 47
CV and VAV Unit Zone Sensor
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Zone Sensor Installation . . . . . . . . . . . . . . . . . 48
Mounting Location . . . . . . . . . . . . . . . . . . . 48
Mounting the Subbase . . . . . . . . . . . . . . . 48
4
SCXF-SVX01Q-EN
TTaabbllee ooff CCoonntteennttss
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Standard Remote Sensor
(BAYSENS077) . . . . . . . . . . . . . . . . . . . . . . 49
Programmable Zone Sensors. . . . . . . . . . . . . 49
BAYSENS119 . . . . . . . . . . . . . . . . . . . . . . . . 49
Time Clock Option . . . . . . . . . . . . . . . . . . . . . . . 50
Grasslin Time Clock Option . . . . . . . . . . . 50
Installing the Time Clock. . . . . . . . . . . . . . 50
Surface Mounting Inside Panel . . . . . . . . 50
Wiring the Time Clock . . . . . . . . . . . . . . . . 50
Remote Human Interface Panel
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Human Interface (HI) Panel. . . . . . . . . . . . 50
Remote Human Interface Panel. . . . . . . . 51
Location Recommendations . . . . . . . . . . 51
Ambient Temperature and Humidity
Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Mounting the Remote Human Interface
(RHI) Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Wall Mounting the RHI Panel. . . . . . . . . . 52
Wiring the Remote Human Interface. . . . . . . 53
Low Voltage (AC) Field Wiring
Connections . . . . . . . . . . . . . . . . . . . . . . . . . 54
Interprocessor Communication
Bridge Module Wiring . . . . . . . . . . . . . . . . 54
Communication Link (Shielded
Twisted Pair) Wiring. . . . . . . . . . . . . . . . . . 54
At the Self-Contained Unit . . . . . . . . . . . . 54
Connecting to Tracer Summit. . . . . . . . . . . . . 55
Communication Wiring. . . . . . . . . . . . . . . 55
Programming the Time Clock
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Setting the Time Clock. . . . . . . . . . . . . . . . 55
Programming the Time Clock . . . . . . . . . 55
Reviewing and Changing
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Manual Override . . . . . . . . . . . . . . . . . . . . . 56
Operating Principles. . . . . . . . .. . . . . . . . . . . . . . 57
Control Sequences of Operation . . . . . . . . . . 57
Occupied/Unoccupied
Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Field-Supplied Occupied/
Unoccupied Input on the RTM. . . . . . . . . 57
Tracer Summit System . . . . . . . . . . . . . . . 57
Factory-Mounted Time Clock. . . . . . . . . . 57
Unoccupied Sequence of Operation . . . . . . . 57
Morning Warm-up . . . . . . . . . . . . . . . . . . . 57
Full Capacity Morning Warm-up
(MWU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Cycling Capacity Morning Warm-up
(MWU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Timed Override Activation—
ICS™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Timed Override Activation—Non-
ICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
VAV Drive Max Output . . . . . . . . . . . . . . . 58
Occupied Sequence. . . . . . . . . . . . . . . . . . . . . . 58
Occupied Zone Temperature—
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Zone Temperature Control (Unit
Model Number Digit 9 = 4 or 5) . . . . . . . . 58
Supply Air Temperature Control (Unit Model Number Digit 9 = 1, 2, 3,
or 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Units With Economizer . . . . . . . . . . . . . . . 59
Cooling/Waterside Economizer. . . . . . . . 59
Cooling/Airside Economizer. . . . . . . . . . . 59
Mechanical Cooling . . . . . . . . . . . . . . . . . . 59
Air-Cooled Units Only . . . . . . . . . . . . . . . . 59
Water-Cooled Units Only . . . . . . . . . . . . . 59
Auto Changeover (Units with Heat
Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Occupied Zone Temperature—
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . 59
Hydronic Heat: Hot Water or
Steam. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Supply Air Setpoint Reset (VAV Units
Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Reset Based on Outdoor
AirTemperature. . . . . . . . . . . . . . . . . . . . . . 60
Reset Based on zone
temperature . . . . . . . . . . . . . . . . . . . . . . . . . 60
Supply AirTempering (Hot Water
and Steam VAV Units Only) . . . . . . . . . . . 60
Daytime Warm-up (Units with Supply Air Temperature Control
Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Supply AirTempering . . . . . . . . . . . . . . . . 60
SCXF-SVX01Q-EN
5
TTaabbllee ooff CCoonntteennttss
Changeover . . . . . . . . . . . . . . . . . . . . . . . . . 60
Thermostatic Expansion Valve. . . . . . . . . . . . 60
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Compressor Cycling. . . . . . . . . . . . . . . . . . 61
Compressor Lead/Lag
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Step Control . . . . . . . . . . . . . . . . . . . . . . . . . 61
Compressor Safety Devices. . . . . . . . . . . 62
Low Ambient Compressor
Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Evaporator Coil Frost Protection
FROSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Service Valve Option . . . . . . . . . . . . . . . . . 63
Waterside Components . . . . . . . . . . . . . . . . . . 63
Water Purge . . . . . . . . . . . . . . . . . . . . . . . . . 63
Water Piping Options. . . . . . . . . . . . . . . . . 63
Basic Water Piping . . . . . . . . . . . . . . . . . . . 63
Intermediate Water Piping . . . . . . . . . . . . 63
Water Flow Switch Option . . . . . . . . . . . . 63
Water-Cooled Condensers . . . . . . . . . . . . 63
Waterside Economizer Option. . . . . . . . . 63
Waterside Economizer Flow
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Constant Water Flow with
Intermediate Piping . . . . . . . . . . . . . . . . . . 64
Variable Water Flow with
Intermediate Piping . . . . . . . . . . . . . . . . . . 64
Unit Airside Components. . . . . . . . . . . . . . . . . 65
Supply Air Fan. . . . . . . . . . . . . . . . . . . . . . . 65
Low Entering Air Temperature
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
High Duct Temperature
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Dirty Filter Sensor Option . . . . . . . . . . . . . 65
Low Ambient Sensor (Air-Cooled
Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Supply Air Static Pressure Limit . . . . . . . 65
Variable Frequency Drive
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
VFD with Bypass . . . . . . . . . . . . . . . . . . . . . 66
Airside Economizer Option . . . . . . . . . . . 66
Comparative Enthalpy Control . . . . . . . . 66
Airside Economizers with Traq
Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Standard Two-Position Damper
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Airside Economizer Interface. . . . . . . . . . 67
Airside Economizer Interface with
Comparative Enthalpy. . . . . . . . . . . . . . . . 67
Air-Cooled Condensers . . . . . . . . . . . . . . . 67
Controls . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . 68
Points List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
RTM Module. . . . . . . . . . . . . . . . . . . . . . . . . 68
GBAS Module . . . . . . . . . . . . . . . . . . . . . . . 68
ECEM Module . . . . . . . . . . . . . . . . . . . . . . . 68
BCI-I option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
LCI-I Points List. . . . . . . . . . . . . . . . . . . . . . . . . . 68
Phase Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Unit Control Components . . . . . . . . . . . . . . . . 68
RTM Module Board—Standard on all
Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Compressor Module . . . . . . . . . . . . . . . . . 71
Human Interface Module—Standard
on all Units . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Remote Human Interface Module
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Waterside Module—Standard on All
Water-cooled Units. . . . . . . . . . . . . . . . . . . 71
Heat Module. . . . . . . . . . . . . . . . . . . . . . . . . 71
Ventilation Override Module (VOM)
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Trane Communications
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Exhaust/Comparative Enthalpy
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Ventilation Control Module
(VCM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Generic Building Automation
System Module Option . . . . . . . . . . . . . . . 73
Input Devices and System
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pre-Startup . . . . . . .. . . . . . . . .. . . . . . . . . . . . . . . . 79
Units with VFD . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Pre-Startup Checklist. . . . . . . . . . . . . . . . . . . . . 79
Supply Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Water-Cooled Unit Piping . . . . . . . . . . . . . . . . 79
Air-Cooled Units Only. . . . . . . . . . . . . . . . . . . . 79
6
SCXF-SVX01Q-EN
TTaabbllee ooff CCoonntteennttss
Units with Hydronic Heat . . . . . . . . . . . . . . . . . 80
Units with Electric Heat . . . . . . . . . . . . . . . . . . 80
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Startup . . . . . .. . . . . . . . .. . . . . . . . . . . . . . . . .. . . . 81
Air-Cooled Only . . . . . . . . . . . . . . . . . . . . . . . . . 81
Final Refrigerant Charge . . . . . . . . . . . . . . . . . 82
Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . 83
Operating & Programming
Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . 83
Startup Log. . . . . . . . . . . . . . . . . . . . . . . . . . 83
Maintenance . . . . . . . . .. . . . . . . . .. . . . . . . .. . . . 85
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Variable Frequency Drive (VFD) . . . . . . . 85
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Inspecting and Cleaning the Drain
Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Inspecting and Cleaning the Fan . . . . . . . . . . 87
Supply Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fan Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fan Bearings . . . . . . . . . . . . . . . . . . . . . . . . 88
Fan Belt Tension . . . . . . . . . . . . . . . . . . . . . 88
Measuring Belt Tension . . . . . . . . . . . . . . 88
Adjusting Belt Tension . . . . . . . . . . . . . . . 89
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Scroll Compressor Failure Diagnosis
and Replacement . . . . . . . . . . . . . . . . . . . . 91
40 Ton Air-Cooled Compressor
Suction Restrictor Replacement . . . . . . . 91
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . 92
Refrigerant Leak Test Procedure. . . . . . . 92
Brazing Procedures . . . . . . . . . . . . . . . . . . 93
System Evacuation Procedures . . . . . . . 93
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Scroll Compressor Failure Diagnosis
and Replacement . . . . . . . . . . . . . . . . . . . . 95
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Cleaning Coil Fin . . . . . . . . . . . . . . . . . . . . . . . . 97
Inspecting and Cleaning Coils . . . . . . . . . 97
Steam and Hot Water Coils . . . . . . . . . . . 97
Refrigerant Coils . . . . . . . . . . . . . . . . . . . . . 98
Draining the Waterside Economizer
Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Cleaning the Condenser . . . . . . . . . . . . . . 98
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Chemical Cleaning of Condenser and
Economizer Coil . . . . . . . . . . . . . . . . . . . . . 99
Piping Components. . . . . . . . . . . . . . . . . . . . . . 99
Water Valves . . . . . . . . . . . . . . . . . . . . . . . . 99
Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . 99
Maintenance Periodic Checklists . . . . . . . . . . 99
Monthly Checklist . . . . . . . . . . . . . . . . . . . . 99
Semi-Annual Maintenance. . . . . . . . . . . 100
Annual Maintenance . . . . . . . . . . . . . . . . 100
Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . 101
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . 101
System Checks . . . . . . . . . . . . . . . . . . . . . 101
Additional Diagnostic Resources. . . . . . . . . 102
Wiring Diagrams . . . . . . . . . .. . . . . . . . . . . . . . . 115
SCXF-SVX01Q-EN
7

