Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
August 2013
“E” and later Design Sequence
GER -036, -048, -060, -072, -090, -120, -150, -180, -240,-300
SAFETY WARNING
WSHP-SVX12B-EN
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potentialhazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughlybefore operatingor servicing
this unit.
ATTENTION: Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that couldresult in
equipment or property-damage only
accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handlingof
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all Personal ProtectiveEquipment (PPE)
recommended for the work being undertaken.
ALWAYSreferto appropriate MSDS sheets and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to follow recommendations could result in death
or serious injury.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of nonapproved refrigerants, refrigerant substitutes, or
refrigerant additives could result in death or serious
injury or equipment damage.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged. Failure to
disconnect power and discharge capacitors before
servicing could result in death or serious injury.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers may also cause
respiratory, skin or eye irritation.
Warnings, Cautions and Notices
Introduction
Revision Summary.
WSHP-SVX12B-EN
Corrected dimensions and added center of gravity
information.
Trademarks
Axiom, Precedent, ReliaTel,TOPSS,Tracer, Voyager II,
Trane, and theTrane logo are trademarks or registered
trademarks ofTrane in the United States and other
countries.Trane is a business of Ingersoll Rand. All
trademarks referenced in this document are the
trademarks of their respective owners.
LonTalk is a registered trademark of Echelon Corporation.
NOTICE:
Equipment Damage From Ultraviolet
(UV) Lights!
The manufacturer does not recommend field
installation of ultraviolet lights in its equipment for the
intended purpose of improving indoor air quality. High
intensity C-band ultraviolet light is known to severely
damage polymer (plastic) materials and poses a
personal safety risk to anyone exposed to the light
without proper personal protective equipment.
Polymer materials commonly found in HVAC
equipment that may be susceptible include insulation
on electrical wiring, fan belts, thermal insulation,
various fasteners and bushings. Degradation of these
materials can result in serious damage to the
equipment.
The manufacturer accepts no responsibility for the
performance or operation of our equipment in which
ultraviolet devices were installed outside of the
manufacturer’s factory or its approved suppliers.
WSHP-SVX12B-EN3
Page 4
Table of Contents
Warnings, Cautions and Notices .......... 2
Introduction ........................ 3
Model Number Descriptions .............. 5
General Information ..................... 6
Jobsite Inspection ................... 6
Jobsite Storage ..................... 6
Unit Description ..................... 6
System Input Devices and Functions .... 6
Field installed ONLY Accessories ....... 8
Component Location ................. 9
Dimensions ............................ 10
Unit Clearances .................... 10
Installation ............................. 30
General Installation Checks ........... 30
Main Electrical Power Requirements . . . 30
Foundation for Rooftop Units ......... 30
Ductwork .......................... 31
Roof Curbs ........................ 31
Rigging the Unit .................... 31
Supply/Return Pipe ................. 31
Drain Connection ................... 32
Horizontal Discharge Conversion ...... 32
TCO-A Instructions .................. 33
Field Installed Power Wiring .......... 34
Field Installed Control Wiring ......... 34
Control Power Transformer ........... 34
Standard Warranty ...................58
Extended Warranty ..................58
Electrical Requirements ................. 38
Pre-Start ............................... 45
Space Temperature Averaging ........ 45
Test Modes ........................ 47
Pre-Startup Checklist ................ 52
Start Up ............................... 53
Initial Unit Start-up .................. 53
Water Pressure Drop ................ 54
Maintenance ........................... 55
Preventive Maintenance ............. 55
Troubleshooting ........................ 56
Warranty ............................... 58
4WSHP-SVX12B-EN
Page 5
Model Number Descriptions
G E R E 060 1 1 A 0 1 1 0 D 0 T 0 A 6 0 0 1 1 0 A 0 B 0 0 0 0 0 000
0= Heating and Cooling Circuit
A = Cooling ONLY Circuit
Digit 12 — Blower Configuration
1= Standard Blower
2= Oversized Blower Motor
Digit 13 — Freeze Protection
A = 20 Degree Freezestat B/T
B = 30 Degree Freezestat B/T
Digit 14 — Open Digit
0= Standard Design
S = Design Special
Digit 15 — Supply-Air
Arrangement
D = Down-Flow Supply-Air
Arrangement
(convertible for3-10Ton)
H = Horizontal Supply-Air
Arrangement
(12 1/2 - 25Ton option)
DIGIT 16 — Return-Air
Arrangement
0= Standard Return-Air
Arrangement
Digit 17 — Control Types
R = ReliaTel™ Standalone Controls
T= Tracer™ Communication
Interface
L= LonTalk™ Communication
Interface
Digit 18 — T’stat/Sensor
Location
0= Wall Mounted Location
A = Wall Mounted Sensor with Unit
Mounted Return-Air Smoke
Detector
B = Wall Mounted Sensor with Unit
Mounted Supply-Air Smoke
Detector
C = Wall Mounted Sensor with Unit
Mounted Return-Air/Supply-Air
Smoke Detectors
Digit 19 — Fault Sensors
0= No Fault Sensor
A = Clogged Filter Switch
B = Fan Failure Switch
C = Discharge Air SensingTube
D = Clogged Filter Switch and Fan
Fail
Switch
E =Clogged Filter Switch and
Discharge Air Sensing Tube
F= Fan Fail Switch and Discharge Air
SensingTube
G =Clogged Filter Switch, Fan Fail
Switch and DA SensingTube
Digit 20 — Temperature Sensor
7= High Pressure Control/Frostat/
Crankcase Heater
Digit 21 — Night Setback
0= No Night Setback Relay
N =Night Setback Relay
Note: Option N is used for the Micro
Standalone Controller ONLY.
Digit 22 — Electric Heat Option
0= No Electric Heat
A = 5 kW (1-Phase)
B = 6 kW (3-Phase)
C = 9 kW (3-Phase)
D = 10 kW (1-Phase)
E =12 kW (3-Phase)
F= 14 kW (1-Phase)
G =18 kW (1 and 3-Phase)
J= 23 kW (3-Phase)
K = 27 kW (3-Phase)
N =36 kW (3-Phase)
P =54 kW (3-Phase)
Digit 23 — Unit Mounted
Disconnect
0= No Unit Mounted Disconnect
1= Non-Fused Disconnect
2= Circuit Breaker
0= Standard Factory Configuration
A = Hinged Access Panels
Digit 27 — Paint Color
0= No Paint Selection Available
Digit 28 — Outside Air Option
0= No Outside Air
A = Manual Outside Air Damper
0-25%
B = Motorized Outside Air Damper
0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E =Economizer, Reference Enthalpy
0-100% without Barometric
Relief
F= Economizer, Reference Enthalpy
0-100% with Barometric Relief
G =Economizer, Comparative
Enthalpy 0-100%
without Barometric Relief
H = Economizer, Comparative
Enthalpy 0-100%
with Barometric Relief
Digit 29 — Piping Arrangement
0= Standard Piping Configuration
Digits 30-36 — Does Not Apply
ToThe Rooftop Product
000 0000= Digit 30-36 Does NOT Apply to
the Rooftop Products
Note: Through-the-base electric is a
standard feature on the water-
source rooftop unit.
WSHP-SVX12B-EN5
Page 6
General Information
Jobsite Inspection
Always perform the following checks before accepting a
unit:
•Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
•Verify that the power supply complies with the unit
nameplate specifications.
•Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once thebill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.
•After assuring that charge has been retained, reinstall
the schrader caps to assure that refrigerant leakage
does not occur.
•After assuring that charge has been retained, reinstall
the schrader caps to assure that refrigerant leakage
does not occur.
•Verify that the refrigerant charge has been retained
during shipment by use of gauges. Schrader taps are
located internal to the cabinet.
•After assuring that charge has been retained, reinstall
the schrader caps to assure that refrigerant leakage
does not occur.
Jobsite Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
•If the unit is stored before it is installed.
• The unit is set on the roof curb, and temporary heat is
provided in the building. Isolate all side panel service
entrances and base pan openings (e.g. conduit holes,
supply air/return airopenings, and flue openings) from
the ambient air until the unit is ready for start-up.
The manufacturer will not assume any responsibility for
equipment damage resulting form condensate
accumulation on the unit’s electrical and/or mechanical
components.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and compressor oil, and run
tested for proper control operation.
Unit Nameplate
The unit nameplateis located onthe units’s corner support
just above the main powerentrance access into the control
panel. It includes the unit model number, serial number,
electrical characteristics, refrigerant charge, and other
pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor terminal box.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak
tested to assure there is no cross leakage between the
water tube (copper/cupro-nickel) and refrigerant gas (steel
tube).
The control system offered to control the unit is a
ReliaTel™ Control Module. It may be installed as a
standalone unit control module, or tied to a full building
automation system.
The ReliaTel™Control Module is a microelectronic control
module that is referred to as a Refrigeration Module
(RTRM).The acronym RTRM is used extensively
throughout this document when referring to the control
system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions that govern unit
operation in response to zone temperature, supply air
temperature and/or humidityconditions depending on the
application.The stages of capacity control for these units
is achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory
wired to the respective internal components. RTRM
receives and interprets information from other unit
modules, sensors, remote panels and customer binary
contacts to satisfy the applicable request for cooling.
System Input Devices and Functions
The RTRM must have a mode input in order to operate the
rooftop unit.The flexibility of having several mode
capabilities depends upon the type of sensor and/or
remote panel selected to interface with the RTRM.The
possibilities are; Fan selection ON or AUTO, System
selection HEAT, COOL, AUTO, and OFF.
The descriptions of the following basic input devices used
with the RTRM network are to acquaint the operator with
their function as they interface with the various modules.
Refer to the unit’s electrical schematic for the specific
module connections.
Compressor Disable (CPR1/2)
This input incorporates the low (LPC) of each refrigeration
circuit and can be activated by opening a field supplied
contact installed in series with the LPC.
6WSHP-SVX12B-EN
Page 7
General Information
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 5-continuous seconds during
compressor operation, the compressor for that circuit is
immediately turned OFF. The compressor will not be
allowed to restart for a minimum of 3-minutes should the
LPC close.
If four consecutive open conditions occur during the first
3-minutes of operation, the compressor forthat circuit will
be locked out, a diagnostic communicated to the remote
panel (if installed) and a manual reset will be required to
restart the compressor.
Low Pressure Control
With the ReliaTel module, the low pressure will be
activated when a field supplied contact is opened.
Anytime this circuit is opened for 5-continuous seconds,
the compressor for that circuit is turned off immediately.
The compressor will not be allowed to restart for a
minimum of 3-minutes.
If four consecutive open conditions occur during the first
3-minutes of operation, the compressor will be locked out,
a diagnostic communicated to ICSTM if applicable, and a
manual reset will be required to restart the compressor.
