Trane GEH 009, GEH 036, GEH 012, GEH 024, GEH 030 User Manual

...
High Efficiency Horizontal and Vertical Water-Source Comfort System
Axiom 1/2 - 5 Tons — 60 HZ 12 1/2 - 25 Tons — 60 HZ
TM
WSHP-PRC001-EN
Introduction
Imagine a full range of comfort utiliz­ing efficiency, sound attenuation, in­tegrated controls, and superior maintenance accessibility... Trane imagined it, then brought it to life.
Introducing models GEH and GEV water source comfort solutions.
Model GEH (pictured below) is a ceil­ing hung product that provides a sleak, innovative shape, along with convertibility of the supply-air and the return-air arrangement; serviceability to maintenance components; indoor air quality standards; sound attenua­tion; and best of all, higher efficien­cies with certified ARI-ISO 13256-1 performance and ASHRAE 90.1 standards.
Trane’s new design incorporates system advantages such as:
Maximum return-air and
1
supply-air flexibility Superior maintenance
2
accessibility
3
Dual-sloped, plastic drain pan
4
Multi-speed motor
Quiet unit design
5 6
Integrated controls
7
Orifice ring motor mounting device as standard for ease of
motor service
8
High and low pressure safeties as standard
9
Internal air-to-refrigerant coil (horizontal design)
Table of Contents
Introduction 2 Features and Benefits 4
Options Controls
16
Application Considerations 26 Selection Procedures 40
How to Select by Computer Manual Selection Procedure Model Number Description
40 41 44
General Data 46 Performance Data 49
Cool and Heat Performance Correction Factors Electrical Performance Fan Performance Waterside Economizer Performance Sound Performance Anti-Freeze Correction Factors
49 84 85
89 101 102 106
4
Controls 107
Wiring
Dimensional Data 111 Accessories 132
Thermostats Options
Mechanical Specifications 140
WSHP-PRC001-EN 3
107
132 138
Figure 1: Horizontal service access
Features and Benefits
Design Advantages
The horizontal configuration model GEH product offers a range of capacities from 1/2 to 5 ton.
This innovative design offers superior field flexibility at the jobsite along with service accessibility.
Cabinet
The cabinet design includes a modular platform that utilizes similar parts and assemblies throughout the product line. It is constructed of heavy gauge (non-painted) galvanized metal for maximum durability and corrosive re­sistive exterior.
The cabinet front allows service ac­cess for the controls and refrigeration circuitry. Water-in/out connection and high/low voltage hook-up is accom­plished at the 45-degree corners on the front-side of the equipment.
The new horizontal design offers six product variations of return-air and supply-air combinations which may be order-specific or job-site modi­fied.(See Figure 1 for service access and Figure 2 for component platform location).
Figure 2: Component platform location
Features and Benefits
Cabinet
The cabinet design includes a modular platform that utilizes similar parts and assemblies throughout the product line. It is constructed of heavy gauge (non-painted) galvanized metal for maximum durability and corrosive resistive exterior.
The cabinet front allows service access for the controls and refrigeration circuitry. Water-in/out connection, drain connection, and high/low voltage hook-up is accomplished at the 45-degree chamfered corners on the front-side of the equipment.
The vertical design offers four product variations of return-air and supply-air combinations.
Figure 4: Component platform location
Design Advantages
Like it’s horizontal (GEH) counterpart, the GEV offers a range of capacities from 1/2- to 5-ton, and 12 1/2 through 25-ton. Only, with the vertical design, Trane includes a 3 1/3-ton configuration physically sized for condominium installations.
The GEV configuration incorporates the unique modular component platform design of the horizontal configuration to provide a repetitious look and feel to installation and maintenance personnel.
The 1/2 through 5-ton supply-air ar­rangement may be field convertible with service kit to aid in stocking of a single unit variation. (See Figure 3 for service access of the unit. See Figure 4 for component platform location.)
This orchestrated family share fea­tures and benefits with only a few vari­ances.
WSHP-PRC001-EN 5
Figure 3: Service access of small tonnage vertical
Field Convertible
The bullet listing below shows the available return-air/supply-air combi­nations on the GEH model whether specified by order or modified on-site to meet your unique installation re­quirement. The six combinations in­clude:
Left return-air with left supply-air
1
combination Left return-air with rear supply-air
2
combination Left return-air with right sup-
3
ply-air combination Right return-air with left sup-
4
ply-air combination Right return-air with rear
5
supply-air combination Right return-air with right
6
supply-air combination
See Figure 5 for the six convertible combinations.
Features and Benefits
1
UNIT
FRONT
4
UNIT
FRONT
Figure 5: Six convertible combinations (GEH 1/2 through 5-ton)
2
5
FRONT
UNIT
FRONT
UNIT
3
FRONT
6
FRONT
UNIT
UNIT
More Flexibility
The GEV model is also capable of on-site modifications. With the vertical configuration, the supply-air is easily
1
UNIT
FRONT
3
UNIT
FRONT
Figure 6: Four combinations (GEV 1/2 through 5-ton)
2
UNIT
FRONT
4
UNIT
FRONT
converted from a top supply-air to a back supply-air with a service retrofit kit. The return-air option is order spe­cific. The four combinations include:
Right return-air with top sup-
1
ply-air combination Right return-air with back sup-
2
ply-air combination Left return-air with top supply
3
-air combination Left return-air with back sup-
4
ply-air combination
See Figure 6 for the four supply-air/ return-air combinations.
Features and Benefits
Vertical Advantages
The vertical (model GEV) configuration offers a range of capacities from 12 1/2-ton through 25-ton.
The sleek, narrow cabinet is designed to fit through a standard doorway for installation during new construc­tion, or retrofit purposes. The units sturdy cabinet is de­signed for durability, and corrosive resistance. The upper panels feature an key hole hanging design for ease of maintenance of the unit, allowing the panel to be hooked into place when attaching the panel to the unit. The panels are also sealed with a rubber gasket at all four edges to help eliminate air from escaping around the panel’s edge.
1
2
Supply/Return Combinations
The 12 1/2 through 25-ton GEV models are available in four sup­ply-air/return-air combinations. These combinations are order specific via the unit model number. The four combinations in­clude:
3
4
Figure 6: Supply-air/return-air combinations
WSHP-PRC001-EN 7
Front return-air with back supply-air combination
1
Front return-air with top supply-air combination
2
Back return-air with front supply-air combination
3
Back return-air with top supply-air combination
4
The 12 1/2 to 25 ton verticals are most prevalently installed in small equipment rooms or above the space on a mezzanine. They are typically used to feed atriums, or core areas of a building where a large heating or cooling load is required. See Figure 6 for the flexibility of the vertical unit offering of four supply-air/re­turn-air combinations.
