Trane SAHL40, SAHL50, SAHL55, SAHL60, SAHL70 Installation, Operation And Maintenance Manual

...
IntelliPak™
Commercial Rooftop Air Conditioners with CV, VAV, or SZVAV Controls
“A” and later Design Sequence
SAHL
SEHL, SFHL, SLHL, SSHL, SXHL
SXHK, SEHK, SFHK, SLHK, SSHK
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
October 2013
*20, *25, *30, *40, *50, *55, *60, *70, *75
*20, *25, *30, *40, *50, *55, *60, *70, *75, *24, *29, *36, *48, *59, *73, *80, *89
*90, *11, *12, *13
SAFETY WARNING
RT-SVX36K-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that
warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
© 2013Trane All rights reserved RT-SVX36K-EN
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
:
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PersonalProtectiveEquipment (PPE) recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and
OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Risk of Roof Collapsing!
Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb and the unit. Refer to “Unit
Dimensions & Weight Information,” p. 26 for typical
unit and curb weights. Failure to ensure proper structural roof support could cause the roof to collapse, which could result in death or serious injury and property damage.
Warnings, Cautions and Notices
Unit Nameplate
One Mylar unit nameplate is located on the outside upper left corner of the control panel door. It includes the unit model number, serial number, electrical characteristics, weight, refrigerant charge, as well as to other pertinent unit data. A small metal nameplate with the Model Number, Serial Number, and Unit Weight is located just above the Mylar nameplate, and a third nameplate is located on the inside of the control panel door.
Compressor Nameplate
The Nameplate for the Scroll Compressor is located on the
compressor lower housing.
Max amps is listed on the nameplate and is the absolute highest amp load on the compressor at any operating condition (does not include locked rotor amps or inrush).
This value should never be exceeded.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.
Precautionary Measures
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes.Wearlong-sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact - Wash affected areas gently with soap and warm water after handling.
Revision Summary
RT-SVX36K-EN (04 Oct 2013)
Added general information on “VZH Variable Speed
Compressors,” p. 18 and “High Compressor Pressure Differential Protection,” p. 17
Updated Table 22, p. 59 (Compressor electrical service sizing data (20-130 ton)
Updated Table 78, p. 175(Supply and Exhaust/Return fanVFD programming parameters), with addition of 0­06 (TR150 only) to Operation / Display Menu and 1-23 to Load and Motor Menu.
Updated Supply Fan Performance Curve on Figure 66,
p. 109
Updated Table 47, p. 118 for 50-59 ton data.
Added information on “eFlex™ Compressor VFD
Programming Parameters,” p. 177
Overview of Manual
This booklet describes proper installation, start-up,
operation, and maintenance procedures for 20 through
130Ton rooftop air conditioners designed for Constant Volume (CV), Single Zone VAV (SZVAV), and Variable Air Volume (VAV) applications. By carefully reviewing the
information within this manual and following the
instructions, the risk of improper operation and/or
component damage will be minimized.
These units are equipped with electronic Unit Control
Modules (UCM) which provides operating functions that
are significantly different than conventional units. Refer to
the “Start-Up” and “Test Mode” procedures within this
Installation, Operation, & Maintenance manual and the
latest edition of the appropriate programming manual for
CV or VAV applications before attempting to operate or
service this equipment.
Note: The procedures discussed in this manual should
only be performed by qualified, experienced HVAC technicians.
Note: One copy of the appropriate service literature ships
inside the control panel of each unit.
It is important that periodic maintenance be performed to
help assure trouble free operation. Should equipment
failure occur, contact a qualified service organization with
qualified, experienced HVAC technicians to properly
diagnose and repair this equipment.
Unit Inspection
As soon as the unit arrives at the job site
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Verify that the power supply complies with the electric heater specifications on the unit nameplate.
Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
Check for material shortages. Refer to the Component Layout and Ship with Location illustration.
RT-SVX36K-EN 3
Warnings, Cautions and Notices
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing.
Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
WARNING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Remove the protective plastic coverings that shipped over the compressors.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
a. the unit is stored before it is installed; or,
b. the unit is set on the roof curb, and temporary heat
is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit's heater for temporary heat
without first completing the startup procedure detailed under “Starting the Unit”.
Trane will not assume any responsibility for equipment
damage resulting from condensate accumulation on the unit's electrical and/or mechanical components.
On all IntelliPak I units, aTrane factory REQUIRED startup (mandatory with Evaporative Condensing or optionally selected ON OTHER UNITS) provides "maximized unit reliability and overall unit performance," in addition to preserving the standard factory warranty.
Additional Requirements for Units Requiring
Disassembly
When a new fully assembled IntelliPak is shipped and
received from ourTrane manufacturing location, and, for any reason, it requires disassembly or partial disassembly-which could include but is not limited to the evaporator, condenser, control panel, compressor/motor, factory mounted starter or any other components originally attachedto the fully assembled unit-compliance with the following is required to preserve the factory warranty:
Trane, or an agent of Trane specifically authorized to perform start-up and warranty ofTrane® products, will perform or have direct on-site technical supervision of the disassembly and reassembly work.
The installing contractor must notifyTrane-or an agent ofTrane specifically authorized to perform start-up and warranty ofTrane® products-two weeks in advance of the scheduled disassembly work to coordinate the disassembly and reassembly work.
Start-up must be performed byTrane or an agent of
Trane specifically authorized to perform start-up and
warranty of Trane® products.
Trane, or an agent ofTrane specifically authorized to
perform startup and warranty of Trane® products, will provide qualified personnel and standard hand tools to perform the disassembly work at a location specified by the contractor.The contractor shall provide the rigging equipment such as chain falls, gantries, cranes, forklifts, etc. necessary for the disassembly and reassembly work and the required qualified personnel to operate the necessary rigging equipment.
Factory Warranty Information
Compliance with the following is required to preserve the factory warranty:
All Unit Installations
Startup MUST be performed by Trane, or an authorized agent ofTrane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification toTrane (or an agent ofTrane specifically authorized to perform startup).
4 RT-SVX36K-EN
Table of Contents
Warnings, Cautions and Notices .......... 2
Unit Nameplate ..................... 3
Compressor Nameplate ............... 3
Overview of Manual .................. 3
Unit Inspection ...................... 3
Storage ............................ 4
Factory Warranty Information .......... 4
Model Number Descriptions .............. 7
General Information .................... 11
Commonly Used Acronyms .......... 11
Unit Description .................... 11
Rooftop Module (RTM - 1U48 Standard on all
units) ............................. 11
Compressor Modules ................ 12
Human Interface Module ............. 12
Heat Module ....................... 12
Modulating Dehumidification Module MDM 12
Ventilation Override Module .......... 13
Variable Speed Module .............. 13
Interprocessor Communications Board . 13
LonTalk/BACnet Communication Interface
Module ........................... 13
Exhaust/Comparative Enthalpy Module . 13
Ventilation Control Module ........... 14
Generic Building Automation System Mod-
ule ............................... 14
Multipurpose Module ................ 15
Input Devices & System Functions ..... 15
Constant Volume (CV), Single Zone Variable Air Volume (SZVAV) & Variable Air Volume (VAV) Sensors and Controls
............ 15
Constant Volume (CV) Units ........... 19
Single Zone Variable Air Volume (SZVAV) Only
................................ 19
Variable Air Volume (VAV) Units ........ 20
Space Temperature Averaging ........ 22
Installation ............................. 26
Unit Clearances ...................... 26
Trane Roof Curb and Ductwork ........ 36
Pitch Pocket Location .................37
If a Trane Curb Accessory Kit is Not Used: 37
Unit Rigging & Placement .............38
General Unit Requirements ............40
Main Electrical Power Requirements ....40
Field Installed Control Wiring ..........40
Requirements for Electric Heat Units ....40
Requirements for Gas Heat (SFH_) ......40
Requirements for Hot Water Heat (SLH_) 40
Requirements for Steam Heat (SSH_) . . .41
O/A Pressure Sensor and Tubing Installation (All units with Statitrac or Return Fans) . .41
Requirements for Modulating Reheat Dehu-
midification (S_HL) ...................41
Condensate Drain Connections ........41
Units with Gas Furnace ...............42
Removing Supply and Exhaust/Return Fan
Shipping Channels (Motors >5Hp) ......42
Optional DDP Supply Fan Shipping Channel Removal and Isolator Spring Adjustment 42
O/A Sensor & Tubing Installation .......45
Evaporative Condenser Make-up Water and
Drain Line Installation ................45
Gas Heat Units (SFH_) ................48
Flue Assembly Installation ............51
Hot Water Heat Units (SLH_) ...........51
Steam Heat Units (SSH_) ..............52
...................................54
Disconnect Switch External Handle .....55
Electric Heat Units (SEH_) .............55
Main Unit Power Wiring ..............56
Power Wire Sizing and Protection Device
Equations ..........................62
Field Installed Control Wiring ..........63
Controls Using 24 VAC ...............64
Controls using DC Analog Input/Outputs .64
Constant Volume System Controls ......64
Variable Air Volume and Constant Volume
System Controls .....................64
Unit Replacement .......................77
RT-SVX36K-EN 5
Table of Contents
Precautionary Measures ............. 77
First Aid Measures .................. 77
Electrical Connection .................. 77
Requirements for Gas Heat ........... 78
Requirements for Hot Water Heat (SLH*) 78
Requirements for Steam Heat (SSH*) . . 78
Space Pressure Sensor and Tubing Installa-
tion (All units with Statitrac) .......... 78
Condensate Drain Connections ........ 78
Supply and Return Duct Connections . . . 79
Lifting procedures .................... 79
Unit Rigging & Placement ............ 79
Installation Checklist .................... 84
20-130 Ton, Air-Cooled and Evaporative Con-
densing ........................... 84
Unit Start Up ........................... 86
Cooling Sequence of Operation ....... 86
Gas Heating Sequence of Operation . . . 91
Modulating Gas Sequence of Operation—Full and Limited Modulating Gas Furnace . . 92
Electric Heat Sequence of Operation . . . 93
Wet Heat Sequence of Operation ...... 93
Voltage Supply and Voltage Imbalance . 95
Verifying Proper Fan Rotation ........ 101
Direct-Drive Supply Fan Speed Adjustment 101
System Airflow Measurements ....... 102
VAV Systems with DDP Supply Fan . . . 104
Exhaust Airflow Measurement (Optional with
all Units) ......................... 104
Traq Sensor Airflow Measurement (Optional with all units equipped with an economizer) 105
Return Plenum Pressure Control (Units
equipped with Return Fan) .......... 105
Economizer Damper Adjustment ..... 125
Compressor Start-Up (All Systems) . . . 127
Compressor Operational Sounds ..... 129
Evaporative Condenser Startup ...... 130
Pressure Curves ................... 131
Thermostatic Expansion Valves ...... 147
Charging by Subcooling .............148
Low Ambient Dampers ..............148
Gas Furnace Start-Up (Constant Volume &
Variable Air Volume Systems) ........150
Two Stage Gas Furnace ..............150
Full Modulating Gas Furnace .........152
Limited Modulating Gas Furnace ......153
Final Unit Checkout .................154
Startup Checklists ......................155
20-75 Ton — Air-Cooled .............155
24-89 Ton — Evaporative Condenser . . .157
90-130 Ton — Air Cooled .............161
Maintenance ...........................165
Fan Belt Adjustment ................171
Scroll Compressor Replacement ......172
Scroll Compressor Replacements .....173
Monthly Maintenance ...............178
Coil Cleaning ......................179
Fall Restraint .......................182
Final Process .......................182
Unit Wiring Diagram Numbers ...........184
Warranty ..............................187
Commercial Equipment Rated 20 Tons and
Larger and Related Accessories .......187
Factory Warranty Information .........187
Index ..................................188
6 RT-SVX36K-EN
Model Number Descriptions
S A H L * 5 0 4 0 A 6 8 A 6 B D 8 0 0 1 0 0 W 0 0 G 0 B 0 0 0 R 0 0 0 8 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
DIGIT 1 - UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 - UNIT FUNCTION
A = DX Cooling, No Heat E = DX Cooling, Electric Heat F = DX Cooling, Natural Gas Heat L = DX Cooling, Hot Water Heat S = DX Cooling, Steam Heat X = DX Cooling, No Heat, Extended Casing
DIGIT 3 - UNIT AIRFLOW
H = Single Zone
DIGIT 4 - DEVELOPMENT SEQUENCE
L = Sixth
DIGITS 5,6,7 - NOMINAL CAPACITY
*20 = 20 Tons Air-Cooled *25 = 25 Tons Air-Cooled *30 = 30 Tons Air-Cooled *40 = 40 Tons Air-Cooled *50 = 50 Tons Air-Cooled *55 = 55 Tons Air-Cooled *60 = 60 Tons Air-Cooled *70 = 70 Tons Air-Cooled *75 = 75 Tons Air-Cooled *24 = 24 Tons Evap Condenser *29 = 29 Tons Evap Condenser *36 = 36 Tons Evap Condenser *48 = 48 Tons Evap Condenser *59 = 59 Tons Evap Condenser *73 = 73 Tons Evap Condenser *80 = 80 Tons Evap Condenser *89 = 89 Tons Evap Condenser
DIGIT8-POWERSUPPLY (See Notes)
4 = 460/60/3 XL E = 200/60/3 XL 5 = 575/60/3 XL F = 230/60/3 XL
Note: SEHL units (units with electric
heat) utilizing 208V or 230V require dual power source.
