Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING – Indicates a potentially hazardous situation
!
which, if not avoided, could result in death or serious
injury.
!
CAUTION – Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in
equipment or property-damage-only accidents.
Important!
Equipment is shipped FOB (Free on Board) at the
manufacturer. Therefore, freight claims for damages
against the carrier must be initiated by the receiver.
NOTICE:
Unit contains HCFC (R-22) Refrigerant
Instructions!
Section 608, Paragraph C of the 1990 Clean Air Act states:
Effective July 1, 1992, it shall be unlawful for any person, in course of
maintaining, servicing, repairing, or disposing of an air conditioning system, to
knowingly vent or release any CFC or HCFC refrigerant. Minimal releases (air
purges or refrigerant hoses) associated with good faith attempts to recapture or
recycle are exempt from the ban on venting.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified. The Federal Clean Air Act (Section 608)
sets forth the requirements for handling, reclaiming, recovering and recycling of
certain refrigerants and the equipment that is used in these service procedures.
In addition, some states or municipalities may have additional requirements that
must also be adhered to for responsible management of refrigerants. Know the
applicable laws and follow them.
Product contains fiberglass wool. Disturbing the insulation in this
product during installation, maintenance or repair will expose you to
airborne particles of glass wool fibers and ceramic fibers known to the
state of California to cause cancer through inhalation. Glass wool fibers
may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of
lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the
bill of lading is signed at the jobsite, the unit(s) are now the property of the
SOLD TO party and future freight claims MAY NOT be accepted by the freight
company.
4. Verify that the refrigerant charge has been retained during shipment by use
of gauges. Schrader taps are located external to the cabinet on the 2-ton
through 6-ton equipment.
5. After assuring that charge has been retained, reinstall the schrader caps to
assure that refrigerant leakage does not occur.
CAUTION
Microbial Growth!
Wet interior unit insulation can become an amplification site for
microbial growth (mold), which may cause odors and damage to the
equipment and building materials. If there is evidence of microbial
growth (mold) on the interior insulation, the insulation should be
removed and replaced prior to operating the system.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to
the elements, and to prevent possible IAQ contaminant sources from growing,
the unit should be stored indoors. If indoor storage is not possible, the following
provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent
moisture from standing on the unit(s) surfaces. Wet interior unit insulation
can become an amplification site for microbial growth (mold) which has
been determined to be a cause of odors and serious health related indoor air
quality problems.
4. Store refrigeration units (chassis) units in the normal UP orientation to maintain oil in the compressor. Cabinet configurations may be stored as crated.
5. Do not stack units.
4WSHP-SVN08B-EN
General
Information
Unit Nameplate
The unit nameplate is located at the
front of the unit. It includes the unit
model number, serial number, electrical characteristics, refrigerant charge,
and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors
are located on the compressor shell.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control
operation.
Water-to-Refrigerant Coils
The co-axial water-to-refrigerant heat
exchanger for the 3/4-ton through 3ton equipment is constructed of copper or cupro-nickel (option) for the water section and stainless steel for the
refrigeration section.
The heat exchanger is leak tested to
assure there is no cross leakage between the water and refrigerant gas.
Water Connections
1/2" or 3/4" water connections are located on the chassis’s upper section
and clearly labeled for water-in/out
hose to riser hook-up.
Blower/Motor
The blower and motor is located inside
the unit cabinet. The blower and motor
may be removed from the cabinet
through the chassis opening. After removing the chassis, the blower assembly is strapped into the unit
cabinet through a single metal, flexible bracket. We refer to this bracket as
a housing belly bracket. After detaching one screw at the bottom/front edge
of the bracket, the housing and motor
are free to be lifted from the fan deck.
Sound Attenuation
Sound attenuation is applied as a standard feature in the product design. The
enhanced reduction package includes
a heavy gage base plate, and gasket/
insulation around the compressor enclosure.
An optional deluxe sound reduction
package is also available. It includes a
heavy gage base plate, gasket and insulation around the compressor enclosure, and vibration isolation between
the chassis and cabinet. An additional
dampening treatment is applied
around the compressor enclosure to
achieve greater acoustical reductions.
