NOTICE: Warnings and Cautions appear at appropriate sections through-
out this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents.
Important - Read This First!
This manual is intended for experienced service personnel familiar with the
proper use of electrical diagnostic instruments and all personal safety
procedures when working on live electrical circuits.
This Manual is not intended for individuals who have not been properly trained
in handling live electrical circuits.
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect the
ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs)
and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all
refrigerants containing these compounds have the same potential impact to the
environment. Trane advocates the responsible handling of all refrigerants—
including industry replacements for CFCs such as and HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified. The Federal Clean Air Act (Section
608) sets forth the requirements for handling, reclaiming, recovering and
recycling of certain refrigerants and the equipment that is used in these service
procedures. In addition, some states or municipalities may have additional
requirements that must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to
relieve pressure before opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant
additives.
Failure to follow proper procedures or the use of non-approved refrigerants,
refrigerant substitutes, or refrigerant additives could result in death or serious
injury or equipment damage.
The Unit Control Modules (UCMs) described in this troubleshooting guide
provide a microprocessor based refrigeration control system, intended for
use with Trane 70-125 ton helical rotor chillers. Six types of modules are
used, and throughout this publication will be referred to by their abbreviations
or their Line Wiring Drawing Designations, see Tab le 1.
Table 1Unit Control Module Designations
Line Drawing
Designation
1U2Options ModuleCSR
1U3Expansion Valve ModuleEXV
1U4 & 1U5Compressor ModuleMCSP A & B
1U6Clear Language DisplayCLD
1U7Interprocessor
Controller Name
Chiller Module
Communications Bridge
(Remote Display Buffer)
Abbrev.
CPM
IPCB
Service Philosophy
With the exception of the fuses, no other parts on or within the modules are
serviceable. The intent of the troubleshooting is to determine which module
is potentially at fault and then to confirm a module problem. This is done
either through voltage or resistance measurements at the suspected input or
output terminals or by checking related wiring and external control devices
(connectors, sensors, transformers, contactors etc.) in a process of elimination. Once a problem has been traced to a module, the module can be
easily replaced using only basic tools. In general, all dip switch settings of the
replaced modules should be copied onto the replacement module's dip
switches before applying control power. CPM replacement is more involved
as there are numerous configuration and set-up items that must be
programmed at the Clear Language Display in order to insure proper unit
operation.
It is helpful to include with the return of a module, a brief explanation of the
problem, sales office, job name, and a contact person for possible follow-up.
The note can be slipped into the module enclosure. Early and timely
processing of Field Returns allows for real measurements of our product
quality and reliability, providing valuable information for product improvement
and possible design changes.
4RLC-SVD03A-EN
General Information
System Description
The CPM is the master module and coordinates operation of the entire
system. One is used per chiller. The MCSP is a compressor protection
module with one being used for each of the compressors in the chiller. The
EXV is the expansion valve controller module which controls two Electronic
Expansion Valves. There is one valve on each of the two refrigeration circuits.
The CLD is a two line, 40 character alphanumeric interface to the system. It
allows the operator to read operating and diagnostic information, as well as
change control parameters. The Interprocessor Communications Bridge
(IPCB) provides an extension of the IPC link to the Remote Clear Language
Display, while protecting the integrity of the IPC communications link
between the local modules.
The CSR is an optional communications module which allows for communications between the chiller and a remote building automation system (i.e.
Tracer, Tracer Summit, Generic BAS).
All modules in the system communicate with each other over a serial interprocessor communications bus (IPC) consisting of a twisted wire pair “daisy
chain” link and RS485 type signal levels and drive capability. Multiple modules
of the same type (i.e. MCSPs) in an operating system are differentiated by
address dip switches.
All the modules operate from 115VAC, 50 or 60Hz power and each have their
own internal step-down transformer and power supply. Each is individually
fused with a replaceable fuse. The modules also are designed to segregate
their high and low voltage terminals by placing the high voltage on the right
side of the module and the low voltage on the left. When stacked, segregation is maintained.
In addition to the modules, there are a number of “system level” components that are closely associated with the modules. These components were
specifically designed and/or characterized for operation with the modules. For
this reason, the exact Trane part must be used in replacement.
System Level Components
Description
The following is a list of all the components that may be found connected to
the various modules.
Transformer, Under/Over voltage
Current Transformer - Compressor
Evap EntlLvg Water Temp Sensor Pair
Sat Evap/Cprsr Suc Rfgt Temp. Sensor Pair
Sat Cond RfgtIOil Temp Sensor Pair
Outdoor Air Temperature Sensor
Zone Temp Sensor
Connector (UCM mating connectors)
Connector Keying Plug
Electronic Expansion Valve
RLC-SVD03A-EN5
General Information
High Pressure Cutout Switch
Low Pressure Cutout Switch
Variable Speed Fan Drive
Motor Temperature Thermostats
Slide Valve Load/Unload Solenoids
Step Load Solenoid Valve
Chiller Module (CPM) IU1
The CPM module performs machine (chiller) level control and protection
functions. Only one CPM is present in the chiller control system. The CPM
acts as the master controller to the other modules, running top level machine
control algorithms, initiating and controlling all inter-module communication
over the IPC, and providing parameters and operational requests (i.e. loading
and unloading, starting and stopping) to the other modules in the system via
the IPC. The CPM also contains nonvolatile memory, which allows it to
remember configuration and set-up values, setpoints, historical diagnostics
etc. for an indefinite period of time following a power loss. Direct hard wired
I/O associated with the CPM includes low voltage analog inputs, low voltage
binary inputs, 115 VAC binary inputs and 115 VAC (rated) relay outputs. See
Chiller Module (CPM) (1U1) on page 46 for further details.
Compressor Module (MCSP) 1U4 and 1U5
The MCSP module employs the input and output circuits associated with a
particular compressor and refrigeration circuit. Two MCSP modules are used
in the UCM system, one for each compressor. Included are low voltage
analog and digital circuits, 115 VAC input, and 115 VAC output switching
devices. The output switching devices associated with the compressor motor
controlling function are contained in this module. The outputs of this module
control one compressor motor stop/start contactor, one compressor motor
transition contactor, one oil heater, three solenoid valves (compressor load,
compressor unload, step loader), and up to four fan motor contactors or
groups of contactors. Refer to the chiller's line wiring diagrams for details. Dip
switches are provided for redundant programming of the compressor current
overload gains, and for unique IPC address identification during operation.
