Trane RTHD User Manual

Series R™ Helical Rotary Liquid Chillers
Model RTHD 175-450 Tons (60 Hz) 125-450 Tons (50 Hz)
Built for Industrial and Commercial Applications
June 2006
Introduction
To meet a wide range of applications in the medium-tonnage, water-cooled market, Trane is proud to introduce the model RTHD helical rotary liquid chiller. The introduction of this next-generation chiller an exciting step forward in application versatility, ease of installation, control precision, reliability, energy­efficiency, and operational cost-effectiveness. The new RTHD chiller is designed to deliver proven Series R performance, plus all the benefits of an advanced heat transfer design and a low­speed, direct-drive compressor.
Important Design Advances and New Features
Major design advances include:
• Higher full-load energy efficiency reduces both operating and life-cycle costs.
• CH530 controls enable:
- scrolling access to inputs and operating
information via the LCD touch-screen display;
- freedom from interoperability
concerns with LonMark communications;
- job-specific communication options
that allow greater reporting flexibility.
• Improved startup temperature capabilities and reduced sensitivity to condenser water temperatures alleviate the most common startup concerns.
• Removed Liquid Vapor Separator, providing lighter unit weight and simplified refrigerant piping, for less expensive handling, separation, and installation.
The industrial-grade design of the Series R helical rotary chiller is ideal for both industrial and commercial markets, in applications such as office buildings, hospitals, schools, retail buildings, and industrial facilities. The linear unloading compressor, wide operating temperature range, advanced controls, electronic expansion valve, short anti-recycle timers, and industry-leading efficiencies mean that this latest Trane Series R chiller is the perfect choice for tight temperature control in almost any application temperatures, and under widely varying loads.
RLC-PRC020-EN© 2004 American Standard Inc. All rights reserved.
Contents
Introduction
Features and Benefits
Options
Controls
Application Considerations
Selection Procedure
Model Nomenclature
General Data
Electrical Data and Connections
Dimensions and Weights
Mechanical Specifications
Conversion Table
2
4
6
8
10
12
14
16
19
22
29
30
RLC-PRC020-EN
3
Features and Benefits
Application Versatility and High Performance
• Screw compressor technology and the electronic expansion valve provide reliable performance in an expanded range of operating temperatures.
• Tight water temperature control extends to operation of multiple chillers in parallel or series configurations, offering further system design flexibility for maximum efficiency.
• Advanced design enables chilled water temperature control to +/- 0.5°F (.28°C) for flow changes up to 10 percent per minute, plus handling of flow changes up to 30 percent per minute for comfort cooling.
• Two-minute stop-to-start and five-minute start-to-start anti-recycle timer allows tight chilled water temperature control in constant or transient low-load applications.
• LonMark communications capability provides excellent, trouble-free interoperability.
Applications in this catalog specifically excluded from the ARI certification program are:
• Low temperature applications, including ice storage
• Glycol
• 50Hz units below 200 nominal tons
• Generic Building Automation System points are available for easy access to operational information.
• Extensive information on professional design selection and layout is available in a simple, highly readable electronic format.
• Standard model RTHD configurations are in stock and available for immediate delivery, and Trane offers the fastest ship cycles in the industry for built-to­order units.
Industrial / Low Temperature Process Cooling – Excellent operating temperature range and precise control capabilities enable tight control with single chiller or series configuration.
Ice/Thermal Storage – Specifiers and operators benefit from dual setpoint control and industry-leading temperature, efficiency, and control capabilities, plus outstanding support through partnership with Calmac, a strong Trane partner providing proven installation examples, templates, and references that minimize design time and energy costs.
Heat Recovery – Maximum condenser temperature exceeds those of previous technologies, providing hot water and tight control that minimizes operating costs for the chilled water plant and boiler/hot water heater, and consistent dehumidification.
Simple, Economical Installation
• Compact size makes the model RTHD well suited for the retrofit and replacement market.
• All units fit through standard double­width doors.
• Bolt-together construction makes for fast, easy unit disassembly.
• Small RTHD footprint saves valuable equipment room space and alleviates access concerns for most retrofit jobs.
• Lightweight design simplifies rigging requirements, further reducing installation time requirements and costs.
• Full factory refrigerant or nitrogen and oil charges reduce required field labor, materials, and installation cost.
• Only evaporator and condenser water piping is required; no starter water cooling (with its associated safety concerns) or field piping is necessary.
• Oil cooler and purge system connections have been eliminated.
• Simple power connection simplifies overall installation.
• Standard unit-mounted starter for Wye-Delta and Solid State eliminates additional jobsite installation considerations and labor requirements.
• Trane has conducted extensive factory testing, and also offers options for in­person and/or documented system performance verification.
• CH530 controls easily interface with Tracer Summit systems through single twisted-pair wire.
building automation
Pueblo
Business Unit
RLC-PRC020-EN4
Features and Benefits
State-of-the-Art, Precision Control
• Microprocessor-based CH530 controls monitor and maintain optimal operation of the chiller and its associated sensors, actuators, relays, and switches, all of which are factory-assembled and extensively tested.
• Easy interface with computers hosting Tracer Summit energy management systems allows the operator to efficiently optimize comfort system performance and minimize operating costs.
• PID (proportional integral derivative) control strategy ensures stable, efficient chilled water temperature control, maintaining +/- 1°F (0.56°C) control by proactively reacting to instantaneous load changes of up to 50 percent.
• Adaptive Control chiller operation under adverse conditions, when many other chillers might simply shut down.
• Easy-to-use operator interface displays all operating and safety messages, with complete diagnostics information, on a highly readable panel with a scrolling touch-screen display.
• The RTHD features a complete range of chiller safety controls.
• Over 120 diagnostic and operating points are available, with standard displays including chiller current draw, condenser pressure, and evaporator pressure.
Reliability and Ease of Maintenance
• Direct drive, low-speed compressor – a simple design with only three moving parts – provides maximum efficiency, high reliability, and low maintenance requirements.
• Electronic expansion valve, with fewer moving parts than alternative valve designs, offers highly reliable operation.
• Suction gas-cooled motor stays uniformly cool at lower temperatures for longer motor life.
building automation/
attempts to maintain
• The Trane helical rotary compressor is a proven design resulting from years of research and thousands of test hours, including extensive testing under extraordinarily severe operating conditions.
• Trane is the world’s largest manufacturer of large helical rotary compressors, with tens of thousands of commercial and industrial installations worldwide demonstrating a reliability rate of greater than 99 percent in the first year of operation.
Operating and Life Cycle Cost-Effectiveness
• Electronic expansion valve enables exceptionally tight temperature control and extremely low superheat, resulting in more efficient full-load and part-load operation than previously available.
• Precise compressor rotor tip clearance ensures optimal efficiency.
• Condenser and evaporator tubes use the latest heat transfer technology for increased efficiency.
• The RTHD includes standard electrical demand limiting.
• Chilled water reset based on return water temperature is standard.