Features and Benefits
Hanging Device
The hanging bracket resides in the chamfered corner of the horizontal unit. This partially-concealed bracket design eliminates added height, width, or length to the product. The brackets are factory mounted to short­en job installation requirements.
The structural integrity of the design helps assure no bracket deflection or unit bowing from the unit’s weight.
Field return-air hook-up and filter maintenance are more simplistic be­cause of this innovative design. Isola­tion for the hanging bracket is provided with a neoprene rubber grommet design. This isolation device helps prevent sound vibration from reaching the structural support mem­bers of the building during compres­sor start and stop. (See Figure 7 for isolation device).
Drain Pan
The unit drain pan is composed of plastic, corrosive resistive material. The pan is positively sloped to comply with ASHRAE 62 for (IAQ) indoor air quality conformity.
Access to the drain pan is provided through two access panels for clean­ing purposes for all models. (See Fig- ure 8 for plastic drain pan).
Refrigeration Piping
The unit’s copper tubing is created from a 99% pure copper formation that conforms to the American Society of Testing (ASTM) B743 for seamless, light-annealed processing.
The unit’s copper refrigeration system is designed to be free from contami­nants and conditions such as drilling fragments, dirt, or oil. This excludes the possibility of these contaminants from damaging the compressor mo­tor.
Compressor
The unit’s design includes a wide vari­ety of compressor motors to accom­modate dedicated voltages and tonnage sizes. The 1/2 ton through 1 1/2 ton products will embody a rota­ry compressor design, where as unit sizes ranging from 2 ton through 4 ton include a reciprocating compressor style, while the 5 ton unit contains a scroll compressor. These different de­signs allow Trane to provide the volt­age variations along with noise reduction. (See Figure 9 for recipro­cating compressor).
The larger tonnage (GEV model) 12 1/2 through 25 ton units include a dual circuit system which incorporate scroll compressors.
Figure 7: Hanging bracket design
Figure 8: Plastic drain pan
Important!
Although the drain pan is sloped, the horizontal unit should be hung at a dual angle (per local code) to provide proper drainage of the condensate system.
Cabinet Insulation
The cabinet insulation design meets UL 181 requirements. The air stream surface of the insulation is fabricated of a non-biodegradable source.
Schrader Connections
The connections for the low and high side of the refrigeration system are lo­cated directly beside the control box at the front (service access) panel. (See Figure 10 for schrader connection lo­cations).
Figure 9: Reciprocating compressor
Figure 10: Schrader connections
Features and Benefits
Co-axial Water-to-Refrigerant Coil
The unit’s internal heat exchanging water coil is engineered for maximum heat transfer.
The copper or cupro-nickel seamless tubing is a tube within a tube design. The inner-water tube contains a deep fluted curve to enhance heat transfer and minimize fouling and scaling. It is available in either copper or cu­pro-nickel (selectable option) coil.The
Figure 11: Coaxial water coil
Figure 12: Water connection device
Figure 13: 12 1/2-ton + water hook-up
Figure 14: Thermal expansion valve
WSHP-PRC001-EN 9
outer refrigerant gas tube is made from steel material. The coil is leak tested to assure there is no cross leak­age between the water tube and the refrigerant gas (steel tube) coil. Co-ax-
ial heat exchangers are more tolerant to freeze rupture. (See Figure 11 for
co-axial water coil).
Compressor and Co-axial Coil Isolation
For the 1/2-ton through 5-ton units, vi­bration isolation of the compressor and co-axial water coil is accom­plished by increasing the rigidity and stiffness at the base. This platform in­cludes double isolation to the com­pressor and single isolation to the co-axial water coil. The combination in the double isolation provide additional attenuation during compressor start and stop.
Water Connections (1/2 thru 5-ton)
The water-in/water-out connections to the co-axial water coil are located on the right-hand chamfered corner of the unit. The fittings are mounted flush to the chamfered wall to help limit shipping damage.
The water connection devices are con­structed of copper or bronze material and include a National Female Pipe Thread (NFPT) junction. The connec­tions are attached to the unit’s cham­fer corner to alleviate the need for a back-up wrench during installation. (See Figure 12 for water connection device).
Water Connections (12 1/2 thru 25-ton)
Water hookups for the larger tonnage units are located internal to the unit to help alleviate damage to the water copper during shipment or job storage of units prior to installation. Each unit (although dual circuited) contains a single supply and return water con­nection. (See Figure 13 for large ton­nage water hook-up). Fittings for the supply and return are internally threaded.
Table 1 defines water connection siz­ing for 1/2 ton through 25 ton configu­rations
Table 1: Water connection sizes
Unit Size
(MBH)
006 thru 015 1/2 FTP 018 thru 042 3/4 FTP 048 thru 060 1 FPT 150 thru 180 1 5/8 FPT 240 thru 300 2 1/8 FPT
Expansion Valve
All Trane water-source systems in­clude an expansion valve flow meter­ing device.
This thermal expansion valve (TXV) al­lows the unit to operate with an enter­ing fluid temperature from 25 F to 110 F, and entering air temperatures from 40 F to 90 F. The valve is designed to meter refrigerant flow through the cir­cuitry to achieve desired heating or cooling.
Unlike cap-tube assemblies, the ex­pansion valve device allows the exact amount of refrigerant required to meet the coil load demands. This precise metering by the TXV increases the ef­ficiency of the unit. (See Figure 14 for thermal expansion valve).
Fitting Size
(in)
FPT
Features and Benefits
Reversing Valve
A system reversing valve (4-way valve) is included with all heating/ cooling units. This valve is piped to be energized in the cooling mode to al­low the system to provide heat if valve failure were to occur. Once the valve is energized for cooling, it will remain energized until the control system is turned to the OFF position, or a heat­ing cycle is initiated.
Units with the cooling only option will not receive a reversing valve. (See Figure 15 for reversing valve).
Blower Motor
The 1/2 through 5-ton supply-air (blower) motor is a multi-speed motor with internal thermal overload protec­tion. The motor bearings are perma­nently lubricated and sealed. Standard motors are rated from .20 ESP. Option- al high static motors are rated from .40 to 1.40 ESP. All motors are factory wired to the option selected. A high, medium, and low speed tap is provid­ed for field customization on all volt­ages. The speed tap modification can be made in the control box of the unit. (See Figure 16 for blower motor).
Note: The 380, 415, 460 and 575 volt designs are provided in a dual or three-speed version only. See
fan performance section for factory ratings (Page 91).