DIGIT 9 - HEATING CAPACITY
Note: When the second digit calls for "F"
(Gas Heat), the following values apply: (please note G and M are available ONLY on 50 ton models and above.
G = Low Heat-Limited Modulation H = High Heat-2-Stage J = High Heat-Limited L = Low Heat-2-Stage M = Low Heat- Full Modulation
0 = No Heat p = High Heat-Full Modulation
Note: When the second digit calls for "E"
(electric heat), the following values apply:
D = 30 kW R = 130 kW H = 50 kW U = 150 kW L = 70 kW V = 170 kW N = 90 kW W = 190 kW Q = 110 kW
Note: When the second digit calls for ''L''
(Hot Water) or ''S''(Steam) Heat, one of the following valve size values must be in Digit 9:
High Heat Coil:
1 = .50" 2 = .75" 3 = 1" 4 = 1.25" 5 = 1.5" 6 = 2"
Low Heat Coil:
A = .50" B = .75" C = 1" D = 1.25" E = 1.5" F = 2"
DIGIT 10 - DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru
Z, or any digit 1 thru 9.
DIGIT 11 - EXHAUST/RETURN OPTION
0 = None 1 = Barometric 3 = 100% Exhaust 3 HP w/Statitrac 4 = 100% Exhaust 5 HP w/Statitrac 5 = 100% Exhaust 7.5 HP w/Statitrac 6 = 100% Exhaust 10 HP w/Statitrac 7 = 100% Exhaust 15 HP w/Statitrac 8 = 100% Exhaust 20 HP w/Statitrac B = 50% Exhaust 3 HP C = 50% Exhaust 5 HP D = 50% Exhaust 7.5 HP F = 100% Exhaust 3 HP w/o Statitrac
(CV Only)
G = 100% Exhaust 5 HP w/o Statitrac
(CV Only)
H = 100% Exhaust 7.5 HP w/o Statitrac
(CV Only)
J = 100% Exhaust 10 HP w/o Statitrac
(CV Only)
K = 100% Exhaust 15 HP w/o Statitrac
(CV Only)
L = 100% Exhaust 20 HP w/o Statitrac
(CV Only) 9 = 100% Return 3 HP w/Statitrac M = 100% Return 5 HP w/Statitrac N = 100% Return 7.5 HP w/Statitrac
P = 100% Return 10 HP w/Statitrac R = 100% Return 15 HP w/Statitrac
T = 100% Return 20 HP w/Statitrac
U = 100% Return 3 HP w/o Statitrac
(CV Only)
V = 100% Return 5 HP w/o Statitrac
(CV Only)
W = 100% Return 7.5 HP w/o Statitrac
(CV Only)
X = 100% Return 10 HP w/o Statitrac
(CV Only)
Y = 100% Return 15 HP w/o Statitrac
(CV Only)
Z = 100% Return 20 HP w/o Statitrac
(CV Only)
DIGIT 12 - EXHAUST/RETURN
AIR FAN DRIVE
(Exhaust/Return Fan) 0 = None 8 = 800 RPM 4 = 400 RPM 9 = 900 RPM 5 = 500 RPM A = 1000 RPM 6 = 600 RPM B = 1100 RPM 7 = 700 RPM (Return Fan only) C = 1200 RPM H = 1700 RPM D = 1300 RPM J = 1800 RPM E = 1400 RPM K = 1900 RPM F = 1500 RPM G = 1600 RPM
DIGIT 13 - FILTER (PRE DX/FINAL)
A=Throwaway B
Cleanable Wire Mesh
=
C
High-EfficiencyThrowaway
=
D
Bag With Prefilter
=
E
Cartridge with Prefilter
=
F
Throwaway Filter Rack (Filter Not
=
Included) Bag Filter Rack (Filter Not Included)
G
=
H
StandardThrowaway Filter/
=
Cartridge Final Filters High EfficiencyThrowaway Filter/
J
=
Cartridge Final Filters
K
Bag Filters with 2"Throwaway
=
Prefilters/Cartridge Final Filters
L
Cartridge Filters with 2"Throwaway
=
Prefilters /Cartridge Final Filters
= StandardThrowaway Filter
M
/Cartridge Final Filters with 2"Throwaway Prefilters
N
= High EfficiencyThrowaway Filters/
Cartridge Final Filters with 2"Throwaway Prefilters
P
= Bag Filters with Prefilters /Cartridge
Final Filters with 2"Throwaway Prefilters
Q
= Cartridge Filters with Prefilters/
Cartridge Final Filters with 2"Throwaway Prefilters
RT-SVX36K-EN 7
Model Number Descriptions
DIGIT 14 - SUPPLY AIR FAN HP
1 = 3 HP FC 2 = 5 HP FC 3 = 7.5 HP FC 4 = 10 HP FC 5 = 15 HP FC 6 = 20 HP FC 7 = 25 HP FC 8 = 30 HP FC 9 = 40 HP FC A = 50 HP FC B = 3 HP DDP 80W C = 3 HP DDP 120W D = 5 HP DDP 80W E = 5 HP DDP 120W F = 7.5 HP DDP 80W G = 7.5 HP DDP 120W H = 10 HP DDP 80W (60-89T = 2 x 5 HP) J = 10 HP DDP 120W (60-89T = 2 x 5 HP) K = 15 HP DDP 80W (60-89T = 2 x 7.5 HP) L = 15 HP DDP 120W (60-89T = 2 x 7.5 HP) M = 20 HP DDP 80W (60-89T = 2 x 10 HP) N = 20 HP DDP 120W (60-89T = 2 x 10 HP) P = 25 HP DDP 80W R = 25 HP DDP 120W T = 30 HP DDP 80W (60-89T = 2 x 15 HP) U = 30 HP DDP 120W (60-89T = 2 x 15 HP) V = 40 HP DDP 80W(60-89T = 2 x 20 HP) W = 40 HP DDP 120W (60-89T = 2 x 20 HP)
50 HP DDP 80W(70 & 75-89T = 2 x 25
X=
HP) 50 HP DDP 120W (70 & 75-89T = 2 x 25
Y=
HP)
Z = 30 HP DDP 100W
(a)50, 55T only
(a)
DIGIT 15 - SUPPLY AIR FAN RPM
4=400 RPM F = 1500 RPM 5=
500 RPM G = 1600 RPM
6 = 600 RPM H = 1700 RPM 7 = 700 RPM J = 1800 RPM 8 = 800 RPM K = 1900 RPM 9 = 900 RPM L = 2000 RPM A = 1000 RPM M = 2100 RPM B = 1100 RPM N = 2200 RPM C = 1200 RPM P = 2300 RPM D = 1300 RPM R = 2400 RPM E = 1400 RPM
DIGIT 16 - OUTSIDE AIR
A = No Fresh Air B = 0-25% Manual D = 0-100% Economizer E = 0-100% Economizer w/ TRAQ/DCV
Note: Must install CO2sensor(s) for DCV
to function properly
DIGIT 17 - SYSTEM CONTROL
1 = CV - Zone Temp Control 2 = CV - Discharge Temp Control 4 = CV - Zone Temp Control
Space Pressure Control w/ Exhaust/ Return VFD w/o Bypass
5 = CV - Zone Temp Control
Space Pressure Control w/ Exhaust/Return VFD and Bypass
6 = VAV Discharge Temp Control w/ VFD
w/o Bypass
7 = VAV Discharge Temp Control w/ VFD
and Bypass
8 = VAV Discharge Temp Control
Supply and Exhaust/Return Fan w/ VFD w/o Bypass
9 = VAV Discharge Temp Control
Supply and Exhaust/Return Fan with VFD and Bypass
A = VAV - Single Zone VAV - w/ VFD
w/o Bypass
B = VAV - Single Zone VAV - w/ VFD
and Bypass
C = VAV - Single Zone VAV - Supply and
Exhaust/Return Fan w/ VFD w/o Bypass
D = VAV - Single Zone VAV - Supply and
Exhaust/Return Fan w/ VFD w/ Bypass
DIGIT 18 - ZONE SENSOR
0 = None A = Dual Setpoint Manual or Auto
Changeover (BAYSENS108*)
B = Dual Setpoint Manual or Auto
Changeover w/ System Function Lights (BAYSENS110*)
C = Room Sensor w/ Override and
Cancel Buttons (BAYSENS073*)
D = Room Sensor w/ Temperature
Adjustment and Override and Cancel Buttons (BAYSENS074*)
L = Programmable Zone Sensor w/
System Function Lights for CV, SZVAV, and VAV (BAYSENS119*)
Note: *Asterisk indicates current model
number digit A, B, C, etc.These sensors can be ordered to ship with the unit.