• High compressor lift capabilities and tight chilled water temperature control allow highly efficient system design with minimal operational concerns.
Design capabilities include:
• variable primary flow;
• series chiller arrangements for evaporator and/or condenser;
• low evaporator and condenser flow.
RLC-PRC020-EN
5
Options
Insulation
All low temperature surfaces are covered with factory installed 3/4 inch (19.05 mm) Armaflex II or equal (k=0.28) insulation, including the evaporator and water boxes, suction line, and motor housing. 3/8" foam insulation is used on the liquid level sensor and gas pump assembly, including piping.
Low-Temperature Evaporator
Addition of an oil cooler to the oil circuit enables evaporator operation down to minimum leaving water temperature of 10°F (-12.2°C).
High-Temperature Condenser
Addition of an oil cooler to the oil circuit enables condenser operation up to maximum leaving water temperature of 114°F (45.6°C).
Smooth-Bore Condenser Tubes
Smooth-bore copper or premium cupro­nickel condenser tubes, 3/4" (19.05 mm) in diameter with .035" (0.889 mm) wall thickness, are available for high fouling water applications.
Refrigerant Isolation Valves
Factory-installed condenser inlet and outlet refrigerant valves allow isolation of the full refrigerant charge in the condenser while servicing the chiller.
Marine Water Boxes
Addition of marine water boxes for the condenser allows tube cleaning without water pipe interference.
300 psig Evaporator and Condenser Water Boxes
Water boxes are designed for 300 psig maximum waterside working pressure, and grooved pipe water connections are provided for ease of installation.
2-Way Condenser Water Regulating Valve
For water regulation, a field-installed, 2-way butterfly-type (lug-style) valve, with integral electrical operator and factory-mounted valve actuator, is available. The single-phase, reversible motor can be factory-wired for 115 VAC, 60 Hz or 220 VAC, 50 Hz; the 2-way valve is field-wired and controlled by the chiller regulating valve control output; valves are available in 6" and 8" (152.4 and
203.2 mm) sizes.
Nitrogen Charge
Unit is shipped with a nitrogen holding charge in lieu of refrigerant.
Seal Kit for Reassembly
Ideal for situations when the bolt-together construction of the RTHD will be separated for installation, this seal kit provides replacement gaskets and rings for reassembly.
Solid State Starter
Solid State Starter is unit-mounted with a NEMA 1 gasketed enclosure. To extend starter life, contactors bypass current from the silicon control rectifiers (SCRs) after startup.
Under/Over-Voltage Protection
Unit receives protection against variations in voltage (current lag and spike protection is standard).
Performance and Witness Tests
ARI-certified RTHD Performance and Witness Tests are available, based on requested operating points, to certify chiller performance before delivery.
Main Power Disconnect Options:
Non-fused Disconnect
A UL-approved non-fused molded case disconnect switch, factory pre-wired with terminal block power connections and equipped with a lockable external operator handle, is available to disconnect the chiller from main power.
Standard Interrupting Capacity Circuit Breaker
A UL-approved standard interrupting molded case capacity circuit breaker, factory pre-wired with terminal block power connections and equipped with a lockable external operator handle, is available to disconnect the chiller from main power.
High Interrupting Capacity Circuit Breaker
A UL-approved high interrupting molded case capacity circuit breaker, factory pre­wired with terminal block power connections and equipped with a lockable external operator handle, is available to disconnect the chiller from main power.
Ground Fault Circuit Breaker
A UL-approved standard interrupting molded case capacity circuit breaker with ground fault interrupting capability, factory pre-wired with terminal block connections and equipped with a lockable external operator handle, is available to disconnect the chiller from main power.
RLC-PRC020-EN6
Options
Control Options:
Tracer Summit Communications
Link to factory-installed, tested communication board, via single twisted­pair wiring, adds Tracer Summit communications to the system.
LonTalk LCI-C Interface
LonTalk (LCI-C) communications capabilities are available, with communication link via single twisted-pair wiring to factory-installed, tested communication board.
External Chilled Water Setpoint
External Chilled Water Setpoint is communicated to a factory-installed, tested communication board through a 2­10Vdc or 4-20mA signal.
External Current Limiting
External Current Limit Setpoint is communicated to a factory-installed, tested communication board through a 2­10Vdc or 4-20mA signal.
External Base Loading
External Base Loading is communicated to a factory-installed and tested communication board through a 2-10Vdc or 4-20mA signal.
Ice Making Control
Controls and safeties allow operation with brine temperatures down to 20°F (-6.7°C) , and dual setpoints enable both ice making and daytime comfort cooling.
Programmable Relays
Default-set, factory-installed, programmable relays allow the operator to select four relay outputs from a list of eight. Available relays are: Alarm­Latching, Alarm-Auto Reset, General Alarm, Warning, Chiller Limit Mode, Compressor Running, Head Pressure Relief Request, and Tracer Control.
Chilled Water Reset – Outdoor Air Temperature
Controls, sensors, and safeties allow reset of chilled water temperature, based on temperature signal, during periods of low outdoor air temperature (chilled water reset based on return chilled water temperature is standard).
Condenser-Regulating Valve Control
Chiller applies a Proportional Integrative Control (PID) algorithm to control water regulating valve via 0-10Vdc signal.
Percent of Full Run Load Amps Output
Control system indicates the active chiller percent of full run load amps, based on a 0-10Vdc signal.
Condenser Pressure Output
Control system indicates chiller differential pressure or condenser pressure, based on a 0-10Vdc signal.
Refrigerant Monitor Input
Control system indicates refrigerant monitor status of 0-100 or 0-1000 ppm (user selectable), based on a 2-10Vdc / 4-20 mA signal.
RLC-PRC020-EN
7
Controls
LCD Touch-Screen Display with Multi-Language Support
The standard DynaView display provided with the CH530 control panel features an LCD touch-screen, allowing access to all operational inputs and outputs. This display supports eleven languages: English, Chinese, Dutch, French, German, Italian, Japanese, Korean, Portugese, Spanish and Thai.
Additional Display Features Include:
• LCD touch-screen with LED backlighting, for scrolling access to input and output operating information
• Weather-proof enclosure for reliable operation in non-standard indoor environments
• Spin value buttons to allow continuously variable setpoints when applicable
• Radio and action buttons for easy, one­time actions and settings
• Single-screen, folder/tab-style display of all available information on individual components (evaporator, condenser, compressor, etc.)