The 12 1/2 through 25 ton GEV models incorporate a belt driven motor selec­tion into the design. The 12 1/2 and 15 ton units include a single fan assem­bly, while the 20 and 25-ton units in­clude dual fan assemblies. Because the motor sheave and the motor base are adjustable in the field, a greater variation in external static pressures are available. The large tonnage units are capable of providing 0 ESP to 3.0 ESP allowing a higher static ductwork to be applied on the mechanical sys­tem when the application requires
extensive ductwork design. This is a low cost alternative to purchasing, in­stalling, and maintaining multiple smaller tonnage units to meet the re­quired air flow demand for the space.
Serviceability to the motor is made through either of the two air-side ac­cess doors for the horizontal configu­ration, and through one air-side access door for the 1/2 through 5-ton vertical configuration. The motor and blower wheel are removable by an or- ifice ring mounted to the fan hous­ing.
Access to the 12 1/2 through 25 ton units is made through the back of unit by way of two panels, and/or through a side access panel if adjustment to the motor belt or motor base are need­ed. (See Figure 17 for motor accessibility).
Blower Housing
The blower housing is constructed of non-corrosive galvanized steel. A fac­tory-mounted orifice ring is provided for ease of motor serviceability on the 1/2 through 5-ton direct drive units.
All air-side panels are interchangeable with one another for ease of field con­vertibility of the supply-air on the GEH model.
Air-Side Filter
The air-side filter incorporates a 1-inch thick (nominal) or 2-inch thick (nomi­nal) disposable fiberglass option. These filters include an average syn­thetic dust weight arrestance of ap­proximately 75%. This dust holding capability includes a colorless, odor­less adhesive to retain dirt particles within the filter media after fiber con­tact. (See Figure 18 for filter media)
Figure 15: Reversing valve
Figure 16: Blower motor (direct drive)
Figure 17: Motor accessibility
Figure 18: Filter media
Features and Benefits
Air-to-Refrigerant Coil
The air-to-refrigerant heat exchanger is constructed of staggered
copper tubes with die-formed corrugated lanced aluminum fins.
The fins are then mechanically bonded to the tubes through ex-
pansion.
The coil is placed internal of the unit design for model
GEH to assure no fin surface damage during shipment,
jobsite storage, or installation. The internal placement of the coil on the horizontal con-
figuration provides an option of a dual filtration applica­tion. With dual filtration to the GEH unit, maintenance to the filter is significantly less than with a single filtration system.
The maximum working pressure for both the GEH and GEV coils is 450 psig. It is designed for maximum capac­ity with an additional benefit of physical unit size reduc-
tion.
Coil specifications for both GEH and GEV may be found on
in the General Data section on page 48 of this catalog. See
Figure 19 for internal air to refrigerant coil placement.
Figure 19: Internal air-to-refrigerant coil placement (GEH)
The sound package for the horizontal unit includes:
Table 2: Sound Package (1/2 through 5-ton units ONLY)
Enhanced Sound Attenuation
Package
18-gauge compressor enclosure 16-gauge compressor enclosure 18-gauge single wall front panel 16-gauge single wall front panel lined compressor enclosure with
1/2-inch cabinet insulation compressor discharge muffler compressor discharge muffler 12-gauge compressor/water-to-refrig-
erant heat exchanger pan with second stage of vibration isolation
compressor vibration isolation compressor vibration isolation water-to-refrigerant heat exchanger
vibration isolation lengthwise unit base stiffeners lengthwise unit base stiffeners
Deluxe Sound Attenuation
Package
lined compressor enclosure with 1/2-inch cabinet insulation
12-gauge compressor/water-to-refrig­erant heat exchanger pan with second stage of vibration isolation
water-to-refrigerant heat exchanger vibration isolation
3/32-inch foam gasket sealant placed around the compressor and end panel perimeter
Sound Attenuation Package
Testing of conventional units has iden­tified that the sound radiated by the casing of the unit is an important com­ponent of the sound that reaches occu­pants, especially when the unit is located directly over the occupied space.
This sound reduction package reduces radiated noise from the cabinet. Trane double-isolates the compressor and single-isolates the co-axial coil in the unit. This design absorbs the vibration that contributes to radiated sound
For sound critical spaces, an enhanced sound package as de­scribed in Table 2 provides additional attenuation.
Complete sound data taken in accor­dance with ARI 260 is available for all 1/2 through 5-ton units. The test data reflects multi-speed fan motor along a single system curve. (See sound per­formance data on Page 107.)
WSHP-PRC001-EN 11
Boilerless Control/Electric Heat
(option)
In cooling dominant regions where heat may be used 15 to 30 days out of the winter season, eliminating the boiler may be an economical advan­tage to the building owner. Eliminat­ing a boiler from the system reduces costs associated with the mechanical system installation, as well as the maintenance and service of the boiler.
How can heat be provided for the few days of the year when heat is neces­sary? Through the water-source heat
pump of course. The advantage of the water-source heat pump is it’s ability to provide heat recovery within the closed water-loop. While some WSHPs may be extracting heat from the closed water loop, other WSHPs may be adding heat to the closed water loop. This creates a perfect sys­tem balance for heat sharing or move­ment from one space to another.
But when water temperatures fall in a boilerless system, and no further heat recovery may be made via the closed loop, heat may be added to the space through a boilerless control electric heat option. See Figure 20 for the boilerless control, electric heat system diagram.
With the boilerless electric heat option, the heat pump encompasses an internal nichrome open wire heat-
Features and Benefits
Figure 20: Boilerless control, electric heat system
ing element (factory mounted and wired in the 1/2 through 5-ton models) It is comprised of a single stage of electric heat designed to invoice an electric heater in place of the com­pressor in the event entering water temperature falls below 55 F or a field adjusted temperature setting between 25 F to 60 F.
The 12 1/2 through 25-ton GEV model will contain the boilerless controls
ONLY to interface for a field provided supplemental electric heat selection. The heater for this model shall be placed external to the equipment by the contractor for ease of installation. All power connections for the electric heater will be completely separate from the unit for field supplied electric heat.
Boilerless Control/Electric Heat
Heating/Cooling Mode
In heating mode, when the water tem­perature falls below 55 F (factory set­ting), the electric heater is energized, locking out the compressor. The systems electric heat source will continue to be utilized for primary heating until the loop tempera­ture rises above 60 F. Once the entering water tempera­ture rises above 60 F, the boiler­less controller returns the unit to normal compressor heating opera­tion and locks out the electric heater. This maximizes efficiency from the unit during the few days requiring heat from the mechanical system. See Figure 21 for the factory mounted and wired boilerless control electric heat water-source heat pump. Avail-
able on the 1/2 through 5-ton equip­ment ONLY as a single point power connection.