Overview

NNoottee:: One copy of this document ships inside the
control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This manual describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
This manual covers installation, operation and maintenance of 20-110 ton Signature Series Commercial Self Contained products with R-410A refrigerant.

R-410A Compressors

Use crank case heaters which must be energized 24 hours prior to compressor start.
Contain POE oil which readily absorbs potentially damaging moisture from air.
Control box includes a phase monitor to detect phase loss, line voltage imbalance and reversal.
Refer to previous IOM versions for R-407C and R-22 units, or contact your local Trane representative.
Refer to the appropriate IOM for air-cooled condenser CXRC-SVX01*-EN and programming IntelliPak™ controls PKG-SVP01*-EN.

Signature Series Self-Contained Unit Components

Commercial self-contained units are complete HVAC systems used in floor-by-floor applications. Units are easy to install because they feature:
A single point power connection.
Factory-installed and tested controls.
A single water point connection.
Factory-installed options.
An internally trapped drain connection.
NNoottee:: Refer to the following figure for typical unit
components.
The hermetically sealed scroll compressor motors utilize internal motor protection and time delays to prevent excessive cycling.
Water-cooled units have 2-6 refrigerant circuits and ship with a full refrigerant and oil charge. Each circuit includes filter drier, pressure relief valve, sight glass/ moisture indicator, thermal expansion valve with sensing bulb and external equalizing line, discharge line schrader valve, suction line schrader valve and high and low pressure cutout switches. The water­cooled condensers are shell and tube type with an internal subcooler. Condensers are available as mechanically or chemically cleanable.
Air-cooled units have two circuits and ship with oil and a dry nitrogen holding charge. Therefore, air-cooled units require field piping refrigerant connections to an air-cooled condensing unit and charging. Each circuit includes filter drier (field installed), sight glass/ moisture indicator, thermal expansion valve with sensing bulb and external equalizing line, discharge line schrader valve, suction line schrader valve, high and low pressure cutout switches, discharge line check valve and liquid line solenoid valve.
All units include liquid line service valves for each circuit as standard (suction and discharge service valves are optional).
Evaporator fans are double width, double inlet and forward curved with fixed pitch belt drive assembly. Variable frequency drives are optional. EISA efficiency open drip proof (ODP) and totally enclosed fan cooled (TEFC) motor options are available.
8
SCXF-SVX01Q-EN
Figure 1. Commercial self-contained signature series unit components
Waterside economizer (cleanable option shown)
Sight glasses with ports for viewing while unit is running
Unit mounted microprocessor control with easy-to-read human interface panel
Swing out VFO panel with Tri-VFO for efficient VAV operation
Trane 3-D® Scroll Compressor for reliability, efficiency and
quiet operation Two-bolt connection on cleanable condenser for quick, easy maintenance
Waterside valve package option to enhance system efficiency
Internally trapped drain for low cost installation
2-inch flat filter box inside unit casing
OOvveerrvviieeww

Standard Controls

Standard controls supplied with the unit include the human interface (HI) panel with unit control module (UCM). All basic setup parameters are preset from the factory.