• Automatic and immediate stop capabilities for standard or immediate manual shutdown
• Manual override indication
• Password entry/lockout system to enable or disable display
• Fast, easy access to available chiller data in tabbed format, including: — Modes of operation, including normal
cooling and icemaking — Water temperatures and setpoints — Loading and limiting status and
setpoints — Average line current — Outdoor air temperature — Start/stop differential timers — Auto/Manual mode for EXV, slide
valve, and head pressure control — Pump status and override — Chilled water reset, start point, ratio,
and outdoor start point — External setpoints, including:
- chilled water
- current limit
- ice building
- base loading
— Display specifics, including:
- date
- format
- time
- display lockout
- display units
- language setting
- Reports, listed on a single tabbed screen for easy access, including:
• ASHRAE, containing all guideline 3
report information
• Evaporator
• Condenser
• Compressor
— Evaporator, condenser, and
compressor reports containing all operational information on individual components, including:
- Water and air temperatures
- Refrigerant levels, temperatures, and approach
- Oil pressure
- Flow switch status
- EXV position
- Head pressure control command
- Compressor starts and run-time
- Line phase percent RLA, amps, and volts
— Alarm and diagnostic information,
including:
- Flashing alarms with touch-screen button for immediate address of alarm condition
- Scrollable list of last ten active diagnostics
- Specific information on applicable diagnostic from list of over one­hundred
- Automatic or manual resetting diagnostic types
RLC-PRC020-EN8
Controls
Trane Chiller Plant Automation
Trane’s depth of experience in chillers and controls makes us a well-qualified choice for automation of chiller plants using air­cooled Series R control capabilities of the Trane Tracer Summit unequaled in the industry. Our chiller plant automation software is fully pre­engineered and tested. It is a standard software application, not custom programming which can prove to be difficult to support, maintain, and modify.
Energy Efficiency
Trane chiller plant automation intelligently sequences starting of chillers to optimize the overall chiller plant energy efficiency. Individual chillers are designated to operate as base, peak, or swing based on capacity and efficiency. Sophisticated software automatically determines which chiller to run in response to current conditions. The software also automatically rotates individual chiller operation to equalize runtime and wear between chillers.
Trane chiller plant automation enables unique energy-saving strategies. An example is controlling pumps, and chillers from the perspective of overall system energy consumption. The software intelligently evaluates and selects the lowest energy consumption alternative.
Regulatory Compliance Documentation
Comprehensive documentation of refrigerant management practices is now a fact of life. Trane chiller plant automation generates the reports mandated in ASHRAE Guideline 3.
Keeping Operators Informed
A crucial part of efficiently running a chiller plant is assuring that the operations staff is instantly aware of what is happening in the plant. Graphics showing schematics of chillers, piping, pumps, and towers clearly depict the chiller plant system, enabling building operators to easily monitor overall conditions. Status screens display both current conditions and upcoming automated control actions to add or subtract chiller capacity. Series R other chillers can be monitored and controlled from a remote location.
®
chillers®. The chiller plant
®
building automation system are
and
Tracer Summit features standard report templates listing key operating data for troubleshooting and verifying performance. Reports for each type of Trane chiller and three and six-chiller systems are also standard. Detailed reports showing chiller runtimes aid in planning for preventative maintenance.
Swift Emergency Response
We understand the importance of maintaining chilled water production while protecting your chillers from costly damage. If no water flow is detected to a chiller’s piping, the start sequence is aborted to protect the chiller. The next chiller in the sequence is immediately started to maintain cooling.
In the event of a problem, the operator receives an alarm notification and diagnostic message to aid in quick and accurate troubleshooting. A snapshot report showing system status just prior to an emergency shutdown helps operators determine the cause. If emergency conditions justify an immediate manual shutdown, the operator can override the automatic control.
Integrated Comfort
Capabilities
When integrated with a Tracer Summit building management system performing building control, Trane chiller plant automation coordinates with Tracer Summit applications to optimize the total building operation. With this system option, the full breadth of Trane’s HVAC and controls experience are applied to offer solutions to many facility issues. If your project calls for an interface to other systems, Tracer Summit can share data via BACnet
, the ASHRAE open systems
protocol.
LonTalk Chiller Controls
LonTalk is a communications protocol developed by the Echelon Corporation. The LonMark association develops control profiles using the LonTalk communication protocol. LonTalk is a unit level communications protocol, unlike BACNet used at the system level.
LonTalk Communications Interface for Chillers (LCI-C) provides a generic automation system with the LonMark chiller profile inputs/outputs. In addition to the standard points, Trane provides other commonly used network output variables for greater interoperability with any automation system. The complete reference list of Trane LonTalk points is available on the LonMark website. Trane controls or another vendor’s system can use the predefined list of points with ease to give the operator a complete picture of how the system is running.
Hardwire Points
Remote devices wired from the control panel are another reliable method of providing auxiliary control to a building automation system. Inputs and outputs can be communicated via a typical 4-20 mA electrical signal (or an equivalent Vdc signal of 0-10 or 2-10) or by utilizing contact closures.
• External Chilled Water Setpoint
• External Current Limit Setpoint
• Condenser-Regulating Valve Control
• Percent of Full Run Load Amps Output
• Condenser Pressure Output
• Refrigerant Monitor Input
• Programmable Relays Allows the selection of 4 relay outputs from a list of eight different default settings: Alarm-Latching, Alarm-Auto Reset, General Alarm, Warning, Chiller Limit Mode, Compressor Running, Head Pressure Relief Request, and Tracer Control. These contact closures may be used to trigger jobsite supplied audible or visual alarms
• Ice Making Control Provides an interface with ice making control system and safeties, enabling both ice making and daytime comfort cooling
• Chilled Water Temperature Reset Supplies controls, sensors and safeties to reset the chilled water temperature setpoint based upon return water temperature (standard) or outdoor air temperature (optional)
RLC-PRC020-EN
9
Application Considerations
Condenser Water Temperatures
Reduced sensitivity to condenser water startup temperatures is one major enhancement in the newest-generation water-cooled Series R chiller. With the model RTHD chiller, a condenser water control method is necessary only if the unit starts with entering water temperatures below 55°F (12.8°C), or between 45°F (7.2°C) and 55°F (12.8°C), when a temperature increase of 1°F (0.56°C) per minute to 55°F (12.8°) is not possible.
When the application requires startup temperatures below the prescribed minimums, a variety of options are available. To control a 2-way or 3-way valve, Trane offers a Condenser Regulating Valve Control option for the CH530 controls. This option enables the CH530 controls to send a signal for opening and closing the valve as necessary to maintain chiller differential pressure. The 2-way valves are available as a ship-with option. Tower bypass is also a valid control method if the chiller temperature requirements can be maintained.
Trane Series R chillers start and operate successfully and reliably over a range of load conditions with controlled entering condenser water temperature. Reducing the condenser water temperature is an effective method of lowering chiller
power input required, but the ideal temperature for optimizing total system power consumption will depend on the overall system dynamics. From a system perspective, some improvements in chiller efficiency may be offset by the increased tower fan and pumping costs required to achieve the lower tower temperatures.
Contact your local Trane systems solution provider for more information on optimizing system performance.
The minimum acceptable refrigerant pressure differential between condenser and evaporator is 23 psid. The chiller control system will attempt to obtain and maintain this differential at startup, but for continuous operation a design should maintain a 25°F (13.9°C) differential from evaporator leaving water temperature to condenser leaving water temperature.