DIGIT 19 - AMBIENT CONTROL
0=Standard 1=0° Fahrenheit
DIGIT 20 - AGENCY APPROVAL
0=None (cULus Gas Heater, see note) 1=cULus
Note: Includes cULus classified gas
heating section only when second digit of Model No. is a "F."
DIGITS 21 - 38 ­MISCELLANEOUS
21 A = Unit Disconnect Switch 22 B = Hot Gas Bypass
C=
Hot Gas Reheat w/out Hot Gas Bypass
D=
Hot Gas Reheat and Hot Gas
23 0 = Without Economizer
Z = Economizer Control w/ W = Economizer Control w/Dry Bulb
24 E = Low Leak Fresh Air Dampers 25 F = High Duct Temperature
26 G = High Capacity Unit
Bypass
C = Economizer Control w/
Comparative Enthalpy
Reference Enthalpy
Thermostat
H = High Efficiency Unit
V = eFlex Variable Speed Compressor
27 0 =
28 B = GBAS 0-10V
29 A =
30 M = Remote Human Interface 31 N = Ventilation Override Module 32 0 = None R = Extended Grease Lines
33 0 = Standard Panels
34 V = Inter-Processor 35 M =
7 = Trane LonTalk Communication 36 8 = Spring Isolators
37 6 = Factory-Powered 15A GFI
38 A = Supply Fan Piezometer
Tip: EXAMPLE
Air-Cooled Aluminum Condenser Coil
J=
Corrosion Protected Condenser
Coil A = Evap Condenser B = Evap Condenser w/ Sump Heater C=
Evap Condenser w/ Dolphin
WaterCare System D=
Evap Condenser w/ Sump Heater
and Dolphin WaterCare System E=
Evap Condenser w/ Conductivity
Controller F=
Evap Condenser w/ Conductivity
Controller and Sump Heater
K = GBAS 0-5V R = Rapid Restart
Motors w/ Internal Shaft
Grounding
1 = Differential Pressure Gauge 2=
Extended Grease Lines and
Differential Pressure Gauge
T = Access Doors U = IRU - w/ Std Panels W = IRU - w/ Access Doors Y = IRU w/SST - w/ Std Panels Z = IRU w/SST - w/ Access Doors
Communication Bridge
BACnet Communication Interface
(BCI) Module Y = Trane Communication Interface
(TCI) Module
Interface (LCI) Module
Convenience Outlet/Disconnect
Switch J = Temperature Sensor
Model numbers: SAHL*5040A68A6BD800100W00G0 B000R0 00800 describes a unit with the following characteristics:
DX Cooling Only unit w/ no extended casing, 50 ton nominal cooling capacity, 460/60/3 power supply,100 percent exhaust with Statitrac, 10 HP exhaust fan motor with drive selection No. 8 (80 0 RPM), throwaway filters, 20 HP supply fan motor with drive selection No. B (1100 RPM), 0-100% economizer w/ dry bulb control, supply and exhaust
VFD w/o bypass, no remote panel,
standard ambient control, cULus agency approval. High capacity unit, extended grease lines and spring isolators.
The service digit for each model
number contains 38 digits; all 38 digits must be referenced.
8 RT-SVX36K-EN
Model Number Descriptions
S X H K * 1 1 4 0 A H 8 C E C D 8 0 0 1 * * Z * * * * * * * * * * * * * * * 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
DIGIT 1 - UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 - UNIT FUNCTION
E = DX Cooling, Electric Heat F = DX Cooling, Natural Gas Heat L = DX Cooling, Hot Water Heat S = DX Cooling, Steam Heat X = DX Cooling, No Heat, Extended
Casing
DIGIT 3 - UNIT AIRFLOW
H = Single Zone
DIGIT 4 - DEVELOPMENT SEQUENCE
K = R-410A Development Sequence
DIGITS 5,6,7 - NOMINAL CAPACITY
*90 = 90 Tons Air-Cooled *11 = 105Tons Air-Cooled *12 = 115Tons Air-Cooled *13 = 130Tons Air-Cooled
DIGIT8-POWERSUPPLY (See Notes)
4 = 460/60/3 XL 5 = 575/60/3 XL
DIGIT 9 - HEATING CAPACITY
0 = No Heat H = High Heat - 2-Stage J = High Heat - Limited Modulation P = High Heat - Full Modulation
Note:When the second digit calls for “E”
(electric heat), the following values apply in the ninth digit:
W= 190kW
Note: When the second digit calls for ''L''
(Hot Water) or ''S''(Steam) Heat, one of the following valve size values must be in Digit 9:
High Heat Coil:3=1",4=1.25",5=1.5", 6 = 2", 7 = 2.5”. Low Heat Coil:C=1",D=1.25",E=1.5", F = 2", G = 2.5”.
DIGIT 10 - DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru
Z, or any digit 1 thru 9.
DIGIT 11 - EXHAUST OPTION
0 = None 7 = 100% Exhaust 15 HP w/Statitrac 8 = 100% Exhaust 20 HP w/Statitrac 9 = 100% Exhaust 25 HP w/Statitrac F = 50% Exhaust 15 HP H = 100% Exhaust 30 HP w/ Statitrac J = 100% Exhaust 40 HP w/ Statitrac K = 100% Exhaust 15 HP w/o Statitrac
(CV Only)
L = 100% Exhaust 20 HP w/o Statitrac
(CV Only)
M = 100% Exhaust 25 HP w/o Statitrac
(CV Only)
N = 100% Exhaust 30 HP w/o Statitrac
(CV Only)
P = 100% Exhaust 40 HP w/o Statitrac
(CV Only)
DIGIT 12 - EXHAUST AIR FAN DRIVE
(Exhaust Fan) 0 = None 5 = 500 RPM 6 = 600 RPM 7 = 700 RPM 8 = 800 RPM
DIGIT 13 - FILTER (PRE DX/ FINAL)
A = Throwaway C = High-EfficiencyThrowaway D = Bag With Prefilter E = Cartridge with Prefilter F = Throwaway Filter Rack (Filter Not
Included) G = Bag Filter Rack (Filter Not Included) H = StandardThrowaway Filter/
Cartridge Final Filters J = High EfficiencyThrowaway Filter/
Cartridge Final Filters K = Bag Filters with 2"Throwaway
Prefilters/Cartridge Final Filters L = Cartridge Filters with 2"Throwaway
Prefilters /Cartridge Final Filters M= StandardThrowaway Filter
/Cartridge Final Filters with
2"Throwaway Prefilters N = High EfficiencyThrowaway Filters/
Cartridge Final Filters with
2"Throwaway Prefilters P = Bag Filters with Prefilters /Cartridge
Final Filters with 2"Throwaway
Prefilters Q = Cartridge Filters with Prefilters/
Cartridge Final Filters with
2"Throwaway Prefilters
DIGIT 14 - SUPPLY AIR FAN HP
C = 30 HP (2-15 HP) D = 40 HP (2-20 HP) E = 50 HP (2-25 HP) F = 60 HP (2-30 HP) G = 80 HP (2-40 HP)
DIGIT 15 - SUPPLY AIR FAN DRIVE
A = 1000 RPM
B = 1100 RPM C = 1200 RPM D = 1300 RPM E = 1400 RPM F = 1500 RPM G = 1600 RPM
DIGIT 16 - OUTSIDE AIR
D = 0-100% Economizer (Std.) E = 0-100% Economizer w/ TRAQ w/ DCV
Note: Must install CO2sensor(s) for DCV
to function properly
DIGIT 17 - SYSTEM CONTROL
1 = CV - Zone Temperature Control 2 = CV - DischargeTemperature Control 4 = CV - Zone Temperature Control
Space Pressure Control w/ Exhaust VFD w/o Bypass
5 = CV - Zone Temperature Control
Space Pressure Control w/ Exhaust VFD and Bypass
6 = VAV DischargeTemperature Control
w/ VFD w/o Bypass
7 = VAV DischargeTemperature Control
w/ VFD and Bypass
8 = VAV DischargeTemperature Control
Supply and Exhaust Fan w/ VFD w/o Bypass
9 = VAV DischargeTemperature Control
Supply and Exhaust Fan w/ VFD and Bypass
A = VAV – Single Zone VAV – w/ VFD
w/o Bypass
B = VAV – Single Zone VAV – w/ VFD
w/ Bypass
C = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/o Bypass
D = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/ Bypass
RT-SVX36K-EN 9
Model Number Descriptions
DIGIT 18 - ZONE SENSOR
0 = None A = Dual Setpoint Manual or Auto
Changeover (BAYSENS108*)
B = Dual Setpoint Manual or Auto
Changeover w/ System Function Lights (BAYSENS110*)
C = Room Sensor w/ Override and
Cancel Buttons (BAYSENS073*)
D = Room Sensor w/Temperature
Adjustment and Override and Cancel Buttons (BAYSENS074*)
L = Programmable Zone Sensor w/
System Function Lights for both CV and VAV (BAYSENS119*)
Note: *Asterisk indicates current model
number digit A, B, C, etc.These sensors can be ordered to ship with the unit.
DIGIT 19 - AMBIENT CONTROL
0 = Standard
DIGIT 20 - AGENCY APPROVAL
0 = None (cULus Gas Heater, see note) 1 = cULus
Note: Includes cULus classified gas
heating section only when second digit of Model No. is a "F."