If the unit employs a cooling only unit design, the electric heat contactor is wired directly to the thermostat for primary heating, and the compressor contactor for cooling.
Note: For geothermal applications, the boilerless controller has an adjust­able setting of 25, 35, 45, 55 and 60 degrees.
Features and Benefits
Figure 21: Boilerless control, electric heat water-source heat pump
What is NOT available with the boilerless electric heat option?
Hot gas reheat
1 2
Basic 24 volt controls TracerTM ZN510 controls
3
115 and 575 volt ratings
4
Supplemental or emergency heat applications
5 6
And, a factory installed heater (applies to unit sizes 12 1/2 through 25-ton ONLY)
WSHP-PRC001-EN 13
Features and Benefits
Figure 22: Model GEH with waterside economizer package
Note: Condensate overflow is not available with
the waterside economizer option.
Figure 23: Waterside economizer system
Waterside Economizer (option)
The beauty of the waterside economiz­er is it’s ability to take advantage of any loop condition that results in cool water temperatures. A prime example would be during fall, winter and spring when cooling towers have more ca­pacity than required and could be con­trolled to lower temperatures for economizer support.
Another more common inexpensive means of free comfort cooling in­cludes buildings systems where pe­rimeter heating and core cooling are needed. In this system, the perimeter units extract heat from the building loop while in the heating mode, forc­ing the building loop temperature to drop. Where as, the core are of a build­ing may require cooling in summer or in winter based upon lighting, people and equipment.
If the water-source system design con­tained an economizing coil option, the moderate temperature loop water cir­culated through a core water-source system can provide an inexpensive means to satisfy room comfort with­out operating the water-source heat pump’s compressor.
During economizer mode, fluid enters the unit, and passes by a water tem­perature sensing bulb. This tempera­ture sensing bulb determines whether the two position, three-way valve will direct the water through the waterside economizing coil, and to the heat pump condenser, or through the con­denser only. If the water temperature is 55 F or less, fluid will flow into the economizing coil, while simultaneous­ly halting mechanical operation of the compressor. Mechanical cooling will continue on a call for second stage from the thermostat.
The factory built waterside economiz­er is available on all GEH models, and all 12 1/2 to 25 GEV models. The 1/2 through 5-ton GEV may be ordered to accept a field provided waterside economizing package.
Features and Benefits
Hot Gas Reheat (option)
For space conditioning and climate control, Trane provides an accurate and cost effective dehumidification control through a hot gas reheat op­tion. This option is designed to accom­modate unit sizes 012, 036, 060, 180 and 240.
With this reheat option, the return air from the space is conditioned by the air-to-refrigerant coil, then reheated by the reheat coil to control not only the space temperature, but to also re­duce the relative humidity of the space. The moisture removal capabili­ty of a specific heat pump is deter­mined by the units latent capacity rating.
When operating in the reheat mode (meaning the sensible temperature has been met in the space), the humi­distat signals the reheat relay coil to energize, allowing the high pressure refrigerant gas to flow from the (1) compressor, through the (2) reheat valve, into the (3) reversing valve, or through the (4) reheat coil for dehu­midification. A switching relay has been provided for the reheat applica­tion to adjust the blower motor from normal operation to low speed when hot gas reheat is energized.
Note: Trane places an air separation space between the air-to-refrigerant coil, and the reheat coil to allow for maximum moisture removal.
Common Reheat Applications
The hot gas reheat option is designed to support building applications re­quiring fresh-air ventilation units de­livering unconditioned-air directly to the space. It also provides dehumidifi-
cation to large latent load spaces such as auditoriums, theaters and class­rooms, or anywhere humidity control is a problem.
Do’s and Don’ts in Design
The factory installed hot gas reheat option is only available with Deluxe or ZN524 controls packages.
A high static blower motor option will be required to support the hot gas re­heat option.
Water regulating valves should not be used with the hot gas reheat option. Trane places a thermal expansion valve on all water-source heat pumps, as well as ground-source heat pumps, to regulate refrigerant flow vs. water flow, making the heat pump more effi­cient to run.
The water-source heat pumps with hot gas reheat should not be used as a make-up air unit.
Figure 24: Hot gas reheat heat pump
WSHP-PRC001-EN 15
Features and Benefits Controls
Controls by Trane
Whether involved in a retrofit or new construction application, Trane has the control design to fit your system requirement. Our control options provide a broad range of packages from the most cost efficient 24 volt standalone to a complete build­ing automation solution, Trane is the right choice in comfort gratification. The following chart provides a brief overview in the different control combinations.
Graphic Description Application ICS Protocol Where to find
Basic 24V
Available on 1/2
through 5 ton
equipment ONLY.
Deluxe 24V
Standard offering
for the 6 through
25 ton equipment.
Tracer ZN510
TM
Used in
single circuit
WSHP design.
Tracer ZN524
TM
Used in
multi-circuit
WSHP design. Or,
for single circuited
WSHPs with HGR,
WSE, or BEH.
TracerTM Loop
Controller
Tracer Summit®
Compressor lockout relay, low and high pressure switches.
24 volt electro­mechanical board designed to provide control of the entire unit, as well as mul­tiple relay offerings to maximize system performance.
Direct Digital Con­trol board designed to provide control of the entire unit as well as outputs for unit status and fault detection.
Direct Digital Con­trol board designed to provide control of the entire unit as well as outputs for unit status and fault detection.
Microproces­sor-based controller that coordinates the water side (boiler, pumps, cooling tower, etc.) of a water-source heat pump system.
Microprocessor based controller that coordinates full building automa­tion from HVAC to lighting.
Retrofit market where sin­gle and multiple unit replacement occurs.
New building design where field provided controls are specified.
Retrofit market where sin­gle and multiple unit replacement occurs.
Multi-unit installation where units may be daisy­chained directly to the
Trane TracerTM Loop Con­troller.
Retrofit market where over­all system upgrade is speci­fied.
Multi-unit (100+) installa­tion where units are linked by a common twisted pair of wire for a communica­tion link.
Retrofit market where over­all system upgrade is speci­fied.
Multi-unit (100+) installa­tion where units are linked by a common twisted pair of wire for a communica­tion link.
Wherever the Tracer ZN510 controls or 24 volt elec­tro-mechanical controls are specified for complete control of the water loop and pumps.
Where any controller is specified.