Inputs to this module include motor temperature thermostats, thermisters,
and safety switches. See Compressor Module (MCSP) (1U4 AND 1U5) on
page 72 for details.
Expansion Valve Module (EXV) 1U3
The EXV module provides power and control to the stepper motor driving the
electronic expansion valves of the chiller. Each module handles two valves,
one in each refrigeration circuit.
Input to the EXV Module is provided by four temperature sensors (two per
refrigeration circuit). The sensors are located in the respective refrigeration
circuits of the chiller and sense Saturated Evaporator and Suction temperatures and calculate the superheat temperatures. High level operational
commands as well as superheat setpoints are received by the EXV Module
over the IPC from the CPM module to modulate the EXV's.
6RLC-SVD03A-EN
General Information
Real time data for temperatures, diagnostics and control algorithms etc. are
made available to the CPM and the other modules for display and for input to
higher level functions. See Electronic Expansion Valve Module (EXV) (1U3) on
page 58 for details.
Options Module (CSR) 1U2
The CSR module is an optional part of the system and employs communications circuits for interface to Trane Building Automation Systems, done
through 1C17. The CSR also provides inputs for hard wired external setpoints
and reset functions. Included are low voltage analog and digital input circuits.
See Options Module (CSR) (1U2) on page 50 for details.
Clear Language Display (CLD) 1U6
The CLD Module provides an operator interface to the system, through a two
line, 40 character alphanumeric display. Three reports may be displayed and
various operating parameters may be adjusted by depressing a minimal
number of keys on the CLD. Also, chiller Start/Stop functions may be
performed at this keypad. See Clear Language Display (CLD) 1U6 Keypad
Overview on page 42 for details.
Interprocessor Communication Bridge (IPCB) 1U7
The IPCB module allows connection of a Remote Clear Language Display
module to the UCM, for distances of up to 1500 feet. The Remote Clear
Language Display communicates with the UCM, utilizing the same IPC
protocol, and provides most of the same functions as the local CLD. The IPCB
then serves to protect the UCM's IPC if wires to the Remote CLD become
shorted or broken. See Section 2 and on page 75 for details.
RLC-SVD03A-EN7
Interprocessor Communications
The respective modules communicate with each other via an InterProcessor
Communication link (IPC). The IPC allows the modules to work in a coordinated manner with the CPM directing overall chiller operation while each
module handles specific subfunctions. This IPC link is integral and necessary
to the operation of the Unit Controls and should not be confused with the
Optional ICS (Integrated Comfort System) communication.
In the IPC communication protocol scheme, the CPM acts as the initiator and
the arbitrator of all module communication. The CPM essentially requests all
the possible “packets” of information from each module in turn, (including
itself), in a predefined serial sequence. The other modules act as
“responders” only and cannot initiate communication. Modules which are not
currently responding to a specific request, can listen to the data and thus,
indirectly, they communicate with each other. It is helpful to remember when
troubleshooting that a module must be able to hear a request for its information from the CPM, or it will not talk.
The link is non-isolated, which means that a good common ground between
all the modules is necessary for trouble-free operation (provided by the
module enclosures' mounting using star washers). Also, the link requires
consistent polarity on all of the module interconnections. Connections
between modules are made at the factory, using unshielded #18 gauge
twisted pair cable terminated into a 4-position MTA type connector (orange
color code). This connector is plugged onto the 4 pin IPC connection jack
designated as J1, located in the upper left corner of the PC board edge on all
of the modules. The 4 pins actually represent 2 pairs of communications
terminals (J1-1 (+) internally connected to J1-3, and J1-2 (-) internally
connected to J1-4) to allow for easy daisy chaining of the bus.
IPC Diagnostics
The modules, in order to work together to control the chiller, must constantly
receive information from each other over the IPC. Failure of certain modules
to communicate or degradation of the communication link, could potentially
result in chiller misoperation. To prevent this situation, each module monitors
how often it is receiving information from designated other modules. If a
module fails to receive certain other module's transmitted data over a 15
second time period it will:
1.On its own, take specific action to safely shut-down (or to default) its controlled loads.
2. Report a diagnostic to the CPM (over the IPC link).
The CPM (if it properly receives such) will then report and display the
diagnostic on the Clear Language Display accordingly. The diagnostic will:
•identify which module is reporting the communication problem and
•identify which module was to have sent the missing information.
The CPM itself will then send out further commands to the other modules to
shutdown or take default actions as the particular case may warrant.
All IPC diagnostics are displayed in the Clear Language Display's diagnostics
section. For example, “Chiller Mod indicating Options Mod Comm Failure”
indicates that the CPM Module has detected a loss of IPC communication
8RLC-SVD03A-EN
Interprocessor Communication
from the Options Module. When some problem exists with the IPC link or a
module fails, it is not uncommon for more than one of these IPC diagnostics
to be displayed. Note that only those diagnostics that are indicated to be
active currently exist. All other historic diagnostics should be disregarded for
the purpose of the following troubleshooting discussion. See RTAA-IOM-4 for
a complete listing of diagnostics.
Troubleshooting Modules Using IPC Diagnostics
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
Communication problems can result from any of the following:
1.Improperly set IPC address dip switches
2. Opens or shorts in the twisted pair IPC wiring or connectors
3. Loss of power to a module
4. Internal module failure
5. Improper connections on terminal J2
6. High levels of EMI (Electro-Magnetic Interference)
7.Module specific function selected without the Options Module.
These are discussed in more detail in the following paragraphs.
1.Improperly set IPC address dip switches:
This could result in more than one module trying to talk at the same time,
or cause the mis-addressed module to not talk at all. Only the MCSP and
the EXV modules have IPC address dip switches, found in the upper left
hand portion of the Module labeled as SW-1. The proper dip switch setups are shown in Table 2.