High Pressure Control
The high pressure controls are wired in series between the
compressor outputs on the RTRM and the compressor
contactor coils. If the high pressure control switch opens,
the RTRM senses a lack of current while calling for cooling
and locks the compressor out.
On dual circuit units, if the high pressure control opens,
the compressor on the affected circuit is locked out. A
manual reset for the affected circuit is required.
Economizer Control Actuator ECA (option)
The ECA monitors the mixed-air temperature, return air
temperature, minimum position setpoint (local or
remote), power exhaust setpoint, CO2 setpoint, CO2 and
ambient dry bulb/enthalpy sensor or comparative
humidity (return air humidity against ambient humidity)
sensors, if selected, to control dampers to an accuracy of
± 5% of stroke.The actuator is spring returned to the
closed position any time power is lost to the unit. It is
capable of delivering up to 25-inch pounds of torque and
is powered by 24 VAC.
RTCI-ReliaTel Trane Communication Interface
(option)
This module is used when the application calls for an ICS
building management type control system. It allows the
control and monitoring of the system through an ICS
panel.The module can be ordered from the factory or
ordered as a kit to be field installed. Follow the installation
instruction that ships with each kit when field installation
is necessary.
RTLI-ReliaTel LonTalk Communication
Interface (option)
This module is used when the application calls for either
an ICS building management type control system that is
LonTalk. It allows the control and monitoring of the system
through an ICS panel.The module canbe ordered from the
factory or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field
installation is necessary.
RTOM-ReliaTel Options Module (option)
The RTOMmonitors the supply fanproving, clogged filter,
supply air temperature, exhaust fan setpoint, supply air
tempering, FrostatTM and smoke detector. Refer to
system input devices and functions for operation.
Supply Fan Failure Input (option)
The fan failure switch can be factory or field installed to
sense indoor fan operation. With the FFS-Fan Failure
Switch, if air flow through the unit is not proven by the
differential pressure switch (factory set point 0.07-inch
w.c.) within 40-seconds nominally, the RTRM will shut off
all mechanical operations, lock the system out, send a
diagnostic to ICS, and the service LED will flash.The
system will remain locked out until a reset is initiated
either manually or through ICS.
Clogged Filter Switch (option)
The unit mounted clogged filter switch monitors the
pressure differential across the return air filters. It is
mounted in the filter section and is connected to the
RTOM. A diagnostic service signal is sent to the remote
panel if the pressure differential across the filters isat least
0.5-inch w.c.The contacts will automatically open when
the pressure differential across the filters decreases to
approximately 0.4-inch w.c.The clogged filter output is
energized when the supply fan is operating and the
clogged filter switch has been closed for at least 2minutes.The system will continue to operate regardless of
the status of the filter switch.
Power Exhaust Control (option)
The power exhaust fan is started whenever the position of
the economizer dampers meets or exceed the power
exhaust setpoint when the indoor fan is on.The setpoint
panel is located in the return air section, and is factory set
to 25%.
Evaporator Frost Control (option)
This input incorporates the Frostat control (FOS) of each
refrigeration circuit and can be activated by closing a field
supplied contact installed in parallel with the FOS.
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 5-continuous seconds during
compressor operation, the compressor for that circuit is
immediately turned OFF. The compressor will not be
WSHP-SVX12B-EN7
Page 8
General Information
allowed to restart for a minimum of 3-minutes should the
FOS close.
Smoke Detector Sensor (option)
This sensor provides high limit shutdown of the unit and
requires a manual reset.The sensor is used to detect
smoke due to fire in the air conditioning or ventilation
ducts.
In order for the supply air smoke detector or return air
smoke detector to properly sense smoke in the supply/
return air stream, the air velocity entering the smoke
detector unit must be between 500 and 4000-feet per
minute.
Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as
a standard option on the discharge line of each system.
This standard option provides extra protection to the
compressors against highdischarge temperatures in case
of loss of charge, extremely high ambient and other
conditions which could drive the discharge temperature
higher.
Field installed ONLY Accessories
High Temperature Sensor (BAYFRST002A)
This sensor connects the RTRM Emergency Stop Input
LTB1-5 and LTB1-6 and provides high limitshutdown of the
unit and requires a manual reset.The sensor is used to
detect high temperatures due to firein the air conditioning
or ventilation ducts.The sensor is designed to mount
directly to the sheet metal duct. Each kit contains two
sensors.The return air duct sensor (X13100040010) is set
to open at 135-degrees F. The supply air duct sensor
(X13100040020) is set to open at 240-degrees F.The
control can be reset after the temperature has been
lowered approximately 25-degrees F below the cutout
setpoint.
ElectronicTimeclock (BAYCLCK001A)
This electronic timeclock is designed to control the
occupied/unoccupied switching of up to four rooftop units.
Once the unit(s) has entered an unoccupied status, night
setback temperatures can be controlled by utilizing a
standard zone sensor wired to the RTRM.The timeclock
contains four binary outputs (RE1, RE2, RE3, RE4), a liquid
crystal display (LCD), and four programming keys (Time/
Day Key, Occupied/Unoccupied Program Key, Run Key,
and an Advance/Override Key). An 18 to 30-VAC power
source is required either from one of the units being
controlled or from a separate class-2 power source.
Zone Panel (BAYSENS106A)
This electronic sensor features three system switch
settings (EM HEAT, HEAT, COOL, and OFF) and two fan
settings (ON andAUTO).It is amanual changeover control
with single setpoint capability.
Zone Panel (BAYSENS108A)
This electronic sensorfeatures four systemswitchsettings
(HEAT, COOL, AUTO, OFF) and two fan settings (ON and
AUTO).It is a manual or auto changeovercontrol with dual
setpoint capability. It can be used with a remote zone
temperature sensor BAYSENS017B.
Remote Panel w/o NSB (BAYSENS110A)
This electronic sensorfeatures four systemswitchsettings
(HEAT, COOL, AUTO, and OFF) and two fan settings (ON
and
AUTO)with four system status LED’s. It is a manualor auto
changeover control with dual setpoint capability. It can be
used with a remote zone temperature sensor
BAYSENS017B.
Programmable Zone Sensor (BAYSENS019B)
This 7-day programmable sensor features 2, 3, and 4-
periods for Occupied/Unoccupied programming per day.
If the power is interrupted, the program is retained in
permanent memory. If power is off longer than 2-hours,
only the clock and day may have to be reset.
The zone sensor allows selection of 2, 3, and 4 system
modes (HEAT, COOL,AUTO, and OFF), two fan modes (ON
and AUTO) It has dual temperature selection with
programmable start time capability.
The occupied cooling setpoint ranges between 45 and 98-
degrees F.The heating setpoint ranges between 43 and 96degrees F.
A liquid crystal display (LCD) displays zone temperature,
temperature set points, day of the week, time, and
operational mode symbols.
The option menu is used to enable or disable applicable
functions, (i.e. morning warm-up, economizer minimum
position override during unoccupied status, fahrenheit or
centigrade, supply air tempering, remote zone
temperature sensor, 12/24-hour time display, smart fan,
and computed recovery.
During an occupied period, an auxiliary relay rated for
1.25-amps at 30-volts AC with one set of single pole,
double throw contacts is activated.
Remote Zone Sensor (BAYSENS013C)
This electronic sensor features remote zone sensing and
timed override with override cancellation. It is used with a
Trane Integrated ComfortTM building management
system.
Remote Zone Sensor (BAYSENS014C)
This electronic sensor features single setpoint capability
and timed override with override cancellation. It is used
with aTrane Integrated ComfortTM building management
system.
8WSHP-SVX12B-EN
Page 9
General Information
Remote Zone Sensor (BAYSENS016A)
This bullet type temperature sensor can be used for
outside-air ambient sensing, return air temperature
sensing, supply air temperature sensing, remote
temperature sensing (uncovered).Wiring procedures vary
according to the particular application and equipment
involved. Refer to the unit’s wiring diagrams for proper
connections.
Remote Zone Sensor (BAYSENS017B)
This electronic sensor can be used with BAYSENS106A,
108A, 110A, 019A, 020A, or 021A remote panels.When this
sensor is wired to a BAYSENS019A or BAYSENS020A
remote panel, wiring must be 18 AWG shielded twisted
pair (Belden 8760 or equivalent). Refer to the specific
remote panel for wiring details.
Component Location
1. Controls
2. Compressor/water-to-refrigerant section
3. Air-to-refrigerant coil
4. Filter location
5. Blower and motor location
WSHP-SVX12B-EN9
Page 10
Dimensions
Unit Clearances
10WSHP-SVX12B-EN
Page 11
Figure 1.036 to 048 Clearances
3-4 tons economizer, manual or
motorized fresh air damper
3-4 tons - swing diameter for hinged
door(s) option
Note: All dimensions are in inches/millimeters.Note: All dimensions are in inches/millimeters.
5-6 tons - economizer, manual or motorized fresh air damper
Note: All dimensions are in inches/millimeters.
5-6 tons - swing diameter for hinged door(s) option
Note: All dimensions are in inches/millimeters.
21 3/8”
(543 MM)
17”
(432 MM)
34 5/8”
(879 MM)
Figure 2.060 to 072 Clearances
12WSHP-SVX12B-EN
Page 13
Figure 3.090 Clearances
7½ tons power exhaust
7½ tons swing diameter for hinged door(s) option
Note: All dimensions are in inches/millimeters.
Note: All dimensions are in inches/millimeters.
21 3/8"
543 MM
17"
432 MM
34 5/8"
879 MM
7½ tons manual or motorized fresh air damper
Note: All dimensions are in inches/millimeters.
Dimensions
WSHP-SVX12B-EN13
Page 14
Dimensions
10 tons exhaust
10 tons swing diameter for hinged door(s) option
Note: All dimensions are in inches/millimeters.
Note: All dimensions are in inches/millimeters.
55/8"
(143 MM)
21 5/8"
(549 MM)
ECONOMIZER HOOD
10 tons economizer, manual or motorized fresh air damper
Note: All dimensions are in inches/millimeters.
ECONOMIZER HOOD
BAROMETRIC RELIEF HOOD
7 3/4”
(198 MM)
12”
(304 MM)
16 3/4”
(425 MM)
6 7/8”
(175 MM)
Figure 4.120 Clearances
14WSHP-SVX12B-EN
Page 15
Figure 5.150 - 300 Clearances
When applying economizer to horizontal units, connected ductwork must be run full size to
allow proper operation of economizer damper.