Human Interface Panel

The HI is unit mounted and accessible without opening the unit’s front panel. It allows easy setpoint adjustment using the HI keypad. In addition, the HI displays all unit operating parameters and conditions in a clear language display, which can be configured for either English, French, or Spanish.
The optional remote human interface (RHI) will control up to four self-contained units, each containing an interprocessor communications bridge (IPCB). It has all the same features as the unit-mounted HI except for the service mode.
For more information on setpoint defaults and ranges and unit programming, see the Self-Contained Programming Guide, PKG-SVP01*-EN. A copy ships with each unit.

Unit Control Module

The UCM provides “smart” unit control with safety features and control relays for pumps, dampers, etc.
SCXF-SVX01Q-EN
The Signature Series self-contained unit is controlled by a microelectronic control system that consists of a network of modules. Modular Series self-contained unit is controlled by microelectronic control system consisting of a network of modules.These modules are referred to as unit control modules (UCM). In this manual, the acronym UCM refers to the entire control system network.
These modules perform specific unit functions using proportional/integral control algorithms. They are mounted in the unit control panel and are factory wired to their respective internal components. Each module receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request; i.e., economizing, mechanical cooling, heating, ventilation.
See the Owner’s section of this manual for a detailed description of each module’s function.
9
OOvveerrvviieeww

Figure 2. Right side view of unit Optional Controls

Optional controls include a disconnect switch, dirty filter switch, water flow switch (water-cooled only), supply air temperature reset, or external setpoint inputs. Daytime heating is available on units with electric, steam, or hot water heat control options. Morning warm-up operation is available on all units.
The static pressure probe, zone night heat/morning warm-up, supply air temperature reset sensor options ship separate inside the unit control panel for field installation. For more detailed information on the unit control options, see the Owner’s section of this manual.

Unit Nameplate

The unit nameplate identifies the unit model number, appropriate service literature, and wiring diagram numbers. It is mounted on the left end of the unit control panel.
10
SCXF-SVX01Q-EN

Model Number Description

Commercial Self-Contained Signature Series

Digit 1 — Unit Model
S = Self-Contained
Digit 2 — Unit Type
C = Commercial I = Industrial
Digit 3 — Condenser Medium
W = Water-cooled R = Air-cooled
Digit 4 — Development Sequence
F = Signature Series
Digit 5— Refrigerant Circuit Configuration
U = Standard Capacity V = High Capacity
Digit 6, 7 — Unit Nominal Capacity
20 = 20 Tons (water only) 22 = 22 Tons (water only) 25 = 25 Tons (water or air) 29 = 29 Tone (water or air) 30 = 30 Tons (air only) 32 = 32 Tons (water only) 35 = 35 Tons (water or air) 38 = 38 Tons (water only) 40 = 40 Tons (air only) 42 = 42 Tons (water only) 46 = 46 Tons (water only) 50 = 50 Tons (air only) 52 = 52 Tons (water only) 58 = 58 Tons (water only) 60 = 60 Tons (air only) 65 = 65 Tons (water only) 72 = 72 Tons (water only) 80 = 80 Tons (water only) 90 = 90 Tons (water only) C0 = 100 Tons (water only) C1 = 110 Tons (water only)
Digit 8 — Unit Voltage
6 = 200 volt/60 hz/3 ph 4 = 460 volt/60 hz/3 ph 5 = 575 volt/60 hz/3 ph
Digit 9 — Air Volume/Temp Control
2 = VFD and supply air temp ctrl 3 = VFD w/ bypass and supply air temp ctrl 4 = Constant volume, zone temp cool only 5 = Constant volume, w/ zone temp heat/
cool
6 = Constant volume and supply air temp ctrl
Digit 10, 11 — Design Sequence
** = Factory Assigned
Digit 12 — Unit Construction
A = Vertical discharge B = Vertical discharge with double wall
Digit 13— Flexible Horizontal Discharge Plenum Type
B = STD plenum w/ factory-cut holes C = Low plenum w/ factory-cut holes E = Std plenum w/ field-cut holes F = Low plenum w/ field-cut holes H = STD plenum double wall w/ field-cut
holes
J = Low plenum double wall w/ field-cut holes K = Extended height plenum w/factory-cut
holes, ship separate L = STD plenum w/factory-cut holes, ship
separate M = Low plenum w/factory-cut holes, ship separate N = Extended height plenum w/field-cut holes, ship separate P = STD plenum w/field-cut holes, ship
separate R = Low plenum w/field-cut holes, ship
separate T = Extended height double-wall plenum w/ field-cut holes, ship separate U = STD double-wall plenum w/field-cut
holes, ship separate V = Low double-wall plenum w/field-cut
holes, ship separate W = STD double-wall (perf) plenum w/field­cut holes (90 to110 ton only) X = Low double-wall (perf) plenum w/field-
cut holes (90 to 110 ton only) Y = Extended height double-wall (perf)
plenum w/field-cut holes, ship separate (90 to 110 ton only)
0 = None
Digit 14— Motor Type
2 = ODP motor 4 = TEFC motor
Digit 15, 16 — Motor HP
05 = 5 hp 07 = 7.5 hp 10 = 10 hp 15 = 15 hp 20 = 20 hp 25 = 25 hp 30 = 30 hp 40 = 40 hp 50 = 50 hp (460V, 575V only) 60 = 60 hp (90 to 110 ton only)
Digit 17, 18, 19 – Fan RPM
040 = 400 rpm 045 = 450 rpm 050 = 500 rpm 052 = 525 rpm 055 = 550 rpm 057 = 575 rpm 060 = 600 rpm 065 = 650 rpm 070 = 700 rpm 075 = 750 rpm 080 = 800 rpm 085 = 850 rpm 090 = 900 rpm 095 = 950 rpm 100 = 1000rpm 105 = 1050 rpm 110 = 1100 rpm 115 = 1150 rpm 120 = 1200 rpm 125 = 1250 rpm 130 = 1300 rpm 135 = 1350 rpm
Digit 20 — Unit Isolators
A = Steam coil B = Hot water coil C = Electric heat, 1 stage D = Electric heat, 2 stage F = Hydronic heat ctrl interface G = Electric heat ctrl interface K = Steam coil ship separate, LH L= Hot water coil ship separate, LH T = Hot water coil, high capacity, LH U = Hot water coil, high capacity, LH, ship
separate
0 = None
Digit 21 — Unit Isolators
A = Isopads B = Spring isolators 0 = None
Digit 22— Unit Finish
1 = Paint - Slate Gray
Digit 23— Supply Fan Options
0 = Standard fan 1 = Low CFM fan
Digit 24— Unit Connection
1 = Disconnect switch 2 = Terminal block 3 = Dual point power (2 blocks)
SCXF-SVX01Q-EN
11
MMooddeell NNuummbbeerr DDeessccrriippttiioonn
Digit 25— Industrial Options
A = Protective coating evaporator coil B = Silver solder C = Stainless steel screws D = A and B E = A and C F = B and C G = A, B, and C 0 = none
Digit 26 — Drain PanType
A = Galvanized sloped B = Stainless steel sloped
Digit 27 — Waterside Economizer
A = Mechanical clean full capacity (4-row) B = Mechanical clean low capacity (2-row) C = Chemical clean full capacity (4-row) D = Chemical clean low capacity (2-row) 0 = None
Digit 28 — Ventilation Control
B = Airside econ w/Traq damper, top O/A C = Airside econ w/ std damper, top O/A E = Airside econ w/Traq damper &
comparative enthalpy, top O/A F = Airside econ w/ std damper &
comparative enthalpy, top O/A
H = 2-position damper ventilation interface J = Airside economizer interface K = Airside economizer interface w/
comparative enthalpy
Digit 29 — Water Piping
D = Left hand basic piping F = Left hand Intermediate piping K = Left hand basic w/ flow switch M = Left hand intermediate w/ flow switch 0 = None
Digit 30 — Condenser Tube Type
A = Standard condenser tubes B = 90/10 CuNi condenser tubes 0 = None (air-cooled only)
Digit 31 — Compressor Service Valves
1 = With service valves 0 = None
Digit 32— Miscellaneous System Control
1 = Time clock 2 = Interface for remote HI (IPCB) 3 = Dirty filter switch 4 = 1 and 2 5 = 1 and 3 6 = 2 and 3 7 = 1, 2 and 3 0 = None
Digit 33 — Control Interface Options
A = Generic BAS Module; 0-5 VDC (GBAS) B = Ventilation Override Module (VOM) D = Remote Human Interface (RHI) G = GBAS and VOM H = GBAS and RHI J = VOM and RHI M = GBAS, VOM, and RHI N = BACnet Communications Interface (BCI) P = BCI and GBAS Q = BCI and VOM R = BCI and RHI T = BCI and GBAS and VOM U = BCI and GBAS and RHI V = BCI and VOM and RHI W = BCI and GBAS and VOM and RHI 0 = None 1 = Lontalk Comm5 Interface (LCI) 2 = LCI and GBAS 3 = LCI and VOM 4 = LCI and RHI 5 = LCI and GBAS and VOM 6 = LCI and GBAS and RHI 7 = LCI and VOM and RHI 8 = LCI and GBAS and VOM and RHI
Digit 34— Agency
U = UL agency listing 0 = None
Digit 35— Filter Type
1 = 2” T/A w/ 2” rack 2 = 2” med. eff. T/A w/ 2” rack 3 = 4” bolt-on rack w/ 2” med eff. filter 4 = 6” rack w/ 2” construction T/A pre-filter &
4” filter space 5 = 6” rack w/ 2” med. eff. T/A pre-filter & 4”
filter space
Digit 36— Miscellaneous Control Option
A = Low entering air temp. protect device
(LEATPD)
B = High duct temp t-stat, ship separate C = Plenum high static switch, ship separate E = A and B F = A and C H = B and C L = A, B, and C 0 = None
12
SCXF-SVX01Q-EN