DIGITS 21 - 38 ­MISCELLANEOUS
21 A = Unit Disconnect Switch 22 B = Hot Gas Bypass 23 C = Economizer Control w/
23 Z = Economizer Control w/
23 W = Economizer Control w/Dry Bulb 24 E = Low Leak Outside Air Dampers 25 F = High Duct Temperature
26 G = High Capacity Evap. Coil
27 0 = Air-Cooled Aluminum
28 K = Generic B.A.S Module
29 A = Motors w/ Internal Shaft
30 M = Remote Human Interface 31 N = Ventilation Override Module
32 0 = None R = Extended Grease Lines
33 0 = Standard Panels
34 V = Inter-Processor
35 Y = Trane Communication Interface
37 6 = Factory-Powered 15A GFI
Comparative Enthalpy
Reference Enthalpy
Thermostat
(105Ton)
H = High Cap. Evap. Coil and High
Eff. Cond. Coil (90 Ton)
Condenser Coil
J = Corrosion-Protected
Condenser Coil
R = Rapid Restart
Grounding
1 = Differential Pressure Gauge 2=
Extended Grease Lines and Differential Pressure Gauge
T = Access Doors U = IRU - w/ Std Panels W = IRU - w/ Access Doors Y = IRU w/SST - w/ Std Panels
Communication Bridge
(TCI) Module
M = BACnet Communication
Interface (BCI) Module
7 = Trane LonTalk Communication
Interface (LCI) Module
Convenience Outlet
Tip: EXAMPLE
Model numbers: SXHK*1140AH8CECD8001**Z describes a unit with the following characteristics:
DX cooling with extended casing, no heat, 105 ton nominal cooling capacity, 460/60/3 power supply, 100 percent exhaust with Statitrac, 30 h.p. exhaust fan motor with drive selection No. 8 - (800 RPM), high-efficiency throwaway filters, 50 hp supply fan motor with 1200 RPM, economizer, w/ reference enthalpy control, Supply and Exhaust with VFD but no bypass, cULus agency approval.
The service digit for each model
number contains 36 digits; all 36 digits must be referenced.
10 RT-SVX36K-EN
General Information
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual.These acronyms are alphabetically listed and defined below.
AC = Air Cooled Condenser MDM = Modulating Dehumidification Module
BAS = Building automation systems MPM = Multipurpose module
BCI = BACnet Communication Interface module MWU = Morning warm-up
CFM = Cubic-feet-per-minute NSB = Night setback
CKT. = Circuit O/A = Outside air
CLV = Cooling valve (reheat only) psig = Pounds-per-square-inch, gauge pressure
CV = Constant volume PTFE = Polytetrafluoroethylene (Teflon®)
CW = Clockwise R/A = Return air
CCW = Counterclockwise RAH = Return air humidity
DDP = Direct-drive plenum RH = Right-hand
E/A = Exhaust air RHP = Reheat pumpout solenoid valve
EC = Evaporative Condenser RHV = Reheat valve
ECEM = Exhaust/comparative enthalpy module RPM = Revolutions-per-minute
F/A = Fresh air RT = Rooftop unit
FC = Forward-curved RTM = Rooftop module
GBAS = Generic building automation system S/A = Supply air
HGBP = Hot gas bypass SCM = Single circuit module
HGRH = Hot gas reheat SZ = Single-zone (unit airflow)
HI = Human Interface SZVAV = Single zone variable air volume
HVAC = Heating, ventilation and air conditioning TCI = Tracer communications module
HPC = High pressure cutout UCM = Unit control modules
I/O = Inputs/outputs VAV = Variable air volume
IOM = Installation/operation/ maintenance manual VCM = Ventilation control module
IPC = Interprocessor communications VFD = Variable frequency drive (inverter)
IPCB = Interprocessor communications bridge VOM = Ventilation override module
IRU = Intellipak replacement unit VSC = Variable speed compressor
LCI-I = LonTalk Communication Interface for IntelliPak VSD = eFlex™variable speed drive compressor
LH = Left-hand VSM = Variable speed module
MCHE = Microchannel Coil w.c. = Water column
LPC = Low pressure cutout WCI = Wireless Communication Interface
MCM = Multiple circuit module
Unit Description
EachTrane commercial, single-zone rooftop air conditioner ships fully assembled and charged with the proper refrigerant quantity from the factory.
An optional roof curb, specifically designed for the S_HL units is available fromTrane.The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Trane Commercial Rooftop Units are controlled by a
microelectronic control system that consists of a network of modules and are referred to as Unit Control Modules (UCM).The acronym UCM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions which provide the best possible comfort level for the customer.
RT-SVX36K-EN 11
They are mounted in the control panel and are factory
wired to their respective internal components.They receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Refer to the following discussion for an explanation of each module function.
Rooftop Module (RTM - 1U48 Standard on all units)
The Rooftop Module (RTM) responds to cooling, heating,
and ventilation requests by energizing the proper unit components based on information received from other unit modules, sensors, remote panels, and customer supplied binary inputs. It initiates supply fan, exhaust fan, exhaust damper, return fan, return damper, variable frequency drive output, and economizer operation based on that information.
General Information
Table 1. RTM Resistance Input vs. Setpoint Temperatures
RTM cooling or heating
setpoint input used
as the source for
a ZONE temp setpoint (°F)
40 40 1084 45 45 992 50 50 899 55 55 796 60 60 695 65 65 597 70 70 500 75 75 403
80 80 305 n/a 85 208 n/a 90 111
RTM cooling setpoint input
used as the source
for SUPPLY AIR temp
setpoint cooling (°F)
Table 2. RTM Resistance Value vs. System Operating Mode
Resistance applied to RTM MODE
input Terminals (Ohms)
Max. Tolerance 5%
2320 Auto Off 4870 Auto Cool
7680 Auto Auto 10770 On Off 13320 On Cool 16130 On Auto 19480 Auto Heat 27930 On Heat
Constant Volume/SZVAV Units
Fan Mode System Mode
Resistance (Ohms) Max.
Tolerance 5%
Compressor Modules
(SCM & MCM - 1U49 standard on all units)
The compressor modules, (Single Circuit & Multiple
Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser
Heat Module
(1U50 used on heating units)
The Heat module, upon receiving a request for Heating,
energizes the appropriate heating stages or strokes the
Modulating Heating valve as required. fans. It monitors the compressor operation through feedback information it receives from various protection devices.
Human Interface Module
(HI - 1U65 standard on all units)
The Human Interface module enables the operator to
adjust the operating parameters for the unit using it's 16 key keypad. The 2 line, 40 character LCD screen provides status information for the various unit functions as well as menus for the operator to set or modify the operating parameters.
12 RT-SVX36K-EN
Modulating Dehumidification Module
MDM
(Optional 1U107 - used with Dehumidification
Control)
The MDM supports specific control inputs and outputs for
Modulating Dehumidification control including
Modulating Reheat and Cooling valve control as well as
the Reheat Pumpout Relay output.The Modulating
Dehumidification control Algorithm provides control
requests to the MDM to accomplish proper
Dehumidification control.
General Information
Ventilation Override Module
(VOM - Optional 1U51)
Important: The ventilation override system should not
be used to signal the presence of smoke caused by a fire as it is not intended nor designed to do so.
The Ventilation Override module initiates specified
functions such as; space pressurization, exhaust, purge, purge with duct pressure control, and unit off when any one of the five (5) binary inputs to the module are activated.The compressors and condenser fans are disabled during the ventilation operation. If more than one ventilation sequence is activated, the one with the highest priority is initiated.
Variable Speed Module
(VSM - Optional 1U123)
The Variable Speed module used in eFlex variable speed
units provides a 0-10VDC output analog speed signal to control the compressor VFD. Table 3 lists VSM output signal (VDC) and corresponding compressor speed (RPM) at 0%, 50% and 100% Intellipak command speeds (Spd %):
Table 3. VSM output signal (VDC)
Variable speed unit
40T 0 1500 4.7 3632 9.5 5762 50T 0 1500 3.9 3271 7.9 5042 55T 0 1500 3.9 3271 7.9 5042 60T 0 1500 4.8 3660 9.6 5820 70T 0 1500 4.8 3660 9.6 5820
Note: voltages and speed +/- 1%
During Auto Run mode, the Intellipak command speed (Spd %) can be monitored at the HI.The 0-10VDC signal and compressor RPM is displayed on theTRV200 inverter keypad (1U128).
Figure 1. Display -TRV200 inverter keypad (1U128)
Spd 0% Spd 50% Spd 100%
VDC RPM VDC RPM VDC RPM
against Table 3. VSM output signal voltage is measured
between terminals 53 and 55 at the VFD (3U119) input.
Figure 2. VSM output signal
Interprocessor Communications Board
(IPCB - Optional 1U55 used with the Optional
Remote Human Interface)
The Interprocessor Communication Board expands
communications from the rooftop unit UCM network to a
Remote Human Interface Panel. DIP switch settings on the
IPCB module for this application should be; Switches 1 and
2“Off”, Switch 3 “On”.
LonTalk/BACnet Communication Interface
Module
(LCI/BCI - Optional 1U54/1U104 - used on
units with Trane ICS™ or 3rd party Building
Automation Systems)
The LonTalk or BACnet Communication Interface modules
expand communications from the unit UCM network to a
TraneTracer Summit or a 3rd party building automation
system and allow external setpoint and configuration
adjustment and monitoring of status and diagnostics.
Exhaust/Comparative Enthalpy Module
(ECEM - Optional 1U52 used on units with
Statitrac and/or comparative enthalpy
options)
The Exhaust/Comparative Enthalpy module receives
information from the return air humidity sensor, the
outside air humidity sensor,and the return air temperature
sensor to utilize the lowest possible humidity level when
considering economizer operation. In addition, it receives
space pressure information which is used to maintain the
space pressure to within the setpoint control band. Refer
to Figure 4, p. 14 for the Humidity vs. Current input values.
0-10VDC signal
TheVSM output signal can also be checked in ServiceTest
mode. Compressor relays should be commanded off as shown in Figure 2, and the Spd% command can be changed at the HI. Then check the VSM output signal
RT-SVX36K-EN 13
General Information
Figure 3. Humidity vs. Current (ECEM Return RH, RTM
Outdoor RH)
Figure 4. Humidity vs. Current (RTM Space Humidity)
Table 4. Outside air flow range with Traq Sensor
Unit (AC/EC) CFM
20 & 25, 24 & 29 Ton 0-14000
30/36 Ton 0-17000 40/48 Ton 0-22000
50/59, 55 Ton 0-28000
60-75, 73-89 Ton 0-33000
90-130 Ton 0-46000
The velocity pressure transducer/solenoid assembly is
illustrated below. Refer to the “Traq Sensor Sequence of
Operation” section for VCM operation.
Figure 5. Velocity pressure transducer/solenoid
assembly
Ventilation Control Module
Tube from Tee to low side of Transducer
Transducer
Assembly is located inside the lter compartment
Tube from Solenoid to high side of Transducer
Ventilation Control Module
(VCM - Optional 3U218 used with Traq Fresh
Air Measurement and/ or CO2 Sensor)
The Ventilation Control Module (VCM) is located in the
filter section of the unit and is linked to the unit's UCM network. Using a “velocity pressure” sensing ring located in the outside air section, allows the VCM to monitor and control the quantity of outside air entering the unit to a minimum airflow setpoint.