Fresh Air Hood (Horizontal Units)
Economizer - Horizontal Units
Power Exhaust Dimensions
Unit Model # A B C
GERE150-240 19½ 64¾ 39
Dimensions
WSHP-SVX12B-EN15
Page 16
Dimensions
Figure 6.3 to 4-Ton Unit
16WSHP-SVX12B-EN
Page 17
Figure 7.5 -Ton Unit
Dimensions
WSHP-SVX12B-EN17
Page 18
Dimensions
Figure 8.6 -Ton Unit
18WSHP-SVX12B-EN
Page 19
Figure 9.7 1/2-Ton Unit
Dimensions
WSHP-SVX12B-EN19
Page 20
Dimensions
Figure 10. 10 -Ton Unit
20WSHP-SVX12B-EN
Page 21
Figure 11. 12 1/2 and 15-Ton Unit
20 13/16"
529mm
12 5/16"
313mm
23"
584mm
Dimensions
54"
1372mm
(a)See tables in chapter “General Data,” p. 13, for water connection sizes.
26 7/8"
684mm
WSHP-SVX12B-EN21
Page 22
Dimensions
Figure 12. 20-Ton Unit
20 7/8"
530mm
12 1/2"
317mm
24 1/4"
616mm
22WSHP-SVX12B-EN
Page 23
Figure 13. 25-Ton Unit
85 5/16"
2167mm
20 13/16"
529mm
12 5/16"
313mm
Dimensions
54"
64”
1372mm
1626 mm
26 7/8"
264mm
WSHP-SVX12B-EN23
Page 24
Dimensions
Figure 14. 3 to 4-Ton Roofcurb
24WSHP-SVX12B-EN
Page 25
Figure 15. 5, 6 and 7 1/2 -ton roofcurb
20 13/16"
529mm
12 5/16"
313mm
23"
584mm
Dimensions
54"
1372mm
(a)See tables in chapter “General Data,” p. 13, for water connection sizes.
26 7/8"
684mm
WSHP-SVX12B-EN25
Page 26
Dimensions
Figure 16. 10 -Ton Roofcurb
20 7/8"
530mm
12 1/2"
317mm
24 1/4"
616mm
26WSHP-SVX12B-EN
Page 27
Figure 17.12 1/2 to 25-Ton Roofcurb
85 5/16"
2167mm
20 13/16"
529mm
12 5/16"
313mm
Dimensions
54"
64”
1372mm
1626 mm
(a)See tables in chapter “General Data,” p. 13, for water connection sizes.
26 7/8"
264mm
WSHP-SVX12B-EN27
Page 28
Dimensions
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown.
Each of the cables (chains or slings) used to lift the unit
must be capable of supporting the entire weight of the
unit. Lifting cables (chains or slings) may not be of the
same length. Adjust as necessary for even unit lift.
Other lifting arrangements may cause equipment or
property-only damage. Failure to properly lift unit could
result in death or serious injury. See details below.
Figure 18. Corner weight locations and center of
gravity
Center
of Gravity
A
nter of Gravity
Width
Length
Figure 19. Rigging
B
D
Center of Gravity
Table 1.Typical unit weights and point loading data
Net
ModelABCDLength Width
Weight
03648713212111212133.019.0
04853814613412413433.019.0
06067818816415417340.523.0
07270019416915917940.523.0
09079421819418220141.023.0
12094123525123422152.028.0
150180049148141041860.032.0
180184850549342142960.032.0
240200854853645846660.032.0
300190652050943544230.032.0
Corner WeightsCenter of Gravity
Table 2.Net weights for electric heat are as follows
Unit Size23-36 kW54 kW72 kW
GER 150, 180, 240, 30033/2740/3243/34
C
28WSHP-SVX12B-EN
Page 29
Dimensions
Table 3.Option and accessory weights
Option/Accessory Description Net Weight 036-060 Net Weight 072-120 Net Weight 150-180, 300 Net Weight 240
Electric Heat1515--
Economizer H/D263665/8065/80
Motorized Damper203060/7560/75
Manual Damper16263232
Barometric Relief710--
Power ExhaustN/A809595
Oversized Motor5855
Belt Drive Motor (3-phase only)31Standard1010
Hinged Access10122727
Hail Guard1220--
Through the base electrical8132323
Unit Disconnect Switch551010
Unit Circuit Breaker551010
TCI, LCI1111
Frostat1111
Crankcase Heater1111
Smoke Detector, Return77--
Smoke Detector, Supply5555
Clogged Filter Switch1111
Fan Fail Switch1111
Discharge Air Tube3333
Roof curb70115235235
Zone Sensors1111
WSHP-SVX12B-EN29
Page 30
Installation
General Installation Checks
The checklist below is a summary of the steps required to
successfully install a commercial unit.This checklist is
intended to acquaint the installing personnel with what is
required in the installation process. It does not replace the
detailed instructions called out in the applicable sections
of this manual.
•Check the unit for shipping damage and material
shortage; file a freight claim and notify appropriate
sales representation.
•Verify the correct model, options and voltage from the
unit nameplate.
•Verify the installation location of the unit will provide
the required clearance for proper operation.
•Assembleand install the roof curb (if applicable). Refer
to the latest edition of the curb installers guide that
ships with each curb kit.
•Fabricate and installduct work; secure duct work to the
curb.
Factory Installed Economizer
•Ensure the economizer has been pulled out into the
operating position. Refer to the economizer installers
guide for proper position and setup.
•Install all access panels.
Filter Installation
•Each unit ships with 1-inchfilters.The quantity of filters
is determined by unit size. Access to the filters is
obtained by removing the fan access panel.To modify
the unit’s filter rack to accept 2-inch filters, remove the
L-shaped angle attachment screws and rotate the
angles 90-degrees.
•Reinstall the screws and insert new filters. Refer to the
unit Service Facts (shipped with each unit) for filter
requirements.
Note: Do not operate the unit without filters.
Main Electrical Power Requirements
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
•Verify the power supply complies with the unit
nameplate specifications.
•Inspect all control panel components; tighten any
loose connections.
•Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect switch
and to themain power terminal block (HTB1) in the unit
control panel.
•Install proper grounding wires to an earth ground.
Note: All field-installed wiring must comply with NEC
and applicable local codes.
Electric Heat Requirements
•Verify that the power supply complies with the electric
heater specifications on the unit and heater nameplate.
•Inspect the heater junction box and control panel;
tighten any loose connections.
•Check electric heat circuits for continuity.
Low Voltage Wiring (AC & DC) Requirements
•Install the zone thermostat, with or without switching
subbase.
•Connect properly sized control wiring to the proper
termination points between the zone thermostat and
the unit control panel.
Foundation for Rooftop Units
If the unit is installed at ground level (horizontal design),
elevate it above the snow line.Provideconcrete footings at
each support location with a full perimeter support
structure or a slab foundationfor support. Refer toTable 1,
p. 28 for the unit’s operating and point loading weights
when constructing a footing foundation.
If anchoring is required, anchor the unit to the slab using
hold down bolts or isolators. Isolators should be installed
to minimize the transmission of vibrations into the
building.
For rooftop applications, ensure the roof is strong enough
to support the combined unit and support structural
weight.
30WSHP-SVX12B-EN
Page 31
WARNING
Risk of Roof Collapsing!
Confirm with a structural engineer that the roof
structure is strong enough to support the combined
weight of the roofcurb and the unit. Refer to Table 1,
p. 28 and Table 3, p. 29 for typical unit and curb
weights. Failure to ensure proper structural roof
support could cause the roof to collapse, which could
result in death or serious injury and property damage.
If anchoring is required, anchor the unit to the roof with
hold-down bolts or isolators.
Check with the contractor for proper waterproofing
procedures.
Installation
Note: For sound consideration, cut only the holes in the
roof deck for the duct work penetrations. Do not cut
out the entire roof deck within the curb perimeter.
If Curb Accessory Kit is not used:
The duct work can be attached directly to the factory
provided flanges around the unit’s supply and return air
openings. Be sure to use flexible duct connections at the
unit.
For built-up curbs supplied by others, gaskets must be
installed around the curb perimeter flange and the supply
and return air opening flanges.
Note: For sound consideration, cut only the holes in the
roof deck for the duct work penetrations. Do not cut
out the entire roof deck within the curb perimeter.
Ductwork
When attaching the ductwork to the unit, provide a
watertight flexible connector at the unit to prevent
operating sounds from transmitting through the
ductwork.
Elbows with turning vanes or splitters are recommended
to minimize air noise due to turbulence and to reduce static
pressure.
All outdoor ductwork between the unit and the structure
should be weather proofed after installation is complete.
See dimensional data on pages 13 through 16 for
connection sizes.
Roof Curbs
The roof curbs for these units (down flow) consists of a full
perimeter enclosure to support the unit. Before installing
any roof curb:
•Verify that the correct roof curb is applied to the unit
•Verifythat the roofcurb includes thenecessary gaskets
and hardware.
•Verify that the proposed installation location provides
the required clearance for proper unit operation.
•Insure that the curb is level and square.The topsurface
of the curbmust be true to assure an adequate curb-tounit seal.
Step-by-step curb assembly and installation instructions
ship with each accessory roof curb kit. Follow the
instructions carefully to assure proper fit-up whenthe unit
is set into place.
To assure proper condensate flow during operation, the
unit (and curb) must be level.
If the unit is elevated, a field constructed catwalk around
the unit is strongly recommended to provide easy access
for unit maintenance and service.
Recommendations for installing the supply air and return
air ductwork joining the roof curb are included in the curb
instruction booklet. See dimensional data on pages 17
through 20 for roof curb sizing.
Rigging the Unit
A rigging illustration and center-of-gravity dimensional
data table are shown in Table 1, p. 28. Refer to the typical
unit operating weights table before proceeding.
1. Remove the two screws from each end of the unit that
secures the wooden shipping top.Remove the wooden
top and metal retaining brackets. Remove the
protective covering from around the unit.
2. Rig the unit. Attach adequate strength lifting slings to
all four lifting brackets in the unit base rail. Do not use
cables, chains, or slings except as shown.
3. Install a lifting bar, (as shown in the illustration), to
protect the unit, and to facilitate a uniform lift.The
minimum distance between the lifting hook and the
top of the unit should be 7-feet.
4. Test lift the unit to ensure it is properly rigged and
balanced. Make any necessary rigging adjustments.
5. Lift the unit and position it into place.
6. Downflow units; align the base rail of the unit with the
curb rail while lowering the unit onto the curb. Make
sure that the gasket on the curb is not damaged while
positioning the unit.
7. Set the unit onto the curb; check for levelness.
8. Ensure unit-to-curb seal is tight and without buckles or
cracks.
9. Install and connect a condensate drain line to the
evaporator drain connection.
Supply/Return Pipe
Connect the supply and return line to the water inlet and
outlet of the unit. On open loop systems, an in-line strainer
or mesh screen should be used to eliminate contaminants
from entering the water-to refrigerant heat exchanger.
An isolation valve, p/t plugs and automatic balancing
device are alsorecommended to separatethe closed/open
loop from the mechanical device.
WSHP-SVX12B-EN31
Page 32
Installation
Drain Connection
An evaporator condensate drain connection is provided
on each unit.The condensate drain pan is factory installed
to drain condensate to the back side of the unit. It can be
converted to drain condensate out of the front of the unit
or through the base
To convert drain condensate out the front of the
unit:
1. Remove the evaporator access panel and supply air
access panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit and
rotate 180°.