No Non Applicable Page 17
No Non Applicable Page 19
Yes
Yes SCC LonTalk
Yes LonTalk
Yes BACnet
SCC LonTalk®
open protocol
(Comm5)
open protocol
(Comm5)
compatible
(Comm5)
(Comm 2,3,4,5)
Page 22
Page 22
WSHP-MG-3
EMTW-SVN01B-EN EMTW-SVP01B-EN EMTW-SVU01B-EN
HGR = Hot Gas Reheat WSE = Waterside Economizer BEH = Boilerless Electric Heat
Features and Benefits Basic Controls
Basic 24 Volt Controls
The basic 24 V electro-mechanical unit control provides component protec­tion devices for maximum system reli­ability. Each device is factory mounted, wired and tested.
Figure 25: Basic 24 volt control box
WSHP-PRC001-EN 17
The Basic 24 volt control package is only available for the 1/2 through 5-ton unit sizes. See Figure 25 for basic 24 volt control box (model GEH shown).
Figure 26: Safety devices
Safety Devices
System safety devices are provided to prevent compressor damage through the use of low and high pressure switches in the refrigeration circuit.
The low pressure switch or suction line temperature sensor to prevent compressor operation during low tem­perature operation. The switch and sensor are set to activate at refrigerant pressures of 20 psig to fit most appli­cations.
In cases where a low charge, or exces­sive loss of charge occurs, each com­pressor comes equipped with an external overload device to halt the compressor operation.
The high pressure switch prevents compressor operation during high or excessive discharge pressures that ex­ceed 395 psig.
A lockout relay provides the me­chanical communication of the low and high pressure switches to prevent compressor operation if the unit is un­der low or high refrigerant circuit pres­sure, or during a condensate overflow condition. The lockout relay may be re­set at the thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay and is used in driving light emitting diodes. This feature will drive dry contacts only, and cannot be used to drive field in­stalled control inputs.
See Figure 26 for safety devices on the basic 24V control unit.
Features and Benefits Basic Controls
Stand-alone System
The 24 volt electro-mechanical design may be applied as a stand-alone control system. The stand-alone design provides accurate temperature control directly through a wall-mounted mercury bulb or electronic thermostat. This system set-up may be utilized in a replacement design where a single unit retrofit is needed. It may be easily interfaced with a field provided control system by way of the factory installed 18-pole terminal strip.
This stand-alone control is frequently utilized on lower volume jobs where a building controller may not be necessary, or where field installed direct digital controls are specified. This type of control design does require a constant flow of water to the water source heat pump. With a positive way to sense flow to the unit, the units safety devices will trigger the unit off.
The stand-alone system design provides a low cost option of installation while still allowing room control for each unit. See Figure 27 for 24 volt stand-alone
system controls.
Figure 27: 24 volt stand-alone system
Features and Benefits Deluxe Controls
Deluxe 24V Electronic Controls
The deluxe 24V electronic unit control provides component protection devices similar to the basic design, but contains upgraded features to maximize system performance to extend the system life. Each device, is factory mounted, wired, and tested in the unit.
Note: On dual circuited systems, Each circuit contains a deluxe micro-processing
control board.
Figure 28: Deluxe 24 volt control box
The deluxe 24 volt control package is available for all unit sizes. See Figure 28 for deluxe 24 volt control box (model GEH shown).
WSHP-PRC001-EN 19
Features and Benefits Deluxe Controls
Microprocessor Design
The 24 volt deluxe design is a microprocessor-based control board conveniently located in the control box. The board is unique to Trane water-source products and is designed to control the unit as well as provide outputs for unit status and fault detection. The Trane microprocessor board is factory wired to a terminal strip to provide all necessary terminals for field connections. See Figure 29 for the deluxe 24V control board.
Figure 29: Deluxe 24V control board
Deluxe 24V features include: Random Start
The random start relay provides a time delay start-up of the compressor when cycling in the occupied mode. A new start delay time between 3 and 10 seconds is applied each time power is enabled to the unit.
Anti-short Cycle Timer
The anti-short cycle timer provides a three minute time delay between compressor stop and compressor restart.
Brown-out Protection
The brown-out protection function measures the input voltage to the controller and halts the compressor operation. Once a brown-out situation has occurred, the anti-short cycle timer will become energized. The general fault contact will not be
affected by this condition. The voltage will continue to be monitored until the voltage increases. The compressors will be enabled at this time if all start-up time delays have expired, and all safeties have been satisfied.
Compressor Disable
The compressor disable relay pro­vides a temporary disable in compres­sor operation. The signal would be provided from a water loop controller in the system. It would disable the compressor because of low water flow, peak limiting or if the unit goes into an unoccupied state. Once the compressor has been disabled, the an­ti-short cycle time period will begin. Once the compressor disable signal is no longer present, and all safeties are satisfied, the control will allow the compressor to restart.
Generic Relay
The generic relay is provided for field use. Night setback or pump restart are two options that may be wired to the available relay. (Note: Night setback is available as factory wired). An exter­nal Class II 24VAC signal will energize the relay coil on terminals R1 and R2. Terminals C (common), NO (normally open), and NC (normally closed) will be provided for the relay contacts.
Safety Control
The deluxe microprocessor receives separate input signals from the refrig­erant high pressure switch, low suc­tion pressure switch and condensate overflow.
In a high pressure situation, the compressor contactor is de-energized, which suspends compressor opera­tion. The control will go into soft lock- out mode initializing a three minute time delay and a random start of 3 to 10 second time delays. Once these de­lays have expired, the unit will be al­lowed to run. If a high pressure situation occurs within one hour of the first situation, the control will be placed into a manual lockout mode,
halting compressor operation, and ini­tiating the general alarm.
In a low temperature situation, the low pressure switch will transition open after the compressor starts. If the switch is open for 45 seconds during compressor start, the unit will go into soft lockout mode initializing a three minute time delay and a random start of 3 to 10 second time delays. Once these delays have expired, the unit will be allowed to run. If the low pressure situation occurs again within 30 min­utes, and the device is open for more than 45 seconds, the control will be placed into a manual lockout mode, halting compressor operation, and ini­tiating the general alarm.
In a condensate overflow situation, the control will go into
manual lockout mode, halting com­pressor operation, and initiating the general alarm.
The general alarm is initiated when the control goes into a manual lockout mode for either high pressure, low pressure or condensate overflow con­ditions.
Diagnostics
Component device connections to the microprocessor board are referenced in Figure 29. Three LEDs (light emitting diodes) are provided for indicating the operating mode of the controller. See the unit IOM for diagnostics or trouble­shooting through the use of the LEDs.
Features and Benefits Deluxe Controls
Small Building Control
The deluxe 24V electro-mechanical design may be applied as a stand-alone control system or as a multi-unit installation system. With a stand-alone design, units run independently of one another with a mercury bulb or electronic digital thermostat.