Variable Evaporator Flow and Short Evaporator Water Loops
Variable evaporator flow is an energy­saving design strategy which has quickly gained acceptance as advances in chiller and controls technology have made it possible. With its linear unloading compressor design and advanced CH530 controls, the RTHD has excellent capability to maintain leaving water temperature control within +/-0.5°F (0.28°C) , even for systems with variable evaporator flow and small chilled water volumes.
Some basic rules should be followed whenever using these system design and operational savings methods with the RTHD. The proper location of the chilled water temperature control sensor is in the supply (outlet) water. This location allows the building to act as a buffer, and it assures a slowly changing return water temperature. If there is insufficient water volume in the system to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation and excessive compressor cycling. To ensure consistent operation and tight temperature control, the chilled water loop should be at least two minutes. If this recommendation cannot be followed, and tight leaving water temperature control is necessary, a storage tank or larger header pipe should be installed to increase the volume of water in the system.
For variable primary flow applications, the rate of chilled water flow change should not exceed 10 percent of design per minute to maintain +/-0.5°F (0.28°C) leaving evaporator temperature control. For applications in which system energy savings is most important and tight temperature control is classified as +/-2°F (1.1°C), up to 30 percent changes in flow per minute are possible. Flow rates should be maintained between the minimum and maximum allowed for any particular chiller configuration.
RLC-PRC020-EN10
Application Considerations
Series Chiller Arrangements
Another energy-saving strategy is to design the system around chillers arranged in series, on the evaporator, condenser, or both. The actual savings possible with such strategies depends on the application dynamics and should be researched by consulting your Trane Systems Solutions Representative and applying the Trane System Analyzer program. It is possible to operate a pair of chillers more efficiently in a series chiller arrangement than in a parallel arrangement. It is also possible to achieve higher entering-to-leaving chiller differentials, which may, in turn, provide the opportunity for lower chilled water design temperature, lower design flow, and resulting installation and operational cost savings. The Trane screw compressor also has excellent capabilities for “lift,” which affords an opportunity for savings on the evaporator and condenser water loops.
Like series arrangements on the evaporator, series arrangements on the condenser may enable savings. This approach may allow reductions in pump and tower installation and operating costs. Maximizing system efficiency requires that the designer balance performance considerations for all system components; the best approach may or may not involve multiple chillers, or series arrangement of the evaporators and/or condensers.
design integrity with installation and operating cost considerations can also be obtained by consulting a Trane representative and applying the Trane System Analyzer program.
Water Treatment
The use of untreated or improperly treated water in chillers may result in scaling, erosion, corrosion, and algae or slime buildup. It is recommended that the services of a qualified water treatment specialist be engaged to determine what treatment, if any, is advisable. Trane assumes no responsibility for the results of using untreated or improperly treated water.
This ideal balance of
Water Pumps
Where noise limitation and vibration-free operation are important, Trane strongly encourages the use of 1750-rpm (60 Hz), 1450-rpm (50 Hz) pumps. Specifying or using 3600-rpm (60 Hz), 3000-rpm (50 Hz) condenser water and chilled water pumps must be avoided, because such pumps may operate with objectionable levels of noise and vibration. In addition, a low frequency beat may occur due to the slight difference in operating rpm between 3600-rpm (60 Hz), 3000-rpm (50 Hz) water pumps and Series R chiller motors. pump must not be used to stop the chiller.
Acoustic Considerations
For chiller sound ratings, installation tips, and considerations on chiller location, pipe isolation, etc., refer to
Water-Cooled Series R Chillers Sound Ratings and Installation Guide
information provided in this bulletin, contact a certified sound consultant to aid in proper mechanical room design and treatment.
Important Note: The chilled water
the Trane
. Using the
Figure 1. Typical series chiller arrangement
RLC-PRC020-EN
11
Selection Procedure
Trane Series R chiller performance is rated in accordance with the ARI Standard 550/590-2003 Certification Program. Chiller selection assistance and performance information can be obtained by using the Series R chiller selection program, available through local Trane sales offices.
Performance
The computerized Series R chiller selection program provides performance data for each possible chiller selection at both full-load and part-load design points, as required.
It should be noted that changing the number of water passes or the water flow rates will generally alter the performance of a particular chiller. To attain maximum benefit from the wide range of chiller models and options available, designers are encouraged to first develop performance specifications and then use the chiller selection program to optimize all selections. This will help ensure selection of the compressor­evaporator-condenser combination that most closely meets the job requirements. To optimize system performance, all selections should also be balanced with other system components.
Fouling Factors
ARI Standard 550 includes a definition of clean tube fouling. The recommended standard fouling adjustments are 0.0001 hr-sq ft-deg F/Btu (0.0176 sq m-deg C/kW) for the evaporator and 0.00025 hr-sq ft deg F/Btu (0.044 sq m-deg C/kW) for the condenser, from an increment of 0.0000 “clean.” Chiller specifications should be developed using the most current standard fouling factors.
Part Load Performance
Actual air-conditioning system loads are frequently less than full-load design conditions. Depending on the number of chillers on the job and the load profile, chillers may operate at full load a small percentage of the time. With their excellent part-load performance characteristics and highly energy-efficient operation, Series R chillers can provide significant operating savings at these part-load conditions.
System Considerations
Part-load chiller operation is frequently associated with reduced condenser water temperatures. However, rather than focusing only on the chiller, it is important to balance these temperatures to achieve the most efficient system operation possible. At part-load operation, the heat rejected to the cooling tower is less than at full-load operation.
Part-load chiller operation is also typically associated with reduced outside wet bulb temperatures, resulting in improved cooling tower performance. The net result of reduced heat rejection and lower wet bulb temperatures can be cooler condenser water entering the chiller, ultimately improving unit performance. However, this does not improve pump or tower efficiency. To achieve the most efficient system operation possible, it is best to minimize the total power draw of the chiller, tower, and pumps, which may not mean limiting the condenser water temperature to what the tower can provide. To determine specific unit and system part-load performance for chiller selection purposes, use the Series R chiller computer selection program or contact the local Trane sales office.
RLC-PRC020-EN12
Selection Procedure
Unit Performance with Fluid Media Other Than Water
Series R chillers can be provided with a wide variety of fluid media other than water, including ethylene glycol and propylene glycol— in the evaporator, condenser or both. Chillers using media other than water are excluded from the ARI 550/590-2003 Certification Program, but are rated in accordance with ARI Standard 550/590-2003. Trane factory performance tests are only performed with water as the cooling and heat­rejection media. When considering selection of media other than water, contact the local Trane sales office for chiller selections and factory performance testing information.
Fluid media other than water lowers the heat transfer coefficient, and therefore reduces chiller performance. In general, it is good practice to hold the percent glycol added to within the minimum allowed by the Trane selection program, based on either (a) unit operating temperatures, or (b) the operating temperatures the evaporator or condenser water will experience under its full range of conditions. Adding more glycol than required for the specific application is equivalent to selecting a less efficient chiller. Lower-viscosity glycols such as ethylene will have less adverse impact on chiller performance than higher­viscosity glycols such as propylene.