4. Slide the condensate drain pan back into the unit,align
the drain with the grommeted opening in the rear
support panel and push until the coupling is seated in
the grommet.
5. Replace the front support panel by aligning the panel
with tabs in the raceway. Align the condensate drain
pan support in the grommeted hole as the panel is put
in place.
6. Replace the evaporator access paneland the supply air
access panels.
To convert drain condensate through the base of the
unit:
1. Remove the evaporator access panel and supply air
access panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit.
4. Place on a level surface in the position it was removed
from the unit.
5. Remove the plug knockout in the bottom of the drain
pan to convert it to through the base drainage.
6. Plug theoriginal condensate drain opening with a field
supplied 3/4-inch NPT plug.
7. Slide the condensate drain pan back into the unit, align
the drain support with the grommeted opening in the
rear support panel and push until the supportis seated
in the grommet.
8. Replace the front support panel by aligning the panel
with tabs in the raceway.Align the plugged condensate
drain pan coupling in thegrommeted hole as the panel
is put in place.
9. Replace evaporator access panel and supply air access
panels.
10. A condensate trap must be installed at the unit due to
the drain connection being on the negative pressure
side of the fan. Install the p-trap using the guidelines
below.
A condensate drain line must be connected to the p-trap.
Pitch the drain lines at least 1/2-inch for every 10-feet of
horizontal run to assure proper condensate flow. Do not
allow the horizontal run to sag causing a possible doubletrap condition which could result in condensate backup
due to air lock.
Figure 20.
Horizontal Discharge Conversion
Units are factory shipped in the downflow discharge
configuration, but can be field converted to a horizontal
discharge configuration. Some, but not all units require a
different thermal cut-out limit switch (which is wire tied
near the terminal block in the heater compartment) if the
horizontal discharge configuration is used.
The following units require a limit switch change out for
the horizontal discharge.The additional limit switch is
shipped attached to the blower housing.
If any of the units listed in the following list are installed in
the downflow discharge configuration, remove the wire
tiedTCO-A (located near the terminal block in the heater
compartment) and discard.
Conversion 3 through 5-Ton Units
To convert a unit from down flow to horizontal discharge,
1. Remove the return and supply duct covers.
2. Apply gasket to the supply duct cover as shown in
Figure 21, p. 32.
Figure 21. Gasket Installation
32WSHP-SVX12B-EN
Page 33
Installation
3. Position duct covers. Rotate the supply duct cover 90degrees to allow it to be slid into the supply opening.
Figure 22. Duct cover with gasket installed
Note: If the unit is equipped with a return air smoke
detector, refer to the field conversion for horizontal
discharge before installing the return air duct
cover.
4. Slide the duct covers into the duct openings until the
end ward edge of the duct cover engages with the two
retaining clips on theduct flanges. Secure the outward
edge of each duct cover with two screws.
Note: If unit should include a limit switch change out,
proceed to theTCO-A instruction sheet on “TCO-A
Instructions,” p. 33
Figure 23. Installing duct cover
.
Conversion 6 through 10-Ton Units
To convert a unit from down flow to horizontal discharge,
1. Remove the return and supply duct covers.
2. Apply gasket to the return duct cover as shown in
Figure 22.
3. Position the duct covers as shown below.The supply
duct cover is installed over the down flow return
opening by engaging one side of the panel under a
retaining angle and securing the other side with three
screws.
Note: If the unit is equipped with a return air smoke
detector, refer to the field conversion for horizontal
discharge before installing the return air duct
cover.
4. Slide return duct cover into supply openings until end
ward edge of the duct cover engages with the two
retaining clips on theduct flanges. Secure the outward
edge of each duct cover with two screws.
Note: If unit should include a limit switch change out,
proceed to theTCO-A instruction sheet on this
page.
TCO-A Instructions
If the unit being installed is listed in the following table,
and is equipped with the corresponding model number of
factory installed electric heater package in the table, the
limit controlTCO-A must be replace with the extra limit
control shipped in the heater compartment. ReplaceTCOA following the instruction in steps 1 through 4. If the unit
being installed does not have a factory installed electric
heater package, or is equipped with a factory installed
electric heater model that does not correspond to models
listed below, skip steps 1 through 4, and go on to the next
step in the installation process.
Note: See Table 7, p. 40 for electric heater kit part #s and
equipment models.
1. Remove the heater section access panel and open the
electric heater front panel.
2. TCO-A is the limit control located in the central part of
the heater mounting plate and that is located on the
bottom of the two heater element assemblies.To
replace this device, first remove the two wires
connected to the terminals. Next, remove the two
screws which secure it to the heater element mounting
plate. OnceTCO-A has been removed from the heater
element mounting plate, discard this device.
3. Obtain the replacement TCO-A which is secured by a
wire tie near the electric heater terminal block in the
heater compartment. Attach it to the heater element
mounting plate with the twoscrews that were removed
in step 2 above. Connect the two wires that were
unhooked in step 2 to the terminals on the newTCO-A.
Refer to the heater package wiring diagram to assure
that the wiring is connected properly.
4. Close the electric heater dead front panel and replace
heat section access panel.
WSHP-SVX12B-EN33
Page 34
Installation
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Verify that the power supply available is compatible with
the unit’s nameplate.The available supply power must be
within 10% of the rated voltage stamped on the nameplate.
Use only copper conductors to connect the power supply
to the unit.
Figure 24. Electrical entrance
Main Unit Power Wiring
1. If the unit is NOT equipped with an optional factory
installed non-fused disconnect switch or circuit
breaker, a field supplied disconnect switch must be
installed at or near the unit in accordance with the
National Electric Code (NEC latest edition).
2. Location of the applicable electric service entrance
may be found in
3. Complete the unit’s power wiring connections onto
either; the main terminal wire connectors inside the
unit control panel, the factory mounted non-fused
disconnect switch (UCD) orcircuit breaker (UCB). Refer
to the customer connection diagram that is shipped
with the unit for specific termination points.
4. Provide proper grounding for the unit in accordance
with the local and national codes.
Figure 24, p. 34.
Field Installed Control Wiring
An overall layout of the various control options available
with the required number of conductors for each control
device may be found on Figure 25, p. 35 and Figure 26,
p. 36.
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.
34WSHP-SVX12B-EN
Control PowerTransformer
The 24-volt control power transformersare to beused only
with the accessories called out in this manual.
Transformers rated greater than 50VA are equipped with
internal circuit breakers. If a circuit breaker trips, turn OFF
all power to the unit before attempting to reset it.
Page 35
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Figure 25.
Installation
The transformer is located in the control panel.The circuit
breaker is located on the left side of the transformer and
can be reset by pressing in on the black reset button.
WSHP-SVX12B-EN35
Page 36
Installation
Figure 26.
36WSHP-SVX12B-EN
Page 37
Installation
Controls Using 24 VAC
Before installing any wire, refer to the electrical access
locations in Figure 24, p. 34.
1. Use copper conductors unless otherwise specified.
2. Ensure thatthe AC control wiring between the controls
and the unit’s termination point does not exceed three
(3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3-ohms per conductor may
cause component failure due to insufficient AC
voltage supply.
3. Check all loads and conductors for grounds, shorts,
and mis-wiring.
4. Do not run the AC low voltage wiring in the same
conduit with the high voltage power wiring.
5. Route low voltage wire per Figure 27 below.
Figure 27.Wire Routing
Note: Resistancein excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
2. Ensure that the wiring between controls and the unit’s
termination point does not exceed two and a half (2.5)
ohms/conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
4. Route low voltage wiring per Figure 27.
Table 5.DC conductors; zone sensor module wiring
Distance from unit to
Control
0-150 feet22 gauge
151-240 feet20 gauge
241-385 feet18 gauge
386-610 feet16 gauge
611-970 feet14 gauge
Recommended Wire
Size
Table 4.24V AC conductors
Distance from unit
to Control
000-460 feet18 gauge
461-732 feet16 gauge
733-1000 feet14 gauge
Recommended Wire
Size
Controls using DC Analog Input/Outputs
(Standard LowVoltage Multi-conductor Wire)
Before installing any connecting wire between the unit
utilizing a DC analog input/output signal,
refer to Figure 24, p. 34 for electrical access locations
provided on the unit.
1. Review Table 5, it lists the conductor sizing guidelines
that must be followed when interconnecting the DC
binary output devices and the system components
utilizing a DC analog input/output signal to the unit.
WSHP-SVX12B-EN37
Page 38
Electrical Requirements
Table 6.Electrical perfomance
Model No. Unit Volts
208/60/124.618.6105.016.000.75129.345
230/60/124.618.6105.016.000.75129.345
GERE036
GERE048
GERE060
GERE072
GERE090
GERE120
208/60/318.513.588.015.001121.935
230/60/318.513.588.015.001121.935
460/60/38.96.439.012.501110.515
575/60/36.85.134.011.70118.115
208/60/130.723.1134.017.601136.550
230/60/130.723.1134.017.601136.550
208/60/321.016.091.015.001125.040
230/60/321.016.091.015.001125.040
460/60/39.67.146.012.501111.415
575/60/37.35.637.011.70118.715
208/60/135.227.6158.017.601142.160
230/60/135.227.6158.017.601142.160
208/60/323.118.1137.015.001127.645
230/60/323.118.1137.015.001127.645
460/60/311.59.062.012.501113.820
575/60/38.56.850.011.701110.215
208/60/327.422.4149.015.001133.050
230/60/327.422.4149.015.001133.050
460/60/313.110.675.012.501115.825
575/60/39.27.754.011.501111.115
208/60/328.722.4149.016.302134.350
230/60/328.722.4149.016.302134.350
460/60/313.710.675.013.102116.425
575/60/310.17.754.012.402112.015
208/60/328.625.0164.013.601134.950
230/60/328.625.0164.013.601134.950
460/60/313.912.2100.011.701117.025
575/60/310.49.078.011.401112.720
208/60/334.425.0164.019.403140.760
230/60/334.425.0164.019.403140.760
460/60/316.812.2100.014.603119.930
575/60/312.49.078.013.403114.720
208/60/326.618.1137.028.503.6149.260
230/60/326.618.1137.028.503.6149.260
460/60/313.39.062.024.303.6124.630
575/60/311.16.850.024.303.6119.625
Total
Unit FLA
Comp
RLA (ea)
Comp
LRA (ea)
No. of
Compres.