Controls
The control system offered to control
the unit is a Basic 24 volt control for
the 3/4-ton through 2-ton retrofit
(WPRD) equipment. A 50 VA transformer is factory supplied on this unit
configuration. See wiring diagram on
chassis access panel for field wiring
connection to the 24 volt mechanical
thermostat.
Deluxe 24V Controls
(GET model)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board. The
Trane microprocessor board is factory
wired to a terminal strip to provide all
necessary terminals for field connection. The deluxe board is equipped
with a random start relay, anti-short
cycle timer, brown out protection,
compressor disable, unit safety control, diagnostics and a generic relay
(which may be available for field use).
See page 16 for diagnostic information.
Power wiring is made at the contactor.
The wiring is fed through the left or
right conduit tube, and into the cabinet’s control box (contactor).
ZN510 Controls
(GET option)
Units incorporating the ZN510 control
option design will include a digital
LonTalk
control board will support such options as: random start delay, heating/
cooling status, occupied/unoccupied
mode and fan/filter status.
Power wiring is made at the contactor.
The wiring is fed through the left or
right conduit tube, and into the cabinet’s control box (contactor). See
manual WSHP-IOP-2 for diagnostic information.
Schrader Connections
Connections for the low and high side
of the refrigeration system are located
conveniently on the chassis’ top beneath a sheet metal plate.
TM
certified control board. The
WSHP-SVN08B-EN5
Table 1: Unit weights
Size
009135115
012135115
015175150
018175150
024225195
036225195
0099080
0129585
015110100
018115105
024190180
036200190
Shipping
Weight
with pallet (lb)
Cabinet
Chassis
w/o pallet (lb)
Shipping
Weight
Dimensions/Weights/
Clearance
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
RSD
ALLOW 36" (914 mm)
AT UNIT FRONT FOR
CHASSIS REMOVAL
Figure 1: Mechanical clearances
Unit Location and Clearances
Locate the unit in an indoor area. The
ambient temperature surrounding the
unit must not be less than 45°F. Do not
locate the unit in areas subject to
freezing.
Attention should be given to service
clearance and technician safety. The
unit chassis should be easily removed
from the cabinet in all applications.
There must be enough space for service personnel to perform maintenance or repair. Provide sufficient
room to make water, and electrical
connection(s). Local and national
codes should be followed in providing
electrical power connections. See Fig-ure 1 for mechanical clearances.
NOTE:
RIGHT RISER
LOCATION SHOWN
IN FRONT AND RIGHT
VIEWS.
FRONTRIGHT SIDE
WSHP-SVN08B-EN7
Return Air (hinged)
Acoustical Door
The hinged acoustical door is recessed
into the wall so that the door is flush
with the surface of the wall.
The opening through the wall
for the door assembly must be
centered with the return-air
opening of the unit cabinet.
For full installing instructions
of the return-air acoustical
door, see page 12.
Dimensions
Hinged Acoustical Door
3 1/2” ±3/8”
A
SHEETROCK
B
RETURN AIR OPENING
FLANGE ON CABINET
2“ X 4” STUD
1“ X 1” CLOSED
CELL INSULATION
1 1/4”
+1/2”/-0”
SHEET ROCK
Unit Size
SHEETROCK
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
OPENING
09
012
015
018
024
036
3 1/2” ±3/8”
A
19 1/4”
(489)
23 1/4”
(591)
27 1/8”
(689)
RETURN AIR OPENING
FLANGE ON CABINET
B
44 1/8”
(1121)
45 1/4”
(1149)
54 5/8”
(1387)
2 X 4 STUD
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN AIR
DOOR FLANGE
SHEETROCK
Note:
Finished wall and framing should not
touch the unit cabinetry.
B
CABINET
2“ X 4”
STUD
CABINET
1“ X 1” CLOSED
CELL INSULATION
1 1/4”
+1/2”/-0”
TOP VIEW
A
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR
DOOR FRAME
SHEETROCK
FLOOR
1 1/2” X 2 3/8”
3 1/2” ±3/8”
RETURN-AIR OPENING
FLANGE ON CABINET
2 1/4“
4 5/8“
CABINET
5“
SIDE VIEW
8WSHP-SVN08B-EN
Installation
General Installation Checks
The checklist below is a summary of
the steps required to successfully install a unit. This checklist is intended to
acquaint the installing personnel with
procedures required in the installation
process. It does not replace the detailed instructions called out in the applicable sections of this manual.