An optional temperature sensor can be connected to the
VCM which enables it to control a field installed outside air
preheater.
If the unit has a VCM, an optional CO connected to the unit to the unit for CO reset permits the unit to reduce the amount of outside air entering the unit from the Design OA (Design OA damper%) to the DCV OA (DCV Minimum damper%) based on the space or return CO
level.The following table lists
2
the possible airflow range per unit size.
sensor can be
2
reset control. CO
2
Tube from low side of Velocity Flow Ring
Tube from high side of Velocity Flow Ring
Tee
N.O.
N.C.
COM.
Solenoid
Generic Building Automation System
Module
(GBAS - Optional 1U51 used with non-Trane
building control systems; 0-5 or 0-10 VDC)
The Generic Building Automation System (GBAS) module
allows a non-Trane building control system to
communicate with the rooftop unit and accepts external
setpoints in form of analog inputs for cooling, heating,
2
supply air pressure, and a binary Input for demand limit.
Refer to the“Field Installed ControlWiring” section for the
input wiring to the GBAS module and the various desired
setpoints with the corresponding DC voltage inputs for
both VAV and CV applications.
14 RT-SVX36K-EN
General Information
Phase Monitor (1U3) Standard on 20-89 ton
Continuously monitors line voltage to protect against phase, loss, imbalance and reversal. If a fault is found with the supply voltage a LED on the phase monitor will indicate a fault and a unit External Auto Stop is activated through the controls. 75 to 130 ton units have a phase monitor on each compressor.
Multipurpose Module
MPM (Optional 1U105 used on units with Return Fan or with Evaporative Condenser)
The Multipurpose Module (MPM) receives information
from the Return Plenum Pressure sensor and provides for Return Fan control to maintain this pressure to the Active Return Plenum Pressure Setpoint and Deadband. The liquid line pressure sensor inputs for the refrigeration circuits are received through the MPM in support of head pressure control on Evaporative condenser units.
Input Devices & System Functions
The descriptions of the following basic Input Devices used
within the UCM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit's electrical schematic for the specific module connections.
Constant Volume (CV), Single
temperatures will be monitored during compressor
operation and compressor circuits will be shut down if this
difference exceeds a Human Interface selectable setpoint
value.
Leaving EvaporatorTemperature Sensor
(3RT14 and 3RT15)
An analog input device used to monitor the refrigerant
temperature inside the evaporator coil to prevent coil
freezing. It is attached to the suction line near the
evaporator coil and is connected to the MCM. It is factory
set for 30°F and has an adjustable range of 25°F to 35°F.The
compressors are staged “Off” as necessary to prevent
icing. After the last compressor stage has been turned
“Off”, the compressors will be allowed to restart once the
evaporator temperature rises 10°F above the “coil frost
cutout temperature” and the minimum three minute“Off”
time has elapsed.
Filter Switch (3S21 and 3S58)
This binary input device measures the pressure
differential across the unit filters. It is mounted in the filter
section and is connected to the RTM (1U48). A diagnostic
SERVICE signal is sent to the remote panel if the pressure
differential across the filters is at least 0.5" w.c.The
contacts will automatically open when the pressure
differential across the filters decrease to 0.4" w.c.The
switch differential can be field adjusted between 0.17" w.c.
to 5.0" w.c. ± 0.05" w.c.
Zone Variable Air Volume (SZVAV) & Variable Air Volume (VAV) Sensors and Controls
Supply Air Temperature Sensor (3RT9)
This analog input device monitors the supply air
temperature for; supply air temperature control (used with discharge temperature control), supply air temperature reset (used with discharge temperature control), supply air temperature low limiting (used with discharge temperature control), and supply air tempering. It is mounted in the supply air discharge section of the unit and is connected to the RTM (1U48).
Return Air Temperature Sensor (3RT6)
This analog input device is used with a return humidity
sensor when the comparative enthalpy option is ordered. It monitors the return air temperature and compares it to the outdoor temperature to establish which temperature is best suited to maintain the cooling requirements. It is mounted in the return air section and is connected to the ECEM (1U52).
Entering EvaporatorTemperature Sensor (3RT28 and 3RT29)
This analog input device is used with the Leaving
EvaporatorTemp sensor to provide Low Charge Protection of the refrigerant systems.The difference in these two
RT-SVX36K-EN 15
Supply and Exhaust Airflow Proving Switches
(3S68 and 3S69)
3S68 is a binary input device used to signal the RTM when
the supply fan is operating. It is located in the supply fan
section of the unit and is connected to the RTM (1U48).
During a request for fan operation, if the differential switch
is detected to be open for 40 consecutive seconds;
compressor operation is turned “Off”, heat operation is
turned “Off”, the request for supply fan operation is turned
“Off” and locked out, exhaust dampers (if equipped) are “closed”, economizer dampers (if equipped) are “closed”,
and a manual reset diagnostic is initiated.
3S69 is a binary input device used on all rooftop units
equipped with an exhaust fan. It is located in the exhaust/
return fan section of the unit and is connected to the RTM
(1U48). During a request for fan operation, if the
differential switch is detected to be open for 40
consecutive seconds, the economizer is closed to the
minimum position setpoint, the request for exhaust fan
operation is turned “Off” and locked out, and a manual
reset diagnostic is initiated.The fan failure lockout can be
reset; at the Human Interface located in the unit's control
panel, byTracer, or by cycling the control power to the
RTM (1S70 Off/On).
Lead-Lag
Is a standard mode of operation on 20 thru 130Ton units.
It alternates the starting between the first compressor of
General Information
each refrigeration circuit. On 40 - 89 Ton units only the compressor banks will switch, not the order the compressors within a bank, providing the first compressor in each circuit had been activated during the same request for cooling. Lead lag is not available with variable speed compressor.
Supply and Exhaust/Return Fan Circuit Breakers (with 1CB1 and 1CB2)
The supply fan and exhaust fan motors are protected by
circuit breakers 1CB1 and 1CB2 respecti vely for 208 -230 V applications.They will trip and interrupt the power supply to the motors if the current exceeds the breaker's “must trip” value. For 460 -575 V applications, fan motors will be protected with manual motor protectors.The rooftop module (RTM) will shut all system functions “Off” when an open fan proving switch is detected.
Manual Motor Protectors (380V through 575V Only)
Manual motor protectors will be used as branch circuit protection for compressors and supply fan motors.These devices are capable of providing both overload and short­circuit protection. Before operating, the manual motor protector must be switched with the rotary on/off switch to the “ON” position and the overload setpoint dial must be set to the appropriate rating of the motor.
Important: In order to avoid nuisance trips, the
overload setpoint dial must be adjusted to the following calculated value: Overload Setting = (Motor FLA) Overload Setting = (Compressor RLA) x 1.12
Return Plenum Pressure High Limit
The Return Plenum Pressure High Limit Setpoint has a
non-adjustable value of 3.5 iwc. When the return plenum pressure exceeds the Return Plenum Pressure High Limit for more than 1 second, a “Return Pressure shutdown” signal is sent, and an automatically resetting diagnostic is set. After the return fan is off, the Return Pressure Shutdown signal is cancelled.The unit will not be allowed to restart within 15 seconds of shutdown. Three consecutive occurrences of the Return Plenum Pressure exceeding the Return Plenum Pressure Limit will cause a manual reset diagnostic.The occurrence counter will be reset every time the unit goes through a reset, transitions from Stop to Auto, or transitions into and out of Occupied or Unoccupied control.
Low Pressure Control (LPC)
LPC is accomplished using a binary input device. LP cutouts are located on the suction lines near the scroll compressors.The LPC contacts are designed to close when the suction pressure exceeds 41± 4 psig. If the LP control is open when a compressor is requested to start, none of the compressors on that circuit will be allowed to operate.They are locked out and a manual reset diagnostic is initiated.
The LP cutouts are designed to open if the suction
pressure approaches 25± 4 psig. If the LP cutout opens
after a compressor has started, all compressors operating
on that circuit will be turned off immediately and will
remain off for a minimum of three minutes. If the LP cutout
trips four consecutive times during the first three minutes
of operation, the compressors on that circuit will be locked
out and a manual reset diagnostic is initiated.
Saturated CondenserTemperature Sensors
(2RT1 and 2RT2)
These analog input devices are mounted inside a
temperature well located on a condenser tube bend.They
monitor the saturated refrigerant temperature inside the
condenser coil and are connected to the SCM/MCM
(1U49). As the saturated refrigerant temperature varies
due to operating conditions, the condenser fans are cycled
“On” or “Off” as required to maintain acceptable
operating pressures. For evaporative condensers, this
value is determined by the MPM whichconvertsa pressure
to a temperature value that is sent to the MCM to be used
for head pressure control.
Head Pressure Control (HPC)
This is accomplished using one saturated refrigerant
temperature sensors per refrigeration circuit. During a
request for compressor operation, when the condensing
temperature rises above the “lower limit” of the control
band, the Compressor Module (SCM/MCM) starts
sequencing condenser fans “On”. If the operating fans can
not bring the condensing temperature to within the
control band, more fans are turned on.
As the saturated condensing temperature approaches the
lower limit of the control band, fans are sequenced “Off”.
The minimum “On/Off” time for condenser fan staging is
5.2 seconds. If the system is operating at a given fan stage
below 100% for 30 minutes and the saturated condensing
temperature is above the “efficiency check point” setting,
a fan stage will be added. If the saturated condensing
temperature falls below the “efficiency check point”
setting, the fan control will remain at the present operating
stage. If a fan stage cycles four times within a 10 minute
period, the control switches from controlling to the“lower
limit” to a temperature equal to the “lower limit” minus
the “temporary low limit suppression” setting. It will
utilize this new “low limit” temperature for one hour to
reduce condenser fan short cycling.
For Evaporative Condensing units, Head pressure is
monitored with pressure transducers attached to the
Saturated Condensing line and converted to a
temperature by the MPM.This temperature is used to
control the variable speed fan and control the sump pump.
When the temperature rises above the Upper Limit (120F)
the Sump Pump is energized. If the Condensing
Temperature drops below the Lower Limit (70F) the Sump
Pump is de-energized.
16 RT-SVX36K-EN
General Information
High Pressure Controls (HPC)
High Pressure controls are located on the discharge lines near the scroll compressors.They are designed to open when the discharge pressure approaches 650 ± 10 psig.
The controls reset automatically when the discharge
pressure decreases to approximately 550 ± 10 psig. However, the compressors on that circuit are locked out and a manual reset diagnostic is initiated after the fourth occurrence of a high pressure condition.
If the HPC opens after a compressor has started, all compressors on that circuit will be turned off immediately and will remain off for a minimum of 15 minutes. If the HPC trips four consecutive times during the first 3 minutes of operation, the compressors on that circuit will be locked out and a manual reset diagnostic is initiated.