Commercial Self-Contained Air-Cooled Condenser

MMooddeell NNuummbbeerr DDeessccrriippttiioonn
Digit 1 — Unit Model
C = Condenser
Digit 2 — Unit Type
C = Commercial I = Industrial
Digit 3 — Condenser Medium
R = Remote
Digit 4 — Development Sequence
C = C
Digit 5, 6, 7 — Nominal Capacity
020 = 20 Tons 029 = 29 Tons 035 = 35 Tons 040 = 40 Tons 050 = 50 Tons 060 = 60 Tons
Digit 8 — Unit Voltage
4 = 460 Volt/60 Hz/3 ph 5 = 575 Volt/60 Hz/3 ph 6 = 200 Volt/60 Hz/3 ph
Digit 12 — Unit Finish
1 = Paint — Slate Gray
Digit 13— Coil Options
A = Non-Coated Aluminum C = Protective Coating Aluminum
Digit 14— Unit Isolators
0 = None A = Spring Isolators B = Isopads
Digit 15— Panels
1 = Louvered Panels
Digit 16— Agency
0 = None U = With UL Listing
Digit 9 — Control Option
0 = No Low Ambient, IPak A = No Low Ambient, T-Stat* B = Low Ambient, IPak C = Low Ambient, T-Stat*
Note: *T-Stat only available on SCRG.
Digit 10, 11— Design Sequence
** = Factory Assigned
SCXF-SVX01Q-EN
13