2. Opens or shorts in the twisted pair IPC wiring or connectors:
One or more modules may be affected by an open or a short in the IPC
wiring, depending on the location of the fault in the daisy chain. The diagram below shows the daisy chain order and is helpful in diagnosis of an
open link.
Extreme care should be used in making any dip switch changes or when
replacing MCSP modules. “Swapping” of addresses on the MCSPs
cannot be detected by the communication diagnostics discussed above
and serious chiller misoperation will result.
Table 2IPC Address Dip Switch (SW1) Settings for MCSP an EXV Modules
MODULEDESIG.CONTROLLINGDIP SWITCH SETTING
SW1-1SW1-2
MCSP “A”1U4COMPRESSOR AOFFOFF
MCSP “B”1U5COMPRESSOR BOFFON
EXV1U3CKTS. 1 & 2OFFOFF
3. Loss of power to a module:
Generally a power loss to a particular module will only affect communications with that module. The module can usually be identified by analysis
of the IPC diagnostics. (When the display is blank, check power at the
CLD). Loss of power can most directly be diagnosed by measuring the
AC voltage at the top of the fuse with respect to the neutral of the power
connection (pins 4 or 5) on the terminal just below the fuse:
IXVHGVLGH
)86(
+
-
1&
1(875$/
Figure 2Module Fuse and Power Connection, Except CLD
4. Internal module failure:
Internal module failures usually result only in communication loss to the
failed module, but could, in some cases, affect all the modules because
the failed module may “lock up” the IPC bus and prevent all communications. The former can be identified by analyzing all of the active IPC diagnostics. The latter can be identified in a process of elimination, whereby
each module, in turn, is taken out of the IPC link and a jumper installed in
its place. See Figure 3. The CPM can then be reset and the new IPC diagnostics that result can be analyzed.
XQVZLWFKHGVLGH
+
+
1
1
³9$&´
7R&KHFN
)XVH
9$&3RZHU
&RQQHFWLRQ
1
RLC-SVD03A-EN11
Interprocessor Communication
-
$03FF
KHDGHUSLQV
Figure 3IPC Jumper For Bypassing Modules (to be inserted into MTA
connector in place of module)
5. Improper connections to terminal J2:
Jack J2, present on all modules except CLD, should have no connections.
This input is for manufacturing test purposes only and any connections,
shorts, etc. will potentially cause the module to not respond, respond to
the wrong address, or (in the case of the CPM) fail to initiate any communications and thus fail the entire IPC.
6. High levels of Electro-Magnetic Interference:
The modules and the IPC have been qualified under severe EMI (both
radiated and conducted) and the system was determined to be immune
to all but extremely high noise levels. Always be sure to close and latch
the control panel cabinet doors as the panel enclosure provides significant shielding and is integral in the overall noise immunity of the control
system.
7.Module specific function selected without the Options Module:
If any of the functions on the Options Module are selected but the
Options Module is not present, the UCM will look for this module and
generate an error. The Options Module functions include Chilled Water
Reset, Ice Machine Control, External Chilled Water Setpoint, External
Current Limit Setpoint, and Tracer/Summit Communications.
RUHTXLY
:LUH
MXPSHUV
VROGHUHGRU
ZUDSSHGLQWR
SLQV
Troubleshooting Procedure
1.Place the CPM in “Stop”. Record the active IPC diagnostics as shown in
the Diagnostics Report of the CLD. The communication failure diagnostics and their meanings are shown in IPC Diagnostics of the RTAA-IOM-4
manual.
2. Determine which modules are not talking. These modules must be
affected by one of the previously stated problems. If there is a group of
modules not talking, suspect a wiring problem early in the daisy chain
link. If only one module is not talking, suspect a loss of power or blown
fuse.
12RLC-SVD03A-EN
Interprocessor Communication
3. Determine which modules are still talking. Wiring up to these is likely to
be OK.
4. Try disconnecting the link or jumping out modules in the link at various
places (use Figure 1). Reset the diagnostics and note which diagnostics
reappear.
Here are some examples of IPC diagnostics:
Diagnostics present:
Chiller Mod Indicating EXV Mod Communications
Cprsr A Indicating EXV Mod Communications
Cprsr B Indicating EXV Mod Communications
The CPM and both MCSP modules are detecting a loss of communications
with the EXV. Suspect power to the EXV or its fuse or a wiring problem
downstream of the MCSP A and B modules.
Diagnostics present:
Chiller Mod Indicating Options Mod Communications
Chiller Mod Indicating EXV Mod Communications
Chiller Mod Indicating Cprsr A Communications
Chiller Mod Indicating Cprsr B Communications
The CPM is reporting that it cannot talk to any of the other modules. Suspect
a shorted IPC bus or a module locking up the bus. The CPM could also be bad
and not be sending recognizable tokens. Discriminating between these possibilities is done by disconnecting the link or jumping out modules in the link at
various places. Refer to Item 4 in Troubleshooting Modules (Troubleshooting
Modules Using IPC Diagnostics on page 9) for the procedure and the IPC
Jumper for bypassing the Modules.
Diagnostics present:
Chiller Mod Indicating Cprsr B Communications
EXV Mod Indicating Cprsr B Communications
The CPM and EXV have both detected a communication loss with MCSP B.
Suspect the address switch on MCSP B or a power/fuse problem.
Diagnostics present:
Chiller Mod Indicating Cprsr A Communications
Chiller Mod Indicating Cprsr B Communications
EXV Mod Indicating Cprsr A Communications
EXV Mod Indicating Cprsr B Communications
The CPM and EXV have both detected a communication loss with MCSP A
and MCSP B. Suspect that the address switches on both modules are set to
the same address. Wiring is probably OK since the EXV can talk to the CPM.
Diagnostics present:
Chiller Mod Indicating Cprsr B Communications
Chiller Mod Indicating Cprsr A Communications
Chiller Mod Indicating EXV Mod Communications
RLC-SVD03A-EN13
Interprocessor Communication
The CPM has detected loss of communications with MCSP A, MCSP B,
and EXV. Suspect an open early in the IPC link between the CPM and
MCSP B.
There are a large number of possible combinations of diagnostics. One must
deduce what is causing the problem using all available information.