Variable speed compressor circuits use a different HPC
switch with 24 VDC contacts input to the inverter. Otherwise, the variable speed HPC circuit is functionally the same as described above.
High Compressor Pressure Differential Protection
20-75T units provides High Compressor Pressure Differential protection for the equipment , also referred to as Low VI compressor protection.This protection is active on a per circuit basis and prevents scroll involute stresses from exceeding levels that could cause compressor damage.
Two levels of control are implemented to support the High
Compressor Pressure Differential protection: Limit and Diagnostic trips.
During a Limit trip, the controller will determine when the pressure differential has exceeded predetermined limits and will then take action by either limiting the compressor capacity or by unloading/reducing the compressor capacity on that circuit. Once the pressure differential returns to an acceptable level, the circuit will become unlimited if still needed for temperature control.
During a Diagnostic trip, the controller will determine when the pressure differential has exceeded acceptable levels for the equipment and will then de-energize the circuit completely. Once the pressure differential returns to an acceptable level, the circuit will be allowed to re­energize if still needed for temperature control. If four Diagnostic trips occur within the same request for compressor operation, the circuit will be locked out on a manual reset diagnostic.
If actively limiting or controlling compressor outputs “OFF” due to a High Compressor Pressure Differential event, the Limit/Diagnostic event will be found under Status/ Compressor Status Submenu at the Human Interface. During a diagnostic trip a diagnostic will be indicated at the Human Interface.
Outdoor Air Humidity Sensor (3U63)
This is an analog input device used on applications with
100% economizer. It monitors the outdoor humidity levels
for economizer operation. It is mounted in the outside air
intake section and is connected to the RTM (1U48).
Return Air Humidity Sensor (3U64)
This is an analog input device used on applications with
the comparative enthalpy option. It monitors the return air
humidity level and compares it to the outdoor humidity
level to establish which conditions are best suited to
maintain the cooling requirements. It is mounted in the
return air section and is connected to the ECEM (1U52).
Space/Duct Humidity Sensor (5U108)
Analog input device used on applications with modulating
dehumidification option and/or humidification field
installed option. It is used to monitor the humidity level in
the space and for comparison with the dehumidification
and humidification setpoints to maintain space humidity
requirements. It is field mounted in the space and
connected to the RTM (1TB16).
Low Ambient Option 0° Fahrenheit (2U84,
2U85)
Air cooled units ordered with Low Ambient 0° Fahrenheit
will control the low ambient dampers (2U84, 2U85) to the
programmable Low Ambient Control Point based on
saturated condenser temperature during compressor
operation.
Status/Annunciator Output
This is an internal function within the RTM (1U48) module
that provides;
a. diagnostic and mode status signals to the remote
panel (LEDs) and to the Human Interface.
b. control of the binary Alarm output on the RTM.
c. control of the binary outputs on the GBAS module
to inform the customer of the operational status and/or diagnostic conditions.
Low Ambient Compressor Lockout
Utilizes an analog input device. When the system is
configured for low ambient compressor lockout, the
compressors are not allowed to operate if the temperature
of the outside air falls below the lockout setpoint. When
the temperature rises 5°F above the lockout setpoint, the
compressors are allowed to operate.The setpoint for units
without the low ambient option is 50°F. For units with the
low ambient option, the setpoint is 0°F. The setpoints are
adjustable at the Human Interface inside the unit control
panel.
Space Pressure Transducer (3U62)
This is an analog input device that modulates the exhaust
damper or exhaustVFD to keep the space pressure within
the building to a customer designated control band. It is
RT-SVX36K-EN 17
General Information
mounted in the filter section just above the exhaust damper actuator and is connected to the ECEM (1U52). Field supplied pneumatic tubing must be connected between the space being controlled and the transducer assembly.
MorningWarm-Up - Zone Heat (CV and VAV)
When a system changes from an unoccupied to an
occupied mode, or switches from STOPPED to AUTO, or power is applied to a unit with the MWU option, the heater in the unit or external heat will be brought on if the space temperature is below the MWU setpoint.The heat will remain on until the temperature reaches the MWU setpoint. If the unit is VAV, then the VAV box/unocc relay will continue to stay in the unoccupied position and the
VFD output will stay at 100% during the MWU mode.When
the MWU setpoint is reached and the heat mode is terminated, then the VAV box/unocc relay will switch to the occupied mode and the VFD output will be controlled by the duct static pressure. During Full Capacity MWU the economizer damper is held closed for as long as it takes to reach setpoint. During Cycling Capacity MWU the economizer damper is allowed to go to minimum position after one hour of operation if setpoint has not been reached.
Compressor Motor Winding Thermostats
CSHD compressors (20-70 Ton) Air-Cooled and (24­80 Ton) Evaporative Condensers
The compressors contains an internal line break overload
whichstops the compressors under a number of operating conditions that cause excessi ve motor temperature.These include rapid cycling, loss of charge, abnormally high suction temperatures, excessive amperage, phase loss and low voltage
CSHN Compressors (75 - 130 Ton) Air-Cooled and (89 Ton) Evaporative Condensers
PTC sensors are embedded in the motor windings of each Scroll compressor. These sensors are wired to the protection module which protects the motor from over temperature that can occur under a number of abnormal operating conditions.These include rapid cycling, loss of charge, abnormally high suction temperatures, low voltage and excessive amperage.
During a request for compressor operation, if the Compressor Module (SCM) detects a problem outside of normal parameters, it turns any operating compressor(s) in that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
VZH Variable Speed Compressors
Over current and over torque protection for VZH compressors are provided by theTRV200 inverter. VZH over temperature protection is not required.
Freeze Avoidance
FreezeAvoidanceis a feature which helps prevent freezing
of hydronic heat coils and avoiding nuisance hydronic
heat freezestat trips.This is accomplished by opening
inactive hydronic heat valve(s) at low ambient
temperatures.
Typically, when the unit is in a mode where the supply fan
is off, the OA temperature is monitored. If it falls below 45
ºF (5 degrees above the freezestat), the hydronic heat
valve(s) are opened to the Standby Freeze Avoidance
Position. When the OA temperature rises above 47 ºF,
occupied mode is requested, or the supply fan is
requested ON the hydronic heat valve(s) release to normal
control.
When the supply fan is commanded on, the OA dampers
will remain closed for one minute to remove the heat from
the hydronic heating coil.This prevents freezestat trips
and falsely loading the supply air temperature causing
premature compressor operation.This function is
disabled if the Standby FreezeAvoidance Position is set to
0%.
Supply Air Temperature Low Limit
Uses the supply air temperature sensor input to modulate
the economizer damper to minimum position in the event
the supply air temperature falls below the occupied
heating setpoint temperature.
Freezestat (4S12)
This is a binary input device used on units with Hydronic
Heat. It is mounted in the heat section and connected to the
Heat Module (1U50). If the temperature of the air entering
the heating coil falls to 40°F, the normally open contacts on
the freezestat closes signalling the Heat Module (1U50)
and the Rooftop Module (RTM) to:
Drive the Hydronic Heat Actuator (4U15) to the full open position.
Turn the supply fan “Off”.
Closes the outside air damper;
Turns “On” the SERVICE light at the Remote Panel.
Initiates a “Freezestat” diagnostic to the Human Interface.
High Duct Temp Thermostats (Optional 3S16, 3S17)
These are binary input devices used with a Trane
Communication Interface Module (TCI).They provide
“high limit” shutdown of the unit and requires a manual
reset.They are factory set to open if the supply air temperature reaches 240°F, or the return air temperature reaches135°F. Once tripped, the thermostat can be reset by pressing the button located on the sensor once the air temperature has decreased approximately 25°F below the cutout point.
18 RT-SVX36K-EN
General Information
Compressor Circuit Breakers (1CB8, 1CB9, 1CB10, 1CB11)
The Scroll Compressors are protected by circuit breakers
for 208 - 230 volt units which interrupt the power supply to the compressors if the current exceeds the breakers“must trip” value. For 460 -575 volt units the Scroll compressors will be protected with Manual Motor protectors. During a request for compressor operation, if the Compressor Module detects a problem outside of it's normal parameters, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
Constant Volume (CV) Units
Zone Temperature - Cooling
Relies on input from a sensor located directly in the space, while a system is in the occupied “Cooling” mode. It modulates the economizer (if equipped) and/or stages the mechanical cooling “On and Off” as required to maintain the zone temperature to within the cooling setpoint deadband.
Zone Temperature - Heating
Relies on input from a sensor located directly in the space, while a system is in the occupied “Heating” mode or an unoccupied period, to stage the heat “on and off” or to modulate the heating valve (hydronic heat only) as required to maintain the zone temperature to within the heating setpoint deadband.The supply fan will be requested to operate any time there is a requested for heat. On gas heat units, the fan will continue to run for 60 seconds after the furnace is turned off.
Supply Air Tempering
On CV ZoneTemperature Control units, if the supply air temperature falls 10°F below the zone temperature setpoint up to half of the available heat capacity will be brought on until the supply air temperature reaches 10°F above zone temperature setpoint.
Single Zone Variable Air Volume (SZVAV) Only
The IntelliPak controls platform supports Single ZoneVAV
as an optional unit control type in order to meet ASHRAE
90.1.The basic control is a hybrid VAV/CV configured unit that provides discharge temperature control to a varying discharge air temperature target setpoint based on the space temperature and/or humidity conditions. Concurrently, the unit will control and optimize the supply fan speed to maintain the zone temperature to a zone temperature setpoint.
Supply Fan VFD Control
Single Zone VAV units are equipped with a VFD-controlled supply fan which is controlled via a 0-10VDC signal from
the Rooftop Module (RTM). With the RTM supply fan output energized and the RTMVFD output at 0VDC, the fan speed output is 37% from the VFD by default; and at 10VDC the fan speed output is 100%.The control scales the VDC output from the RTM linearly to control fan speed output between 37-100%.The VFD will modulate the supply fan motor speed, accelerating or decelerating as required to maintain the zone temperature to the zone temperature setpoint. When subjected to high ambient return conditions the VFD will reduce its output frequency to maintain operation. Bypass control is offered to provide full nominal airflow in the event of drive failure.
Ventilation Control
Units configured for Single Zone VAV control require special handling of the OA Damper Minimum Position control in order to compensate for the non-linearity of airflow associated with the variable supply fan speed and damper combinations. Units configured for TRAQ with or without DCV use the same sequence of operation as VAV or CV units.