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
38WSHP-SVX12B-EN
Page 39
Table 6.Electrical perfomance
Electrical Requirements
Model No. Unit Volts
208/60/333.022.4149.0210.603161.080
230/60/333.022.4149.0210.603161.080
460/60/315.410.675.024.803128.735
GERE150
GERE180
GERE240
GERE300
575/60/311.87.954.023.903121.725
208/60/339.122.4149.0216.705167.180
230/60/339.122.4149.0216.705167.180
460/60/318.210.675.027.605131.540
575/60/314.07.954.026.105123.930
208/60/335.625.0164.0210.603166.990
230/60/335.625.0164.0210.603166.990
460/60/317.312.5100.024.803132.945
575/60/314.210.378.023.903127.135
208/60/341.725.0164.0216.705173.090
230/60/341.725.0164.0216.705173.090
460/60/320.112.5100.027.605135.745
575/60/316.410.378.026.105129.335
208/60/355.839.1267.0216.7051104.7125
230/60/355.839.1267.0216.7051104.7125
460/60/324.917.3142.027.605146.560
575/60/321.515.4103.026.105140.850
208/60/356.739.1267.0217.607.51105.6125
230/60/356.739.1267.0217.607.51105.6125
460/60/325.917.3142.028.607.5147.560
575/60/322.415.4103.027.007.5141.750
208/60/363.339.1267.0224.207.51112.2150
230/60/363.339.1267.0224.207.51112.2150
460/60/329.618.6103.0211.007.5152.970
575/60/324.415.4160.029.007.5143.750
Total
Unit FLA
Comp
RLA (ea)
Comp
LRA (ea)
No. of
Compres.
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
WSHP-SVX12B-EN39
Page 40
Electrical Requirements
Table 7.Electrical Perfomance for units with electric heat (single point connection)
Standard Indoor MotorOversized Indoor Motor
Unit Model
Number
Heater Model
Number
208 Volt Single Phase
BAYHTRE105*18.33.8152.160——
GERE036
GERE048
GERE060
BAYHTRE110*36.17.5274.480——
BAYHTRE114*50.010.4291.8100——
BAYHTRE105*18.33.8159.470——
BAYHTRE110*36.17.5281.690——
BAYHTRE114*50.010.4299.0100——
BAYHTRE118*63.513.22115.9125——
BAYHTRE105*18.33.8165.080——
BAYHTRE110*36.17.5287.2100——
BAYHTRE114*50.010.42104.6110——
BAYHTRE118*63.513.22121.5125——
230 Volt Single Phase
BAYHTRE105*20.85.0155.360——
GERE036
GERE048
GERE060
BAYHTRE110*41.710.0281.490——
BAYHTRE114*57.513.82101.1110——
BAYHTRE105*20.85.0162.580——
BAYHTRE110*41.710.0288.6100——
BAYHTRE114*57.513.82108.4110——
BAYHTRE118*73.317.62128.1150——
BAYHTRE105*20.85.0168.190——
BAYHTRE110*41.710.0294.2110——
BAYHTRE114*57.513.82114.0125——
BAYHTRE118*73.317.62133.7150——
208 Volt Three Phase
BAYHTRE306*12.54.5137.545——
GERE036
GERE048
GERE060
GERE072
GERE090
BAYHTRE312*25.09.0253.160——
BAYHTRE318*36.413.1267.470——
BAYHTRE306*12.54.5140.650——
BAYHTRE312*25.09.0256.360——
BAYHTRE318*36.413.1270.580——
BAYHTRE306*12.54.5143.350——
BAYHTRE312*25.09.0258.970——
BAYHTRE318*36.413.1273.180——
BAYHTRX323*48.017.3287.690——
BAYHTRW309A6.818.9156.67057.970
BAYHTRW318A13.537.5179.99081.290
BAYHTRW327A20.356.32103.4110104.7110
BAYHTRW336A27.074.92126.6150127.9150
BAYHTRU309A6.818.9158.47064.280
BAYHTRU318A13.537.5181.79087.5100
BAYHTRU327A20.356.32105.3110111.1125
BAYHTRU336A27.074.92128.5150134.3150
Electric Heat
Amps
Electric Heat kWControl
Stages
Mimimum
Circuit
Ampacity
Overcurrent
Max
Protection
Mimimum
Circuit
Ampacity
——
Max
Overcurren
t Protection
40WSHP-SVX12B-EN
Page 41
Table 7.Electrical Perfomance for units with electric heat (single point connection)
Standard Indoor MotorOversized Indoor Motor
Unit Model
Number
GERE120
GERE150
GERE180
GERE240
GERE300
Heater Model
Number
BAYHTRB318A13.537.5196.1100——
BAYHTRB327A20.356.32119.7125——
BAYHTRB336A27.074.92142.9150——
BAYHTRB354A40.6112.72190.1200——
AYDHTRK318/
AYHHTRM318
AYDHTRK336/
AYHHTRM336
AYDHTRK354/
AYHHTRM354
AYDHTRK318/
AYHHTRM318
AYDHTRK336/
AYHHTRM336
AYDHTRK354/
AYHHTRM354
AYDHTRL336/
AYHHTRN336
AYDHTRL354/
AYHHTRN354
AYDHTRK372/
AYHHTRN372
AYDHTRL336/
AYHHTRN336
AYDHTRL354/
AYHHTRN354
AYDHTRK372/
AYHHTRN372
230 Volt Three Phase
BAYHTRE306*14.46.0139.945——
GERE036
GERE048
GERE060
GERE072
GERE090
BAYHTRE312*28.912.0258.060——
BAYHTRE318*41.917.4274.380——
BAYHTRE306*14.46.0143.050——
BAYHTRE312*28.912.0261.170——
BAYHTRE318*41.917.4277.480——
BAYHTRE306*14.46.0145.660——
BAYHTRE312*28.912.0263.870——
BAYHTRE318*41.917.4280.080——
BAYHTRX323*55.323.0296.8100——
BAYHTRW309A9.021.7160.17061.470
BAYHTRW318A18.043.3187.19088.4100
BAYHTRW327A27.065.02114.2125115.5125
BAYHTRW336A36.086.62141.3150142.6150
BAYHTRU309A9.021.7161.98067.780
BAYHTRU318A18.043.3189.010094.8100
BAYHTRU327A27.065.02116.0125121.8125
BAYHTRU336A36.086.62143.1150148.9150
Electric Heat
Amps
37.513.51107.9110114.0125
74.927.02154.6175160.7175
112.440.52201.5225207.6225
37.513.51113.7125119.8125
74.927.02160.5175166.6175
112.440.52207.4225213.5225
74.927.02198.3200199.2200
112.440.52245.2250246.1250
149.954.02292.1300293.0300
74.927.02205.8225——
112.440.52252.7300——
149.954.02299.6300——
Electric Heat kWControl
Stages
Mimimum
Circuit
Ampacity
Overcurrent
Electrical Requirements
Max
Protection
Mimimum
Circuit
Ampacity
Max
Overcurren
t Protection
WSHP-SVX12B-EN41
Page 42
Electrical Requirements
Table 7.Electrical Perfomance for units with electric heat (single point connection)
Standard Indoor MotorOversized Indoor Motor
Unit Model
Number
GERE120
GERE150
GERE180
GERE240
GERE300
Heater Model
Number
BAYHTRB318A18.043.31103.4110——
BAYHTRB327A27.065.02130.4150——
BAYHTRB336A36.086.62157.5175——
BAYHTRB354A54.0129.92211.6225——
AYDHTRK318/
AYHHTRM318
AYDHTRK336/
AYHHTRM336
AYDHTRK354/
AYHHTRM354
AYDHTRK318/
AYHHTRM318
AYDHTRK336/
AYHHTRM336
AYDHTRK354/
AYHHTRM354
AYDHTRL336/
AYHHTRN336
AYDHTRL354/
AYHHTRN354
AYDHTRK372/
AYHHTRN372
AYDHTRL336/
AYHHTRN336
AYDHTRL354/
AYHHTRN354
AYDHTRK372/
AYHHTRN372
460 Volt Three Phase
BAYHTRE406*7.26.0119.520——
GERE036
GERE048
GERE060
GERE072
GERE090
BAYHTRE412*14.412.0228.530——
BAYHTRE418*20.917.4236.640——
BAYHTRE406*7.26.0120.425——
BAYHTRE412*14.412.0229.430——
BAYHTRE418*20.917.4237.540——
BAYHTRE406*7.26.0122.825——
BAYHTRE412*14.412.0231.835——
BAYHTRE418*20.917.4239.940——
BAYHTRX423*27.723.0248.450——
BAYHTRW409A9.010.8129.33529.935
BAYHTRW418A18.021.7142.84543.445
BAYHTRW427A27.032.5256.36056.960
BAYHTRW436A36.043.3269.97070.580
BAYHTRU409A9.010.8130.53533.440
BAYHTRU418A18.021.7144.05046.950
BAYHTRU427A27.032.5257.56060.470
BAYHTRU436A36.043.3271.18074.080
Electric Heat
Amps
43.318.01115.1125121.2125
86.636.02169.3175175.4200
129.954.02223.4225229.5250
43.318.01121.0125127.1150
86.636.02175.1200181.2200
129.954.02229.2250235.3250
86.636.02212.9225213.8225
129.954.02267.1300268.0300
173.272.02321.2300322.1300
86.636.02220.4225——
129.954.02274.6300——
173.272.02328.7300——
Electric Heat kWControl
Stages
Mimimum
Circuit
Ampacity
Overcurrent
Max
Protection
Mimimum
Circuit
Ampacity
Max
Overcurren
t Protection
42WSHP-SVX12B-EN
Page 43
Table 7.Electrical Perfomance for units with electric heat (single point connection)
Standard Indoor MotorOversized Indoor Motor
Unit Model
Number
GERE120
GERE150
GERE180
GERE240
GERE300
Heater Model
Number
BAYHTRB418A18.021.7151.660——
BAYHTRB427A27.032.5265.170——
BAYHTRB436A36.043.3278.780——
BAYHTRB454A54.065.02105.7110——
AYDHTRK418/
AYHHTRM418
AYDHTRK436/
AYHHTRP436
AYDHTRK454/
AYHHTRM454
AYDHTRK418/
AYHHTRM418
AYDHTRK436/
AYHHTRP436
AYDHTRK454/
AYHHTRM454
AYDHTRL436/
AYHHTRN436
AYDHTRL454/
AYHHTRN454
AYDHTRK472/
AYHHTRN472
AYDHTRL436/
AYHHTRN436
AYDHTRL454/
AYHHTRN454
AYDHTRK472/
AYHHTRN472
575 Volt Three Phase
BAYHTREW06*5.86.0115.320——
GERE036
GERE048
GERE060
GERE072
GERE090
GERE120
BAYHTREW12*11.512.0222.525——
BAYHTREW18*16.717.4229.030——
BAYHTREW06*5.86.0116.020——
BAYHTREW12*11.512.0223.125——
BAYHTREW18*16.717.4229.630——
BAYHTREW06*5.86.0117.520——
BAYHTREW12*11.512.0224.625——
BAYHTREW18*16.717.4231.135——
BAYHTRXW23*22.123.0237.840——
BAYHTRWW18A18.017.3132.83533.735
BAYHTRWW27A27.026.0243.64544.545
BAYHTRWW36A36.034.6254.46055.360
BAYHTRUW18A18.017.3134.33536.340
BAYHTRUW27A27.026.0245.15047.150
BAYHTRUW36A36.034.6256.06058.060
BAYHTRBW18A18.017.3141.245——
BAYHTRBW36A36.034.6262.970——
BAYHTRBW54A54.052.0284.690——
Electric Heat
Amps
21.718.0155.86058.660
43.336.0282.89085.690
65.054.02109.9110112.7125
21.718.0160.17062.970
43.336.0287.19089.990
65.054.02114.2125117.0125
43.336.02100.7110101.7110
65.054.02127.8150128.8150
86.672.02154.8175155.8175
43.336.02107.0110——
65.054.02134.1150——
86.672.02161.1175——
Electric Heat kWControl
Stages
Mimimum
Circuit
Ampacity
Overcurrent
Electrical Requirements
Max
Protection
Mimimum
Circuit
Ampacity
Max
Overcurren
t Protection
WSHP-SVX12B-EN43
Page 44
Electrical Requirements
Table 7.Electrical Perfomance for units with electric heat (single point connection)
Standard Indoor MotorOversized Indoor Motor
Unit Model
Number
GERE150
GERE180
GERE240
GERE300
Heater Model
Number
AYDHTRKW18/
AYHHTRMW18
AYDHTRKW36/
AYHHTRMW36
AYDHTRKW54/
AYHHTRMW54
AYDHTRKW18/
AYHHTRMW18
AYDHTRKW36/
AYHHTRMW36
AYDHTRKW54/
AYHHTRMW54
AYDHTRLW36/
AYHHTRNW36
AYDHTRLW54/
AYHHTRNW54
AYDHTRKW72/
AYHHTRNW72
AYDHTRMW36/
AYHHTRMW36
AYDHTRLW54/
AYHHTRNW54
AYDHTRKW72/
AYHHTRNW72
Electric Heat
Amps
17.318.0143.34545.550
34.636.0264.97067.170
52.054.0286.79088.990
17.318.0148.75050.960
34.636.0270.38072.580