General Data

Table 1. SCWF/SIWF Water-cooled self-contained, 20 to 42 tons
Unit Size 20 22 25 29 32 35 38 42
Compressor Data
Quantity
Nominal Ton/comp
Evaporator Coil
Data
Circuits 2 2 2 2 2 3 3 3
Rows 2 2 3 or 6 2 4 or 6 3 4 or 6 3
Sq. Ft.
Fpf
Condenser Data
Minimum Gpm w/o
Econ
Minimum Gpm w/
Econ
Maximum Gpm
Evaporator Fan
Data
Quantity
Diameter 18" 18" 18" 18" 18" 20" 20" 25"
Minimum Hp
Minimum Kw
Maximum Hp
Maximum Kw
Minimum Design Cfm
Maximum Design Cfm
High Capacity
Option
Rows
Optional Low Flow
Fan 6
Diameter
Min/max Design Cfm
Refrigerant Charge,
lbs. R-410A
(Standard
Capacity/High
Capacity)
Circuit A 19.5 19.5 21.5 24.7
Circuit B 19.5 19.5 21.5 20.5
Circuit C
2 2 2
10 10 10
21.81 21.81 21.81 29.98 29.98 31.35 31.35 38.57
144 144 144 144 144 144 144 144
36 36 36 46 46 54 54 64
41 41 41 60 60 65 65 64
80 80 80 102 102 119 119 142
1 1 1 1 1 1 1 1
5 5 5 5 5 5 5 7. 5
(3.73) (3.73) (3.73) (3.73) (3.73) (3.73) (3.73) (5.39)
20 20 20 20 20 25 25 30
(14.91) (14.91) (14.91) (18.64) (18.64) (18.64) (18.64) (22.37)
6325 6325 6500 8700 8700 9100 9880 11200
8500 9350 10625 12325 13600 14875 16150 17850
N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A
6
1/1 1/1
15/10 15/10
N/A
6
28.5/29.3
23.5/23.5
3 3
10 10
N/A
21.5
21.5
21.5
23.5/26.5
23.5/26.5
23.5/26.5
6
18”
6000/
10625
2/1
10/15
N/A
N/A
N/A
22.0
22.0
22.0
14
SCXF-SVX01Q-EN
GGeenneerraall DDaattaa
Table 1. SCWF/SIWF Water-cooled self-contained, 20 to 42 tons (continued)
Unit Size 20 22 25 29 32 35 38 42
Capacity Steps - %
Notes:
1. Compressors are Trane 3-D™ scroll.
2. All units operate with R-410A. Units ships with full operating charge.
3. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
4. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
5. Optional low flow fan (unit model number digit 23 = 1) is available ONLY when High Capacity option is selected (unit model number digit 5 = V).
100/53/0 100/53/0 100/53/0
Table 2. SCWF/SIWF Water-cooled self-contained, 46-110 tons
Unit Size 46 52 58 65 72 80 90 100 110
Compressor
Data
Quantity
Nominal Ton/
Comp
Circuits 3 3 3 4 4 4 5 6 6
Evaporator Coil
Data
Rows 4 or 6 2 4 or 6 3 4 or 6 6 6 or 8 6 or 8 6 or 8
Sq. Ft.
FPF 144 144 144 144 144 144 144 144 144
Condenser Data
Min GPM w/o Econ
Min GPM w/ Econ
Maximum GPM 142 186 186 226 226 248 300 350 350
Evaporator Fan
Data
Quantity
Size (Dia.)
Minimum HP 7.5 7.5 7.5 10 10 10 15 15 15
Minimum kW
Maximum HP 30 40 40 50 50 50 60 60 60
Maximum kW
Min Design CFM
Max Design CFM
High Capacity
Option
Rows 6
Optional Low
Flow Fan
Size (Dia.)
Min./Max Design
CFM
2/1
10/15
38.57 49.09 49.09 49.09 49.09 49.09 56.81 56.81 56.81
64 84 84 102 102 112 140 168 168
64 84 84 102 102 112
1 1 1 1 1 1 1 1 1
25" 25" 25" 27.5" 27.5" 27.5" 27.5" 27.5" 27.5"
(5.59) (5.59) (5.59) (7.46) (7.46) (7.46) (11.19) (11.19) (11.19)
(22.37) (29.84) (29.84) (37.29) (37.29) (37.29) (44.74) (44.74) (44.74)
11960 14250 15080 16900 18700 20800 17500 17500 17500
19550 22100 24650 27625 29800 29800 35000 35000 35000
18"
7700/13600 N/A
3 3
15 15
N/A
N/A
8900/ 13600
6
18"
100/62/39/0100/59/39/0100/65/31/0100/65/30/
3/1 3/1
15/10 15/10
N/A
N/A
N/A
6
20"
10700/
16150
4 5
15 15
N/A N/A N/A
N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
8 8 8
0
2/4
10/15
100/71/43/
26/0
6
15
SCXF-SVX01Q-EN
15
GGeenneerraall DDaattaa
Table 2. SCWF/SIWF Water-cooled self-contained, 46-110 tons (continued)
Unit Size 46 52 58 65 72 80 90 100 110
Refrigerant Charge — lbs. R­410A (Standard
Capacity/High
Capacity)
Circuit A
Circuit B
Circuit C
Circuit D
Circuit E
Circuit F
Capacity Steps - %
Notes:
1. Compressors are Trane 3-D™ scroll.
2. All units operate with R-410A. Units ships with full operating charge.
3. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
4. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
24.5/28.5
24.5/28.5
24.5/28.5
N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
100/70/41/30/
0
21.0
21.0
21.0
100/65/
32/0
26.5/
31.5
26.5/
31.5
26.5/
31.5
100/65/
30/0
22.0 24.5 28.0 24.5 24.5 24.5
22.0 24.5 28.0 24.5 24.5 24.5
22.0 24.5 28.0 24.5 24.5 24.5
21.0 22.0 28.0 24.5 24.5 24.5
24.5 24.5 24.5
24.5 24.5
100/71/ 44/24/0
100/71/ 43/23/0
100/73/ 46/20/0
100/80/ 40/20/0
100/75/ 38/19/0
100/66/ 33/17/0
Table 3. SCRF/SIRF Air-cooled self-contained
Unit Size 25 29 30 35 40 50 60
Compressor Data
Quantity
Nominal Ton/Comp
Circuits 2 2 2 2 2 2 2
Evaporator Coil Data
Rows 4 4 3 4 4 4 6
Sq. Ft.
FPF 144 144 120 144 144 144 144
Evaporator Fan Data
Quantity
Size (Dia.)
Minimum HP 5 5 5 5 7.5 7.5 10
Minimum kW
Maximum HP 20 20 25 25 30 40 50
Maximum kW
Minimum Design CFM
Maximum Design CFM
Refrigerant Charge
Capacity Steps - %
1/1 1/1
15/10 15/10
29.98 29.98 31.35 31.35 38.57 49.09 49.09
1 1 1 1 1 1 1
18" 18" 20" 20" 25" 25" 27.5"
(3.73) (3.73) (3.73) (3.73) (5.59) (5.59) (7.46)
(18.64) (18.64) (18.64) (18.64) (22.37) (29.84) (37.29)
8700 8700 9100 9880 11960 15080 20800
12325 13600 14875 16150 19550 24650 29800
100/62/39/0 100/59/39/0 100/65/31/0 100/65/30/0
3 3
10 10
See Note 2 below
2/1
10/15
100/70/41/
30/0
15 15
100/65/30/0
3 4
100/73/46/
20/0
16
SCXF-SVX01Q-EN
GGeenneerraall DDaattaa
Table 3. SCRF/SIRF Air-cooled self-contained (continued)
Unit Size 25 29 30 35 40 50 60
CCRC/CIRC Unit Match
Notes:
1. Compressors are Trane 3-D™ scroll.
2. All units operate with R-410A. Units ship with a dry nitrogen holding charge. Field refrigerant system charge required. Refer to Table 4, p. 17 for
amounts required.
3. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
4. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
Table 4. SCRF/SIRF Air–cooled self–contained and CCRC/CIRC remote air-cooled condenser refrigerant data
29 29 35 35 40 50 60