If the CLD Comm link to the CPM is broken, the message is:
No Communication, Data Not Valid
14RLC-SVD03A-EN
Temperature Sensor Checkout
With the exception of the thermostats located in the motor windings of the
screw compressors, all the temperature sensors used on the UCMs are
negative temperature coefficient (NTC) thermistors. The thermistors
employed all have a base resistance of 10 Kohms at 77F (25C) and display a
decreasing resistance with an increasing temperature. The UCMs “read” the
temperature by measuring the voltage developed across the thermistors in a
voltage divider arrangement with a fixed internal resistance. The value of this
“pull-up” resistor is different depending on the temperature range where the
most accuracy is desired. The voltage source for this measurement is a
closely regulated 5.0 VDC supply.
An open or shorted sensor will cause the UCM to indicate the appropriate
diagnostic. In most cases, an open or short will cause a CMR or MMR
diagnostic that will result in a machine or circuit shutdown. Open or shorts on
less critical Outdoor Air or Zone Temperature sensors will result in an
Informational Warning Diagnostics and the use of default values for
that parameter.
Temperature Sensor Checkout Procedure
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
1.Measure the temperature at the sensor using an accurate thermometer.
Record the temperature reading observed.
2. With the sensor leads connected to the UCM and the UCM powered,
measure the DC voltage across the sensor leads at the terminal or probe
the back of the MTA plug.
NOTE: Always use a digital volt-ohmmeter with 10 megohm or greater input
impedance to avoid “loading down” the voltage divider. Failure to do so will
result in erroneously high temperature calculations.
3. Locate the appropriate sensor table. Table 3: Evaporator Water and
Refrigerant Temperature Sensors, Tab l e 4 : Saturated Condenser Refrigerant and Entering Oil Temperature Sensors. Then compare the temperature in the table corresponding to the voltage reading recorded in Step 2
with the actual temperature observed in Step 1. If the actual temperature
measured falls within the allowable tolerance range, both the sensor and
the UCM's temperature input circuits are operating properly. However, if
the actual temperature is outside the allowable sensor tolerance range,
proceed to Step 4.
RLC-SVD03A-EN15
Temperature Sensor Checkout
4. Again measure the temperature at the sensor with an accurate thermometer; record the temperature reading observed.
5. Remove the sensor leads from the terminal strip or unplug the respective
MTA. Measure the resistance of the sensor directly or probe the MTA
with a digital volt-ohmmeter. Record the resistance observed.
6. Next, with the sensor still disconnected from the module, check the
resistance from each of the sensor leads to the control panel chassis.
Both readings should be more than 1 Megohm. If not, the sensor or the
wiring to the sensor is either shorted or leaking to chassis ground and
must be repaired.
7.Select the appropriate sensor table and locate the resistance value
recorded in Step 5. Verify that the temperature corresponding to this
resistance value matches (i.e. within the tolerance range specified for
that sensor) the temperature measured in Step 4.
8. If the sensor temperature is out of range, the problem is either with the
sensor, wiring, or the MTA connector (if applicable). If an MTA connector
is used and the thermistor reads open, first try cutting off the MTA, stripping a small amount of insulation from the sensor wire's end and repeating the measurement directly to the leads. Once the fault has been
isolated in this manner, install a new sensor, connector or both. When
replacing a sensor, it is easiest to cut the sensor wire near the MTA end
and splice on a new sensor using wire nuts.
9. A decade box can be substituted for the sensor and any sensor table
value used to relate resistance to temperature. By removing the MTA
plug and applying the resistance to the proper pin terminals, the temperature, as sensed by the UCM, can be confirmed. Using the CLD menu displays, scroll to the display of the temperature of interest.
NOTE: All displayed temperatures are slew rate limited and only accurate
within a specified normal range. It is therefore important to be certain that
the temperature readings are stable and that adequate time, up to 1 minute,
is allowed after step changes in resistance inputs are made.
10. In all instances where module replacement is indicated, first perform the
power supply/fuse check according to the information in the section
“Module Power and Miscellaneous I/O” starting on page 41.
16RLC-SVD03A-EN
Temperature Sensor Checkout
Table 3Sensor Conversion Data: Outdoor Air (6RT3), Entering and Leaving Evap Water Temp Matched
.
Pairs (6RT7, 6RT8), and Saturated Evap and Comp Suction Refrigeration Temp (6RT9, 3B1RT5; 6RT10, 4B1RT6)
Actual
Te m p .
(F)
-20.0170040.34.44830.034838.93.12080.09297.51.533
-19.0164313.44.43431.033833.33.08681.09075.91.509
-18.0158796.54.41432.032861.43.04782.08860.21.484
-17.0153482.94.39533.031935.33.01883.08650.41.460
-16.0148365.04.38034.031038.72.98384.08446.21.436
-15.0143432.24.36035.030170.52.94985.08247.51.411
-14.0138679.64.34136.029329.52.91086.08054.11.387
-13.0134098.64.32137.028515.02.87687.07865.81.362
-12.0129684.94.30238.027725.92.84288.07682.51.343
-11.0125428.54.28239.026961.42.80889.07504.21.318
-10.0121326.14.26340.026220.82.77390.07330.51.294
-9.0117369.64.23841.025503.02.73991.07161.41.274
-8.0113554.94.21942.024807.52.70592.06996.71.250
-7.0109876.54.19443.024133.32.67193.06836.31.230
-6.0106328.14.17544.023479.72.63794.06680.11.211
-5.0102904.94.15045.022846.12.60395.06528.01.187
-4.099602.34.12646.022231.92.56896.06379.81.167
-3.096416.14.10647.021636.22.53497.06235.51.147
-2.093341.64.08248.021058.72.50598.06094.81.128
-1.090374.24.05849.020498.42.47199.05957.81.108
0.087510.34.03350.019955.02.437100.05824.31.089
1.084745.94.00451.019427.92.402101.05694.21.069
2.082077.13.97952.018916.52.368102.05567.41.050
3.079500.53.95553.018420.32.334103.05443.81.030
4.077012.33.92654.017938.82.305104.05323.31.016
5.074609.73.90155.017471.62.271105.05205.90.996
6.072288.83.87256.017018.02.236106.05091.50.977
7.070047.43.84857.016577.82.207107.04979.90.962
8.067881.93.81858.016150.52.173108.04871.10.942
9.065790.23.78959.015735.72.144109.04765.00.928
10.063768.73.76060.015332.92.109110.04661.50.913
11.061815.33.73061.014941.72.080111.04560.60.894
12.059927.83.70162.014561.92.046112.04462.20.879
13.058103.13.67263.014193.02.017113.04366.30.864
14.056339.63.64364.013834.61.987114.04272.60.850
15.054634.73.60865.013486.51.958115.04181.30.835
16.052986.43.57966.013148.31.924116.04092.20.820
17.051392.63.55067.012819.81.895117.04005.30.806
18.049851.63.51668.012500.51.865118.03920.50.791
19.048360.93.48669.012190.21.836119.03837.70.776
20.046919.23.45270.011888.71.807120.03756.90.762
21.045524.63.41871.011595.61.777121.03678.10.747
22.044175.63.38972.011310.71.753122.03601.10.732
23.042870.33.35473.011033.71.724123.03526.50.723
24.041607.63.32074.010764.41.694124.03453.60.708
25.040385.33.28675.010502.61.670125.03382.40.698
26.039202.73.25776.010248.01.641126.03313.00.684
27.038057.93.22377.010000.41.616127.03245.10.674
28.036950.03.18878.09759.61.587128.03178.90.659
29.035877.43.15479.09525.41.563129.03114.20.649
1. Overall accuracy for any of the sensors is at least + 2 F over the range shown. Accuracy of matched sensors is + 1 F over specific ranges.