Evaporator and Condenser Pressure Drop
Pressure drop data is determined by the Series R chiller computer selection program available through local Trane sales offices.
Dimensional Drawings
Dimensional drawings provided for selection purposes illustrate overall measurements of the unit. The recommended service clearances are those required to easily service the Series R chiller.
All catalog dimensional drawings are subject to change, and current submittal drawings should be referenced for more detailed dimensional information. Dimensional drawings are also available from the selection program. Contact the local Trane sales office for submittal information.
Electrical Data Tables
Compressor motor electrical data is provided in the data section for each compressor size. Rated load amperes (RLA), locked rotor wye amperes (LRA) and expected inrush for the Wye-delta and Solid State Starter configurations are shown.
Although the terms “LRA” and “expected inrush” are often used interchangeably, the distinction applied here is that LRA is the rated inrush for the motor, but expected inrush is that allowed by the starter, based on the specific configuration.
Selecting starters in the Wye-delta or Solid State configuration lowers expected inrush vs. the Delta (or “across­the-line”) configuration. A Solid State Starter configuration lowers the expected inrush by approximately 50 percent, while Wye-Delta lowers it by approximately 66 percent.
The RLA is based on the motor’s performance when reaching full rated horsepower. The kW rating of the motor will equal or exceed the kW requirement indicated by the Series R computer selection program at design conditions. If motor kW draw at design conditions is less than the kW rating of the motor, the RLA at design conditions is determined by multiplying the motor RLA (at the desired voltage) by this ratio: design kW/ motor kW rating. This calculation is performed within the Series R chiller computer selection program, making RLA available as part of the design predictions. Predicted values include power factor variation from point to point.
A voltage utilization range is tabulated for each voltage listed. Series R chillers are designed to operate satisfactorily over a utilization range of ±10 percent of the standard design voltages: (a) 200 V, 230 V, 380 V, 460 V, and 575 V for 60 Hertz, 3­phase, and (b) 380 V, 400 V, 415 V for 50 Hertz, 3-phase.
RLC-PRC020-EN
13
Model Nomenclature
RTH D U D 2 F 0 A0 U A G 3 A 4 L A L G 3 F 2 L A L
1,2,34 5 6 7 8 9 10,1112131415 16 17 1819 2021 222324 252627
Digits 01, 02, 03 – Series R
RTH = Series R
Digit 04 – Dev Sequence
D = 4th Major Development
Digit 05 – Design Control
U = WCBU
Digit 06 – Compressor Frame
B = B Compressor C = C Compressor D = D Compressor E = E Compressor
Digit 07 – Compressor Capacity
1 = Smaller Capacity for Frame 2 = Larger Capacity for Frame 3 = 50Hz Capacity
Digit 08 – Unit Power Supply
A = 200V/60Hz/3Ph power C = 230V/60Hz/3Ph power D = 380V/60Hz/3Ph power R = 380V/50Hz/3Ph power T = 400V/50Hz/3Ph power U = 415V/50Hz/3Ph power F = 460V/60Hz/3Ph power H = 575V/60Hz/3Ph power
Digit 09 – Specials
X = No specials C = All specials denoted by digits elsewhere S = Uncategorized special not denoted by
other digits
Digits 10, 11 – Design Sequence
** = First Design, etc. increment when parts
are affected for service purposes
Digit 12 – Agency Listing
X = No agency listing U = C/UL
Digit 13 – Pressure Vessel Code
A = ASME L = Chinese Pressure Vessel Code
Digit 14 – Evaporator Frame
B = B Frame C = C Frame D = D Frame E = E Frame F = F Frame G = G Frame
Digit 15 – Evaporator Capacity
1 = Tube count #1 2 = Tube count #2 3 = Tube count #3 4 = Tube count #4 5 = Tube count #5 6 = Tube count #6
Digit 16 – Evaporator Tube Type
A = Enhanced Fin Copper
Digit 18 – Evaporator Water Connection
L = Left Hand Evaporator Connection R = Right Hand Evaporator Connection
Digit 19 – Evaporator Connection Type
A = Standard Grooved Pipe
Digit 20 – Evaporator Waterside Pressure
L = 150 psi H = 300 psi
Digit 21 – Condenser
B = B Frame D = D Frame E = E Frame F = F Frame G = G Frame
Digit 22 – Condenser Capacity
1 = Tube count #1 2 = Tube count #2 3 = Tube count #3 4 = Tube count #4 5 = Tube count #5
Digit 23 – Condenser Tube Type
A = Enhanced Fin Copper B = Smooth Bore Copper C = Smooth Bore 90/10 CU/NI
Digit 24 – Condenser Passes
2 = 2 Pass
Digit 25 – Condenser Water Connection
L = Left Hand Connection R = Right Hand Connection
Digit 17 – Evaporator Water Pass Configuration
2 = 2 pass 3 = 3 pass 4 = 4 pass
Digit 26 – Condenser Connection Type
A = Standard Grooved Pipe C = Marine
Digit 27 – Condenser Waterside Pressure
L = 150 psi H = 300 psi
RLC-PRC020-EN14
Model Nomenclature
A V X Q X E X A A B D Y 444 D A X A 4 X X X R X V X
28 2 9 30 31 32 33 34 35 36 37 38 39 40,41,42 43 44 45 46 47 48 49 50 51 52 53 5 4
Digit 28 – Condenser Leaving Water Temperature
A = Standard
Digit 29 – Refrigerant Specialties
X = No Refrigerant Isolation Valves V = With Refrigerant Isolation Valves
Digit 30 – Oil Cooler
X = Without Oil Cooler C = With Oil Cooler
Digit 31 – Thermal Insulation
X = No Insulation Q = Factory Installed Insulation
Digit 32 – Acoustic Insulation
X = No Insulation A = Standard Insulation
Digit 33 – Label and Literature Language
C = Spanish E = English F = French
Digit 34 – Safety Devices