Space Pressure Control
For SZVAV units configured with or without Space Pressure Control (StatiTrac), the Exhaust Enable Setpoint (based on the outside air damper position) is used when the Supply Fan is at 100%. A Target setpoint is internally calculated when the supply fan is at less than 100%. The exhaust fan is allowed to start when theTarget setpoint is reached. If the Exhaust Enable Setpoint is set to 0%, then the exhaust fan will be allowed to start whenever the
Active Minimum position is reached regardless of supply
fan speed.
Occupied Cooling Operation
For normal cooling operation, cooling capacity will be staged or modulated in order to meet the calculated discharge air target setpoint. If the current active cooling capacity is controlling the discharge air within the deadband, no additional cooling capacity change will be requested. As the Discharge Air Temperature rises above the deadband, the algorithm will request additional capacity as required (additional compressors or economizer).As the Discharge AirTemperature falls below the deadband, the algorithm will request a reduction in active capacity.
Default Economizer Operation
By default, the unit will be setup to optimize the minimum supply fan speed capability during Economizer Only operation. If the economizer is able to meet the demand alone, due to desirable ambient conditions, the supply fan speed will be allowed to increase above the minimum prior to utilizing mechanical cooling if discharge air setpoint falls below the discharge air Lower Limit (Cooling) setpoint.
RT-SVX36K-EN 19
General Information
Unoccupied Mode
In Unoccupied mode the unit will utilize setback setpoints, 0% Minimum OA Damper position, and Auto Fan Mode operation as on normal CV units.The Supply Fan speed, and cooling and modulating types of heat, will be controlled to the discharge air target setpoint as is done during occupied periods.The Supply fan speed during staged heat control will be forced to 100% as on normal CV units.
Occupied Heating Operation
If the unit has 2 Stage Gas or Electric Heat, the unit will drive the supply fan to maximum flow and stage heating to control to the Zone Heating Setpoint. If the unit has Modulating Gas or Hydronic heat, the supply fan VFD will modulate as needed. On an initial call for heating, the supply fan will drive to the minimum heating airflow. On an additional call for heating, the heat will control in order to meet the calculated discharge air target setpoint. As the load in the zone continues to request heat operation, the supply fan will ramp-up while the control maintains the heating discharge air temperature. If the unit has Modulating Gas or Hydronic heat, heating can be configured for either the energy saving SZVAV Heating solution as described above, or with the supply fan required to ramp to 100% during heating.
Compressor (DX) Cooling
Compressor control and protection schemes will function identical to that of a traditional unit. Normal compressor proving and disable input monitoring will remain in effect as well as normal 3-minute minimum on, off, and inter­stage timers. Also, all existing head pressure control schemes will be in effect.
Cooling Sequence
If the control determines that there is a need for active cooling capacity in order to meet the calculated discharge air target setpoint, the unit will begin to stage or modulate compressors accordingly. Once the discharge air target setpoint calculation has reached the Minimum Setpoint and compressors are being utilized to meet the demand, the control will begin to ramp the supply fan speed up toward 100% to meet any additional cooling demand.
As the cooling load in the zone decreases the zone cooling algorithm will reduce the speed of the fan down to minimum per compressor stage and control the compressors accordingly. As the compressors begin to stage or modulate back, the supply fan speed will fall back to the Cooling Stage’s associated minimum fan speed, but not below. As the load in the zone continues to drop, cooling capacity will be reduced in order to maintain the discharge air within the ± ½ dischargeair target deadband.
Variable Air Volume (VAV) Units
Occupied Heating - Supply Air Temperature
When a DischargeTemperature Control unit is equipped
with “Modulating Heat”, and the system is in an occupied mode, and the field supplied changeover relay contacts (5K87) have closed, the supply air temperature will be controlled to the customer specified supply air heating setpoint. It will remain in the heating status until the changeover relay contacts are opened.
Occupied Cooling - Supply Air Temperature
When a DischargeTemperature Control unit is in the
occupied mode, the supply air temperature will be controlled to the customers specified supply air cooling setpoint by modulating the economizer and/or staging the mechanical cooling “On and Off” as required.The changeover relay contacts must be open on units with
“Modulating Heat” for the cooling to operate.
DaytimeWarm-up (VAV Only)
On DischargeTemperature Control units equipped with heat, if the zone temperature falls below the daytime warm-up initiate temperature during the occupied mode, the system will switch to full airflow. During this mode, the
VAV box/unocc relay, RTM K3, will be energized (this is to
signal the VAV boxes to go to 100%). After the VAV box max stroke time has elapsed (factory set at 6 minutes), the
VFD output will be set to 100%.The airflow will be at 100%
and the heat will be turned on to control to the occupied heating setpoint. When the zone temperature reaches the daytime warm-up termination setpoint, the heat will be turned off, the K3 relay will be de-energized, releasing the
VAV boxes, the VFD output will go back to duct static
pressure control and the unit will return to discharge air control. If the occ zone heating setpoint is less than the DWU terminate setpoint, the heat will turn off when the occ zone heat setpoint is reached, but it will stay in DWU mode and cycle the heat to maintain setpoint.
Unoccupied Heating - Zone Temperature
When a DischargeTemperature Control unit is equipped
with gas, electric, or hydronic heat and is in the unoccupied mode, the zone temperature will be controlled to the default or customer provided setpoint. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in the unoccupied position and the VFD output will be at 100%.This means that if there is a call for heat (or cool) and the supply fan comes on, it will be at full airflow and the VAV boxes in the space will need to be 100% open as signaled by the VAV box/unocc relay.
Unoccupied Cooling - Zone Temperature
When the unit is in the unoccupied mode, the zone
temperature will be controlled to the default or customer provided unoccupied cooling setpoint. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in the unoccupied position and the VFD will be at
20 RT-SVX36K-EN
General Information
100%. On units with a VSPD Compressor, during Unoccupied Cooling operation the VSPD Compressor will be controlled at its 100% capacity as applied to the unit.
TheVSPD Compressor will be staged On/Off as a standard
staged compressor.
Supply Air Tempering
On DischargeTemperature Control units equipped with
“Modulating Heat”, if the supply air temperature falls 10°F
below the supply air temperature setpoint, the hydronic or modulating gas heat valve will modulate to maintain the supply air temperature to within the low end of the setpoint deadband.
Figure 6. Transducer voltage output vs. pressure input (supply, return, space pressure)
-0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input
4.50
4.00
3.50
3.00
2.50
Volts
2.00
1.50
1.00
0.50
0.00
5
5
5
5
5
5
5
5
5
250.2
75
-0.
-0.
7
2
7
2
7
2
0.
1.
1.
2.
2.
7
3.
3.
Pressure (inches w.c.)
5
2
7
4.
2
4.
5.
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer
when a unit is equipped with a Variable Frequency Drive.
The unit controls will raise or lower the supply fan speed
to maintain the supply duct static pressure to within the static pressure setpoint deadband. Figure 6 below shows the pressure transducer output voltage relationship to input pressure.The unit is comparing supply duct pressure to ambient (outside) pressure.The pressure transducer input is factory piped to measure the pressure in the discharge section of the unit. Refer to Figure 29 to see how the transducer tubing is connected.
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer
when a VAV unit is equipped with a Variable Frequency Drive.This input allows the unit to control the supply fan speed in order to maintain the supply duct static pressure to within the static pressure setpoint deadband.
5
5
5
5
5
5
5
7
2
7
2
5.
6.
6.
7
7.
7.
5
2
7
8.
8.
dischargeopening. 20-55 ton sizes are single fan, 60-75 ton sizes (shown) have two fan assemblies.
Figure 7. DDP supply fan
Direct Drive Plenum (DDP) Supply Fan Option
DDP supply fans are positioned down stream of the fan board. DDP option includes a grate welded in the unit
RT-SVX36K-EN 21
General Information
Figure 8. Unit component layout and "ship with" locations
Optional Heat or final filters
Space Temperature Averaging
Space temperature averaging for Constant Volume applications is accomplished by wiring a number of remote sensors in a series/parallel circuit.
The fewest number of sensors required to accomplish
space temperature averaging is four.The Space
Temperature Averaging with Multiple Sensors figure
illustrates a single sensor circuit (Single Zone), four sensors wired in a series/parallel circuit (Four Zone), nine sensors wired in a series/parallel circuit (Nine Zone). Any number squared, is the number of remote sensors required.
22 RT-SVX36K-EN
Wiring termination will depend on the type of remote
panel or control configuration for the system. Refer to the wiring diagrams that shipped with the unit.
General Information
Figure 9. Space temperature averaging
Space Temperature Averaging with Multiple Sensors Unit Control Modules (UCM)
Unit control modules are microelectronic circuit boards designed to perform specific unit functions.These modules through Proportional/Integral control algorithms provide the best possible comfort level for the customer.
They are mounted in the control panel and are factory
wired to their respective internal components.They receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Figure 9 below illustrates the typical location of each “1U” designated module.
Figure 10. Control module locations for 20-36 ton units
RT-SVX36K-EN 23
General Information
Figure 11. Control module locations for 40 - 89 ton units
eFlex Variable Speed Compressor Staging
Note: The eFlex variable speed compressor can be
manually controlled only in service test mode through the Intellipak controller human interface.
TheTRV200 inverter keypad has been
programmed purposely to provide stop, reset, and diagnostics functions only.This is to prevent bypass of compressor protection functions provided by the Intellipak control logic.
Figure 12 generally describes how the Intellipak controller
sequences the eFlex variable speed compressor as building load increases. It is assumed that the unit is equipped with an economizer.
At low building loads, the economizer will often meet the building load and compressor cooling will not be required.
Then as the building load increases and the economizer no
longer can maintain setpoint, the Intellipak controller sends a signal to the TRV200 inverter to start the variable speed compressor (1A).TheTRV200 inverter ramps the compressor up to 50Hz for 10 seconds to insure compressor startup lubrication. Control is released back to the Intellipak controller and the compressor runs at minimum speed command (0 VDC from VSM board).
Until the building load exceeds the variable speed compressor capacity at minimum speed, the Intellipak compressor will cycle the variable speed compressor to meet setpoint (4 minute minimum on/off time). However,
since variable speed unit minimum capacity is about 15%, this transition cycling will be less than a typical fixed speed compressor unit which may have 25% minimum capacity.
As the building load increases and eventually equals the
variable speed compressor capacity at minimum speed, the compressor will run continuously and no longer cycle.
Then as the building load increases, the Intellipak
controller will increase compressor speed to meet the setpoint.When the variable speed compressor eventually reaches maximum speed and more capacity is required, a fixed speed compressor is started while the variable speed compressor speed is simultaneously ramped back down to minimum. Note that capacity overlap is provided between each stage of operation to provide continuous capacity modulation and minimize compressor cycling between stages.