2. As you compare a thermistor resistance (or input voltage) reading with the “actual” temperature indicated by the thermometer, be sure to
consider the precision and location of the thermometer when you decide whether or not the thermistor is out of specified accuracy.
3. The thermistor resistances given do not account for the self-heating effects that are present when connected to the UCM. A connected
“operating” thermistor will read a slightly lower (less than 1%) resistance.
Actual
Resistance
(Ohms)
Thermistor
Vo lt ag e
(Volts DC)
Actual
Te m p .
(F)
Actual
Resistance
(Ohms)
Thermistor
Vo lt ag e
(Volts DC)
Actual
Te m p .
(F)
130.03051.00.635
Actual
Resistance
(Ohms)
Thermistor
Vo lt ag e
(Volts DC)
RLC-SVD03A-EN17
Temperature Sensor Checkout
Table 4Sensor Conversion Data: Saturated Condenser and Entering Oil Temperature Matched Pairs
(6RT12, 3B1RT1; 6RT13, 4B1RT2)
Actual
Te m p .
(F)
0.087510.34.65150.019955.03.765100.05824.32.356
1.084745.94.64151.019427.93.740101.05694.22.327
2.082072.14.63052.018916.53.715102.05567.42.300
3.079500.14.61953.018420.33.689103.05443.82.272
4.077012.34.60854.017938.83.664104.05323.32.244
5.074609.74.59655.017471.63.638105.05205.92.217
6.072288.84.58456.017018.03.611106.05091.52.189
7.070047.44.57257.016577.83.585107.04979.92.162
8.067881.94.56058.016150.53.558108.04871.12.135
9.065790.24.54759.015735.73.531109.04765.02.108
10.063768.74.53460.015332.93.504110.04661.52.082
11.061815.34.52161.014941.73.477111.04560.62.055
12.059927.84.50762.014561.93.450112.04462.22.029
13.058103.14.49463.014193.03.422113.04366.32.003
14.056339.64.47964.013834.63.394114.04272.61.977
15.054634.74.46565.013486.53.366115.04181.31.951
16.052986.44.45066.013148.33.338116.04092.21.926
17.051392.64.43567.012819.83.310117.04005.31.901
18.049851.64.42068.012500.53.282118.03920.51.876
19.048360.94.40469.012190.23.253119.03837.71.851
20.046919.24.38870.011888.73.225120.03756.91.826
21.045524.64.37271.011595.63.196121.03678.11.802
22.044175.64.35572.011310.73.167122.03601.11.777
23.042870.34.33873.011033.73.139123.03526.51.754
24.041607.64.32174.010764.43.110124.03453.61.730
25.040385.34.30375.010502.63.081125.03382.41.707
26.039202.74.28576.010248.03.051126.03313.01.684
27.038057.94.26677.010000.03.022127.03245.11.661
28.036950.04.24878.09759.62.993128.03178.91.638
29.035877.44.22979.09525.42.964129.03114.21.615
30.034838.94.20980.09297.52.935130.03051.01.593
31.033833.34.19081.09075.92.905131.02989.21.571
32.032861.44.17082.08860.22.876132.02928.91.549
33.031935.34.15083.08650.42.847133.02870.01.528
34.031038.74.13084.08446.22.817134.02812.41.506
35.030170.54.10985.08247.52.788135.02756.21.485
36.029329.54.08886.08054.12.759136.02701.21.464
37.028515.04.06787.07865.82.730137.02647.51.444
38.027725.94.04588.07682.52.700138.02595.01.423
39.026961.44.02489.07504.22.671139.02543.71.403
40.026220.84.00290.07330.52.642140.02493.61.383
41.025503.03.97991.07161.42.613141.02444.61.364
42.024807.53.95792.06996.72.584142.02396.71.344
43.024133.33.93493.06836.32.555143.02349.91.325
44.023479.73.91094.06680.12.526144.02304.11.306
45.022846.13.88795.06528.02.498145.02259.21.287
46.022231.93.86396.06379.82.469146.02216.01.269
47.021636.23.83997.06235.52.440147.02172.81.250
48.021058.73.81598.06094.82.412148.02131.61.232
49.020498.43.79099.05957.82.384149.02090.41.215
1. Overall accuracy for the sensor is at least + 2 F over the range shown.
2. As you compare a thermistor resistance (or input voltage) reading with the “actual” temperature indicated by the thermometer, be sure to
consider the location and precision of the thermometer when you decide whether or not the thermistor is out of specified accuracy.