1 Remove packaging and inspect the
unit. Check the unit for shipping
damage and material shortage; file
a freight claim and notify appropriate sales representation.
Note: The unit cabinet is packaged
in a wooden crate. A pry bar and/
or hammer will be needed for
packaging removal.
The chassis sits inside a cardboard
tray with an upper box for protection. Typically four chassis will be
shrink-wrapped to a single pallet.
2 Verify the correct model, options
and voltage from the unit nameplate.
3 Verify the installation location of
the unit will provide the required
clearance for proper operation.
4 Remove refrigeration access panel
and inspect the unit. Be certain the
refrigerant tubing has clearance
from adjacent parts.
!
WARNING
Hazardous
Voltage!
Disconnect all electric power,
including remote disconnects and
discharge all motor start/run
capacitors before servicing.
Follow proper lockout/tagout
procedures to ensure the power
can not be inadvertently
energized. Failure to disconnect
power before servicing could
result in death or serious injury.
Main Electrical
5 Verify the power supply complies
with the unit nameplate specifications.
6 Inspect all control panel compo-
nents; tighten any loose connections.
7 Connect properly sized and pro-
tected power supply wiring to a
field-supplied/installed disconnect
switch and to the unit power block
(1TB1) in the unit’s cabinet control
box for equipment.
8 Install proper grounding wires to
an earth ground.
Note: All field-installed wiring must
comply with NEC and applicable local
codes.
Low Voltage Wiring (AC & DC)
Requirements
9 Connect properly sized control wir-
ing to the proper termination
points between the field supplied
thermostat and the terminal plug
in the equipment’s junction box.
WSHP-SVN08B-EN9
Installation
FLOOR
FLOOR
Figure 2: Stacking illustration
3" SWAGE
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24
inches to verify proper center of
gravity lift point. To avoid
dropping of unit, reposition lifting
point if unit is not level. Failure to
properly lift unit could result in
death or serious injury or possible
equipment or property-only
damage.
Unit Placement
If unit cabinet assembly includes factory provided risers, and "no" field
provided between-the-floor riser extensions, please move to Step 1.
Note: Risers are designed to accommodate a maximum of 1 1/2" to 3" expansion and contraction. If the total
calculated riser expansion exceeds 3",
expansion devices must be field provided.
If unit cabinet assembly includes factory provided risers and field provided
between-the-floor riser extensions are
required, install the extensions before
installing the cabinet.
1 Install drain valve, shut-off/balanc-
ing valves, flow indicators and
drain at the base of each supply and
return riser to enable system flushing at start-up, balancing and service/maintenance.
2 Lift cabinet into space while align-
ing it into the 3"swage of the riser
below.
Note: Take extra care as not to scrape
or dent risers during positioning. The
riser should fall approximately 2" into
the 3" swage. This will allow for the
variation in floor-to-floor dimensions,
and keep the riser joints from bottoming out.
3 Level the cabinet.
4 Plumb risers in two planes to as-
sure proper unit operation and condensate drainage.
5 Anchor all units into place.
6 For field provided risers, center the
supply/return stubouts into the unit
expansion slots. The stubouts
should be perpendicular to the cabinet panel.
7 Verify all risers are vertical and that
they penetrate the swaged joint at
least 1". Riser should not be allowed to bottom out.
8 Braze riser joints. Soft solder or
low-temperature alloys should not
be used in this application.
9 If risers are field provided, it is rec-
ommended that the risers be anchored to the building structure
with a minimum of one contact
point. For expansion and contraction reasons, do not fasten risers
rigidly to the building.
10 Seal access holes made through the
cabinet for piping with suitable material to help eliminate air leakage.
11 See page 14 for system flushing.
Water Connection
For vibration isolation, it is recommended that flexible steel braided
hoses be installed instead of hard piping between the vertical risers and the
unit chassis.
• Stainless steel braided flexible
hose with manual circuit-setter
valve
• Stainless steel braided flexible
hose with automatic balancing
valve
Additional accessories, such as a
strainer are recommended for use to
eliminate contaminants from entering
the co-axial water-to-refrigerant heat
exchangers.
10WSHP-SVN08B-EN
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.