24 RT-SVX36K-EN
Figure 12. eFlex variable speed compressor, IntelliPak controller sequences
General Information
RT-SVX36K-EN 25
Installation
Unit Inspection
As soon as the unit arrives at the job site
[ ] Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
[ ] Verify that the power supply complies with the unit nameplate specifications.
[ ] Verify that the power supply complies with the electric heater specifications on the unit nameplate.
[ ] Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
[ ] Check for material shortages. Refer to the Component Layout and Ship with location illustration.
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately.Specify the type and extent of the damage on the “bill of lading” before signing.
[ ] Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
WARNING
No Step Surface!
FOR ACCESS TO COMPONENTS,THE BASE SHEET METAL SURFACE MUST BE REINFORCED. DDP SUPPLY FANS REQUIRE BRIDGING OVERTHE DISCHARGE OPENING.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating. Failure to comply could result in death or severe personal injury from falling.
[ ] If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Table 5. Unit Dimensions & Weight Information
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
1. the unit is stored before it is installed; or,
2. the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit's heater for temporary heat
without first completing the startup procedure detailed under “Starting the Unit”.
Trane will not assume any responsibility for equipment
damage resulting from condensate accumulation on the unit's electrical and/or mechanical components.
Unit Clearances
Figure 13 illustrates the minimum operating and service
clearances for either a single or multiple unit installation.
These clearances are the minimum distances necessary to
assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.
Description Reference
Unit dimensions, 20-75 Ton (SAHL)
Unit dimensions, 90-130 Ton Figure 17, p. 33
Typical unit and operation weights Table 13, p. 35
Center-of-Gravity illustration and related dimensional data Figure 18, p. 34
Unit dimensions, 20-89 Ton
(SEH_, SFH_, SLH_, SSH_, and SXH_)
Typical unit and operation weights
Center-of-Gravity illustration and related dimensional data Figure 18, p. 34
(a)Weights shown represent approximate operating weights. Actual weights are stamped on the unit nameplate.
26 RT-SVX36K-EN
Air-Cooled Condenser
Evaporative Condenser
(a)
Figure 14, p. 28, Table 6, p. 28, Table 7,
and Table 8, p. 29,
Figure 15, p. 29, Table 9, p. 30,
Table 10, p. 30, and Table 11, p. 30
Table 14, p. 36
Figure 13. Minimum operation and service clearances for single and multiple unit installation
Single Unit Installation
Legend
Return Air Opening
=
A
Outside Air Intake
=
B
Supply Air Opening
=
C
Condenser Section
=
D
Optional 2’10-3/4” Exhaust/Return Access Door (180° swing)
=
E
Hinged 2’10-3/4” Filter Access Door (180° swing)
=
F
Hinged 2’10-3/4” optional Heater or Final Filter Access Door (180° swing)
=
G
Hinged 2’10-3/4” Supply Fan Access Door (180° swing) (90-130 ton)
=
H
Hinged 2’4-1/2” Control Panel Door (180° swing) (90-130 ton)
=
J
Hinged 2’10-3/4” VFD Access Door (180° swing)
=
K
Hinged 2’10-3/4” Evap Condenser Access Door (180° swing)
=
L
Hinged 2’8” Control Panel Door (180° swing) (20-36 ton)
=
M
Hinged 3’6” Control Panel Door (180° swing) (40-89 ton)
Installation
L
L
M
RT-SVX36K-EN 27
Installation
Figure 14. SAHL cooling-only units (20 - 75) Use Table 6, Table 7 and Table 8
1” CONDENSATE DRAIN CONNECTION (Both Sides)
Table 6. SAHL cooling-only units (20 - 75)
Dimensions for SAHL
Unit Size
20 & 25 Ton 21’-9 3/4” 6’-9” 7'-6 1/2" 7’-3 1/4” 3'-9 5/16" 12'-6” 1" 7’ 1'-3 1/2”
30 Ton 21’-9 3/4” 6’-9” 7'-6 1/2" 7’-3 1/4” 4'-9 5/16" 12'-6” 1" 7’ 1'-3 1/2” 40 Ton 29’-8” 6’-9” 7'-6 1/2" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8’ 2'-5” 50 Ton 29’-8” 6’-9” 7'-6 1/2" 7’-3 1/4” 6'-9 5/16" 15'-11 1/8" 1" 8’ 2'-5” 60 Ton 29’-8” 6’-9” 9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8’ 2'-5”
70 & 75 Ton 29’-8” 6’-9” 9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8’ 2'-5”
A B C D E F G H J
28 RT-SVX36K-EN
Installation
Table 7. SAHL cooling-only units (20 - 75)
Dimensions for SAHL
E F G
Unit Size
20 - 30 Ton 14'-0 1/4" 2'-2 1/2" 11 3/4" 5'-7" 3'-4 3/8" 2'-9 15/16” 5 13/16" 28 5/8” 6'-6 15/16" 3' 40 - 50 Ton 16'-1 13/16” 2'-5" 11 3/4" 5'-7" 3'-4 3/8" 3' - 1 1/2” 5 13/16" 32 15/16” 7'-8 3/16" 3'-4”
60 Ton 16'-1 13/16” 2'-5" 1'-4 9/16" 6'-10 7/8" 4'-5 3/8" 4' - 2 1/2” 5 13/16" 26 7/16” 7'-8 3/16" 4'-5”
70 - 75 Ton 16'-1 13/16” 2'-5" 1'-4 9/16" 6'-10 7/8" 4'-5 3/8" 4' - 2 1/2” 5 13/16" 26 7/16” 7'-8 3/16" 4'-5”
A B C D
w/exhaust
fan
w/return
fan
w/
exhaust
fan
Table 8. SAHL cooling-only units (20 - 75)
Dimensions
Unit Size
20, 25, 30 & 50 Ton 8 7/32" 6 31/32" 15 21/32" 13 21/32" 9 17/32" 8 1/2" 18 1/16" 19 9/16" 40, 60, 70 & 75 Ton 8 3/4" 7 3/4" 17 7/8" 15 7/8" 9 29/32" 10 1/16" 20 13/32" 22 5/32"
F G H J K L M N
Figure 15. SEHL, SFHL, SLHL, SSHL, SXHL units (20 - 89 ton) use Table 9, Table 10 and Table 11.
w/
return
fan
w/exhaust
fan
w/return
fan
1” NPT CONDENSATE DRAIN CONNECTION (Both Sides)
DRAIN HOLE
RT-SVX36K-EN 29
Installation
Table 9. SEHL, SFHL, SLHL, SSHL, SXHL units (20 - 89 ton)
Air-Cooled Unit Dimensions
Unit Size
20 & 25 Ton 24'-1 3/8" 6’-9” 7'-6 1/2" 7’-3 1/4” 3'-9 5/16" 13'-3" 1" 7' 1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
30 Ton 24'-1 3/8" 6’-9” 7'-6 1/2" 7’-3 1/4” 4'-9 5/16" 13'-3" 1" 7' 1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9" 40 Ton 32'-10 1/2” 6’-9” 7'-6 1/2" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8' 2'-5" 19'-7"
50 Ton 32'-10 1/2" 6’-9” 7'-6 1/2" 7’-3 1/4” 6'-9 5/16" 15'-11 1/8" 1" 8' 2'-5" 19'-7"
60 Ton 32'-10 1/2” 6’-9” 9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8' 2'-5" 19'-7"
70 & 75 Ton 32'-10 1/2” 6’-9” 9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8' 2'-5” 19'-7"
Table 10. SEHL, SFHL, SLHL, SSHL, SXHL units (20 - 89 ton)
Unit Size
24 & 39 Ton 26’5 1/2” 6’-9” 7’-6 1/2” 8’-4 3/4” 3’-9 5/16” 13’-3” 1" 7” 1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
36 Ton 26’5 1/2” 6’-9” 7’-6 1/2” 8’-4 3/4” 4’-9 5/16” 13’-3” 1" 7” 1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9" 48 Ton 32’-10 1/2” 6’-9” 7’-6 1/2” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1" 8” 2'-5" 19'-7"
59 Ton 32’-10 1/2” 6’-9” 7’-6 1/2” 8’-4 3/4” 6’-9 5/16” 15’-11 1/8” 1" 8” 2'-5" 19'-7"
73 Ton 32’-10 1/2” 6’-9” 9’-8” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1" 8” 2'-5" 19'-7"
80 & 89 Ton 32’-10 1/2” 6’-9” 9’-8” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1" 8” 2'-5” 19'-7"
Note: 19'-6” for SFHL “High Heat” units or 20'-3” for SFHL “Low Heat” units.
A B C D E F G H J K L M N O
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
Evaporative Condensing Unit Dimensions
A B C D E F G H J K L M N O
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
See
8 1/8" 6 1/4" 9"
Note
Table 11. SEHL, SFHL, SLHL, SSHL, SXHL units (20 - 89 ton)
Dimensions
E
w/ Unit Size (AC/EC)
20-30
/24-36 Ton
40 & 50
/48 & 59 Ton
60/73 Ton 19'-10 5/16" 2'-5" 6 1/16" Note 1 4'-5 3/8" 4'-2 1/2” 5 13/16" 7'-8 3/16" 4'-5” 5 13/16" 26 7/16”
70-75
/80-89 Ton
A B C D
16'-3 3/16" 2'-2 1/2" 5 13/16" 5'-7" 3'-4 3/8" 2'-9 15/16” 5 13/16" 6'-6 15/16" 3' 5 13/16" 28 5/8”
19'-10 5/16" 2'-5" 7 1/16" 5'-7" 3'-4 3/8" 3'-1 1/2” 5 13/16" 7'-8 3/16" 3'-4” 5 13/16" 32 15/16”
19'-10 5/16" 2'-5" 6 1/16" Note 1 4'-5 3/8" 4'-2 1/2” 5 13/16" 7'-8 3/16" 4'-5” 5 13/16" 26 7/16”
exhaust
fan
w/
return fan
exhaust
F
HJKL
20-30
/24-36 Ton
40 & 50
/48 & 59 Ton
60/73 Ton 18'-11 11/16" Note 2 8 3/16" 9 1/16"
70-75
/80-89 Ton
Notes:
1. 5'-5 15/16” for SEHL units or 7'-8 1/2” for SFHL, SLHL, SSHL, SXHL units.
2. 20'-1 3/4” for SFHL “High Heat” units or 20'-6 3/4” for SFHL “Low Heat” units. Either is selectable in field for SL and SS Return.
15'-5 5/16" 16'-9 3/4" 8 13/16" 9 1/16"
18'-11 11/16" Note 2 8 3/16" 9 1/16"
18'-11 11/16" Note 2 8 3/16" 9 1/16"
G F
w/
w/
return
fan
fan
w/
exhaust
fan
return
w/
fan
30 RT-SVX36K-EN
Loading...
+ 162 hidden pages