3. The thermistor resistances given do not account for the self-heating effects that are present when connected to the UCM. A connected
“operating” thermistor will read a slightly lower (less than 1%) resistance.
Actual
Resistance
(Ohms)
Thermistor
Volta ge
(Volts DC)
Actual
Te m p .
(F)
Actual
Resistance
(Ohms)
Thermistor
Vo lt ag e
(Volts DC)
Actual
Te m p .
(F)
150.02051.21.197
Actual
Resistance
(Ohms)
Thermistor
Volta ge
(Volts DC)
18RLC-SVD03A-EN
Compressor Operation
This feature is called the Auto Lead/Lag and can be found in the Service
Settings Group, under the “Balanced CPRSR Starts and Hours” menu. When
this function is disabled, the UCM always starts compressor “A” first. When
this function is enabled, the following occurs:
The UCM equalizes operating starts and hours. This will cause the
compressor with the least amount of starts to be started first. When a
compressor starts, it is always started unloaded.
When a compressor is stopped, it shuts down in an unloaded state, unless
taken out by a manual reset diagnostic.
When the first compressor is brought on line, it attempts to meet the load by
staging on the step load solenoid and by pulsing the male slide valve load
solenoid. If one compressor cannot meet the load demand, the second
compressor is brought on line. It also attempts to meet the load demand by
staging on its step load solenoid and by pulsing its male slide valve solenoid.
When both compressors are running and both of their step load solenoids are
energized, the male load and unload solenoids on both compressors are
pulsed, thus modulating their respective slide valves to balance the load. The
UCM attempts to distribute the load evenly between the two compressors.
When the load drops off, the compressor with the most hours will always be
the first to unload and turn off. The anti-recycle timer is approximately 5
minutes from start to start. The minimum time between compressor
shutdown and restart is approximately 10 seconds, but only if the
compressor has been running over 5 minutes or longer prior to shutting down
on temperature. Otherwise, it is the remaining portion of the 5 minutes.
Restart Inhibit Timer
If compressor operation is interrupted by an extended (not momentary) loss
of power or a manual reset, there will be a two minute delay between the
power up or manual reset and the start of a compressor, assuming there is a
call for cooling. The timer is factory set at 2 minutes but can be field adjusted
from 30 seconds to two minutes in the Service Settings Group.
RLC-SVD03A-EN19
Compressor Start/Stop
To start a compressor after either a “normal' shutdown, a Diagnostic reset, or
power-on-reset, the following sequence will occur:
1.On a call for a compressor, the Restart Inhibit Timer will time out, if any
time remains.
2. The EXV is positioned to the initial closed start position. At the same
time, the unload solenoid is energized and the load solenoid is de-energized. Timing is determined by the time required to position the EXV
3. After the EXV is positioned:
•the compressor is turned on
•the compressor heater is de-energized
•the saturated evaporator ref. temp. cutout ignore time is set, based on
the saturated condenser temperature. Prior to start, the condenser temperature approximates the ambient temperature.
•the fan control algorithm is executed
To stop a compressor due to either the Stop button on the CLD or an
External/Remote “STOP”, the sequence shall be as follows:
1.The unload solenoid is energized for 20 seconds and the load solenoid is
de-energized. The compressor continues to run for the remaining 20 seconds. This is defined as the RUN:UNLOAD mode.
2. The compressor and the fans are turned off. The crankcase heater is
energized.
3. The unload solenoid remains energized for 60 minutes after the compressor stops. The load solenoid is de-energized.
4. The EXV is closed. Closing begins at maximum speed when the compressor is turned off. (Max. speed is 25 steps per second, full stroke is
757 steps.
5. After 60 minutes, the unload solenoid de-energizes.
The RUN:UNLOAD mode is also used to stop a compressor due to normal
LWT control, Low Ambient Run Inhibit, or Freeze Avoidance.
A compressor stop due to any diagnostic will skip step 1 above and go
directly to step 2.
20RLC-SVD03A-EN
Variable Speed
Inverter/Condenser Fan Control
When Fan Control and Variable Speed Fan (VSF) are set to Enable in the
Machine Configuration Menu, the UCM will control both the variable speed
fan and the remaining constant speed fans per the VSF Control Algorithm. If
VSF Control is disabled for a given circuit but Fan Control is enabled for the
machine, the circuit will perform normal constant speed fan control. The VSF
is enabled and operational, the control attempts to provide a 70 ± 5 psid
between the Condenser Pressure and the Evaporator Pressure (as derived
from the temperature sensor measurements).
Figure 4Variable Speed Fan (VSF) and Fan Staging Control
The VSF Inverter is commanded to a given speed by the UCM, using a PWM
(Pulse Width Modulated) signal (10V, 15mA, 10 Hz Fundamental) with a duty
cycle proportional to the desired voltage and frequency from the Inverter. The
UCM also controls power to the Inverter through a contactor. The Inverter
Contactor for the respective circuit is energized approximately 20 seconds
prior to compressor start on that circuit. The VSF Control algorithm runs on a
5-second interval and is limited to a commanded rate of change of no greater
than 40% of full speed per interval. The same algorithm that controls the
RLC-SVD03A-EN21
Variable Speed Inverter/
Condenser Fan Control
speed will also cause constant speed fans to stage On and Off when the
inverter is commanded to full speed and minimum speed respectively. The
stage On (or Off) of a constant speed fan will occur if the inverter speed
command is at max (or min.) for three consecutive intervals (15 seconds).
Outdoor Air Temperature and Fan Control
Outdoor air temperature is used to provide a reasonable startup state. Using
this temperature, the algorithm automatically determines the number of
constant speed fans to turn on immediately at compressor start. The outdoor
air temperature sensor is also used to anticipate new states during normal
running to minimize pressure upsets. This anticipation is based on the staging
and unstaging of compressor steps at given leaving water temperatures. In
this way, precise airflow can be maintained, allowing for stable differential
pressures under part load and low ambient conditions.