X = Standard
Digit 35 – Factory Charge
A = Factory Refrigerant Charge (134a) B = Factory Nitrogen Charge
Digit 36 – Shipping Package
A = No Skid (standard) B = Shrink Wrap C = Skid D = Skid + Shrink Wrap J = Special
Digit 37 – Flow Switch
X = No Flow Switch A = Evaporator (NEMA 1) B = Evaporator and Condenser (NEMA 1) C = Evaporator (NEMA 4) D = Evaporator and Condenser (NEMA 4)
Digit 38 – Factory Test
X = Standard Test C = Witness Test D = Performance Test
Digit 39 – Starter Type
Y = Wye Delta Closed Transition Starter A = Solid State Starter
Digits 40, 41, 42 – Design RLA (for starter)
*** = Selection Assigned
Digit 43 – Power Line Connection Type
A = Terminal Blocks B = Mechanical Disconnect Switch D = Circuit Breaker F = High Interrupt Circuit Breaker H = Ground Fault Circuit Breaker J = Ground Fault High Interrupt Circuit
Breaker
Digit 44 – Enclosure Type
A = NEMA 1
Digit 45 – Under/Over Voltage Protection
X = None U = With Under/Over Voltage Protection
Digit 46 – Operator Interface Language
A = Dyna-View/English B = Dyna-View/French C = Dyna-View/Italian D = Dyna-View/Spanish E = Dyna-View/German F = Dyna-View/Dutch G = Dyna-View/Traditional Chinese H = Dyna-View/Simple Chinese J = Dyna-View/Japanese K = Dyna-View/Portuguese L = Dyna-View/Korean M = Dyna-View/Thai
Digit 47 – Digital Communication Interface
X = None 4 = Tracer Interface 5 = LCI-C (LonTalk)
Digit 48 – External Chilled Water and Current Limit Setpoint
X = None 4 = 4-20mA input 2 = 2-10Vdc
Digit 49 – External Base Loading
X = None 4 = 4-20mA input 2 = 2-10Vdc input
Digit 50 – Icemaking
X = None A = Icemaking with Relay B = Icemaking without Relay
Digit 51 – Programmable Relays
X = None R = With
Digit 52 – Chilled Water Reset
X = Chilled Water Reset – Return Water T = Chilled Water Reset – Outdoor Air
Temperature
Digit 53 – Control Outputs
X = None V = Condenser Regulating Valve Control &
Percent RLA
P = Condenser Pressure (% HPC) & Percent
RLA
D = Chiller Differential Pressure & Percent
RLA
Digit 54 – Refrigerant Monitor Input
X = None A = 100 ppm / 4-20mA B = 1000 ppm / 4-20mA C = 100 ppm / 2-10Vdc D = 1000 ppm / 2-10Vdc
RLC-PRC020-EN
15
General Data
Nominal Data
Nominal Compressor B1 B2 C1 C2 D1 D2 D3 E3 Tonnage (60 Hz) 175-200 200-225 225-275 275-325 325-400 375-450 N/A N/A Tonnage (50 Hz) 125-150 150-175 175-225 225-275 275-325 300-350 325-375 375-450
Notes:
1. Chiller selections can be optimized through the use of the ARI-Certified Series R selection program and by contacting your local Trane sales office.
General Data
Compressor Evaporator Condenser Water Storage Water Storage Refrigerant Charge
Code Code Code Gallons Liters Gallons Liters Type lb kg
B1 B1 B1 41 155 28 106 HFC-134a 410 186 B1 C1 D1 55 208 31 117 HFC-134a 490 222 B2 B2 B2 45 170 29 110 HFC-134a 410 186 B2 C2 D2 58 220 34 129 HFC-134a 490 222 C1 D6 E5 45 170 29 110 HFC-134a 490 222 C1 D5 E4 52 197 32 121 HFC-134a 490 222 C1 E1 F1 82 310 60 226 HFC-134a 525 238 C2 D4 E4 52 197 32 121 HFC-134a 490 222 C2 D3 E3 78 295 47 178 HFC-134a 490 222 C2 F2 F3 107 405 61 231 HFC-134a 625 284 D1 D1 E1 69 261 44 166 HFC-134a 475 216 D1 F1 F2 102 386 57 216 HFC-134a 625 284
1
D1
2
D1
G1 G1 136 515 79 299 HFC-134a --- ---
G2 G2 144 545 91 344 HFC-134a 700 318 D2/D3 D2 E2 74 280 47 178 HFC-134a 475 216 D2/D3 F2 F3 107 405 61 231 HFC-134a 625 284
1
D2/D3 D2/D3
2
G2 G1 144 545 79 299 HFC-134a --- ---
G3 G3 159 602 97 367 HFC-134a 700 318
E3 D2 E2 74 280 47 178 HFC-134a 475 216 E3 F2 F3 107 405 61 231 HFC-134a 625 284
1
E3
2
E3
Notes:
1. 50 Hz units only.
2. 60 Hz units only.
G2 G1 144 545 79 299 HFC-134a --- ---
G3 G3 159 602 97 367 HFC-134a 700 318
Evaporator Condenser Refrigerant
RLC-PRC020-EN16
General Data
Water Flow Rates
RLC-PRC020-EN
Minimum/Maximum Evaporator Flow Rates (Gallons/Minute )
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (In.) Min Max Conn Size (In.) Min Max Conn Size (In.)
B1 253 1104 8 168 736 6 —- — - —­B2 288 1266 8 192 844 6 —- —- —­C1 320 1412 8 213 941 6 —- —- —­C2 347 1531 8 232 1022 6 —- —- —­D1 415 1812 8 275 1206 8 —- —- —­D2 450 1980 8 300 1320 8 —- —- —­D3 486 2131 8 324 1417 8 —- —- —­D4 351 1542 8 234 1028 8 —- —- —­D5 351 1542 8 234 1028 8 —- —- —­D6 293 1287 8 196 860 8 —- —- —­E1 450 1980 8 300 1320 8 —- —- —­F1 563 2478 10 376 1655 8 —- —- —-
F2 604 2667 10 404 1780 8 —- —- —­G1 —- —- —- 505 2218 10 379 1666 8 G2 —- —- —- 550 2413 10 411 1807 8 G3 —- —- —- 622 2732 10 466 2050 8
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Two Pass Three Pass Four Pass
Minimum/Maximum Evaporator Flow Rates (Liters/Second)
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (mm) Min Max Conn Size (mm) Min Max Conn Size (mm)
B1 1 6 70 200 11 46 150 — - —- — -
B2 1 8 80 200 12 53 150 — - —- — -
C1 2 0 89 200 13 59 150 — - —- — -
C2 2 2 97 200 15 65 150 — - —- — -
D1 26 114 200 17 76 200 —- —- — -
D2 28 125 200 19 83 200 — - —- — -
D3 31 134 200 20 89 200 — - —- — -
D4 22 97 200 15 65 200 — - —- — -
D5 22 97 200 15 65 200 — - —- — -
D6 18 81 200 12 54 200 — - —- — -
E1 2 8 125 200 19 83 200 — - —- — -
F1 36 156 250 2 4 104 200 —- —- — -
F2 38 168 250 2 5 112 200 — - —- — ­G1 — - — - —- 32 140 250 24 105 200 G2 — - — - —- 35 152 250 26 114 200 G3 — - — - —- 39 172 250 29 129 200
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates (Gallons/Minute)
Condenser Nominal
Code Min Max Conn Size (In.)