SCRF/SIRF & CCRC/CIRCUnit
Size
No. of Refrigerant Circuits
Operating Charge - lbs. R-410A
Operating Charge - kg R-410A
Cond. Storage Cap. - lbs. R-410A
Cond. Storage Cap. - kg R-410A
Notes:
1. Refrigerant charges are listed as circuit 1 circuit 2 and provide only an estimate. Final charge requires sound field charging practice.
2. Operating charge is for entire system, which includes the air–cooled self–contained, remote air–cooled condenser, and 25 feet of interconnecting
refrigerant piping.
3. At conditions of 95° F (35° C), condenser storage capacity is 95% full.
4. To determine the correct amount of refrigerant needed for a particular application, reference the Trane Reciprocating Refrigeration Manual.
25/29 29/29 30/35 35/35 40/40 50/50 60/60
2 2 2 2 2 2 2
56.2/38.0 56.2/38.0 71/35.5 75/37.5 86.5/39.5 100/52
23.1/17 23.1/17 32.2/16.1 34/17 39.2/17.9 44.5/22.7 46/46
51/37 51/37 74/37 74/37 74/51 102/51 102/102
23.1/16.8 23.1/16.8 33.6/16.8 33.6/16.8 33.6/23.1 46.3/23.1 46.3/46.3
Table 5. SCWF/SIWF water volumes
Water Volume in U.S. Gallons / Liters
Unit Size
20 9.0 34.1 17.4 65.9 16.9 64.0
22 9.0 34.1 17.4 65.9 16.9 64.0
25 9.0 34.1 17.4 65.9 16.9 64.0
29 9.0 34.1 20.5 77.6 18.8 71.2
32 9.0 34.1 20.5 77.6 18.8 71.2
35 10.0 37.9 21.9 82.9 20.2 76.5
38 10.0 37.9 21.9 82.9 20.2 76.5
42 15.0 56.8 32.2 121.9 31.4 118.9
46 15.0 56.8 32.2 121.9 31.4 118.9
52 15.0 56.8 36.9 139.7 35.9 135.9
58 15.0 56.8 36.9 139.7 35.9 135.9
65 16.0 60.6 37.9 143.5 36.9 139.7
72 16.0 60.6 37.9 143.5 36.9 139.7
80 16.0 60.6 37.9 143.5 36.9 139.7
90 22.5 85.2 50.1 189.6
100 23.0 87.1 50.6 191.5
110 24.0 90.8 51.6 195.3
W/o Economizer
Gallons Liters Gallons Liters Gallons Liters
With Mech. Cleanable Econ With Chem. Cleanable Econ
N/A N/A
N/A N/A
N/A N/A
101.5/
101.5
SCXF-SVX01Q-EN
17
GGeenneerraall DDaattaa
Table 6. SCWF/SIWF Refrigerant circuits, number of compressors by circuit
Circuit
Unit Size 1 2 3 4 5 6
20/22/25 Ton
29/32 Ton
35/38 Ton
42/46 Ton
52/58 Ton
60/72 Ton
80 Ton 1- 15T 1- 15T 1- 15T 1- 15T
90 Ton 1- 15T 1- 15T 1- 15T 1- 15T 1- 15T
100 Ton 1-15T 1-15T 1-15T 1-15T 1-10T 1-10T
110 Ton 1- 15T 1- 15T 1- 15T 1- 15T 1- 15T 1- 15T
Note: This table depicts compressor location in unit, plan view from left corner.
1- 10T 1- 10T
1- 15T 1- 10T
1- 10T 1- 10T 1- 10T
1- 15T 1- 10T 1- 10T
1- 15T 1- 15T 1- 15T
1- 15T 1- 15T 1- 15T 1- 10T
Table 7. SCRF/SIRF Refrigerant circuits, number of compressors by circuit
Unit Size 1 2
25/29 Ton
30/35 Ton
40 Ton
50 Ton 2-15T 1-15T
60 Ton 2-15T 2-15T
Note: This table depicts compressor location in unit, plan view from left corner.
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A
N/A N/A
Circuit
1-15T 1-10T
2-10T 1-10T
1-10T, 1-15T
1-10T
Table 8. Filter data, water-cooled units models SCWF & SIWF
Unit Size 20- 38 tons 40-85 tons 90-110 tons
Number - Size (In.)
Number - Size (In.)
8 - 20 x 18 12 - 25 x 20 15 - 24 x 24
4 - 20 x 20 6 - 20 x 20 3 - 24 x 12
Units With Hot Water Or Steam
4 - 16 x 20 4 - 25 x 20
4 - 20 x 20 2 - 20 x 20
4 - 18 x 20 8 - 25 x 16
Table 9. Filter data, air-cooled units models SCRF & SIRF
Unit size 20- 35 tons 40-60 tons
Number - Size (in.)
Units With Hot Water Or Steam
18
8 - 20 x 18 12 - 25 x 20
4 - 20 x 20 6 - 20 x 20
n/a
4 - 20 x 16
SCXF-SVX01Q-EN
Table 9. Filter data, air-cooled units models SCRF & SIRF (continued)
Unit size 20- 35 tons 40-60 tons
4 - 16 x 20 4 - 25 x 20
Number - Size (in.)
4 - 20 x 20 2 - 20 x 20
4 - 18 x 20 8 - 25 x 16
N/A
4 - 20 x 16
Table 10. Self-contained heating coil
Unit Size SCWF 20 - 38 SCWF 42 - 80 SCRF 20 - 35 SCRF 40 - 60
Steam Coil
Coil Type
Rows 1 1 1 1
No./Size (inches) (2) 24 x 58 (2) 30 x 81 (2) 24 x 58) (2) 30 x 81
No./Size (mm) (2) 609.6 x 1473.2 (2) 762 x 2057.4 (2) 609.6 x 1473.2 (2) 762 x 2057.4
FPF 42 42 42 42
Hot Water Coil
Coil Type
Rows 1 or 2
No./Size (inches) (2) 24 x 58 (2) 30 x 81 (2) 24 x 58 (2) 30 x8 1
No./Size (mm) (2) 609.6 x 1473.2 (2) 762 x 2057.4 (2) 609.6 x 1473.2 (2) 762 x 2057.4
FPF 80 or 108 80 or 108 80 or 108 80 or 108
Notes:
1. Hot water and steam heating coils have Prima-Flo® fins without turbulators.
2. For coil capacities, use TOPSS™ (Trane Official Product Selection Program).
3. Full capacity coils consist of two coils stacked and piped in parallel.
NS NS NS NS
5W 5W 5W 5W
N/A N/A N/A
GGeenneerraall DDaattaa
Table 11. Waterside economizer coil physical data
Model Unit Size
SCXF
SCXF
SCXF
SCXF
SCXF 29 & 32
SCXF 29 & 32 Mechanical Cleanable 2 108 55 78.5
SCXF 29 & 32 Mechanical Cleanable 4 108 55 78.5
SCXF 29 & 32
SCXF 35 & 38
SCXF 35 & 38 Mechanical Cleanable 2 108 57.5 78.5
SCXF 35 & 38
SCXF 35 & 38 Mechanical Cleanable 4 108 57.5 78.5
SCXF 42 & 46
20, 22 & 25 Chemically Cleanable
20, 22 & 25
20, 22 & 25 Chemically Cleanable
20, 22 & 25
Type
Mechanical Cleanable 2 108 40 78.5
Mechanical Cleanable 4 108 40 78.5
Chemically Cleanable
Chemically Cleanable
Chemically Cleanable
Chemically Cleanable
Chemically Cleanable
Rows FPF
2 108 40 78.5
4 108 40 78.5
2 108 55 78.5
4 108 55 78.5
2 108 57.5 78.5
4 108 57.5 78.5
2 144 55 101
SCXF-SVX01Q-EN
Height
(in)
Length
(in)
19
GGeenneerraall DDaattaa
Table 11. Waterside economizer coil physical data (continued)
Model Unit Size
SCXF 42 & 46 Mechanical Cleanable 2 144 70 101
SCXF 42 & 46
SCXF 42 & 46 Mechanical Cleanable 4 144 70 101
SCXF
SCXF
SCXF
SCXF
SCXF
52, 58, 65, 72, 80, 85 Chemically Cleanable
52, 58, 65, 72, 80, 85
52, 58, 65, 72, 80, 85 Chemically Cleanable
52, 58, 65, 72, 80, 85
90, 100 & 110
Type
Chemically Cleanable
Mechanical Cleanable 2 144 70 101
Mechanical Cleanable 4 144 70 101
Mechanical Cleanable 4 144 70 119.3
Rows FPF
4 144 55 101
2 144 70 101
4 144 70 101
(in)
Height
Length
(in)
20
SCXF-SVX01Q-EN