VSF Inverter Fault
A fault signal will be sent to the UCM from the Inverter when it has gone
through a self-shutdown or if the output frequency of the Inverter is being
limited to less than 50% of the signal speed commanded by the UCM. Upon
receipt of the fault signal, the UCM shall attempt to reset the fault by sending
a 0 PWM command to the Inverter for a total of five seconds. The fault signal
will again be checked and repeated if still in fault. If four faults are detected
within one minute of each other, the power to the Inverter will be cycled off
for 30 seconds (through contactor control) and then re-powered. If the fault
still remains or occurs again within one minute, an IFW diagnostic occurs.
The UCM will remove power from the Inverter and attempt to run the
remaining constant-speed fans using normal constant-speed Fan Control
Algorithm. See page 80 for step-by-step troubleshooting procedure.
22RLC-SVD03A-EN
Current Transformer
Each compressor motor has all three of its line currents monitored by torroid
(doughnut) current transformers. While the MCSP utilizes all three of the
signals, it only displays the maximum phase at any given time. These currents
are normalized with respect to the Rated Load Amps of the respective
compressor and thus are expressed in terms of % (percent) RLA. The
currents are “normalized” thru the proper selection of the Current Transformer, the setting of the Compressor Current Overload dip switch (SW2) on
the MCSPs, and the redundant programming of the decimal equivalent of
these settings in the Service Settings Group of the CLD. (The term
“Compressor Current Overload setting” is actually a misnomer. Instead the
setting should be thought of as an internal software gain that normalizes the
currents to a % RLA for a given CT and compressor rating. The true nominal
steady state overload setting is fixed at 132%). Refer to Tables 5 thru 9 for
setup details.
The current transformers provide the input for six basic functions of the
MCSP:
1.Motor overload protection using a programmed “% RLA versus time to
trip” characteristic. Refer to Ta bl e 6 for details. The steady state “must
trip” value is 140% RLA and the “must hold” value is 125% RLA. The
MCSP will trip out the compressor. The appropriate diagnostic descriptions are then displayed in the CLD diagnostic section.
2. Verifying contactor drop-out. If currents corresponding to less than 12
±7% RLA are not detected on all three of the monitored compressor
phases within approximately 5 seconds after an attempted contactor
drop-out, the compressor will continue to be commanded Off, the Unload
solenoid will be pulsed, the EXV will be opened to its fullest position, and
the fans will continue to be controlled. This condition will exist until the
diagnostic is manually reset.
3. Loss of Phase Current. If the detection of any or all of the three motor
phase currents falls below 12 ±7% RLA for 2 ±1 seconds while the
branch circuit should be “energized”, the MCSP will trip out the compressor. The Phase Loss diagnostic, or the Power Loss diagnostic, will be displayed. Failure of a contactor to pull in will cause the Phase Loss
diagnostic. However when reduced voltage starting is employed, it may
take an additional 3 seconds to detect a phase loss at startup, as phase
loss protection is not active during the 3 second transition time.
4. Phase Rotation. Screw compressors cannot be allowed to run in reverse
direction. To protect the compressors, the phase rotation is detected by
the current transformers immediately at start up. If improper phasing is
detected, within 1 second of startup, the MCSP will trip out the compressor. The Phase Rotation diagnostics will be displayed. This function is not
sensitive to the current transformer's polarity.
5. Phase Unbalance. The MCSP will shut down the compressor if a phase
current unbalance is detected by the current transformers while the compressor is running. A 15% unbalance, if protection is enabled, will cause
the MCSP to trip out the compressor. The Phase Unbalance diagnostics
RLC-SVD03A-EN23
Current Transformer
will be displayed. If this protection is disabled, a 30% phase unbalance
will still be in effect with the diagnostic code Severe Phase Imbalance
being displayed.
6. Current Limit. The MCSP will begin to unload its compressor as the
%RLA exceeds 120%. Further, the CPM will cause the compressors to
automatically unload when the Chiller Current Limit Setpoint is reached.
The Current Limit Setpoint is set in the Service Setting Group. Individual
compressor phase currents are averaged and added together to compare
to the Chiller Current Limit which is in terms of % Total of all of the
Compressor RLNs.
NOTE: The current transformers are NOT polarity or directionally sensitive.
CT and MCSP Compressor Current Input Checkout
Procedure
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
1.Check incoming 3-phase power for voltage within 10% of nominal per
Chiller nameplate.
2. Interrogate the CPM for all of the presently active diagnostic codes or the
historic diagnostic codes in the Diagnostics Menu. Narrow the problem
down to a particular compressor or contactor as noted above. Write down
all of the diagnostic codes stored in the diagnostic registers.
If there is any question as to which compressor or current transformer is
causing a problem, or simply to verify and “witness” the problem, an
attempt should be made to restart the chiller after clearing diagnostics.
The diagnostics can be cleared by entering the Diagnostics Menu and
stepping to the CLEAR DIAGNOSTICS display.
It is possible to “force” certain compressors to be the first or next compressor to stage on, using the “Compressor Test” feature in the Service
Tests Menu. The Leaving Water Temperature must, however, be above
the Chilled Water Setpoint by more than the “differential to start” setting,
in order to stage on the first compressor.
At startup, verify the appropriate contactor(s) pull-in. The “Compressors
On” menu item in the Chiller Report Group will indicate which compressor started approximately five seconds after the contactor pulls in. Note
the diagnostic(s) that results, then place the Chiller into the “Stop” mode
by depressing the Stop button on the CLD.
24RLC-SVD03A-EN
Current Transformer
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures to
ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components provided by
Trane or others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of capacitors. Verify
with an appropriate voltmeter that all capacitors have discharged.
Failure to disconnect power and discharge capacitors before
servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of
capacitors, see PROD-SVB06A-EN or PROD-SVB06A-FR
3. For the next portion of the procedure, pull the unit's disconnect and interrupt all high voltage power to the control panel. Locate the torroid (doughnut) current transformers encircling the compressor power wiring and
branching to the compressor contactors of the suspect compressor-in the
control panel. Refer to the Component Location Drawing in the panel to
identify the particular current transformer(s) of interest. Locate the part
number/UL tag on the transformer leads and note the Trane part number
which identifies the transformers. Note: all compressors of a given tonnage should have the same transformer extension number. Verify the
proper current transformer using Tabl e 5 in this section. Also check the
setting of the dip switch (SW2) on each of the MCSP modules and verify
these against Tab l e 5 for each compressor. (Switch position SW2-1 is the
Most Significant Bit). The decimal equivalent of this setting should also
be verified in the Service Setting Group under the “CURRENT OVRLD
SETTINGS” display. If the programmed value does not agree with the dip
switch setting for each of the MCSP's, an informational diagnostic will
result. The compressors will be allowed to run, but default settings (the
most sensitive possible) will be used for the internal software compressor current gains.