With a multiple unit installation, the units may be daisy-chained directly to the Trane Tracer loop controller (TLC), pump(s), boiler, and tower for a complete networked water-source system. The TLC provides a night setback output, and a pump request input for system
optimization.See Figure 30 for 24 volt deluxe control system.
Figure 30: 24 volt deluxe control system
WSHP-PRC001-EN 21
Features and Benefits ZN510 & ZN524 Controls
Tracer ZN510 & ZN524 Controls
The Tracer ZN510 and ZN524 are direct digital control (DDC) systems specifically designed for single and dual circuited water-source equipment to provide control of the entire unit, as well as outputs for unit status and fault detection. Each de­vice is factory installed, commissioned, and tested to ensure the highest level of quality in unit design.
Each of the controller’s features and options were selected to coordinate with the unit hardware to provide greater energy efficiency and equipment safety to pro­long the equipment life.
In addition to being factory configured for control of the unit fan, compressor and reversing valve, the ZN510 and ZN524 controllers are designed to coordinate the waterside of the water-source system through the Tracer Loop Controller (TLC). If applied in a peer-to-peer communication environment, data between similar controllers may be exchanged without requiring a building automation system.
By teaming the ZN510 and ZN524 with the TLC, a low first-cost for the mechanical equipment, water loop, and water pump optimization is provided to the owner.
For owners who require a full building integrated "open protocol" system, The ZN510/ZN524/TLC application is upgradable to support complete building con­trol through Tracer Summit. Because the ZN510 and ZN524 is LonTalk certified, it is capable of working with, and talking to other LonTalk certified controllers providing the building owner more choices, and the design engineers more flex­ibility to meet the challenges of building automation. See Figure 31 for ZN510 control box.
Figure 31: ZN510 control box
Features and Benefits ZN510 & ZN524 Controls
Direct Digital Controls
When the ZN510 or ZN524 controller is linked directly to the Tracer Summit, each Tracer Summit building automation system can connect a maximum of 120 Tracer ZN510 or ZN524 controllers. See Figure 32 for the Tracer ZN524 board.
Figure 32: Tracer ZN524 controller
Tracer ZN510 and ZN524 functions include:
Compressor Operation
The compressor is cycled on and off to meet heating or cooling zone de­mands. Single and dual compressor units use the unit capacity and pulse width modulation (PWM) logic along with minimum on/off timers to deter­mine the compressor’s operation. The compressor is controlled ON for long­er periods as capacity increases and shorter periods as capacity decreases.
Random Start
To prevent all of the units in a building from energizing major loads at the same time, the controller observes a random start from 0 to 25 seconds. This timer halts the controller until the random start time expires.
Reversing Valve Operation
For cooling, the reversing valve output is energized simultaneously with the compressor. It will remain energized until the controller turns on the compressor for heating. At this time, the reversing valve moves to a de-energized state. In the event of a power failure or controller OFF situation, the reversing valve output
will default to the heating (de-energized) state.
Fan Operation
The supply air fan operates at the fac­tory wired speed in the occupied or oc­cupied standby mode. When switch is set to AUTO, the fan is configured for cycling ON with heating or cooling. In heat mode, the fan will run for 30 sec­onds beyond compressor shutdown in both occupied and unoccupied mode.
Fan Run Timer
The controller’s filter status is based on the unit fan’s cumulative run hours. The controller compares the fan run time against an adjustable fan run hours limit and recommends unit maintenance as required.
Data Sharing
The Tracer ZN510/ZN524 controller is capable of sending or receiving data (setpoints, fan request, or space tem­perature) to and from other controllers on the communication link. This al­lows multiple units to share a common space temperature sensor in both stand-alone and building automation applications.
Night Setback
The four operations of the Tracer ZN510/ZN524 controller include occu­pied, occupied standby, occupied by­pass and unoccupied.
In an occupied situation, the con­troller uses occupied heating and cool­ing setpoints to provide heating and cooling to the building. This occupied operation is normally used during the daytime hours when the building is at the highest occupancy level.
In an occupied standby situation, the controllers heating and cooling setpoints are usually wider than the occupied setpoints. This occupied standby operation is used during day­time hours when people are not present in the space (such as lunch­time or recess). To determine the space occupancy, an occupancy sen­sor is applied.
In an unoccupied situation, the controller assumes the building is va­cant, which normally falls in evening hours when a space may be empty. In the unoccupied mode, the controller uses the default unoccupied heating and cooling setpoints stored in the controller. When the building is in un­occupied mode, individual units may be manually placed into timed over­ride of the unoccupied mode at the units wall sensor. During timed over­ride, the controller interprets the re­quest and initiates the occupied setpoint operation, then reports the ef­fective occupancy mode as occupied
bypass. In the occupied bypass mode, the
controller applies the occupied heat­ing and cooling setpoint for a 120 minute time limit.
High and Low Pressure Safety Controls
The Tracer ZN510/ZN524 controller detects the state of the high pressure or low pressure switches. When a fault is sensed by one of these switch­es, the corresponding message is sent to the controller to be logged into the fault log. When the circuit returns to normal, the high pressure control and low pressure control automatically re­set. If a second fault is detected within a thirty-minute time span, the unit must be manually reset.
Condensate Overflow
When condensate reaches the trip point, a condensate overflow signal generates a diagnostic which disables the fan, unit water valves (if present), and compressor. The unit will remain in a halted state until the condensation returns to a normal level. At this time, the switch in the drain pan will auto­matically reset. However, the control­ler’s condensate overflow diagnostic must be manually reset to clear the di­agnostic and restart the unit.
WSHP-PRC001-EN 23
Features and Benefits ZN510 & ZN524 Controls
Additional Functions of the ZN524 Controller
When the building owners choice is Trane Tracer controls, the ZN524 con­troller is required when any of the fol­lowing applications are selected on a single and dual circuited equipment.
Waterside Economizer
Hot Gas Reheat
(for Dehumidification)
Boilerless Control for Electric Heat
Water Isolation Valve Control
(for Variable Speed Pumping)
Entering Water Temperature Sampling
The ZN524 controller will sample the entering water temperature to deter­mine proper control action for units equipped with boilerless electric heat or waterside economizer.
Waterside Economizer: Entering water temperature (EWT) sampling will automatically occur at power up when the unit is equipped with a wa­terside economizer (WSE). The EWT is used to determine if economizing is feasible. When the conditions are met, the isolation valve(s) are driven open for three minutes and the EWT reading is taken. The determination as to whether or not the economizer can be enabled will be made and the control­ler will take appropriate action. The isolation valve will remain open re­gardless if the WSE or the DX cooling is enabled.