52.054.0292.110094.3100
34.636.0284.09084.990
52.054.02105.8110106.7110
69.372.02127.4150128.3150
34.636.0286.990——
52.054.02108.7110——
69.372.02130.3150——
Electric Heat kWControl
Stages
Mimimum
Circuit
Ampacity
Overcurrent
Max
Protection
Mimimum
Circuit
Ampacity
Max
Overcurren
t Protection
44WSHP-SVX12B-EN
Page 45
Pre-Start
ZSMREMOTE SENSORS
#1#2#3#4
1
2
11112222
REMOTE SENSOR
2#1#
REMOTE SENSOR
REMOTE SENSOR
#3
REMOTE SENSOR
#4
ZSM
TERMINAL
#1
TERMINAL
#2
ZSM
REMOTE SENSORS
2
1
21
ZSM
#1
2112
TERMINAL
#1
ZSMZSM
TERMINAL
#2
#2#3
REMOTE
SENSOR
#1
REMOTE
SENSOR
#2
REMOTE
SENSOR
#3
REMOTE
SENSOR
#4
REMOTE
SENSOR
#5
REMOTE
#6
SENSOR
SENSOR
REMOTE
#7
SENSOR
REMOTE
#8
SENSOR
#9
REMOTE
#4
21
#6#5
121 2
12
#7
2112
#8#9
REMOTE SENSORS
2
1
21
ZSM
#1
21
TERMINAL
#1
MSZMSZ
TERMINAL
#2
#2
#1#2
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS017*, at least four
sensors are required to accomplish space temperature
averaging.
Figure 28. Example 1
Example #2 illustrates three sensors squared in a series/
parallel circuit. Using BAYSENS032*, two sensors are
required to accomplish space temperature averaging.
Figure 29. Example 2
Example #1 illustrates two series circuits with two sensors
in each circuit wired in parallel.The square of any number
of remote sensors require.
Example #3 illustrates the circuit required for this sensor.
Figure 30. Example 3
WSHP-SVX12B-EN45
Page 46
Pre-Start
Table 8 lists the temperature versus resistance coefficient
for all sensors.
Table 8.Temp vs. Resistance
Degrees
F
-20170.14522.85
-15143.55019.96
-10121.45517.47
-5103.06015.33
087.566513.49
574.657011.89
1063.807510.50
1554.66809.297
2046.94858.247
2540.40907.330
3034.85956.528
3530.181005.824
4026.22
*Temperature vs. resistance coefficient is negative
Nominal
Resistance
K-Ohms
Degrees
F
Nominal
Resistance
K-Ohms
Voltage Imbalance
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from
the average voltage.
Example: If the voltage readings of the supply power
measured 221, 230 and 227, the average volts would be:
221+230+227
3
= 226 Avg.
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
226 - 221
100 x
226
= 2.2%
The 2.2% imbalance in this example exceeds the
maximum allowable imbalance of 2.0%.This much
imbalance between phases can equal as much as a 20%
current imbalance with a resulting increase in motor
winding temperatures that will decrease motor life. If the
voltage imbalance is over 2%, notify the proper agencies
to correct the voltage problem before operating this
equipment.
Electrical Phasing (Three Phase Motors)
The compressor motor(s) and the supply fan motor are
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
internally connected for the proper rotation when the
incoming power supply is phased as A, B, C.
Proper electrical supply phasing can be quickly
determined and corrected before starting the unit by an
instrument such as an Associated Research Model 45
Phase Sequence Indicator and following the steps below:
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
Hazardous Voltage!
WARNING
Disconnect all electric power, including remote
Three phase electrical power to the unit must meet
stringent requirements for the unit to operate properly.
Measure each leg (phase-to-phase) of the power supply.
Eachreading must fall within the utilization range listed on
the unit nameplate. If any of thereadings do not fall within
the proper tolerances, notify the power company to
correct this situation before operating the unit.
Excessive three phase voltage imbalance between phases
will cause motors to overheat and eventually fail.The
maximum allowable voltage imbalance is 2%. Measure
and record the voltage between phases 1, 2, and 3 and
calculate the amount of imbalance as follows:
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
1. Turn the field supplieddisconnect switch that provides
power to the main power terminal block or to the Line
side of theoptional factory mounteddisconnect switch
to the OFF position.
2. Connect the phase sequence indicator leads to the
terminal block or the Line side of the optional factory
mounted disconnect switch as follows:
Black (phase A) to L1
% Voltage Imbalance =
where;
AV (average voltage) =
100 x AV - VD
AV
Volt 1 + Volt 2 + Volt 3
3
Red (phase B) to L2
Yellow (phase C) to L3
3. Close the field supplied main power disconnect switch
or circuit protector switch that provides the supply
power to the unit.
4. Observe theABC and CBA phase indicatorlights on the
face of the sequencer.The ABC indicator light will glow
46WSHP-SVX12B-EN
Page 47
Pre-Start
if the phase is ABC. If the CBA indicator light glows,
open the disconnect switch or circuit protection switch
and reverse any two power wires.
5. Restore the main electrical power and recheck the
phasing. If the phasing is correct, open the disconnect
switch or circuit protection switch and remove the
phase sequence indicator.
Compressor Crankcase Heaters (Optional)
Each compressor can be equipped with a crankcase
heater.The proper operation of the crankcase heater is
important to maintain an elevated compressor oil
temperature during the OFF cycle to reduce oil foaming
during compressor starts. Oil foaming occurs when
refrigerant condenses in the compressor and mixes with
the oil. In lower ambient conditions, refrigerant migration
to the compressor could increase.
When the compressor starts, the sudden reduction in
crankcase pressure causes the liquid refrigerant to boil
rapidly causing the oil to foam.This condition could
damage compressor bearings due to reduced lubrication
and could cause compressor mechanical failures.
Before starting the unit in the COOLING mode, set the
system switch to theOFF position andturn the mainpower
disconnect to the ON position and allow the crankcase
heater to operate a minimum of 8-hours.
Before closing the main power disconnect switch, ensure
that the SYSTEM selection switch is in the OFF position
and the FAN selection switch is in the AUTO position.
Close the main power disconnect switch and the unit
mounted disconnect switch, if applicable.
Upon power initialization, the RTRM performs selfdiagnostic checks to ensure that all internal controls are
functional. It also checks the configuration parameters
against the components connected to the system.The
Liteport LED, located on the RTRM module, is turned ON
within one second of power-up if internal operation is
okay.
Use one of the followingTEST procedures to bypass some
time delays and to start the unit at the control panel. Each
step of unit operation can be activated individually by
temporarily shorting across theTEST terminals for two or
three seconds.The Liteport LED will blink when the test
mode has been initiated.The unit can be left in anyTEST
step for up to one hour before it will automatically
terminate, or it can be terminated by opening the main
power disconnect switch. Once the test mode has been
terminated, the Liteport LED will glow continuously and
the unit will revert to the SYSTEM control.
shorting across the two test terminals for two or three
seconds.
For the initial start-up of the unit, this method initiates the
different components of the unit, one at a time, by
temporarily shorting across the two test terminals for two
or three seconds.
Resistance Test Mode: This method may be used for
start-up providing a decade box for variable resistance
outputs.This method initiatesthe different components of
the unit, one at a time, when a specific resistance value is
placed across the two test terminals.The unit will remain
in the specific test mode for approximately one hour even
though the resistance is left on the test terminals.
Auto Test Mode: This method is not recommended for
start-up due to the short timing between individual
component steps.This method initiates the different
components of the unit, one at a time, when a jumper is
installed across the test terminals.The unit will start the
first test step and change to the next step every 30
seconds. At the end of the test mode, control of the unit
will automatically revert to the applied SYSTEM control
method.
For unit test steps, test modes and step resistance values
to cycle the various components, see Table 9.
Test Modes
There are three methods in which theTEST mode may be
cycled at LTB-Test 1 and LTB-Test 2.
StepTest Mode: This method initiates the different
components of the unit, one at a time, by temporarily
WSHP-SVX12B-EN47
Page 48
Pre-Start
Table 9.ServiceTest Guide
Test StepModeFan
1
2
3CoolStage-1ONMin PositionON(Note 1)OFFOFFOFF4.7K
4(Note 3)CoolStage-2ONMin PositionON(Note 1) ON (Note 1)OFFOFF6.8K
5(Note 3)Heat Stage-1ONMinOFFOFFONOFF10K
6(Note 3)HeatStage-2ONMinOFFOFFONON15K
Notes:
1. The condenser fans will operate any time a compressor is ON providing the outdoor temperatures are within the
operating values.
2. The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan
setpoint.