4. Utilizing the Schematic Wiring Diagram, locate the termination of the
transformer's wiring into the MTA plug at the appropriate MCSP module
at pin header J5. Pull off the appropriate MTA connector from the pin
header on the MCSP.
Current Transformers can be damaged and high voltages can result due
to running the compressors without a suitable burden load for the CTs.
This load is provided by the MCSP input. Take care to properly reconnect
the CT's MTA prior to attempted start of the compressors.
5. Using a digital volt-ohmmeter, measure the resistance of the transformer(s) by probing the appropriate pair(s) of receptacles within the
MTA. The receptacle pairs of the MTA are most easily measured by using
meter leads with pointed probes and contacting the exposed metal of the
connector through either the top or the side of the MTA. (It may be nec-
RLC-SVD03A-EN25
Current Transformer
essary to remove a cap over the top of the connector to gain access to
the connector conductors.)
6. Refer to Tab le 7 which lists the normal resistance range for each extension of current transformer. Check the measured resistance against the
value listed per transformer extension. If the resistance is within tolerance, the transformer and MTA can be considered good. Go on to step 8.
7.If the resistance reading above is out of tolerance, the problem is either
with the transformer, its wiring, or the MTA connector. First double check
the schematic to be sure you are working the proper lead pair. Then cut
the leads to the particular transformer near the MTA connector and
repeat the resistance measurement by stripping insulation from the
wire's end. Once the fault has been isolated in this manner, reconnect
leads or install a new transformer or connector.
More than one current transformer is terminated to a single MTA. When
replacing, take care to note the proper positions of the respective transformer wire terminations on the MTA for the re-termination. The current
transformers are NOT polarity or directionally sensitive. The transformer
lead wiring is #22 AWG, UL 1015 600V and the proper MTA connector
(red color code) must be used to ensure a reliable connection. If the fault
can be isolated to the current transformer or its wiring apart from the connector, the connector can be reused by cutting off the bad transformer
and splicing in a new transformer using wire nuts.
8. If the transformer/connector resistance proves accurate, recheck the
resistance with the connector held at different angles and with a light
lead pull (less than 5 lb.) to test for an intermittent condition.
9. To perform the following test, you will need to use a digital voltmeter with
a diode test function,. With the transformer MTA disconnected and the
power off to the MCSP, perform a diode test across the corresponding
pair of current transformer input pins on the MCSP (header J5). The
meter should read from 1.0 to 1.5 volts for each current transformer input.
Repeat using the opposite polarity. The same reading should result.
Extreme errors suggest a defective MCSP module. If the diode voltage
drops prove accurate, reconnect the transformers to the MCSP and
repower the unit.
10. With the CT's reconnected to the MCSP, attempt a restart of the chiller.
As the given compressor is started, and the inrush locked rotor transient
has passed, (locked rotor transient should last less than one second)
simultaneously monitor the actual compressor phase current(s) (using a
clamp-on type ammeter) and the voltage developed at the respective current transformer's termination at the MCSP (using a digital volt-meter on
a 0-20 VAC scale). Refer to Table 8 for the compressor phase current to
output voltage relationship for each extension current transformer. Using
Tab l e 8 , look up to current that corresponds to the output voltage read by
the voltmeter and compare to ammeter reading. Assuming relatively
accurate meters, the values should agree to within 5%.
11. If the measured current and the output voltage from the CT agree within
the tolerance specified, the CT is good. If diagnostics, overload trips, or
other problems potentially involving current sensing continue to occur
26RLC-SVD03A-EN
Current Transformer
with all phase currents to the compressors verified to be within their normal range, then the problem is either with the CT selection, MCSP Compressor Overload Dip Switch Setting, or the MCSP's current input, analog
to digital (A/D), or dip switch input circuitry. Since the first two items
were verified in Step 2 using Tabl e 5, that leaves only the MCSP circuitry
as an issue. It is advisable to replace the MCSP module at this point.
However if verification of the MCSP Current sensing operation is desired,
go to step 12 below.
12. There are two ways that the MCSP's current sensing can be checked.
Both methods use the CLD display of the %RLA from each MCSP (Compressor Report) for indication of the sensed current. The first is straightforward equation and assumes that the proper Compressor Overload dip
switch setting and current transformer have been selected:
Measured Compr. amps of max. phase
%RLA =
To check the displayed % RLA as a function of the output voltage from the
current transformers (as connected at the MCSP), Tables 8 and 9 are utilized.
In Tab l e 8 look up (or interpolate) the “% of CT rating” corresponding to the
maximum of the three CT Input Voltages (VAC rms) as read at the MCSP. (The
table is necessary because the voltage developed at the MCSP is not linear
with the CT's secondary current). Next, check the Compressor Current
Overload setting of switch SW2 on the MCSP and find the corresponding
“SOFTWARE GAIN” in Tabl e 9 . The % RLA displayed by the CPM should be:
The preceding equations should only be applied during steady state current
draws (after transition). Inrush transient currents and associated CT output
voltages can be expected to be from 3 to 6 times the steady state values, and
the displayed value only reads up to 255% RLA. The accuracy of the
displayed value should be within ± 5% of that predicted using the Input
voltage. However, the end to end accuracy of the displayed value compared
to the actual %RLA max. phase current is ± 3.3% over the range of 50 to
150% of CT rating.
13. If no phase currents are measured with the amprobe on any or all of the
legs to a given compressor immediately following the attempted staging
of that compressor by the MCSP, the problem lies either with the
contactor, motor circuit or the MCSP relay outputs. Refer to MCSP
Checkout Procedure in Compressor Module (MCSP) (1U4 AND 1U5) on
page 72.
RLC-SVD03A-EN27
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.