The unit’s waterside economizer will contain a 2-position water valve wired to the ZN524. The economizing water coil will be optimized to provide 100% of the unit capacity at 80.6 F/66.2 F re­turn air temperature with 45 F entering water. The flow rate is established at 86 F entering water temperature and 96 F leaving water temperature.
Low leaving air protection will be fur­nished to protect the unit against de­livering air that is cold enough to sweat discharge air grilles. Coil icing protection will also be provided.
Waterside economizer cooling will be active during occupied, unoccupied and standby cooling modes.
Boilerless Control Electric Heat and Supplemental Electric Heat:
The ZN524 supports a single stage of boilerless electric heat operation or concurrent heating.
When the unit is configured for boiler­less control, the EWT will be used to determine whether DX heating should be disabled and the electric heater en­abled. When these conditions are met, the isolation valve(s) are driven open for three minutes and the entering wa­ter temperature reading is taken. The determination as to whether or not to utilize electric heat will be made and the controller will take appropriate ac­tion. If boilerless electric heat is en­abled, then the isolation valve will be closed, shutting down the water flow to the unit.
When the unit is configured for con­current operation of DX heating (com­pressor in heat pump mode) and electric heat, the electric heat will act as a second stage of heat for single compressor units, and a third stage of heat for dual compressor units. Note:
With concurrent (or supplemental) electric heat, the electric heater is field provided.
Water Isolation Valves
Variable speed pumping systems are supported by the ZN524 controller when water isolation valves are present. Up to two isolation valves are supported by the controller (one for each compressor circuit).
The valves are normally closed unless DX heating, DX cooling, waterside economizer or dehumidification is re­quested. When the isolation valves are driven open for operation, the outputs will be driven for 20 seconds to ensure
adequate water flow before the com­pressor outputs are energized. Once an isolation valve has been opened, it will remain open for a 10 minute mini­mum to reduce excessive cycling of the valve.
Dehumidification
Dehumidification for the single and dual circuited water-source heat pump is applicable with the ZN524 control­ler. The controller is capable of direct­ing one stage of DX cooling in conjunction with one stage of reheat (hot gas reheat).
Dehumidification can only occur when the controller is in the cooling mode. A humidity transmitter is used to mea­sure the zone’s relative humidity (RH), then compares the zone relative hu­midity to the relative humidity enable/ disable setpoint parameters. The de­fault values for dehumidification en­able is 60% RH with the disable point at 52% RH. These values are config­urable.
Features and Benefits ZN510 & ZN524 Controls
Building Control Advantages
The Tracer ZN510/ZN524 controller has the ability to share information with one or several units on the same communication link. This sharing of information is made possibe via a twisted pair of wire and a building automation system or through Trane’s Rover
An advantage of installing a ZN510/ZN524 is its capability to work with other LonTalk certified controllers. This provides greater flexibility to the building own­er, as well as greater flexibility in design.
Integrating the ZN510/ZN524 on water-source equipment, and tying it to a Tracer Summit system provides a complete building management system. Each Tracer Summit can connect to a maximum of 120 controllers. With the ICS system, the Tracer can initiate an alarm on a loss of performance on equipment malfunctions; allowing problems to be handled in a timely manner before compromising com­fort.
This type of application would most commonly be used for a large space(s) that
TM
service tool .
may require more than one unit. In
addition to this application
design, the Tracer
ZN510/ZN524 controller provides a way for units located within the same space to share the same zone sensor to prevent units from
simultaneously heating and cooling in the same space.See
Figure 33 for Tracer ZN510/ZN524 controller system.
Figure 33: Tracer ZN510/ZN524 controller system
WSHP-PRC001-EN 25
Application Considerations
How it Works? Cooling Mode (Figure 34) If cooling is called for, the thermostat activates the
centrifugal blower and sets the reversing valve into the cooling position. If all safeties are met, high temperature refrigerant vapor is pumped from the compressor throught the reversing valve to the refrigerant-to-water heat exchanger. The refrigerant vapor condenses to a liquid as it passes through the heat exchanger, giving up its heat to the circulating water loop. High pressure liquid refrigerant then passes through the expansion device into the
refrigerant-to-air fin tube coil heat
exchanger. As the low pressure refrigerant passes through the coil, it evaporates to become a low temperature vapor, absorbing heat from the air, which is drawn over the coil by the blower. The refrigerant then flows as a low pressure gas through the reversing valve back to the suction side of the compressor where the cycle begins again.
Heating Mode (Figure 35) If heating is called for, the thermostat activates the centrifugal blower and sets the reversing valve into the heating position. If
all safeties are met, high temperature refrigerant vapor is pumped from the compressor through the reversing valve to the refrigerant-to-air fin tube coil heat exchanger. The high pressure refrigerant vapor condenses to a liquid as it passes through the coil, giving up its heat to the air which is drawn over the coil by the blower. Liquid refrigerant then passes through the expansion devise into the refrigerant-to-water heat exchanger. As the low pressure refrigerant passes through the heat exchanger, it evaporates to become a low temperature vapor, absorbing heat from the circulating water. The refrigerant then flows as a low pressure gas through the
reversing valve back to the suction side of the compressor where the cycle begins again.
Figure 34: Cooling mode
The energy generated from the com­pressor motor operation will also be rejected to the air-to-refrigerant heat exchanger (heating) or water-to-refrig­erant heat exchanger (cooling).
Figure 35: Heating mode
Application Considerations
Flexibility
The high efficiency vertical and hori­zontal water-source heat pump sys­tem is versatile for installation in boiler/cooling tower applications, as well as ground-source (geothermal) applications. The system design may employ either a central pumping de­sign, or a distributed pumping design.
A central pumping design involves a single pump design, usually located within a basement or mechanical room to fulfill pumping requirements for the entire building system. An aux­iliary pump is typically applied to less­en the likelihood of system downtime if the main pump malfunctions.
A distributed pumping system con­tains a single pump module connected directly to the units supply and return. This module is field installed and piped to the unit. This design requires individual pump modules specifically sized for each water-source heat pump.
Advantages of Geothermal
The advantages of a geothermal heat pump system could literally cut a busi­ness’ heating and cooling costs by 30 to 40-percent. The units are durable, and typically last longer than conven­tional systems because they are pro­tected from harsh outdoor weather conditions, and because the unit is in­stalled indoors and the loop under­ground. (According to ASHRAE, the estimated service life for a commercial water-to-air heat pump is 19-years.) Geothermal heat pumps have fewer mechanical components, making them more reliable and less prone to failure. Manufacturers of the loop ma­terials guarantee their products for up to 25-years, with no maintenance re­quired.
Geothermal heat pumps work toward the preservation of the environment by reducing the environ­mental impacts of electric power gen­eration.