3. Steps for optional accessories and non-applicable modes in unit will be skipped.
FanON
Min VentilationONSelectableOFFOFFOFFOFF
EconomizerTest
Open
ONOPENOFFOFFOFFOFF3.3K
Verifying Proper Air Flow (Units with DD
Indoor Fan)
Much of the systems performance and reliabilityis closely
associated with, and dependent upon having the proper
airflow supplied both to the space that is being
conditioned and across the evaporator coil.
The fan motor is factory wired to operate on low speed in
the cooling and heating mode. It can be rewired for high
speed operation should the application require it. Refer to
the wiring diagram on the unit.
The fan motor is specifically designed to operate within
the Blower Horse Power (BHP) parameters listed inthe fan
performance tables of the unit Service Facts. By
understanding that these motors will safely work within
these conditions, before an oversized motor is required,
will allow the air distribution system to be set up properly
and diagnostics enhanced should a problem occur.
When verifying direct drive fan performance, the tables
must be used somewhat differently than those of belt
driven fans. Fan performance diagnostics can be easily
recognized when these tables are used correctly.
Before starting the SERVICETEST, set the minimum
position setpoint for the economizer to 0% using the
setpoint potentiometer locatedon the Economizer Control
(ECA), if applicable.
Using Table 9, momentarily jump across the Test 1 and
Test 2 terminals on LTB1 one time to start the minimum
ventilation test.
With the fan operating properly, determine the total
system external static pressure (inches w.c.) by:
1. Measuring the supply and return duct static pressure.
2. Using the accessory pressure drop table in the Service
Facts, calculate the total static pressure drop for all of
the accessories installed on the unit; (i.e. curb,
economizer, etc.)
Econ
(Note 2)Compr 1Compr 2Heat 1 Heat 2 Ohms
Min Position
Setpoint 0%
OFFOFFOFFOFF
Note: Static pressure is based on desired CFM and may
not be actual static pressure.
3. Add the total accessory static pressure drop (Step 2) to
the duct external static pressure (Step 1).The sum of
these two values represents the total system external
static pressure.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical
components could result in death or serious injury.
4. Measure theamperage at the supply fan contactor and
compare it with the full load amp (FLA) rating printed
on the motor nameplate.
a. Calculate the theoretical BHP
Actual Motor Amps x Motor HP
Motor Nameplate Amps
b. Using thefan performance tablesin the unitService
Facts, plot the total external static pressure (Step 3)
and the BHP (Step 4a) to obtain the operating CFM.
When plotted, if the two values can notbe interpolated
correspondingly, thestatic pressure will most likely be
the least accurate measurement. Because of the direct
drive motor operation, the RPM performance is
relatively constant making theoperating current a very
reliable diagnostic tool.
Example: GERE060 single phase, low speed
Actual Motor Amp (5.25)
Motor Nameplate Amps (5.3)
= 99%
2.2K
48WSHP-SVX12B-EN
Page 49
0.99 x Motor HP (0.6) = .59 BHP
The actual external static pressure is approximately
0.45" w.c., airflow equals 2100 CFM.
If the static pressure reading was higher, motor current
would have to be lower proportionately to get an
accurate CFM measurement in direct drive
applications.
5. If the required CFM is too low, (external staticpressure
is high causing motor HP output to be below table
value),
a. Relieve supply and/or return duct static.
b. Change indoor fan speed to HIGH and repeat steps
1 through 4.
6. If the required CFM is too high, (external static
pressure is low causing motor HP output to be above
table value), increase supply and/or return duct static.
7. To stop the SERVICETEST, turn the main power
disconnect switch to the OFF position or proceed to the
next component start-up procedure.
Verifying Proper Air Flow (Units with Belt
Drive Fan)
Much of the systems performance and reliabilityis closely
associated with, and dependent upon having the proper
airflow supplied both to the space that is being
conditioned and across the evaporator coil.
The fan speed is changed by opening or closing the
adjustable motor sheave.
Before starting the SERVICETEST, set the minimum
position setpoint for the economizer to 0% using the
setpoint potentiometer locatedon the Economizer Control
(ECA), if applicable.
Using Table 9, p. 48, momentarily jump across the Test 1
andTest 2 terminals on LTB1 one time to start the
minimum ventilation test.
WARNING
Rotating Components!
During installation, testing, servicing and
troubleshooting of this product it may be necessary to
measure the speed of rotating components. Have a
qualified or licensed service individual who has been
properly trained in handling exposed rotating
components perform these tasks. Failure to follow all
safety precautions when exposed to rotating
components could result in death or serious injury.
Pre-Start
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
2. Measure theamperage at the supply fan contactor and
compare it with the full load amp (FLA) rating printed
on the motor nameplate.
a. Calculate the theoretical BHP.
Actual Motor Amps x Motor HP
Motor Nameplate Amps
b. Using thefan performance tablesin the unitService
Facts, plot the total external static pressure (Step 1)
and the BHP (Step 2) to obtain the operating CFM.
3. If the required CFM is too low, (external staticpressure
is high causing motor HP output to be below table
value),
a. Relieve supply and/or return duct static.
b. Change fan speed and repeat steps 1 and 2.
4. To increase fan RPM; Loosen the pulleyadjustment set
screw and turn sheave clockwise.
5. To decrease fanRPM; Loosen the pulleyadjustment set
screw ant turn sheave counterclockwise.
6. If the required CFM is too high, (external static
pressure is low causing motor HP output to be above
table value), change fan speed and repeat steps 1 and
2.
7. To stop the SERVICETEST, turn the main power
disconnect switch to the OFF position or proceed to the
next component start-up procedure.
Fan Belt Adjustment (Units with Belt Drive
Fan)
The fan belts must be inspected periodically to assure
proper unit operation.
Replacement is necessary if the belts appear frayed or
worn. Units with dual belts require a matched set of belts
to ensure equal belt length.
Once the supply fan has started, check for proper rotation.
The direction ofrotation is indicated by an arrow on the fan
housing. With the fan operating properly, determine the
total system airflow (CFM) by;
1. Measuring the actual RPM
WSHP-SVX12B-EN49
Page 50
Pre-Start
WARNING
Rotating Components!
During installation, testing, servicing and
troubleshooting of this product it may be necessary to
measure the speed of rotating components. Have a
qualified or licensed service individual who has been
properly trained in handling exposed rotating
components perform these tasks. Failure to follow all
safety precautions when exposed to rotating
components could result in death or serious injury.
When moving or installing the new belts, do not stretch
them over the sheaves. Loosen the belts using the belt
tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning™ or
Gates™ tension gauge (or equivalent) illustrated in
Figure 31; adjust the belt tension as follows:
1. To determine the appropriate belt deflection;
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measure in Step 1a by 64; the
resulting value represents the amount of belt
deflection that corresponds to the proper belt
tension.
2. Set the large O-ring on the belt tension gauge at the
deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the
gauge plunger.
4. Place thelarge end ofthe gauge at thecenter of thebelt
span; then depress the gauge plunger until the largeOring is even with the top of the next belt or even with
the straightedge placed across the fan and motor
sheaves.
5. Remove the belt tension gauge.The small O-ring now
indicates a number other than zero on the plunger’s
force scale.This number represents the force (in
pounds) required to give the needed deflection.
6. Compare the "force" scale reading (Step 5) with the
appropriate "force" value listed in
"force" reading is outside the range, readjust the belt
tension.
Note: Actual belt deflection "force" must not exceed the
maximum force value shown in Table 10.
7. Recheck the belt tension at least twice during the first
2 to 3-days of operation. Belt tension may decrease
until the new belts are "run-in".
Table 10.Ifthe
Figure 31. Belt tension gauge
Table 10. Belt tension measurement an deflection
ranges
Belts Cross SectionAB
3.0 - 3.63.4 - 4.2
Small P.D. Range
Super Gripbelts
Gripnotch
Steel Cable
Gripbelts
Min34
Max4.55.5
Min3.55.125
Max57.125
Min46.375
Max5.58.75
Min3.8755.75
Max5.58
Min4.56.5
Max6.259.125
Min57.375
Max6.87510.125
Min3.254.5
Max45.5
Min3.755.75
Max4.757.25
Min4.257
Max5.258.75
3.8 - 4.84.4 - 5.6
5.0 - 7.05.8 - 8.8
Return Air Smoke Detector
The return air smoke detector is designed to shut off the
unit if smoke is sensed in the return air stream. Sampling
the airflow entering the unit at the return air opening
performs this function.
In order for the smoke detector to properlysense smoke in
the return airstream, the air velocity enteringthe unit must
be between 500 and 4000 feet per minute. Equipment
covered in this manual will developan airflow velocitythat
falls within these limits over the entire airflow range
specified in the fan performance tables.
50WSHP-SVX12B-EN
Page 51
Pre-Start
There are certain models however, if operated at low
airflow, will not develop anairflow velocity that falls within
the required 500 to 4000 feet per minute range. For these
models, the design airflow shall be greater than or equal
to the minimum CFM specified in W_C-IOM-1B manual.
Failure to follow these instructions will prevent the smoke
detector from performing its design function.
Economizer Start-Up
Using Table 9, p. 48 momentarily jump across the Test 1
andTest 2 terminals on LTB1 one time to start the
minimum ventilation test.
1. Set the minimum position setpoint for the economizer
to the required percentage of minimum ventilation
using the setpoint potentiometer located on the
Economizer Control (ECA).
The economizer will drive to its minimum position
setpoint, exhaust fans (if applicable) may start at
random, and the supply fan will start when the
SERVICETEST is initiated.
WARNING
Unexpected Fan Start Up!
The supply fan will start when ServiceTest is initiated
and the exhaust fan may start at random. The exhaust
fan will start anytime the economizer damper position
is equal to or greater than the exhaust fan setpoint.
Leave all access panels and guards to fan sections in
place when performing minimum ventilation test.
Failure to follow proper procedure could result in death
or serious injury.
The exhaust fan will start anytime the economizer
damper position is equal to or greater than the exhaust
fan setpoint.
2. Verify that the dampers stroked to the minimum
position.
3. Verify ambient sesor has been mouted into inside
corner post grommet.
ReliaTel Control
1. Momentarily jump across theTest 1 and Test 2
terminals on LTB1 one additional time if continuing
from previous component start-up or until the desired
start-up component test is started.
2. Verify that the dampers stroked to the full open
position.
3. To stop the SERVICETEST, turn the main power
disconnect switch to the OFF position or proceed to the
next component start-up procedure.
Compressor Start-Up
Using the service test guide in Table 9, p. 48, continue the
SERVICETEST start-up procedure for each compressor
circuit.
1. Attach a set of service gauges onto the suction and
discharge gauge ports for each circuit. Refer to the
refrigerant circuit illustration in the Service Facts.
2. Momentarily jump across the Test 1 andTest 2
terminals on the LTB one additional time if continuing
from previous component start-up or until the desired
start-up componentTest is started.