B1 193 850 6 B2 212 935 6 D1 193 850 6 D2 212 935 6 E1 291 1280 8 E2 316 1390 8 E3 325 1420 8 E4 245 1080 8 E5 206 910 8 F1 375 1650 8 F2 355 1560 8 F3 385 1700 8 G1 444 1960 8 G2 535 2360 8 G3 589 2600 8
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Two Pass Three Pass Four Pass
Minimum/Maximum Condenser Flow Rates (Liters/Second)
Two Pass
Condenser Nominal
Code Min Max Conn Size (mm)
B1 12 54 150 B2 13 59 150 D1 12 54 150 D2 13 59 150 E1 18 81 200 E2 20 88 200 E3 21 90 200 E4 15 68 200 E5 13 57 200 F1 24 104 200 F2 22 98 200 F3 24 107 200 G1 28 124 200 G2 34 149 200 G3 37 164 200
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Two Pass
17
General Data
Brine Flow Rates
Minimum/Maximum Evaporator Flow Rates (GPM)
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (In.) Min Max Conn Size (In.) Min Max Conn Size (In.)
B1 303 1104 8 200 736 6 —- — - —­B2 346 1266 8 233 844 6 —- —- —­C1 346 1412 8 254 941 6 —- —- —­C2 375 1531 8 276 1022 6 —- —- —­D1 498 1812 8 330 1206 8 —- —- —­D2 541 1980 8 357 1320 8 —- —- —­D3 584 2131 8 389 1417 8 —- —- —­D4 422 1542 8 281 1028 8 —- —- —­D5 422 1542 8 281 1028 8 —- —- —­D6 352 1287 8 233 860 8 —- —- —­E1 487 1980 8 357 1320 8 —- —- —­F1 676 2478 10 454 1655 8 —- —- —­F2 725 2667 10 487 1780 8 —- —- —­G1 —- —- —- 606 2218 10 454 1666 8 G2 —- —- —- 660 2413 10 492 1807 8 G3 —- —- —- 747 2732 10 557 2050 8
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Two Pass Three Pass Four Pass
Minimum/Maximum Evaporator Flow Rates (Liters/Second)
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (mm) Min Max Conn Size (mm) Min Max Conn Size (mm)
B1 19 7 0 200 13 46 150 — - —- —­B2 2 2 80 200 15 53 150 — - —- — ­C1 2 2 89 200 16 59 150 — - —- — ­C2 2 3 97 200 17 65 150 — - —- — ­D1 31 114 200 2 1 76 200 — - —- — ­D2 34 125 200 23 83 200 — - —- — ­D3 37 134 200 25 89 200 — - —- — ­D4 27 97 200 18 65 200 — - —- — ­D5 27 97 200 18 65 200 — - —- — ­D6 22 81 200 15 54 200 — - —- — ­E1 2 8 125 200 23 83 200 — - —- — ­F1 43 156 250 2 9 104 200 —- —- —­F2 46 168 250 3 1 112 200 —- —- —­G1 — - — - —- 38 140 250 29 105 200 G2 — - — - —- 42 152 250 31 114 200 G3 — - — - —- 47 172 250 35 129 200
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates (GPM)
Condenser Nominal
Code Min Max Conn Size (In.)
B1 230 850 6 B2 255 935 6 D1 230 850 6 D2 255 935 6 E1 350 1280 8 E2 380 1390 8 E3 390 1420 8 E4 295 1080 8 E5 250 910 8 F1 450 1650 8 F2 430 1560 8
F3 460 1700 8 G1 530 1960 8 G2 650 2360 8 G3 710 2600 8
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Two Pass Three Pass Four Pass
Minimum/Maximum Condenser Flow Rates (Liters/Second)
Two Pass
Condenser Nominal
Code Min Max Conn Size (mm)
B1 15 54 150 B2 16 59 150 D1 15 54 150 D2 16 59 150 E1 2 2 8 1 200 E2 2 4 8 8 200 E3 2 5 9 0 200 E4 19 6 8 200 E5 1 6 5 7 200 F1 28 104 200 F2 27 98 200
F3 29 107 200 G1 33 124 200 G2 41 149 200 G3 45 164 200
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Two Pass
RLC-PRC020-EN18
Electrical Data and Connections
Compressor Motor Electrical Data (60 Hertz)
Compressor Voltage 180/ 208/ 342/ 414/ 516/
Code Utilization Range 220 254 418 506 633
B1, B2 RLA @ Max kW 557 484 291 241 193
C1, C2 RLA @ Max kW 812 698 421 349 279
D1, D2 RLA @ Max kW 888 888 549 455 367
Notes:
1. See Selection Procedure Section for details.
2. The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3. Electrical component sizing should be based on actual jobsite operating conditions. This factor can be obtained through the use of the Series R chiller selection program available through local Trane sales offices.
Nominal Voltage 200 230 380 460 575
Max kW 174 174 174 174 174
LRAY 970 818 488 400 329 LRAD 3103 2617 1561 1280 1053
Max kW 249 249 249 249 249
LRAY 1173 936 558 469 375 LRAD 3634 2901 1727 1453 1162
Max kW 329 329 329 329 329
LRAY 1690 1532 850 730 612 LRAD 5477 4966 2755 2366 1984
Compressor Motor Electrical Data (50 Hertz)
Compressor Voltage 342/ 360/ 374/
Code Utilization Range 418 440 457
B1, B2 RLA @ Max kW 233 233 233
C1, C2 RLA @ Max kW 349 349 349
D1, D2, D3 RLA @ Max kW 455 455 455
E3 RLA @ Max kW 488 488 488
Notes:
1. See Selection Procedure Section for details.
2. The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3. Electrical component sizing should be based on actual jobsite operating conditions. This factor can be obtained through the
use of the Series R chiller selection program available through local Trane sales offices.
Nominal Voltage 380 400 415
Max kW 139 145 148
LRAY 391 412 428 LRAD 1229 1296 1348
Max kW 201 209 213
LRAY 456 480 498 LRAD 1414 1488 1544
Max kW 271 280 284
LRAY 7 11 748 776 LRAD 2303 2424 2515
Max kW 288 301 306
LRAY 7 11 748 776 LRAD 2303 2424 2515
RLC-PRC020-EN
Electrical Connections
Starter Panel Selection Lug Size
Connection RLA L1-L3 (Each Phase)
Terminals Only 000-760 (2) #4-500 MCM
Main Circuit 000-185 (1) #4-350 MCM
Breaker or 186-296 (2) 2/0-250 MCM Non-Fused 297-444 (2) 3/0-350 MCM
Disconnect Switch 445-592 (2) #1-500 MCM
Note:
1. Lug sizes are independent of starter type.
761-888 (4) 4/0-500 MCM
593-888 (4) 4/0-500 MCM
19
Electrical Data and Connections
RLC-PRC020-EN20
Electrical Data and Connections
RLC-PRC020-EN
21
Dimensions and Weights
Shipping and Operating Weights
Compressor Evaporator Condenser Operating Weight Shipping Weight
Code Code Code ( lbs ) (kg) (lbs) (kg)
B1 B1 B1 9,867 4,476 9,292 4,215 B1 C1 D1 10,554 4,787 9,837 4,462 B2 B2 B2 10,019 4,545 9,402 4,265 B2 C2 D2 10,653 4,832 9,953 4,515 C1 D6 E5 13,397 6,077 12,780 5,797 C1 D5 E4 13,673 6,202 12,973 5,884 C1 E1 F1 15,818 7,175 14,718 6,676 C2 D4 E4 13,672 6,201 12,972 5,884 C2 D3 E3 15,044 6,824 14,002 6,351 C2 F2 F3 17,560 7,965 16,168 7,334 D1 D1 E1 15,385 6,978 14,443 6,551 D1 F1 F2 17,537 7,955 16,187 7,342 D1 G1 G1 20,500 9,299 18,600 8,437
D1 G2 G2 21,065 9,555 19,107 8,667 D2, D3 D2 E2 15,570 7,062 14,562 6,605 D2, D3 F2 F3 18,220 8,264 16,820 7,629 D2, D3 G2 G1 20,700 9,389 18,700 8,482 D2, D3 G3 G3 21,641 9,816 19,508 8,849
E3 D2 E2 15,728 7,134 14,720 6,677
E3 F2 F3 18,356 8,326 16,956 7,691
E3 G2 G1 20,800 9,435 18,800 8,528
E3 G3 G3 21,786 9,882 19,653 8,914
Notes:
1. All weights +- 3%.
2. Shipping weights include standard 150 psig water boxes, refrigerant charge, and oil charge.
3. Operating weights include refrigerant, oil, and water charges.
RLC-PRC020-EN22
Dimensions and Weights
BBB Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 108" (2743 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN
23
Dimensions and Weights
BCD Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN24
Dimensions and Weights
CDE, DDE, EDE Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 108" (2743 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN
25
Dimensions and Weights
CEF Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN26
Dimensions and Weights
CFF, DFF, EFF Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN
27
Dimensions and Weights
DGG, EGG Configuration
Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm)
Top 36" (914 mm) * Clearance for tube removal Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each compressor.
Recommended Clearances
RLC-PRC020-EN28
Mechanical Specifications
General
Exposed metal surfaces are painted with air-dry beige, direct-to-metal, single­component paint. Each unit ships with full operating charges of refrigerant and oil. Molded neoprene isolation pads are supplied for placement under all support points. Startup and operator instruction by factory-trained service personnel are included.
Compressor and Motor
The unit is equipped with a semi­hermetic, direct-drive, 3600-rpm (3000 rpm @ 50 Hz) rotary compressor that includes a capacity control slide valve, oil sump heater, and differential pressure refrigerant oil flow system. Four pressure-lubricated, rolling-element bearing groups support the rotating assembly.
The motor is a suction gas-cooled, hermetically sealed, two-pole, squirrel cage induction-type.
Unit-Mounted Starter
The unit is supplied with a NEMA 1 type enclosure with top power-wiring access and three-phase, solid state overload protection. The starter is available in a Wye-Delta configuration, factory­mounted and fully pre-wired to the compressor motor and control panel. A factory-installed, factory-wired 600VA control power transformer provides all unit control power (120 VAC secondary) and CH530 module power (24 VAC secondary). Optional starter features include circuit breakers, ground fault circuit breakers, and mechanical, non­fused disconnects.
Evaporator and Condenser
Shells are carbon steel plate. The evaporator and condenser are designed, tested, and stamped in accordance with ASME Code for refrigerant-side/ working-side pressure of 200 psig.
All tube sheets are made of carbon steel; tubes are mechanically expanded into tube sheets and mechanically fastened to tube supports. Evaporator tubes are 1.0­inch (25.4 mm) diameter and condenser tubes are 0.75-inch (19.05 mm) diameter. Both types can be individually replaced. Standard tubes are externally finned, internally enhanced seamless copper with lands at all tube sheets.
All water pass arrangements are available with grooved connections (150 or 300 psig waterside). All connections may be either right- or left-handed. Waterside shall be hydrostatically tested at 1.5X design working pressure.
Refrigerant Circuit
An electronically controlled expansion valve is provided to maintain proper refrigerant flow.
Unit Controls (CH530)
The microprocessor-based control panel is factory-installed and factory-tested. The control system is powered by a control power transformer, and will load and unload the chiller through adjustment of the compressor slide valve. Microprocessor-based chilled water reset based on return water is standard.
The CH530 microprocessor automatically acts to prevent unit shutdown due to abnormal operating conditions associated with low evaporator refrigerant temperature, high condensing temperature, and/or motor current overload. If an abnormal operating condition continues and the protective limit is reached, the machine should shut down.
The panel includes machine protection shutdown requiring following conditions:
• low evaporator refrigerant temperature and pressure
• high condenser refrigerant pressure
• low oil flow
• critical sensor or detection circuit faults
• motor current overload
• high compressor discharge temperature
• lost communication between modules
• electrical distribution faults: phase loss, phase imbalance, or phase reversal
• external and local emergency stop
• starter transition failure
The panel also includes machine protection shutdown with
for the following correctable
reset
conditions:
• momentary power loss
• under/over voltage
• loss of evaporator or condenser water flow
When a fault is detected, the control system conducts more than 100 diagnostic checks and displays results.
manual reset
automatic
for the
The display will identify the fault, indicate date, time, and operating mode at time of occurrence, and provide type of reset required and a help message. The diagnostic history will display the last ten diagnostics with their times and dates of occurrence.
Clear Language Display Panel
Factory-mounted to the control panel door, the operator interface has an LCD touch-screen display for operator input and information output. This interface provides access to the following information: evaporator report, condenser report, compressor report, ASHRAE Guideline 3 report, operator settings, service settings, service tests, and diagnostics. All diagnostics and messages are displayed in “clear language.”
Data contained in available reports includes:
• Water and air temperatures
• Refrigerant levels and temperatures
• Oil pressure
• Flow switch status
• EXV position
• Head pressure control command
• Compressor starts and run-time
• Line phase percent RLA, amps, and volts
All necessary settings and setpoints are programmed into the microprocessor­based controller via the operator interface. The controller is capable of receiving signals contemporaneously from a variety of control sources, in any combination, and priority order of control sources can be programmed. The control source with priority determines active setpoints via the signal it sends to the control panel. Control sources may be:
• the local operator interface (standard)
• a hard-wired 4-20 mA or 2-10 VDC signal from an external source (interface optional; control source not supplied)
• Generic BAS (optional points; control source not supplied)
• LonTalk LCI-C (interface optional; control source not supplied)
• Trane Tracer Summit optional)
system (interface
RLC-PRC020-EN
29
Conversion Table
RLC-PRC020-EN30
RLC-PRC020-EN
31
Trane A business of American Standard Companies www.trane.com
For more information, contact your local sales office or e-mail us at comfort@trane.com.
Literature Order Number
File Number
Supersedes
Stocking Location
RLC-PRC020-EN
PL-RF-RLC-000-PRC020-EN-0606
RLC-PRC020-EN-00406
Inland
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...