A ground source (geothermal) system consist of a:
• A ground water heat pump
• A closed loop ground heat ex­changer made of high density polyethylene pipe (guaranteed 25- years or more by many man­ufacturers); and
• A low wattage circulating pump(s)
The fluctuating temperatures of fluid from the earth are more stable than air, allowing the equipment to operate at a lower discharge pressure and use fewer kilowatts. The constant earth temperature will heat or cool the fluid running through buried high density polyethylene pipe to provide heating and cooling to a building.
Figure 36: Geothermal energy recovery loop
A geothermal loop can be installed ei­ther horizontally or vertically. Vertical loops require less overall land area to reject (i.e., sink) the excess heat from the building. Horizontal loops require trenches in the ground spanning a larger overall land area.
Although external piping is the re­sponsibility of the installer and/or pip­ing manufacturer, many electric utilities and rural electric cooperatives are offering monetary incentives to in­stall geothermal systems. Utility com­panies offer the incentives because of reduced peak loads that flatten out their demand curve over time, and save them money. These savings are ultimately transferred to the consum­er. See Figure 36 for geothermal en­ergy recovery loop.
WSHP-PRC001-EN 27
Application Considerations
Boiler/Cooling Tower Application
In a boiler/cooling tower application (Figure 37), the closed water-loop, along with multiple water-source heat pumps are utilized in a more conventional manner.
Typically, a boiler is used to maintain closed-loop temperatures above 60 F, and a cooling tower is used to maintain closed-loop temperature below 90 F. All the units function independently, either by adding heat, or rejecting heat, or moving heat from the closed water-loop. Because the heat from a building is being rejected through a cooling tower, the system is more efficient than air cooled sys­tems.
The boiler/cooling tower system pro­vides a low installation cost to the owner when compared to other sys­tems, and is the most common applica­tion. It also allows the owner to add units to the condenser water loop as needed.
Ground Coupled Application
Systems that utilize the ground-coupled (geothermal) design are also applied to a closed water-loop, along with the multiple ground-source heat pumps. With the ground-coupled (geothermal) system, heat is exchanged with the earth by either moving heat into the earth, or absorbing heat from the earth. Water temperature ranges vary from 25 F to 105 F depending on climate, and season. Because the ground-coupled system does not use the fluctuating outside-air temperature, the geothermal heat pumps are capable of using less energy.
The choices in earth-loop coupling consists of a vertical (Figure 38), hor­izontal, or a pond-loop design. Each of these options offer different system design characteristics. The vertical and horizontal loop systems can be designed to provide the same fluid temper­atures under a given set of conditions.
Operating and maintenance cost are lower because an auxiliary electric/fossil fuel boiler and cooling tower are not re­quired to maintain the loop tempera­ture in a properly designed system.
Because the ground loop is made of chemically inert, non-polluting, high density polyethylene pipe, the loop is environmentally responsible. The heat pumps use HCFC-22 refrigerant, which has a low ozone depletion poten­tial. Because the closed-loop system does not require a heat adder, there are no C02 emis­sions. Less power is consumed by the system, thereby reducing secondary emissions from the power plant. Therefore, the ground-coupled system offers advantages not seen by other HVAC system types.
Figure 37: Boiler/cooling tower
application
Figure 38: Vertical bore ground loop
application
Figure 39: Pond loop system
Application Considerations
Open-Loop Design
Ground water from a well can be used to exchange heat
in an open-loop system Figure 39. The ground water is pumped from the well into the geothermal heat pump, where heat is extracted or rejected and then returned to an aquifer. The only change to the ground water is a slight temperature difference. The
rejected water is dumped into a surface well,
lake, or stream, continually removing
water from the aquifer. Alternatively,
a recharge well may be installed to
return the water into the ground.
Open-loop systems use a large amount of water, and can only be economically justified where wells and disposal systems are easy to install.
Operation and benefits are
similar to those for closed-loop
systems. There are, however, several
considerations that should be addressed
prior to installation.
1 Water quality must be acceptable, with minimal suspended solids and proper pH. To help ensure clean water, a straining device may be required.
2 An acceptable way to discharge the significant volume of used water from
the heat pump should be defined. It may be necessary to install a recharge
well to return the water to the aquifer.
Slinky Loop
With the slinky-loop system application Figure 40, groups of water-coupling, pipe coils are submerged several feet below the low water level or within a
horizontal ground trench. This system has all of the
advantages of a vertical bore, or horizontal trench
application, and can be very cost effective
when applied in the proper land region.
With the slinky-loop system design,
some special considerations should be
taken for the installation if a pond application is used.
1 The body of water should be close
to the structure. If the distance
from the water to the building must
accommodate a horizontal field, the
submerged loop would offer no
advantage over a horizontal water-loop
design.
Figure 40: Slinky loop system
be used.
WSHP-PRC001-EN 29
3 The loop should not be placed within a moving body of water that is subject
to flooding.
2 Anti-freeze fluid of at least 20-percent by volume must
Application Considerations
Central Pumping System
Units that employ a central pumping system contain single or dual pumps to fulfill pumping requirements for the entire building system.
The central system’s supply and re­turn lines should be sized to handle the required flow with a minimum pressure drop.
The water-source heat pump (in this case a high efficiency GEH) may in­clude add-on accessories to help aid in system balancing, acoustics and safe­ty requirements. Some of these items may be ordered from the factory, then field installed. Many are provided by the contractor.
1
Hose kits are used to connect the
water supply and return line to the water inlets and outlets. Trane of­fers various hose kit combina­tions to better facilitate system flow balancing. These flexible hoses also aid in the reduction of vibration between the unit and the rig­id central piping system.
A two position isolation valve is often applied to systems which in­corporate variable frequency pumping. This valve is capable of stopping/starting water flow to the unit, which in-turn reduces the pumping requirements for the entire system.
The central system supply and
5
return lines should be sized to
handle the required flow with a minimum pressure drop.
Note: Pipe will sweat if low tem­perature water is below the dew point of the surrounding space. Trane recommends that these lines be insulated to prevent dam­age from condensation when con­denser loop is designed to be below 60 F.
For acoustically sensitive areas, a
6
six-inch deep fiberglass insula­tion is recommended to be field
installed below the horizontal unit. This field supplied insulation should be approximately twice the footprint size of the unit. It pro­vides sound damping of the unit while in operation.
2
The unit’s (item 2) 3/4-inch high
voltage and (item 3) 1/2-inch low
3
voltage connections are located
on the left chamfered corner of the unit. They are de­signed to accept con­duit.
A field supplied line voltage dis-
4
connect should be installed for
branch circuit protection. Check local codes for requirements.
Loading...
+ 114 hidden pages