3. Scroll Compressors
a. Once each compressor has started, verify that the
rotation is correct. If a scroll compressor is rotating
backwards, it will not pump and a loud rattling
sound can be observed.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
b. If the electrical phasing is correct, before
condemning a compressor, interchange any two
leads (at the compressorTerminal block) to check
the internal phasing. Refer to p. 47 for phase
sequencing. If thecompressor runs backward for an
extended period (15 to 30 minutes), the motor
winding can overheat and cause the motorwinding
thermostat to open.
c. Check the compressor oil levels.The oil lever in
eachcompressor sight glassshould be 1/2 to3/4 full
when they are OFF.
Note: The scroll compressor usesTrane OIL-42 without
substitution.The appropriate oil charge for a 9 and
10-ton scroll compressor is 8-pints. For a 14 and 15ton scroll compressor, use 14 pints.
4. After the compressor and condenser fan have started
and operated for approximately 30-minutes, observe
the operating pressures. Compare the operating
pressures to the operating pressure curve in the
Service Facts.
5. Check system superheat. Follow the instruction list on
the superheat charging curve in the Service Facts.
Note: Superheat should be within ±5° F of the superheat
chart value.
6. Repeat steps 1 through 4 for each refrigerant circuit.
7. To stop the SERVICETEST, turn the main power
disconnect switch to the OFF position or proceed to the
next component start-up procedure.
WSHP-SVX12B-EN51
Page 52
Pre-Start
Heating Start-up
Using Table 9, p. 48 continue the SERVICE TEST start-up
procedure for each compressor circuit.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
1. Clamp an amp meter around one of the first stage
heater power wires at the heater contactor.
2. Momentarily jump across the Test 1 andTest 2
terminals on LTB one additional time if continuing
from previous component start-up or until the desired
start-up component test is started.
3. Verify that the heater stage is operating properly.
4. Clamp an amp meter around one of the two stage
heater power wires at the heater contactor (if
applicable).
5. Momentarily jump across the test 1 and test 2
terminals on LTB one additional time if continuing
from previous component start-up or until the desired
start-up component test is started.
6. Verify that the heater stage is operating properly.
7. To stop the SERVICETEST, turn the main power
disconnect switch to the OFF position or proceed to the
next component start-up procedure.
Pre-Startup Checklist
Before energizing the unit, the following system devices
must be checked:
•Check all electrical connections for tightness and point
of termination accuracy.
•Is the high voltage power supply correct and in
accordance with the nameplate ratings?
•Is phasing of the unit correct per compressor rotation?
•Is the field wiring and circuit protection the correct
size?
•Is the low voltage control circuit wiring correct per the
unit wiring diagram?
•Is the piping system clean/complete and correct? (A
recommendation of all system flushing of debris from
the water-to-refrigerant heat exchanger, along with air
purging from the water-to-refrigerant heat exchanger
be done in accordance with the Closed-Loop/Ground
Source Heat Pump Systems Installation Guide).
•Is unit serviceable? (See section “Unit Clearances,”
p. 10 for clearance recommendations.)
52WSHP-SVX12B-EN
•Are the low/high-side pressure temperature caps
secure and in place?
•Is the thermostat in the OFF position?
•Is the water flow established and circulating through
all the units?
•Is the duct work correctly sized, run, taped, insulated
and weather proofed with proper unit arrangement?
•Is the condensate line properly sized, run, trapped and
pitched?
•Is the zone sensor (when used) correctly wired and in
a proper location?
•Does the indoor blower turn freely without rubbing
and is it properly tightened on the shaft? Check the
supply fan belts (if applicable) for proper tension and
the fan bearings for sufficient lubrication. If the belts
require adjustment, or if the bearings need lubricating,
refer to the maintenance section for instructions.
•Has all work been done in accordance with applicable
local and national codes?
•Has heat transfer fluid been added in the proper mixto
prevent freezing in closed system application?
•Are all the unitaccess panels secure and in place? And,
is unit interior free from tools or debris?
•Verifythat the Remote panelSYSTEMselection switch,
FAN selection switch, and ZONETEMPERATURE
settings for automatic operation are correct.
•Is the main disconnect switch or circuit protector
switch that provides the supply power to the unit’s
terminal block or the unit mounted disconnect switch
closed?
•Is the Night Setback panel (if applicable) programmed
for proper unoccupied operation?
•For units with economizer option verify ambient
sensor is mounted inside corner post grommet.
Page 53
Start Up
Use this form to thoroughly check-out the system and
units before and during start-up. (This form need not be
returned to the factory unless requested during technical
service support).
Job Name:
Model Number:
Date:
Serial Number:
In order to minimize troubleshooting and costly system
failures, complete the following checks and data entries
before the system is put into full operation.
MODEHeatCool
Entering fluid temperature degrees F
Leaving fluid temperature degrees F
Temperature differential degrees F
Return air temperature DB/WB degrees F
Supply air temperature DB/WB degrees F
Temperature differential degrees F
Water coil heat exchanger (Water
Pressure IN) PSIG
Water coil heat exchanger (Water
Pressure OUT) PSIG
Pressure Differential PSIG
COMPRESSOR
Amps
Volts
Discharge line temperature (after 10
minutes) degrees F
Initial Unit Start-up
Start-up with the conventional thermostat is included
below:
1. Set the thermostat to the highest position.
2. Set thethermostat systemswitch to COOL with the fan
control to AUTO. The compressor should NOT run.
3. Reduce the thermostat setting until the compressor,
reversing valve, solenoid valve, and loop pump are
energized. Adjust water flow utilizing pressure/
temperature plugs and comparing to tables contained
in specification sheet data. Water leaving the heat
exchanger should be warmer than the entering water
temperature (approximately 9°F-12°F); blower
operation should be smooth; compressor and blower
amps should be within data plate ratings; the suction
line should be cool with no frost observed in the
refrigerant circuit.
4. Check the cooling refrigerant pressures.
5. Turn the thermostatsystem switch to theOFF position.
Unit should stop running and the reversing valve
should de-energize.
6. Leave unit off for approximately FIVE minutes to allow
for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set thethermostat systemswitch to the HEAT position.
9. Adjust the temperature setting upward until the unit is
energized. Warm air should blow from the register. A
water temperature decrease of approximately 5° Fto 9°
F leaving the heat exchanger should be noted.The
blower and compressor operation should be smooth
with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures.
11. Set the thermostat to maintain the desired space
temperature.
12. Instruct the owner on system operation.
WSHP-SVX12B-EN53
Page 54
Start Up
Water Pressure Drop
Table 11 and Table 12 should be used to define feet of
head/pressure drop. Please note the feet of pressure (ft/
head) provided is at ARI/ISO standard.
Note: To calculate feet of head, when using gauges that
read in PSIG, multiply PSI by 2.31.
Table 11.Cooling water pressure drops (WPD) in feet of
head
Unit SizeEWTFGPMFt.Pressure
036869.011.0
0488612.09.0
0608615.013.3
0728618.011.4
0908622.512.1
1208630.015.2
1508637.513.7
180864519.3
240866013.2
300867513.1
Table 12. Heating water pressure drops (WPD) in feet of
head
Unit SizeEWTFGPMFt. Pressure
036689.012.0
0486812.09.7
0606815.014.3
0726818.012.3
0906822.513.1
1206830.016.4
1506837.514.8
180684520.8
240686014.3
Table 13. Water volume
Water Side
Unit Size
03676.044.329
048171.099.74
060171.099.74
072259.151.121
090210.122.910
120342.1981.48
150508.2962.201
1805082.962.201
240779.4533.374
3001057.6154.576
Volume Cubic
In.
54WSHP-SVX12B-EN
Water Side
Volume Cubic
Ft.
Water Side
Volume Gallons
Page 55
Maintenance
Preventive Maintenance
Maintenance on the unit is simplified with the following
preventive suggestions:
Filter maintenance must be performed to assure proper
operation of the equipment. Filters should be inspected at
least every three months, and replaced when it is evident
they are dirty. Filter sizing includes:
Table 14. Filter sizing
Unit Size
036-0482/ 20 x 30 x 1
0604/16 x 25 x 2
072-0904/ 16 x 25 x 2
1204/ 20 x 25 x 2
150, 180, 300
Downflow
150, 180, 300
Horizontal
240 Downflow
240 Horizontal12/20 x 20 x 2
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Filter Size
nominal inch
4/20 x 20 x 2
4/20 x 25 x 2
8/20 x 25 x 2
8/20 x 20 x 2
4/20 x 16 x 2
WARNING
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly
alkaline. Handle chemical carefully. Proper handling
should include goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For
personal safety, refer to the cleaning agent
manufacturers Materials Safety Data Sheet and follow
all recommended safe handling practices. Failure to
follow all safety instructions could result in death or
serious injury.
It should be noted that the water quality shouldbe checked
periodically. (See Table 15).
Table 15. Water quality
Scaling
Calcium and magnesium (total hardness) Less than 350 ppm
Note: Forother maintenance information concerning the
GERA unit, please read W_C-IOM-1*.
7-9.5
Less than 1 ppm
Less than 25 ppm
Less than 125 ppm
Less than 75 ppm
Less than 1000 ppm
Check the contactors and relays within the control panel at
least once a year. It is good practice to check the tightness
of the various wiring connections within the control panel.
A strainer (60 mesh or greater) must be used on an open
loop system to keep debris from entering the unit heat
exchanger and to ensure a clean system.
For units on well water, it is important to check the
cleanliness of the water-to-refrigerant heat exchanger.
Should it become contaminated with dirt and scaling as a
result of bad water, the heat exchanger will have to be back
flushed and cleaned with a chemical that will remove the
scale.This service should be performedby an experienced
water treatment specialist.
WSHP-SVX12B-EN55
Page 56
Troubleshooting
WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures.When possible, disconnect all electrical
power including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.When
necessary to work with live electrical components, have
a qualified licensed electrician or other individual who
has been trained in handling live electrical components
per these tasks. Failure to follow all of the
recommended safety warnings provided, could result in
death or serious injury.
Table 16. Troubleshooting
ProblemHeatingCoolingCauseCorrection
XXMain power offCheck fuses
No response to any
thermostat setting
Unit short cyclesXXThermostat or sensor improperly located Relocate
XXHeat transfer fluid too coldRaise water temperature
Troubleshooting
WSHP-SVX12B-EN57
Page 58
Warranty
Standard Warranty
The standard water-source heat pump warranty isTrane
parts-only warranty, running 12 months from startup, not
to exceed 18-months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth
year warranty.The time starts at the end of the standard 1year coverage through the fifth year.
These extended warranties apply only to new equipment
installed in domesticTrane Commercial Systems Group
sales territories and must be ordered prior to start-up.
58WSHP-SVX12B-EN
Page 59
Page 60
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments,Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.