Pre-Installation

Receiving

Receiving Checklist

Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage:
Inspect individual cartons before accepting. Check for rattles, bent carton corners, or other visible indications of shipping damage.
If a unit appears damaged, inspect it immediately before accepting the shipment. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery. Report concealed damage to the freight line within the allotted time after delivery. Check with the carrier for their allotted time to submit a claim.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing, cartons, and crate. Take photos of damaged material if possible.
Notify the carrier of the damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.
NNoottee:: Notify your Trane representative of the damage
and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.
Ship-Separate Accessories
Field-installed sensors ship separately inside main control panel of the unit. Extra filters, sheaves, and belts ship in the fan motor section of the unit. Condenser plugs, spring isolators, and Iso-pads ship stored in the bottom left side of the unit.

Contractor Installation Responsibilities

Complete the following checklist before beginning final unit installation:
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and sufficient to support the unit and accessory weights. Level or repair the floor before positioning the unit if necessary.
Allow minimum recommended clearances for routine maintenance and service. Allow space at
end of the unit for shaft removal and servicing. Refer to the unit submittals for dimensions. See also the “Service Clearances” section in the Dimensional Data chapter.
Allow three fan diameters above the unit for the discharge ductwork. Return air enters the rear of the unit and conditioned supply air discharges through the top.
Electrical connection knockouts are on the top, left side of the unit.
Allow adequate space for piping access and panel removal. Condenser water piping, refrigerant piping, and condensate drain connections are on the lower left end panel.
NNoottee:: Unit height and connection locations will
change if using vibration isolators. The unit height may increase up to 5-7/8” with spring type isolators.
Electrical supply power must meet specific balance and voltage requirements as described in chapter “Electrical Installation”.
Water-cooled units only: The installer is responsible for providing a condenser main, standby water pump, cooling tower, pressure gauges, strainers, and all components for waterside piping. See
“Water Piping,” p. 38 for general waterside
recommendations.
Air-cooled units only: The installer is responsible for providing and installing the remote air-cooled condenser and refrigerant piping.

Unit Inspection

To protect against loss due to damage incurred in transit, perform inspection immediately upon receipt of the unit.
Exterior Inspection
If the job site inspection reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the bill of lading before signing. Notify the appropriate sales representative.
IImmppoorrttaanntt:: Do not proceed with installation of a
damaged unit without sales representative’s approval.
Visually inspect the complete exterior for signs of shipping damages to unit or packing material.
Verify that the nameplate data matches the sales order and bill of lading.
Verify that the unit is properly equipped and there are no material shortages.
Verify that the power supply complies with the unit nameplate specifications.
SCXF-SVX01Q-EN
21
Shipping Cover
PPrree--IInnssttaallllaattiioonn
Inspection for Concealed Damage
Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored.
If concealed damage is discovered:
Notify the carrier’s terminal of the damage immediately by phone and by mail.
Concealed damage must be reported within 15 days.
Request an immediate, joint inspection of the damage with the carrier and consignee.
Stop unpacking the unit.
Do not remove damaged material from receiving location.
Take photos of the damage, if possible.
Figure 3. Typical unit shipping package
The owner must provide reasonable evidence that the damage did not occur after delivery.
Repair
Notify the appropriate sales representative before arranging unit installation or repair.
IImmppoorrttaanntt:: Do not repair unit until the damage has
been inspected by the carrier’s representative.

Unpacking

Commercial self-contained units ship assembled with protective coverings over the coil and discharge openings.Figure 3, p. 22 illustrates a typical shipping package.
22
SCXF-SVX01Q-EN
PPrree--IInnssttaallllaattiioonn

Unit Protective Covers

Remove shipping protection coverings from human interface panel (HI) at control panel, filter box (or air inlet opening), discharge air opening, and optional variable frequency drive (VFD).

Supply Fan Isolators

Remove the shipping channels and four fan mounting bolts from beneath the fan. Open both fan compartment doors to access the channels.
Figure 4. Fan Assembly Shipping Spacer Locations
NNootteess::
There are six fan mounting points for 40-110 ton units.
The 20 to 38 ton units use neoprene isolators, and 40 to 110 ton units use spring isolators.
SCXF-SVX01Q-EN
23

Dimensional Data

Figure 5. 20 to 38 ton self-contained
NNootteess::
24
1. All unit weights include refrigerant, water, controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
SCXF-SVX01Q-EN
Figure 6. 42 to 80 ton self-contained
DDiimmeennssiioonnaall DDaattaa
NNootteess::
1. All unit weights include refrigerant, water, controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate shipping weight.
SCXF-SVX01Q-EN
25
Ext. Height
Std. Height
Low Height
43.50"
27.75"
19.625"
Human
Interface
89.50"
Unit Control
Box
140.00"
VFD/
Interface
Plenum (low, standard,
and extended height shown)
72.00"
3.50"
133.00"
69.75"
3.50"
Filter Rack
*
*
*
*
*
*
Isolator Mounting Location (x6)
on bottom of unit
80.50”
86.25”
DDiimmeennssiioonnaall DDaattaa
Figure 7. 90 to 110 ton self-contained: front view
Figure 8. 90 to 110 ton self-contained: top view (isolator mounting locations shown)
26
SCXF-SVX01Q-EN
Figure 9. Detail A: electrical connections 20 to 110 tons
40 3/8” (20-38 Ton)
PLUGS
PLUGS
DDiimmeennssiioonnaall DDaattaa
Table 12. Discharge dimensions (in.)
Unit Model Fan Size A B C D
Standard Fan
SCWF 20-25 18” 31.85 23.5 23.11 20.4
SCWF 29-32
SCRF 25-29
SCWF 35-38
SCRF 30-35
SCWF 42-58
SCRF 40-50
SCWF 65-80
SCRF 60
SCWF 90-110 27.5” 50.7 33.5 28.8 34.5
SCWF 38 18” 44.8 23.25 36.78 19
SCWF 46 18” 44.8 23.25 36.78 19
SCWF 58 18” 44.8 23.25 36.78 20.4
SCWF 72 20” 43.4 26.2 34.77 24.6
18” 31.85 23.5 23.11 20.4
20” 30.5 26.2 21.25 25.75
25” 43.75 33 31.5 31.5
27.5” 43.5 33.5 28.63 34.5
Low Flow Fan Option
SCXF-SVX01Q-EN
27
Main Control Panel
Vacuum Trap Connection
Condensate Return
Vacuum Trap Connection Steam Inlet Connection
Condensate Return
Air Inlet
L
K
F
N
M
H
J
A
C
B
Notes:
1. All coils are factory mounted, piped, and wired.
2. All piping connections are 1-1/2” (38.1mm) female NPT fittings.
Main Control Panel
Air Inlet
Hot Water Outlet Connection
Hot Water Inlet Connection
H
F
G
A
B
E
D
C
DDiimmeennssiioonnaall DDaattaa

Steam and Hot Water Coils

Steam Coils

Figure 10. Steam Coil
Table 13. Piping locations for steam coils (in)(lbs)
Unit Size A B C D E F G H J K L M N
20-38 Ton
42-80 Ton
Note: Weight includes complete heating coil box.
60-3/8 82-7/8
72-7/8 105-1/4
18
18
22-3/8
13-1/4
18-1/2 3-7/8
22-1/8 6-3/8
5
5-375
4-3/8 1-1/4
4-3/8 1-1/4
Weight
460
600

Hot Water Coils

Figure 11. Hot Water Coil
Table 14. Hot water coil piping locations & weight (in)(lbs)
Unit Size A B C D E F G H
20-38 Ton
42-80 Ton
Note: Weight includes complete heating coil box.
28
60 3/8 82 7/8
72 7/8 105 1/4
18
18
20 5/8 8 1/8 22 3/8 3 5/8 8 1/4
24 1/2 10 3/4 13 1/4 3 5/8 8 1/4
Weight
460
600
SCXF-SVX01Q-EN
B
C
A
DDiimmeennssiioonnaall DDaattaa

Plenum

Figure 12. Six-inch filter rack
Table 15. Plenum dimensions (in)(lbs)
Unit Model A B C
64-7/8 24-5/8 95-7/8
64-7/8 32-3/8 95-7/8
64-7/8
80-3/8 21-1/8 119-7/8
80-3/8 28-5/8 119-7/8
80-3/8
80-1/2 19-5/8
80-1/2 27-3/4
80-1/2 43-1/2
45
45
20-38 Ton
42-80 Ton
90-110 Ton
low
std.
ext.
low
std.
ext.
low
std.
ext.

Filters

95-7/8
119-7/8
140 430
140 595
140 795
Weight
325
430
705
390
540
705
Table 16. Six-inch filter rack weight, lbs.
SCXF-SVX01Q-EN
Unit Size
20-38 212
42-80 257
Weight
29
DDiimmeennssiioonnaall DDaattaa

Airside Economizer

Figure 13. Airside economizer
Table 17. Airside economizer sizes and dimensions (in.)
Size A B C D E
SXWF 20 44 74
SXRF 25 44 74
SXWF 22 44 74
SXRF 29 44 74
SXWF 32 44 74
SXRF 30-35 44 74
SXWF 35-38 44 74
SXWF 42
SXRF 40
SXWF 46
SXRF 50
SXRF 60
SXRF 52-58
SXWF 65-80
Size
SXWF 20
SXRF 25
SXWF 22
SXRF 29
SXWF 32
SXRF 30-35
SXWF 35-38
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 83-5/8 63-1/2
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 94-1/8 63-1/2 28-1/8
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 94-1/8 63-1/2 28-1/8
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 96-5/8 63-1/2
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 96-5/8 63-1/2
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 96-5/8 63-1/2
57-3/8 86-1/2 13-1/4 104-3/8 8-7/8 96-5/8 63-1/2
H (1) H (2)
9-3/4 11-1/8 20-1/2 22-1/4
7-1/4 11-1/8 20-1/2 22-1/4
7-1/4 11-1/8 20-1/2 22-1/4
9-3/4 11-1/8 20-1/2 22-1/4 9-1/2 62-3/4
9-3/4 11-1/8 20-1/2 22-1/4 9-1/2 62-3/4
4-7/8 11-1/8 20-1/2 22-1/4 9-1/2 62-3/4
4-7/8 11-1/8 20-1/2 22-1/4 9-1/2 62-3/4
22-3/8 81-3/4 8-3/4 66-3/4 49-3/4 23-1/4 20-1/2
22-3/8 81-3/4 8-3/4 68-5/8 49-3/4 28-1/8 20-1/2
22-3/8 81-3/4 8-3/4 68-5/8 49-3/4 28-1/8 20-1/2
22-3/8 81-3/4 8-3/4 74-1/4 62-3/4 23-1/4 20-1/2
22-3/8 81-3/4 8-3/4 74-1/4 62-3/4 23-1/4 20-1/2
22-3/8 81-3/4 8-3/4 73-1/2 62-3/4
22-3/8 81-3/4 8-3/4 73-1/2 62-3/4
J K L M
16
16
16
F (1) F (2) G (1) G (2)
33
33
33 26
52
52
52
52
20-1/2
20-1/2
26
26
37-1/2
37-1/2
37-1/2
37-1/2
Weight
49-3/4
49-3/4
49-3/4
430
500
500
500
500
500
500
30
SCXF-SVX01Q-EN
Loading...
+ 90 hidden pages